4-4.R-134a Temperature - Pressure Chart4-11.........................................
iii
Page 6
SAFETY SUMMARY
GENERAL SAFETY NOTICES
Thefollowinggeneralsafetynoticessupplementthe specificwarningsand cautionsappearingelsewherein
this manual. They are recommended precautions that must be understood and applied during operation
and maintenance of the equipment covered herein. The general safety notices are presented in the
followingthree sectionslabeled:First Aid,OperatingPrecautionsand MaintenancePrecautions.Alisting
ofthespecific warningsandcautions appearingelsewhereinthe manualfollows thegeneralsafetynotices.
FIRST AID
An injury, no matter howslight, shouldnevergo unattended. Alwaysobtain first aid or medicalattention
immediately.
OPERATING PRECAUTIONS
Always wear safety glasses.
Keep hands, clothing and toolsclear of the evaporator and condenser fans.
Noworkshouldbeperformedonthe unituntilallcircuitbreakersand start-stopswitchesareturnedoff,and
power supply is disconnected.
Always work in pairs. Never work on the equipment alone.
In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator and condenser fans. Do not open the condenser fan
grilleor evaporatoraccesspanelsbeforeturningpoweroff,anddisconnectingandsecuringthe powerplug.
Be sure power is turned off before working on motors, controllers, solenoid valvesand electrical control
switches. Tag circuit breaker and power supply to prevent accidental energizing of circuit.
Do not bypass any electricalsafety devices, e.g. bridging an overload, or using any sort of jumper wires.
Problems with the systemshould be diagnosed, and any necessaryrepairs performed, by qualified service
personnel.
When performingany arc weldingonthe unit,disconnectallwire harness connectors fromthemodules in
the controlbox.Donotremove wire harness from the modulesunless you aregroundedto the unit frame
with a static-safe wriststrap.
In case of electrical fire, open circuit switch and extinguish with CO
(never use water).
2
1
Page 7
SECTION 1
DESCRIPTION
1.1 INTRODUCTION
ThismanualcontainsOperating andService Instructions
and Electrical Data for the Model Capri 280 Air
Conditioning and Heating equipment furnished by
Carrier Transicold Division.
The Capri 280 consists of a condenser, evaporator and
3
2
1
compressor.The airconditioningandheatingequipment
interfaces with electrical cabling, refrigerant piping,
engine coolant piping for heating, ductwork and other
components furnished by the bus manufacturer to
completethesystem.
7645
8
9
Figure 1-1. A/C Component Identification
1.Compressor
2.Pressure Switches
3.Electrical Control and Relay Board
4.Evaporator Section
5.Evaporator Blowers and Motors
6.Condenser Axial Fan/Motor Assemblies.
7.Condenser Section
8.Main Harness
9.Power Harness
10. Alternator
11. Power Relay
1-1
T-283
Page 8
1.2 General description
1.2.1 Condenser Unit
The condenser unit includes condenser coils, fan and
motor assemblies, filter-drier, receiver, liquid line
solenoidvalve,kingvalves, discharge check valve, andan
ambient temperaturesensor.
The condenser coils provide a heat transfer surface for
condensing refrigerant gas at a high temperature and
pressure into a liquidat high temperature and pressure.
The condenser fans circulate ambient air across the
outside of the condenser tubes at a temperature lower
than refrigerant circulating inside the tubes; this results
in condensing the refrigerant into a liquid. The
filter-drierremovesmoisture andothernoncondensibles
from the liquid refrigerant before it enters the thermal
expansion valves in the evaporator assembly.
The receiver collects and stores liquid refrigerant. The
receiver is fitted with upper and lower liquid level sight
glasses to enable determining refrigerant liquid level in
thereceiver. Thereceiverisalsofitted witha fusibleplug
which protects the system from unsafe high refrigerant
temperatures. Themain liquid linesolenoid valvecloses
whensystemisshutdowntopreventfloodingofcoils with
liquid refrigerant and to isolate the filter-drier for
servicing when the compressor is shut down. The king
valves enable servicing of the filter-drier. The ambient
temperature sensormeasures ambient temperature and
sends an electrical signal to the controller.
The discharge line check valve is a spring loaded,
normally closed valve that opens with the flow of
refrigerant from the compressor. When the compressor
clutchisdisengaged,the discharge checkvalvewill close,
preventing the flow of high pressure liquid from the
condenser to flow back into the compressor.
1. Condenser Coil
2. Condenser Fan Motor Assembly
3. Receiver Tank
4. Service Valve
5. Filter Drier
6. Liquid Hose
7. Gas Hose
8. Condenser Motor Harness
9. Condenser Motor Plate
10. Lid Screw Nut
11. Locking Screw Gasket
12. Lid Bolt Support
T-283
Figure 1-2. Condenser Unit
13. Square Nut
14. Locking Screw Gasket
15. Right Front Grille
16. Left Front Grille
17. Right Front Lateral Grille
18. Left Front Grille
19. Right Rear Lateral Grille
20. Left Rear Lateral Grille
21. Condenser Fiberglass Base
22. Condenser Top Cover Lid
23. Liquid Line Solenoid Valve
24. Receiver Tank Support
1-2
Page 9
1.2.2 Evaporator Unit
The evaporator unit includes roadside and curbside
evaporator coils.
Each evaporator unit includes six fan and motor
assemblies, evaporator/heater coil assemblies, thermal
expansion valves, condensate drain connection(s), and
evaporator heat valve.
The evaporator coils provide a heat transfer surface for
transferring heat from air circulating over the outside
surface of the coil to refrigerant circulating inside the
tubes;thusprovidingcoolingwhenrequired.Theheating
coilsprovideaheat transfer surfacefortransferringheat
fromengine coolantwater circulating insidethetubes to
air circulating overtheoutside surfaceofthe tubes,thus
providing heating when required. The fans circulate the
air over the coils. The air filtersfilter dirt particlesfrom
the air before the air passes over the coils. The thermal
expansion valves meter the flow of refrigerant entering
the evaporator coils. The heat valve controls the flow of
engine coolant water supplied to the heating coils upon
receipt of a signal from the controller. The condensate
drainconnectionsprovide ameans forconnecting tubing
for disposing of condensate collected on the evaporator
coilsduring cooling operation.
1. Evaporator Coil, Roadside
1a. Evaporator Coil, Curbside
2. Expansion Valve
3. Evaporator Blower and Motor
3a. Allen Screw
4. Humidity Sight Glass
5. Return Air Filter
6. Liquid Line
7. Relay Board
8. Logic Board
Figure 1-3. Evaporator Unit
10. Discharge Line
11. Heating Line
12. Evaporator Motor Harness
13. Lid Screw --- Stopper
14. Locking Screw Gasket
15. Lid Bolt Support
16. Square Nut
17. Lid Locking Screw
1-3
9. Suction Line
T-283
Page 10
1.2.3 Compressor Assembl y
The compressor assembly includes the refrigerant
compressor, clutch assembly, suction and discharge
service valves, high pressure switch, low pressure switch,
suction and discharge servicing (charging) ports and
electricsolenoid unloaders.
The compressor raises the pressure and temperature of
the refrigerant and forces it into the condenser tubes.
The clutch assembly provides a means of belt drivingthe
compressorby thebusengine. Thesuctionand discharge
servicevalvesenableservicingofthecompressor.Suction
anddischarge servicing(charging)portsmountedonthe
service valves enable connection of charging hoses for
servicing of thecompressor, as well as otherpartsofthe
refrigerant circuit. The high pressure switch contacts
open on a pressure rise to shut down the system when
abnormallyhighrefrigerant pressuresoccur.Theelectric
unloaders provide a means of controlling compressor
capacity,whichenablescontroloftemperatureinsidethe
bus. For more detailed information on the compressor,
refer to manual number 62-02756.
1.3 REFRIGERATION SYSTEM COMPONENT
SPECIFICATIONS
a. Refrigeration Charge
R-134a:11.3 lb (5.1 kg)
b. Compressor
Model: 05G
No. of Cylinder: 6
Weight (Dry): 165 lb (75 kg)
Oil Charge:
New Compressor: 6.75 pints (3.2liters)
Replacement Compressor:5.5 pints (2.6 liters)
1.5 ELECTRICAL SPECIFICA TIONS -Controller Input Sensors and Transducers
a. Suction and Discharge Pressure Transducer
Supply Voltage: 4.5 to 5.5 vdc (5 vdcnominal)
Supply current: 8 mA maximum
Output Range: 8K ohms minimum
InputRange: ---6.7to450psig(---46.2kPa to 3.1 mPa)
Output Current: -1.5 mA minimum to
1.5 mA maximum
Output Voltage: vdc = 0.0098 x psig
+ 0.4659 (Se e Table 4-2 for calculations.)
b. Temperature Sensors
Input Range: ---52.6 to 158_F(---47 to 70_C)
Output: NTC 10K ohms at 77_F (25_C)
(See Table 4-1 for calculations.)
1.6 SAFETY DEVICES
System components are protected from damage caused
byunsafeoperatingconditionswithsafetydevices.Safety
devices with Carrier Transicold supplied equipment
include high pressure switch(HPS), low pressure switch
(LPS), circuit breakersand fuses.
a. Thermal Switches
Condenser Motor Overloads
Each condenser fan motor is equipped with an internal
thermalprotector switch, condensermotor overloads. If
excessivemotortemperatureexists,thecondensermotor
overloadswitchwillopentode-energizethe
corresponding condenser fan.
Evaporator Motor Overloads
The evaporator fan motors are equipped with internal
thermalprotectorswitches.Ifexcessivemotor
temperature exists, the switch will open to de-energize
the corresponding evaporator fan; this will prevent the
affected evaporator motor fromoperating.
T-283
1-4
Page 11
b. Pressure Switches
High PressureSwitch (HPS)
During the A/C mode, HVAC system operation will
automaticallystopiftheHPSswitchcontactsopen dueto
an unsafe operating condition. Opening HPS contacts
de-energizes,throughthecontroller,theA/Ccompressor
clutchand condenserfanmotor relaysshutting downthe
system.
The high pressure switch (HPS)isinstalledinthecenter
head of the compressor and opens on a pressure rise to
shut down the system when high pressure conditions
occur. For R-134a systems, the switch is factory set to
open at 300 10 psig and close at 200 10 psig.
Low Pressure Switch (LPS)
Thelowpressureswitchisinstalled inthecompressorand
opensona pressuredrop toshutdownthesystemwhena
low pressure condition occurs. For R-134a systems, the
switchisfactorysetto openat63psig.In addition,ifthe
control monitors a pressure less than 10 psig by the
suction pressure transducer mounted in the evaporator
section, the system will be shut down for at least one
minute.
c. Fuses and Breakers
All outputs from the relay board are protected against
high current by circuit breakers. Independent 15 amp
circuitbreakersprotecteachmotor.Inaddition,a 15amp
fuse protects a motor from over current. During a hi gh
current condition, the breaker or fuse may open. When
the breaker opens, power will be removed from the
device and a breaker alarm will be generated. When a
fuseopens, groundwillbe removedfromthedevice anda
motor alarm will be generated.
d. Ambient Lockout
The ambient temperature sensor located in the
condensersectionmeasuresthecondenserair
temperature.Whenthetemperatureislessthan45F, the
compressorislocked outuntilthe temperature increases
above 50F to prevent compressor damage.
system using R-134a as a refrigerant. The main
components of the system are the reciprocating
compressor, air-cooledcondensercoils, receiver,
filter-drier, thermostatic expansion valves, liquid line
solenoid valve and evaporator coils.
The compressorraisesthe pressure and thetemperature
of the refrigerant and forces it into the condenser tubes.
Thecondenserfan circulatessurrounding air(whichis at
a temperature lower than the refrigerant) over the
outside of the condenser tubes. Heat transfer is
established fromthe refrigerant (insidethe tubes)tothe
condenser air (flowing over the tubes). The condenser
tubeshavefinsdesignedtoimprovethetransferofheat
from the refrigerant gas to the air; this removal of heat
causes the refrigerant to liquefy, thus liquid refrigerant
leaves the condenserandflows to the receiver.
The receiver serves as a liquid refrigerant reservoir so
that a constant supply of liquid is available to the
evaporatorsasneeded, and acts asastorage spacewhen
pumping down thesystem.The receiverisequippedwith
sightglassesto observethe refrigerantfor restrictedflow
and correct charge level.
The refrigerant leaves the receiver and passes through
the receiver outlet/service valve, through a filter-drier
where an absorbent keeps the refrigerant cleananddry.
Fromthe filter-drier, the liquid refrigerant then flowsto
the thermal expansion valves which reduce pressure and
temperature of the liquid and meters the flow of liquid
refrigerant to the evaporator to obtain maxi mum use of
the evaporator heat transfer surface.
The lowpressure,lowtemperature liquid that flowsinto
the evaporator tubes is colder than the air that is
circulated over the evaporator tubes by the evaporator
blower (fan). Heat transfer is established from the
evaporatorair (flowingover thetubes) tothe refrigerant
(flowing inside the tubes). The evaporator tubes have
aluminum fins to increase heat transfer from the air to
the refrigerant; therefore the cooler air is circulated to
the interior of the bus. Liquid line solenoid valvesclose
during shutdown to prevent refrigerant flow.
1.7 AIR CONDITIONING REFRIGERANT CYCLE
When air conditioning (cooling) is selected by the
controller, the unit operates as a vapor compression
The transfer of heat from the air tothelowtemperature
liquid refrigerant in the evaporator causes the liquid to
vaporize. This low temperature, low pressure vapor
passes through the suction line and returns to the
compressor where the cycle repeats.
1-5
T-283
Page 12
Figure 1-4. Heater Flow Diagram
1.8 HEATER FLOW CYCLE
Heating circuit components furnished by Carrier
Transicold include heater cores and evaporator heat
valves for each evaporator assembly. Components
furnished by the bus manufacturer include auxiliary
heater and engine water pumps. The controller
automaticallycontrolsthe heatvalvesduringheatingand
T-283
reheat cycles to maintain required temperatures inside
the bus. Engine coolant (glycol solution) is circulated
through the heating circuit by the engine and auxiliary
waterpumps. Whenthe evaporator heat valvesolenoid
isenergized,thevalvewillopentoallowengine coolantto
flowthrough theheater coil(see Figure 1-4).Thevalveis
normallyclosedso thatifafailureoccurs,it willbe ableto
cool.
1-6
Page 13
1.9 Relay Board -- Electronically Commutated DC Motors with 2-speed Input Signal
+
13
K1
1
K3
2
K2
D2D6D14D17D26D37D38 D41
---
EF2 EF1
4
EF3 EF4
3
K4
5
6
D81
EF HIGH
SIGNAL
EF6 EF5
K7
K8
10
7
8
9
K6
CF2 CF1
CF2 CF2
K9
K10
K24 K22 K21 K23
11
12
D85
CF
HIGH
SIGNAL
CF6 CF5
Figure 1-5 Relay Board
K14
K16
K18
K19
JP1
K15
K17
K20
K13
JP6
JP5
JP4
JP3
D57
D54
D63
D60
D72
D66
D51
D69
JP2
a. Relays
K1Energizes evaporator fans 1 & 2.
K2Energizes evaporator fans 3 & 4.
K3Energizes evaporator fan 5.
K4Energizes evaporator fan 6.
K5Provides the evaporator fan high output
signal.
K 6Provides the condenser fan high output
signal. (Not used).
K 7Energizes condenser fans 1 & 2.
K 8Energizes condenser fans 3 & 4.
K9Notused
K10Not used
K13Energizes the A/C clutch.
K14Energizes unloader 1.
K15Energizes unloader 2.
K16Energizes the high low pressure failure.
K17Energizes the heat solenoid valve.
K18Energizes the alarm output.
K19Energizes the booster pump.
K20Energizes the motor fail light.
b. Thermal Circuit Breakers 24V
CB 1 Evaporator fan #1.15 Amp.
CB 2 Evaporator fan #2.15 Amp.
CB 3 Evaporator fan #3.15 Amp.
CB 4 Evaporator fan #4.15 Amp.
CB 5 Evaporator fan #5.15 Amp.
CB 6 Evaporator fan #6.15 Amp.
CB 7 Condenser fan #1.15 Amp.
CB 8 Condenser fan #2.15 Amp.
CB 9 Condenser fan #3.15 Amp.
CB10 Condenser fan #4.15 Amp.
CB11 Spare.15 Amp.
CB12 Spare.15 Amp.
CB13 A/c clutch, unloaders 1&2
motor fail, heat valve, pressure fail
&spareoutput.15Amp.
c. Connectors
EF1-EF6Evaporator Fans.
CF1-CF4Condenser Fans.
JP1External evaporator & condenser fan
J7 Diagnostics interface (RS232, DB9).
D2 Blinks once per second in normal operation.
On steady to indicate alarms detected.
D3 Off In normal operation, blinks out alarm
codes (2 digits each) when alarms detected.
1-8
Page 15
1.11Control Panel (Diagnostic Module)
12
3
5
6
4
7
91011
8
1.Display
2.Down --- decrease selection
3.Up --- increase selection
4.Ventilation
5.Auto Control Selection
6.Air Conditioning
Figure 1-7. Diagnostic Module
7.Heating
8.Fan Speed Selection
9.Not used
10. Temperature Inside / Outside
11. Turn On / Turn Off
1-9
T-283
Page 16
SECTION 2
OPERATION
2.1 STARTING, STOPPING AND OPERATING
INSTRUCTIONS
2.1.1HVAC Power to Controller
Before starting the system, electrical power must be
available from the bus power supply. The HVAC
controller receives power from two sources:
a.24 vdc power for the microprocessor electronics
is supplied throughthebusmultiplexmodule.
b.24vdc, 125amp,powerfrom afuse inthe battery
compartment supplies power which controls
relays, clutch and unloader solenoids in the
compressor,evaporatorandcondenser
assemblies; thispower iscontrolledbythe HVAC
controller.
2.1.2Starting
a.If the engine is not running, start the engine.
After the engine is started place the A/C switch
locatedonthedashin theonposition. All system
controls will operate automatically in heating,
cooling or ventilating mode, as required.
2.1.3Self-Test and Diagnostics
(Check for Errors and/or Alarms)
Self-test of the main controller electrical circuit is
automatically initiated when the system is first
powered up. If there is an error in the circuit, ER‘‘x”
willbeindicatedbyflashingtheerrorcodeonboththe
statusandcodeLED’ssimultaneously. Ifadiagnostic
module is connectedtothe controller, the error code
canalsobe readonthe display. Ifthereare noerrors
in the circuit, system will operate normally and flash
the status LED at a one second interval. During
normal operation, the controller monitors system
operating parametersfor outoftolerance conditions.
If an out of tolerance condition occurs, ALARM will
be indicated through the code LED or on the
diagnostic tool display. If an alarm condition exists,
diagnosticscanbemanuallyinitiatedtoisolatesystem
fault(s) by simultaneously pressing the up and down
keys continuously for five seconds to view more
information. Refer to section 3 for definition of
systemerrorsandalarmsandgeneraltroubleshooting
procedures.
2.1.4Stopping
Withthesystemoperating,switching theACswitchto
the offposition will stoptheHVAC systemoperation
by removing power to the logic module.
2.2PRE-TRIP INSPECTION
After starting system operation, allow system to
stabilize for ten to fifteen minutes and check for the
following:
a.Listen for abnormal noises in compressor or fan
motors.
b.Check compressor oil level. (Refer to section
4.12.2.)
c.Check refrigerant level. (Refer to section 4.7.1.)
d.Ensure that self-test has been successfully
Temperature is controlled by maintaining the return
air temperature measured at the return air grille.
2.3.1.1Capacity Control
The controller automatically compares system
temperatures with the controller setpoints and
changessystemoperatingmodesatcertain
temperature deviations. Figure 2-1 shows various
changes in operating modes and controller actions at
various temperature deviations from controller
setpoint. Upon rising temperature, mode changes
occur when temperatures are above those given in
Figure 2-1 above controller setpoints, On a falling
temperature,modechangesoccurwhen
temperaturesarebelowthosegiveninFigure2-1.The
system will operate in these modes unless pressures
override the controller settings.
T-283
2-1
Page 17
Cool
High Speed
Loaded
Cool
High Speed
4 Cylinders
Cool
High Speed
2 Cylinders
Reheat
High Speed
2 Cylinders
T-283
Heat
Low Speed
Heat
High Speed
Figure 2-1. Auto Reheat Mode
2-2
Page 18
2.3.1.2Cooling/Reheat
Cooling and reheat require various combinations of
compressor unloading. Cooling is accomplished by
energizing the compressor and condenser fans,
opening the liquid solenoid valve and closing the
heating valve. Reheat opens the heat valve while
cooling. This allows for reduced capacity around
setpoint and de-humidification.
2.3.1.3Heating
Duringheating,theliquidsolenoidisclosedtostop
cooling and the compressor and condenser fans will
shut down. The fan speed will vary based on the
temperature difference from setpoint. Heating will
notstartuntil theenginecoolant switch(ECS)closes.
The ECS is located on the block of the vehicle andis
provided by the OEM. It senses the engine coolant
temperature. The switch closes at 105Fon
temperature rise.Theswitch prevents thecirculation
of cooler air throughout the vehicle during initial
start-up.
2.3.2Boost Pump
When the unit is in heat the boost pump relay is
energized. This signal is read by the bus multiplex
system to activate the boost pump.
2.3.3Compressor Unloader Control
The unloader outputs control the capacity of the
compressor by energizing or de-energizing unloader
solenoid valves.Energizing avalvesolenoid
de-activates a pair of compressor cylinders. The
Model 05G compressor has six cylinders. Four
cylinders are equipped with two sets of unloader
valves (UV1 and UV2), each controlling two
cylinders; this allows the compressor to be operated
withtwo,fourorsixcylinders.Whenthecompressoris
off, the unloaders are de-energized immediately.
Whenever the compressor is changed from off to on,
the unloaders are forced energized for fifteen
seconds. After fifteen seconds, one unloader may be
de-energized, if required. Any subsequent changes
between energizing and de-energizing theunloaders
must be staged with a two second delay. Only one
unloader may change state at a time when staging is
required.
secondcompressorcylinderbank(twocylinders);
this output will remain energized until the
pressure increases to above31psig.
b.Discharge Pressure
Head Pressure is also controlledby the unloaders:
1. CompressorUnloaderUV1Relay.
When the
discharge pressure increases above 275 psig, the
first compressor unloader is energized; this
output will remain energized until the pressure
decreases below 220 psig. Staging is ignored for
energizing the unloader due to discharge
pressure overrides.
2. CompressorUnloaderUV2Relay.
When the
discharge pressure increases above 285 psig, the
second unloader is energized; this output will
remain energized until the pressure decreases
below 225 psig.
2.3.4Evaporator Fan Speed Selection
Each air conditioning unit is equipped with six two
speedfan motors.Temperaturecontrolis theprimary
method of determining the fan speed selection. The
following table indicates relay operational status for
the various fan motor states.
Table 2-1. Main Evaporator Fan Speed
Relay Operation
STATE
HIGH
SPEED
EVAP FAN
RELAYS
RELAY
OffOffOff
LowOffOn
HighOnOn
Theevaporatorfans wills tart in lowspeed andrunin
high speed for cool and reheat modes. During heat
modethe fanswill runin eitherhighorlowspeed(see
figure 2-1).
Exceptions to the above are as follows:
a.In the event that the coolant temperature switch
is open, the evaporator fans are kept off during
heating.
a.Suction Pressure
In addition to temperature control, the electric
unloaders will be used to preventcoil frosting:
1. CompressorUnloaderUV1Relay.
suctionpressuredecreasesbelow26psig,thefirst
unloader is energized unloading the first
compressor cylinder bank (two cylinders); this
output will remain energized until the pressure
increases to above 34 psig.
2. CompressorUnloaderUV2Relay.
suction pressure decreases below 23 psig, the
second unloader is energized unloading the
T-283
When the
When the
2.3.5Condenser Fan Speed Control
The condenser fans are energized when the
compressor clutch output isenergized. Thefanswill
also be activated if a high pressure alarm has been
activated and operation has not been locked out
(refer to table3-3).
2.3.6Compressor Clutch Control
A belt driven electric clutch is employed to transmit
engine power to the air conditioning compressor.
De-energizing the clutch electric coil disengages the
clutch and removes power fromthecompressor. The
clutchwillbeengagedwhenin cooling.Theclutchwill
2-3
Page 19
bedisengagedwhen thesystem isoff,wheninheating
or during high andlowpressure conditions.
The clutch coil is prevented from engagement when
the ambient temperature is below 45_F (7.2_C).
The clutch coil will be de-energized if the discharge
pressure rises to 300 psig, the setting of the
compressormountedhighpressureswitch.Theclutch
coil willenergizewhen thedischargepressure falls to
200 psig.
The clutch coil will be de-energized if the suction
pressure decreases below10 psig.
b.Connect theMDSTtothe service port locatedin
the return air section.
c.Unplug the logicboardconnector J3.
d.Turn the A/C main switch located in the driver’s
area back to the ON position.
e.Activatethesystembypressingthe1/0 keyon the
MDST panel.
NOTE
Be sure to reconnect J3 when testing is
completed or the system will fail to operate
when the MDST is disconnected.
2.3.7Alarm Description
Alarm descriptions and troubleshooting procedures
are provided in section 3.
2.3.8Hour Meters
An hour meter records the compressor run time
hours. The maximumhours is 999,999.
(Refer to table 3-2)
Anhourmeter recordsthetotal timetheevaporators
are on in hours. The maximum hours is 999,999.
(Refer to table 3-2)
2.4 MICROPROCESSOR DIAGNOSTIC
SERVICE TOOL (MDST)
TheMDSTis adiagnostic servicetool that allowsthe
user to interface with the microprocessor based
control. This allows system parameters, alarms and
settings to be viewed and modified.
2.4.1 Connecting
Connect the MDST harness to the service port
located in the return air section of the A/C system.
WhentheMDSTisconnected, thepanel lightswillbe
energized and the currently stored setpoint will be
displayed. If any alarm is active, the reading will be
Axx, where A indicates that the alarm is active and xx
indicates the alarm number.
2.4.2 Control
2.4.3 Setpoint Change
Setpoint may be changed by pressing up or down
arrow keys. The up key will increase the setpoint
temperature and the down key will decrease the
setpoint temperature.
NOTE
When modifying the setpoint temperature
for diagnostic purposes, be sure to reset the
setpoint when testing is complete.
2.4.4 Mode Keys
The mode keys allow the operation tobe selected as
auto,cool, heat,orvent.Thedefaultoperationisauto
asshowninFigure2-1.
2.4.4.1 Cool
The compressor is always operational in cool mode
unless overridden by safety device. Air conditioning
willrununtilsetpointisreachedatwhichtimetheheat
valve will open and reheatis performed.
2.4.4.2 Heat
The compressor will not operate in heat mode. The
heatvalveis openeduntil1_Fbelowsetpointatwhich
timethe heatvalve closesandthe evaporatorfans run
in ventilation.
2.4.4.3 Vent
In vent mode, only the evaporator fans operate.
NOTE
This procedure should be performed by an
HVAC educated technician who knows the
Carrier Capri 280 system design. Control
configurationispresetinbythe
manufacturerandresettingofthe
parameters should not be required. It is
recommended that Carrier Service or
Engineering is contacted before anycontrol
configuration is changed. Carrier can not be
responsible for changes made by the
customer whichcause system failure if there
has not been an opportunity to approve the
changes.
a.Turn the A/C main switch located in the driver’s
area to OFF.
T-283
2.4.5 Fan Key
The fan key allows the evaporator fan speed to be
overridden to high or low. Theevaporator fan speed
willberesettoautowhenautomodekeyispressed.
2.4.6 Temperature Key
The temperature key allows the actual return air
ambient temperatures to be displayed.
2.4.7 Diagnostic Mode
Diagnostic mode can be entered by pressing the up
and down arrow keys simultaneously for 5 seconds.
Diagnosticmodeallowsalarmsandsystem
parameters to be viewed. If there are any alarms
stored, the most recent alarm will beshown. To view
additionalalarm information,refer tosection3. Press
the up and down arrow keys to view parameters.
2-4
Page 20
2.4.8 SYSTEM PARAMETERS
again indicate the setpoint setting. The parameters
are shown in Table 2-2. When scrolling through the
Pressingthe up/downarrowkeyswillallowtheuser to
scrollup ordown throughthe parameters.If nokey is
pressed for30secondsthismodeisexitedandthe
displaywillrevertbacktosetpoint.Pressingtheon/off
key any time will exit this mode and the display will
parameters, thecurrent parameter parameterwillbe
displayed for two seconds. After two seconds, the
display will show the data for the currentparameter.
When the last parameter is reached, the next
parameter will wrap back to one.
Table 2-2. Parameter Codes
CODECODE NAMEDESCRIPTION
P1Return Air TemperatureThis value is the temperature measured by the return air sensor. If the sensor
P2Coil TemperatureThis value is the coil temperature measured by the evaporatortemperature
P3Ambient TemperatureThis value is the outside temperature measured by the ambient temperature
P4Suction Line Tempera-
ture (not used)
P5Suction PressureThis value is the suction pressure measured by the suction pressure transduc-
P6Discharge PressureThis value is the discharge pressure measured by thed ischarge pressure
P9A/C Control Window #1This is the number of degrees F above setpoint at which theunloaders will be
P10A/C Control Window #2This is the number of degrees F above AC control window one at which the
P11A/C Control Window #3This is the number of degrees F above AC control window two at which the
P12Heat Control WindowThis is the number of degrees F below setpoint before the heat valve is ener-
P13Compressor Safety Off
Delay
P14Fan DelayThis is the minimum time (in seconds) that the fans must run at a particular
is shorted it will display CL. If it is open circuited it will display OP.
sensor. If the sensor is shorted it will display CL. If it is open circuited it will
display OP.
sensor. If the sensor is shorted it will display CL. If it is open circuited it will
display OP.
Not used.
er. If the sensor is shorted it will display CL If it is open circuited it will display
OP. If the auto key is pressed and held for five secondsthe suction pressure
will be calibrated to zero and the offset will be stored in no-volatile memory.
This calibration will be locked out if the offset is greater than 20 or lessthan
6.7 or if the clutch output is energized.
transducer. If the sensor is shorted it will display “CL” and if it is open circuited
it will display “OP”. If the auto key is pressed and held for five seconds the
suction pressure will be calibrated to zero and the offset will be stored in
non-volatile memory. This calibration will be locked out if the offset is greater
than 20 or less than 6.7 or if the clutch output is energized.
Not used.
both energized. This value can be modified between 0 and 10 degrees F. The
default value is 1 degree F.
first unloader will be energized. This value can be modified between 0 and 10
degrees F. The default value is 1 degree F.
evaporator fan speed will be set to low. This value can be modified between
0 and 10 degrees F. The default value is 1 degree F.
gized. This value can be modified between 0 and 10 degreesF. The default
value is 2 degree F for heat and 4 degrees F for reheat.
This number is the minimum timeinminutes that the compressor must be off
after a high or low pressure alarm before it can be restarted. This value can be
modified between one and five minutes. The default value is 1.
speed before changing to another speed. This value can be modified between one and 60 seconds. The default value is two seconds.
T-283
2-5
Page 21
Table 2-2. Parameter Codes --- Continued
CodeCode NameDescription
P15Unloader/Heat Valve
Delay
P16Compressor Head Pres-
sure Switch
P17Condenser Fan Speed
Switch (not used)
P18Maximum SetpointThis is the maximum value that the operatorwill be allowed to set the setpoint
P19Minimum SetpointThis is the minimum value that the operatorwill be allowed to set the setpoint
P20Compressor Hours High This is the number of hours of operation that the compressor has run with the
P21Compressor Hours LowThisis the number of hours of operation that the compressor has run with the
P22Evaporator Hours HighThis is the number (in thousands) of hours of operation with the evaporator
P23Evaporator Hours LowThis is the number (in hundreds, tens and ones) of hours of operation with the
P24Maintenance 1 Hour
High
P25Maintenance 1 Hour
Low
P26Maintenance 2 Hours
High
P27Maintenance 2 Hours
Low
P28Freeze Alarm SettingThis is the value at which the freeze alarm will be activated. The default value
P29RelayModuleVoltageThis is the voltage being supplied to the relay module.
P30Main Board Software
Version
P31Display Software Ver-
sion
P32KiNot used.
P33KpNot used.
This is the minimum time (in seconds) that the unloaders and heat valve must
be in a particular state (open /closed) before changingtoanother state. This
value can be modified between 1 and 60 seconds. The default value is 2 seconds.
This is the current state of the compressorh ead pressure switch input. “CL”
will be displayed if it is closed and “OP” will be displayed if it is open.
Not used.
temperature. The value can be modified in degreeswiththeup and do wn keys
to a value between 60Fand80F.
temperature. The value can be modified in degreeswiththeup and do wn keys
to a value between 60Fand80F.
clutch energized in thousands
clutch energized in hundreds, tens and ones.
fans energized.
evaporator fans energized.
This is the value of compressor hours high (P20) at which maintenance alarm
#1 will be activated. This valuecan be modified by the up and down arrow
keys. If both high and low values are zero the alarm is disabled.
This is the value of compressor hours low (P21) at which maintenance alarm
#1 will be activated. This valuecan be modified by the up and down arrow
keys. If both high and low values are zero the alarm is disabled.
This is the value of evaporator fan hours high (P22)at which maintenance
alarm #2 will be activated. This value can be modified bythe up and down
arrow keys. If both high and low values are zero the alarm is disabled.
This is the value of evaporator fan hours low (P23)at which maintenance
alarm #2 will be activated. This value can be modified bythe up and down
arrow keys. If both high and low values are zero the alarm is disabled.
is 32F. This value can be modified between 20Fand40F in one degree in-
crements by using the arrow keys
This is the software version of the logicmodule.
This is the software version of the display module.
T-283
2-6
Page 22
SECTION 3
TROUBLESHOOTING
!
DO NOT UNDER ANY CIRCUMSTANCES
ATTEMPT TO SERVICE THE MICROPROCESSOR. SHOULD A PROBLEM DEVELOP WITH
THE MICROPROCESSOR, REPLACE IT.
3.1 SELF DIAGNOSTICS
Self testsareexecuted on powerupduring operation. Errors,ifany,willbeindicatedbythedisplayandtheunitwill
notbe allowedto operate.Thedisplay willindicateerrors
Table 3-1. Error Codes
CodeNAMEDESCRIPTION
ER 1Data MemoryLogic board data memory failure.
ER 2Program MemoryLogic board program memory failure.
ER 3A/DA/D and multiplexer failure.
ER 4Communication FailureFailure in communication between the logic board and MDST.
ER 5Program MemoryDisplay program memory failure.
3.2 SYSTEM ALARMS
a. Alarm codes
Alarms will be displayed by “AXX”, or “IXX” where“A”
indicates thatthe alarm isactiveand “I”indicatesthat the
alarmisinactive. Ifthe autokey is pressedthe displaywill
scroll through the three digit hour meter readings. If
multiple alarms are present the user can scroll through
eachalarm bypressing theautokey. Whentheendofthe
alarm lis t is reached the displa y will s how “--- --- --- ”. If the
auto ke y is held d own f or five s econds while “ --- --- --- ” is
displayed all inactive alarms are cleared.
with the code ER-X (X is the error number). The error
codes can also be read by counting the number of times
that the status and alarm LED’s flash simultaneously.
alarm is already present. Each alarm recorded will also
have an evaporator hour meter reading corresponding to
the activation time. When an alarm becomes inactive a
statusindicator inthe alarmqueue willchange toindicate
thatthe alarmis inactive.If anyalarms areactive thefault
output will be energized.
c. Alarm queue
The alarm queue consist of10alarmlocations.Whenthe
alarm queue is full an alarm will be generated but not
stored toindicated this. Whenalarmsare viewed this will
be the first alarm to be shown.
!CAUTION
b. Activation
When an alarm becomes active they will be placed in an
alarm queueinthe order at whichthey initiate unless the
T-283
d. Alarm clear
TheusermayclearinactivealarmsthroughtheMDST
keypad or computer communications.
3-1
Page 23
Table 3-2. Alarm Codes
ALARM
NO.
11Coil FreezeCoil temperature is less
12High VoltageThebatteryvoltageis
13Low VoltageThebatteryvoltageis
14Return Air Probe FailureReturn air temperature
15Suction Pressure
Transducer Failure
16Discharge Pressure
Transducer Failure
17Low Pressure ShutdownLow suction pressure
21High Discharge PressureHigh discharge pressure
22Breaker Trip AlarmA breaker on the relay
23Evaporator Fan OverloadEvaporator fan overload
24Condenser Fan OverloadCondenser fan overload
TITLECAUSEREMEDYCONTROLLER
than 32Fandthecompressor is operating.
greater than 32 volts.
less than 17 volts.
sensor failure or wiring
defective.
Suction pressure transducer failure or wiring
defective.
Discharge pressure
transducer failure or wiring defective.
switch open or wiring
defective.
switch open or wiring
defective.
board has tripped or a
fan relay has failed.
jumper is open.
jumper is open.
Check causes of coil
freezing. (Refer to section 3.5.6)
Check, repair or replace
alternator.
Check, repair or replace
wiring or alternator.
Ensure all connectors
are plugged in. Check
sensor resistance or wiring. Replace sensor or
repair wiring.
Ensure all connectors
are plugged in. Check
sensor voltage or wiring.
Replacesensororrepair
wiring.
Ensure all connectors
are plugged in. Check
sensor voltage or wiring.
Replacesensororrepair
wiring.
Check cause of low suction pressure. (Refer to
section 3.5.3)
Check discharge pressure transducer reading,
wiring or cause of high
discharge pressure.
(Refer to section 3.5.3)
Check breakers for
tripped device. Repair
short and reset breaker.
Ensure connector is
plugged in or repair
wiring.
Ensure connector is
plugged in or repair
wiring.
RESPONSE
An alarm will be generated
and the system will shutdown. The evaporator fans
will remain running whilethe
compressor is off.
The system is shut down
until the voltage returns to
normal levels.
The system is shut down
until the voltage returns to
normal levels.
All outputs except the evaporator fans will be de-energized.
Both unloaders are energized.
One unloader is energized.
The clutch is de-energized
for the minimum off time.
The evaporator fans will remain running during this period. After the compressor
cycles off three times in 30
minutes all outputs will be
de-energized and the system is locked out until the
poweriscycledorthealarm
is reset through the keypad.
The clutch is de-energized
for the minimum off time.
The condenser and evaporator fans will remain running during this period. Afterthecompressorcycles
off three times in 30 minutes
all outputs will be de-energized and the system is
locked out until the power is
cycled or the alarm is reset
through the keypad.
Alarm will be generated.
Alarm will be generated.
Alarm will be generated.
T-283
3-2
Page 24
Table 3-2. Alarm Codes (Continued)
ALARM
NO
25Motor FailureA motor has not reached
26Not used
31Maintenance Alarm 1The compressor hour
32Maintenance Alarm 2The evaporator hour
99AlarmQueue FullAll locations of the alarm
TITLECAUSEREMEDYCONTROLLER
full operating speed or
the condenser motors
have shut down due to a
pressure alarm or the
motor fuse has blown.
meter is greater than the
value in Maintenance
Hour Meter 1.
meter is greater than the
value in Maintenance
Hour Meter 2.
queue are currently full
and no more alarms can
be saved.
Replace motor, or correct pressure shutdown.
Reset the maintenance
hour meter.
Reset the maintenance
hour meter.
Record and clear alarm
queue.
RESPONSE
Alarm displayed and the
motor fail output is energized.
Alarm will be generated.
Alarm will be generated.
Alarm will be generated.
T-283
3-3
Page 25
Table 3-3. General System Troubleshooting Procedures
Low refrigerantcharge
High suction pressureCompressorvalve(s)wornorbrokenSee Note.
Low suction pressureSuction service valve partially closed
Filter-drier inlet valve partially closed
Filter-drier partially plugged
Low refrigerantcharge
Expansion valve malfunction
Restricted air flow
Suction transducer failure
Suction and dischargepressures
Compressor valve defectiveSee Note.
Open
Check/ Open
4.10
4.5 and 4.7
p. 3-5
p. 3-5
Replace
tend to equalize when system is
operating
ABNORMAL NOISE OR VIBRATIONS
CompressorLoose mounting hardware
Worn bearings
Worn or broken valves
Liquid slugging
Insufficient oil
Clutch loose, rubbing or is defective
V-belt cracked, worn or loose
Dirt or debris on fan blades
Check/Tighten
See Note.
See Note.
p. 3-5
4.12.2
Check
Check/Adjust
Clean
T-283
3-4
Page 26
Table 3-3. General System Troubleshooting Procedures - Continued
INDICATION/
TROUBLE
POSSIBLE CAUSES
REFERENCE
SECTION
ABNORMAL NOISE OR VIBRATIONS --- Continued
CondenserorevaporatorfansLoose mounting hardware
Defective bearings
Blade interference
Blade missing or broken
No or partial evaporator air flowMotor(s) defective
Motor brushes defective
Evaporator fan loose or defective
Fan damaged
Return air filter dirty
icing of coil
Fan relay(s) defective
Safety device open
Fanrotationincorrect
Defrost coil
Clean
Clean/Replace
Repair/Replace
Replace
Repair/Replace
Repair/Replace
Clean/Replace
Clean/Defrost
Check/Replace
1.6
Check
EXPANSION VALVE MALFUNCTION
Low suction pressure with high
superheat
Low superheatandliquid slugging
in the compressor
Side to side temperature difference (Warm Coil)
Low refrigerantcharge
Wax, oil or dirt plugging valve orifice
Ice formation at valve seat
Power assembly failure
Loss of bulb charge
Broken capillary
Superheat setting too low
Ice or other foreign material holding valve open
Wax, oil or dirt plugging valve orifice
Ice formation at valve seat
Power assembly failure
Loss of bulb charge
Broken capillary
4.5 and 4.7
Check
4.6
Replace
Replace
4.11
4.11
4.6
Check
4.6
Replace
Replace
4.11
HEATING MALFUNCTION
Insufficient heatingDirtyorpluggedheatercore
Coolant solenoid valve(s) malfunctioning or plugged
Low coolant level
Strainer(s) plugged
Hand valve(s) closed
Water pumps defective
Auxiliary Heater malfunctioning.
No HeatingCoolant solenoid valve(s) malfunctioning or plugged
Controller malfunction
Pump(s) malfunctioning
Safety device open
BE SURE TO OBSERVE WARNINGS LISTED IN
THE SAFETY SUMMARY IN THE FRONT OF THIS
MANUAL BEFORE PERFORMING MAINTENANCE ON THE HVAC SYSTEM
4.1 MAINTENANCE SCHEDULE
SYSTEM
ONOFF
a. Daily Maintenance
X
b. Weekly Inspection
X
c. Monthly Inspection and Maintenance
Pre-trip Inspection --- after starting
Check tension and condition of V-belt
X
X
Perform daily inspection
X
Check condenser, evaporator coils and air filters for cleanliness
X
Check refrigerant hoses and compressor shaft seal for leaks
Feel filter-drier for excessive temperature drop across drier
X
Perform weekly inspection and maintenance
X
Clean evaporator drain pans and hoses
X
Check wire harnesses for chafing and loose terminals
X
Check fan motor bearings
X
Check compressor mounting bolts for tightness
X
Check fan motor brushes
WARNING
!
REFERENCE
SECTION
2.2
None
4.1.a
None
4.5
4.10
4.1.b
None
Replace/Tighten
None
None
None
4.2SUCTION AND DISCHARGE SERVIC E VAL VES
The suction and discharge service valves used on the
compressor are equipped with mating flanges for
connection to flanges on the compressor. These valves
are providedwith a doubleseat and a gauge connection,
whichallowsservicingof the compressorandrefrigerant
lines. (See Figure 4-1.)
Turningthe valvestemcounterclockwise (allthewayout)
will backseat the valve to open the suction or discharge
line to the compressor and close off the gauge
connection. Innormaloperation, the valve isbackseated
to allow full flow through the valve. The valve should
always be backseated when connecting the service
manifold gauge lines to the gauge ports.
Turning the valve stem clockwise (all the way forward)
willfrontseatthevalvetocloseoffthesuctionordischarge
line to isolate the compressor and open the gauge
connection.
To measure suction or discharge pressure, midseat the
valve byope ningthe valve clockwise1/4 to1/2 turn. With
the valve stem midway between frontseated and
backseated positions, the suction or discharge line is
open to both the compressorandthegauge connection.
To Dischargeor
from Suction Line
Port to
Compressor
Service Valve
Frontseated
(clockwise)
Figure 4-1. Suction or Discharge Service Valve
4-1T-283
Gauge
Connection
Service Valve
Backseated
(counterclockwise)
Valve Cap
Valve
Stem
Page 28
4.3INSTALLING MANIFOLD GAUGES
Themanifold gaugeset canbe usedtodeterminesystem
operatingpressures,addcharge,equalizeorevacuatethe
system. (See figure4-2.)
Low Pressure
Gauge
Hand Valve
(Open)
A. Connection to
Low Side of System
ABC
C. Connection to Either:
High Pressure
Gauge
Hand Valve
(Frontseated)
Vacuum Pump
Refrigerant Cylinder
B. Connection to
High Side of System
Oil Container
Evacuation Line
Figure 4-2. Manifold Gauge Set
The manifold gauge in figure 4-2 shows hand valves,
gaugesandrefrigerantopenings. Whenthelowpressure
hand valve is frontseated (turned all the way in), the low
(evaporator) pressure can be checked. When the high
pressure hand valve is frontseated, high (condensing)
pressure can be checked. When both valves a re open
(turned counterclockwise), high pressure vapor willflow
into the low side. When the low pressure valve is open,
the system can be charged or evacuated. Oil can also be
added to the system.
Install the manifold gauge set as follows:
a.Remove both service valve stems and service port
caps. Backseat (counterclockwise) both service
valves.
b.Connect the high side hose tightly to discharge
service valve port.
c.Connect the low side hose loosely to suction service
valve port.
d.Loosen charging (center) hose at dummy fitting of
manifold set.
e.Frontseat (clockwise) both manifold gauge hand
valves.
f.Open discharge service valve counterclockwise
approximately 1/4 to 1/2 turns.
g.Slowly open (counterclockwise) manifold discharge
hand valve approximatelyone turn.
h.Tighten charging hose onto dummy fitting.
i.Slowly open the manifold suction hand valve to
remove air from line.
j.Tightensuctionhoseatthesuctionservicevalveport.
k.Frontseat (close)both manifold hand valves.
l.Opensuctionservicevalvecounterclockwise
approximately 1/4 to 1/2 turns.
4.4PUMPING THE SYSTEM DOWN OR
REMOVING THE REFRIGERANT CHARGE
Thefollowingproceduremayhavetobe
repeatedseveraltimestomaintainthe1psig(6.9kPa) pressure depending upon amount of
refrigerant absorbed in the oil.
b.Frontseat filter-drier inlet service valve by turning
clockwise. Start system and run in cooling. Stopthe
unit when the suction pressure reaches 1 psig (6.9kPa) to maintain a slight positive pressure.
c.Frontseat (close) suction service valve to trap the
refrigerantinthe highsideof thesystembetweenthe
compressor suction service valve andthe filter drier
inlet valve. Thelowside ofthesystemwill nowbe at1
psig (6.9 kPa) pressure and ready for servicing,
d.Service or replace the necessary component on the
low side of the system.
e.Leak check connections. (Referto section4.5.)
f.Evacuate and dehydrate the low side. (Refer to
section4.6.)
4.4.2Removing the Refrigerant Charge
Connect a refrigerant recovery system to the unit near
the receiver to remove refrigerant charge. Refer to
instructions provided by the manufacturer of the
refrigerant recoverysystem.
NOTES
a.Before openingupany partofthe system, a
slightpositivepressure shouldbe indicated on
the gauge.
b.When opening up the refrigerant system,
certain parts may frost. Allow the part to
warm to ambient temperature before
dismantling; this avoids internal
condensation, which puts moisture in the
system.
4.5REFRIGERANT LEAK CHECK
A refrigerant leak check should always be performed
after the system has been opened to replace or repair a
component.
To check for leaks in the refrigeration system, perform
the followingprocedure:
4-2T-283
Page 29
NOTE
Itmust beemphasized thatonly the correct
refrigerant drum should be connected to
pressurizethesystem. Any other gas or
vapor willcontaminate the system, which
will requireadditionalevacuation and
evacuation of the high (discharge) side of
the system.
a.Ensure the main liquid line and driver solenoid
valves are open.
b.If system is without refrigerant, charge system with
refrigeranttobuilduppressurebetween30to50psig
(207 to 345 kPa).
c.Add sufficient nitrogen to raise system pressure to
150 to 200 psig (1.03 to 1.4 mPa).
d.Check for leaks. The recommended procedure for
finding leaks in a system is with a halide torch or
electronicleakdetector. Testingjointswithsoapsuds
is satisfactory only for locating large leaks.
e.Remove refrigerant using a refrigerant recovery
system and repair any leaks.
f.Evacuate and dehydrate the system. (Refer to
section4.6.)
g.Charge the unit. (Refer to section 4.7.)
h. Ensure that self-test has been performed and that
there are no errors or alarms indicated. (Refer to
paragraph 2-1.7.)
4.6EVACUATION AND DEHYDRATION
a. General
Thepresenceofmoistureinarefrigerationsystemcan
have many undesirable effects. The most common are
copper plating, acid sludge formation, “freezing-up” of
metering devices by free water, and formation of acids,
resulting in metal corrosion.
b. Preparation
NOTE
Using a compound gauge is not recommended
because of its inherent inaccuracy.
1.Evacuateanddehydrateonlyafterpressureleaktest.
(Refer to section 4.5.)
2.Essential tools to properly evacuate and dehydrate
any system include a good vacuum pump with a
minimumof 5 cfm (8.5 m
3
/hr)volume displacement,
CTDP/N07-00176-01),andagoodvacuumindicator
(availablethroughRobinairManufacturing,
Montpelier, Ohio, Part Number 14010).
3.Keepthe ambienttemperatureabove 60_F(15.6_C)
to speed evaporation of moisture. If ambient
temperature is lower than 60_F (15.6_C),icemay
formbefore moisture removalis complete.Itmay be
necessary to use heater blankets, heat lamps or
alternatesourcesofheattoraisesystem
temperature.
c. Procedure for Evacuation and
Dehydrating System
1.Remove refrigerant using a refrigerant recovery
system.
2.The recommendedmethodisconnecting three lines
(3/8”ODcoppertubingorlarger)tomanifold.
Attach one line to the filter-drier outlet valve,
compressor suction and discharge service valves.
(See Figure 4-3.)
3.Connect lines to unit and manifold and make sure
vacuumgaugevalve isclosedandvacuumpumpvalve
is open.
4.Opensolenoidvalveselectrically(jumper24vtocoil)
to ensure a good vacuum is obtained.
5.Start vacuum pump. Slowly open valveshalfway and
then open vacuum gauge valve.
6.Evacuate unit until vacuum gauge indicates 1500
microns (29.86 inches =75.8 cm)Hg vacuum. Close
gauge valve, vacuum pump valve, and stop vacuum
pump.
7.Break the vacuum with clean dry refrigerant. Use
refrigerant that the unit calls for. Raise system
pressure to approximately 2 psig (13.8 kPa).
8.Remove refrigerant using a refrigerant recovery
system.
9.Start vacuum pump and open all valves. Dehydrate
unit to 500 microns (29.90 inches = 75.9 cm) Hg
vacuum.
10. Closeoffpumpvalve,isolatevacuumgaugeinsystem
and stop pump. Wait five minutes to see if vacuum
holds.
11. Withavacuumstillin theunit,the refrigerantcharge
may be drawn into the system from a refrigerant
container on weight scales.
4.7ADDING REFRIGERANT TO SYSTEM
4.7.1Checking Refrigerant Charge
Thefollowingconditions mustbemettoaccuratelycheck
the refrigerant charge.
a.Coach engineoperating at high idle.
b.Unit operating in coolmode for 15 minutes.
c.Headpressureatleast150psig(1.03mPa)forR-134a
systems. (It may benecessary to block condenser
air flow to raise headpressure.)
d.Under the above conditions, the system is properly
chargedwhen therefrigerant liquidlevel is visible in
thereceiverlowersightglass.Ifitisnotvisible,addor
removerefrigerant until it is at the properlevel.
4.7.2Adding Full Charge
a.Evacuate and dehydrate system. (Refer to section
4.6)
b.Place appropriate refrigerant cylinderonscales and
connect charging hose from container to filter-drier
inlet valve. Purge air from hoses.
4-3T-283
Page 30
c.Note weight of refrigerant and cylinder.
d.Openliquid valve onrefrigerant container. Midseat
filter-drier inlet valve and allow refrigerant to flow
intotheunit. Correctcharge willbe foundinsection
1.3.
e.When cylinder weight (scale) indicates that the
correct charge hasbeenadded,closeliquidlinevalve
on drum and backseat the filter-drierinletvalve.
4.7.3Adding Partial Charge
4.9CHECKING AND REPLACING HIGH
PRESSURE CUTOUT SWITC H
4.9.1Checking High Pressure Switch
!
DO NOT USE A NITROGEN CYLINDER
WITHOUT A PRESSURE REGULATOR.
DO NOT USE OXYGEN IN OR NEAR A
REFRIGERATION SYSTEM OR AS AN
EXPL OSION MAY OCCUR.
WARNING
!
a.Start the vehicle engine and allow unit to stabilize.
b.Place appropriate refrigerant cylinderonscales and
connectcharginghose fromcontainervapor valveto
compressor suction service valve.
c. Rununitincoolmodefor15minutes.Withsuction
service valve midseated, remove air from hose at
refrigerant cylinder. Open cylinder valve and add
vapor charge until refrigerant level appears in the
lowerreceiversightglass.Undertheabove
conditions, thesystemwillbeproperlychargedwhen
the lower receiver sight glass appears full of
refrigerant. Add or remove refrigerant until the
proper level is obtained. Refrigerant level should not
appear in the upper sight glass, as this would indicate
and overcharge.
d.Backseat suction service valve. Close vapor valve on
refrigerant drum and note weight. Replace all valve
caps.
4.8CHECKING FOR NONCONDENSIBLES
To check for noncondensibles, proceed as follows:
a.Stabilize system to equalize pressure between the
suction and discharge side of the system.
b.Checktemperature at the condenser and receiver.
c.Check pressure at the compressor discharge service
valve.
d.Check saturation pressure as it corresponds to the
condenser/receivertemperatureusingthe
Temperature-Pressure Chart, Table 4-4.
e.If gauge readingis 3 psig (21 kPa) or more than the
calculated P/T pressure in step d, noncondensibles
are present.
f.Remove refrigerant using a refrigerant recovery
system.
g.Evacuate and dehydrate the system. (Refer to
section4.6.)
h. Charge the unit. (Refer to section 4.7.)
a.Remove switch from unit. All units are equipped
with schrader valves at the high pressure switch
connection.
b.Connectanohmmeteracrossswitchterminals.Ifthe
switch is good, the ohmmeter will indicate no
resistance, indicating that the contacts are closed.
c.Connect switch to a cylinder of dry nitrogen. (See
Figure 4-4.).
1
4
1. Cylinder V alve
2
3
Figure 4-3. Checking High Pressure Switch
d.Set nitrogen pressure regulator higher than cutout
point on switch being tested. (See section1.3.)
e.Opencylinder valve.Slowlyopenthe regulatorvalve
toincreasethepressureuntilitreachescutoutpoint.
The switch should open, which is indicated by an
infinite reading on an ohmmeter (no continuity).
f.Closecylindervalveandreleasepressurethroughthe
bleed-offvalve.Aspressuredropstocut-inpoint,the
switch contacts shouldclose, indicatingnoresistance
on the ohmmeter.
g.Replace switch if it does not function as outlined
above. (Refer to section 4.9.2.)
4.9.2Repla cing High Pressure Switch
a.The high pressure switch is equippedwith schrader
valve to allow removal and installation without
pumping the unit down.
b.Disconnect wiring from defective switch.
c.Install new cutout switch.
d.Check switch operation. (Refer to section 4.9.1.)
5
6
and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
4. Pressure Gauge
(0 to 400 psig =
0to2.8mPa)
5. Bleed-Off Valve
6. 1/4 inch Connection
4-4T-283
Page 31
4.10 FILTER-DRIER
a. To Check Filter Drier
Check for a restricted or plugged filter-drier by feeling
the liquid line inlet and outlet connections of the
filter-drier. If the outlet side feels cooler than the inlet
side, then the filter-drier should be changed.
b. To Replace Filter Drier
1.Pumpdown the unit. (Refer to section 4.4.)
2.Replacefilter-drier,ensuringthatthearrowpointsin
the direction of the refrigerant flow.
3.Drier can be evacuated at liquid service valve. (See
Figure 4-3.)
4.Check refrigerantlevel. (Refer to section 4.7.1.)
12. Run the coachforapproxi mately 30 minutes on fast
idle.
13. Check refrigerant level. (Refer to section 4.7.1.)
14. Checksuperheat. (Refer to section 4.11.b.)
1
6
7
5
4
3
2
8
9
8
4.11 THERMOSTATIC EXPANSION VALVE
The thermostat expansion valve (TXV) is an automatic
device which maintains constant superheat of the
refrigerant gas leaving the evaporator regardless of
suction pressure. The valve functions are: (a)automatic
responseof refrigerantflowtomatchtheevaporatorload
and (b) prevention of liquid refrigerant entering the
compressor. Unless the valve is defective, it seldom
requires any maintenance.
a. Replacingthe Expansion Valve (SeeFigure4-5.)
1.Pump down low side of the unit. (Refer to section
3.Loosen retainingstraps holding bulb to suction line
and detach bulbfrom the suction line.
4.Loosen flare nuts on equalizer line and disconnect
equalizer linefromthe expansion valve.
5.Remove capscrews and lift off powerheadandcage
assembliesandgaskets.
6.Check, clean and removeany foreignmaterial from
the valve body, valveseatandmating surfaces.
NOTE
Do not adjust the new replacement expansion
valve. Valves are preset at the factory.
7.Usingnew gaskets,i nstall newcage and power head
assembliesprovidedwith repair kit.
8.The thermalbulbisinstalled below the centerofthe
suctionline(fouroreighto’clockposition).Thisarea
must be clean to ensure positive bulbcontact. Strap
thermal bulb to suction line and insulate both with
“Presstite.” Ensure that retaining straps are tight.
(See Figure 4-6.)
9.Fasten equalizer line to the expansion valve.
10. Evacuate and dehydrate. (Refer to section 4-6.)
11. Openfilter-drierinletvalve(liquidlineservicevalve)
and all service valves.
10
11
1. Power Head Assembly7. Bulb
2. Cap Seal8Gasket
3. Flare Seal9. Cage Assembly
4. Retaining Nut10. Body Flange
5. Adjusting Stem11. Capscrew
6. Equalizer Connection
Figure 4-4. Thermostatic Expansion Valve
3
2
1
1. Suction Line (end view)
2. TXV Bulb Clamp
3. Nut and Bolt (clamp)
4. Thermocouple
5.TXVBulb(Showninthe
4’clock position)
Figure 4-5. Thermostatic Expansion Valve
Bulb and Thermocouple
Monitor the superheat over a five minute period and
record the maximum and minimum readings. Add the
maximum and minimum readings and divide by two to
determine the superheat. Thesuperheatshould be10F
to 12F.
b. To Check/Measure Superheat
NOTE
Allreadingsmust betaken fromthe suctionside
areaofthe evaporator nearthe TXV andoutof
the direct air stream.
1.Remove filter access door.
2.Remove Presstite insulation from expansion valve
bulb and suction line.
4
5
4-5T-283
Page 32
3.Loosen one TXV bulb clamp and make sure area
under clamp is clean.
4.Place temperaturethermocouplein contact with the
suction tube and parallel to the TXV bulb,andthen
secure loosened clamp making sure both bulbs are
firmly secured to suction line. (See Figure 4-5).
Reinstall insulation around the bulb.
5.Reinstall evaporator access door being careful to
route thermocouple sensing wire outside the
evaporator.
6.Connect an accurate lowpressure gauge to the 1/4”
portonthesuctionservicevalveorinstalla manifold
gauge set. (Refer to section 4.3.)
When conducting this test, the suction pressure
must be at least 6 psig (41 kPa) below the
expansion valve maximum operating pressure
(MOP). Refer to section 1.3 forMOP.
8.Fromthetemperature/pressurechart, determinethe
saturation temperaturecorrespondingto the
evaporator outlet pressure.(SeeTable 4-4.) Addan
estimatedsuction lineloss of2psig (13.8 kPa) to the
number taken at the compressor.
9.Note the temperature of the suction gas at the
expansion valve bulb. Subtract the saturation
temperature determined i n step 8 from the
temperaturemeasuredin thisstep. Thedifference is
the superheat of the suction gas.
10. Monitorthe superheatoverafiveminute periodand
record the maximum and minimum readings. Add
themaximumandminimumreadingsanddivide by2
to determine superheat. The superheat should be
10Fto12F.
c. To Adjust Superheat
NOTE
It is not recommended to adjust thermal
expansion valves unless absolutely necessary.
Theprocedure is verytimeconsuming.
Therefore, it is highly recommended that the
expansion valve be replaced rather than
adjusting.
2.Removecapscrewsandnote relative position ofcage
assembly.(See Figure 4.5.) Lift out powerheadand
cage assemblies while maintaining position of the
cageassembly.Turn/rotatecageassembly
counterclockwise to decrease superheat setting or
clockwise to increase superheat setting. Each full
turn willchange superheat setting by 1_F (0.56_C).
3.Check, clean and removeany foreignmaterial from
the valve body, valveseatandmating surfaces.
7.Openfilter-drierinletvalve(liquidlineservicevalve)
and all service valves.
8.Runthe coach for approximately 30 minutes on fast
idle.
9.Check refrigerantlevel. (Refer to section 4.7.1.)
10. Checksuperheat setting. (Refer to section 4.11.b.)
4.12 Model 05G COMPRESSOR MAINTENANCE
4.12.1 Remo ving the Compressor
If compressor is inoperative and the unit still has
refrigerant pressure, frontseat suction and discharge
service valves to trap most of the refrigerant in the
system.
If compressor is operative, pump down the system.
(Refer to section 4.4.)
a.T u rnmain batter y discon n ec t switc h to OFF position.
b.Slowly release compressor pressure.
c.Remove bolts from suction and discharge service
valve flanges.
d.Tag and disconnect wiring to the high pressure and
low pressure cutout switch, unloadersand clutch.
e.Remove four bolts holding compressor to base
f.Attach sling or other device to the compressor and
remove compressorfrom the coachthroughthe rear
access door.
g.Remove the three socket head capscrews from both
cylinderheadsthat haveunloader valvesinstalledon
the05G compressor.Removetheunloadervalveand
bypass piston assembly, keepingthesamecapscrews
with the assembly. The original unloadervalve must
be transferred to the replacement compressor. The
plug arrangement removed from the replacementis
installed intheoriginalcompressorasaseal.Ifpiston
is stuck, it may be extracted by threading a socket
headcapscrewinto topof piston.A smallTeflonseat
ring at the bottom of the piston must be removed.
NOTES
1. The service replacement 05G compressors
are sold without shutoff valves. Valve pads
are installed in their place. The optional
unloaders are not supplied, as the cylinder
heads are shipped with plugs. Customer
should retain the original unloader valves
for use on the replacement compressor.
2. The piston plug that is removed from the
replacement compressor head must be
installed inthe failed compressor if
returning for warranty.
3. Donot interchangeallen-headcapscrewsthat
mount the piston plug and unloader, they
are not inte rchangeable.
4-6T-283
Page 33
4. Check oil level in service replacement
compressor. (Refer to section 1.3 and 4.12.2.)
COMPRESSOR
HEAD
GASKET
BYPASS
PISTON
PLUG
FLANGE
COVER
SPRING
capscrews
(NOT INTERCHANGEABLE
WITH CONTROL VALVE
SCREWS)
Figure 4-6. Removing Bypass Piston Plug
h.Remove the high pressure switch assembly and
install on replacement compressor after checking
switchoperation.
12
11
10
9
8
7
1. Electric Unloader
Valve
2. Suction Service
Valve Charging Port
3. Suction Service
Valve
4. Clutch
5.OilFillPlug
1
2
3
4
5
6
6. Bottom Plate
7. Oil Drain Plug
8. Oil Level Sight Glass
9. Oil Pump
10. O-ring
11. Discharge Service
Valve
12. Service Port
i.Install compressor in unit by performing steps c.
through h. in reverse. It is recommended that new
locknutsbe used when replacing compressor.Install
new gaskets on service valves and tighten bolts
uniformly.
j.Unlock and turn main battery disconnect switch to
ON position..
k.Attach two lines (with hand valves near vacuum
pump) to the suction and discharge service valves.
(Dehydrateandevacuate compressorto500microns
(29.90” Hg vacuum= 75.9 cm Hgvacuum). Turn off
valves on both lines to pump.
l.Fully backseat (opencounterclockwise) both suction
and discharge service valves.
m. Remove vacuum pump lines and install manifold
gauges.
n.Start unit and check refrigerant level.
o.Checkcompressoroillevel.(Refertosection4.12.2.)
Addorremove oil if necessary.
p.Check compressor unloader operation.
Figure 4-7. Model O5G Compressor
4.12.2 Compressor Oil Level
4.12.2.1 Checking the Compressor Oil Level
NOTE
The compressor should be fully loaded (six
cylinder operation); the unit should be fully
chargedandthecompressorcrankcaseshouldbe
warm to the touch.
a.Start the unit and allowthe system to stabilize.
b.Checkthe oilsightglassonthe compressorto ensure
that nofoamingof the oilispresent after 20minutes
ofoperation.Iftheoilisfoamingexcessivelyafter20
minutes of operation, check the refrigerant system
for flood-back of liquid refrigerant. Correct this
situationbeforeproceeding.(Referto section3.3.4.)
c.Check the level of the oil in the oil level sight glass
immediately after shutting down the compressor.
Thelowestlevelvisibleshouldbebetweenthe“Min”
and “Max” indicators on the compressor crankcase
adjacent to the sight glass. (See Figure 4-8.)
4.12.2.2 Adding Oil with Compressor in System
Twomethodsforaddingoilare:the oilpumpmethod and
closed system method.
a. Oil Pump Method
1.Onecompressoroilpumpthat maybe purchasedis a
Robinairpart no.14388.This oilpumpadaptstoone
U.S. gallon (3.785 liters) metal refrigeration oil
container and pumps 2-1/2 ounces (72.5 mliters) per
stroke when connected to the suction service valve
port.Also,thereisnoneedtoremovepumpfromcan
after each use.
4-7T-283
Page 34
2.When the compressor is in operation, the pump
Resi
O
h
check valve prevents the loss of refrigerant while
allowingservicementodevelopsufficientpressureto
overcome the operatingsuction pressure to add oil,
as necessary.
3.Backseat suction service valve and connect oil
charging hose to port. Crack open the service valve
andremoveairfromtheoilhoseattheoilpump.Add
oil as necessary.
b. Closed System Method
1.In anemergency whereanoil pump is notavailable,
oil may be drawn into the compressor through the
suction service valve.
!
EXTREMECAREMUSTBETAKENTO
ENSURETHATTHEMANIFOLD
COMMON CONNECTION REMAINS
IMMERSED IN OIL AT ALL TIMES OR
AIR AND MOISTUREWILL BE DRAWN
INTO THE SYSTEM
2.Connect the suction connection of the gauge
manifold to the compressor suction service valve
port, and immerse the common connection of the
gaugemanifoldinan opencontainerofrefrigeration
oil. Refer to section 1.3.b. for oil specifications.
Removeair fromthe lines.Closethe gaugemanifold
valve.
3.Remove air from the lines.
4.With the unit running, frontseat (counterclockwise)
the suction service valve and pull a vacuum in the
compressor crankcase. Slowly crack the suction
gauge manifold valve and oil will flow through the
suctionservice valve intothe compressor.Add oilas
necessary.
4.12.2.3 Adding Oil to Service Replacement
Compressor
Service replacement compressors may or may not be
shippedwith oil.
Ifthe replacementcompressorisshippedwithoutoil,add
oil through the suction service valve flange cavity or by
removingtheoilfillplug.(SeeFigure4-8.)
step c., is above “Max” indication on compressor
crankcase,oil mustbe removedfromthe compressor
by performing the following procedure. If lowest oil
level visible is below “Min” indication, oil must be
added tothecompressor by following theprocedure
in section 4.12.2.2.
b.Closesuctionservicevalve(frontseat)andpumpunit
downt o 3to5 psig(21 to34kPa).Reclaimremaining
refrigerant.
CAUTION
!
NOTE
If oil drain plug is not accessible, it will be
necessary to extract oil through the oil fill plug
with a siphon tube.
c.Removethe oildrainplugonthe bottomplateofthe
compressoranddrain the properamount ofoilfrom
the compressor. Replace the plug securely back into
the compressor.
d.Repeat step a. to ensure proper oil level.
4.13 TEMPERATURE SENSOR CHECKOUT
a.An accurate ohmmeter must be used to check
resistance values shown inTable 4-1.
b.Due to variations and inaccuracies in ohmmeters,
thermometers or other test equipment, a reading
within two percent of the chart value would be
considered good. If a sensor is bad, the resistance
value would usuallybemuchhigher orlower thanthe
value given in the Table 4-1.
c.At least one sensor lead must be disconnectedfrom
the controllerbefore any reading can be taken. Not
doing sowill resultinafalse reading. Two preferred
methodsofdetermining the actualtest temperature
at the sensorare an ice bathat 32_F (0_C) and/ora
calibrateddigitaltemperature meter.
b.Tag and disconnect wiring from defective sensor or
transducer.
c.Remove and replace defective sensor or transducer.
d.Connectwiringtoreplacementsensorortransducer.
e.Checkout replacement sensor or transducer. (Refer
to section 4.13, 4.14 or 4.15, as applicable.)
f.Repair or replace any defective component(s), as
required.
4.16 Controller Configuration
When a controller is replaced it must be configured to
workinthemodelofunititisbeinginstalledin.Table4-3
shows the configuration jumpersettingsthatmustbe set
to correctly operate the Capri-280 SEPTA unit.
4-9T-283
Page 36
Table 4-3. Controller Configuration
ConfigurationDescriptionJumper
A.High Reheat --- When this configuration is removed the unit will default
REMOVED
to high speed in reheat mode and in the low speed cool band. If not
removed heat reheat will default to low speed.
B.High Vent --- When this configuration is removed the unit will default to
REMOVED
high speed in vent mode. If not removed vent mode will default to
low speed.
C.NAIN
D.Reheat/Cycle --- When the reheat cycle configuration is removed the
REMOVED
unit is in reheat mode. The default configuration is cycle clutch
mode.
E.Transducers --- When the transducer configuration is removed trans-
REMOVED
ducers will assumed to be present.
F.NAIN
G.Unit Type --- SEPTA unit enabled with G in and H removedIN
H.Unit Type --- SEPTA unit enabled with G in and H removedREMOVED
I.NANA
J.NAIN
K.Voltage - -- When this configuration is removed the voltage selection
REMOVED
will be changed from 12 to 24V DC.
L.NAREMOVED
M.NAIN
N.C/F --- When this configuration is removed the display will show
REMOVED
temperatures in F. When not removed the display will show temperature in C.