Carrier CAPRI-280 Operation And Service Manual

Page 1
Bus Air Conditioning Equipment
Model CAPRI-280 Septa
T-283
Page 2
OPERATION AND
BUS
AIR CONDITIONING
UNIT
Model CAPRI-280
Carrier T ransicold Division, Carrier Corporation,P.O. Box 4805, Syracuse, N.Y. 13221
Carrier Corporation 1997 D Printed in U. S. A. 1097
Septa
Page 3
TABLE OF CONTENTS
Section Page
SAFETY SUMMARY 1.......................................................
1DESCRIPTION 1-1............................................................
1.1 Introduction 1-1...............................................................
1.2 General description 1-2........................................................
1.2.1 Condenser Unit 1-2...................................................
1.2.2 Evaporator Unit 1-3...................................................
1.2.3 Compressor Assembly 1-4.............................................
1.3 Refrigeration System Component Specifications 1-4...............................
1.4 Electrical Specifications ECDC Motors 1-4........................................
1.5 Electrical Specifications --- Controller Input Sensors and Transducers 1-4.............
1.6 Safety Devices 1-4.............................................................
1.7 Air Conditioning Refrigerant Cycle 1-5............................................
1.8 Heater Flow Cycle 1-6..........................................................
1.9 Relay Board --- Electronically Commutated DC Motors with 2-speed Input Signal 1-7...
1.10 Logic Board 1-8...............................................................
1.11 Control Panel (Diagnostic Module) 1-9...........................................
2OPERATION 2-1..............................................................
2.1 Starting, Stopping and Operating Instructions 2-1.................................
2.1.1 HVAC Power to Controller 2-1..........................................
2.1.1 Starting 2-1..........................................................
2.1.3 Self-Test and Diagnostics (Check for Errors and/or Alarms) 2-1.............
2.1.4 Stopping 2-1.........................................................
2.2 Pre-Trip Inspection 2-1.........................................................
2.3 System Operation 2-1..........................................................
2.3.1 Temperature Control 2-1...............................................
2.3.1.1 Capacity Control 2-1........................................
2.3.1.2 Cooling/Reheat 2-3.........................................
2.3.1.3 Heating 2-3................................................
2.3.2 Boost Pump 2-3......................................................
2.3.3 Compressor Unloader Control 2-3......................................
2.3.4 Evaporator Fan Speed Selection 2-3....................................
2.3.5 Condenser Fan Speed Control 2-3......................................
2.3.6 Compressor Clutch Control 2-3.........................................
2.3.7 Alarm Description 2-4.................................................
2.3.8 Hour Meters 2-4......................................................
2.4 Microprocessor Diagnostic Service Tool (MDST) 2-4...............................
2.4.1 Connecting 2-4.......................................................
2.4.2 Control 2-4...........................................................
2.4.3 Setpoint Change 2-4..................................................
2.4.4 Mode Keys 2-4.......................................................
2.4.4.1 Cool 2-4...................................................
2.4.4.2 Heat 2-4...................................................
2.4.4.3 Vent 2-4...................................................
2.4.5 Fan Key 2-4..........................................................
i
Page 4
2.4.6 Temperature Key 2-4..................................................
2.4.7 Diagnostic Mode 2-4..................................................
2.4.8 System Parameters 2-5................................................
3 TROUBLESHOOTING 3-1......................................................
3.1 Self Diagnostics 3-1...........................................................
3.2 System Alarms. 3-1............................................................
4 SERVICE 4-1.................................................................
4.1 Maintenance Schedule 4-1.....................................................
4.2 Suction And Discharge Service V alves 4-1........................................
4.3 Installing Manifold Gauges 4-1..................................................
4.4 Pumping The System Down Or Removing The Refrigerant Charge 4-2...............
4.4.1 System Pumpdown 4-2................................................
4.4.2 Removing the Refrigerant Charge 4-2...................................
4.5 Refrigerant Leak Check 4-2.....................................................
4.6 Evacuation And Dehydration 4-3................................................
4.7 Adding Refrigerant To System 4-3...............................................
4.7.1 Checking Refrigerant Charge 4-3.......................................
4.7.2 Adding Full Charge 4-3................................................
4.7.3 Adding Partial Charge 4-4..............................................
4.8 Checking For Noncondensibles 4-4..............................................
4.9 Checking And Replacing High Pressure Cutout Switch 4-4.........................
4.9.1 Checking High Pressure Switch 4-4.....................................
4.9.2 Replacing High Pressure Switch 4-4.....................................
4.10 Filter-drier 4-5.................................................................
4.11 Thermostatic Expansion Valve 4-5...............................................
4.12 Model 05G Compressor Maintenance 4-6........................................
4.12.1 Removing the Compressor 4-6.........................................
4.12.2 Compressor Oil Level 4-7..............................................
4.12.2.1 Checking the Compressor Oil Level 4-7........................
4.12.2.2 Adding Oil with Compressor in System 4-7.....................
4.12.2.3 Adding Oil to Service Replacement Compressor 4-8............
4.12.2.4 Removing Oil from the Compressor 4-8........................
4.13 Temperature Sensor Checkout 4-8...............................................
4.14 Suction And Discharge Pressure Transducer Checkout 4-8.........................
4.15 Replacing Sensors and Transducers 4-9.........................................
4.16 Controller Configuration 4-19.....................................................
ii
Page 5
5 ELECTRICAL 5-1.............................................................
5.1 Introduction 5-1...............................................................
LIST OF ILLUSTRATIONS
Figure Page
1-1. A/C Component Identification 1-1...............................................
1-2. Condenser Unit 1-2............................................................
1-3. Evaporator Unit 1-3............................................................
1-4. Heater Flow Diagram 1-6.......................................................
1-5. RelayBoard 1-7...............................................................
1-6. Logic Board 1-8...............................................................
1-7. DiagnosticModule 1-9.........................................................
2-1. Auto Reheat Mode 2-2.........................................................
4-1. Suction or Discharge Service Valve 4-1...........................................
4-2. Manifold Gauge Set 4-2........................................................
4-3. Checking High Pressure Switch 4-4..............................................
4-4. Thermostatic Expansion Valve 4-5...............................................
4-5. Thermostatic Expansion Valve Bulb and Thermocouple 4-5.........................
4-6. Removing Bypass Piston Plug 4-7...............................................
4-7. Model O5G Compressor 4-7....................................................
5-1. Electrical Wiring Schematic Diagram 5-2.........................................
LIST OF TABLES
Table Page
2-1. Main Evaporator Fan Speed Relay Operation 2-3..................................
2-2. ParameterCodes 2-5..........................................................
3-1. Error Codes 3-1...............................................................
3-2 Alarm Codes 3-2..............................................................
3-3. General System Trouble Shooting Procedures 3-4.................................
4-1. Temperature Sensor (AT, TSC, TSD and TSR) Resistance 4-8.......................
4-2. Suction and Discharge Pressure Transducer (SPT and DPT) Voltage 4-9.............
4-3. Controller Configuration 4-10.....................................................
4-4. R-134a Temperature - Pressure Chart 4-11.........................................
iii
Page 6
SAFETY SUMMARY
GENERAL SAFETY NOTICES
Thefollowinggeneralsafetynoticessupplementthe specificwarningsand cautionsappearingelsewherein this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. The general safety notices are presented in the followingthree sectionslabeled:First Aid,OperatingPrecautionsand MaintenancePrecautions.Alisting ofthespecific warningsandcautions appearingelsewhereinthe manualfollows thegeneralsafetynotices.
FIRST AID
An injury, no matter howslight, shouldnevergo unattended. Alwaysobtain first aid or medicalattention immediately.
OPERATING PRECAUTIONS
Always wear safety glasses. Keep hands, clothing and toolsclear of the evaporator and condenser fans. Noworkshouldbeperformedonthe unituntilallcircuitbreakersand start-stopswitchesareturnedoff,and
power supply is disconnected. Always work in pairs. Never work on the equipment alone. In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
Beware of unannounced starting of the evaporator and condenser fans. Do not open the condenser fan grilleor evaporatoraccesspanelsbeforeturningpoweroff,anddisconnectingandsecuringthe powerplug.
Be sure power is turned off before working on motors, controllers, solenoid valvesand electrical control switches. Tag circuit breaker and power supply to prevent accidental energizing of circuit.
Do not bypass any electricalsafety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems with the systemshould be diagnosed, and any necessaryrepairs performed, by qualified service personnel.
When performingany arc weldingonthe unit,disconnectallwire harness connectors fromthemodules in the controlbox.Donotremove wire harness from the modulesunless you aregroundedto the unit frame with a static-safe wriststrap.
In case of electrical fire, open circuit switch and extinguish with CO
(never use water).
2
1
Page 7
SECTION 1
DESCRIPTION
1.1 INTRODUCTION
ThismanualcontainsOperating andService Instructions and Electrical Data for the Model Capri 280 Air Conditioning and Heating equipment furnished by Carrier Transicold Division.
The Capri 280 consists of a condenser, evaporator and
3
2
1
compressor.The airconditioningandheatingequipment interfaces with electrical cabling, refrigerant piping, engine coolant piping for heating, ductwork and other components furnished by the bus manufacturer to completethesystem.
7645
8
9
Figure 1-1. A/C Component Identification
1. Compressor
2. Pressure Switches
3. Electrical Control and Relay Board
4. Evaporator Section
5. Evaporator Blowers and Motors
6. Condenser Axial Fan/Motor Assemblies.
7. Condenser Section
8. Main Harness
9. Power Harness
10. Alternator
11. Power Relay
1-1
T-283
Page 8
1.2 General description
1.2.1 Condenser Unit
The condenser unit includes condenser coils, fan and motor assemblies, filter-drier, receiver, liquid line solenoidvalve,kingvalves, discharge check valve, andan ambient temperaturesensor.
The condenser coils provide a heat transfer surface for condensing refrigerant gas at a high temperature and pressure into a liquidat high temperature and pressure. The condenser fans circulate ambient air across the outside of the condenser tubes at a temperature lower than refrigerant circulating inside the tubes; this results in condensing the refrigerant into a liquid. The filter-drierremovesmoisture andothernoncondensibles from the liquid refrigerant before it enters the thermal expansion valves in the evaporator assembly.
The receiver collects and stores liquid refrigerant. The receiver is fitted with upper and lower liquid level sight glasses to enable determining refrigerant liquid level in thereceiver. Thereceiverisalsofitted witha fusibleplug which protects the system from unsafe high refrigerant temperatures. Themain liquid linesolenoid valvecloses whensystemisshutdowntopreventfloodingofcoils with liquid refrigerant and to isolate the filter-drier for servicing when the compressor is shut down. The king valves enable servicing of the filter-drier. The ambient temperature sensormeasures ambient temperature and sends an electrical signal to the controller.
The discharge line check valve is a spring loaded, normally closed valve that opens with the flow of refrigerant from the compressor. When the compressor clutchisdisengaged,the discharge checkvalvewill close, preventing the flow of high pressure liquid from the condenser to flow back into the compressor.
1. Condenser Coil
2. Condenser Fan Motor Assembly
3. Receiver Tank
4. Service Valve
5. Filter Drier
6. Liquid Hose
7. Gas Hose
8. Condenser Motor Harness
9. Condenser Motor Plate
10. Lid Screw Nut
11. Locking Screw Gasket
12. Lid Bolt Support
T-283
Figure 1-2. Condenser Unit
13. Square Nut
14. Locking Screw Gasket
15. Right Front Grille
16. Left Front Grille
17. Right Front Lateral Grille
18. Left Front Grille
19. Right Rear Lateral Grille
20. Left Rear Lateral Grille
21. Condenser Fiberglass Base
22. Condenser Top Cover Lid
23. Liquid Line Solenoid Valve
24. Receiver Tank Support
1-2
Page 9
1.2.2 Evaporator Unit
The evaporator unit includes roadside and curbside evaporator coils.
Each evaporator unit includes six fan and motor assemblies, evaporator/heater coil assemblies, thermal expansion valves, condensate drain connection(s), and evaporator heat valve.
The evaporator coils provide a heat transfer surface for transferring heat from air circulating over the outside surface of the coil to refrigerant circulating inside the tubes;thusprovidingcoolingwhenrequired.Theheating
coilsprovideaheat transfer surfacefortransferringheat fromengine coolantwater circulating insidethetubes to air circulating overtheoutside surfaceofthe tubes,thus providing heating when required. The fans circulate the air over the coils. The air filtersfilter dirt particlesfrom the air before the air passes over the coils. The thermal expansion valves meter the flow of refrigerant entering the evaporator coils. The heat valve controls the flow of engine coolant water supplied to the heating coils upon receipt of a signal from the controller. The condensate drainconnectionsprovide ameans forconnecting tubing for disposing of condensate collected on the evaporator coilsduring cooling operation.
1. Evaporator Coil, Roadside
1a. Evaporator Coil, Curbside
2. Expansion Valve
3. Evaporator Blower and Motor
3a. Allen Screw
4. Humidity Sight Glass
5. Return Air Filter
6. Liquid Line
7. Relay Board
8. Logic Board
Figure 1-3. Evaporator Unit
10. Discharge Line
11. Heating Line
12. Evaporator Motor Harness
13. Lid Screw --- Stopper
14. Locking Screw Gasket
15. Lid Bolt Support
16. Square Nut
17. Lid Locking Screw
1-3
9. Suction Line
T-283
Page 10
1.2.3 Compressor Assembl y
The compressor assembly includes the refrigerant compressor, clutch assembly, suction and discharge service valves, high pressure switch, low pressure switch, suction and discharge servicing (charging) ports and electricsolenoid unloaders.
The compressor raises the pressure and temperature of the refrigerant and forces it into the condenser tubes. The clutch assembly provides a means of belt drivingthe compressorby thebusengine. Thesuctionand discharge servicevalvesenableservicingofthecompressor.Suction anddischarge servicing(charging)portsmountedonthe service valves enable connection of charging hoses for servicing of thecompressor, as well as otherpartsofthe refrigerant circuit. The high pressure switch contacts open on a pressure rise to shut down the system when abnormallyhighrefrigerant pressuresoccur.Theelectric unloaders provide a means of controlling compressor capacity,whichenablescontroloftemperatureinsidethe bus. For more detailed information on the compressor, refer to manual number 62-02756.
1.3 REFRIGERATION SYSTEM COMPONENT SPECIFICATIONS
a. Refrigeration Charge
R-134a: 11.3 lb (5.1 kg)
b. Compressor
Model: 05G No. of Cylinder: 6 Weight (Dry): 165 lb (75 kg) Oil Charge:
New Compressor: 6.75 pints (3.2liters) Replacement Compressor:5.5 pints (2.6 liters)
Oil Level:
Levelinsightglassbetween Min.---Maxmarkson compressor crankcase (curbside)
Approved Compressor Oils - R-134a:
Castrol: Icematic SW68C Mobil: EALArctic 68 ICI: Emkarate RL68H
c. Thermostatic Expansion Valve - for R-134a
Units:
Superheat Setting(Non-externallyadjustable): 10
to 12_F
MOP Setting (Nonadjustable): 55 4psig(375
28.5 kPa)
d. High Pressure Switch (HPS) - for R-134a
Units:
Opens at: 300 10 psig Closes at: 200 10 psig
1.4 ELECTRICAL SPECIFICATIONS ECDC MOTORS a. Evaporator/Heater Blower (Fan) Motor
FullLoad Amps (FLA): 8.4A Horsepower:0.34 Voltage:24vdc Operating Speed: 4375 rpm
b. Condenser Fan Motor
Bearing Lubrication: Shell Dolium R Horsepower:0.15hp FullLoad Amps (FLA): 7A Operating Speed: 3180 rpm Voltage:24vdc
1.5 ELECTRICAL SPECIFICA TIONS -­Controller Input Sensors and Transducers
a. Suction and Discharge Pressure Transducer
Supply Voltage: 4.5 to 5.5 vdc (5 vdcnominal) Supply current: 8 mA maximum Output Range: 8K ohms minimum InputRange: ---6.7to450psig(---46.2kPa to 3.1 mPa) Output Current: -1.5 mA minimum to
1.5 mA maximum
Output Voltage: vdc = 0.0098 x psig
+ 0.4659 (Se e Table 4-2 for calculations.)
b. Temperature Sensors
Input Range: ---52.6 to 158_F(---47 to 70_C) Output: NTC 10K ohms at 77_F (25_C) (See Table 4-1 for calculations.)
1.6 SAFETY DEVICES
System components are protected from damage caused byunsafeoperatingconditionswithsafetydevices.Safety devices with Carrier Transicold supplied equipment include high pressure switch(HPS), low pressure switch (LPS), circuit breakersand fuses.
a. Thermal Switches
Condenser Motor Overloads
Each condenser fan motor is equipped with an internal thermalprotector switch, condensermotor overloads. If excessivemotortemperatureexists,thecondensermotor overload switch will open to de-energize the corresponding condenser fan.
Evaporator Motor Overloads
The evaporator fan motors are equipped with internal thermal protector switches. If excessive motor temperature exists, the switch will open to de-energize the corresponding evaporator fan; this will prevent the affected evaporator motor fromoperating.
T-283
1-4
Page 11
b. Pressure Switches
High PressureSwitch (HPS)
During the A/C mode, HVAC system operation will automaticallystopiftheHPSswitchcontactsopen dueto an unsafe operating condition. Opening HPS contacts de-energizes,throughthecontroller,theA/Ccompressor clutchand condenserfanmotor relaysshutting downthe system.
The high pressure switch (HPS)isinstalledinthecenter head of the compressor and opens on a pressure rise to shut down the system when high pressure conditions occur. For R-134a systems, the switch is factory set to open at 300 10 psig and close at 200 10 psig.
Low Pressure Switch (LPS)
Thelowpressureswitchisinstalled inthecompressorand opensona pressuredrop toshutdownthesystemwhena low pressure condition occurs. For R-134a systems, the switchisfactorysetto openat63psig.In addition,ifthe control monitors a pressure less than 10 psig by the suction pressure transducer mounted in the evaporator section, the system will be shut down for at least one minute.
c. Fuses and Breakers
All outputs from the relay board are protected against high current by circuit breakers. Independent 15 amp circuitbreakersprotecteachmotor.Inaddition,a 15amp fuse protects a motor from over current. During a hi gh current condition, the breaker or fuse may open. When the breaker opens, power will be removed from the device and a breaker alarm will be generated. When a fuseopens, groundwillbe removedfromthedevice anda motor alarm will be generated.
d. Ambient Lockout
The ambient temperature sensor located in the condenser section measures the condenser air temperature.Whenthetemperatureislessthan45F, the compressorislocked outuntilthe temperature increases above 50F to prevent compressor damage.
system using R-134a as a refrigerant. The main components of the system are the reciprocating compressor, air-cooled condenser coils, receiver, filter-drier, thermostatic expansion valves, liquid line solenoid valve and evaporator coils.
The compressorraisesthe pressure and thetemperature of the refrigerant and forces it into the condenser tubes. Thecondenserfan circulatessurrounding air(whichis at a temperature lower than the refrigerant) over the outside of the condenser tubes. Heat transfer is established fromthe refrigerant (insidethe tubes)tothe condenser air (flowing over the tubes). The condenser tubeshavefinsdesignedtoimprovethetransferofheat from the refrigerant gas to the air; this removal of heat causes the refrigerant to liquefy, thus liquid refrigerant leaves the condenserandflows to the receiver.
The receiver serves as a liquid refrigerant reservoir so that a constant supply of liquid is available to the evaporatorsasneeded, and acts asastorage spacewhen pumping down thesystem.The receiverisequippedwith sightglassesto observethe refrigerantfor restrictedflow and correct charge level.
The refrigerant leaves the receiver and passes through the receiver outlet/service valve, through a filter-drier where an absorbent keeps the refrigerant cleananddry.
Fromthe filter-drier, the liquid refrigerant then flowsto the thermal expansion valves which reduce pressure and temperature of the liquid and meters the flow of liquid refrigerant to the evaporator to obtain maxi mum use of the evaporator heat transfer surface.
The lowpressure,lowtemperature liquid that flowsinto the evaporator tubes is colder than the air that is circulated over the evaporator tubes by the evaporator blower (fan). Heat transfer is established from the evaporatorair (flowingover thetubes) tothe refrigerant (flowing inside the tubes). The evaporator tubes have aluminum fins to increase heat transfer from the air to the refrigerant; therefore the cooler air is circulated to the interior of the bus. Liquid line solenoid valvesclose during shutdown to prevent refrigerant flow.
1.7 AIR CONDITIONING REFRIGERANT CYCLE
When air conditioning (cooling) is selected by the controller, the unit operates as a vapor compression
The transfer of heat from the air tothelowtemperature liquid refrigerant in the evaporator causes the liquid to vaporize. This low temperature, low pressure vapor passes through the suction line and returns to the compressor where the cycle repeats.
1-5
T-283
Page 12
Figure 1-4. Heater Flow Diagram
1.8 HEATER FLOW CYCLE
Heating circuit components furnished by Carrier Transicold include heater cores and evaporator heat valves for each evaporator assembly. Components furnished by the bus manufacturer include auxiliary heater and engine water pumps. The controller automaticallycontrolsthe heatvalvesduringheatingand
T-283
reheat cycles to maintain required temperatures inside the bus. Engine coolant (glycol solution) is circulated through the heating circuit by the engine and auxiliary waterpumps. Whenthe evaporator heat valvesolenoid isenergized,thevalvewillopentoallowengine coolantto flowthrough theheater coil(see Figure 1-4).Thevalveis normallyclosedso thatifafailureoccurs,it willbe ableto cool.
1-6
Page 13
1.9 Relay Board -- Electronically Commutated DC Motors with 2-speed Input Signal
+
13
K1
1
K3
2
K2
D2 D6 D14 D17 D26 D37 D38 D41
---
EF2 EF1
4
EF3 EF4
3
K4
5 6
D81
EF HIGH SIGNAL
EF6 EF5
K7
K8
10
7 8 9
K6
CF2 CF1
CF2 CF2
K9
K10
K24 K22 K21 K23
11
12
D85
CF
HIGH
SIGNAL
CF6 CF5
Figure 1-5 Relay Board
K14
K16 K18
K19
JP1
K15
K17 K20
K13
JP6
JP5
JP4
JP3
D57 D54 D63 D60 D72 D66 D51 D69
JP2
a. Relays
K1 Energizes evaporator fans 1 & 2. K2 Energizes evaporator fans 3 & 4. K3 Energizes evaporator fan 5. K4 Energizes evaporator fan 6. K5 Provides the evaporator fan high output
signal.
K 6 Provides the condenser fan high output
signal. (Not used). K 7 Energizes condenser fans 1 & 2. K 8 Energizes condenser fans 3 & 4. K9 Notused K10 Not used K13 Energizes the A/C clutch. K14 Energizes unloader 1. K15 Energizes unloader 2. K16 Energizes the high low pressure failure. K17 Energizes the heat solenoid valve. K18 Energizes the alarm output. K19 Energizes the booster pump. K20 Energizes the motor fail light.
b. Thermal Circuit Breakers 24V
CB 1 Evaporator fan #1. 15 Amp. CB 2 Evaporator fan #2. 15 Amp. CB 3 Evaporator fan #3. 15 Amp. CB 4 Evaporator fan #4. 15 Amp. CB 5 Evaporator fan #5. 15 Amp. CB 6 Evaporator fan #6. 15 Amp. CB 7 Condenser fan #1. 15 Amp. CB 8 Condenser fan #2. 15 Amp. CB 9 Condenser fan #3. 15 Amp. CB10 Condenser fan #4. 15 Amp. CB11 Spare. 15 Amp. CB12 Spare. 15 Amp. CB13 A/c clutch, unloaders 1&2
motor fail, heat valve, pressure fail
&spareoutput. 15Amp.
c. Connectors
EF1-EF6 Evaporator Fans. CF1-CF4 Condenser Fans. JP1 External evaporator & condenser fan
thermal overload connections. JP2 Logic board connector. JP3 Booster pump. JP4 A/C Clutch, Pressure fault output,
Compressor High Pressure Switch. JP5 High pressure fail, motor fail output,
heat valve. JP6 Unloaders 1 & 2. EF-HIGHSIGNAL Output to the evaporator
fans to operate on high speed.
CF-HIGH SIGNAL Output to condenser fans to
operate on high speed. (Not used)
d. LEDS
D 2 Evaporator fans 1 & 2 are energized. D 6 Evaporator fans 3 & 4 are energized. D14 Evaporator fan 5 is energized. D17 Evaporator fan 6 is energized. D26 Condenser fans 1 & 2 energized. D30 Condenser fans 3 & 4 energized. D38 Condenser fans 5 & 6 energized. (Not used). D51 A/C clutch output active. D54 Unloader 1 output active. D57 Unloader 2 output active. D60 High low pressure failure. D63 Heat valve output active. D66 Alarm output active. D69 D72 Motor fail light. D81 Evaporator fans on high. D85 Condenser fans on high. (Not used).
1-7
T-283
Page 14
1.10Logic Board
J1 Logic board power in. J2 Display interface. J3 Manual control inputs. J4 Interlock Inputs
(WTS, low side pressure switch etc.) J5 Relay board interface. J6 Sensor inputs (Thermistors, etc.).
T-283
Figure 1-6 Logic Board
J7 Diagnostics interface (RS232, DB9). D2 Blinks once per second in normal operation.
On steady to indicate alarms detected.
D3 Off In normal operation, blinks out alarm
codes (2 digits each) when alarms detected.
1-8
Page 15
1.11Control Panel (Diagnostic Module)
12
3
5
6
4
7
91011
8
1. Display
2. Down --- decrease selection
3. Up --- increase selection
4. Ventilation
5. Auto Control Selection
6. Air Conditioning
Figure 1-7. Diagnostic Module
7. Heating
8. Fan Speed Selection
9. Not used
10. Temperature Inside / Outside
11. Turn On / Turn Off
1-9
T-283
Page 16
SECTION 2
OPERATION
2.1 STARTING, STOPPING AND OPERATING INSTRUCTIONS
2.1.1 HVAC Power to Controller
Before starting the system, electrical power must be available from the bus power supply. The HVAC controller receives power from two sources:
a. 24 vdc power for the microprocessor electronics
is supplied throughthebusmultiplexmodule.
b. 24vdc, 125amp,powerfrom afuse inthe battery
compartment supplies power which controls relays, clutch and unloader solenoids in the compressor, evaporator and condenser assemblies; thispower iscontrolledbythe HVAC controller.
2.1.2 Starting
a. If the engine is not running, start the engine.
After the engine is started place the A/C switch locatedonthedashin theonposition. All system controls will operate automatically in heating, cooling or ventilating mode, as required.
2.1.3 Self-Test and Diagnostics
(Check for Errors and/or Alarms)
Self-test of the main controller electrical circuit is automatically initiated when the system is first powered up. If there is an error in the circuit, ER‘‘x” willbeindicatedbyflashingtheerrorcodeonboththe statusandcodeLED’ssimultaneously. Ifadiagnostic module is connectedtothe controller, the error code canalsobe readonthe display. Ifthereare noerrors in the circuit, system will operate normally and flash the status LED at a one second interval. During normal operation, the controller monitors system operating parametersfor outoftolerance conditions. If an out of tolerance condition occurs, ALARM will be indicated through the code LED or on the diagnostic tool display. If an alarm condition exists, diagnosticscanbemanuallyinitiatedtoisolatesystem fault(s) by simultaneously pressing the up and down keys continuously for five seconds to view more
information. Refer to section 3 for definition of systemerrorsandalarmsandgeneraltroubleshooting procedures.
2.1.4 Stopping
Withthesystemoperating,switching theACswitchto the offposition will stoptheHVAC systemoperation by removing power to the logic module.
2.2 PRE-TRIP INSPECTION
After starting system operation, allow system to stabilize for ten to fifteen minutes and check for the following:
a. Listen for abnormal noises in compressor or fan
motors.
b. Check compressor oil level. (Refer to section
4.12.2.) c. Check refrigerant level. (Refer to section 4.7.1.) d. Ensure that self-test has been successfully
performedand thatthereare noerrors oralarms indicated. (Referto section 2.1.7.)
2.3 SYSTEM OPERATION
2.3.1 Temperature Control
Temperature is controlled by maintaining the return air temperature measured at the return air grille.
2.3.1.1 Capacity Control
The controller automatically compares system temperatures with the controller setpoints and changes system operating modes at certain temperature deviations. Figure 2-1 shows various changes in operating modes and controller actions at various temperature deviations from controller setpoint. Upon rising temperature, mode changes occur when temperatures are above those given in Figure 2-1 above controller setpoints, On a falling temperature, mode changes occur when temperaturesarebelowthosegiveninFigure2-1.The system will operate in these modes unless pressures override the controller settings.
T-283
2-1
Page 17
Cool
High Speed
Loaded
Cool
High Speed
4 Cylinders
Cool High Speed 2 Cylinders
Reheat High Speed 2 Cylinders
T-283
Heat
Low Speed
Heat
High Speed
Figure 2-1. Auto Reheat Mode
2-2
Page 18
2.3.1.2 Cooling/Reheat
Cooling and reheat require various combinations of compressor unloading. Cooling is accomplished by energizing the compressor and condenser fans, opening the liquid solenoid valve and closing the heating valve. Reheat opens the heat valve while cooling. This allows for reduced capacity around setpoint and de-humidification.
2.3.1.3 Heating
Duringheating,theliquidsolenoidisclosedtostop cooling and the compressor and condenser fans will shut down. The fan speed will vary based on the temperature difference from setpoint. Heating will notstartuntil theenginecoolant switch(ECS)closes. The ECS is located on the block of the vehicle andis provided by the OEM. It senses the engine coolant temperature. The switch closes at 105Fon temperature rise.Theswitch prevents thecirculation of cooler air throughout the vehicle during initial start-up.
2.3.2 Boost Pump
When the unit is in heat the boost pump relay is energized. This signal is read by the bus multiplex system to activate the boost pump.
2.3.3 Compressor Unloader Control
The unloader outputs control the capacity of the compressor by energizing or de-energizing unloader solenoid valves. Energizing a valve solenoid de-activates a pair of compressor cylinders. The Model 05G compressor has six cylinders. Four cylinders are equipped with two sets of unloader valves (UV1 and UV2), each controlling two cylinders; this allows the compressor to be operated withtwo,fourorsixcylinders.Whenthecompressoris off, the unloaders are de-energized immediately.
Whenever the compressor is changed from off to on, the unloaders are forced energized for fifteen seconds. After fifteen seconds, one unloader may be de-energized, if required. Any subsequent changes between energizing and de-energizing theunloaders must be staged with a two second delay. Only one unloader may change state at a time when staging is required.
secondcompressorcylinderbank(twocylinders); this output will remain energized until the pressure increases to above31psig.
b. Discharge Pressure
Head Pressure is also controlledby the unloaders:
1. CompressorUnloaderUV1Relay.
When the discharge pressure increases above 275 psig, the first compressor unloader is energized; this output will remain energized until the pressure decreases below 220 psig. Staging is ignored for energizing the unloader due to discharge pressure overrides.
2. CompressorUnloaderUV2Relay.
When the discharge pressure increases above 285 psig, the second unloader is energized; this output will remain energized until the pressure decreases below 225 psig.
2.3.4 Evaporator Fan Speed Selection
Each air conditioning unit is equipped with six two speedfan motors.Temperaturecontrolis theprimary method of determining the fan speed selection. The following table indicates relay operational status for the various fan motor states.
Table 2-1. Main Evaporator Fan Speed
Relay Operation
STATE
HIGH
SPEED
EVAP FAN
RELAYS
RELAY
Off Off Off
Low Off On
High On On
Theevaporatorfans wills tart in lowspeed andrunin high speed for cool and reheat modes. During heat modethe fanswill runin eitherhighorlowspeed(see figure 2-1).
Exceptions to the above are as follows:
a. In the event that the coolant temperature switch
is open, the evaporator fans are kept off during heating.
a. Suction Pressure
In addition to temperature control, the electric unloaders will be used to preventcoil frosting:
1. CompressorUnloaderUV1Relay. suctionpressuredecreasesbelow26psig,thefirst unloader is energized unloading the first compressor cylinder bank (two cylinders); this output will remain energized until the pressure increases to above 34 psig.
2. CompressorUnloaderUV2Relay. suction pressure decreases below 23 psig, the second unloader is energized unloading the
T-283
When the
When the
2.3.5 Condenser Fan Speed Control
The condenser fans are energized when the compressor clutch output isenergized. Thefanswill also be activated if a high pressure alarm has been activated and operation has not been locked out (refer to table3-3).
2.3.6 Compressor Clutch Control
A belt driven electric clutch is employed to transmit engine power to the air conditioning compressor. De-energizing the clutch electric coil disengages the clutch and removes power fromthecompressor. The clutchwillbeengagedwhenin cooling.Theclutchwill
2-3
Page 19
bedisengagedwhen thesystem isoff,wheninheating or during high andlowpressure conditions.
The clutch coil is prevented from engagement when the ambient temperature is below 45_F (7.2_C).
The clutch coil will be de-energized if the discharge pressure rises to 300 psig, the setting of the compressormountedhighpressureswitch.Theclutch coil willenergizewhen thedischargepressure falls to 200 psig.
The clutch coil will be de-energized if the suction pressure decreases below10 psig.
b. Connect theMDSTtothe service port locatedin
the return air section. c. Unplug the logicboardconnector J3. d. Turn the A/C main switch located in the driver’s
area back to the ON position. e. Activatethesystembypressingthe1/0 keyon the
MDST panel.
NOTE
Be sure to reconnect J3 when testing is
completed or the system will fail to operate
when the MDST is disconnected.
2.3.7 Alarm Description
Alarm descriptions and troubleshooting procedures are provided in section 3.
2.3.8 Hour Meters
An hour meter records the compressor run time hours. The maximumhours is 999,999. (Refer to table 3-2)
Anhourmeter recordsthetotal timetheevaporators are on in hours. The maximum hours is 999,999. (Refer to table 3-2)
2.4 MICROPROCESSOR DIAGNOSTIC SERVICE TOOL (MDST)
TheMDSTis adiagnostic servicetool that allowsthe user to interface with the microprocessor based control. This allows system parameters, alarms and settings to be viewed and modified.
2.4.1 Connecting
Connect the MDST harness to the service port located in the return air section of the A/C system. WhentheMDSTisconnected, thepanel lightswillbe energized and the currently stored setpoint will be displayed. If any alarm is active, the reading will be Axx, where A indicates that the alarm is active and xx indicates the alarm number.
2.4.2 Control
2.4.3 Setpoint Change
Setpoint may be changed by pressing up or down arrow keys. The up key will increase the setpoint temperature and the down key will decrease the setpoint temperature.
NOTE
When modifying the setpoint temperature for diagnostic purposes, be sure to reset the setpoint when testing is complete.
2.4.4 Mode Keys
The mode keys allow the operation tobe selected as auto,cool, heat,orvent.Thedefaultoperationisauto asshowninFigure2-1.
2.4.4.1 Cool
The compressor is always operational in cool mode unless overridden by safety device. Air conditioning willrununtilsetpointisreachedatwhichtimetheheat valve will open and reheatis performed.
2.4.4.2 Heat
The compressor will not operate in heat mode. The heatvalveis openeduntil1_Fbelowsetpointatwhich timethe heatvalve closesandthe evaporatorfans run in ventilation.
2.4.4.3 Vent
In vent mode, only the evaporator fans operate.
NOTE
This procedure should be performed by an HVAC educated technician who knows the Carrier Capri 280 system design. Control configuration is preset in by the manufacturer and resetting of the parameters should not be required. It is recommended that Carrier Service or Engineering is contacted before anycontrol configuration is changed. Carrier can not be responsible for changes made by the customer whichcause system failure if there has not been an opportunity to approve the changes.
a. Turn the A/C main switch located in the driver’s
area to OFF.
T-283
2.4.5 Fan Key
The fan key allows the evaporator fan speed to be overridden to high or low. Theevaporator fan speed willberesettoautowhenautomodekeyispressed.
2.4.6 Temperature Key
The temperature key allows the actual return air ambient temperatures to be displayed.
2.4.7 Diagnostic Mode
Diagnostic mode can be entered by pressing the up and down arrow keys simultaneously for 5 seconds. Diagnostic mode allows alarms and system parameters to be viewed. If there are any alarms stored, the most recent alarm will beshown. To view additionalalarm information,refer tosection3. Press the up and down arrow keys to view parameters.
2-4
Page 20
2.4.8 SYSTEM PARAMETERS
again indicate the setpoint setting. The parameters
are shown in Table 2-2. When scrolling through the Pressingthe up/downarrowkeyswillallowtheuser to scrollup ordown throughthe parameters.If nokey is pressed for30secondsthismodeisexitedandthe displaywillrevertbacktosetpoint.Pressingtheon/off key any time will exit this mode and the display will
parameters, thecurrent parameter parameterwillbe
displayed for two seconds. After two seconds, the
display will show the data for the currentparameter.
When the last parameter is reached, the next
parameter will wrap back to one.
Table 2-2. Parameter Codes
CODE CODE NAME DESCRIPTION
P1 Return Air Temperature This value is the temperature measured by the return air sensor. If the sensor
P2 Coil Temperature This value is the coil temperature measured by the evaporatortemperature
P3 Ambient Temperature This value is the outside temperature measured by the ambient temperature
P4 Suction Line Tempera-
ture (not used)
P5 Suction Pressure This value is the suction pressure measured by the suction pressure transduc-
P6 Discharge Pressure This value is the discharge pressure measured by thed ischarge pressure
P7 Superheat(notused) Not used. P8 Analog Setpoint Tem-
perature (not used)
P9 A/C Control Window #1 This is the number of degrees F above setpoint at which theunloaders will be
P10 A/C Control Window #2 This is the number of degrees F above AC control window one at which the
P11 A/C Control Window #3 This is the number of degrees F above AC control window two at which the
P12 Heat Control Window This is the number of degrees F below setpoint before the heat valve is ener-
P13 Compressor Safety Off
Delay
P14 Fan Delay This is the minimum time (in seconds) that the fans must run at a particular
is shorted it will display CL. If it is open circuited it will display OP.
sensor. If the sensor is shorted it will display CL. If it is open circuited it will display OP.
sensor. If the sensor is shorted it will display CL. If it is open circuited it will display OP.
Not used.
er. If the sensor is shorted it will display CL If it is open circuited it will display OP. If the auto key is pressed and held for five secondsthe suction pressure will be calibrated to zero and the offset will be stored in no-volatile memory. This calibration will be locked out if the offset is greater than 20 or lessthan
6.7 or if the clutch output is energized.
transducer. If the sensor is shorted it will display “CL” and if it is open circuited it will display “OP”. If the auto key is pressed and held for five seconds the suction pressure will be calibrated to zero and the offset will be stored in non-volatile memory. This calibration will be locked out if the offset is greater than 20 or less than 6.7 or if the clutch output is energized.
Not used.
both energized. This value can be modified between 0 and 10 degrees F. The default value is 1 degree F.
first unloader will be energized. This value can be modified between 0 and 10 degrees F. The default value is 1 degree F.
evaporator fan speed will be set to low. This value can be modified between 0 and 10 degrees F. The default value is 1 degree F.
gized. This value can be modified between 0 and 10 degreesF. The default value is 2 degree F for heat and 4 degrees F for reheat.
This number is the minimum timeinminutes that the compressor must be off after a high or low pressure alarm before it can be restarted. This value can be modified between one and five minutes. The default value is 1.
speed before changing to another speed. This value can be modified be­tween one and 60 seconds. The default value is two seconds.
T-283
2-5
Page 21
Table 2-2. Parameter Codes --- Continued
Code Code Name Description
P15 Unloader/Heat Valve
Delay
P16 Compressor Head Pres-
sure Switch
P17 Condenser Fan Speed
Switch (not used)
P18 Maximum Setpoint This is the maximum value that the operatorwill be allowed to set the setpoint
P19 Minimum Setpoint This is the minimum value that the operatorwill be allowed to set the setpoint
P20 Compressor Hours High This is the number of hours of operation that the compressor has run with the
P21 Compressor Hours Low Thisis the number of hours of operation that the compressor has run with the
P22 Evaporator Hours High This is the number (in thousands) of hours of operation with the evaporator
P23 Evaporator Hours Low This is the number (in hundreds, tens and ones) of hours of operation with the
P24 Maintenance 1 Hour
High
P25 Maintenance 1 Hour
Low
P26 Maintenance 2 Hours
High
P27 Maintenance 2 Hours
Low
P28 Freeze Alarm Setting This is the value at which the freeze alarm will be activated. The default value
P29 RelayModuleVoltage This is the voltage being supplied to the relay module. P30 Main Board Software
Version
P31 Display Software Ver-
sion P32 Ki Not used. P33 Kp Not used.
This is the minimum time (in seconds) that the unloaders and heat valve must be in a particular state (open /closed) before changingtoanother state. This value can be modified between 1 and 60 seconds. The default value is 2 sec­onds.
This is the current state of the compressorh ead pressure switch input. “CL” will be displayed if it is closed and “OP” will be displayed if it is open.
Not used.
temperature. The value can be modified in degreeswiththeup and do wn keys to a value between 60Fand80F.
temperature. The value can be modified in degreeswiththeup and do wn keys to a value between 60Fand80F.
clutch energized in thousands
clutch energized in hundreds, tens and ones.
fans energized.
evaporator fans energized. This is the value of compressor hours high (P20) at which maintenance alarm
#1 will be activated. This valuecan be modified by the up and down arrow keys. If both high and low values are zero the alarm is disabled.
This is the value of compressor hours low (P21) at which maintenance alarm #1 will be activated. This valuecan be modified by the up and down arrow keys. If both high and low values are zero the alarm is disabled.
This is the value of evaporator fan hours high (P22)at which maintenance alarm #2 will be activated. This value can be modified bythe up and down arrow keys. If both high and low values are zero the alarm is disabled.
This is the value of evaporator fan hours low (P23)at which maintenance alarm #2 will be activated. This value can be modified bythe up and down arrow keys. If both high and low values are zero the alarm is disabled.
is 32F. This value can be modified between 20Fand40F in one degree in- crements by using the arrow keys
This is the software version of the logicmodule.
This is the software version of the display module.
T-283
2-6
Page 22
SECTION 3
TROUBLESHOOTING
!
DO NOT UNDER ANY CIRCUMSTANCES ATTEMPT TO SERVICE THE MICROPRO­CESSOR. SHOULD A PROBLEM DEVELOP WITH THE MICROPROCESSOR, REPLACE IT.
3.1 SELF DIAGNOSTICS
Self testsareexecuted on powerupduring operation. Er­rors,ifany,willbeindicatedbythedisplayandtheunitwill notbe allowedto operate.Thedisplay willindicateerrors
Table 3-1. Error Codes
Code NAME DESCRIPTION
ER 1 Data Memory Logic board data memory failure. ER 2 Program Memory Logic board program memory failure. ER 3 A/D A/D and multiplexer failure. ER 4 Communication Failure Failure in communication between the logic board and MDST. ER 5 Program Memory Display program memory failure.
3.2 SYSTEM ALARMS a. Alarm codes
Alarms will be displayed by “AXX”, or “IXX” where“A” indicates thatthe alarm isactiveand “I”indicatesthat the alarmisinactive. Ifthe autokey is pressedthe displaywill scroll through the three digit hour meter readings. If multiple alarms are present the user can scroll through eachalarm bypressing theautokey. Whentheendofthe alarm lis t is reached the displa y will s how “--- --- --- ”. If the auto ke y is held d own f or five s econds while “ --- --- --- ” is displayed all inactive alarms are cleared.
with the code ER-X (X is the error number). The error codes can also be read by counting the number of times that the status and alarm LED’s flash simultaneously.
alarm is already present. Each alarm recorded will also have an evaporator hour meter reading corresponding to the activation time. When an alarm becomes inactive a statusindicator inthe alarmqueue willchange toindicate thatthe alarmis inactive.If anyalarms areactive thefault output will be energized.
c. Alarm queue
The alarm queue consist of10alarmlocations.Whenthe alarm queue is full an alarm will be generated but not stored toindicated this. Whenalarmsare viewed this will be the first alarm to be shown.
!CAUTION
b. Activation
When an alarm becomes active they will be placed in an alarm queueinthe order at whichthey initiate unless the
T-283
d. Alarm clear
TheusermayclearinactivealarmsthroughtheMDST keypad or computer communications.
3-1
Page 23
Table 3-2. Alarm Codes
ALARM
NO.
11 Coil Freeze Coil temperature is less
12 High Voltage Thebatteryvoltageis
13 Low Voltage Thebatteryvoltageis
14 Return Air Probe Failure Return air temperature
15 Suction Pressure
Transducer Failure
16 Discharge Pressure
Transducer Failure
17 Low Pressure Shutdown Low suction pressure
21 High Discharge Pressure High discharge pressure
22 Breaker Trip Alarm A breaker on the relay
23 Evaporator Fan Overload Evaporator fan overload
24 Condenser Fan Overload Condenser fan overload
TITLE CAUSE REMEDY CONTROLLER
than 32Fandthecom­pressor is operating.
greater than 32 volts.
less than 17 volts.
sensor failure or wiring defective.
Suction pressure trans­ducer failure or wiring defective.
Discharge pressure transducer failure or wir­ing defective.
switch open or wiring defective.
switch open or wiring defective.
board has tripped or a fan relay has failed.
jumper is open.
jumper is open.
Check causes of coil freezing. (Refer to sec­tion 3.5.6)
Check, repair or replace alternator.
Check, repair or replace wiring or alternator.
Ensure all connectors are plugged in. Check sensor resistance or wir­ing. Replace sensor or repair wiring.
Ensure all connectors are plugged in. Check sensor voltage or wiring. Replacesensororrepair wiring.
Ensure all connectors are plugged in. Check sensor voltage or wiring. Replacesensororrepair wiring.
Check cause of low suc­tion pressure. (Refer to section 3.5.3)
Check discharge pres­sure transducer reading, wiring or cause of high discharge pressure. (Refer to section 3.5.3)
Check breakers for tripped device. Repair short and reset breaker.
Ensure connector is plugged in or repair wiring.
Ensure connector is plugged in or repair wiring.
RESPONSE
An alarm will be generated and the system will shut­down. The evaporator fans will remain running whilethe compressor is off.
The system is shut down until the voltage returns to normal levels.
The system is shut down until the voltage returns to normal levels.
All outputs except the evap­orator fans will be de-ener­gized.
Both unloaders are ener­gized.
One unloader is energized.
The clutch is de-energized for the minimum off time. The evaporator fans will re­main running during this pe­riod. After the compressor cycles off three times in 30 minutes all outputs will be de-energized and the sys­tem is locked out until the poweriscycledorthealarm is reset through the keypad.
The clutch is de-energized for the minimum off time. The condenser and evapo­rator fans will remain run­ning during this period. Af­terthecompressorcycles off three times in 30 minutes all outputs will be de-ener­gized and the system is locked out until the power is cycled or the alarm is reset through the keypad.
Alarm will be generated.
Alarm will be generated.
Alarm will be generated.
T-283
3-2
Page 24
Table 3-2. Alarm Codes (Continued)
ALARM
NO
25 Motor Failure A motor has not reached
26 Not used 31 Maintenance Alarm 1 The compressor hour
32 Maintenance Alarm 2 The evaporator hour
99 AlarmQueue Full All locations of the alarm
TITLE CAUSE REMEDY CONTROLLER
full operating speed or the condenser motors have shut down due to a pressure alarm or the motor fuse has blown.
meter is greater than the value in Maintenance Hour Meter 1.
meter is greater than the value in Maintenance Hour Meter 2.
queue are currently full and no more alarms can be saved.
Replace motor, or cor­rect pressure shutdown.
Reset the maintenance hour meter.
Reset the maintenance hour meter.
Record and clear alarm queue.
RESPONSE
Alarm displayed and the motor fail output is ener­gized.
Alarm will be generated.
Alarm will be generated.
Alarm will be generated.
T-283
3-3
Page 25
Table 3-3. General System Troubleshooting Procedures
INDICATION/
TROUBLE
POSSIBLE CAUSES
REFERENCE
SECTION
SYSTEM WILL NOT COOL
Compressor willnotrun Active system alarm
V-Belt loose or defective Clutch coil defective Clutch malfunction Compressor malfunction
Electrical malfunction Coach power source defective
Circuit Breaker/safety device open
3.2
Check Check/Replace Check/Replace
See Note
Check/Repair
Check/Reset
SYSTEM RUNS BUT HAS INSUFFICIENT COOLING
Compressor V-Belt loose or defective
Compressor valves defective
Refrigeration system Abnormal pressures
No or restricted evaporator air flow Expansion valve malfunction Restricted refrigerant flow Low refrigerantcharge Service valves partially closed Safety device open Liquid solenoid valve stuck closed
Check
See Note. see below
3.5.6 p. 3-5 and 4.11 p. 3-5 and 4.11
4.5 and 4.7 Open
1.6
Check Restricted air flow No evaporator air flow or restriction p. 3-5 Heating system Heat valve stuck open p. 3-5
ABNORMAL PRESSURES
High dischargepressure Discharge transducer failure
Refrigerant overcharge Noncondensable in system Condenser motor failure Condenser coil dirty
Low discharge pressure Discharge transducer failure
Compressorvalve(s)wornorbroken
Replace
4.4 Check Check
Clean
See Note.
4.5 & 4.7
Low refrigerantcharge High suction pressure Compressorvalve(s)wornorbroken See Note. Low suction pressure Suction service valve partially closed
Filter-drier inlet valve partially closed
Filter-drier partially plugged
Low refrigerantcharge
Expansion valve malfunction
Restricted air flow
Suction transducer failure Suction and dischargepressures
Compressor valve defective See Note.
Open
Check/ Open
4.10
4.5 and 4.7 p. 3-5 p. 3-5
Replace
tend to equalize when system is operating
ABNORMAL NOISE OR VIBRATIONS
Compressor Loose mounting hardware
Worn bearings Worn or broken valves Liquid slugging Insufficient oil Clutch loose, rubbing or is defective V-belt cracked, worn or loose Dirt or debris on fan blades
Check/Tighten
See Note. See Note.
p. 3-5
4.12.2 Check
Check/Adjust
Clean
T-283
3-4
Page 26
Table 3-3. General System Troubleshooting Procedures - Continued
INDICATION/
TROUBLE
POSSIBLE CAUSES
REFERENCE
SECTION
ABNORMAL NOISE OR VIBRATIONS --- Continued
Condenserorevaporatorfans Loose mounting hardware
Defective bearings Blade interference Blade missing or broken
Check/Tighten
Replace
Check
Check/Replace
CONTROL SYSTEM MALFUNCTION
Will not control Sensor or transducer defective
Relay(s) defective Microprocessor controller malfunction
4.14 or 4.15 Check Check
NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW
Air flow through coil blocked Coil frosted over
Dirty coil Dirty filter
No or partial evaporator air flow Motor(s) defective
Motor brushes defective Evaporator fan loose or defective Fan damaged Return air filter dirty icing of coil Fan relay(s) defective Safety device open Fanrotationincorrect
Defrost coil
Clean
Clean/Replace
Repair/Replace
Replace Repair/Replace Repair/Replace
Clean/Replace
Clean/Defrost
Check/Replace
1.6
Check
EXPANSION VALVE MALFUNCTION
Low suction pressure with high superheat
Low superheatandliquid slugging in the compressor
Side to side temperature differ­ence (Warm Coil)
Low refrigerantcharge Wax, oil or dirt plugging valve orifice Ice formation at valve seat Power assembly failure Loss of bulb charge Broken capillary
Superheat setting too low Ice or other foreign material holding valve open
Wax, oil or dirt plugging valve orifice Ice formation at valve seat Power assembly failure Loss of bulb charge Broken capillary
4.5 and 4.7 Check
4.6 Replace Replace
4.11
4.11
4.6
Check
4.6 Replace Replace
4.11
HEATING MALFUNCTION
Insufficient heating Dirtyorpluggedheatercore
Coolant solenoid valve(s) malfunctioning or plugged Low coolant level Strainer(s) plugged Hand valve(s) closed Water pumps defective Auxiliary Heater malfunctioning.
No Heating Coolant solenoid valve(s) malfunctioning or plugged
Controller malfunction Pump(s) malfunctioning Safety device open
Clean
Check/Replace
Check
Clean
Open Repair/Replace Repair/Replace
Check/Replace
Replace
Repair/Replace
1.6
Continuous Heating Coolant solenoid valve stuck open Replace
T-283
3-5
Page 27
SECTION 4
OPERATIONREFERENC
E
SERVICE
!
BE SURE TO OBSERVE WARNINGS LISTED IN THE SAFETY SUMMARY IN THE FRONT OF THIS MANUAL BEFORE PERFORMING MAINTE­NANCE ON THE HVAC SYSTEM
4.1 MAINTENANCE SCHEDULE SYSTEM
ON OFF
a. Daily Maintenance
X
b. Weekly Inspection
X
c. Monthly Inspection and Maintenance
Pre-trip Inspection --- after starting Check tension and condition of V-belt
X
X
Perform daily inspection
X
Check condenser, evaporator coils and air filters for cleanliness
X
Check refrigerant hoses and compressor shaft seal for leaks Feel filter-drier for excessive temperature drop across drier
X
Perform weekly inspection and maintenance
X
Clean evaporator drain pans and hoses
X
Check wire harnesses for chafing and loose terminals
X
Check fan motor bearings
X
Check compressor mounting bolts for tightness
X
Check fan motor brushes
WARNING
!
REFERENCE
SECTION
2.2 None
4.1.a None
4.5
4.10
4.1.b None Replace/Tighten None None None
4.2 SUCTION AND DISCHARGE SERVIC E VAL VES
The suction and discharge service valves used on the compressor are equipped with mating flanges for connection to flanges on the compressor. These valves are providedwith a doubleseat and a gauge connection, whichallowsservicingof the compressorandrefrigerant lines. (See Figure 4-1.)
Turningthe valvestemcounterclockwise (allthewayout) will backseat the valve to open the suction or discharge line to the compressor and close off the gauge connection. Innormaloperation, the valve isbackseated to allow full flow through the valve. The valve should always be backseated when connecting the service manifold gauge lines to the gauge ports.
Turning the valve stem clockwise (all the way forward) willfrontseatthevalvetocloseoffthesuctionordischarge line to isolate the compressor and open the gauge connection.
To measure suction or discharge pressure, midseat the valve byope ningthe valve clockwise1/4 to1/2 turn. With the valve stem midway between frontseated and backseated positions, the suction or discharge line is open to both the compressorandthegauge connection.
To Discharge or from Suction Line
Port to Compressor
Service Valve Frontseated (clockwise)
Figure 4-1. Suction or Discharge Service Valve
4-1 T-283
Gauge Connection
Service Valve
Backseated
(counterclockwise)
Valve Cap
Valve Stem
Page 28
4.3 INSTALLING MANIFOLD GAUGES
Themanifold gaugeset canbe usedtodeterminesystem operatingpressures,addcharge,equalizeorevacuatethe system. (See figure4-2.)
Low Pressure
Gauge
Hand Valve
(Open)
A. Connection to
Low Side of System
ABC
C. Connection to Either:
High Pressure
Gauge
Hand Valve
(Frontseated)
Vacuum Pump Refrigerant Cylinder
B. Connection to
High Side of System
Oil Container Evacuation Line
Figure 4-2. Manifold Gauge Set
The manifold gauge in figure 4-2 shows hand valves, gaugesandrefrigerantopenings. Whenthelowpressure hand valve is frontseated (turned all the way in), the low (evaporator) pressure can be checked. When the high pressure hand valve is frontseated, high (condensing) pressure can be checked. When both valves a re open (turned counterclockwise), high pressure vapor willflow into the low side. When the low pressure valve is open, the system can be charged or evacuated. Oil can also be added to the system.
Install the manifold gauge set as follows:
a. Remove both service valve stems and service port
caps. Backseat (counterclockwise) both service valves.
b. Connect the high side hose tightly to discharge
service valve port.
c. Connect the low side hose loosely to suction service
valve port.
d. Loosen charging (center) hose at dummy fitting of
manifold set.
e. Frontseat (clockwise) both manifold gauge hand
valves.
f. Open discharge service valve counterclockwise
approximately 1/4 to 1/2 turns.
g. Slowly open (counterclockwise) manifold discharge
hand valve approximatelyone turn. h. Tighten charging hose onto dummy fitting. i. Slowly open the manifold suction hand valve to
remove air from line. j. Tightensuctionhoseatthesuctionservicevalveport. k. Frontseat (close)both manifold hand valves.
l. Open suction service valve counterclockwise
approximately 1/4 to 1/2 turns.
4.4 PUMPING THE SYSTEM DOWN OR REMOVING THE REFRIGERANT CHARGE
NOTE
Toavoiddamagetotheearth’sozonelayer,usea refrigerant recoverysystemwhenever removing refrigerant.
4.4.1 System Pumpdown
To service or replace the filter-drier, expansion valve, evaporatorcoil,orsuctionline,pumptherefrigerantinto condenser coil and receiver asfollows:
a. Install manifold gauge set. (Referto section4.3.)
NOTE
Thefollowingproceduremayhavetobe repeatedseveraltimestomaintainthe1psig(6.9 kPa) pressure depending upon amount of refrigerant absorbed in the oil.
b. Frontseat filter-drier inlet service valve by turning
clockwise. Start system and run in cooling. Stopthe unit when the suction pressure reaches 1 psig (6.9 kPa) to maintain a slight positive pressure.
c. Frontseat (close) suction service valve to trap the
refrigerantinthe highsideof thesystembetweenthe compressor suction service valve andthe filter drier inlet valve. Thelowside ofthesystemwill nowbe at1 psig (6.9 kPa) pressure and ready for servicing,
d. Service or replace the necessary component on the
low side of the system. e. Leak check connections. (Referto section4.5.) f. Evacuate and dehydrate the low side. (Refer to
section4.6.)
4.4.2 Removing the Refrigerant Charge
Connect a refrigerant recovery system to the unit near the receiver to remove refrigerant charge. Refer to instructions provided by the manufacturer of the refrigerant recoverysystem.
NOTES
a. Before openingupany partofthe system, a
slightpositivepressure shouldbe indicated on the gauge.
b. When opening up the refrigerant system,
certain parts may frost. Allow the part to warm to ambient temperature before dismantling; this avoids internal condensation, which puts moisture in the system.
4.5 REFRIGERANT LEAK CHECK
A refrigerant leak check should always be performed after the system has been opened to replace or repair a component.
To check for leaks in the refrigeration system, perform the followingprocedure:
4-2T-283
Page 29
NOTE
Itmust beemphasized thatonly the correct refrigerant drum should be connected to pressurizethesystem. Any other gas or vapor willcontaminate the system, which will requireadditionalevacuation and evacuation of the high (discharge) side of the system.
a. Ensure the main liquid line and driver solenoid
valves are open.
b. If system is without refrigerant, charge system with
refrigeranttobuilduppressurebetween30to50psig (207 to 345 kPa).
c. Add sufficient nitrogen to raise system pressure to
150 to 200 psig (1.03 to 1.4 mPa).
d. Check for leaks. The recommended procedure for
finding leaks in a system is with a halide torch or electronicleakdetector. Testingjointswithsoapsuds is satisfactory only for locating large leaks.
e. Remove refrigerant using a refrigerant recovery
system and repair any leaks.
f. Evacuate and dehydrate the system. (Refer to
section4.6.) g. Charge the unit. (Refer to section 4.7.) h. Ensure that self-test has been performed and that
there are no errors or alarms indicated. (Refer to
paragraph 2-1.7.)
4.6 EVACUATION AND DEHYDRATION a. General
Thepresenceofmoistureinarefrigerationsystemcan have many undesirable effects. The most common are copper plating, acid sludge formation, “freezing-up” of metering devices by free water, and formation of acids, resulting in metal corrosion.
b. Preparation
NOTE
Using a compound gauge is not recommended
because of its inherent inaccuracy.
1. Evacuateanddehydrateonlyafterpressureleaktest.
(Refer to section 4.5.)
2. Essential tools to properly evacuate and dehydrate
any system include a good vacuum pump with a
minimumof 5 cfm (8.5 m
3
/hr)volume displacement,
CTDP/N07-00176-01),andagoodvacuumindicator
(available through Robinair Manufacturing,
Montpelier, Ohio, Part Number 14010).
3. Keepthe ambienttemperatureabove 60_F(15.6_C)
to speed evaporation of moisture. If ambient
temperature is lower than 60_F (15.6_C),icemay
formbefore moisture removalis complete.Itmay be
necessary to use heater blankets, heat lamps or
alternate sources of heat to raise system
temperature.
c. Procedure for Evacuation and
Dehydrating System
1. Remove refrigerant using a refrigerant recovery system.
2. The recommendedmethodisconnecting three lines (3/8”ODcoppertubingorlarger)tomanifold. Attach one line to the filter-drier outlet valve, compressor suction and discharge service valves. (See Figure 4-3.)
3. Connect lines to unit and manifold and make sure vacuumgaugevalve isclosedandvacuumpumpvalve is open.
4. Opensolenoidvalveselectrically(jumper24vtocoil) to ensure a good vacuum is obtained.
5. Start vacuum pump. Slowly open valveshalfway and then open vacuum gauge valve.
6. Evacuate unit until vacuum gauge indicates 1500 microns (29.86 inches =75.8 cm)Hg vacuum. Close gauge valve, vacuum pump valve, and stop vacuum pump.
7. Break the vacuum with clean dry refrigerant. Use refrigerant that the unit calls for. Raise system pressure to approximately 2 psig (13.8 kPa).
8. Remove refrigerant using a refrigerant recovery system.
9. Start vacuum pump and open all valves. Dehydrate unit to 500 microns (29.90 inches = 75.9 cm) Hg vacuum.
10. Closeoffpumpvalve,isolatevacuumgaugeinsystem and stop pump. Wait five minutes to see if vacuum holds.
11. Withavacuumstillin theunit,the refrigerantcharge may be drawn into the system from a refrigerant container on weight scales.
4.7 ADDING REFRIGERANT TO SYSTEM
4.7.1 Checking Refrigerant Charge
Thefollowingconditions mustbemettoaccuratelycheck the refrigerant charge.
a. Coach engineoperating at high idle. b. Unit operating in coolmode for 15 minutes. c. Headpressureatleast150psig(1.03mPa)forR-134a
systems. (It may benecessary to block condenser air flow to raise headpressure.)
d. Under the above conditions, the system is properly
chargedwhen therefrigerant liquidlevel is visible in thereceiverlowersightglass.Ifitisnotvisible,addor removerefrigerant until it is at the properlevel.
4.7.2 Adding Full Charge
a. Evacuate and dehydrate system. (Refer to section
4.6)
b. Place appropriate refrigerant cylinderonscales and
connect charging hose from container to filter-drier inlet valve. Purge air from hoses.
4-3 T-283
Page 30
c. Note weight of refrigerant and cylinder. d. Openliquid valve onrefrigerant container. Midseat
filter-drier inlet valve and allow refrigerant to flow intotheunit. Correctcharge willbe foundinsection
1.3.
e. When cylinder weight (scale) indicates that the
correct charge hasbeenadded,closeliquidlinevalve on drum and backseat the filter-drierinletvalve.
4.7.3 Adding Partial Charge
4.9 CHECKING AND REPLACING HIGH PRESSURE CUTOUT SWITC H
4.9.1 Checking High Pressure Switch
!
DO NOT USE A NITROGEN CYLINDER WITHOUT A PRESSURE REGULATOR. DO NOT USE OXYGEN IN OR NEAR A REFRIGERATION SYSTEM OR AS AN EXPL OSION MAY OCCUR.
WARNING
!
a. Start the vehicle engine and allow unit to stabilize. b. Place appropriate refrigerant cylinderonscales and
connectcharginghose fromcontainervapor valveto compressor suction service valve.
c. Rununitincoolmodefor15minutes.Withsuction
service valve midseated, remove air from hose at refrigerant cylinder. Open cylinder valve and add vapor charge until refrigerant level appears in the lowerreceiversightglass.Undertheabove conditions, thesystemwillbeproperlychargedwhen the lower receiver sight glass appears full of refrigerant. Add or remove refrigerant until the proper level is obtained. Refrigerant level should not
appear in the upper sight glass, as this would indicate and overcharge.
d. Backseat suction service valve. Close vapor valve on
refrigerant drum and note weight. Replace all valve caps.
4.8 CHECKING FOR NONCONDENSIBLES
To check for noncondensibles, proceed as follows: a. Stabilize system to equalize pressure between the
suction and discharge side of the system. b. Checktemperature at the condenser and receiver. c. Check pressure at the compressor discharge service
valve. d. Check saturation pressure as it corresponds to the
condenser/receiver temperature using the
Temperature-Pressure Chart, Table 4-4. e. If gauge readingis 3 psig (21 kPa) or more than the
calculated P/T pressure in step d, noncondensibles
are present. f. Remove refrigerant using a refrigerant recovery
system. g. Evacuate and dehydrate the system. (Refer to
section4.6.) h. Charge the unit. (Refer to section 4.7.)
a. Remove switch from unit. All units are equipped
with schrader valves at the high pressure switch connection.
b. Connectanohmmeteracrossswitchterminals.Ifthe
switch is good, the ohmmeter will indicate no resistance, indicating that the contacts are closed.
c. Connect switch to a cylinder of dry nitrogen. (See
Figure 4-4.).
1
4
1. Cylinder V alve
2
3
Figure 4-3. Checking High Pressure Switch
d. Set nitrogen pressure regulator higher than cutout
point on switch being tested. (See section1.3.)
e. Opencylinder valve.Slowlyopenthe regulatorvalve
toincreasethepressureuntilitreachescutoutpoint. The switch should open, which is indicated by an infinite reading on an ohmmeter (no continuity).
f. Closecylindervalveandreleasepressurethroughthe
bleed-offvalve.Aspressuredropstocut-inpoint,the switch contacts shouldclose, indicatingnoresistance on the ohmmeter.
g. Replace switch if it does not function as outlined
above. (Refer to section 4.9.2.)
4.9.2 Repla cing High Pressure Switch
a. The high pressure switch is equippedwith schrader
valve to allow removal and installation without
pumping the unit down. b. Disconnect wiring from defective switch. c. Install new cutout switch. d. Check switch operation. (Refer to section 4.9.1.)
5
6
and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
4. Pressure Gauge (0 to 400 psig = 0to2.8mPa)
5. Bleed-Off Valve
6. 1/4 inch Connection
4-4T-283
Page 31
4.10 FILTER-DRIER a. To Check Filter Drier
Check for a restricted or plugged filter-drier by feeling the liquid line inlet and outlet connections of the filter-drier. If the outlet side feels cooler than the inlet side, then the filter-drier should be changed.
b. To Replace Filter Drier
1. Pumpdown the unit. (Refer to section 4.4.)
2. Replacefilter-drier,ensuringthatthearrowpointsin the direction of the refrigerant flow.
3. Drier can be evacuated at liquid service valve. (See Figure 4-3.)
4. Check refrigerantlevel. (Refer to section 4.7.1.)
12. Run the coachforapproxi mately 30 minutes on fast idle.
13. Check refrigerant level. (Refer to section 4.7.1.)
14. Checksuperheat. (Refer to section 4.11.b.)
1
6 7
5
4
3
2
8
9 8
4.11 THERMOSTATIC EXPANSION VALVE
The thermostat expansion valve (TXV) is an automatic device which maintains constant superheat of the refrigerant gas leaving the evaporator regardless of suction pressure. The valve functions are: (a)automatic responseof refrigerantflowtomatchtheevaporatorload and (b) prevention of liquid refrigerant entering the compressor. Unless the valve is defective, it seldom requires any maintenance.
a. Replacingthe Expansion Valve (SeeFigure4-5.)
1. Pump down low side of the unit. (Refer to section
4.4.)
2. Remove insulation(Presstite)fromexpansion valve bulb.
3. Loosen retainingstraps holding bulb to suction line and detach bulbfrom the suction line.
4. Loosen flare nuts on equalizer line and disconnect equalizer linefromthe expansion valve.
5. Remove capscrews and lift off powerheadandcage assembliesandgaskets.
6. Check, clean and removeany foreignmaterial from the valve body, valveseatandmating surfaces.
NOTE
Do not adjust the new replacement expansion valve. Valves are preset at the factory.
7. Usingnew gaskets,i nstall newcage and power head assembliesprovidedwith repair kit.
8. The thermalbulbisinstalled below the centerofthe suctionline(fouroreighto’clockposition).Thisarea must be clean to ensure positive bulbcontact. Strap thermal bulb to suction line and insulate both with “Presstite.” Ensure that retaining straps are tight. (See Figure 4-6.)
9. Fasten equalizer line to the expansion valve.
10. Evacuate and dehydrate. (Refer to section 4-6.)
11. Openfilter-drierinletvalve(liquidlineservicevalve) and all service valves.
10
11
1. Power Head Assembly 7. Bulb
2. Cap Seal 8 Gasket
3. Flare Seal 9. Cage Assembly
4. Retaining Nut 10. Body Flange
5. Adjusting Stem 11. Capscrew
6. Equalizer Connection
Figure 4-4. Thermostatic Expansion Valve
3
2
1
1. Suction Line (end view)
2. TXV Bulb Clamp
3. Nut and Bolt (clamp)
4. Thermocouple
5.TXVBulb(Showninthe 4’clock position)
Figure 4-5. Thermostatic Expansion Valve
Bulb and Thermocouple
Monitor the superheat over a five minute period and record the maximum and minimum readings. Add the maximum and minimum readings and divide by two to determine the superheat. Thesuperheatshould be10F to 12F.
b. To Check/Measure Superheat
NOTE
Allreadingsmust betaken fromthe suctionside areaofthe evaporator nearthe TXV andoutof the direct air stream.
1. Remove filter access door.
2. Remove Presstite insulation from expansion valve bulb and suction line.
4
5
4-5 T-283
Page 32
3. Loosen one TXV bulb clamp and make sure area under clamp is clean.
4. Place temperaturethermocouplein contact with the suction tube and parallel to the TXV bulb,andthen secure loosened clamp making sure both bulbs are firmly secured to suction line. (See Figure 4-5). Reinstall insulation around the bulb.
5. Reinstall evaporator access door being careful to route thermocouple sensing wire outside the evaporator.
6. Connect an accurate lowpressure gauge to the 1/4” portonthesuctionservicevalveorinstalla manifold gauge set. (Refer to section 4.3.)
7. Startbusandrunonfastidleuntilunithasstabilized, about20to30minutes.
NOTE
When conducting this test, the suction pressure must be at least 6 psig (41 kPa) below the expansion valve maximum operating pressure (MOP). Refer to section 1.3 forMOP.
8. Fromthetemperature/pressurechart, determinethe saturation temperature corresponding to the evaporator outlet pressure.(SeeTable 4-4.) Addan estimatedsuction lineloss of2psig (13.8 kPa) to the number taken at the compressor.
9. Note the temperature of the suction gas at the expansion valve bulb. Subtract the saturation temperature determined i n step 8 from the temperaturemeasuredin thisstep. Thedifference is the superheat of the suction gas.
10. Monitorthe superheatoverafiveminute periodand record the maximum and minimum readings. Add themaximumandminimumreadingsanddivide by2 to determine superheat. The superheat should be 10Fto12F.
c. To Adjust Superheat
NOTE
It is not recommended to adjust thermal expansion valves unless absolutely necessary. The procedure is very time consuming. Therefore, it is highly recommended that the expansion valve be replaced rather than adjusting.
Ifadjustment isnecessary, performthe followingprocedure:
1. Pumpdowntheloadsideofthesystem.(Referto section4.4.)
2. Removecapscrewsandnote relative position ofcage assembly.(See Figure 4.5.) Lift out powerheadand cage assemblies while maintaining position of the cage assembly. Turn/rotate cage assembly counterclockwise to decrease superheat setting or clockwise to increase superheat setting. Each full turn willchange superheat setting by 1_F (0.56_C).
3. Check, clean and removeany foreignmaterial from the valve body, valveseatandmating surfaces.
4. Reinstall powerhead andcage assemblies usingnew gaskets.
5. Tighten capscrews.
6. Evacuate and dehydrate. (Refer to section 4-6.)
7. Openfilter-drierinletvalve(liquidlineservicevalve) and all service valves.
8. Runthe coach for approximately 30 minutes on fast idle.
9. Check refrigerantlevel. (Refer to section 4.7.1.)
10. Checksuperheat setting. (Refer to section 4.11.b.)
4.12 Model 05G COMPRESSOR MAINTENANCE
4.12.1 Remo ving the Compressor
If compressor is inoperative and the unit still has refrigerant pressure, frontseat suction and discharge service valves to trap most of the refrigerant in the system.
If compressor is operative, pump down the system. (Refer to section 4.4.)
a. T u rnmain batter y discon n ec t switc h to OFF position. b. Slowly release compressor pressure. c. Remove bolts from suction and discharge service
valve flanges.
d. Tag and disconnect wiring to the high pressure and
low pressure cutout switch, unloadersand clutch.
e. Remove four bolts holding compressor to base f. Attach sling or other device to the compressor and
remove compressorfrom the coachthroughthe rear access door.
g. Remove the three socket head capscrews from both
cylinderheadsthat haveunloader valvesinstalledon the05G compressor.Removetheunloadervalveand bypass piston assembly, keepingthesamecapscrews with the assembly. The original unloadervalve must be transferred to the replacement compressor. The plug arrangement removed from the replacementis installed intheoriginalcompressorasaseal.Ifpiston is stuck, it may be extracted by threading a socket headcapscrewinto topof piston.A smallTeflonseat ring at the bottom of the piston must be removed.
NOTES
1. The service replacement 05G compressors
are sold without shutoff valves. Valve pads are installed in their place. The optional unloaders are not supplied, as the cylinder heads are shipped with plugs. Customer should retain the original unloader valves for use on the replacement compressor.
2. The piston plug that is removed from the
replacement compressor head must be installed in the failed compressor if returning for warranty.
3. Donot interchangeallen-headcapscrewsthat
mount the piston plug and unloader, they are not inte rchangeable.
4-6T-283
Page 33
4. Check oil level in service replacement compressor. (Refer to section 1.3 and 4.12.2.)
COMPRESSOR HEAD
GASKET
BYPASS PISTON PLUG
FLANGE COVER
SPRING
capscrews
(NOT INTERCHANGEABLE WITH CONTROL VALVE SCREWS)
Figure 4-6. Removing Bypass Piston Plug
h. Remove the high pressure switch assembly and
install on replacement compressor after checking switchoperation.
12
11 10
9 8
7
1. Electric Unloader Valve
2. Suction Service Valve Charging Port
3. Suction Service Valve
4. Clutch
5.OilFillPlug
1 2
3 4
5
6
6. Bottom Plate
7. Oil Drain Plug
8. Oil Level Sight Glass
9. Oil Pump
10. O-ring
11. Discharge Service Valve
12. Service Port
i. Install compressor in unit by performing steps c.
through h. in reverse. It is recommended that new locknutsbe used when replacing compressor.Install new gaskets on service valves and tighten bolts uniformly.
j. Unlock and turn main battery disconnect switch to
ON position..
k. Attach two lines (with hand valves near vacuum
pump) to the suction and discharge service valves. (Dehydrateandevacuate compressorto500microns (29.90” Hg vacuum= 75.9 cm Hgvacuum). Turn off valves on both lines to pump.
l. Fully backseat (opencounterclockwise) both suction
and discharge service valves.
m. Remove vacuum pump lines and install manifold
gauges.
n. Start unit and check refrigerant level.
o. Checkcompressoroillevel.(Refertosection4.12.2.)
Addorremove oil if necessary.
p. Check compressor unloader operation.
Figure 4-7. Model O5G Compressor
4.12.2 Compressor Oil Level
4.12.2.1 Checking the Compressor Oil Level
NOTE
The compressor should be fully loaded (six cylinder operation); the unit should be fully chargedandthecompressorcrankcaseshouldbe
warm to the touch. a. Start the unit and allowthe system to stabilize. b. Checkthe oilsightglassonthe compressorto ensure
that nofoamingof the oilispresent after 20minutes
ofoperation.Iftheoilisfoamingexcessivelyafter20
minutes of operation, check the refrigerant system
for flood-back of liquid refrigerant. Correct this
situationbeforeproceeding.(Referto section3.3.4.) c. Check the level of the oil in the oil level sight glass
immediately after shutting down the compressor.
Thelowestlevelvisibleshouldbebetweenthe“Min”
and “Max” indicators on the compressor crankcase
adjacent to the sight glass. (See Figure 4-8.)
4.12.2.2 Adding Oil with Compressor in System
Twomethodsforaddingoilare:the oilpumpmethod and closed system method.
a. Oil Pump Method
1. Onecompressoroilpumpthat maybe purchasedis a
Robinairpart no.14388.This oilpumpadaptstoone
U.S. gallon (3.785 liters) metal refrigeration oil
container and pumps 2-1/2 ounces (72.5 mliters) per
stroke when connected to the suction service valve
port.Also,thereisnoneedtoremovepumpfromcan
after each use.
4-7 T-283
Page 34
2. When the compressor is in operation, the pump
Resi
O
h
check valve prevents the loss of refrigerant while allowingservicementodevelopsufficientpressureto overcome the operatingsuction pressure to add oil, as necessary.
3. Backseat suction service valve and connect oil charging hose to port. Crack open the service valve andremoveairfromtheoilhoseattheoilpump.Add oil as necessary.
b. Closed System Method
1. In anemergency whereanoil pump is notavailable, oil may be drawn into the compressor through the suction service valve.
!
EXTREMECAREMUSTBETAKENTO ENSURE THAT THE MANIFOLD COMMON CONNECTION REMAINS IMMERSED IN OIL AT ALL TIMES OR AIR AND MOISTUREWILL BE DRAWN INTO THE SYSTEM
2. Connect the suction connection of the gauge manifold to the compressor suction service valve port, and immerse the common connection of the gaugemanifoldinan opencontainerofrefrigeration oil. Refer to section 1.3.b. for oil specifications. Removeair fromthe lines.Closethe gaugemanifold valve.
3. Remove air from the lines.
4. With the unit running, frontseat (counterclockwise) the suction service valve and pull a vacuum in the compressor crankcase. Slowly crack the suction gauge manifold valve and oil will flow through the suctionservice valve intothe compressor.Add oilas necessary.
4.12.2.3 Adding Oil to Service Replacement
Compressor
Service replacement compressors may or may not be shippedwith oil.
Ifthe replacementcompressorisshippedwithoutoil,add oil through the suction service valve flange cavity or by removingtheoilfillplug.(SeeFigure4-8.)
4.12.2.4 Removing Oil from the Compressor:
a. If thelowest oillevel observedinparagraph4.12.2.1,
step c., is above “Max” indication on compressor crankcase,oil mustbe removedfromthe compressor by performing the following procedure. If lowest oil level visible is below “Min” indication, oil must be added tothecompressor by following theprocedure in section 4.12.2.2.
b. Closesuctionservicevalve(frontseat)andpumpunit
downt o 3to5 psig(21 to34kPa).Reclaimremaining refrigerant.
CAUTION
!
NOTE
If oil drain plug is not accessible, it will be necessary to extract oil through the oil fill plug with a siphon tube.
c. Removethe oildrainplugonthe bottomplateofthe
compressoranddrain the properamount ofoilfrom the compressor. Replace the plug securely back into the compressor.
d. Repeat step a. to ensure proper oil level.
4.13 TEMPERATURE SENSOR CHECKOUT
a. An accurate ohmmeter must be used to check
resistance values shown inTable 4-1.
b. Due to variations and inaccuracies in ohmmeters,
thermometers or other test equipment, a reading within two percent of the chart value would be considered good. If a sensor is bad, the resistance value would usuallybemuchhigher orlower thanthe value given in the Table 4-1.
c. At least one sensor lead must be disconnectedfrom
the controllerbefore any reading can be taken. Not doing sowill resultinafalse reading. Two preferred methodsofdetermining the actualtest temperature at the sensorare an ice bathat 32_F (0_C) and/ora calibrateddigitaltemperature meter.
Table 4-1. Temperature Sensor
(AT, TSC, TSD and TSR) Resistance
Temperature
_F _C
--- 20 --- 28.9 165,300
--- 10 --- 23.3 117,800 0 ---17.8 85,500
10 --- 12.2 62,400 20 --- 6.7 46,300 30 --- 1.1 34,500 32 0 32,700 40 4.4 26,200 50 10.0 19,900 60 15.6 15,300 70 21.1 11,900 77 25 10,000 80 26.7 9,300
90 32.2 7,300 100 37.8 5,800 110 43.3 4,700 120 48.9 3,800
4.14 SUCTION AND DISCHARGE PRESSURE TRANSDUCER CHECKOUT
NOTE
System must be operating to check transducers.
a. With the system running use the driver display or
manifold gauges to check suction and/or discharge pressure(s).
stanceIn
ms
4-8T-283
Page 35
b. Useadigital volt-ohmmeter measurevoltage across
thetransducerand compare tovalues inTable4-2. A readingwithin two percent of the values in thetable would be considered good.
Table4-2.SuctionandDischargePressure
Transducer (SPT and DPT) Voltage
Psig Voltage Psig Voltage Psig Voltage
20” 0.369 105 1.495 220 2.622 10” 0.417 110 1.544 225 2.671
0 0.466 115 1.593 230 2.720
5 0.515 120 1.642 235 2.769 10 0.564 125 1.691 240 2.818 15 0.614 130 1.740 245 2.867 20 0.663 135 1.789 250 2.916 25 0.712 140 1.838 255 2.965 30 0.761 145 1.887 260 3.014 35 0.810 150 1.936 265 3.063 40 0.858 155 1.985 270 3.112 45 0.907 160 2.034 275 3.161 50 0.956 165 2.083 280 3.210 55 1.007 170 2.132 285 3.259 60 1.054 175 2.181 290 3.308 65 1.103 180 2.230 295 3.357 70 1.152 185 2.279 300 2.406 75 1.204 190 2.328 305 3.455 80 1.250 195 2.377 310 3.504 85 1.299 200 2.426 315 3.553 90 1.348 205 2.475 320 3.602 95 1.397 210 2.524 325 3.651
100 1.446 215 2.573 330 3.700
4.15 Replacing Sensors and Transducers
a. Turnmainbatterydisconnectswitchto OFFposition
and lock.
b. Tag and disconnect wiring from defective sensor or
transducer. c. Remove and replace defective sensor or transducer. d. Connectwiringtoreplacementsensorortransducer. e. Checkout replacement sensor or transducer. (Refer
to section 4.13, 4.14 or 4.15, as applicable.) f. Repair or replace any defective component(s), as
required.
4.16 Controller Configuration
When a controller is replaced it must be configured to workinthemodelofunititisbeinginstalledin.Table4-3 shows the configuration jumpersettingsthatmustbe set to correctly operate the Capri-280 SEPTA unit.
4-9 T-283
Page 36
Table 4-3. Controller Configuration
Configuration Description Jumper
A. High Reheat --- When this configuration is removed the unit will default
REMOVED to high speed in reheat mode and in the low speed cool band. If not removed heat reheat will default to low speed.
B. High Vent --- When this configuration is removed the unit will default to
REMOVED high speed in vent mode. If not removed vent mode will default to low speed.
C. NA IN D. Reheat/Cycle --- When the reheat cycle configuration is removed the
REMOVED unit is in reheat mode. The default configuration is cycle clutch mode.
E. Transducers --- When the transducer configuration is removed trans-
REMOVED ducers will assumed to be present.
F. NA IN G. Unit Type --- SEPTA unit enabled with G in and H removed IN H. Unit Type --- SEPTA unit enabled with G in and H removed REMOVED
I. NA NA
J. NA IN
K. Voltage - -- When this configuration is removed the voltage selection
REMOVED
will be changed from 12 to 24V DC.
L. NA REMOVED
M. NA IN
N. C/F --- When this configuration is removed the display will show
REMOVED temperatures in F. When not removed the display will show tempera­ture in C.
O. NA IN
P. NA IN
4-10T-283
Page 37
Ta bl e 4-4. R-134a Temperature - Pressure Chart
BOLD NO. = Inches Mercury Vacuum (cm Hg Vac)
Temperature
Pressure Temperature Pressure
_F _C Psig kPa Kg/cm@ Bar _F _C Psig kPa Kg/cm@ Bar
--- 40 ---40 14.6 49.4 37.08 0.49 30 ---1 26.1 180.0 1.84 1.80
--- 35 ---37 12.3 41.6 31.25 0.42 32 0 27.8 191.7 1.95 1.92
--- 30 ---34 9.7 32.8 24.64 0.33 34 1 29.6 204.1 2.08 2.04
--- 25 ---32 6.7 22.7 17.00 0.23 36 2 31.3 215.8 2.20 2.16
--- 20 ---29 3.5 11.9 8.89 0.12 38 3 33.2 228.9 2.33 2.29
--- 18 ---28 2.1 7.1 5.33 0.07 40 4 35.1 242.0 2.47 2.42
--- 16 ---27 0.6 2.0 1.52 0.02 45 7 40.1 276.5 2.82 2.76
--- 14 ---26 0.4 1.1 0.03 0.03 50 10 45.5 313.7 3.20 3.14
--- 12 ---24 1.2 8.3 0.08 0.08 55 13 51.2 353.0 3.60 3.53
--- 10 ---23 2.0 13.8 0.14 0.14 60 16 57.4 395.8 4.04 3.96
--- 8 --- 22 2.9 20.0 0.20 0.20 65 18 64.1 441.0 4.51 4.42
--- 6 --- 21 3.7 25.5 0.26 0.26 70 21 71.1 490.2 5.00 4.90
--- 4 --- 20 4.6 31.7 0.32 0.32 75 24 78.7 542.6 5.53 5.43
--- 2 --- 19 5.6 36.6 0.39 0.39 80 27 86.7 597.8 6.10 5.98 0 --- 18 6.5 44.8 0.46 0.45 85 29 95.3 657.1 6.70 6.57 2 --- 17 7.6 52.4 0.53 0.52 90 32 104.3 719.1 7.33 7.19 4 --- 16 8.6 59.3 0.60 0.59 95 35 114.0 786.0 8.01 7.86 6 --- 14 9.7 66.9 0.68 0.67 100 38 124.2 856.4 8.73 8.56 8 --- 13 10.8 74.5 0.76 0.74 105 41 135.0 930.8 9.49 9.31
10 --- 12 12.0 82.7 0.84 0.83 110 43 146.4 1009 10.29 10.09 12 --- 11 13.2 91.0 0.93 0.91 115 46 158.4 1092 11.14 10.92 14 --- 10 14.5 100.0 1.02 1.00 120 49 171.2 1180 12.04 11.80 16 --- 9 15.8 108.9 1.11 1.09 125 52 184.6 1273 12.98 12.73 18 --- 8 17.1 117.9 1.20 1.18 130 54 198.7 1370 13.97 13.70 20 --- 7 18.5 127.6 1.30 1.28 135 57 213.6 1473 15.02 14.73 22 --- 6 19.9 137.2 1.40 1.37 140 60 229.2 1580 16.11 15.80 24 --- 4 21.4 147.6 1.50 1.48 145 63 245.6 1693 17.27 16.93 26 --- 3 22.9 157.9 1.61 1.58 150 66 262.9 1813 18.48 18.13 28 --- 2 24.5 168.9 1.72 1.69 155 68 281.1 1938 19.76 19.37
4-11 T-283
Page 38
SECTION 5
ELECTRICAL
Figure 5-1 INTRODUCTION
Thissectionincludes electricalwiring schematics.Theschematic shownin thissectionis for R-134a refrigerantsystems.
5-1
Page 39
Figure 5-1. Electrical Wiring Schematic Diagram
Drawing No. 62-10112-00 Sheet 1 of 3
5-2
Page 40
Figure 5-1. Electrical Wiring Schematic Diagram
Drawing No. 62-10112-00 Sheet 2 of 3
5-3
Page 41
Figure 5-1. Electrical Wiring Schematic Diagram
Drawing No. 62-10112-00 Sheet 3 of 3
5-4
Page 42
INDEX
A
A/D, 3-1 Abnormal Noise or Vibrations, 3-5 Activation, 3-1 Adding Full Charge, 4-3 Adding Oil, 4-7
Closed system method, 4-8 Adding PartialCharge, 4-4 Adding Refrigerant to System, 4-3 Adjust Superheat , 4-6 Air Conditioning Refrigerant Cycle, 1-5 Alarmclear, 3-1 Alarm Codes, 3-2 Alarm codes, 3-1 Alarm Description, 4 Alarm queue, 3-1 Alarm Queue Full, 3-3 Alternator, 1-1 Ambient temperaturesensor, 1-2 Auto Reheat Mode, 2
compressor, 1-4, 1-5 Compressor Clutch Control, 3 Compressor Oil Level, 4-7 Compressor Unloader, 3 Compressor Unloader Control, 3 Compressor will not run, 3-4 condensate drain connections, 1-3 Condenser, 1-1
coils, 1-2
Fans, 1-2 Condenser Coil, 1-2, 1-5 Condenser Fan Motor, 1-2, 1-4 Condenser Fan Overload, 3-2 Condenser Fan Speed Control, 3 Condenser Fiberglass Base, 1-2 Condenser Motor Harness, 1-2 Condenser Motor Overloads , 1-4 Condenser Motor Plate, 1-2 Condenser Top Cover Lid, 1-2 condenser tubes, 1-4 Connectors, 1-7 Control System Malfunction, 3-5
B
Boost Pump, 3 Breaker Trip Alarm, 3-2 Breakers, 1-5 Bypass Piston Plug, 4-7
C
Capacity control, 1 charging hoses, 1-4 Check/Measure Superheat , 4-5 Checking for Noncondensibles, 4-4 Checking Refrigerant Charge, 4-3 clutch, 1-4 clutch , 1-4 Coil Freeze, 3-2 Communication Failure, 3-1 Compressor, 1-1, 3-4
controller, 1 Controller Configuration, 4-9 Controller Input Sensor, 1-4 controlling compressor capacity, 1-4 cooling, 1-3 Cooling/Reheat, 3
D
Daily Maintenance, 4-1 Data Memory, 3-1 DEHYDRATION , 4-3 Diagnostic Module, 1-9 Diagnostics, 1 discharge check valve, 1-2 Discharge Line, 1-3 Discharge Pressure, 3 Discharge Pressure Transducer Failure, 3-2 discharge service valve, 1-4
Index-1 T-283
Page 43
INDEX
E
electricsolenoid unloaders, 1-4 Electrical, 5-1 Electrical Control, 1-1 Electrical malfunction, 3-4 Electrical Specifications, 1-4 Electronically Commutated DC Motors, 1-7 Error Codes, 3-1
ER 5, Program Memory, 3-1 Evacuation, 4-3 Evaporator,1-1,1-2,1-3
Blower and Motor, 1-3
Blowers, 1-1
Coils, 1-3
Fan, 1-3
Motor, 1-3
Motors, 1-1 Evaporator Coil, Curbside,Evaporator, 1-3 Evaporator Coil, Roadside, 1-3 Evaporator Fan Overload, 3-2 Evaporator Fan Speed, 3
H
heat valve, 1-3 Heater Flow Cycle, 1-6 Heating, 3 heating coils, coils, 1-3 HeatingLine, 1-3 Heating Malfunction, 3-5 Heating system, 3-4 High Pressure Cutout Switch , 4-4 High Discharge Pressure, 3-2 High discharge pressure, 3-4 HighPressureSwitch,HPS,1-5 high pressure switch, 1-4 High Pressure Switch (HPS), 1-4 High Reheat, 4-10 High suction pressure, 3-4 High V ent, 4-10 High Voltage, 3-2 Hour Meters, 4 Humidity Sight Glass, 1-3
Evaporator Fan Speed Selection, 3 Evaporator Motor Harness, 1-3 Evaporator Motor Overloads, 1-4 Evaporator/HeaterBlower (Fan)Motor,1-4 evaporator/heater coil assemblies, 1-3 excessive motor temperature, 1-4 Expansion Valve, 4-5
TXV, 1-3 ExpansionValve Malfunction, 3-5
F
Filter-drier, 1-2, 1-5, 4-5 Filter-drier, 4-5 Fuses, 1-5
G
Gas Hose, 1-2 General System Troubleshooting Procedures, 3-4
I
Installing Manifold Gauges, 4-2 internal thermalprotector switch, 1-4
K
king valves, 1-2
L
LEDS, 1-7 Left F ront Grille, 1-2 LidBoltSupport,1-2,1-3 Lid Locking Screw, 1-3 Lid Screw --- Stopper, 1-3 Lid Screw Nut, 1-2 Liquid Hose, 1-2 Liquid Line, 1-3 Liquid Line SolenoidValve, 1-2 liquid line solenoid valve, 1-2 Locking Screw Gasket, 1-2, 1-3
Index-2T-283
Page 44
INDEX
LogicBoard,1-3,1-8 Low discharge pressure, 3-4 Low Pressure Shutdown, 3-2 low pressure switch, 1-4 Low Pressure Switch (LPS), 1-5 Low suction pressure, 3-4 LowVoltage,3-2
M
Main Harness, 1-1 Maintenance Alarm 1, 3-3 Maintenance Alarm 2, 3-3 Maintenance Schedule, 4-1 Manifold Gauge Set, 4-2 Model 05G Compressor, 4-6 Monthly Inspection and Maintenance, 4-1 Motor Failure, 3-3
R
receiver,1-2,1-5 Receiver Tank, 1-2 Receiver Tank Support, 1-2 Refrigerant Leak C heck, 4-2 Refrigeration Charge, 1-4 Refrigeration CycleDiagram, 1-6 Refrigeration system,3-4 Reheat/Cycle, 4-10 RelayBoard,1-1,1-3,1-7 Relays, 1-7 RemovingThe Refrigerant Charge, 4-2 ReplacingSensors and Transducers, 4-9 Restricted air flow, 3-4 Return Air Filter, 1-3 Return Air Probe Failure, 3-2 Right Front Grille, 1-2 Right Rear Lateral Grille, 1-2
N
No Evaporator Air Flow Or Restricted Air Flow, 3-5
O
Oil Pump Method, 4-7
P
Parameter Codes
P2, Coil Temperature, 5 P20, Compressor Hours High, 5 P33, Kp, 6
Superheat, 5 PowerHarness, 1-1 Power Relay, 1-1 pre---tripinspection, 1 PressureSwitches,1-1,1-5 Procedurefor Evacuationand Dehydrating System ,
4-3 ProgramMemory, 3-1 Pumping The System Down, 4-2
S
Safety Devices, 1-4 Self Diagnostics, 3-1 Self-Test , 1 Service, 4-1 Service Valve, 1-2 Square Nut, 1-2, 1-3 Starting, 1 Stopping, 1 Suction and Discharge Pressure Transducer, 1-4 Suction And Discharge Service Valves, 4-1 SuctionLine, 1-3 Suction Pressure, 3 Suction Pressure Transducer, 4-8 Suction Pressure Transducer Failure, 3-2 suction service valve, 1-4, 4-1 Superheat, 4-5 System Alarms, 3-1 system operation, 1 System Parameters, 5 System Pumpdown, 4-2
Index-3 T-283
Page 45
INDEX
T
Temperature --- Pressure Chart, 4-11 Temperature Sensor Checkout, 4-8 ThermalCircuit Breakers, 1-7 thermal expansionvalves, TXV, 1-3 Thermal Switches, 1-4 ThermostaticExpansion Valve, 1-4 ThermostaticExpansion Valve , 4-5 Transducers, 1-4, 4-10
Troubleshooting, 3-1
U
UV1 Relay, 3 UV2 Relay, 3
W
Weekly Inspection, 4-1
Index-4T-283
Loading...