1.3 Status Indication ..................................................................................................................... 57
1.4 Sequence of Operation ............................................................................................................. 58
1.5 Theory of Operation................................................................................................................. 60
Information and specifi cations outlined in this manual in effect at the
time of printing of this manual. Manufacturer reserves the right to
discontinue, change specifi cations or system design at any time without
notice and without incurring any obligation, whatsoever.
3
1 - INTRODUCTION
1.1 Designated Use
• Hot water heating boiler.
• Indoor installation.
• Closet or alcove installation.
• Direct vent boiler.
• For use with natural gas or liquefi ed petroleum gases
(LP/propane).
1.2 The unit MUST NOT:
• Directly heat potable water. Indirect heating is acceptable.
• Heat water with non-hydronic heating system chemicals
present (example, swimming pool water).
• Exceed 50 psig (344 kPa) system pressure.
• Exceed 195°F (90.5°C) system design temperature.
1.3 Operational Features
• Modulating: 20-100%.
• Integral Dual Limit.
• Integral Low Water Cutoff (with test button).
• Outdoor Temperature Reset.
• Integral Multiple Boiler Control.
4
!
This is the safety alert symbol. Symbol alerts you to
potential personal injury hazards. Obey all safety messages
following this symbol to avoid possible injury or death.
2.2
Become familiar with symbols identifying
potential hazards.
2 - IMPORTANT SAFETY INFORMATION
2.1 General
Boiler installation shall be completed by qualifi ed agency.
See glossary for additional information.
WARNING
!
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
2.2
Become familiar with symbols identifying
potential hazards.
This is the safety alert symbol. Symbol alerts you to
potential personal injury hazards. Obey all safety messages
following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in death or serious injury
2.3 Installation shall conform to requirements
of authority having jurisdiction or in absence of
such requirements:
• National Fuel Gas Code, ANSI Z223.1/NFPA 54
• National Electrical Code, NFPA 70.
2.4Where required by authority having
jurisdiction, installation shall conform to
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1.
Additional manual reset low water cutoff may be required.
2.5 Requirements for Commonwealth of
Massachusetts:
Boiler installation must conform to Commonwealth of
Massachusetts code 248 CMR which includes but is not
limited to:
• Installation by licensed plumber or gas fi tter.
.
!
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal
injury.
5
3 - COMPONENT LISTING
Return Water From Heating System (In)
(see
page 8)
-
Connection supplied at bottom of boiler.
Low Voltage Terminal Strip
(see page 8) -
Connection of all low voltage wiring, including
thermostat. See section
8.
Heat Exchanger Pump
Gas Shutoff Valve
- Fuel supply isolation
during servicing. See section 7.3 page 26.
Combustion Air Blower
- Delivers
proper quantity of combustion air, receives fuel from
gas valve, mixes air and fuel sending mixture to burner
for combustion.
Gas (Control) Valve
- Delivers
proper quantity of fuel to Combustion Air Blower.
See section 7.
High Temperature Supply Switch
Low Water Cutoff
Senses inadequate
quantity of water. Turns off boiler before damage can
occur.
8
Gas Connection
See section 7.
Control Module
3.1 Component Listing
1.
User Interface (see Appendix A) - Displays
information regarding boiler condition. Allows
adjustment of boiler operating parameters. NOTE: Does
not replace thermostat used to control central heating
space.
2.
Combustion Air Inlet (2"/3") (see page 7 & 8)
3.
Return Water From Heating System (In)
page 8)
4.
Low Voltage Terminal Strip
Connection of all low voltage wiring, including
thermostat. See section
5.
Igniter (see page 8)
6.
Flame Sensor (see page 8)
7.
Sight Glass (see page 8) - Permits observation of
burner fl ame.
-
Connection supplied at bottom of boiler.
(see page 8) -
8.
(see
20.
Gas (Control) Valve (see page 8)
proper quantity of fuel to Combustion Air Blower.
See section 7.
21.
High Temperature Supply Switch (see page 8)
22.
Low Water Cutoff (see page 8) --
quantity of water. Turns off boiler before damage can
occur.
23.
Safety Relief Valve (see pages 7 & 8) - Factory
supplied, Field installed. See section 5.3 page 11.
24.
High Voltage Junction Box (see page 8) - For
connection of 120V components. See section
25.
Vent Connector (see pages 7 & 8) - See section 6.
26.
Gas Connection (see page 8)
27.
Wall Hanging Support Bracket (see page 7) -
Integral to boiler. Allows wall mounting when used
with supplied wall mounting bracket. See section 4.
- Delivers
Senses inadequate
See section 7.
8.
8.
Burner (see page 32)
9.
Heat Exchanger (see page 8)
10.
Condensate Collector (see page 8)
11.
Return Temperature Sensor (see page 8)
12.
Drain Valve (see page 12)
13.
Heat Exchanger Ball Valve (see page 8)
14.
Supply Water Outlet to Heating System (Out)
(see page 8) - Connections supplied for connecting
from bottom of boiler. See section 5.
15.
Vent Temperature Sensor (see page 8)
16.
Condensate Drain (see Section 6.6 page 24) - Boiler
produces a liquid (condensate) as a by-product of
combustion. Condensate must be piped to appropriate
drain.
17.
Heat Exchanger Pump (see page 8)
28.
Air Vent (see page 7 & 8)
29.
Control Module (see page 8)
30.
Transformer (see page 8) - Supplies 24V power to low
water cutoff.
31.
Pressure Test Port - (see page 8)
32.
Combustion Analysis Test Port - (see page 8)
33.
Return Water Sensor - (see page 8)
34.
User Interface - (see page 8)
18.
Gas Shutoff Valve (see page 8)
during servicing. See section 7.3 page 26.
19.
Combustion Air Blower (see page 8)
proper quantity of combustion air, receives fuel from
gas valve, mixes air and fuel sending mixture to burner
for combustion.
- Fuel supply isolation
- Delivers
6
3 - COMPONENT LISTING
SAFETY RELIEF VALVE
AIR VENT
WALL HANGING
SUPPORT
BRACKET
FIGURE 3-1 Boiler Components (Viewed from Back of Boiler)
VENT CONNECTOR
COMBUSTION
AIR INLET
WALL HANGING
SUPPORT
BRACKET
AIR VENT
SAFETY RELIEF VALVE
NOTE:
See Section 5-3
For Safety Relief
Valve Piping
Instructions
FIGURE 3-2 Upper and Lower Jacket Latch
(Viewed from front of boiler)
Jacket Latch
Lift Jacket up,
engage jacket with chassis
push down.
7
3 - COMPONENT LISTING
GAS SHUTOFF
VALVE
COMBUSTION
AIR
BLOWER
GAS (CONTROL)
VALVE
LOW WATER
CUTOFF
SAFETY RELIEF VALVE
AIR VENT
HEAT EXCHANGER
PUMP
HEAT
EXCHANGER
RETURN WATER
FROM HEATING
SYSTEM (IN)
SUPPLY WATER TO
HEATING SYSTEM
(OUT)
LOW VOLTAGE
TERMINAL STRIP
IGNITER
SIGHT
GLASS
GAS CONNECTION
CONDENSATE
DRAIN
COMBUSTION
ANALYSIS TEST
PORT
HIGH VOLTAGE
JUNCTION BOX
HEAT EXCHANGER
BALL VALVE
USER INTERFACE
3 - COMPONENT LISTING
FIGURE 3-4 Boiler Components (View from Front of Boiler)
AIR VENT
HIGH TEMPERATURE
SUPPLY SWITCH
LOW WATER
CUTOFF
GAS (CONTROL)
VALVE
SAFETY RELIEF VALVE
VENT CONNECTOR
NOTE:
See Section 5
For Piping
Instructions
COMBUSTION
AIR INLET
IGNITER
FLAME
SENSOR
SIGHT
GLASS
COMBUSTION
AIR
BLOWER
GAS SHUTOFF
VALVE
(SHOWN IN OPEN
POSITION)
HEAT EXCHANGER
PUMP
COMBUSTION
ANALYSIS TEST
PORT
VENT
TEMPERATURE
SENSOR
CONDENSATE
COLLECTOR
LOW VOLTAGE
TERMINAL STRIP
PRESSURE
TEST PORT
USER INTERFACE
CONTROL
MODULE
Fuse and
Holder
HEAT
EXCHANGER
TRANSFORMER
RETURN WATER
SENSOR (Located
behind piping)
CONDENSATE
DRAIN
HIGH VOLTAGE
JUNCTION BOX
SUPPLY WATER TO
HEATING SYSTEM
(OUT)
HEAT EXCHANGER
BALL VALVE
RETURN WATER
FROM HEATING
SYSTEM (IN)
GAS CONNECTION
8
4 - LOCATING BOILER
4.1 Boiler Location Considerations
• Ambient room temperature always above 32°F (0°C) to
prevent freezing of liquid condensate.
• Approved for installation in closets.
• Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during operation and
service (circulator replacement, condensate trap, control
replacement, etc.).
• Wall mounting.
• Wall must be plumb and capable of supporting boiler
weight plus 60 lbs (28 kg). See Table 1, page 2.
• Wall mounting. See section 4.2.
• Access to outdoors to meet minimum and maximum
pipe lengths for combustion air and vent piping. See
section 6.
• Disposal of condensate. See section 6.
• Drainage of water (or water - antifreeze solution) during
boiler service or from safety relief valve discharge. See
section 5.
• Access to system water piping, gas supply, and electrical
service. See sections 5, 7 and 8.
FIGURE 4-1 Clearance to Combustible Materials
A
B
F
FLOOR
E
A
C
F
A
• Clearances to combustible materials and service
clearances. See Table 2 and fi gure 4-1.
• Multiple Boilers can be wall mounted, placed side by
side,orback to back.
FIGURE 4-2 Wall Mount Bracket Engaged with
Bracket on Boiler
Center brackets. Avoid
overhang on sides of wall
mount bracket.
4 Slots for attaching Wall
Mount Bracket to Studs
4.2 Pre-pipe supply and return water connections
with factory fi ttings before wall mounting.
4.3 Wall Mounting
Mount boiler on wall using wall mounting bracket included
with unit.
• Structure must be capable of supporting boiler weight
plus 60 lbs (28 kg). See Table 1, page 2.
• Wall mount bracket has 4 slots allowing mounting on
two (2) wall studs spaced at 11½" to 16½" on center.
See fi gure 4-2.
• Boiler includes (4) 3/8" x 3" lag screws and (4) washers
for attaching wall mount bracket to wood studs. Field
source appropriate fasteners for other wall constructions
(masonry, concrete).
• Attach wall mount bracket level on wall.
• Boiler must engage with wall mount bracket.
• Avoid overhang on sides of wall mount bracket. Verify
boiler bracket is centered on wall bracket. See fi gure
4-2.
!
CAUTION
Boiler weight exceeds 75 pounds (34 kg). Do not
lift boiler onto wall without assistance.
10
5 - HYDRONIC PIPING
5.1 General
• Install piping in accordance with authority having jurisdiction.
NOTICE
Use two (2) wrenches when tightening and fi tting
to pipe boiler's threaded fi ttings. Boiler's internal
piping can be damaged if subjected to excessive
torque.
• Support system piping and safety relief valve discharge
piping. Boiler's internal piping and wall mount bracket can
be damaged if subjected to excessive weight.
• Size central heating pump (and domestic hot water pump,
if used) for system requirements only. Heat exchanger
pump compensates for pressure drop through boiler
internal piping and heat exchanger.
• Thoroughly clean and fl ush system before connecting to
boiler.
5.2 Special Conditions
• System piping exposed to freezing conditions: Use
inhibited proplyene glycol solutions certifi ed by fl uid
manufacturer for use with closed water heating system.
Do not use automotive or ethylene glycol.
!
WARNING
• Poison hazard. Ethylene glycol is toxic. Do not use
ethylene glycol.
• Never use automotive or standard glycol antifreeze,
even ethylene glycol made for hydronic systems.
• Ethylene glycol can attack gaskets and seals used in
hydronic systems.
• Use only inhibited proplyene glycol solutions certifi ed
by fl uid manufacturer as acceptable for use with closed
water heating system.
• Thoroughly clean and fl ush any system that used glycol
before installing new Boiler.
• Provide user with Material Safety Data Sheet (MSDS)
on fl uid used.
NOTICE
Do not expose boiler and condensate piping to
freezing temperatures.
• Boiler installed above radiation level (or as required by
authority having jurisdiction). Integral low water cutoff
provided in boiler. See page 6.
• Boiler used in connection with refrigeration system.
Install piping in parallel with boiler, with appropriate
valves to prevent chilled medium from entering boiler.
• System piping connected to heating coils located in air
handling unit exposed to refrigerated air circulation.
Install fl ow control valves or other automatic means to
prevent gravity circulation of boiler water during cooling
cycle.
5.3 Safety Relief Valve and Air Vent
NOTICE
Boiler rated at 50 psig (345 kPa) maximum
allowable working pressure. Boiler provided with
30 psig (206 kPa) safety relief valve. Field source
safety relief valve for system pressures greater than
30 psig (206 kPa). Temperature Pressure Gauge
and Air Vent satisfactory for 30-50 psig (206-345
kPa) operation.
FIGURE 5-1 Safety Relief Valve & Air Vent (View
from front of boiler)
Safety Relief
Valve
Air Vent
3/4"F x 3/4"M
NPT Tee
3/4 NPT
3/4" x 1/4" NPT
90° Elbow
3/4" NPT
Close Nipple
• Install safety relief valve and air vent using pipe fi ttings
provided with boiler. See fi gure 5-1
• Install safety relief valve with spindle in vertical position.
• Do not install shutoff valve between boiler and safety
relief valve.
Position Air Vent and Safety Relief Valve
to provide space for discharge piping.
11
5 - HYDRONIC PIPING
!
WARNING
• Install discharge piping from safety relief valve. See
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
FIGURE 5-2 Safety Relief Valve Discharge Piping
Safety Relief Valve
5.4 Trim Piping
• Temperature - Pressure Gauge. Install temperature
fi gure 5-2.
• Use ¾" or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C)
or greater.
• Individual boiler discharge piping shall be independent
of other discharge piping.
• Size and arrange discharge piping to avoid reducing
safety relief valve relieving capacity below minimum
relief valve capacity stated on rating plate.
• Run pipe as short and straight as possible to location
protecting user from scalding and properly drain
piping.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve
outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
pressure gauge using nipple, tee and bushing provided
with boiler. See fi gure 5-3.
Check Local Codes
For Maximum
Distance To Floor
FIGURE 5-3 Temperature Pressure Gauge and
Drain Valve Installations
Gas Supply
• Drain Valve. Install drain valve using nipple, tee and
bushing provided with boiler. See fi gure 5-3.
5.5 System Piping
• Systems with automatic fi ll valves require back fl ow
prevention device.
• Single boiler system. See fi gures 5-4, 5-5, 5-6, 5-7 for
general guidance. Additional considerations:
• Control system designed for single central heating
pump. Installer responsible for integration of
multiple central heating pumps.
• Control system allows domestic hot water
prioritization. Function could be lost if central
heating pump not directly connected to control
system.
• Multiple boiler system. See fi gure 5-8 for general
guidance. Additional considerations:
• Control system requires equivalent water
temperatures entering each boiler to properly
sequence and adjust system supply temperature.
• Install multi boiler sensor kit. See "Parts, Kits &
Optional Accessories" manual for part number.
Temperature Pressure
Gauge shown at
System Supply
Connection
Drain Valve shown
at System Return
Connection to Boiler
12
5 - HYDRONIC PIPING
NOTICE
Illustrations are meant to show system piping
concept only. Installer responsible for all equipment
and detailing required by authority having
jurisdiction.
FIGURE 5-4 System Piping
Safety Relief Valve
Piping Legend
Check Local Codes
For Maximum
Distance To Floor
System
Supply
FLOOR
System
Return
13
5 - HYDRONIC PIPING
5-5 TWO-PIPE ZONED SYSTEM WITH VALVES
DHW
Pump
CH/System
Pump
Heat exchanger
ball valve open
(as shipped)
5-6 TWO-PIPE ZONED SYSTEM WITH PUMPS
DHW
Pump
Zone
Pump
3/8"/10mm
Open End
Wrench
Heat exchanger
ball valve open
(as shipped)
3/8"/10mm
Open End
Wrench
14
5 - HYDRONIC PIPING
5-7A SINGLE BOILER USING PRIMARY/SECONDAY PUMPING
12"/305mm Max. apart
12"/305mm
Max. apart
CH/System
Existing closely spaced tees
in primary system loop
Limit length
Pump
Heat exchanger
ball valves closed
5-7B SINGLE BOILER USING PRIMARY/SECONDAY PUMPING
to
5'/1.6 m
3/8"/10mm Open
End Wrench
12"/305mm Max. apart
12"/305mm
Max. apart
CH/System
Pump
Heat exchanger
ball valve open
Existing closely spaced tees
in primary system loop
Limit length
to
5'/1.6 m
3/8"/10mm Open
End Wrench
15
5 - HYDRONIC PIPING
5-8 TYPICAL MULTIPLE BOILER PIPING - (See Multiple Boiler Guide)
DHW
Pump
CH/
System
Pump
12"/305mm Max. apart
System
T emperature
Sensor
Size common piping
according to
maximum heat
capacity of
entire system
Up to 16
boilers
All heat exchanger
ball valves closed
3/8"/10mm Open
End Wrench
(See Multiple Boiler Guide)
16
6 - COMBUSTION AIR AND VENT PIPING
6.1 General
This boiler requires a dedicated direct vent system.
Install combustion air and vent piping in accordance
with these instructions, authority having jurisdiction,
and
National Fuel Gas Code, ANSI 223.1/NFPA 54.
Vent connections serving appliances vented by natural draft
shall not be connected into any portion of mechanical draft
systems operating under positive pressure.
Install vent system in accordance with these instructions.
6.2 Removal of Existing Boiler From Common
Vent System
When existing boiler is removed from common venting
system, common venting system is likely to be too large for
proper venting of appliances remaining connected to it.
After removal of existing boiler, following steps shall
be followed with each appliance remaining connected to
common venting system placed in operation, while other
appliances remaining connected to common venting system
are not in operation:
• Seal any unused openings in common venting system.
• Visually inspect venting system for proper size and
horizontal pitch. Determine there is no blockage or
restrictions, leakage, corrosion and other defi ciencies
which could cause an unsafe condition.
• When practical, close all building doors, windows, and
all doors between space in which appliances remaining
connected to common venting system are located and
other spaces of building. Turn on clothes dryer and any
appliance not connected to common venting system.
Turn on exhaust fans, such as range hoods and bathroom exhaust so they will operate at maximum speed.
Do not operate summer exhaust fan. Close fi replace
dampers.
• Turn on appliance being inspected. Follow lighting
instructions. Adjust thermostat so appliances will operate
continuously.
• Any improper operation of common venting system
should be corrected so installation conforms with National
Fuel Code, ANSI Z223.1/NFPA 54. When re-sizing any
portion of common venting system, common venting
system should be re-sized to approach minimum size as
determined using appropriate tables in Chapter 13 of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54.
6.3 Materials
• See Table 3
Table 3 - Combustion air and vent pipe fi ttings
must conform with the following:
ItemMaterial Standards
PVC schedule 40ANSI/ASTM D1785
PVC - DWVANSI/ASTM D2665
CPVC schedule 40
Vent Pipe
and Fittings
Pipe
Cement/
Primer
• IPEX is approved vent manufacturer in Canada listed
to ULC-S636.
• IPEX System 636 Cements and Primers are approved
in Canada listed to ULC-S636.
SDR-21 & SDR-26 PVCANSI/ASTM D2241
ABS-DWVANSI/ASTM D2661
Schedule 40ANSI/ASTM F628
PVC ANSI/ASTM D2564
CPVCANSI/ASTM F493
Schedule 40 ABSANSI/ASTM D2235
DO NOT USE CELLULAR (FOAM) CORE PIPE
ANSI/ASTM D1784/
F441
• Test for spillage at draft hood relief opening after 5
minutes of main burner operation. Use fl ame of match or
candle, smoke from cigarette, cigar or pipe.
• Determine each appliance remaining connected to
common venting system properly vents when tested
as outlined above. Then return doors, windows,
exhaust fans and any other gas-burning appliance to
their previous condition of use.
!
WARNING
Use of cellular core PVC for venting fl ue gas could
result in death, serious injury.
17
6 - COMBUSTION AIR AND VENT PIPING
6.4 Pipe Installation
• Minimum and maximum combustion air and vent pipe
lengths listed in Table (3). Pipe length counted from
combustion air connector to termination.
• Install fi eld-sourced 2" to 3" transition, if used, in vertical
section at combustion air inlet and vent connector.
• 90° elbows equivalent to 5.0 ft (1.6 m). 45° elbows
equivalent to 3.5 ft (1.1 m). 2" to 3" transition has no
equivalent length.
• Slope vent pipes minimum 1/4" per foot (21 mm/m)
back toward boiler. Support horizontal sections to
prevent sags capable of accumulating condensate.
• Support piping in accordance with pipe manufacturer's
instruction and authority having jurisdiction. In absence
of manufacturer's instruction use pipe hooks, pipe
straps, brackets, or hangers of adequate and strength
located at intervals of 4 ft (1.2m) or less. Allow for
expansion/contraction of pipe.
• Combustion air and vent piping must be air tight and
water tight.
• Certifi ed vent system components must NOT be inter-
changed with other vent systems or unlisted pipe/fi ttings.
6.5 Termination
• Terminate combustion air and vent pipes with fi ttings or
concentric vent kit.
• See "Parts, Kits and Optional Accessories" manual
for concentric vent kit part numbers.
• Use horizontal pipe for vent and 90° elbow for
combustion air termination when using fi ttings.
• Terminate combustion air and vent pipes in same
atmospheric pressure zone through exterior sidewall or
roof.
• Locate combustion air termination as far as possible
from swimming pool, swimming pool pump house, and
other sources of airborne chlorine.
• Locate combustion air and vent terminals as required by
authority having jurisdiction.
!
WARNING
Vent extending through exterior wall shall not
terminate adjacent to wall or below building
extensions such as eaves, balconies, parapets or
decks. Failure to comply could result in death or
serious injury.
Table 4 - Combustion Air and Vent Piping Length
Combustion Air and Vent Pipe Equivalent Length
2” Pipe 3” Pipe
Model050075/100075/100150/200
Min.
Max.
6 ft.
(1.8 m)
100 ft.
(30.5 m)
6 ft.
(1.8 m)
50ft.
(15.2 m)
6 ft.
(1.8 m)
100 ft.
(30.5 m)
6 ft.
(1.8 m)
100 ft.
(30.5 m)
1 - 90° elbow = 5 ft (1.6 m)
1 - 45° elbow = 3.5 ft (1.1 m)
1- 2" x 3" adapter = 0 ft (0 m)
Note: Concentric Vent Kit=5 ft (1.6m) equivalent length
For Example: Boiler can be installed on outside wall and vented with
1-90° elbow and 1 ft (0.30 m) of vent pipe.
18
6 - COMBUSTION AIR AND VENT PIPING
FIGURE 6-1
12" (30 cm)
Minimum
8" (21 cm)
Minimum
VentCombustion
12" (30 cm) Minimum above
anticipated snow line
FIGURE 6-2
3" (8 cm)
Maximum
Air
15" (38 cm)
Maximum
Roof Line
Roof
Terminations
3" (8 cm) Maximum horizontal
separation between combustion air
intake and vent of same appliance.
8" (21 cm) Minimum vertical
separation between combustion
air intake and vent of different
appliances.
15" (38 cm) Maximum horizontal
length of vent.
Maximum vent/intake between
different appliances 12" (30cm).
Maximum allowable total vertical
vent length with outside exposure is
10 ft.(3.05m).
Abandoned unused masonry
chimney may be used as chaseway
for combustion air and vent. Both
combustion air and vent pipe must
exit above top of chimney with
clearances as shown in fi gure 6-1.
12" (30 cm)
Minimum from
overhang
See snow & ice
page 23
FIGURE 6-3
3" (8 cm)
Minimum
separation
12" (30 cm) Separation
between bottom of
combustion air intake
and bottom of vent
Vent
Combustion Air
12" (30cm)
Minimum
separation
Side Wall
Terminations
3" (8 cm) Minimum horizontal
separation between combustion air
intake and vent terminations.
8" (21 cm) Minimum vertical
separation between combustion air
intake and vent terminations.
12" (30 cm) Separation between
bottom of combustion air intake and
bottom of vent.
Multiple terminations as shown in
6-1, 6-2, and 6-3 must be a minimum
of 12” (30 cm) horizontally between
vent of one termination and air intake
of next appliance.
Maximum allowable total outside
exposure vent length equals 10 ft.
(3.05m).
Maintain a pitch of 1/2" per ft.
(42mm/m) outside exposure back to
boiler to ensure proper condensate
drainage for horizontal runs.
See snow & ice
page 23
Combustion Air
Vent
19
6 - COMBUSTION AIR AND VENT PIPING
FIGURE 6-4
Combustion
Air
1" (2.54cm)
Maximum
1"(2.54cm) Maximum
Vent
FIGURE 6-7
FIGURE 6-5
1" (2.54cm)
Maximum
* See Note
Below
Combustion
Air
*Must be less than 4" or greater than 24" Horizontal distance between end bells of each air intake to prevent fl ue
gas recirculation.
Note: Securing strap must
be fi eld installed to prevent
movement of termination
kit in side wall
Roof overhang
12" (30cm) Minimum
36"(0.9m) Minimum
Maintain 12"(30cm)
Vent
clearance above
clearance above highest
highest anticipated
anticipated snow level or
snow level or grade
Maintain 12"
grade
OD 3½" (
OD 4½" (11.4cm) - 3" (7.6cm) kit
Combustion Air
Elbow fi eld
supplied
** Note Overall length may be modifi ed by cutting or
extending both combustion air and vent pipes. 12" is
minimum allowable length and 60" is maximum allowable
length for this dimension. SDR-26 PVC (D2241) only may
be used for extending pipes. Do not use Schedule 40 PVC
or use couplings to extend pipes. Dimension will change if
intake/vent pipes are lengthened or shortened.
8.9cm)
- *2" (
5.0cm)
kit
**See
Note
*2 or 3" (5.0 or 7.6cm) Diameter
PVC intake/combustion air
*2" (
5.0cm)
Diameter = 41" Length (1.0m))
46-3/4" (1.2 m)
3" (7.6cm) Diameter = 47" Length (1.2m)
Combustion Air
Vent
1"(2.54cm)
Maximum
* Note: 2" For use with models 050/075/100.
3" For use with models 075/100/150/200
20
6 - COMBUSTION AIR AND VENT PIPING
Concentric
Vent Roof
Terminations
Glue inner vent pipe to prevent
recirculation.
Maintain 12" (30 cm) minimum
clearance above highest anticipated
snow level. Maximum of 24"(0.61m)
above roof.
Support must be fi eld installed to
secure termination kit to structure.
Avoid locations where snow may drift
and block vent and combustion air. Ice
or snow may cause boiler to shut down
if vent or combustion air becomes
obstructed.
Vent termination shall NO T be installed
closer than 3' (0.9 m) from inside
corner of “L” shaped structure.
22
Vegetation,
Plants &
Shrubs
Meters,
Regulators,
deck, porch
Walkways
6 - COMBUSTION AIR AND VENT PIPING
Keep vent termination 3’ minimum
(0.9m) away from vegetation. Position
termination where vent vapors will not
damage plants/shrubs or air conditioning
equipment.
Termination
Vent termination 4’ (1.2m), horizontally
from, no case above or below, electric
meters, gas meters, regulators, and
relief equipment, or under deck or
porch.
3' (0.9 cm)
Minimum
Locate vent termination minimum 7'
(2.1 m) above any public walkway, with
consideration to condensate.
People or
Pets
Stones,
Balls,
Etc.
Vapors
Locate combustion air and vent termination
to prevent accidental contact with people
or pets.
Position combustion air and vent
termination where it will NOT be damaged
by foreign objects, such as stones, balls,
etc.
Position termination where vent vapors are
not objectionable.
7' (2.1 m)
Minimum
Position termination so it will not be effect-
Eddy,
Flue
Gases
ed by wind eddy, air born leaves, snow, or
recirculated vent gases. Give consideration
to excessive wind and locate away from
windward side of building.
Multiple
Family
Dwellings
23
Vent shall not terminate directly above
paved sidewalk or paved driveway located
between two single-family dwellings serving
both dwellings.
6 - COMBUSTION AIR AND VENT PIPING
FIGURE 6-1 Condensate Drain
6.6 Condensate Piping
• Use materials acceptable to authority having jurisdiction.
In absence of such authority:
• PVC or CPVC per ASTM D1785/D2845 Cement or
primer per ASME D2564 or F493.
• Attach PVC tee provided with boiler and fi eld sourced
piping to condensate drain at bottom of boiler. See
fi gure 6-1.
• Slope condensate drain pipe minimum 1/4" per foot
(21mm/m) away from boiler.
• Use fi eld source condensate pump if boiler located
below disposal point.
• Field source condensate neutralizing kit as required
by authority having jurisdiction or for environmentally
friendly condensate disposal.
Condensate Tee
(fi eld installed)
on condensate drain
pipe
24
!
7 - GAS SUPPLY PIPING
7-1 Gas Connection
Gas Connection
NOTICE
Use two (2) wrenches when tightening and fi tting
to pipe boiler's threaded fi ttings. Boiler's internal
piping can be damaged if subjected to excessive
torque.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switches; do not use any
phones in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re
department.
7.1 General
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements National Fuel Gas Code, ANSI Z223.1/
NFPA 54.
• Size and install gas piping system to provide suffi cient
gas supply to meet maximum input at not less than
minimum supply pressure. See Table 5.
• Support piping with hooks straps, bands, brackets,
hangers, or building structure components to prevent or
dampen excessive vibrations and prevent strain on gas
connection. Boiler will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for
liquefi ed petroleum gas.
• Provide sediment trap up stream of gas valve.
• Install manual main shutoff valve outside of jacket. See
fi gure 7-2.
MODEL
050
075
100
150
200
7.2 Conversion Kit Instructions
• See Gas Conversion Kit Instructions included with Boiler.
TABLE 5: GAS SUPPLY PRESSURE
Natural GasPropane
Min.Max.Min.Max.
3.0" w.c.
(0.7 kPa)
3.0" w.c.
(0.7 kPa)
3.0" w.c.
(0.7 kPa)
3.0" w.c.
(0.7 kPa)
3.0" w.c.
(0.7 kPa)
Note: See Glossary - Piping Table 16
13.5" w.c.
(3.3 kPa)
13.5" w.c.
(3.3 kPa)
13.5" w.c.
(3.3 kPa)
13.5" w.c.
(3.3 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
5.0" w.c.
(1.2 kPa)
5.0" w.c.
(1.2 kPa)
5.0" w.c.
(1.2 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
13.5" w.c.
(3.4 kPa)
13.5" w.c.
(3.4 kPa)
13.5" w.c.
(3.4 kPa)
13.5" w.c.
(3.4 kPa)
25
7 - GAS SUPPLY PIPING
a
s
!
DANGER
Fire Hazard. Do not use matches, candles, open
fl ames, or other methods providing ignition source.
Failure to comply will result in death or serious
injury.
7.3 Leak Check Gas Piping
Pressure test boiler and gas connection before placing
boiler in operation.
•
Pressure test over 1/2 psig (3.5 kPa). Disconnect
boiler and its individual gas shutoff valve from
gas supply system.
•
Pressure test at 1/2 psig (3.5 kPa) or less.
Isolate boiler from gas supply system by closing
manual gas shutoff valve. See fi gure 7-3.
•
Locate leakage using gas detector, noncorrosive
detection fl uid, or other leak detection method
acceptable to authority having jurisdiction. Do
not use matches, candles, open fl ames, or other
methods providing ignition source.
7-2 Manual Main Gas Shutoff Valve Outside
Boiler Jacket
Manual Main Gas
Shutoff Valve
G
•
Correct leaks immediately and retest.
7-3 Gas Shutoff Valve
Gas shutoff valve
(shown in closed
position)
26
8 - ELECTRICAL CONNECTIONS
8.1 General
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to
National Electrical Code, ANSI/NFPA 70.
8.2 Electric Knockouts (Figure 8-1)
• Five knockouts located on bottom of chassis.
A. Three knockouts located under junction box are
reserved for high voltage wires. Choose connectors
using total diameter of wire bundles.
B. Two knockouts located to right of high voltage
knockouts (outside of junction box) are reserved
for low voltage wiring. Use supplied grommets
when using these knockouts.
8.3 Line Voltage Connections (Figure 8-2)
• Boiler
A. Provide individual 120V, 15 amp circuit
(recommended) with fused disconnect or service
switch as required by authority having jurisdiction.
B. Open High Voltage Junction Box (see fi gure 3-4) to
access line voltage terminal strip.
C. Connect 120 VAC circuit to line voltage terminal
strip 120 VAC L,N,G.
• Central Heating Pump, if used.
A. Isolate pump from control module if pump FLA (Full
Load Amps) exceeds 2 amps (or 1 amp if external
DHW pump is used).
B. Connect pump to line voltage terminal strip CH
PUMP L,N,G.
• Domestic Hot Water Pump, if used.
A. Isolate pump from control module if pump FLA
exceeds 1.0 amp.
B. Connect pump to line voltage terminal strip DHW
PUMP L,N,G.
!
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
NOTICE
Wiring diagrams can be found in Section 14 of this
Manual.
8-1 ELECTRIC KNOCKOUTS BOTTOM OF BOILER
Front of Boiler
Low Voltage
High Voltage
Knockouts
5"
4½"
(1.6m)
(1.4m)
Back of Boiler
8-2 LINE VOLTAGE CONNECTIONS
Knockouts
(Use supplied
grommets when using
these knockouts)
8.4 External Connections (Figure 8-3)
• User Interface Terminals
A. Factory wired to USER INTERFACE terminals
B. Optional - Remote mount user interface for
improved access. Use low voltage knockout.
C. Maximum wire length is 100 ft (30m) for 22 ga.
wire, or 150 ft (45m) for 18 ga. wire.
27
8 - ELECTRICAL CONNECTIONS
• Argus Link (Multiple boiler applications only)
• Outdoor Sensor, if used.
A. Provided with boiler.
B. Locate outdoor sensor to protect against wind and
direct sunlight. Mounting instructions provided with
sensor.
C. Maximum wire length is 100 ft (30m) for 22 ga.
wire, or 150 ft (45m) for 18 ga. wire.
D. Connect wires to OUTDOOR SENSOR terminals.
Wires are interchangeable.
• System Sensor (Multiple boiler applications only)
• Domestic Hot Water (DHW) Thermostat, if used.
A. Use temperature control with dry contacts rated
at 0.5 amps @ 120 VAC. Boiler control does not
provide power to DHW temperature control.
NOTICE
IMPORTANT: Do not apply power to DHW T-T
terminals. Dry contact only, use of isolation relay
may be necessary.
8-3 EXTERNAL CONNECTIONS
(Do not apply voltage to external terminals.)
B. Maximum wire length is 330 ft (100 m) 22 gauge
wire.
C. Connect wires (interchangeable) to DHW T-T
terminals. Wires are interchangeable.
• Central Heating Thermostat
A. Use thermostat or boiler system control with dry
contacts related 0.5 amps @ 120 VAC.Boiler
control does not provide 24 VAC power to central
heating thermostat.
B. Locate and install thermostat per manufacturer's
instructions. Maximum wire length is330 ft (100
m) for 22 ga. wire.
C. Connect wires to CH T-T terminals. Wires are
interchangeable.
28
9 - START UP PROCEDURE
NOTICE
IMPORTANT: Condensate trap must be manually
fi lled with water at initial start up.
9-1 Condensate Drain Assembly
9.1 Fill boiler with water and purge air
• Fill boiler with potable water.
•
Fill boiler and system piping with water (or antifreezewater solution, if used). See antifreeze information
page 11. Purge air from boiler using air vent. Purge
air from system piping.
•
Inspect system piping and boiler connections. Repair
any leaks immediately.
9.2 Fill Condensate Trap with Water
•
Disconnect collet clip from condensate hose barb. See
fi gure 9-1.
•
Disconnect tubing below from hose barb.
•
Pour approximately 2 cups (473 ml) of water into
condensate drain.
•
Reconnect tubing to hose barb with collet clip. See
fi gure 9-1.
1. Disconnect collet clip from
hose barb and fi ll Condensate
trap with water.
2. Reconnect hose to hose
barb with collet clip before
starting boiler.
29
9 - START UP PROCEDURE
e
9 -2 User Interface
-2 User Interfac
9.3 Program Boiler Control
Key Description
- Manual Lockout Reset
- Enter/Exit user menu
- Go to previous screen
- Select a menu item
- Confi rm new parameter value
- Scroll up to next menu item
- Increase value
- Scroll down to next menu item
- Decrease value
Boiler is factory programmed with following factory
default settings, fi gure 9-3.
Parameters can be adjusted to suit particular
application.
Detailed explanation of each can be found in Appendix
A - Control Module.
List parameters in event of Control Module Failure to
reprogram your settings.
Factory Default
9-3 Default Table
Control Parameter
Central Heating Setpoint
User
Menu
Installer
Menu
* List parameters in event of Control Module Failure to reprogram your settings.
Settings
Boiler
Confi guration
CH Settings
DHW Setpoint180°F82°C104-195°F40-91°C
Temperature Units°F°F/°C
Boiler Address00-15
Low Water CutoffEnabledEnable/Disabled
Pump Mode00 & 4
Service Reminder StatusOnON/OFF
Service Reminder Days365 Days1- 999 Days
CH Mode10, 1, 2, 3
Warm Weather Shutdown70°F21°C35-100°F2-38°C
Reset Curve Design Temperature - Boiler180°F82°C60-195°F40-91°C
Reset Curve Design Temperature - Outdoor25°F-4°C-60-32°F-51-
Reset Curve Mild Weather Temperature - Boiler100°F37°C35-120°F2-49°C
Reset Curve Mild Weather Temperature - Outdoor70°F21°C35-85°F2-29°C
Reset Curve Boiler Minimum Temperature70°F21°C 40-180°F4-82°C
Reset Curve Boiler Maximum Temperature180°82°C80-195°F27-91°C
Boost Function Temperature0°F0°C0-36°F0-20°C
Boost Function Time20 Minutes1-120
Maximum Power CH100%1-100%
DHW Mode00/2
DHW Maximum Priority Time30 Minutes1-60 minutes
Setting
StandardMetricStandard Metric
140°F60°C104-195°F40-91°C
Setting Range
25°C
*Actual
Parameter
Settings
30
9 - START UP PROCEDURE
9.4 Boiler Start-up and Operational Test
1. Verify air is purged from hydronic piping
2. System test pumps - verify each pump is opera-
tional
3. Verify gas piping
•
Confi rm pressure test. See section 7.3.
•
Visually inspect piping to determine there are no
open fi ttings or ends, and all valves at unused
outlets are closed and plugged/capped.
•
Purge air from piping
•
Check piping and connections for leaks
immediately after gas is turned on. Shut off
gas supply and make necessary repairs if leaks
found.
4. Follow OPERATING INSTRUCTIONS to initiate boiler
operation. See section 10.
5. Inspect combustion air and vent piping. Verify pipe
is not leaking and terminations are unobstructed
and vent gas discharge is not a nuisance or hazard.
6. Verify boiler functions.
7. Inspect condensate disposal system. Verify
condensate fl ows adequately and is disposed
properly.
8. Check control module operation.
9. Check fi eld-sourced limits, low water cutoffs, etc.
per manufacturer's instructions.
9.5 Check Combustion
Natural Gas
1. Measure input. English units*
•
Turn off gas to all other appliances.
if needed using fi gure 9-3 below.
SizeMinimumMaximum
0504551
0756576
10090102
150140153
200185204
Natural Gas and Propane
3. Measure CO
and compare to table. Adjust CO2 if
2
needed using fi gure 9-3 below. See fi gure 9-4 for
combustion air analyzer port.
CO
Gas
Natural Gas8.59.5<100ppm
Propane10.011.0<150ppm
Min.
2
Max.
CO
Natural Gas only**
4.
Measure input. Compare to table above. Continue
to measure input and CO2 until both measured
values are within range specifi ed in tables.
Propane Gas
Most propane systems do not have fl ow meters.
1. Check CO
11.0%.
•
If CO2 is low increase gas fl ow following fi gure
9-3.
•
If CO2 is high decrease gas fl ow following fi gure
9-3.
. Propane should be between 10% and
2
•
Use ½, 1 or 2 cu ft dial on gas meter. Measure
time required for one or more complete
revolutions. Measure time for 1-2 minutes.
•
Calculate input.
3600 x cu ft
Input (MBH)=
seconds
Example: Gas fl ow fromMeter = 2 cu ft
Measured time = 72 seconds
3600 x 2 cu ft
Rate (MBH)=
=100 MBH
72 seconds
*Metric - See Glossary
** Most propane systems do not have gas fl ow meters.
2. Compare measured input to table. Adjust input rate
9-3 Gas Valve
•
To increase gas fl ow turn 'throttle' left or counter
clockwise .
•
To decrease gas fl ow turn 'throttle' right or
clockwise .
•
Limit adjustment to one turn and retest.
31
9 - START UP PROCEDURE
WARNING
!
Asphyxiation hazard. Carbon monoxide is odorless,
tasteless, clear colorless gas, which is highly toxic.
Verify cap is fi rmly placed on combustion analyzer
port to prevent CO emission. Failure to do so could
result in death or serious injury.
9-4 Combustion Analyzer Port
Combustion Analyzer Port
9-5 Burner Flame
Burner
Flame
Flame
Look for BLUE fl ame
with slight YELLOW tips
evenly spaced around
burner
Verify Burner, Proper Operation
1. Inspect burner fl ame through Sight Glass. See
fi gure 9-5.
2. Operate boiler through several heating cycles,
including domestic hot water, if used. Verify proper
operation.
3. Reset control parameters to operating settings if
adjusted to allow startup and operation test.
4. Follow instructions TO TURN OFF GAS TO APPLIANCE
if boiler is not being placed into immediate operation.
5. Enter installer information on Warranty Registration
Card.
6. Gather all instructions, manuals, wiring diagrams,
warranty registration card and other supporting
information. Review with user and/or affi x in
conspicuous location adjacent to boiler.
9.6 Perform CSD-1 Compliance Test (see
paragraph 2.4 page 5)
Verify operation of boiler safety control operation with
regard to no fl ow conditions as follows:
1. Turn off boiler using boiler service switch.
2. Disable primary boiler pump. Disconnect multi pin
connector J7 from control module. See fi gure 9-6.
3. Disable secondary system pumps attached to
system.
4. Establish call for heat. Jump CHW T-T terminals
on low voltage terminal block. Turn on boiler using
boiler service switch.
5. Boiler will fi re. Based on natural convection within
boiler, boiler will either:
A.
Lockout A-06 "Safety Relay Error". Requires
manual reset of control module. Press reset
button on User interface. See 9.3 Program Boiler Control page 30 .
OR
B.
Shut off burner E40 "Return Water Temp". This
is a soft lockout. When water temperature drops
below limit boiler will automatically refi re then
Lockout A-06 requiring manual reset of control
module. Press Reset button on User Interface.
OR
C.
Shut off burner E39 "Flue Temperature Sensor".
This is a soft lockout. When fl ue sensor drops
below limit, boiler will automatically refi re then
Lockout A-06 requiring manual reset of control
module. Press Reset button on User Interface.
6. After safety operation is verifi ed, turn off boiler via
service switch. Remove jumper in T-T. Replace J7
connector into control module, enable secondary
pump operation, turn service switch on and restart
system to verify operation.
32
9 - START UP PROCEDURE
9-6 Control Module J7 Connector
9.7 Complete Start Up Procedure
1.
Reset control parameters to operating settings if
adjusted to allow startup and operation test.
2. Follow instructions TO TURN OFF GAS TO APPLIANCE
if boiler is not being placed into immediate
operation.
3. Enter installer information on Warranty Registration
Card.
4. Gather all instructions, manuals, wiring diagrams,
warranty registration card and other supporting
information. Review with user and/or affi x in
conspicuous location adjacent to boiler.
33
10 - OPERATING INSTRUCTIONS
!
Gas Shutoff Valve
FOR YOUR SAFETY READ BEFORE OPERATING
!
WARNING
If you do not follow these instructions
exactly, a fi re or explosion may result
causing property damage, personal injury
or loss of life.
• This appliance is equipped with an ignition device
which automatically lights burner. Do NOT try to
light this burner by hand.
• Before operating smell all around appliance area for
gas. Be sure to smell next to fl oor because some gas
is heavier than air and will settle to the fl oor.
• Use only your hand to turn the gas shutoff valve.
Never use tools. If valve will not turn by hand, do not
try to repair it, call a qualifi ed service technician. Force
or attempted repair may result in fi re or explosion.
• Do not use this appliance if any part has been
under water. Immediately call a qualifi ed service
technician to inspect appliance and to replace any part
of control system and any gas control which has been
under water.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re
department.
10.2 TO TURN OFF GAS TO APPLIANCE
• Set thermostat to lowest setting.
• Turn "OFF" all electric power to appliance if service is
to be performed.
• Remove front jacket panel.
• Turn gas shutoff valve handle clockwise to closed
position. Handle should be perpendicular to gas pipe.
• Replace front jacket panel.
10.1 OPERATING INSTRUCTIONS
Stop! Read Safety information above.
• Set thermostat to lowest setting.
• Turn "OFF" all electrical power to appliance.
• This appliance is equipped with an ignition device which
automatically lights the burner. Do not try to light
burner by hand!
• Remove upper front jacket panel.
• Turn gas shutoff valve clockwise to closed position.
Handle should be perpendicular to gas pipe.
• Wait 5 minutes for any gas to clear. Smell for gas,
including near fl oor. If you smell gas, STOP! Follow
instructions on this page: “What To Do If You Smell Gas.” If you do not smell gas, go to next step.
• Turn gas shutoff valve counter clockwise to the
open position. Handle should be parallel to gas pipe.
• Replace upper jacket panel.
• Turn "ON" electrical power to appliance.
10-1 Gas Shutoff Valve
OPEN POSITION
CLOSED POSITION
• Set thermostat to desired setting.
• If the appliance will not operate, follow instructions TO
TURN OFF GAS TO APPLIANCE and call your service
technician or gas supplier.
Gas Shutoff Valve
34
11 - GENERAL MAINTENANCE AND CLEANING
!
!
DANGER
Before servicing, turn off electrical power to boiler
at service switch. Close manual gas valve to turn
gas supply OFF to boiler. Failure to comply will result
in death or serious injury.
!
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation.
NOTICE
Verify proper operation after servicing.
NOTICE
Perform regular service and maintenance by
qualifi ed service agency at least once every 12
months to assure safe, trouble free operation
and maximum effi ciency .
11-1 Sight Glass
11.1 Beginning of Each Heating Season
• Check boiler area is free from combustible materials,
gasoline, and other fl ammable vapors and liquids.
• Visually inspect combustion air and vent piping for
proper operation. Check for and remove any obstruction
to fl ow of combustion air or vent gases. Immediately
repair or replace pipe showing deterioration or leakage.
Reassemble per instructions in section 6. Verify proper
reassembly and resealing of system.
• Visually inspect condensate drain line for proper
operation. Checking for deteriorated or plugged
condensate drain line. Verify condensate trap drains
freely.
• Test safety relief valve for proper operation. Refer to
valve manufacturer's instructions packaged with relief
valve.
• Inspect burner and heat exchanger and clean (if
necessary) by following instructions in “Annual Inspection
and Cleaning of Boiler Components” in this section.
• Circulator pump and combustion air blower motor
furnished with boiler are permanently lubricated from
factory and require no further lubrication. Lubricate fi eld
sourced pumps and/or motors according to pump and/or
motor manufacturer’s instruction.
Sight Glass
Pressure Test Port
• Check following components are operating properly and
are free of blockages or obstructions:
• air vent;
• check venturi air inlet for blockage and clean as
required;
• verify pressure test port cap and combustion test port
are in place;
• return temperature sensor clip must be securely
seated on pipe; Check boiler for any sign of leaks.
• Check low water cutoff using user interface.
• Check operation by pressing test button on low water
cutoff.
• "Low Water" LED should illuminate and burner
should shut down.
• Should get error message on User Interface
(E36).
• Every 5 years remove low water cutoff. Reinstall
after cleaning.
• Every 10 years replace low water cutoff.
• Check fl ame signal with user interface. Should be 8
amps at 100%.
micro
• Visual inspection of fl ame through sight glass. Burner
should be fully illuminated. See fi gure 9-5.
• Check expansion tank.
35
11 - GENERAL MAINTENANCE AND CLEANING
Figure 11-2 Condensate Trap
Flue Pipe
Coupling
Condensate Collector
Condensate Trap connection
to Condensate Collector
Flexible Gas Line
Temperature Sensor
Hose Barb w/Cap
11.2 Annual Shut Down Procedure
• Follow instructions “To Turn Off Gas To Appliance”unless
boiler is also used to supply domestic hot water. See
section 10.
• Drain system completely if system does not have
antifreeze when heating system is to remain out of
service during freezing weather.
• Drain condensate lines when boiler is to be exposed to
freezing temperatures.
!
WARNING
Following service procedures must be performed
by qualifi ed service agent. Boiler owner shall not
attempt these steps. Failure to do so could result in
death or serious injury.
11.3 Annual Inspection and Cleaning of Boiler
Components
• Obtain Burner Inspection Kit. Follow kit instructions to
prepare for examination and cleaning.
• Burner and heat exchanger inspection and cleaning.
• Remove gasket and burner. Allow burner to clear top
lip of chassis.
• Remove any residual sleeve and/or gasket material
from removed burner.
• Clean burner using air hose directed into top of
burner opening to dislodge any debris in burner ports.
Inspect burner for foreign matter in fl ame ports or
inside burner. Remove foreign matter by blowing with
compressed air or vacuuming. Replace burner if it
cannot be cleaned or is showing deterioration.
• Clean heat exchanger with low pressure water spray.
Use fl exible handle nylon brush to loosen sediment
and oxide on all accessible heating surfaces of heat
exchanger. Take care not to get brush stuck in heat
exchanger.
• Remove any remaining loosened sediment using shop
vacuum with snorkel attachment.
• Clean condensate collector if signifi cant debris found in
heat exchanger.
• Expand upper collet clip of condensate trap using
hose clamp pliers. Disconnect condensate trap from
condensate collector. See fi gure 11-2.
• Disconnect wire harness from vent temperature
sensor. See fi gure 11-2.
• Loosen upper hose clamp securing condensate
collector to fl ue pipe using 3/8" socket with 6"
extension.
36
11 - GENERAL MAINTENANCE AND CLEANING
• Remove ¼-20 hex fl ange nuts securing condensate
collector to heat exchanger using 7/16" deep well
socket. See fi gure 11-2.
• Remove condensate collector assembly from heat
exchanger and fl ue pipe.
• Flush collector and condensate trap with water.
• Follow Burner Inspection Kit instructions to reassemble
boiler and resume operation.
37
12 - RATINGS AND CAPACITIES
TABLE 12-1: SEA LEVEL RATINGS
NATURAL AND PROPANE GASES
Size
050
075
100
150
200
(1)
1000 Btu/hr (British Thermal Units Per Hour)
(2)
Heating Capacity and AFUE (Annual Fuel Utilization Effi ciency) are based on DOE (Department of Energy) test procedures.
(3)
Net AHRI Ratings based on piping and pickup allowance of 1.15.
• Constructed and hydrostatically tested for maximum
allowable working pressure of 50 psig (pounds per
square inch gauge) (345 kPa) in accordance with ASME
Boiler and Pressure Vessel Code, Section IV, Rules for
Construction of Heating Boilers.
Heating Capacity
(MBH)
(1)(2)
Net AHRI Rating,
Water (MBH)
(1)(3)
AFUE
(2)
• Ratings used for elevations up to 2000 ft (600m) above
sea level.
• For elevations above 2000 ft. (600m) reduce input rate
4% for each 1000 ft (300m) above sea level.
38
YESNO
Does User Interface Display work?
13 - TROUBLE SHOOTING
YESNO
NOYES
Locate fuse holder on front of
control and pull to check fuse.
Spare fuse located on controller.
Make sure all wire harness plugs
are properly pushed in. Release
plug lock with finger, remove and
reconnect all 7 plugs . Check
Voltage Terminal Strip including
wiring from User Interface to Low
checking continuity of the wires.
Does User Interface Display work?
Remove User Interface from
base. Using Digital Voltmeter
voltage present?
check for 25 to 30 Vdc. Is
GO TO NEXT PAGE
YES
NO
Remove Top Jacket.
Is User Interface Lit?
NOYES
External Power Switch ON?
Turn ON power to Boiler.
Is Power Light Lit?
NO
YES
Check for 120 Vac Inside High
Check 120 Vac on Molex
available?
Voltage Terminal Box. Is 120 Vac
is 120 Vac available?
Connector on top of Lower Jacket
YESNO
NOYES
Check Circuit Breaker or
Emergency Disconnect Switch
and 120 Vac Wiring to Boiler. Fix
Replace Wire
Replace Control ModuleReplace User Interface
or Repair External Wiring.
Harness.
Replace Power Light
39
13 - TROUBLE SHOOTING
Go to Page 41
Go to Page 42
Go to Page 41
Replace Control
Module
Go to Page 43
Replace Control
Module
Go to Page 44
Go to Page 45
Go to Page 46
Go to Page 47
Replace Control
Module
Go to Page 47
Go to Page 48
Go to Page 49
Replace Gas
Valve
Replace Gas
Valve
Replace Control
Module
Go to Page 45
Replace Control
Module
Replace Control
Module
Replace Control
Module
Go to Page 49
Go to Page 50
Go to Page 51
Go to Page 51
Go to Page 52
Go to Page 52
Error Clears in
1-2 minutes
Replace Control
Module
40
13 - TROUBLE SHOOTING
to Control Module J13?
Is harness connected to Gas
Lockout Alarm A 0 5
GV relay error
Valve? Is harness connected
_ P _ _ _
NOYES
Connect harness
YESNO
and Control Module?
Valve. Does each wire have
Disconnect harness from Gas
continuity between Gas Valve
Replace harness
Replace Gas Valve
1.0 and 1.2 kohms?
Disconnect harness from
resistance across J13-3 and
Control Module J13. Measure
J13-4. Is resistance between
YESNO
Module
Replace Control
Lockout Alarm A 0 0
Blocking too long error
_ _ _ _ _
Enter Installer Menu, Boiler
Status. Scroll to most recent
Diagnose corrective action using
Lockout Alarm or Blocking Error.
appropriate Troubleshooting Tree.
41
13 - TROUBLE SHOOTING
Tree
Valve
Refer to the Gas
Is there any
apparent debris or
flue way?
obstruction of the
YESNO
blockages.
way along the
Inspect the flue
near the coil for
sides of the baffle
Clear vent blockage
check for secure fit
Connect all wires and
Troubleshooting
section
Refer to the Heat
Exchanger cleaning
inspect.
burner and
Remove the
flue transition.
Remove the gas
all wires
including the
Check all wires
startup?
Is this a new boiler on first
YESNO
and tight
sensor leads.
Check for proper
igniter and flame
Valve closed?
Is the Gas Shutoff
connected?
connections to
control board. Are
YESNO
YESNO
Open gas shutoff
valves
System for
Inspect Vent
clear?
blockages.
Is the vent system
Reset the boiler by
pressing the
YESNO
‘Reset’ button.
When the boiler
tries to ignite, is
`
there a strong,
consistent spark
Disconnect the gas
evident throught
train including the
valve.
valve electrical
the gas shutoff
harness and close
YESNO
the sight glass?
With the ignition
lead connected to
the igniter, hold the
Any sign of
damage to burner
ignition.
tip near the chassis
ground and attempt
sensor and igniter
Remove the flame
surface?
YESNO
and ground?
between the igniter
Is a spark observed
there any
indication of
and inspect. Is
damage or debris
YESNO
baked on?
YESNO
Replace Burner
Module
Replace Control
to run with
Is this boiler
Lockout Alarm A 0 1
Ignit error
YESNO
propane gas?
gas orifice
Is the propane
_ P _ _ _
YESNO
properly
installed?
sensor or igniter
Check vent
Replace/clean flame
consideration of wind
termination for proper
effects
running?
YESNO
ignite and stay
Does the boiler
Install
Orifice
propane
Once the boiler
Menu and place
Enter the Installer
starts, go to the
mode in high fire.
the boiler into test
signal.
screen and
boiler status
monitor the flame
8.0uA?
greater than
YESNO
Is the flame signal
42
13 - TROUBLE SHOOTING
NO
operating?
YES
Is Combustion Air Blower
Lockout Alarm A 0 8
Fan error
_ _ _ _ _
NO
Are 3-wire and 4-wire
YES
harnesses connected to
Combustion Air Blower?
Connect harness
Disconnect harness from
NO
Is voltage 120 Vac ± 10%
Control Module J9. Measure
voltage between J9-2 and J9-3.
Air Blower
Replace Combustion
NO
YES
Module
Replace Control
NO
YES
Disconnect 3-wire harness
Measure continuity in each
from Combustion Air Blower.
wire. Continuity in each wire?
Replace harness
Air Blower
Replace Combustion
speed increase?
YES
Disconnect 4-wire harness
from Combustion Air Blower.
Does Combustion Air Blower
43
Replace harness
Disconnect harness from
Control Module J9. Continuity
(yellow, red, white, black)?
in each wire of 4-wire harness
YESNO
Module
Replace Control
13 - TROUBLE SHOOTING
Replace Control
Module
2K to 1K ohms
2K to 3K ohms
3K to 9K ohms
°F°CResistance
50 to 9010 to 329K to 24K ohms
Resistance Chart
90 to 130
150 to 200
130 to 150
and Control Module J13.
Temperature Supply Switch
Lockout Alarm A 1 8
Max Temp Error
Disconnect harness from High
_ _ _ _ _
NO
Switch 3?
YES
1? Continuity from J13-6 to
Continuity from J13-5 to Switch
Replace wire(s)
NO
YES
less than 185°F (91°C)?
Is supply water temperature
High Temperature Supply Switch
YESNO
Switch open (no continuity
Is High Temperature Supply
between terminals 1 and 3)?
Switch
Replace High
Temperature Supply
Replace High
Temperature Supply
YESNO
High Temperature Supply
Switch terminals 2 and 4?
Measure resistance across
Does resistance match supply
water temperature (see table)?
Module
32 to 54
Switch
54 to 66
66 to 94
44
Is High Temperature Supply
Switch open (no continuity
between terminals 1 and 3)?
Replace Control
YESNO
Switch
Replace High
Temperature Supply
13 - TROUBLE SHOOTING
clean and secure?
Inspect harness connection
Lockout Alarm A 2 4
3 flame failures
Flame Sensor. Is connection
_ P _ _ _
NO
YES
Replace Flame
Sensor or harness
NO
YES
free of contamination?
Remove Flame Sensor. Is rod
Clean or replace
Follow OPERATING
Flame Sensor
INSTRUCTIONS to initiate
boiler operation. Enter Installer
Menu, Boiler Status, Flame
Signal. Is flame signal greater
NO
than 3.7 uA?
YES
Replace Flame
Sensor and Burner
Module
Blocking Error E 3 5
False flame detect
_ P _ _ _
Replace Control
Module
NOYES
glass. Is flame present?
Inspect burner through sight
Replace Control
Turn Gas Shutoff
Valve clockwise to
closed position.
Follow instructions
TO APPLIANCE.
TO TURN OFF GAS
Replace Gas Valve.
45
13 - TROUBLE SHOOTING
46
13 - TROUBLE SHOOTING
Blocking Error E 4 0
Return Temp
_ _ _ _ _
Is correct harness connected to
return sensor (2 Brown Wires)?
NOYES
Correct wiring
oriented properly?
Is Heat Exchanger Pump
YESNO
(Pump Arrow pointing down?)
Install Heat
proper orientation
Exchanger Pump in
Return Water Sensor.
Disconnect harness from
Measure resistance using
digital ohm meter. Is
resistance between 950 to
Sensor
Replace Return Water
33,000 ohms?
YESNO
Module
Replace Control
47
13 - TROUBLE SHOOTING
48
13 - TROUBLE SHOOTING
Blocking Error E 5 1
Supply Sens Open
_ P _ _ _
NOYES
Module J5?
Water Sensor?
Is harness plugged into Supply
Is harness plugged into Control
Insert Harness
Disconnect J5 from Control
Module. Using digital meter
measure check continuity of
and Sensor. Continuity?
brown wires between Control
YESNO
Replace Wires
Using digital meter measure
resistance between Supply
of Sensor with digital meter.
Water Sensor terminals J5-11
and J5-3. Measure resistance
Estimate Sensor temperature.
Does it fall in the range of the
Resistance Chart?
YESNO
Water Sensor
Replace Supply
Module
Blocking Error E 4 6
Faulty ground
_ P _ _ _
conductor
Connect ground
YESNO
connected to High Voltage
Is field grounding conductor
Terminal Strip 120 VAC (G)?
Disconnect field wiring. Is
neutral and ground less than
continuity between field wiring
10 ohms?
Replace Control
conductor
NOYES
Correct faulty ground
°F°CResistance
Resistance Chart
Supply Water Sensor
Module
Replace Control
3K to 9K ohms
50 to 9010 to 329K to 24K ohms
90 to 130
32 to 54
2K to 1K ohms
2K to 3K ohms
150 to 200
130 to 150
54 to 66
66 to 94
49
13 - TROUBLE SHOOTING
2K to 1K ohms
2K to 3K ohms
3K to 9K ohms
°F°CResistance
50 to 9010 to 329K to 24K ohms
Resistance Chart
Return Temperature Sensor
90 to 130
32 to 54
150 to 200
130 to 150
54 to 66
66 to 94
Blocking Error E 5 2
Return Sens Open
_ P _ _ _
Module J5?
Temperature Sensor?
Is harness plugged into Return
Is harness plugged into Control
YESNO
Insert Harness
Continuity?
wires between Return
Temperature Sensor and
Check continuity of brown
YESNO
Control Module J5-4 and J5-12
Replace Wires
meter. Estimate Sensor
Measure Return Temperature
Sensor resistance with digital
temperature. Do temperature
ranges shown in chart?
and resistance fall within
Replace Return
Temperature Sensor
YESNO
Module
Replace Control
50
13 - TROUBLE SHOOTING
Replace wires
Switch 4?
High Temperature Supply
Blocking Error E 5 9
Supply Sensor Shorted
Disconnect wire harness from
_ P _ _ _
Switch. Measure resistance
across terminals 2 and 4. Do
temperature and resistance fall
within ranges shown in chart?
NOYES
Insert harness
J5-11 and Switch 2?
Disconnect J5 from Control
Module. Continuity between
Switch
Replace High
Temperature Supply
YESNO
Continuity between J5-3 and
Module
Replace Control
Resistance Chart
High Temperature Supply Switch
°F°CResistance
3K to 9K ohms
50 to 9010 to 329K to 24K ohms
90 to 130
32 to 54
2K to 1K ohms
2K to 3K ohms
150 to 200
130 to 150
54 to 66
66 to 94
Module J5?
Temperature Sensor? Is
Is harness plugged into Vent
Blocking Error E 5 7
Flue sens open
harness plugged into Control
_ P _ _ _
Replace wires
NOYES
Replace Vent
Temperature Sensor
for each blue wire?
Temperature Sensor and
Disconnect harness from Vent
YESNO
Control Module J5. Continuity
YESNO
match estimated flue
terminals. Does resistance
temperature (see table)?
Vent Temperature Sensor
Measure resistance across
Module
Replace Control
51
Blocking Error E 6 5
Flue Sens Shorted
_ P _ _ _
13 - TROUBLE SHOOTING
NOYES
Does resistance match
Vent Temperature Sensor.
Measure Sensor resistance.
Disconnect wire harness from
estimated flue temperature?
Replace Vent
Temperature Sensor
in blue wires?
Disconnect harness from
Control Module J5. Continuity
YESNO
Replace wires
Module
°F°CResistance
Resistance Chart
Vent Temperature Sensor
3K to 9K ohms
50 to 9010 to 329K to 24K ohms
90 to 130
32 to 54
2K to 1K ohms
2K to 3K ohms
150 to 200
130 to 150
54 to 66
66 to 94
Disconnect harness from
Blocking Error E 6 0
Return sens shorted
_ P _ _ _
Disconnect harness from
Control Module J5. Measure
less than 50 ohms?
YESNO
Measure resistance across
Return Temperature Sensor.
sensor terminals. Is resistance
Sensor
resistance between brown
wires at terminals J5-4 and J5-
Replace Control
NOYES
ohms?
12. Is resistance less than 50
Module
Replace Control
Replace wires
Replace Return Water
52
14.1 Connection Diagram
14 - WIRING DIAGRAM
53
14 - WIRING DIAGRAM
14.2 Schematic Diagram of Ladder Form
54
15 - GLOSSARY
• ANSI - American National Standards Institute, Inc.
oversees creation and maintenance of voluntary
consensus standards, including ANSI Z21.13/CSA 4.9:
Gas-Fired Low Pressure Steam and Hot Water Boilers.
• ASTM - American Society for Testing and Materials.
ASTM International is one of largest voluntary standards
development organizations in world trusted source for
technical standards for materials, products, systems,
and services. Known for their high technical quality and
market relevancy, ASTM International standards have
important role in information infrastructure that guides
design, manufacturing and trade in the global economy.
• AUTHORITY HAVING JURISDICTION - Individual or
organization adopting and enforcing codes, rules, and
by-laws governing various concerns of community.
Commonly referred to as "fi nal authority" for any matters
relating to LIFE SAFETY and BUILDING CONSTRUCTION
within a community.
Pipe Capacity - BTU Per Hour Input Includes Fittings
1/2”3/4”1”1 1/4”
PROPANE GAS
Pipe Capacity - BTU Per Hour Input Includes Fittings
Copper Tubing
(Outside Diameter)
5/8”3/4”1/2”3/4”
Iron Pipe
• HIGH-VOLTAGE - Circuit involving potential of not more
than 600 volts and having circuit characteristics in excess
of those of low-voltage circuit.
• Btu - Abbreviation for British Thermal Unit. Quantity of
• IGNITER - Device utilizing electrical energy to ignite gas
heat required to raise temperature of 1 pound of water
1°F.
• LEAK CHECK - Operation performed on gas piping system
• BURNER - Device for fi nal conveyance of gas or mixture
of gas and air, to combustion zone.
• LOW WATER CUTOFF - Device constructed to automati-
• COMBUSTION - Rapid oxidation of fuel gases accompanied
by production of heat or heat and light. Complete combustion
of fuel is possible only in presence of adequate supply of
Oxygen.
• LOW-VOLTAGE - Circuit involving potential of not more
• COMBUSTIBLE MATERIAL - Materials made of or surfaced
with wood, compressed paper, plant fi bers, or other
• METRIC GAS METERS
materials capable of being ignited and burned. Such
material shall be considered combustible even though
fl ame-proofed, fi re-retardant treated, or plastered.
• CONDENSATE - Liquid separated from fl ue gas due to
reduction in temperature.
For example: Gas Meter measures 0.1 cubic Meters in 100
seconds
• DIRECT VENT BOILER - Boiler constructed and installed
so all combustion air is derived directly from outdoors
and all vent gases are discharged to outdoors.
• DRAFT - Pressure difference causes gases or air to fl ow
• PRESSURE TEST - Operation performed to verify gas
through a chimney, vent, fl ue or appliance.
• FLA - Full load amps.
• PURGE - To free gas conduit of air or gas, or mixture of
• FLUE GASES - Products of combustion plus excess air in
appliance fl ues or heat exchanger.
• PURGE TIME - Period of time intended to allow for
• GAS PIPE SIZES - Table 16
at main burner.
to verify system does not leak.
cally cut off fuel supply when surface of water in boiler
falls to lowest safe water level.
than 30 volts.
MBH=
MBH=
127,116 x cu meters
Seconds
127,116 x 0.1
100
= 127 MBH
tight integrity of gas piping following its installation or
modifi cation.
gas and air.
dissipation of any unburned gas or residual products of
combustion.
55
15 - GLOSSARY
• QUALIFIED AGENCY - Any individual, fi rm, corporation, or
company engaged in and responsible for:
• Installation, testing, or replacement of gas piping,
or connection, installation, testing, repair or
servicing of appliances and equipment.
• Experienced in such work.
• Familiar with all precautions required.
• Complies with all requirements of authority having
jurisdiction.
• SAFETY RELIEF VALVE - Valve designed to relieve
pressure in hot water supply system when pressure
exceeds pressure capability of equipment.
• SAFETY SHUTOFF DEVICE - Device that will shut off gas
supply to controlled burner in event source of ignition
fails.
• SEDIMENT TRAP - Gas piping arrangement designed to
collect any liquid or solid contaminant before reaching
gas valve.
• VENT - Passageway used to convey fl ue gases from
appliance vent connector to outdoors.
• VENTING SYSTEM - Continuous open passageway from
of appliance vent connector to outdoors for purpose of
removing fl ue or vent gases.
56
APPENDIX A - CONTROL MODULE
1.1 Introduction
Boiler is equipped with programmable electronic control
and user interface module.
1.2 Operation
• Display: 4x20 character LCD screen to show boiler
status.
• Function Keys
Key Description
- Manual Lockout Reset
- Enter/Exit user menu
- Go to previous screen
- Select a menu item
- Confi rm new parameter value
- Scroll up to next menu item
- Increase value
- Scroll down to next menu item
- Decrease value
Operation with LCD character display module
eration with LCD character display module
1.3 Status Indication
The following status screens can be displayed:
Boiler Status Indicator
F = Flame Detected
SERVICE Reminder
P = Central Heating System pump On
B = Combustion Air Blower On
S = Safety Relay Check
G = Gas Valve Open
D = DHW Pump On
Combustion Air Blower
Speed Indicator
Service Reminder Indica
Boiler in Standby Mode
Boiler Supply Water
Temperature Indicator.
tor
Boiler Running in Central
Heat mode
Boiler Running in DHW
mode
Lockout Alarm Indicator
Error code and short text
description is displayed
Press 'Reset" key for manual
reset.
Blocking Error
Error code and short text
description is displayed Boiler
automatically returns to
Standby Mode when condition is
eliminated.
If fl ame detected before Gas Valve
opens during ignition boiler will
lockout.
Please refer to troubleshooting
guide.
Gas Valve energized to deliver air/
fuel to burner.
If fl ame undetected after 3 sec-
onds boiler will de-energize Gas
Valve and enter post purge mode
for 30 seconds.
Ignition attempted 5 times before
lockout.
Boiler will run provided all operational and safety devices are
within limits
Refer to for more information.
Control module adjusts fi ring rate
according to heating demand.
When Boiler detects demand met,
will enter post purge mode then
standby mode.
Simultaneous
DHW + CH
Demand?
Yes
DHW
Priority
Mode
See Max DHW
Priority Time
Setting
If simultaneous demand for
Central Heat and DHW, boiler will
enter DHW Priority Mode.
Priority mode limits amount of
time boiler can run in DHW mode
to meet CH demand.
Max DHW Priority Time setting
determines maximum time
allowed for DHW heating mode.
Please refer to section Appendix A
section 1.5 for more information.
59
APPENDIX A - CONTROL MODULE
60
APPENDIX A - CONTROL MODULE
61
INS
TALLER MENU
Bo i l e rS t a
tus
Bo i l e rCon f i g
CHSe t t i n g s
DHWS e t t i n g s
Casc a
deSe t t i ngs
Sys t em Tes t
STATUS
Fa n S p e ed
Ac t u a l4000RPM
L owP o we r1560RPM
▼
STATUS▲
Fa n S p e ed
I g n i t i on3500RPM
HiPower5725RPM
▼
STATUS▲
Fl ame
Signal07.2uA
Fa i l ures2
▼
APPENDIX A - CONTROL MODULE
User Interface Display
Installer Menu
Installer Menu
Explanation
The Installer Menu structure includes:
• User Menu can be accessed by pressing ‘Menu’ key
on user interface. Installer Menu can be accessed by
simultaneously holding ‘Menu’ and ‘Enter’ keys for 5
seconds.
• ‘Boiler Status’ submenu – User monitors detailed boiler
status parameters such as fl ame signal, fan speeds and
stored error codes.
• ‘Boiler Confi g’ submenu – Modifi es general boiler
settings.
• ‘CH Settings’ submenu – Modifi es advanced Central
Heating settings including outdoor reset curve
parameters and boost function.
• ‘DHW Settings’ – Modifi es Domestic hot Water control
settings such as DHW priority time.
Boiler Status
• ‘Cascade Settings’ - Refer to Multiple Boiler Manual.
• ‘System Test’ – Tool aids setup of boiler installation or
diagnosis of common problems.
Combustion air Blower provides airfl ow through Combustion and
Vent systems.
Fan speed status screen indicates actual and operational fan
speeds in RPM, high, low and ignition power speed settings.
Settings are for information only to aid in troubleshooting.
Boiler equipped with ionization rod to detect presence of
combustion using fl ame rectifi cation method. When fl ame is
present, fl ame ionization rod measures small DC offset current
across fl ame to ground (i.e. burner surface).
‘Flame’ screen in ‘Boiler Status’ submenu displays information
regarding fl ame ionization system; for information only and
used in diagnosing combustion problems. See troubleshooting
guide.
62
APPENDIX A - CONTROL MODULE
STATUS▲
Ign i t i on Attempts
Su c c e s f u l4267
Fa i led 21
▼
User Interface Display
Installer Menu
Explanation
Control module logs successful and failed ignition attempts.
Information accessed in ‘Ignition Attempts’ Screen as shown.
Ignition attempts are stored in non-volatile memory and are
retained in event of power failure.
Figure A-1 Typical Ignition Cycle
Boiler Status
Following control features are implemented to ensure safe and
reliable operation of Combustion System:
False Flame
Detection
Re-ignition
Intermittent
Operation
Flame out too
late
Safety relay test
UL3563
High Limit
Temperature
Device
If fl ame is detected at end of pre-spark
period (Ignit_0) than lockout will occur.
If at end of safety period no fl ame detected
control will go to post-purge removing
unburned gas. Re-ignition attempt started
following same cycle. Number of re-ignition
attempts limited to 4 after which lockout
occurs.
Boiler can be fi ring continuously for 24
hours. Burner switched off and restart
sequence follows.
If fl ame detected after post purge lockout
follows.
In Safety ON/OFF state correct operation
of safety relay is proved before ignition.
Boiler comes equipped with UL353
approved temperature high limit device.
Gas Valve de-energized when supply
temperature exceeds 203°F lockout
follows.
63
APPENDIX A - CONTROL MODULE
64
BO I L E RC ON F I G
▲
Pump Mo de MODE : 0
CHo rC H&DHW
▼
BO I L E RC ON F I G▲
SE R V I C EREM I NDER
Sta tusOn
R em i n d e r365days
APPENDIX A - CONTROL MODULE
User Interface Display
Explanation
Two pump modes are available:
1.
Pump Mode = 0 ‘CH or CH&DHW’
• In this mode either the CH or DHW pump terminal is
energized depending on the type of demand (CH or DHW).
• CH and DHW pumps are never energized at the same time.
• In the case of a simultaneous call for both CH and DHW,
the energized pump depends on whether the boiler is
currently supplying the CH or DHW demand. Refer to DHW
Priority settings below.
• This is typical of a hydronic system design with separate CH
and DHW Pumps.
2.
Pump Mode = 4 ‘System Pump’
• In this mode only one external system pump is installed in
the hydronic system. This pump will energize independent
of the type of demand (CH or DHW).
Boiler Confi guration
• Connect this pump to the CH/System Pump electrical
terminal block. See page56 for diagram.
• The DHW pump terminal does not function.
• This is typical of a hydronic system design which utilizes
zone valves for all CH zones and an DHW indirect tank.
Note:
• Pump Mode selection depends on electrical and
hydronic system design. Please refer to sections 5
and 8 for recommended hydronic piping and electrical
confi gurations.
• Internal heat exchanger pump is energized anytime
demand exists regardless of Pump Mode setting or type
of demand (CH or DHW).
'Service Reminder’ feature allows the installer to enable or
disable a service reminder notifi cation on the User Interface at a
predefi ned interval .
Service reminder does not affect operation of boiler in any way.
It is only a reminder to End User that routine preventative
maintenance is required by qualifi ed service technician.
Allowed Range: 1 to 999 days
65
CHSETT I NGS
CH mo d eMODE: 1
CHw i t hthe rmost at
▼
APPENDIX A - CONTROL MODULE
User Interface Display
Explanation
4. Central Heating (CH) modes available:
• CH Mode = 0 ‘CH with Thermostat’
• Boiler will attempt to satisfy CH demand while CH
thermostat input is closed.
• Boiler will modulate its fi ring rate to maintain CH set
point and match system heat load.
• CH set point adjusted in ‘Settings’ submenu under ‘User
Menu’
• CH Mode = 1 ‘CH with Thermostat and Outdoor Reset’
• Boiler will attempt to satisfy CH demand when CH
thermostat input is closed.
• Boiler will modulate its fi ring rate to maintain CH set
point and match system heat load.
• CH set point calculated as function of outdoor
temperature using outdoor reset curve. See fi gure A-2
• CH Mode = 2 ‘CH with Full Outdoor Reset’
• Boiler will permanently attempt to satisfy CH
demand.
• CH thermostat input is ignored.
• CH set point calculated as function of outdoor
temperature using outdoor reset curve. See fi gure A-2
CH Settings
• CH Mode = 3 ‘CH with Permanent Demand’
• Boiler will permanently attempt to satisfy CH
demand.
• CH thermostat input is ignored.
• CH set point is adjusted in ‘Settings’ submenu under
‘User Menu’
Note:
• Once CH demand is satisfi ed (i.e. CH thermostat opens or
boiler determines its minimum fi ring rate exceeds system
heating load):
• Burner shuts off, boiler enters post purge.
• CH pump continues to run for 30 seconds.
• Control will wait until Anti-cycle time of 180 seconds
elapses before boiler fi res again. Prevents short-
cycling.
• The internal heat exchanger pump is energized anytime demand
exists regardless of Pump Mode setting or type of demand (CH or
DHW).
66
APPENDIX A - CONTROL MODULE
CHSETT I NGS▲
Wa
rmWe ather
Shut down Temp
70°F
▼
CHSETT I NGS▲
Rese t Curve
Bo i l e rMin070 °F
Bo i l e rMax180 °F
▼
CHSETT I NGS▲
R.Curve Mild Weath.
Bo i l e r 70°F
Ou t d o o r70°F
▼
CHSETT I NGS▲
Rese t Curve
Bo i l e rMi n070 °F
Bo i l e rMax180 °F
▼
User Interface Display
Allowed Range: 35°F to 100°F (2°C to 38°C)
Default Setting: 70°F (21°C)
A
Allowed Boiler Range: 60°F to 195°F (40°C
to 91°C)
Default Boiler Setting:180° F (82°C)
B
Allowed Boiler Range: 35°F to 120 F (2°C to
49°C)
Default Boiler Setting: 100°F (37°C)
Allowed Outdoor Range: 35°F to 85°F (2°C to
29°C)
Default Outdoor Setting: 70°F (21°C)
CH Settings
100
Explanation
If outdoor temperature is greater than Warm Weather
Shutdown Temperature, demand for CH blocked and pumps
stopped.
Boiler capable of operating in Outdoor Reset Mode when
included Outdoor Sensor is connected and proper CH Mode
selected.
If CH Mode = 1, ‘Outdoor Temperature Reset with Thermostat’ or 2, ‘Full Outdoor Reset’ boiler will adjust CH set point
proportional to outdoor temperature as defi ned by Outdoor
Reset Curve below.
Outdoor reset curve adjusted by modifying Design and Mild
Weather reference temperatures. See points A & B of Reset
Curve below.
Calculated CH set point always limited between ‘Reset Curve
Boiler Minimum/Maximum’ temperatures. See points C & D
of Reset Curve below.
Figure A-2 Outdoor Reset Curve
A
D
Allowed Min. Range: 40°F to 180°F (4°C to 82°C)
Default Min. Setting: 70°F (21°C)
Allowed Max. Range: 80°F to 195°F (27°C to 91°
C)
Default Max. Setting: 180°F (82°C)
C
D
B
C
Note:
• Modes only function when outdoor temperature sensor
connected.
• If ‘Open’ outdoor sensor detected CH set point equal to
‘Boiler Reset Curve Design’ temperature.
• Outdoor temperature used for CH set point calculation
measured once a minute and averaged with
previous measurement to compensate for rapid outdoor
temperature variations.
67
APPENDIX A - CONTROL MODULE
CHSETT I NGS▲
Boos t F unct ion
Temp10°F
Time20min
▼
CHSETT I NGS▲
Max i mum Power CH
Max100%
▼
D
HWS E T T I NGS
DHW m o d eMODE : 1
DHWs t o r e w i t h
se n s o r
▼
User Interface Display
CH Settings
Explanation
Outdoor reset boost function increases CH set point by
increment (‘Temp’) if CH demand continues beyond pre-set
time limit (‘Time’).
CH set point will continue to increase until set point reaches
0
195°F / 91°C
Allowable Temperature Increment: 0..36 °F (0..20 °C)
Default Temperature increment: 0 °F (10 °C)
Allowable Time Delay: 1..120 minutes
Default Time Delay: 20 minutes
Maximum boiler power in CH mode limited by adjusting
‘Maximum Power CH’ setting. Boiler will not exceed this
value while operating in CH Mode.
Allowable Range: 1..100%
Default Setting: 100%
Two DHW modes are available
• DHW Mode = 0 ‘No DHW
DHW Settings
• DHW Mode is disabled
• The DHW thermostat input is ignored and the DHW
pump is not used.
• DHW Mode = 2 ‘DHW Store with Thermostat’
• Boiler reacts to DHW demand when DHW thermostat
input closes.
• Boiler modulates to meet DHW demand similar to CH
Mode except DHW set point is used. DHW set point set
in Settings’ submenu found in 'User Menu’.
• Simultaneous CH & DHW demands handled using DHW
Priority Timing. See ‘DHW Maximum Priority Time’
setting below.
Note:
• Outdoor reset function disabled while operating in DHW
Mode.
• Typical when using a DHW indirect storage tank.
• After DHW demand satisfi ed, boiler enters post purge
mode and DHW pump continues to run for 15 seconds.
68
DHWS E T T I NGS▲
DH Wm a x .p r i o r i t y
time
30mi n
SYSTEM TEST
Sett e s tpower
Of f
S
YSTEM TEST
Bo i l e rPumpOff
CH \ S y s t em Pump Off
DHWPumpOf f
APPENDIX A - CONTROL MODULE
User Interface Display
Allowed Range: 1 to 60 Minutes
DHW Settings
Default Setting: 30 Minutes
Explanation
Maximum time boiler operates in DHW mode limited by DHW
Maximum Priority Time Setting.
Priority timer starts when both CH and DHW demand is
present. Boiler will switch from DHW back to CH operation after
Maximum Priority Time has elapsed.
CH demand then has priority until Maximum Priority Time has
elapsed.
Process repeats until either CH or DHW demand satisfi ed.
System test can be activated via installer menu for testing
system at fi xed power rates.
Boiler can be started without CH or DHW demand being
present. System Test has priority over any system demand
while test mode activated.
System test mode automatically ends after 30 minutes boiler
resumes normal operation.
The following modes are available:
System Test
• Disabled
• Low power - Burner starts. After ignition period has
fi nished the burner stays at low power
• Ignition power - Burner starts. Stays at ignition power
• High power - Burner starts. After ignition period has
fi nished burner stays at high power.
Note:
• Before running system test modes, check if hydronic
system capable of dissipating heat.
• Both heat exchanger and CH pumps are activated during
system test only.
• During System Test Mode, boiler will run at fi xed power
rates until supply water temperature is 93°C/195°F
• All other safety functions remain active while in System
Test Mode.
69
NOTES
70
DateService PerformedCompany Name & Tech InitialsCompany Address & Phone #
71
CAC/BDP
7310 West Morris St.
Indianapolis, IN. 48231
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.