CAUTION: Information in this manual is intended to be used by Taylor Authorized
Service Technicians only.
Note: Continuing research results in steady improvements; therefore, information
in this manual is subject to change without notice.
E June, 2005 Taylor
All rights reserved.
059061--S
The word T aylor and the Crown design
are registered trademarks in the United States
of America and certain other countries.
Models C708/C709/C716/C717Table of Contents
Taylor Company
750 N. Blackhawk Blvd.
Rockton, IL 61072
Notes:
Table of ContentsModels C708/C709/C716/C717
Section 1:Introduction
SSafety
SRefrigerant
SSpecifications
SGeneral Installation Instructions
SRunning Specifications
SImportant to the Operator
Models C708/C709/C716/C717
1
Introduction
Safety
______________________________
Refrigerant
______________________________
We at Taylor Company, are committed to
manufacturing safe operating and serviceable
equipment. The many built-in safety features that
are part of all Taylor equipment are aimed at
protecting operators and trained service technicians
alike.
This manual is intended exclusively for Taylor
Company authorized service personnel.
This equipment must be properly grounded.
Failure to follow this instruction may result in serious
electrical shock.
Stationary appliances which are not
equipped with a power cord and a plug or other
device to disconnect the appliance from the power
source must have an all-pole disconnecting device
with a contact gap of at least 3 mm installed in the
external installation. Failure to follow this instruction
may result in electrocution.
Taylor Company uses R404A refrigerant. This
refrigerant is generally considered non-toxic and
non-flammable; however, any gas under pressure is
potentially hazardous.
NEVER fill any refrigerant cylinder
completely with liquid. Filling the cylinder to
approximately 80% will allow for normal expansion.
Refrigerant liquid sprayed onto the skin may
cause serious damage to tissue. Keep eyes and skin
protected. If refrigerant burns should occur, flush
immediately with cold water. If burns are severe,
apply ice packs and contact a physician
immediately.
The Taylor Company reminds technicians
to be cautious of government laws regarding
refrigerant recovery, recycling, and reclaiming
systems. If you have any questions regarding these
laws, please contact the factory Service
Department.
These machines must be placed on a level
surface. Failure to comply may result in personal
injury or equipment damage.
DO NOT install the unit in an area where a
water jet could be used to clean or rinse the freezer.
Failure to follow this instruction may result in serious
electrical shock.
These machines are designed to operate indoors,
under normal ambient temperatures of 70°-75°F
(21°-24°C). The machines have successfully
performed in high ambient temperatures of 104°F
(40°C) at reduced capacities.
NOISE LEVEL: Airborne noise emission does not
exceed 78 dB(A) when measured at a distance of
1.0 meter from the surface of the machine and at a
height of 1.6 meters from the floor.
WARNING: R404A refrigerant used in conjunction
with polyolester oils is extremely moisture
absorbent. When opening a refrigeration system, the
maximum time the system is open must not exceed
15 minutes. Cap all open tubing to prevent humid air
or water from being absorbed by the oil.
If the crossed out wheeled bin symbol is
affixed to this product, it signifies that this product is
compliant with the EU Directive as well as other
similar legislation in effect after August 13, 2005.
Therefore, it must be collected separately after its
use is completed, and cannot be disposed as
unsorted municipal waste.
The user is responsible for returning the product to
the appropriate collection facility, as specified by
your local code.
For additional information regarding applicable local
laws, please contact the municipal facility and/or
local distributor.
050920
Introduction
2
Models C708/C709/C716/C717
Compressor Warranty
Disclaimer
______________________________
The refrigeration compressor(s) on this machine are
warranted for the term indicated on the warranty
card accompanying this machine. However, due to
the Montreal Protocol and the U.S. Clean Air Act
Amendments of 1990, many new refrigerants are
being tested and developed; thus seeking their way
into the service industry. Some of these new
refrigerants are being advertised as drop-in
replacements for numerous applications. It should
be noted that, in the event of ordinary service to this
machine’s refrigeration system, only the refrigerant
specified on the affixed data label should be used.
The unauthorized use of alternate refrigerants will
void your compressor warranty. It will be the owners’
responsibility to make this fact known to any
technicians they employ.
It should be noted, that Taylor does not warrant the
refrigerant used in its equipment. For example, if the
refrigerant is lost during the course of ordinary
service to this machine, Taylor has no obligation to
either supply or provide its replacement either at
billable or unbillable terms. Taylor does have the
obligation to recommend a suitable replacement if
the original refrigerant is banned, obsoleted, or no
longer available during the five year warranty of the
compressor.
The Taylor Company will continue to monitor the
industry and test new alternates as they are being
developed. Should a new alternate prove, through
our testing, that it would be accepted as a drop-in
replacement, then the above disclaimer would
become null and void. To find out the current status
of an alternate refrigerant as it relates to your
compressor, call the local Taylor Distributor or the
Taylor Factory. Be prepared to provide the
model/serial number of the unit in question.
Models C708/C709/C716/C717
3
Introduction
Model C708 Specifications
Freezing Cylinder
One, 3.4 quart (3.2 liter)
Mix Hopper
One, 20 quart (18.9 liter)
Beater Motor
One, 1.5 hp
Refrigeration Unit
One, approximately 9,500 btu/hr compressor.
Refrigerant R404A.
This unit may be manufactured in other electrical
characteristics. Refer to the local Taylor Distributor
Maximum
Fuse Size
Minimum
CircuitAmpacity
for availability. (For exact electrical information,
always refer to the data label of the unit.)
Air Cooled
Clearance: A minimum of 6” (152 mm) is required on
both sides, and the back of the unit placed against
the wall to prevent recirculation of warm air. An
optional air discharge chute is available to direct
heated air exhaust upward. No clearance is required
on the right side if the air discharge chute is used.
Water Cooled
Water inlet and drain connections on the right side
or under the side of the base, 3/8” FPT.
Dimensions
Width: 18-1/4” (464 mm)
Height: 33-7/8” (860 mm)
Depth: 34” (864 mm)
Floor Clearance: Rests on a plastic pad directly on
counter top.
This unit may be manufactured in other electrical
characteristics. Refer to the local Taylor Distributor
Maximum
Fuse Size
Minimum
CircuitAmpacity
for availability. (For exact electrical information,
always refer to the data label of the unit.)
Air Cooled
Clearance: A minimum of 6” (152 mm) is required on
both sides, and the back of the unit placed against
the wall to prevent recirculation of warm air. An
optional air discharge chute is available to direct
heated air exhaust upward. No clearance is required
on the right side if the air discharge chute is used.
Water Cooled
Water inlet and drain connections on the right side
or under the side of the base, 3/8” FPT.
Dimensions
Width: 18-1/4” (464 mm)
Height: 33-7/8” (860 mm)
Depth: 34” (864 mm)
Floor Clearance: Rests on a plastic pad directly on
counter top.
This unit may be manufactured in other electrical
characteristics. Refer to the local Taylor Distributor
for availability. (For exact electrical information,
always refer to the data label of the unit.)
Air Cooled
Clearance: A minimum of 3” (76 mm) is required
around all sides. Install the deflector provided to
prevent recirculation of warm air.
Water Cooled
Water inlet and drain connections under the side of
the base, 1/2” FPT.
This unit may be manufactured in other electrical
characteristics. Refer to the local Taylor Distributor
for availability. (For exact electrical information,
always refer to the data label of the unit.)
Air Cooled
Clearance: A minimum of 3” (76 mm) is required
around all sides. Install the deflector provided to
prevent recirculation of warm air.
Water Cooled
Water inlet and drain connections under the side of
the base, 1/2” FPT.
Net: 728 lbs. (330 kgs)
Crated: 766 lbs. (348 kgs)
Volume: 66.5 cu. ft. (1.88 cu. m.)
Models C708/C709/C716/C717
Figure 4
7
Introduction
General Installation Instructions
The following are general installation instructions.
For complete installation details, please see the
check out card.
Disconnect Switch
If the unit has no plug, a separate disconnect switch
must be installed, or another alternate means to
disconnect power must be implemented.
Air Cooled Units
C708 & C709: These units require a minimum of 6”
(152 mm) air clearance on both sides, and the back
of the unit placed against the wall to prevent
recirculation of warm air. An optional air discharge
chute is available to direct heated air exhaust
upward. No clearance is required on the right side if
the air discharge chute is used.
C716 & C717: These units require a minimum of 3”
(76 mm) air clearance around all sides. Install the
deflector provided to prevent recirculation of warm
air.
Refrigeration
Main Compressor:
Air cooled units:40 oz (1,134 g) of R404A.
Water cooled units: 38 oz (1,077g) of R404A.
Gear Alignment and Rear Shell Bearing
1.Make certain the drive shaft(s) can easily slide
in and out of the female socket on the gear
unit(s).
2.If a drive shaft is binding, the gear unit could be
out of alignment (loose). Check the bolts on the
gear unit to be sure they are tight.
3.Inspect the rear shell bearing for tightness. Be
sure the locking tab has been folded over to
prevent the nut from loosening.
Beater Rotation
REMEMBER TO DISCONNECT ALL
POWER TO THE FREEZER! Failure to follow this
instruction may result in electrocution or severe
personal injury from hazardous moving parts.
1.Remove the door assembly, beater and scraper
blades.
2.Place a magnet over the door switch in the
front panel. This deactivates the safety feature
which prevents the operation of the machine
when the door is not installed.
3.Place the power switch in the ON position.
4.Press the WASH symbol on the control panel.
This activates the beater motor only.
5.Look into the freezing cylinder. The drive shaft
should be turning clockwise. (If necessary, lift
the swing panel to view rotation.)
6.Press the WASH symbol again to stop the
beater motor.
Note: Repeat these steps for the other side on the
model C716 & C717.
To correct rotation on a single-phase unit, exchange
leads inside the beater motor. (Follow the diagram
printedonthemotor.)
To correct rotation on a three-phase unit,
interchange any two incoming power supply lines at
freezer main terminal block only.
REMEMBER TO DISCONNECT ALL
POWER TO THE FREEZER! Failure to follow this
instruction may result in electrocution or severe
personal injury from hazardous moving parts.
Introduction
8
Models C708/C709/C716/C717
Pump Motor Rotation
1.Remove the air/mix pump assembly.
2.Connect power to the freezer and place the
power switch in the ON position.
Installation of Optional Syrup Rail
X48015-27 (C708 & C709 Only)
The syrup rail can mount to only the left side of the
C708 or C709 if the top air discharge chute is not
used.
3.Press the PUMP symbol on the control panel.
This will activate the pump motor only.
4.Observe the pump ball crank. It should be
rotating counterclockwise.
If rotation is not correct, refer to the wiring diagram
on the pump motor and re-wire accordingly.
Note: Repeat these steps for the other side on the
model C716 & C717.
REMEMBER TO DISCONNECT ALL
POWER TO THE FREEZER! Failure to follow this
instruction may result in electrocution or severe
personal injury from hazardous moving parts.
Electrical Connections
Each freezer requires one power supply. Check the
data label on the freezer for fuse, circuit ampacity
and electrical specifications. Refer to the wiring
diagram provided inside the control box for proper
power connections.
The syrup rail can be mounted to either the left or
right side of the C708 or C709 units if a top air
discharge chute is used.
Perform the following steps to mount the syrup
rail on the side of a unit where a top air
discharge chute is not installed:
1.Remove the (4) panel screws as shown in
Figure 5.
In the United States, this equipment is intended to
be installed in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70-1987. The
purpose of the NEC code is the practical
safeguarding of persons and property from hazards
arising from the use of electricity. This code contains
provisions considered necessary for safety.
Compliance therewith and proper maintenance will
result in an installation essentially free from hazard!
In all other areas of the world, equipment should be
installed in accordance with the existing local codes.
Please contact your local authorities.
Stationary appliances which are not equipped with a
power cord and a plug or other device to disconnect
the appliance from the power source must have an
all-pole disconnecting device with a contact gap of at
least 3 mm installed in the external installation.
Models C708/C709/C716/C717
Figure 5
2.Install the Mounting Assembly – Syrup Rail
(X57317) using the (4) Spacers (053600) and
the (4) Screws-1/4-20X3 HEX CAP (025984)
with (4) Washers (000655).
3.Install the (4) Plugs – Square Tubing (057381)
in the ends of the Mounting Assembly – Syrup
Rail (X57317).
4.Install the (3) Holding Collars (046551) using
the (3) Screws-10-32X3/4 OVAL HD-SS.
5.Hang the Syrup Rail Assembly (048015-27) on
the holding collars.
9
Introduction
050920
Perform the following steps to mount the syrup
rail on the side of a unit where a top air
discharge chute is installed:
1.Three holes must be created in the side of the
chute as shown in Figure 6. (See the Syrup Rail
Instruction 048014-DRW included with the
Syrup Rail Kit.)
Syrup Rail Operating Instructions
1.Remove the stainless steel syrup jar with
topping pump from the syrup rail. Check the
water level in the well. Make sure the water is
filled to the indicating mark on the inside wall
(16 oz [454 g]). Check the water level daily.
2.Place the heater switch in the ON position. The
heating process will take approximately 1-1/4
hours.
3.Prepare a pail with an approved 100 PPM
sanitizing solution. USE WARM WATER AND
FOLLOW THE MANUFACTURER’S
SPECIFICATIONS.
4.Sanitize the pump by placing the entire
assembly in the solution and pump the solution
through the pump until sanitized.
5.Fill the heated and room temperature syrup jars
with toppings. Place the topping pump in the
heated syrup jar. Sanitize the ladle and place it
in the room temperature jar.
Figure 6
2.Install the (3) Nutserts (021106) in the panel.
3.Install the (3) Holding Collars (046551) using
the (3) Screws-10-32X3/4 OVAL HD-SS.
4.Hang the Syrup Rail Assembly (048015-27) on
the holding collars.
Introduction
10
Models C708/C709/C716/C717
Running Specifications
Pressures/Temperatures
The following are the Taylor Company
recommended settings for various components
within these models. The freezers in this manual use
refrigerant R404A.
Note: These settings apply to both sides of the
C716 and C717.
Air Cooled - 21 psi (145 kPa)
Water Cooled - 21 psi (145 kPa)
for a normal product of 16° to 18°F (-8.8° to -7.7°C).
Low Side (Suction)
Suction pressure equals expansion valve setting.
High Side (Discharge)
High side pressure varies for air cooled units,
depending on the ambient temperature.
Ambient TemperatureNormal Operating Head
Pressures
FCPSI
70°21.1°240 -270
(1,655 - 1,862 kPa)
80°26.7°270 -300
(1,862 - 2,069 kPa)
90°32.2°300 -340
(2,069 - 2,344 kPa)
100°37.8°340 - 380
(2,344 - 2,620 kPa)
Water Valve
Expansion Valve Adjustment (AXV)
Place your gauge on the access valve on the suction
line (located at the compressor).
Adjust higher or lower by turning the adjustment
screw. Clockwise turns raise the pressure and
counterclockwise lower the pressure.
Note: Make expansion valve adjustments with mix
in the cylinder and the freezer in the AUTO mode.
Be sure to allow adequate time for the pressure to
stabilize.
On a water cooled unit, the water valve should be
set to maintain a compressor head pressure of 255
PSI (1,758 kPa).
Water Valve Adjustment
Place your gauge on the high side access port of the
compressor. Turning the adjustment stem on the
water valve clockwise will lower the pressure.
Note: Make this adjustment with mix in the cylinder
and the freezer in the AUTO mode. Be sure to allow
adequate time for pressure to stabilize.
NOTE: MODELS C709 & C717 DO NOT HAVE MIX
PUMP KEYS.
Figure 9
050622
Introduction
12
Models C708/C709/C716/C717
C708/C709
C716/C717
Figure 10
Figure 11
Symbol Definitions
To better communicate in the International arena, symbols have replaced words on many of our operator
switches, function, and fault indicators. Your Taylor equipment is designed with these International symbols.
ITEM
1AUTO
2HEAT CYCLE
3WASH
4MIX PUMP (C708/C716 ONLY)
5MIX OUT
6STANDBY
7HEATER-RIGHT SIDE (C716/C717 ONLY)
8MIX LOW
When placed in the ON position, the power switch
allows control panel operation.
Fluorescent Display
The fluorescent display is located on the front
control panel. During normal operation the display is
blank. The display is used to show menu options
and notifies the operator if a fault is detected. On
International models, the display will indicate the
temperature of the mix in each hopper.
Adjustable Draw Handle
This unit features an adjustable draw handle(s) to
provide the best portion control, giving a better,
consistent quality to your product and controlling
food costs. The draw handle should be adjusted to
provide a flow rate of 5 to 7-1/2 oz (142 to 213 g) of
product by weight per 10 seconds. To INCREASE
the flow rate, turn the screw CLOCKWISE, and
COUNTERCLOCKWISE to DECREASE the flow
rate. (See Figure 12.)
10354
+
-
Indicator Lights
MIX LOW - When the MIX LOW symbol is
illuminated, the mix hopper has a low supply of mix
and should be refilled as soon as possible.
MIX OUT - When the MIX OUT symbol is
illuminated, the mix hopper has been almost
completely exhausted and has an insufficient supply
of mix to operate the freezer. At this time, the AUTO
mode is locked out and the freezer will be placed in
the STANDBY mode. To initiate the refrigeration
system, add mix to the mix hopper and touch the
AUTO symbol. The freezer will automatically begin
operation.
HEAT MODE - When the HEAT MODE symbol is
illuminated, the freezer is in the process of a heat
cycle.
BRUSH CLEAN COUNTER - When the BRUSH
CLEAN COUNTER display has counted down to “1”,
the machine must be disassembled and brush
cleaned within 24 hours.
Figure 12
Beater Motor Overload
C708/C709: The beater motor overload is located in
the service panel on the left side.
C716/C717: The beater motor overloads are located
in the rear panel.
The overload protects the beater motor from an
overload condition. Should an overload occur, the
reset mechanism will trip. To properly reset the
freezer, place the power switch in the OFF position.
Press the reset button firmly. Turn the power switch
to the ON position. Touch the WASH symbol and
observe the freezer’s performance.
WARNING: Do not use metal objects to
press the reset button. Failure to comply may result
in severe personal injury or death from electrical
shock.
If the beater motor is turning properly, touch the
WASH symbol to cancel the cycle. Touch the AUTO
symbol to resume normal operation. If the freezer
shuts down again, contact your authorized service
technician.
Introduction
14
Models C708/C709/C716/C717
Air/Mix Pump Reset Mechan ism
(C708 & C716 Only)
C708: The reset button for the pump is located on
the left side.
C716: The reset buttons for the pumps are located
in the rear panel.
The reset protects the pump from an overload
condition. Should an overload occur, the reset
mechanism will trip. To reset the pump, press the
reset button firmly.
WARNING: Do not use metal objects to
press the reset button. Failure to comply may result
in severe personal injury or death.
Condenser Fan Motor
The condenser fan motor is driven by the software.
The L1 to the fan is connected to the interface board
at J6-6. The condenser fan is programmed to run
any time the compressor is on and to stay running
for 30 seconds after the compressor cycles off. The
fan motor runs constantly through heat cycles
regardless of the compressor status, then cycles off
30 seconds after the compressor cycles off at the
end of the Heat Cycle and subsequent Standby
Mode.
Models C708/C709/C716/C717
15
Introduction
Notes:
Introduction
16
Models C708/C709/C716/C717
Section 2:
Controls, Systems and Operations
SUniversal Control Programming
SHeat Treatment Cycle
SHeat Treatment Graph
SFreezer Lock-out
SPower Interrupt
SPump Operation
STimers
SJumper Pins - UVC3
SBeater Stir Cycles
SSetting Viscosity
SControl Overview
SRefrigeration System - Hot Gas Treatment
SChecking and Setting Refrigeration Valves
SRefrigeration Schematic
SRefrigeration System Components
Models C708/C709/C716/C717
17
Controls, Systems and Operations
Universal Control Programming
Operating Screen
Descriptions
______________________________
The fluorescent display located in the center of the
control panel is normally blank during the daily
operation of the machine. The display is activated
when the SEL symbol or the Manager’s Menu is
selected. The display screen will also alert the
operator of specific faults detected by the control.
Note: The displays illustrated in this section are
those seen on the Models C708/C709. The Model
C716/C717 versions may vary slightly.
Power Up Memory (Initializing)
The seven segment display should display “00”
during the initializing sequence.
When the machine is powered, the control system
will initialize to perform a system check. The screen
will display “INITIALIZING”. There will be four types
of data the system will check: LANGUAGE,
SYSTEM DATA, CONFIG DATA, and LOCKOUT
DATA.
Language Initialization
is another language initialization fault. English is the
factory default setting.
System Data
System data is protected separately from the rest of
the data in memory. System data includes variables
that change frequently such as the mode the
machine is in, lockout status, serving counters, fault
codes, and others. While System Data is being
checked the following screen is displayed.
Initializing
System Data
If the System Data is corrupted, the machine is set
to OFF, the serving counters are set to zero, and the
faults are cleared. A “SYSTEM CRC ERR” fault is
set and displayed on the VFD. An acknowledgement
(SEL key) is required.
The UVC platform supports multiple languages by
keeping specific strings in battery backed RAM.
After power-up or a CPU reset, the strings are
tested to see if the language strings are present and
not corrupted. If the strings are present and not
corrupted, initialization continues. Otherwise, the
operator is prompted to select a language. While
language strings are being checked for integrity, the
following screen is displayed.
Initializing
Language
Note: If there is a language initialization fault, the
machine will force a language selection prior to the
initializing sequence. The standard menu LED’s
should light, as if it were in a menu. If a language
has been selected, the unit is powered down, the
machine should not ask for a language unless there
Configuration Data
Configuration data is separate from the rest of the
data in the memory. Configuration data is
information entered through operator and service
menus. While Configuration Data is being checked
the following screen is displayed.
Initializing
Config Data
If Configuration data is corrupted, all user and
service settings are set to defaults. A “CONFIG
CRC ERR” fault is set and displayed on the VFD.
The system will continue to operate in its previous
mode but according to default settings.
Controls, Systems and Operations
18
Models C708/C709/C716/C717
Lockout Data
Lockout data is protected separately from the rest of
the data in the memory. While the Lockout Data is
being checked, the following screen is displayed.
Once the system has initialized, the number of days
until brush cleaning is required is indicated on the
control panel. The SAFETY TIMEOUT screen will
be displayed with the alarm on for 60 seconds or
until any control symbol is touched.
Initializing
Lockout Data
If Lockout Data is corrupted, all lockout history data
is cleared. A “LOCKOUT CRC ERR” fault is
displayed.
After the memory integrity has been tested, the
Safety Timeout screen will be displayed.
Heat Cycle Data
Heat cycle data is checked separately from the rest
of the data in memory. Each individual Heat Cycle
Data record is monitored for corruption individually.
At the start of a heat cycle, the next Heat Cycle data
record is cleared and data for the heat cycle is
writtentoit.ThecurrentHeatCycleDatais
displayed as the first heat cycle record in the HEAT
CYCLE DATA menu option.
The heat cycle data records are checked for integrity
when the record is accessed, presently only through
the HEAT CYCLE DATA menu option. (For
additional Heat Cycle Data information,
see page 26.)
SAFETY TIMEOUT
ANY KEY ABORTS
Power Switch OFF
After the safety timeout has been completed and the
power switch is OFF, the following screen is
displayed.
POWER SWITCH OF F
-- = -- = -- = -- = -- = -UNIT CLEANED
Power Switch ON
When the power switch is placed in the ON position,
the control panel touch keys become operative. The
fluorescent display will be either blank or indicate
that the unit has been cleaned.
UNIT CLEANED
Models C708/C709/C716/C717
19
Controls, Systems and Operations
Heat Cycle
The HEAT symbol on the control panel is illuminated
throughout the heat treatment cycle. Two warning
messages will be displayed on the screen. “DO NOT
DRAW” will be displayed when the mix temperature
is below 130°F (54.4°C).
International Models Only:
Some International models will continuously display
the temperature of the mix hopper when the power
switch is in the ON position.
HOPPER21.0
UNIT CLEANED
DO NOT DRAW
When the temperature of the mix is above 130°F
(54.4°C) the screen will display a message
indicating that HOT PRODUCT is in the machine.
HOT PRODUCT
DO NOT attempt to draw product or
disassemble the unit during the HEAT cycle. The
product is hot and under extreme pressure.
In the HEAT cycle, the mix temperature in the
hopper and freezing cylinder must be raised to
151°F (66.1°C) within 90 minutes.
When the heating phase is complete, the freezer
goes into the holding phase of the cycle. The holding
phase will keep the temperature above 151°F
(66.1°C) for a minimum of 35 minutes.
If the control is set for international configuration, the
following screen will appear when the heat symbol is
touched.
ARE YOU SURE
>Yes
No
Use the up or down arrow symbol to move the
cursor to “YES”. Touch the SEL symbol to
immediately start a heat cycle.
Note: The machine must be in AUTO or STANDBY
and have sufficient mix in the hopper before the
machine can successfully enter the HEAT mode of
operation.
Manager’s Menu
______________________________
The Manager’s Menu is used to enter the operator
function displays. To access the Menu, touch the
center of the CONE symbol on the control panel.
The arrow symbols, the SEL symbol and the CONE
symbol will be lit when the ACCESS CODE screen
is displayed.
13201
The final phase of the heat treatment cycle is the
cooling phase. The freezer must cool the mix below
41°F (5°C) within 90 minutes.
When the entire heat cycle has been completed, the
HEAT symbol will no longer be illuminated. The
machine will enter the STANDBY mode (STANDBY
symbol illuminates). The machine can be placed in
AUTO or left in STANDBY.
Controls, Systems and Operations
20
®
SEL
Figure 13
Models C708/C709/C716/C717
In the Menu program, the arrow symbols and the
SEL symbol will function as menu keys.
SUP ARROW - increases the value above the
cursor and is used to scroll upward in text
displays.
SDOWN ARROW - decreases the value
above the cursor and is used to scroll
downward in text displays.
SSEL - advances the cursor position to the
right and is used to select menu options.
There is a two minute time-out in effect during the
Manager’s Menu. While in the Manager’s Menu, if
no activity occurs within a two minute period, the
display will exit to the Main Menu. There is one
exception to this time-out, and that is the Current
Conditions Display.
If an incorrect number is entered for the access
code, the display will exit the Menu program when
the SEL symbol is touched.
13202
®
SEL
Figure 14
Note: The machine will continue operation in the
mode it was in when the Menu was selected. However,
the control keys will not be lit and are non--functional
when the Manager’s Menu is displayed. The control
keys are functional in the Manager’s Menu when the
CURRENT CONDITIONS screen is displayed. (See
CURRENT CONDITIONS on page 28.)
Entering Access Code
With the ACCESS CODE screen on the display, use
the SEL symbol to set the first code number in the
cursor position. When the correct number is
selected, touch the SEL symbol to move the cursor
to the next number position.
ENTER ACCESS CODE
83 0 9
__
Continue to enter the proper access code numbers
(8309) until all four numbers are displayed, then
touch the SEL symbol. The Manager’s Menu list will
display on the screen, provided the correct access
code is entered.
Manager Menu Options
Touch the ARROW symbols to move up or down
through the Menu. Select a Menu option by touching
the SEL symbol. Exit the Menu program by selecting
EXIT FROM MENU or touch the CONE symbol.
The following menu options are listed in the
Manager’s Menu.
EXIT FROM MENU
RESET DRAW COUNTER
SET CLOCK
AUTO HEAT TIME
AUTO START TIME
STANDBY MODE
BRUSH CLEAN CYCLE
MIX LEVEL AUDIBLE
F AULT DESCRIPTION
LOCKOUT HISTORY
HEAT CYCLE SUMMARY
HEAT CYCLE DATA
SYSTEM INFORMATION
CURRENT CONDITIONS
Models C708/C709/C716/C717
21
Controls, Systems and Operations
Exit From Menu
Selecting “EXIT FROM MENU” will exit the
Manager’s Menu and the return the control panel
symbols to normal operation.
To change the date or time, select the SET CLOCK
option in the menu. Touch the UP arrow symbol to
advance the arrow from Exit to Change, then touch
the SEL symbol to select the Change option.
Reset Draw Counter
The SERVING COUNTER screen is used to check
or reset the number of servings dispensed from the
machine. The SERVING COUNTER will
automatically reset to zero when the machine is
brush cleaned.
SERVINGS COUNTER
0
> Next
Reset the SERVING COUNTER by touching the
SEL symbol to advance to the next screen. Touch
the UP arrow symbol to move the arrow (>) to YES
and touch the SEL symbol. The servings counter will
reset to zero and exit back to the Manager’s Menu.
RESET DRAW COUNTER
Yes
>No
Set Clock
SET CLOCK
12:012/21/2004
Change
>Exit
Change the time by touching the UP arrow with the
cursor under the hour position. Move the cursor to
the minutes position by touching the SEL symbol.
Once the correct minutes are entered, touch the
SEL symbol to advance the cursor to the month.
SET CLOCK
:012/21/2004
12
>Exit
Enter the correct month, day, and year. Then touch
the SEL symbol to advance to the DAYLIGHT
SAVING TIME screen.
The SET CLOCK option allows the Manager to
adjust the control clock date and time. The date and
time may only be changed after the freezer has
been manually cleaned but before it has been
placed in the AUTO or STANDBY mode. The
following message will be displayed if the SET
CLOCK option is selected when the machine is not
in a brush clean state.
SET CLOCK
12:012/21/2004
NO CHANGES ALLOWED
Press Any Key
Controls, Systems and Operations
DAYLIGHT SAVING TIME
ENABLED
> Enable
Disable
The Daylight Saving feature, when enabled, will
automatically adjust the control clock for daylight
saving time. To disable the Daylight Saving Time
feature, touch the DOWN arrow to move the arrow
to “Disable”. Then touch the SEL symbol to save the
new setting.
22
Models C708/C709/C716/C717
Auto Heat Time
The AUTO HEAT TIME screen allows the Manager
to set the time of day in which the heat treatment
cycle will start.
AUTO HEAT TIME
00:00
Change
>Exit
To set the AUTO HEAT TIME, touch the UP arrow
symbol to move the arrow to “Change”. Then touch
the SEL symbol. The screen will display the time
with the cursor under the hour position.
AUTO HEAT TIME
:00
00
Touch the arrow symbols to increase or decrease
the hour to the desired setting. Then move the
cursor to the minutes position by touching the SEL
symbol. Adjust the setting for minutes. Then touch
the SEL symbol to save the setting and return to the
AUTO HEAT TIME screen. Touch the SEL symbol
to exit the screen and return to the Menu.
AUTO START TIME
00:00
Change
>Exit
Program the AUTO START TIME by touching the
UP arrow symbol to move the arrow to “Change”.
Touch the SEL symbol to advance to the next
screen.
AUTO START TIME
:00
00
Use the arrow symbols to program the AUTO
START TIME by increasing or decreasing the hour
setting above the cursor. Touch the SEL symbol to
advance the cursor and program the minutes
setting. Touch the SEL symbol to return to the
previous screen with the new time setting displayed.
Touch the SEL symbol to exit the screen and return
to the Menu.
Auto Start Time
The AUTO START TIME option allows the Manager
to set the time of day at which the machine
automatically enters the AUTO mode from the
STANDBY mode. The machine must be in the
STANDBY mode without a freezer lock condition in
order to AUTO start at the programmable time. The
AUTO START TIME can also be Disabled and
require starting the AUTO mode manually.
AUTO START TIME
DISABLED
Enable
> Disable
Enable the AUTO START TIME by touching the UP
arrow symbol to move the arrow up to Enable.
Touch the SEL symbol to advance to the next
screen.
Standby Mode
The STANDBY option is used to manually place the
machine in the standby mode during long, no draw
periods. Select the STANDBY screen from the
Manager’s Menu. Touch the SEL symbol to activate
Standby. Standby may also be entered by touching
the STANDBY key when not in the Manager’s Menu.
Discontinue Standby operation by exiting the
Manager’s Menu and select the AUTO mode.
STANDBY MODE
> EXIT
Models C708/C709/C716/C717
23
Controls, Systems and Operations
Brush Clean Cycle
The BRUSH CLEAN CYCLE option allows the
Manager to select the maximum number of days
between brush cleaning the machine. The brush
clean cycle may only be changed after the freezer
has been manually cleaned but before it has been
placed in the AUTO or STANDBY mode.
The following message will be displayed if the
BRUSH CLEAN CYCLE option is selected when the
machine is not in a brush clean state.
BRUSH CLEAN CYCLE
No Changes Allowed
Press any Key
Disable the audible tone feature by touching the
DOWN arrow symbol to move the arrow to
“Disable”. Touch the SEL symbol to save the new
setting and return to the Menu. The control panel
icons for Mix Low and Mix Out will illuminate as the
mix level drops in the hopper, but the audible tone
will be disabled.
Fault Description
The FAULT DESCRIPTION display will indicate if
there is a fault with the freezer and where the fault
occurred. When no faults are detected, the following
screen will be displayed.
Change the number of days between brush clean
intervals by using the arrow symbols. Touch the SEL
symbol to save the setting and exit back to the
Menu. The number of days displayed on the brush
clean counter will change to the new setting.
BRUSH CLEAN CYCLE
TIME14DAYS
Always comply with local guidelines on the number
of days allowed between brush clean cycles.
Mix Level Audible
The MIX LEVEL AUDIBLE option, when enabled,
will alert the operator with an audible tone when
there is Mix Low or Mix Out condition. The following
screen is displayed upon selecting this option.
MIX LEVEL AUDIBLE
> Enable
Disable
FAULT DESCRIPTION
NO FAULT FOUND
Touch the SEL symbol to display the next fault
found or return to the Menu if no other faults exist.
Touching the SEL symbol any time faults are
displayed will clear the faults, if corrected, upon
returning to the Menu screen.
Listed below are the variable messages which will
appear, along with an explanation for the corrective
action.
NO FAULT FOUND - There was no fault found in
the freezer. Nothing will appear on the screen after
this variable message appears.
BEATER OVERLOAD - Place the power switch in
the OFF position. Press the beater reset button
firmly. Place the power switch in the ON position
and restart in AUTO.
HPCO COMPRESSOR - Place the power switch in
the OFF position. Wait 5 minutes for the machine to
cool. Place the power switch in the ON position and
restart in AUTO.
Controls, Systems and Operations
24
Models C708/C709/C716/C717
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.