APU WIRING (Serial# KZX98002290 to Date) ......................................... A-13
c-ii
62-11175 COMFORTPRO SERVICE MANUAL
Page 4
SAFETY
Safety Alerts
Throughout this manual, you will see notes labeled "Warnings" or "Cautions"
to alert you to special instructions or precautions concerning a particular
procedure that would be hazardous if performed incorrectly or carelessly.
Observe them carefully!
These safety alerts alone cannot eliminate hazards that can occur. Strict
compliance with these special instructions when performing the installation and
maintenance, plus common sense, are major accident prevention measures.
DANGER
Immediate hazards that will result
in severe personal injury or death.
CAUTION
Hazards or unsafe practices that
could result in minor injury or
product or property damage.
For example:
DANGER
A certified refrigeration technician
must charge and test the CCU.
WARNING
Hazards or unsafe practices that
could result in severe personal
injury or death.
NOTICE
Information that is important to
proper installation or maintenance,
but is not hazard-related.
62-11175 COMFORTPRO SERVICE MANUAL
c-iii
Page 5
Safety Considerations
Exhaust
Fuel/Batteries
Electrical
Inhalation of exhaust gas (containing carbon monoxide) may cause severe
personal injury and/or death. Anyone suspected of suffering from CO
inhalation should be removed from the hazardous area and given medical
assistance immediately.
WARNING
California Proposition 65 Warning: This product contains lead, a
chemical known to the State of California to cause cancer and birth
defects and other reproductive harm.
Exercise extreme caution when working near fuel or fuel-filled equipment.
Do not operate equipment during fueling operations. Use eye protection
when working near batteries, which contain acid and can explode. Do not
smoke or use open flames near batteries.
Electric shock can cause severe personal injury, burns, and death. Before
working on any unit, disconnect the batteries. Use only approved materials
and methods when working on the electrical system, and follow local
electrical codes. Never work on the APU or the electrical circuitry when the
APU is running. Never work with electricity in wet conditions or when you
are tired.
Intoxicants
Hot or Moving Parts
Misuse
Fuel, oil, coolant, and refrigerant are toxic and in some cases, carcinogenic.
Wear eye and hand protection at all times. Remove contaminated clothing
immediately and wash contaminated skin. Do not breathe in vapors.
Moving parts can cause severe injury and/or death. Before working on any
unit, shut it off and disconnect the battery. Do not start until protective
covers have been replaced. Also, loose parts falling into rotating machinery
can cause severe accidents. Always ensure bolts and clamps are correctly
torqued and secured. Inspect mechanical components periodically for
damage, corrosion, and proper torque.
The APU is designed to provide electrical power for heating and cooling
vehicles in normal on-road conditions. Never use the APU to power critical
medical equipment or sensitive electronic equipment without the
manufacturer's express written approval.
c-iv
62-11175 COMFORTPRO SERVICE MANUAL
Page 6
COMPONENT LAYOUT
COOLANT SUPPLY
AND RETURN
PANEL (DCP)
DRIVER CONTROL
CONDENSER
120 VAC
RECEPTACLE PANEL
UNIT (CCU)
CLIMATE CONTROL
BATTERY
VEHICLE FUEL TANK
AND RETURN
FUEL SUPPLY
AUXILIARY POWER UNIT (APU)
62-11175 COMFORTPRO SERVICE MANUAL
Figure C1: Main Components of the Carrier ComfortPro system and Where They Should Best be Installed on the Truck
c-v
Page 7
GENERAL ARRANGEMENT
APU Dimensions (Measurements in inches)
3.0
2.753.875
18.5
16.0
10.5
REAR
2.6
24.9
28.5
LEFT SIDE
c-vi
FRONT VIEW
RIGHT SIDE
TOP VIEW
62-11175 COMFORTPRO SERVICE MANUAL
Page 8
CCU Dimensions (Measurements in inches)
FRONT VIEW
12"
7.9"
23.4"
24.4"
BOTTOM VIEW
16.2"
15.2"
3.3"
3.1"
3.0"
6.9"
3.0"
6.9"
Condenser Dimensions (Measurements in inches)
3.0"
3.4"
3.0"
12.6"
.125"
1.3"
12.9"
5.62"
13.93"
16.25"
16.90"
5.62"
62-11175 COMFORTPRO SERVICE MANUAL
26.5"
24.25"
8"
3.5"
2.0"
DOWN
FRONTRIGHT SIDE
c-vii
Page 9
c-viii
62-11175 COMFORTPRO SERVICE MANUAL
Page 10
1.0
OPERATION OF MULTI-FUNCTION
DRIVER CONTROL PANEL
45
3
APU
ON/OFF
2
MENU
HOURS
00000
6789
APU
A/ CFANHEAT
1
Figure 1-0: Multi-Function Driver Control Panel
PREPARATION 1.1
1011
SP
T2T
1
HVAC
OFF
ESC/
RESET
NOTICE
The DCP (driver control panel), which
is mounted inside the truck bunk,
controls the APU and the CCU. The
central panel on the DCP provides
status information using words
and icons:
1.1.1 Multi-Function Driver Control Panel Components
1When visible, the heating system is heating.
2When visible, the A/C is cooling.
3 Indicates the number of operating hours on the APU.
4 Indicates the state of the APU.
APU
The APU engine is running.
APU
The APU engine is off.
APU
The APU engine is in the starting process (flashing).
5Indicates that Battery Monitor mode is enabled.
6Indicates that maximum run time is enabled.
7Indicates that Cold Weather Watch mode is enabled.
8Indicates that Comfort Monitor mode is enabled.
T2T
1
9Indicates that Timer 1 or Timer 2 mode is enabled.
10 Indicates that the ComfortPro is connected to shore power.
The APU cannot be started in Shore Power mode.
11 Indicates the state of the 115V outlet and CCU auto-reset breakers.
115 VAC power is being supplied to the outlet.
OFF
No power is being supplied to the outlet.
TRIP
CCU breaker has tripped.
High Heat/Outlet breaker has tripped.
TRIP
RE-
The breaker that tripped has reset automatically and the DCP needs
SET
to be reset.
62-11175 COMFORTPRO SERVICE MANUAL
1-1
Page 11
1.1.2 How the ComfortPro Operates
The ComfortPro has two modes of operation: manual and automatic.
Manual Mode
You start the APU from within the truck bunk using the On/Off button on
the driver control panel (DCP). Once the APU is running, you can start and
stop the fan, heater and air conditioning using the DCP. See page 1-3.
Once the heater or A/C is running, it will cycle (automatically turn on and
off) in order to keep the truck bunk at the temperature you specify. The
HVAC will continue to cycle until you turn it off. While the HVAC is cycling,
the APU remains on and will only turn off when you manually turn it off
using the button on the DCP.
Note that in manual mode, the APU remains on until you turn it off. But in
Comfort Monitor mode (described below), the APU automatically turns off
and on as required.
When the APU is running, power is supplied to the power outlet in the
truck bunk (except in high heat).
In manual mode, the APU will turn off automatically if the Maximum Run
Time is reached.
Automatic Mode
The ComfortPro has several functions that will start it in automatic mode.
FEATUREDESCRIPTION
1-2
Comfort Monitor
(page 1-7)
Timer
(page 1-8)
Cold Weather Watch
(page 1-10)
Battery Monitor
(page 1-12)
There are icons on the DCP that flash when the APU and HVAC are running.
See page 1-1. If you enter the truck bunk and APU or HVAC is on but you
did not start it, you can assume it has started in one of the automatic
modes, as described above. On the DCP, one icon will be flashing steadily:
this is the icon for the mode that is currently operating.
Whenever the ComfortPro is running in automatic mode, if you then press
the heat, A/C or fan buttons on the DCP, the ComfortPro will switch to
manual mode. The APU will not automatically turn off! This icon on the
DCP will also stop flashing.
The APU and HVAC automatically turn on to
maintain a comfortable temperature in the truck
bunk. When the desired temperature is met, the
APU and HVAC automatically turn off. When the
temperature is again out of range, they will both
turn on again, and cycle heat and air conditioning
as needed.
At the specified time, the APU and HVAC
automatically turn on. During the specified
timer duration, the HVAC cycles on and off to
maintain the desired temperature. When the
timer duration expires, both the APU and HVAC
turn off automatically and remain off.
The APU and heater on the HVAC automatically
turn on in order to prevent the APU engine and
truck engine from getting too cold. (Turning on
the heater creates a “load” that makes the APU
work harder and therefore warm up faster).
Both the APU and HVAC turn off automatically
once the preset duration time expires.
The APU automatically turns on for 90 minutes
in order to recharge the batteries. The HVAC
does not turn on. After the 90 minute run time,
the system will sense voltage for 10 minutes,
before restarting if needed.
62-11175 COMFORTPRO SERVICE MANUAL
Page 12
Automatic Mode and Minimum Time Off
APU
APU
APU
All these automatic functions work on a "minimum time off": the ComfortPro
must be off for at least 10 minutes before the automatic function will turn
it on again. For example, the Timer function may be set to turn on the
ComfortPro at 10:00 a.m. You have been running the ComfortPro in manual
mode. You turn off the ComfortPro at 9:55 a.m. The timer will only turn on
the ComfortPro again 10 minutes later, at 10:05 a.m.
Clock
In order to use the Timer correctly, you must set the DCP clock. See page 1-7.
Maximum Run Time
You can set the maximum time that the APU is allowed to continuously run
in manual mode. See page 1-11.
Password Protection
You can add a password to the DCP, then you can protect one or more
functions so that only a person who knows the password can set the
function. See page 1-5.
1.2MANUAL OPERATIONS
WARNING
Do not start the APU when the enclosure
cover is removed. Operating with the
cover off may result in injury and/or death.
WARNING
When the APU is about to start, a buzzer
sounds. Make sure no one is standing
near the APU or touching it.
1.2.1 Starting the APU "One Touch Start"
Press and releaseonce.
The display shows "PLEASE WAIT – APUSTARTING" and flashes.
Whenstops flashing, then the APU
has started successfully.
The APU startup sequence consists of
20 seconds of glowing (30 seconds when
the ambient temperature is below -5°C or
23°F) and up to 10 seconds of cranking.
If the sequence fails, "RESTARTING"
appears for six seconds. Then the
startup sequence automatically repeats
up to five times or until the APU starts.
If "CRANK LIMIT" appears, see
Troubleshooting section.
HOURS
00000
APU
PLEASE WAIT
APU STARTING
HOURS
00000
APU
RESTARTING
HOURS
00000
APU
CRANK LIMIT
1.2.2 Stopping the APU
Press
.
The APU will stop. The display
shows .
HOURS
00000
APU
OFF
OFF
OFF
OFF
OFF
OFF
OFF
62-11175 COMFORTPRO SERVICE MANUAL
1-3
Page 13
1.2.3 Turning the Heater ON/OFF
NOTICE
The heat mode will not function if the
temperature is higher than 85°F.
1 Press to activate the heater.
The display shows "HEAT LOW".
The heater will turn on only if the
temperature is too low (to adjust the
temperature, see below). When the
heater is on, appears.
2 Press again to switch between
high and low heat to heat the truck
bunk more or less quickly. In "HEATHIGH" mode, the power outlet is
disabled and the display indicates.
The heat or A/C will turn off when the
desired temperature is reached.
3 Press to deactivate heating.
HOURS
00000
APU
HEAT LOW
CH
HOURS
00000
APU
HEAT HIGH
OFF
CH
1.2.4 Heating: Setting the Temperature
Pressorwhen the heater is on ("HEAT LOW"or "HEAT
HIGH" shows).
The notch on the temperature bar moves. The heater will automatically
turn on and off to maintain this temperature.
OFF
NOTICE
The air conditioning function will not
operate if the temperature is lower
than 65°F.
1.2.5 Turning the A/C ON or OFF
1 Press to activate the A/C.
The display shows "A/C LOW".
The A/C will turn on only if the
temperature is too high (to adjust the
temperature, see below). When the
A/C is on, appears.
2 Press again to switch between
high and low A/C to cool the truck
bunk more or less quickly.
3 Press to deactivate the A/C.
HOURS
00000
APU
A/C LOW
CH
HOURS
00000
APU
A/C HIGH
CH
1.2.6 A/C Setting the Temperature
Pressorwhen the A/C is on ("A/C LOW" or "A/C HIGH" shows).
The notch on the temperature bar moves. The A/C will automatically turn
on and off to maintain this temperature.
1-4
62-11175 COMFORTPRO SERVICE MANUAL
Page 14
1.2.7 Fan Operation
You can still have the fan working even when the temperature is not low or
high enough for the heat or A/C to come on.
The fan operation is independent of the air conditioning and heat modes.
When the fan speed is manually set to high or low, the fan will return to
that setting when the desired temperature has been reached as the air
conditioning or heat cycles off.
Pressto toggle between low,
high and off.
HOURS
00000
APU
The speed of the fan may automatically
change when the heat or A/C comes on,
then automatically change back when
CH
the heat or A/C goes off.
HOURS
00000
APU
CH
1.3AUTOMATIC OPERATIONS
1.3.1 Password Protection
You can add a password to the DCP, then you can protect one or more
functions so that only a person who knows the password can set the function.
On a newly installed DCP, the password is always 000, which means that
no password protection is in place.
To password-protect functions, first change the factory password; see
'Setting up for Password Protection'. All functions will now be password
protected. Then remove password protection from chosen functions, as
desired; see 'Protect Functions with a Password'.
If you know the password, you can change it at any time, if you need to.
Note that if you change the password to 000, you will remove password
protection from all functions.
If the password is ever lost, contact your dealer to have the password
reset to 000.
FAN
LOW
FAN
HIGH
62-11175 COMFORTPRO SERVICE MANUAL
Setting up for PASSWORD PROTECTION
1 Press.
2 Pressoruntil "SET/CHANGE PASSWORD" is displayed,
then press.
"ENTER PASSWORD" is displayed
with three blank squares, one for
each digit in the password. The
HOURS
00000
ENTER PASSWORD
APU
000
OFF
OFF
first digit flashes.
1-5
Page 15
3
Pressoruntil the first number in the password is displayed
For example, if your password is "432" pressuntil "4" shows,
then press.
4 Repeat for each digit in the password.
5 Pressagain after entering the last digit. "NEW PASSWORD"
is displayed.
6 Repeat the above steps to enter the new password. "CONFIRM"
is displayed.
7 Enter the new password again, then pressto exit this function.
PROTECT FUNCTIONS with a PASSWORD
1 Press.
.
2 Press or until
"PASSWORD PROTECT"
is displayed, then press.
If this menu item does not appear,
HOURS
00000
APU
PASSWORD
PROTECT
then you have not yet changed the
factory password from 000. Change
the password and then try again.
"ENTER PASSWORD" is displayed with three blank squares, one for
each digit in the password. The first square flashes.
3 Press or until the first number in the password is
displayed, then press.
4 Repeat for each digit in the password.
5 Pressagain after entering the last digit.
The first feature that can be password protected is displayed with
"YES" or "NO" (indicating whether it is currently password protected).
6 Press or to change the "YES" or "NO".
7 Pressto move to the next feature.
Or pressor to skip to the next feature.
OFF
OFF
1-6
1.3.2 Entering the Password
When you try to set up a function, you may be prompted to enter the password.
1 Pressoruntil the first number in the password
is displayed, then press.
2 Repeat for each digit in the password.
3 Pressagain after entering the last digit.
62-11175 COMFORTPRO SERVICE MANUAL
Page 16
NOTICE
The clock does not automatically
adjust for time zone changes; you
must adjust it.
1.3.3 Setting the Clock
You can set the clock on the DCP. This clock is used by the Timer function
(page 1-8). If you use the Timer function, remember that as you move from
one time zone to another, you must adjust the clock. Otherwise the Timer
will start the APU at the wrong time.
The clock settings remain even when the APU is turned off.
1 Press
2 Press or until "CLOCK"
is displayed, then press .
If "ENTER PASSWORD" is displayed,
enter your password. If you do not
know the password, then you cannot
set up this function (see page 1-5).
The clock function takes you through
several settings: 12/24-hour-clock,
hour set, minutes set, am/pm-set (for
12-hour clock only), and day of the week.
3 Pressorto change the setting.
4 Pressto move to the next setting. Or press to cancel any
changes you have not yet accepted.
5 When done, pressto exit.
.
HOURS
00000
APU
CLOCK
HOURS
00000
APU
CLOCK: SET MODE
12 HOUR
OFF
OFF
1.3.4 Comfort Monitor
You can specify the temperature you want in the truck bunk. Whenever the
truck bunk temperature goes 2° above or below this temperature, the APU
starts and the HVAC turns on until that temperature is reached or for
fifteen minutes, whichever is longer.
Turning COMFORT Monitor ON and OFF
1 Press.
2 Pressoruntil
"COMFORT MONITOR" is displayed,
then press.
If "ENTER PASSWORD" is displayed,
enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Pressorto display "ON" or "OFF".
4 Pressto confirm this setting.
The current setting remains until you change it; turning off the APU or
manually starting the APU does not permanently cancel this setting.
HOURS
00000
COMFORT MONITOR:
APU
ON
62-11175 COMFORTPRO SERVICE MANUAL
1-7
Page 17
NOTICE
Factory Default Temperature Setting is
21°C / 70°F. Range is 18°C / 64°F to
30°C / 86°F.
Setting the TEMPERATURE
1 Press .
2 Press or until
"COMFORT MONITOR" is displayed,
then press.
HOURS
00000
APU
COMFORT MONITOR
SET
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET".
4
Press to confirm this setting. The current temperature is displayed.
5 Press or to scroll to the desired temperature.
6 Press to confirm this setting. Or press to cancel and
retain the current temperature.
7 Press to exit.
1.3.5 Timer
You can set up the ComfortPro so that the
a specified
time on specified days of the week. There are two timers, so you
APU and CCU run automatically for
can set up two schedules.
For example, one schedule may be to run every day at 6:00 p.m. for .5 hours
and the other schedule may be to run every Monday at 6.00 a.m. for .5 hours.
You must set up the timer as follows: Specify the day and time you want
the APU to run, specify the duration (the length of time you want the APU to
run for) and specify the temperature you want maintained in the truck bunk
while the APU is running.
Turning TIMER On or Off
1 Press.
2 Pressor until
"TIMER 1" or "TIMER 2" is displayed,
HOURS
00000
TIMER 1
APU
ON
OFF
OFF
T
1
then press.
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Pressor to display "ON" or "OFF".
4 Pressto confirm this setting.
The current setting remains until you change it; turning off the APU or
manually starting the APU does not cancel the timer function.
1-8
62-11175 COMFORTPRO SERVICE MANUAL
Page 18
NOTICE
Factory Default Duration Setting
Range is 0.5 hrs - 10 hrs (in 0.5 hr
increments).
is 1 hour.
Setting the Start Time/Day
1 Press .
2 Press or until
"TIMER 1" or "TIMER 2" is displayed,
HOURS
00000
TIMER 1
APU
SET START
OFF
OFF
T
1
then press.
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET START".
4 Press to confirm this setting. The current start time is displayed.
5 Press or to set the hours, minutes and day.
6 Pressto confirm each setting.
Setting the DURATION
1 Press.
2 Pressor until
"TIMER 1" or "TIMER 2" is displayed,
HOURS
00000
APU
TIMER 1
SET DURATION
OFF
OFF
T
1
then press.
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press orto display "SET DURATION".
4
Pressto confirm this setting. The current duration time is displayed.
5 Pressorto scroll to the length of time to run the APU.
NOTICE
Factory Default Temperature
21°C / 70°F. Range is
30°C / 86°F.
18°C / 64°F to
Setting is
6 Pressto confirm this setting. Or pressto cancel and
retain the current duration.
7 Pressto exit.
Setting the TEMPERATURE for the Timer
1 Press .
2 Press or until
"TIMER 1 or TIMER 2" is displayed,
then press.
HOURS
00000
TIMER 1
APU
SET TEMP
T
1
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET TEMP".
4
Press to confirm this setting. The current temperature is displayed.
5 Pressorto scroll to the desired temperature.
6 Pressto confirm this setting. Or pressto cancel and
retain the current temperature.
7 Pressto exit.
OFF
OFF
62-11175 COMFORTPRO SERVICE MANUAL
1-9
Page 19
1.3.6 Cold Weather Watch
You can set up the APU so that it automatically runs for a specified time
whenever the ambient temperature goes below a specified value. This
feature ensures that the APU engine and truck engine do not get so cold
that they will not start.
This feature is not intended to maintain a comfortable truck bunk
temperature; instead, see “Comfort Monitor”.
Turning Cold weather watch On and Off
1 Press .
2 Press or until
"TEMP START" is displayed, then
press.
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or
manually starting the APU does not permanently cancel this setting.
HOURS
00000
APU
TEMP START
ON
OFF
OFF
NOTICE
Factory Default Temperature
-10°C / 14°F. Range is -
5°C / 41°F.
20°C / -4°F to
Setting
Setting the START TEMPERATURE
1 Press .
2 Press or until
"TEMP START" is displayed, then
HOURS
00000
TEMP START : SET TEMP
APU
-10C 14F
press.
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET TEMP".
4 Press to confirm this setting. The current start temperature
is displayed.
5 Press or to scroll to the desired start temperature.
6 Pressto confirm this setting. Or pressto cancel and
retain the current start temperature.
7 Press to exit.
OFF
OFF
1-10
62-11175 COMFORTPRO SERVICE MANUAL
Page 20
NOTICE
Factory Default Duration Setting
hours. Range is 1 hr to 4 hrs.
is 2
NOTICE
Factory Default Run Time Setting is 8
hours. Range is 2 to 24 hours.
Setting the DURATION
1 Press .
2 Press or until
"TEMP START" is displayed, then
press.
HOURS
00000
TEMP START
APU
SET DURATION
OFF
OFF
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET DURATION".
4 Press to confirm this setting. The current duration is displayed
in hours.
5 Press or to scroll to the
amount of time you want the APU to
run before automatically shutting off.
HOURS
00000
TEMP START : DURATION
APU
OFF
OFF
1.0 hrs
6 Press to confirm this setting.
Or press to cancel and retain the current start temperature.
7 Pressto exit.
1.3.7 Maximum Run Time
You can set the maximum time that the APU is allowed to run continuously.
If the APU runs for longer than the specified time, it automatically shuts off.
You can then start it manually, if desired; the "run time" clock will start
counting again.
Turning MAXIMUM RUN TIME ON OR OFF
1 Press .
2 Press or until
"MAXIMUM RUN TIME" is displayed,
then press.
HOURS
00000
MAXIMUM RUN TIME
APU
ON
62-11175 COMFORTPRO SERVICE MANUAL
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
Setting the DESIRED RUN TIME
1 Press .
2 Press or until
"MAXIMUM RUN TIME" is displayed,
HOURS
00000
MAXIMUM RUN TIME
APU
SET
then press.
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET".
4 Press to confirm this setting.The current duration is displayed.
5 Press or to scroll to the desired number of hours.
6 Pressto confirm this setting. Or pressto cancel and
retain the current duration.
7 Press to exit.
1-11
Page 21
1.3.8 Battery Monitoring
You can set up the APU so that it automatically runs for 90 minutes when
the truck batteries are low.
When you set up this feature, you must enter the current voltage of the
batteries (see “Set the Initial Voltage”). The ComfortPro can then calculate
how much the voltage drops, as the batteries are used.
Set the INITIAL VOLTAGE
1. Press .
2 Press or until
"CALIBRATE VOLTAGE" is displayed,
then press.
HOURS
00000
APU
CALIBRATE
VOLTAGE
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to set the current voltage of the batteries.
4 Press to confirm this setting.
Turning BATTERY MONITORING ON and OFF
1 Press .
2 Press or until
"BATTERY MONITOR" is displayed,
then press.
HOURS
00000
BATTERY MONITOR
APU
ON
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "ON" or "OFF".
4 Press to confirm this setting.
The current setting remains until you change it; turning off the APU or
manually starting the APU does not permanently cancel this setting.
OFF
OFF
OFF
OFF
NOTICE
Factory Default Voltage Setting is
Range is 11.0V to 13.5V.
1-12
11.8V.
The APU starts if the battery voltage goes below the level you specify here.
Setting the Voltage Level
1 Press .
2 Press or until
"BATTERY MONITOR" is displayed,
HOURS
00000
APU
BATTERY MONITOR : SET
11.8 V
OFF
OFF
then press.
If "ENTER PASSWORD" is displayed, enter your password. If you do not
know the password, then you cannot set up this function (see page 1-5).
3 Press or to display "SET".
4 Press to confirm this setting. The current voltage level is
MENU
displayed and flashes.
5 Press or to scroll to the desired voltage.
6 Press to confirm this setting. Or pressto cancel and
retain the current voltage.
7 Pressto exit.
62-11175 COMFORTPRO SERVICE MANUAL
Page 22
2.0
CLIMATE CONTROL UNIT (CCU)
2.1
WARNING
This procedure must be performed by
a certified air conditioning technician
who has experience with hermetic
systems and Refrigerant R-134A.
CAUTION
Vapor charge CCU only.
NOTICE
Refrigerant Recovery:
Venting of refrigerant is against
the law and subject to fines and
loss of certification.
EPA regulations require that all
CFC and HCFC refrigerants be
recovered before any system can
be opened for service.
Recovery of refrigerant is done
using a certified recovery unit.
• Before a refrigeration system
can be opened to make repairs.
• Before pressurizing the system
with nitrogen for leak testing.
•
Before disposing of any system or
component containing refrigerants.
• When it is necessary to remove
excess charge from an
overcharged system.
PREPARATION
2.1.1 Charging the CCU
1Pressure test the system for leaks with nitrogen.
2Vacuum all the nitrogen for a minimum of 30 minutes to 500 microns.
3With the high and the low side valves open, charge the system with
R-134A
high and the low side pressures match, close the high side valve.
4With only the low side valve open, start the A/C compressor by
selecting High A/C (APU Running). If needed lower the temperature
set point to start the A/C compressor.
5Continue charging the system with vapor, on the low side only, until a
total of 64–68 oz of R-134A refrigerant has
been added as measured by the scale.
The air conditioning system has a 5
minute delay timer (minimum time
between cycles is 5 minutes).
RED
vapor to break the vacuum. Once the scale stabilizes and the
CONDENSER
NOTICE
LOW
HIGH
BLUE
NOTICE
Total System Capacity is 64–68 oz.
A scale must be used to measure the
refrigerant weight. No other method
is acceptable. Failure to follow this
procedure exactly will result in
improper air conditioning function.
62-11175 COMFORTPRO SERVICE MANUAL
CCU
SCALE 64–68 OZ
Figure 2- 1: Connecting hoses to CCU to Condenser
2-1
Page 23
2.2SERVICE
2.2.1 Maintenance Schedule
First Every
Interval between checks (in hours of operation)5010002000
Change oil and oil filterxx
Check fuel hoses, fuel pipes, and clampsxx
Check fasteners, muffler clamps and frame grippersxx
Check battery cable connectionsxx
Check coolant hoses and clampsxx
Check alternator fan belt tensionxx
Check generator belt tensionxx
Check APU air filter, clean or replace as necessaryx
Change fuel filtersx
Change fan belt regardless of conditionx
Adjust valve lashx
Clean inside enclosurex
Clean radiator finsx
Clean condenser finsx
Check CCU air filter, clean or replace as necessary. To clean, remove the
filter and vacuum or wash (soap and water). Shake dry and reattach.x
Check injection nozzle opening pressurex
Check injection pump timingx
Check water pump performancex
Check alternator performancex
Check starter performancex
Check air conditioning performance (HVAC)x
Check heater performance (HVAC)x
Check generator line voltagex
Check coolant hoses and clamps (from APU to main engine)x
Check engine thermostatx
Check air intake hose and clamps on APUx
Check fuel hoses and clampsx
2-2
62-11175 COMFORTPRO SERVICE MANUAL
Page 24
2.2.2 CCU Spring Tune-Up
COMFORTPRO CCU EVAPORATOR DEFROST SENSOR TEMPERATURE – RESISTANCE CHART
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
6065707580859095100105110115120
TEMPERATURE (°F)
kOhm
77°F, 100 kOhm
Purpose:Recommended service and maintenance:
• Condenser.
• Air ducting and outlets.
• Evaporator and temperature sensor.
• Refrigerant lines connections and routing.
• Harness Connections and wiring.
• A/C operating efficiency - charge level.
Frequency:
Annually – preferably in the spring for the coming A/C season.
Recommended1. Check the condenser for:
Service Actions:Damage, leakage and/or contaminated fins that may restrict air flow.
2. Check air ducting and outlets for:
Damage and/or restrictions.
3. Check electrical harnesses for:
Tight connections and harness abrasions.
4. Check the evaporator for:
• Intake filter cleanliness, clean if required.
• Damaged and/or contaminated fins that may restrict air flow.
•
Refrigerant leaks indicated by wet spots or dark stains on the evaporator
fins and connections.
• Check evaporator temperature sensor for proper function (see chart).
62-11175 COMFORTPRO SERVICE MANUAL
5. Check the Refrigerant lines and connections for:
• Abrasion and wear points.
• Connection wet spots that may indicate refrigerant leakage.
2-3
Page 25
6. Check the refrigerant charge level:
• Install the A/C gauges as shown in the ComfortPro Installation
Manual. Operate the A/C on high.
• Refer to chart below for high and low reference pressure.
COMFORTPRO AIR CONDITIONING OUTDOOR AMBIENT TEMPERATURE AND
PRESSURE CHART
OUTDOOR TEMPERATURE 70°F 95°F 110°F
SUCTION PRESSURE 20 PSI 35 PSI 45 PSI
DISCHARGE PRESSURE 110 PSI 175 PSI 225 PSI
OVERALL CURRENT 5-9 AMPS 9-12 AMP 12-15 AMP
Note: A/C - High
Measure at 120 volt teck cable
FAN ONLY AMP READING
FAN LOW 1.2-1.5 AMP
FAN HGH 1.8-2.2 AMP
If both suction and discharge pressure is lower than the chart,
the system is undercharged.
If both suction and discharge pressure is higher than the chart,
the system is overcharged.
If level is not ok, recover and recharge the A/C system with the
correct amount of refrigerant as shown on page 2-1.
7. Check the CCU drain:
For damage and that it operates correctly.
2-4
62-11175 COMFORTPRO SERVICE MANUAL
Page 26
3.0TROUBLESHOOTING
WARNING
Before undertaking ANY repair to
the APU, CCU or component of the
ComfortPro system disconnect
the batteries from the APU.
3.1 APU (AUXILIARY POWER UNIT) .....................................................3-2
Disconnect the batteries from the
APU before performing any
repairs.
Each symptom is followed by a probable cause and suggested solution. To isolate the
possible cause, proceed in a systematic manner to determine the faulty component. This
guide does not cover all possible situations that may occur under all conditions of operation.
WARNING
Before using this guide verify correct voltage and ground to components.
SYMPTOMPROBABLE CAUSESOLUTIONREFERENCE
Engine does not start • No fuel• Check fuel stand pipe length • A-8
(starter works)
• Air in the fuel system • Bleed air• A-8
• Water in fuel system • Drain fuel tank(s) and replace
• Fuel solenoid not pulling in • Check for rust in plunger/check
• Fuel pipe/line clogged • Clean/replace
• Fuel filters clogged • Replace • A-8
• Excessively high viscosity of • Use the specified engine oil • A-2
This will occur when the APU
Control Unit sees a problem
during or after startup
APU stops after start • Alternator belt loose or broken • Tighten/replace• A-2
sequence completes.
APU will only run with
start button depressed
(no message on Driver
• Alternator Defective • Repair/replace• 3-15
• Poor connection between alternator • Check connection / wire for breaks
and APU controller (brown wire)
Control Panel display)
This will occur when the APU
Control Unit does not see the
Alternator feed back signal
during or after start up.
*
No "GLOWING" message
on the Driver Control APU Control Unit, CCU Control
Panel, but APU will startBoard and/or the Driver Control Panel
•
Faulty communication between the
• Check APU control cable, and
Driver Control Panel cable for shorts
or opens/replace
and run normally
•
No "GLOWING" message
Faulty communication between the
on the Driver Control APU Control Unit, CCU Control
Panel and APU will onlyBoard and/or the Driver Control Panel
• Check APU control cable, and
Driver Control Panel cable for shorts
or opens/replace
run with ON button
depressed
APU only ‘clicks’ after• Faulty APU Controller• Replace APU Controller
glowing has finished
and is attempting to start
(ALT POWER light not on,
ALT F/B light does not
come on during glowing)
APU only ‘clicks’ after• Loose connection from APU controller
glowing has finishedto alternator, either at the APU
and is attempting to startcontroller end or at the Alternator end
(ALT F/B light on,
APU controller does not
come on during glowing)
• Faulty Alternator
•
Faulty APU Harness• Troubleshoot the Alternator• 3-15
*Kubota Workshop Manual 97897-02400
62-11175 COMFORTPRO SERVICE MANUAL
3-5
Page 31
3.2GENERATOR
Each symptom is followed by a probable cause and suggested solution. To isolate the
possible cause, proceed in a systematic manner to determine the faulty component. This
guide does not cover all possible situations that may occur under all conditions of operation.
WARNING
Disconnect the batteries from the
APU before performing any repairs.
SYMPTOMPROBABLE CAUSESOLUTIONREFERENCE
No voltage • 35 Amp Breaker tripped • Determine reason and reset • A-5
• Generator Belt loose/broken • Tighten/replace • A-2
Low voltage• Generator belt loose/broken• Tighten/replace • A-2
(below 100 Volts)
Very low voltage• Wiring to capacitor • Repair/replace
(4-10 Volts AC)
• Engine air filter dirty • Clean/replace filter • A-3
• Engine fuel system problem • Change fuel filters• A-3
• Engine exhaust system problem • Clean/replace
• Engine speed low • Adjust • 3- 13
• Capacitor defective • Test and replace • 3- 13, 3- 14
3-6
62-11175 COMFORTPRO SERVICE MANUAL
Page 32
3.3DRIVER CONTROL PANEL
WARNING
Disconnect the batteries from the
APU before performing any repairs.
Each symptom is followed by a probable cause and suggested solution. To isolate the
possible cause, proceed in a systematic manner to determine the faulty component. This
guide does not cover all possible situations that may occur under all conditions of operation.
SYMPTOMPROBABLE CAUSESOLUTIONREFERENCE
APU starts and runs,• No 120 Volt power to CCU Board • See "Generator" section • 3- 6
but no CCU functions
work and "OUTLET
OFF" is displayed
• Controls "locked up" • Re-boot by turning APU off and
disconnecting battery power to
APU for 30 seconds
A/C will not turn on • Temperature in sleeper is too cold • Temperature must be above 65°F • 1- 4, 1- 8
(no icon)
• Temperature is below Driver Control • Set temperature to lower setting • 1- 4, 1- 8
Panel set point
Heat will not turn on • Temperature in sleeper is too hot • Temperature must be below 85°F • 1- 4, 1- 8
(no icon)
• Temperature is above Driver Control • Set temperature to higher point • 1- 4, 1- 8
Panel set point
"HVAC BREAKER • 20 Amp CCU breaker tripped • Determine reason and press reset on
RESET" is displayed the Driver Control Panel
• Generator belt loose • Tighten/replace• A-2
"TRIP W/LIGHTENING• 20 Amp outlet breaker tripped • Determine reason and press reset on
BOLT ICON" is displayedthe Driver Control Panel
• Generator belt loose • Tighten/replace
"LOW VOLTAGE"• Generator 35 Amp breaker tripped • Determine reason and reset • 3-6, A-5
is displayed
• Generator belt loose/broken • Tighten/replace • 3-6
• Engine air filter dirty • Clean/replace filter • A-3
• Engine fuel system problem • Change fuel filters • A-3
• Engine exhaust system problem • Clean/replace
• Engine speed low • Adjust• A-2
(turn heat on to raise the sleeper temp)
(turn A/C on to lower the sleeper temp)
62-11175 COMFORTPRO SERVICE MANUAL
3-7
Page 33
3.4CCU AIR CONDITIONING
Each symptom is followed by a probable cause and suggested solution. To isolate the
possible cause, proceed in a systematic manner to determine the faulty component. This
guide does not cover all possible situations that may occur under all conditions of operation.
WARNING
Disconnect the batteries from the
APU before performing any repairs.
NOTE: The five minute timer is activated any time the compressor is turned off (by the
thermostat, EVAP temp sensor or high pressure switch. It is used to let the pressure
between the high and the low side equalize so that the compressor can start under a
"no load" condition.
SYMPTOMPROBABLE CAUSESOLUTIONREFERENCE
Does not produce • Refrigerant leaked out • Check for leaks and repair• 2-3
cold air
Produces cold air and• Evaporator blocked with ice • Increase air flow, increase return air
gradually stops
Tripped high • Condenser fan not working • See "Condenser fan not working"• 3-9
pressure switch
Tripped on EVAP • Evaporator blocked with ice• Increase air flow, increase return air
temp sensor
• Compressor not working • Check voltage at compressor
• Inlet filter clogged • Clean filter • A-3
• Low refrigerant charge • Check for leaks and repair • 2-1
• Air Duct blocked• Check and remove any blockage
• Condenser is dirty • Clean
• Poor air flow around condenser • Check condenser location, relocate
if necessary
• Refrigerant is over charged • Reduce charge to 64–68 oz • 2-1
• Low refrigerant charge • Check for leaks and repair • 2-1
• EVAP temp sensor faulty • Verify sensor operation by using Temperature vs. Resistance Chart • 2-3
3-8
62-11175 COMFORTPRO SERVICE MANUAL
Page 34
SYMPTOMPROBABLE CAUSESOLUTIONREFERENCE
Condenser fan not • A/C is not on • Set temperature to lower setting• 1- 4, 1- 8
working
• DC power fuse blown •
Determine reason and replace fuse
• A-4
• Wiring damaged • Repair/replace
• Fan defective (seized) • Replace
Compressor will not • High pressure switch open • See "Tripped high pressure switch"• 3- 8
start (no hum)
• Evaporator frozen • See "Produces cold air and • 3- 8
gradually stops"
• Five minute timer active • Wait five full minutes
• Overload protector tripped • Let unit cool down, check for • 2- 1
low refrigerant
Driver Control Panel not calling for A/C
•
• Set temperature to lower setting
• Compressor seized • Replace compressor
Compressor will not • Low A/C Voltage to CCU • See "Generator" section• 3- 6
start (hums)
• Starting capacitor defective • Determine reason and replace
• Potential relay is open• Determine reason and correct,
replace if necessary
• Compressor motor winding open • Replace compressor
• High temperature cut out due to • Increase air flow/Increase return air
insufficient air flow
• Temperature sensor wiring damaged • Repair/replace
• Temperature sensor defective • Verify sensor operation by using Temperature vs. Resistance Chart • A-11
• Ducting blocked• Check and remove any blockage
WARNING
Heat works OK, but • Driver Control Panel too close to duct• Remount away from ducts • 1- 1
short cycles
Heat operates long or • Driver Control Panel temp sensor • Verify sensor operation by using
continuouslydefectiveTemperature vs. Resistance Chart • A-11
62-11175 COMFORTPRO SERVICE MANUAL
• Driver Control Panel temp sensor • Verify sensor operation by using
defectiveTemperature vs. Resistance Chart
• Sleeper has an excessive heat loss • Cover windows, close sleeper curtains
• Sleeper has poor insulation • Insulate sleeper
• CCU air filter dirty • Clean/replace CCU filter • A-3
3-11
Page 37
3.7RECEPTACLE PANEL
WARNING
Disconnect the batteries from the
APU before performing any repairs.
Each symptom is followed by a probable cause and suggested solution. To isolate the
possible cause, proceed in a systematic manner to determine the faulty component. This
guide does not cover all possible situations that may occur under all conditions of operation.
SYMPTOMPROBABLE CAUSESOLUTIONREFERENCE
No 120 VAC power• High Heat Mode is selected • Switch to 'Low Heat' position • 1- 4, 1- 8
• APU not running • Start APU • 1- 4, 1- 8
• 35 Amp breaker tripped at • See "Generator" Section • 3-6
generator
3-12
62-11175 COMFORTPRO SERVICE MANUAL
Page 38
3.8TESTING PROCEDURES
3.8.1 Testing AMP draw for components
When checking functions of individual components, place amp clamp over black (power)
wire coming in from the generator to the CCU board. (As shown in below.)
When cross-referenced with the “AMP DRAW AND VOLTAGE CHART”, the components
should show the same amp readings.
3.8.2 Testing Voltage and Hz readings:
When checking for 120 VAC at the CCU board, the probes are placed at the black wire
terminal and the white wire terminal.
When APU is running there should always be between 110 – 130 VAC present.
When APU is running the Hz reading should always be 60 +/- 2.
62-11175 COMFORTPRO SERVICE MANUAL
3-13
Page 39
3.9ADDITIONAL INFORMATION
3.9.1 Adjusting the 120 AC Voltage
This does not need to be adjusted under normal operation. If you find low
AC voltage, check the generator belt, air filter, fuel filters and exhaust
system before adjusting.
1With the APU running turn all 120-volt components off.
2Measuring the voltage at the outlet panel adjust the engine speed
until 120 (+/- 10) volts AC and 60 Hz +/- 2 Hz is read.
3If voltage < 105 volts AC, try a known good capacitor and retest.
NOTE: Most multimeters will not test this capacitor reliably in either MF
(capacitance) or Ω (resistance) modes. The above methods are the ONLY
reliable means of testing the capacitor without a lab-grade capacitance meter.
3.9.3 Capacitor Theory
A single-phase motor can not be "fed" with just single-phase current
(120 Volt AC), there must be some way to create an artificial second
(or third) phase to smooth out the magnetic filed. Capacitors are electrical
components that help create and strengthen the artificial second phase in
single-phase electric motors. They work much like a battery, storing and
releasing a charge of electricity (AC Voltage) that is out of phase with the
oscillating (AC) current that is fed into the motor.
If single-phase induction motors do not have a second phase (created by
the capacitor) then it will not have an even magnetic field. This will cause
the rotor to hesitate at those spots that are uneven. This hesitation will
cause the rotor to spin slowly or even stop moving (compounding the
problem), draw more current (Amp's), become noisy, and overheat.
The CCU Fan and the Compressor use a Run Capacitor. Run Capacitors
are designed for continuous duty, and are energized the entire time the
motor is running.
The Compressor motor needs a Start Capacitor in addition to the Run
Capacitor. Start Capacitors are designed for momentary use. Start
capacitors stay energized long enough to bring the motor to75% of full
speed (RPM) and are then taken out of the circuit by means of a
Potential Relay.
3-14
62-11175 COMFORTPRO SERVICE MANUAL
Page 40
3.9.4 Potential Relay Theory
In a Capacitor Start, Capacitor Run compressor the start capacitor is only designed for
momentary use. The Potential Relay (NC) is used to connect and disconnect the start
capacitor from the compressors start windings. Induced Voltage is generated in the start
winding when of the compressor when it is running. The voltage induced in to the start
winding is a function of the speed of the rotor and the magnetic field that is generated.
When the compressor is first energized, the voltage in the start windings is less than the
line voltage (120 VAC). As the compressor speed (RPM) increases, the voltage in the
start windings increases significantly higher than the line voltage (up to 275 Volts) until
full compressor speed (RPM) is reached.
The Potential Relay's coil is connected across the start windings, and is designed to
respond to the increase of voltage as the compressor's speed increases. The normally
closed Potential relay contacts are designed to open at a 75% of the full compressor
speed (RPM). The Start Capacitor is connected to the relay contacts so when the relay
opens (75% of the full compressor speed RPM) the start capacitor is disconnected from
the system.
3.9.5 Alternator Troubleshooting
1 Unit switched OFF, harness connected
Check alternator feedback wire (brown) at the alternator for 5 volts.
If 5 volts are not found disconnect 'T' connector from alternator and retest. If 5 volts are
found the alternator is faulty.
If 0 volt is found check alternator feedback wire (brown) for open, and power (B+) and ground
(B-) to APU controller and repair as required. If no fault is found the APU controller is faulty.
2 Unit switched ON (glowing), harness connected
Check alternator field power wire (purple) for 12 volts. If 0 volt is found check alternator
field power wire (purple) for open and power (B+) and ground (B-) to APU controller and
repair as required. If no fault found the APU controller is faulty.
Check alternator feedback wire (brown) at alternator for 0 volt. If 5 volts are found the
alternator is faulty.
3 Unit running, harness connected
Check alternator feedback wire (brown) at alternator for 5 volt. If 0 volts are found the
alternator is faulty.
4 Unit running, then stops
Check alternator jumper harness (red) at alternator connection for 12.5-14.1 volts.
If 16-17 volts is found, check for alternator jumper (red) open and replace as required.
62-11175 COMFORTPRO SERVICE MANUAL
3-15
Page 41
3-16
62-11175 COMFORTPRO SERVICE MANUAL
Page 42
APPENDICES
CAPACITIES AND SPECIFICATIONS .................................................... A-2
System Oil capacity . . 14 oz of PVE (Polyvinylether).
Compressor . . . . . . . 6–10 Amps @ 120 Volts.
Condenser Fan . . . . . 9-12 Amps .
Binary Pressure Switch
. Normally closed between 26–335 psi.
Operating pressures . . Low side, 24–45 psi, High side, 110–250 psi.
Condenser Air inlet to outlet temperature difference should be no more
than 30°F. Evaporator Air inlet to outlet temperature difference 18° - 25°F.
STARTER – This is the output (+) to the Starter solenoid.
GLOW PLUGS – This is the output (+) to the Glow Plugs.
STARTER
GLOW PLUGS
SOL PULL
SOL HOLD
ALT POWER
COOLANT
TEMP
ALT F/B
Figure A-4: APU Control Unit
OIL
SOL PULL – This is the output (+) to the Fuel Solenoid Pull windings
(Only on during cranking for the first .5 seconds).
SOL HOLD – This is the output (+) to the Fuel Solenoid Hold windings.
ALT POWER – This is the output (+) to the Alternator field windings.
Input Indicators
OIL – This is the input (-) from the Oil Pressure Switch (NC). You will see
this light illuminated when the oil pressure is below 7 psi. This will shut
the APU off when it is illuminated.
TEMP – This is the input (-) from the Overheat Switch (NO). You will see
this light illuminated when the coolant temperature is above 245°F. This
will shut the APU off when it is illuminated.
ALT F/B – This is the input (-) from the Alternator Charging light. When
the APU is not running this light will be on. When the APU is running and
the Alternator is charging this light will be out (or very dim). This will shut
the APU off when the light is illuminated.
A-6
62-11175 COMFORTPRO SERVICE MANUAL
Page 48
Figure A-5: CCU Controller
CCU CONTROLLER
Inputs
AC – This is the input from the Driver Control Panel only when it is calling
for Air conditioning. (Low or High A/C.)
HEAT – This is the input from the Driver Control Panel only when it is
calling for Heat. (Low or High Heat.)
FAN LOW – This is the input from the Driver Control Panel only when it is
calling for CCU Low Fan. (Used in Fan, A/C, and Heat modes.)
FAN HIGH – This is the input from the Driver Control Panel only when it is
calling for CCU High Fan. (Used in Fan, A/C, and Heat modes.)
*Outputs
OUTLET – This is the output signal to the Power Outlet relay. It is On any
time 120 VAC Power is available to the Outlet. If High Heat mode is selected
the Outlet will be turned off.
LOW HEAT – This is the output signal to the Low Heat relay. It is On any
time Low Heat is called for.
**COMPRESSOR – This is the output signal to the A/C Compressor relay.
It is On any Time the A/C is called for. (Low or High.)
**CONDENSER – This is the output signal to the Condenser Fan relay. It is
On any Time the A/C is called for. (Low or High.)
LOW FAN – This is the Output signal to the CCU Low Fan relay. It is On any
time the CCU Low Fan is called for. (Used in Fan, A/C, and Heat mode.)
HIGH FAN – This is the Output signal to the CCU High Fan relay. It is On any
time the CCU High Fan is called for. (Used in Fan, A/C, and Heat modes.)
HIGH HEAT – This is the output signal to the High Heat relay. It is On any
time High Heat is called for. High Heat and Outlet can not be on at the
same time.
NOTICE
Yellow Service Light will flash when
CCU is OFF.
62-11175 COMFORTPRO SERVICE MANUAL
Service Light
If yellow Service Light is illuminated, reprogram or replacement of CCU
board may be required.
*NOTE: Outputs only indicate the signal to turn the component relay on.
They do not indicate that the actual component itself is working.
**NOTE: Air Conditioning is a sequence start. CCU fan will come on first,
0.5 seconds later the Condenser Fan will come on, and 0.5 seconds after
the Condenser fan the A/C Compressor will come on.
A-7
Page 49
FUEL SYSTEM PURGE
PROCEDURE
1. Start the APU with the APU Test Switch Module. If APU fails to start,
crank in 15 second bursts until fuel system is purged of air and APU
starts and runs smoothly.
OPEN TO BLEED THE
FUEL SYSTEM
Figure A-6: Fuel Filter
FUEL FILTER
A-8
62-11175 COMFORTPRO SERVICE MANUAL
Page 50
COOLANT PURGE PROCEDURE
1Ensure that the coolant supply valve to the APU (located at the truck
engine) and the coolant return valve to the APU (also located at the
truck engine) are open.
2Release pressure from coolant system.
3Remove the truck engine radiator cap.
4Top up the coolant if necessary in the expansion tank.
5Run the truck engine at fast idle until 185°F (85°C)is reached on truck
temperature gauge. This
6Purging Air From the Coolant.
• Place thermostat drain hose into bucket (see Figure A-7).
• Open the thermostat bleed valve, using a wrench, and let any trapped
air escape until a steady stream of coolant flows from the valve.
• Close thermostat bleeder fitting.
• Top up the coolant if necessary in the truck expansion tank.
• Run the truck engine at fast idle for another 10 minutes to continue
purging air.
should
purge most of the air out of the APU.
THERMOSTAT
DRAIN HOSE
1/2"
WRENCH
BLEEDER VALVE
OPEN 1/4–1/2 CCW
62-11175 COMFORTPRO SERVICE MANUAL
Figure A-7: Drain Hook-up
A-9
Page 51
7Start the APU by following the instructions on page 1- 3 (Multi-Function
Driver Control Panel).
8With the APU and truck engines running, open the thermostat bleed
valve and let any trapped air escape until a steady stream of coolant
flows from the valve.
9Shut the truck engine off.
10 Check the truck engine; ensure it is getting hot coolant from the APU.
If it is not, the APU is not purged of all its air. Stop APU by following
the instructions on page 1- 3 (Multi-Function Driver Control Panel).
Check for a restriction (i.e. valves/kinks etc.) and repeat steps 5 to 9.
11 Let APU run for at least 30 minutes. During this time keep checking
for signs of coolant leaks, fuel leaks and overheating.
12 Top up the coolant if necessary in the truck expansion tank and
replace the truck engine radiator cap.
13 Clean up any spilled coolant from inside APU and on the ground.
A-10
62-11175 COMFORTPRO SERVICE MANUAL
Page 52
DEFROST/HEAT & DCP SENSOR
Temperature vs.
Resistance Chart
T(°C)T(°F)
1559157.6
1661150.4
1763143.5
1864137.1
1966130.9
2068125.1
2170119.6
2272114.3
2373109.3
2475104.5
2577100.0
267995.7
278191.6
288287.7
298484.0
308680.5
318877.1
329073.9
339170.9
349368.0
359565.2
369762.5
379960.0
3810057.6
3910255.3
4010453.1
4110651.0
4210849.0
4310947.1
4411145.3
4511343.5
4611541.9
4711740.3
4811838.7
4912037.3
5012235.9
RESISTANCE Ω
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(k
Ω)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
(kΩ)
62-11175 COMFORTPRO SERVICE MANUAL
A-11
Page 53
APU Controller Pin 9
Wired to engage when truck ignition on
ENGINE INTERLOCK (PG1011)
High Side Switching
LS1
5
3
4
1
2
RELAY SPDT
Low Side Switching
APU Controller Pin 9
Wired to engage when truck ignition on
12V
LS2
5
3
4
1
2
RELAY SPDT
NOTE:
1 Relay is supplied by end user.
2 Ground connections MUST be common with APU controller.
A-12
62-11175 COMFORTPRO SERVICE MANUAL
Page 54
CLIMATE CONTROL UNIT (CCU)VEHICLE SLEEPERAUXILLARY POWER UNIT (APU)
APU WIRING DIAGRAM (Serial No.s KZX98002290 to Date)
62-11175 COMFORTPRO SERVICE MANUAL
A-13
Page 55
North America
Carrier Transicold
700 Olympic Drive
Athens, GA 30601 USA
Tel: 1--706--546 --6469
Fax: 1 --706 --546--5207
A member of the United Technologies Corporation family. Stock symbol UTX
2006 Carrier Corporation • PrintedinU.S.A.0706