NOTE: Read the entire instruction manual before starting the
installation.
PAGE
SAFETY CONSIDERATIONS1........................
INTRODUCTION2..................................
INSTALLATION3...................................
Rules for Safe Installation and Operation3.............
Before Installing the Boiler3........................
Placing the Boiler5...............................
Near Boiler Piping5..............................
Combustion Air and Vent Pipe6.....................
Gas Supply Piping10.............................
Controls and Accessories14........................
START--UP AND CHECK--OUT PROCEDURES15........
Water Treatment and Freeze Protection15..............
Filling Boiler With Water and Purging Air for
Systems With Diaphragm Type Expansion Tanks17......
Filling Boiler With Water and Purging Air for
Systems With Conventional Closed Type
Expansion Tanks17...............................
Placing Boiler in Operation18.......................
Check Out Procedures and Adjustments18.............
CARE AND MAINTENANCE20.......................
SERVICE HINTS AND TROUBLESHOOTING23.........
REPAIR PART S3 5...................................
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due
to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as maintaining water level. All other operations must be
performed by trained service personnel. When working on
heating equipment, observe precautions in literature, on tags, and
on labels attached to or shipped with unit and other safety
precautions that may apply.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the unit and in instruction
manuals, be alert to the potential for personal injury.
UnderstandthesignalwordsDANGER,WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices
which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
ama
ASME
Read and obey the following rules to ensure safe installation and
operation:
1. Read the entire installation manual before beginning the
installation.Failure to follow these rules of safe
installation and operation and these instructions could
cause a malfunction of the boiler and result in death,
serious bodily injury, and/or property damage.
2. Check all applicable state and local building codes and
utility company requirements before installation. The
installation must conform with these requirements in their
entirety. In the absence of these codes, use NFPA
Installation Codes and good industry practices.
3. Before servicing the boiler, allow boiler to cool. Always
shut off any electricity and gas supply connected to the
boiler prior to servicing.
4. Inspect gas line for leaks.
5. Be certain gas input rate is correct. Overfiring may result
in early failure of boiler sections. This may cause
dangerous operation. Underfiring may result in too much
air for the pre--mix burner causing poor combustion or
loss of combustion.
6. Never vent the products of combustion from this boiler to
an enclosed space. Always vent to the outdoors. Never
vent to another room or to inside a building.
7. Be sure there is adequate air supply to boiler for complete
combustion.
8. Follow a regular service and maintenance schedule for
efficient and safe operation.
9. Keep boiler area clean and free from combustible and
flammable materials.
CERTIFIED
®
GAS SUPPLY OPENING
(1/2 NPT)
OPENING FOR RELIEF VALVE
DISCHARGE PIPE
JUNCTION BOX FOR 120V. POWER
& 24 V THERMOSTAT LEADS
COMBUSTION AIR INTAKE FITTING
(2 PVC)
6 1/4
25 1/4
4 7/16
TOP
OPENING FOR AIR VENT
AND EXPANSION TANK
CONNECTION
10. Proper through the wall or through the roof combustion
venting shall be in accordance with the materials and
methods described in this manual. Installation must
comply with local codes.
11. This boiler and related hot water heating systems are not
do-- it--yourself items. They must be installed and serviced
by qualified professionals.
!
WARNING
PERSONAL SAFETY AND INSTALLATION
HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
This boiler has been designed for residential
installations. If used for commercial applications, any
additional code requirements must be adhered to for
installation. This may require additional controls
including, but not limited to, a low water cut off,
manual reset high temperature limit, and wiring and/or
piping modifications. The manufacturer is not
responsible for any installation changes made to boiler
installation which are not described or acknowledged in
this manual.
INTRODUCTION
This appliance is a gas-- fired direct vent cast aluminum hot water
boiler. A revolutionary cast aluminum heat exchanger means
better heat transfer and thermal storage than similarly sized cast
iron boilers, which results in higher efficiency. The heating
system water absorbs large amounts of heat from the cast
aluminum heat exchanger, cooling the flue gases and causing
condensation. Sealed combustion, premix gas burner, and low
flame temperature means drastically reduced CO and NOx
emissions, which contribute to a cleaner and healthier
environment.
This appliance, unlike normal residential atmospheric and
induced draft units, takes its combustion air directly from the
outdoors (sealed combustion) and does not compete with
building occupants for fresh air. Sealed combustion (also known
as “direct vent”) is the safest and best way to obtain plenty of
RIGHT SIDE
LEVELING FEET
BACK
clean combustion air. The forced draft fan draws in the outside
combustion air to mix with gas, which flows into the pre--mix
burner and combusts. The fan then forces the resulting flue gases
from the boiler unit and provides a positive removal of the flue
gases from the building through inexpensive and readily available
PVC and CPVC pipes.
BOILER RATINGS AND CAPACITIES
Ratings shown are for sea level applications. (See Table 1.) The
boiler automatically derates input as altitude increases, at 4
percent for every 1000 feet above sea level. No alterations to
boiler are required for altitudes above sea level.
These low pressure gas-- fired hot water boilers are design certified
by CSA International, for use with natural and propane gases.
The boilers are constructed and hydrostatically tested for a
maximum working pressure of 50 psig (pounds per square inch
gauge) in accordance with ASME (American Society of
Mechanical Engineers) Boiler and Pressure Vessel Code Section
IV Standards for heating boilers.
The Boilers are certified in accordance with ANSI (American
National Standards Institute) Z21.13 standards as gas--fired, direct
vent, condensing, hot water boilers.
The Heating Capacity indicates the amount of heat available
after subtracting the losses up the stack. Most of this heat is
available to heat water. A small portion is heat loss from the
jacket and surfaces of the boiler, and it is assumed that this heat
stays in the structure. The Net I=B=R Rating represents the
portion of the remaining heat that can be applied to heat the
radiation or terminal units (i.e. finned tube baseboard, cast iron
radiators, radiant floor, etc.). The difference between the Heating
Capacity and the Net I=B=R Rating, called the piping and pickup
allowance, establishes a reserve for heating the volume of water
in the system and offsetting heat losses from the piping. The Net
I=B=R Ratings shown are based on a piping and pickup factor of
1.15 in accordance with the I=B=R Standard as published by the
Hydronics Institute. The Net I=B=R Rating of the boiler selected
should be greater than or equal to the calculated peak heating load
(heat loss) for the building or area(s) served by the boiler and
associated hot water heating systems. The manufacturer should be
consulted before selecting a boiler for installations having
unusual piping and pickup requirements.
A04049
2
Table 1—Sea Level Ratings--Natural and Propane Gases
{HEATING
MODELINPUT* (MBH)
125125112.59828490
15015013511728490
175175157.513728490
20020018015728490
*1 MBH = 1,000 Btuh
Btuh = British Thermal Units per Hour
{ AFUE (Annual Fuel Utilization Efficiency) and Heating Capacity is based on the D.O.E. (Department of Energy) test procedure
Ratings shown are for sea level applications. The boiler automatically derates input as altitude increases (See Table 6 and 7 for the approximate rate at given
altitudes). No alterations to boiler are required for altitudes above sea level.
CAPACITY*
(MBH)
INSTALLATION
STEP 1 —Rules for Safe Installation and Operation
1. Read the entire installation manual before beginning the
installation. Failure to follow these rules for safe
installation and operation and these instructions could
cause a malfunction of the boiler and result in death,
serious bodily injury, and/or property damage.
2. Check all applicable state and local building codes and
utility company requirements before installation. The
installation must conform with these requirements in their
entirety. In the absence of these codes, use NFPA
Installation Codes and good industry practices.
3. Before servicing the boiler, allow the boiler to cool.
Always shut off any electricity and gas supply connected
to the boiler prior to servicing.
4. Inspect gas line for leaks.
5. Be certain gas input rate is correct. Over firing may result
in early failure of the boiler sections. This may cause
dangerous operation. Under firing may result in too much
air for the pre--mix burner causing poor or loss of
combustion.A combustion analyzer is required to
properly determine the correct firing rate.
6. Never vent the products of combustion from this boiler to
an enclosed space. Always vent to the outdoors. Never
vent to another room or to inside a building.
7. Be sure there is adequate outdoor air supply to boiler for
complete combustion.
8. Follow a regular service and maintenance schedule for
efficient and safe operation.
9. Keep boiler area clean of debris and free of combustible
and flammable materials.
10. Proper through the wall or through the roof combustion
venting shall be in accordance with the materials and
methods described in this manual. Installation must
comply with local codes.
11. This boiler and related hot water heating systems are not
do it yourself items. They must be installed and serviced
by qualified professionals.
STEP 2 —Before Installing the Boiler
Complete all of the following prior to installing the boiler.
CODES
This boiler product is a gas--fired, direct vent, condensing boiler
and must be installed in accordance with all applicable federal,
state and local building codes including, but not limited to the
following:
NET I=B=R
RATING* (MBH)
Canada -- Installation shall be in accordance with CSA--B149.1
and .2 installation codes.
Where required by the authority having jurisdiction, the
installation must conform to the American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers, No. CSD--1.
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the National Fuel Gas Code, ANSI Z223.1 -latest revision.
Installers -- Follow local regulations with respect to installation
of CO (Carbon Monoxide) Detectors. Follow maintenance
recommendations in this manual.
BOILER
Check to be sure you have selected the boiler with the proper
capacity before continuing the installation. The I=B=R Rating of
the boiler selected should be greater than or equal to the
calculated peak heating load (heat loss) for the building or area(s)
served by the boiler and associated hot water heating systems.
(See Table 1.)
Heat loss calculations should be based on approved industry
methods.
CONSIDERATIONS FOR BOILER LOCA
Before selecting a location for the boiler, the following should be
considered. Each boiler considered for installation must be:
SHIPPING
WEIGHT (LBS)
}AFUEFLUE DIAM.
2” CPVC and 3”
PVC
2” CPVC and 3”
PVC
2” CPVC and 3”
PVC
2” CPVC and 3”
PVC
SIZING
TION
SSupplied with the correct type of gas (natural gas or
propane).
SConnected to a suitable combustion air intake piping
system to supply the correct amounts of fresh (outdoor)
air for combustion (maximum length 60 ft).
SConnected to a suitable venting system to remove the
hazardous products of gas combustion (maximum
length60ft).
SConnected to a suitable hot water heating system.
SSupplied with a suitable electrical supply for all boiler
motors and controls.
SConnected to a properly located thermostat or operating
control (not included with boiler).
SPlaced on level surface (must NOT be installed on
carpeting).
SCondensate drain line must be pitched down to floor
drain or external condensate pump with reservoir at 1/4
in. per foot (wood frame or blocks may be used to raise
boiler).
United States -- Installation shall conform with National Fuel
Gas Code (NFPA--54/ANSI Z223.1-- latest edition)
3
Table 2—Boiler Clearances (In.)
UNIT
Top188
Left Side82424
Right Side1------
Base1------
Front02424
Back1------
Intake/Vent Piping0------
Near Boiler Hot Water Piping1------
LOCATING THE BOILER
All distances measured from the cabinet of the boiler. (See Table
2.)
1. Select a location which is level, central to the piping
systems served and as close to the vent and air intake
terminals as possible.
2. Accessibility clearances, if more stringent (i.e. larger
clearances) than required fire protection clearances, must
be used for the boiler installation. Accessibility clearances
may be achieved with the use of removable walls or
partitions.
3. The boiler is approved for installation in closets and on
combustible floors. This boiler shall NOT be installed on
carpeting.
4. The clearances shown in Table 2indicate required
clearances per CSA listing. A minimum 1 in. clearance
must be maintained between combustible construction and
each of the right, top and back surfaces of the boiler. A
minimum 8” clearance is required on the left side,
to allow room for the inlet air pipe. An 18” clearance must
be maintained at the front where passage is required for
cleaning or servicing, inspection or replacement of any
parts that normally may require such attention. Allow at
least 24” at the front and left side and 8” at the top for
servicing. No combustible clearances are required to
venting or combustion air intake piping.
5. Equipment shall be installed in a location which facilitates
the operation of venting and combustion air intake piping
systems as described in this manual.
6. Advise owner of boiler to keep venting and combustion
air intake passages free of obstructions. Both the venting
and combustion air intake piping systems connected to the
outdoors must permit flow through the piping systems
without restrictions for the boiler to operate.
7. The boiler shall be installed such that the automatic gas
ignition system components are protected from water
(dripping, spraying, rain, etc.) during operation and
service (circulator replacement, control replacement, etc.).
8. The boiler must be located where ambient temperatures
(minimum possible room air temperatures where boiler is
installed assuming boiler is not in operation and therefore
contributes no heat to the space) are always at or above 32
degrees F to prevent freezing of liquid condensate.
COMBUSTION AND VENT PIPE
This boiler requires a dedicated direct vent system. In a direct
vent system, all air for combustion is taken directly from outside
atmosphere, and all flue products are discharged to outside
atmosphere.
Combustion air and vent pipe connections must terminate
together in the same atmospheric pressure zone, either through
the roof or sidewall (roof termination preferred). See Fig. 8
through 12 for required clearances.
COMBUSTIBLE
CONSTRUCTION
REQUIREMENTS
ACCESSIBILITY/
CLEANING
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in fire,
explosion, personal injury or death.
Keep boiler area clear of debris and free of flammable
and combustible materials, vapors, and liquids to
prevent fires.
!
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in property
damage, personal injury, or death.
When vent pipe is exposed to temperatures below
freezing, such as when it passes through an unheated
space or when a chimney is used as a chaseway, vent
pipe must be insulated with 1/2” Armaflex or
equivalent. In extreme cold climate areas, use
3/4”Armaflex or equivalent. Combustion air must be
clean outdoor air. Combustion air must not be taken
from inside structure because that air frequently is
contaminated by halogens, which include fluorides,
chlorides, phosphates, bromides and iodides. These
elements are found in aerosols, detergents, bleaches,
cleaning solvents, salts, air fresheners, paints, adhesives
and other household products. Locate combustion air
inlet as far away as possible from swimming pool and
swimming pool pump house.
All combustion air and vent pipes must be airtight and
watertight. Combustion air and vent piping must also
terminate exactly as shown in Fig. 8 or 9. If the
concentric vent termination is being used, refer to Fig.
10 through 12 for proper setup.
Vent connections serving appliances vented by natural
draft shall not be connected into any portion of
mechanical draft systems operating under positive
pressure.
Solvent cements are combustible. Keep away from heat,
sparks, open flame. Use only in well ventilated areas.
Avoid breathing in vapor or allowing contact with skin
or eyes.
CONDENSATE DRAIN REQUIREMENTS
Condensate drain line to be pitched down to floor drain at a
minimum of 1/4” per foot. An external condensate pump (not
furnished) may be used if floor drain is not available. The
condensate pump must be designed for flue gas condensate
application.
WARNING
WARNING
SERVICING
4
NOTE: Condensate trap is to be built in the field per Fig. 7.
Wood frame or blocks may be used to raise the boiler
to maintain drain pitch or to be above external condensate
pump reservoir.
There is a 115 volt AC receptacle provided on the service switch
junction box located at the boiler right side, to provide power for
an external condensate pump (if needed).
FOUNDATION
REQUIREMENTS
Boiler must be placed on level surface. Boiler is NOT to be
installed on carpeting.
NOTE: If boiler is not level, condensate drain lines will not
function properly. Adjustable feet are located on the boiler to
make up for minor surface irregularities or tilt.
Wood frame or blocks may be used to raise boiler to maintain
drain pitch or to be above external condensate pump reservoir.
REMOVAL OF EXISTING BOILER FROM
VENT
SYSTEM
COMMON
When an existing boiler is removed from a common venting
system, the common venting system is likely to be too large for
proper venting of the appliances remaining connected to it.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps oulined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide
poisoning or death.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system are
not in operation.
9. After it has been determined that each appliance remaining
connected to the common venting system properly vents
when tested as outlined above, return doors, windows,
exhaust fans and any other gas--burning appliances to their
previous condition of use.
STEP 3 —Placing the Boiler
The boiler should be placed to provide the most direct
connections to the combustion air, vent and system piping as
possible.
Place crated boiler as close to selected location as possible and
uncrate boiler. The uncrated boiler may be moved into position
with an appliance dolly or 2--wheel hand truck. The dolly or hand
truck should be inserted under the right hand side of the boiler.
It is possible to slide the boiler for a short distance on a smooth
floor or surface.
SUPPLY TO
SYSTEM
GATE VALVE
FEED
WATER
REDUCED PRESSURE
BACKFLOW PREVENTER
PRESSURE
REDUCING VALVE
SHUT OFF VALVE
PURGE VALVE
SERVICE
VALV E
CIRCULATOR
CAN VENT
SERVICE
VALV E
RETURN FROM
SYSTEM
EXPANSION TANK
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch as required in the National Fuel Gas Code,
ANSI Z223.1--2002/NFPA 54--2002 or the CSA B149.1,
Natural Gas and Propane Installation Code and these
instructions. Determine there is no blockage or restrictions,
leakage, corrosion and other deficiencies which could
cause an unsafe condition.
3. When it is practical, close all building doors and windows
and all doors between the space in which the appliances
remaining connected to the common venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryer and any appliance not connected to
the common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhaust, so they will
operate at maximum speed. Do not operate a summer
exhaust fan.
6. Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliances
will operate continuously.
7. Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a
match or candle, or the smoke a cigarette, cigar or pipe.
8. Any improper operation of the common venting system
should be corrected so the installation conforms with the
National Fuel Code, ANSI Z223.1--2002/NFPA 54--2002
and/or CSA--B149.1, Natural Gas and Propane Installation
Code for Canadian standards.
A04050
Fig. 2 --- Single Zone Boiler Piping
NOTE: Refer to manual section “LOCATING THE BOILER”
for required clearances for servicing and maintenance.
STEP 4 —Near Boiler Piping
!
CAUTION
UNIT CORROSION HAZARD
Failure to follow this caution may result in property or unit
damage.
Copper supply and return piping must NOT be installed
directly into aluminum boiler section castings due to
galvanic corrosion between dissimilar metals. Iron or steel
bushings or pipe nipples should be used between copper
system piping and boiler to make final connection to boiler.
Also, the use of dielectric unions is acceptable. The
packaged boiler is furnished with iron piping in the front
boiler section for the supply and return connections.
When the installation of the boiler is for a new heating system,
first install all of the radiation units (panels, radiators, baseboard,
or tubing) and the supply and return mains. After all heating
system piping and components have been installed, make final
connection of the system piping to the boiler.
5
A hot water boiler installed above radiation level must be
equipped with a low water cut off device. A periodic inspection is
necessary, as is flushing of float type devices, per low water cut
off manufacturer’s specific instructions.
EXPANSION TANK AND MAKE --UP WA
TER
Determine required system fill pressure, system design
temperature, and system water content. Boiler contains 2.6
gallons (U.S.) Size expansion tank accordingly. Consult
expansion tank manufacturer for proper sizing information.
Connect properly sized expansion tank (not furnished) as shown
in Fig. 6 for diaphragm type expansion tank. For diaphragm type
expansion tanks, adjust the tank air pressure to match the system
fill pressure. Install air vent (furnished) as shown for diaphragm
type expansion tank system only. Install make--up water
connections as shown and per local codes. If a pressure reducing
valve is used, adjust to match the system fill pressure.
ZONE SERVICE
VALVE
FEED
WATER
RETURN FROM
ZONES
ZONE SERVICE
VALVE
SUPPLY TO
ZONES
ZONE SERVICE
VALVE
GATE VALVE
REDUCED PRESSURE
BACKFLOW PREVENTER
A04051
EXPANSION TANK
SHUT OFF VALVE
PURGE VALVE
PRESSURE
REDUCING VALVE
CAN VENT
CIRCULATOR
ZONE VALVE
ZONE SERVICE
VALVE
Fig. 3 --- Multizone Boiler Piping with Zone Valves
In connecting the cold make--up water supply to the boiler, make
sure that clean water supply is available. When the water supply
is from a well or pump, a sand strainer should be installed at the
pump.
PRESSURE RELIEF VALVE/TEMPERA
PRESSURE
GAUGE
TURE
The boiler is furnished with a relief valve and temperature
pressure gauge in the boiler parts bag. Provide 3/4” piping from
the supplied relief valve to a local floor drain, but leave an air gap
between piping and drain. Install the relief valve as shown in Fig.
5. No shutoff of any description shall be placed between safety
relief valve and the boiler, or on the discharge pipes between such
safety valve and the atmosphere. Installation of the safety relief
valve shall conform to ANSI/ASME Boiler and Pressure Vessel
Code, Section IV. The manufacturer is not responsible for any
water damage.
SUPPLY AND RETURN
LINES
The packaged boiler unit is set up to receive 1--1/4” NPT supply
and return piping from top access.
NOTE: The circulator pump is furnished within a carton inside
the boiler cabinet and can be installed at the installer preferred
location.
CONDENSATE DRAIN
PIPING
The condensate trap is to be field installed as shown in Fig. 7.
The 1/2” PVC condensate drain fittings are provided in the loose
parts bag. Condensate drain to be pitched down to floor drain at a
minimum of 1/4” per foot.
The 1/2” diameter schedule 40 PVC or CPVC condensate drain
piping and pipe fittings must conform to ANSI standards and
ASTM D1785 or D2846. Schedule 40 PVC or CPVC cement
and primer must conform to ASTM D2564 or F493. In Canada,
use CSA or ULC certified schedule 40 PVC or CPVC drain pipe
and cement.
A condensate pump with a reservoir (not furnished) may be used
to remove condensate to a drain line (sanitary line) above boiler if
a floor drain is not available or is inaccessible.
FILLING CONDENSATE TRAP WITH WA
TER
NOTE: On the initial start up, the condensate trap must be
manually filled with water.
The following are the steps required to initially fill the condensate
trap for start up. These steps are only required at the initial start
up or if maintenance requires draining of the condensate trap:
1. Pour about 1 cup of cold tap water into the vent drain line.
2. Excess water should go through the overflow and out
through the condensate drain line. Verify proper operation
of the drain line (or external condensate pump if used).
CHILLED WATER
PIPING
The boiler, when used in connection with a refrigeration system,
must be installed so the chiller medium is piped in parallel with
the boiler with appropriate valves to prevent the chilled medium
from entering the boiler.
The boiler piping system of a hot water boiler connected to
heating coils is located in air handling units, where they may be
exposed to refrigerated air circulation, must be equipped with
flow control valves or other automatic means to prevent gravity
circulation of the boiler water during cooling cycle.
STEP 5 —Combustion Air and Vent Pipe
CONNECTIONS AND TERMINA
TIONS
For boilers connected to gas vents or chimneys, vent installations
shall be in accordance with part 7, V enting of Equipment, of the
National Fuel Gas Code NFPA 54-- 2002/ANSI Z223.1-- 2002,
CSA-- B149.1 and B149.2, and applicable provisions of the local
building codes.
Provisions for combustion and ventilation air must be in
accordance with section 5.3, Air For Combustion and Ventilation,
of the National Fuel Gas Code NFPA 54-- 2002/ANSI
Z223.1--2002, CSA--B149.1 andB149.2, or applicable
provisions of the local building code.
These boilers require a dedicated direct vent system. All air for
combustion is taken directly from outdoors through the
combustion air intake pipe. All flue products are discharged to
the outdoors through the vent pipe.
1. See Fig. 8 through 12 for combustion air and vent pipe
roof and sidewall termination (Roof termination is
preferred). Combustion air and vent pipes must terminate
together in same atmospheric pressure zone as shown.
Construction through which vent and air intake pipes may
be installed is a maximum 24 inches, minimum 1/4”
thickness.
2. Combustion air and vent pipe fittings must conform to
American National Standards Institute (ANSI) standards
and American Society for Testing and Materials (ASTM)
standardsD1784(schedule--40CPVC),D1785
(schedule--40 PVC), D2665 (PVC--DWV), D2241
(SDR--21 and SDR--26 PVC), D2661 (ABS-- DWV), or
F628 (schedule--40 ABS). Pipe cement and primer must
conform to ASTM standards D2564 (PVC) or D2235
(ABS).
In Canada construct all combustion air and vent pipes for
this unit of CSA or ULC certified schedule--40 CPVC,
schedule--40 PVC, PVC--DWV or ABS--DWV pipe and
pipe cement. SDR pipe is NOT approved in Canada.
6
ZONE SERVICE
ZONE SERVICE
VALVE
ZONE SERVICE
VALVE
VALVE
SUPPLY TO
ZONES
ZONE SERVICE VALVE
FLOW CHECK
VALVE
FEED
WATER
RETURN FROM
ZONES
GATE VALVE
REDUCED PRESSURE
BACKFLOW PREVENTER
A04052
FLOW CHECK VALVE
PRESSURE
REDUCING VALVE
EXPANSION TANK
NOTE: When zoning with circulators, the furnished circulator pump should
be used as one of the zone pumps. Each stripped end of the electrical wires
for the circulator pump inside the junction box should be taped or wired
nutted to prevent short circuits. Unplug the circulator pump wiring at the
integrated boiler control.
CIRCULATORS
CAN VENT
Fig. 4 --- Multizone Boiler Piping with Circulators
3. Combustion air and vent piping connections on boiler are
2”, but must increase to ( 3”). Due to potential for flue gas
temperatures over 155_F, the first 5 feet of vent pipe must
be CPVC, the remaining vent pipe can be PVC. If any
elbows are employed within the first 2--1/2 feet of vent,
they must be CPVC. Two -- 30” pieces of 2” CPVC pipe
and one -- 2” CPVC coupling are furnished with the boiler.
NOTE: The exhaust transition from 2” pipe to 3” pipe must be
made in a vertical run. Transition pieces not included. (See Fig.
13.)
Combustion and Vent Pipe Lengths
The length of pipe is counted from the boiler jacket (air intake
pipe) or from vent tee (vent pipe). The first five feet of “Total
Equivalent Length” of vent pipe must be CPVC.
Boiler Size3” Pipe Min.
Venting
125--- 2006ftinlength+
4 --- 9 0 _ elbows
3” Pipe Max.
60 ft in length and
u p t o 4 --- 9 0 _
elbows
Reduce the maximum vent length 5 feet per each additional
elbow.
1. Combustion air and vent piping to be pitched back to
boiler at minimum 1/4” per foot from intake and vent
terminals so that all moisture in combustion air and vent
piping drains to boiler. Pipes must be pitched continuously
with no sags or low spots where moisture can accumulate
and block the flow of air or flue gas. Combustion air and
vent pipes must be airtight and watertight.
PRESSURE
RELIEF DEVICE
A04053
Fig. 5 --- Relief Valve Discharge Piping
2. Consideration for the following should be used when
determining an appropriate location for termination of
combustion air and vent piping:
a. Comply with all clearances required as stated in
paragraph 3 below.
b. Termination should be positioned where vent vapors
will not damage plants/shrubs or air conditioning
equipment.
c. Termination should be positioned so that it will not be
affected by wind eddy, airborne leaves, snow, or
recirculated flue gases.
d. Termination should be positioned where it will not be
subjected to potential damage by foreign objects, such
as stones, balls, etc.
e. Termination should be positioned where vent vapors
are not objectionable.
f. Put vent on a wall away from the prevailing winter
wind. Locate or guard the vent to prevent accidental
contact with people or pets.
g. Terminate the vent above normal snowline. Avoid
locations where snow may drift and block the vent. Ice
or snow may cause the boiler to shut down if the vent
becomes obstructed.
h. Under certain conditions, flue gas will condense,
forming moisture, and may be corrosive. In such cases,
steps should be taken to prevent building materials at
the vent from being damaged by exhaust of flue gas.
7
COMBINATION QUICK FILL
VALVE, STRAINER, CHECK
VALVE AND PRESSURE
REDUCING VALVE
COLD WATER FILL
PRESSURE
REDUCING VALVE
REDUCED PRESSURE
BACKFLOW PREVENTER
GATE VALVE
Fig. 6 --- Diaphragm Type Expansion Tank Piping
FEED
WATER
DIAPHRAGM TYPE
EXPANSION TANK
EXPANSION TANK SERVICE VALVE
(GATE VALVE OR FULL
PORT BALL VALVE)
AUTOMATIC AIR
VENT*
3/4" x 1/8" BUSHING*
- FURNISHED IN
*
PARTS BAG
A04054
TO CONDENSATE DRAIN
(FIELD SUPPLIED)
1/2" UNTHREADED
PVC TEE
1/2" UNTHREADED
PVC PIPING
3-3/4" LONG
TO EXHAUST VENT
(2" CPVC)
1/2" ADAPTER
MALE NPT X SOCKET WELD
PVC PIPING
1/2" UNTHREADED
PVC PIPING
1-3/8" LONG
1/2" UNTHREADED
PVC PIPING
2" LONG
1/2" UNTHREADED
PVC PIPING
3-3/4" LONG
1/2" UNTHREADED
PVC ELBOW
1/2" UNTHREADED
PVC ELBOW
1-3/8" LONG
2" UNTHREADED MALE
X 2" NPT MALE
PVC BUSHING
2" NPT MALE PVC BUSHING
Fig. 7 --- Condensate--Drain Piping
TO BOILER FLUE OUTLET
(2" CPVC)
A04055
8
Table 3—Gas Piping Sizes
NATURAL GAS
Length of Pipe (ft.)
2092,000190,000350,000625,000
4063,000130,000245,000445,000
6050,000105,000195,000365,000
Length of Pipe (ft.)
20131,000216,000189,000393,000
4090,000145,000129,000267,000
6072,000121,000103,000393,000
* Outside diameter
The length of pipe or tubing should be measured form the gas meter or propane second stage regulator
1/2”3/4”1”1--- 1/4”
Copper Tubing*Iron Pipe
5/8”3/4”1/2”3/4”
Pipe Capacity --- BTU per hour Input Includes Fittings
PROPANE GAS
Pipe Capacity --- BTU per hour Input Includes Fittings
5. Clean and dry all surfaces to be joined.
3. The venting system shall terminate at least 3 feet above
any forced air inlet (except the boiler’s combustion air
inlet) within 10 feet. The venting system shall terminate at
least 12 inches from any air opening into any building.
The bottom of the vent shall be located at least 12 inches
above grade. Termination of the vent shall be not less than
7 feet above an adjacent public walkway. The vent
terminal shall not be installed closer than 3 feet from the
inside corner of an L shaped structure. Termination of the
vent should be kept at least 3 feet away from vegetation.
The venting system shall terminate at least 4 feet
horizontally from, and in no case above or below electric
meters, gas meters, regulators, and relief equipment. If
multiple terminations are used, there must be a minimum
of 3 feet between the exhaust of one termination and the
air intake of the next termination.
INSTALLA
TION
1. Attach combustion air intake piping to supplied Fernco 2”
coupling on CVI gas valve. Attach vent piping to
furnished 2” CPVC vent tee on draft inducer outlet.
NOTE: All pipe joints are to be watertight
2. Working from the boiler to the outside, cut pipe to
required length(s).
3. Deburr inside and outside of pipe. Remove all chips and
shavings.
4. Chamfer outside edge of pipe for better distribution of
6. Check dry fit of pipe and mark insertion depth on pipe.
NOTE: It is recommended that all pipes be cut, prepared, and
pre--assembled before permanently cementing any joint.
7. After pipes have been cut and pre--assembled, apply
cement primer to pipe fitting socket and end of pipe to
insertion mark. Quickly apply approved cement to end of
pipe and fitting socket (over primer). Apply cement in
light, uniform coat on the inside of socket to prevent
buildup of excess cement. Apply second coat.
8. While cement is still wet, insert pipe into socket with a 1/4
turn twist. Be sure pipe is fully inserted into fitting socket.
9. Wipe excess cement from joint. A continuous bead of
cement will be visible around perimeter of a properly
made joint.
10. Handle pipe joint carefully until cement sets.
11. Support combustion air and vent piping a minimum of
every 5 feet using pre--formed metal hanging straps. Do
not rigidly support pipes.Allow movement due to
expansion and contraction.
NOTE: Rigid supports will cause excess noise in vent piping
12. Slope combustion air and vent pipes toward boiler a
minimum of 1/4” per linear foot with no sags between
hangers.
13. Use appropriate methods to seal openings where vent and
combustion air pipes pass through roof or side wall.
primer and cement.
12" MINIMUM VERTICAL
SEPARATION BETWEEN
COMBUSTION AIR INTAKE
AND VENT
The gas pipe to your boiler must be the correct size for the length
of run and for the total BTU per hour input of all gas utilization
equipment connected to it. See Table 3 for the proper size. Be
sure your gas line complies with local codes and gas company
requirements.
The boiler and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psig (3.5kPa).
The boiler must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to
or greater than 1/2 psig (3.5kPa).
Max. Gas Supply
Pressure
Min. Gas Supply
Pressure
NOTE: Check gas supply line pressure with all gas appliances
running
CONNECTING THE GAS
Refer to Fig. 14 for the general layout at the boiler, which shows
the basic fittings you will need. The gas line enters the boiler
through the left side panel.
The boiler is equipped with a 1/2” NPT connection on the gas
valve for supply piping and 1/2” NPT ball cock for manual
shutoff. The following rules apply:
1. Use only those piping materials and joining methods listed
as acceptable by the authority having jurisdiction, or in the
absence of such requirements, by the National Fuel Gas
Code NFPA 54-- 2002/ANSI Z223.1--2002. In Canada,
follow the CAN/CGA B149.1 and .2 Installation Codes
for Gas Burning Appliances and Equipment.
2. Use pipe joint compound suitable for liquefied petroleum
gas on male threads only.
3. Use ground joint unions.
4. Install a sediment trap upstream of gas controls.
5. Use two pipe wrenches when making the connection to
the gas valve to keep it from turning.
6. Install an additional external manual shutoff valve in the
vertical pipe about 5 feet above floor outside the boiler
jacket.
7. Tighten all joints securely.
8. Propane gas connections should only be made by a
licensed propane installer.
9. Two stage regulation should be used by the propane
installer.
10. Propane gas piping should be checked out by the propane
installer.
11. It is recommended to use a 1/2” union suitable for natural
and propane gas after the ball cock to facilitate service on
the unit.
Y
Natural GasPropane Gas
10” w.c.
4” w.c.
PIPING
14” w.c.
10” w.c.
CHECKING THE GAS
After all connections have been made, check immediately for
leaks. Open the manual shutoff valve. Test for leaks by applying
soap suds (or a liquid detergent) to each joint. Bubbles forming
indicate leak. CORRECT EVEN THE SMALLEST LEAK AT
ONCE.
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Never use a match or open flame to test for leaks.
STEP 7 —Electrical Wiring
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Turn off electrical power at fuse box before making any
line voltage connections. Follow electrical codes.
All electrical work must conform to local codes as well as the
National Electrical Code, ANSI/NFPA--70, latest revision. In
Canada, electrical wiring shall comply with the Canadian
Electrical Codes, CSA--C22.1 and .2.
ELECTRICAL POWER SUPPL
Prior to making any line voltage connections, service switch at
boiler should be in the off position and the power turned off at the
fuse box.
Run a 120 volt circuit from a separate over current protection
device in the electrical service entrance panel. (NOTE: Use
copper conductors only.) This should be a 15 ampere circuit. A
service switch has been pre--wired and located on the exterior
boiler jacket. See Fig. 15 for diagram showing location of service
switch junction box and power supply connection points.
Connect black (hot) lead from the power supply to either of the
unused brass screws on the service switch. Connect the white
(neutral) lead from the power supply to the white screw on the
service switch. Connect the green (ground) lead from the power
supply to the ground (green) screw on the service switch. The
receptacle on the service switch is always powered regardless of
whether the switch is on or off, and could be used as a power
supply for an external condensate pump if one is used.
The boiler, when installed, must be electrically grounded in
accordance with the requirements of the authority having
jurisdiction or, in the absence of such requirements, with the
National Electrical Code, ANSI/NFPA--70, latest revision. In
Canada, electrical wiring shall comply with the Canadian
Electrical Codes, CSA--C22.1 and .2.
Run a 14 gauge or heavier copper wire from the boiler to a
grounded connection in the service panel or a properly driven and
electrically grounded ground rod.
PIPING
WARNING
WARNING
Y
10
OVERHANG
12” MINIMUM
90°
VENT
3”
MAXIMUM
SEPARATION
15”
18”
MAXIMUM
MAXIMUM
LESS THAN 12” CLEARANCE
OVERHANG
12” MINIMUM
VENT
12” SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR INTAKE
AND BOTTOM OF VENT
NOTE: SECURING STRAP MUST BE
FIELD INSTALLED TO PREVENT
MOVEMENT OF TERMINATION KIT IN SIDE WALL.
(FIELD SUPPLIED)
ELBOW
(FIELD
SUPPLIED)
STRAP
Fig. 11 --- Concentric Vent
COMBUSTION AIR
VENT
1"
MAXIMUM
A99165
A04057
MAINTAIN 12 IN.CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE
WHICHEVER IS
GREATER
Fig. 10 --- Concentric Vent Terminations
A01382
11
COMBUSTION AIR
ROOF/BOOT
FLASHING
(FIELD
SUPPLIED)
NOTE: SUPPORT MUST BE FIELD INSTALLED
TO SECURE TERMINATION KIT TO STRUCTURE
VENT
Fig. 12 --- Concentric Vent Roof Installation
3 INCH INTAKE AND
EXHAUST TERMINATIONS
INSTALL FIELD SUPPLIED
2˝ BY 3˝ TRANSITION IN
THE VERTICAL POSITION ONLY
VENT
MAINTAIN 12 IN.
(18 IN FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
SUPPORT
(FIELD
SUPPLIED)
ELBOW
(FIELD
SUPPLIED)
COMBUSTION AIR
2˝ (50.8MM) CPVC COUPLING
(FURNISHED)
2˝ (50.8MM) CPVC VENT PIPING
(FURNISHED & REQUIRED)
A04058
INSTALL YOUR THERMOSTA
T
The thermostat location has an important effect on the operation
of your boiler system. BE SURE TO FOLLOW THE
INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT.
Locate the thermostat about five feet above the floor on an inside
wall. It may be mounted directly on the wall or on a vertically
mounted outlet box. It should be sensing average room
temperature. Avoid the following:
DEAD SPOTS COLD SPOTSHOT SPOTS
Behind doorsConcealed
pipes or ducts
Corners and
alcoves
Stairwells --drafts
Unheated
rooms on other side of wall
Concealed
pipes
Lamps
FireplaceDirect
sunlight
TV sets
Radios
Kitchens
Set heat anticipator at 0.7 amps. Connect 24 volt thermostat leads
to the # (2) yellow wires located in service switch junction box,
located on outer jacket of boiler. See Fig. 15 for service switch
junction box and thermostat field wiring connections.
CONNECT CIRCULATOR PUMP
WIRING
See Fig. 15 for service switch junction box and circulator pump
field wiring connections. If the two 120 volt circulator wire
terminals inside the junction box are not used, leave the two wire
nuts to prevent the short circuit.
!
CAUTION
5˝
EXHAUST TEE
(FURNISHED)
Fig. 13 --- Combustion Air and Vent Piping
2˝ (50.8MM) COMBUSTION AIR
INTAKE PIPING
NOT IN
HORIZONAL
SECTION
A04177
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper unit
operation.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
GAS CONNECTION
A04061
Fig. 14 --- Gas Piping
12
Fig. 15 --- Field Wiring Connections
A06088
If any of the original wire as supplied wiht this appliance must be replaced, it must be replaced with type 150_C Thermoplastic wire or its equivalent
A06089
Fig. 16 --- Schematic Wiring Connections
13
Fig. 17 --- Ladder Wiring Diagram
A06090
STEP 8 —Controls and Accessories
This section provides a brief description of the key controls and
accessories found in this boiler.
See Troubleshooting in the Service Hints section of this
installation manual for detailed sequences of operation and
troubleshooting procedures. See the Repair Pa rts section of this
manual for locations of all control components and accessories
described.
INTEGRATED BOILER CONTROL
The Integrated Boiler Control (IBC) is a microprocessor based
controller for a high efficiency gas boiler that monitors all safety
controls and controls the operation of the combustion air blower,
circulator pump, burner, and a combination hot surface
igniter/flame sensor. This controller is not intended for use with a
vent damper. This controller is mounted on the control panel
inside of the boiler and contains five diagnostic indicator lights.
(See Fig. 18 and T able 4.)
GAS CONTROL VAL
The electronic 24 volt gas control valve contains a 1:1 gas/air
pressure regulator to control the gas flow to the main burner of
the appliance and is suited for natural and propane gases. The
valve is rated in accordance with ANSI Z21.21-- latest revision
and CGA--6.5--M95. (See Fig. 19.)
HOT SURFACE
The 120 volt Hot Surface Igniter heats up to 1800_F to initiate
combustion of the gas in the burner. The igniter is mounted next
to the burner through the gas/air mixer. The igniter also serves as
a means for proving the main burner flame by flame rectification.
In the event of a lack of flame signal on three (3) consecutive
trials for ignition, the IBC will lockout. The “VALVE” and
“FLAME” diagnostic indicator lamps (lamp “D” and “E” on the
IBC, see Fig. 18) will blink indicating the failure mode as a lack
of flame signal. The IBC is manually reset from lockout by either
VE
IGNITER
(IBC)
removing and reestablishing the thermostat’s call for heat, or by
turning the service switch off, then back on.
L4006A HIGH LIMIT AQUASTAT
The High Limit Aquastat Control determines the maximum boiler
water temperature and also provides a means for protecting the
boiler and heating system from unsafe operating conditions
which could damage the boiler. The aquastat is mounted in the
1/2” NPT control well and 3/4” x 1/2” bushing on the top of the
front boiler section at the hot water outlet. The aquastat is tied in
with the IBC and is factory set at 180_F water temperature. The
high limit setpoint is field adjustable and may be set anywhere
between 100_F and 200_F . The field setpoint adjustment for each
installation depends on heating system requirements. The
aquastat automatically resets when the boiler water temperature
decreases 20_ below the setpoint value. The reset value can be
field adjusted within a range of 5 to 30_F.
NOTE: The maximum setpoint of the Aquastat must not exceed
200_F.
CASTING TEMPERATURE SAFETY
In the event of lack of or loss of water in the boiler, the Casting
Temperature Safety Switch (230_F setpoint) installed on the top
of the aluminum boiler section behind the supply piping shuts off
the boiler by shutting off power to the Integrated Boiler Control
(IBC) and causes the Power Indicator Light to go out. This fault
requires manual reset of the casting temperature safety switch to
restart the boiler. Verify that the boiler is properly filled with
water before resetting this switch.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
Never run cold water into a hot, empty boiler.
CONTROL
SWITCH
14
DIFFERENTIAL PRESSURE AIR PROVING SWITCH
(2)
The diaphragm type differential pressure switches are connected
by vinyl tubing to the gas valve and the air inlet connection on
the negative side and the sight glass adapter on the positive side.
The pressure switches monitors airflow by sensing the diffential
pressure measured in inches of water (“ w.c.). The factory settings
on these switches are 0.5” w.c. on the normally open switch and
3.5” w.c. for the normally closed switch. See the Sequence ofOperation section of this manual for details on the operation of
the differential pressure switches.
BLOWER
The blower provides a means for pushing combustion air into and
through the mixer, the burner, and the flue ways of the cast
aluminum boiler section before being discharged through the vent
piping to the outdoors.
CIRCULATOR
PUMP
Every forced hot water system requires at least one circulating
pump. The circulating pump imparts the necessary energy to
move the water through the closed loop supply and return piping
systems, terminal heating equipment (i.e. finned tube radiators,
etc.) and back through the boiler for reheating. To provide the
required hot water flow rates, the circulator pump must be
properly sized to overcome frictional losses (usually measured in
feet of water, also referred to as “pump head loss”) of the supply
and return piping systems and boiler. The circulator pump is
furnished in a carton within the boiler cabinet. The circulator(s)
should always be located in the downstream (i.e., “pumping
away”) side of the expansion tank.
DRAIN VAL
VE
The manual drain valve provides a means of draining the water in
the heating system, including the boiler and hot water supply and
return piping systems installed above the drain valve. This drain
valve is installed in the 3/4” tapping at the bottom of the front
boiler section. Any piping installed below the elevation of this
drain valve will require additional drain valves to be installed at
low points in the piping systems in order to drain the entire
system.
ASME RATED PRESSURE RELIEF VAL
VE
Each boiler must have a properly sized and installed American
Society of Mechanical Engineers rated pressure relief valve.
Water expands as it is heated by the burner/boiler sections. If
there is no place for the water to expand its volume, (i.e. a
properly sized and properly functioning expansion tank) pressure
on the inside of the boiler and heating system will increase. The
furnished relief valve will automatically open at 30 psig pressure
to relieve the strain on the boiler and heating system from the
increasing pressure. The pressure relief valve discharge must be
piped with the same size as the valve discharge opening to an
open drain, tub or sink, or other suitable drainage point not
subject to freezing, in accordance with ASME specifications.
Failure to provide the pressure relief valve with piping as herein
described may cause water damage and/or serious bodily injury.
The boiler manufacturer is not responsible for any water damage
or personal injury.
BLOCKED VENT SAFETY SHUT
OFF
The boiler is equipped with a blocked vent safety shutoff which
shuts off the main burner gas in the event that the airflow of
combustion products through the flue--way is reduced. In the
event of a blocked flue--way, enough air will not be available to
support combustion and the IBC will lock out due to loss of
adequate air flow. Pressure switches monitor air flow by sensing
differential pressure. The contacts are normally open and close
when the draft inducer is running and causing the differential
pressure at the switch to exceed its setting. The closed switch
proves there is adequate air flow for combustion. The pressure
switch shuts off the main burner if the differential pressure is
inadequate due to a blocked vent pipe, a blocked air intake, a
blocked boiler section, or a blocked air inducer. After 5 minutes
of inadequate differential pressure, the IBC will lock out. The
“Purge” indicator lamp will blink, indicating a failure to prove
adequate combustion air flow or flue gas flow. (See Fig. 18.) The
IBC will automatically reset after 15 minutes or can be manually
reset as noted in the section titled “Hot Surface Igniter.” If the
boiler cannot be restored to normal operating condition by
resetting the control, contact a qualified service agency to check
the heat exchanger flue--ways for blockage.
LOW WATER
CUT--OFF
This unit is equipped with a Low Water Cut--Off control that
protects against dry firing. This control provides burner cut--off if
there is an unsafe water loss, which can result from a broken or
leaking radiator or pipe, or a cracked section in the boiler. A
water/glycol mixture up to 50 percent concentration may be used
with the Low Water Cut--Off.
(OPTIONAL) EXTERNAL CONDENSATE
PUMP
For installations where there is no floor drain or other appropriate
drainage receptacle available to receive condensate from the
boiler, an external float activated condensate pump with integral
sump is required. The condensate pump can be piped to a remote
tie in point to a sanitary sewer system. For this application, the
boiler must be installed so that proper pitch of piping to the
external condensate reservoir (sump) can be accomplished. Use
wood frame or blocks to raise boiler as required for proper
installation.
START--UP AND CHECK--OUT PROCEDURES
STEP 1 —Water Treatment and Freeze Protection
1. When filling the boiler and heating system, water
treatment is generally not required or desired. Consult
local water treatment specialist for water treatment
recommendations if your water pH levels are below 7.0 or
hardness is above 7 grains hardness.
a. This boiler is designed for use in a closed hydronic
heating system ONLY!
b. Excessive feeding of fresh make--up water to the boiler
may lead to premature failure of the boiler sections.
2. Use clean fresh tap water for initial fill and periodic
make--up of boiler.
a. A sand filter must be used if fill and make--up water
from a well is to be used.
b. Consideration should be given to cleaning the heating
system, particularly in retrofit situations, where a new
boiler is being installed in an older piping system.
c. In older systems, obviously discolored, murky, or dirty
water, or a pH reading below 7, are indications that the
system should be cleaned.
d.ApHreadingbetween7and8ispreferred.
3. Antifreeze, if needed, must be of a type specifically
designed for use in closed hydronic heating systems and
must be compatible with aluminum and be compatible
with type 356 T6 aluminum at operating temperatures
between 20 and 250 degrees F.
a. Use of antifreeze must be in accordance with local
plumbing codes.
b. Pure glycol solutions are very corrosive, therefore
hydronic system antifreeze typically contains corrosion
inhibitors. Different brands of hydronic system
antifreeze contain different types of corrosion
inhibitors. Some brands have corrosion inhibitors that
break down more rapidly or become ineffective at
higher temperatures when used with aluminum. This
could lead to premature failure of the aluminum boiler.
Consult the antifreeze manufacturer on the
compatibility of their product with aluminum.
15
Table 4—Diagnostic Sequence
SEQUENCE OF OPERATION
Lamp A is illuminated, indicating that the integrated control
is receiving 24 volts and is in standby waiting for the
thermostat to call for heat.
Thermostat calls for hea t, energizing the system circulator.X
Integrated boiler control performs self check of internal cir ---
cuitry, lasting approximately two seconds, and energizes theX
draft inducer.
The draft inducer comes up to speed and establishes
combustion airflow, causing the normality open differential
pressure air proving switch contacts to close.
When combustion air flow is proved, Lamp B is illuminated
indicating that the 15 second pre---purge cycle has begun.
After the pre--- purge has completed, Lamp B is extinguished
and Lamp C is illuminated, indicating power is being deliv---
ered to the hot surface igniter for the 20 second igniter warm --up period. The bright yellow--- orange glow of the hot
surfaceignitercanbeobservedthroughtheobservationport
on the boiler.
After the igniter warm - -- up period the integrated boiler con ---
trol ener gizes the gas valve, which is indicated by the illumi ---
nation of Lamp D. Two seconds later Lamp C will extinguishXXX
when the integrated boiler control stops sending power to the
hot surface igniter.
The integrated boiler control then enters a 6 second trial for
ignition mode. This is indicated by a low level illumination of
Lamp E. During the last 2 seconds of this trial for ignition
mode, main burner flame is proven by flame rectificationXXX
through the hot surface igniter, providing a flame signal that
is relayed to the integrated boiler control, fully illuminating
Lamp E.
The thermostat ends its call for heat, causing the integrated
boiler control to de---energize the gas valve and system circulator.
Lamp D is extinguished while the unit enters the 30 second
post purge mode, indicated by the illumination of Lamp B.
Lamp E will remain illuminated as the remainder of the
gas in the blower is burned off (approximately 2 seconds).
During post purge the blower remains powered and clears
out any residual products of combustion.
After the post purge mode the draft inducer is de--- energized,
lamp B is extinquished, and the unit goes into standby modeX
until the next call for heat from the thermostat.
NOTE: First attempts at cold starts may be rough due to gas line not being completely purged of air causing low firing r ate and h igh excess air level s.
ABCDE
X
XX
XX
XX
DIAGNOSTIC INDICATOR LAMPS
16
c. Follow the antifreeze manufacturer’s instructions on
determining proper ratio of antifreeze to water for the
expected low temperature conditions, and for
maintaining the quality of the antifreeze solution from
year to year. Improperly maintained antifreeze
solutions will gradually lose their ability to protect the
aluminum boiler from corrosion.
d. The recommended premixed antifreeze solution is
INTERCOOL NFP-- 5 0 . This product is sold direct to
installing contractors by the antifreeze manufacturer.
Please contact Interstate Chemical Company, New
York Customer Service at 1--800--422--2436 to
purchase. Use of an alternate manufacturer’s premix
antifreeze is acceptable if the product specifications are
compatible with those of the recommended premix
antifreeze and the antifreeze is compatible with type
356 T6 aluminum. Use of incompatible antifreeze
could damage the heat exchanger and could void
product warranty.
The antifreeze must be maintained per the
specifications of the manufacturer. Failure to do so
could result in the warranty being voided. Follow the
antifreeze manufacturer’s instructions on determining
the proper ratio of antifreeze to water for the expected
low temperature conditions and for maintaining the
antifreeze solution from year to year.
e. DO NOT USE AUTOMOTIVE ANTIFREEZE,as
the type of corrosion inhibitors used will coat the
boiler’s heat transfer surfaces and greatly reduce
capacity and efficiency.
f. Use of antifreeze in any boiler will reduce heating
capacity by as much as 10 --20 percent, due to differing
heat transfer and pumping characteristics. This must be
taken into consideration when sizing the heating
system, pump(s) and expansion tank. Consult
antifreeze manufacturer’s literature for specific
information on reduced capacity.
g. Water content of the boiler is 2.6 gallons (10 liters).
STEP 2 —Filling Boiler with Water and Purging Air for
Systems with Diaphragm Type Expansion Tanks
Refer to appropriate “Near Boiler Piping” diagrams.
1. Close all zone service valves on the supply and return
piping. Open the feed valve and fill boiler with water.
Make sure air vent is open. Hold relief valve open until
water runs air free for five seconds to rapidly bleed air
from boiler, then let the relief valve snap shut.
2. Open the zone service valve on the supply pipe for the
first zone. Open the purge valve on the first zone. Feed
water will fill the zone, pushing air out the purge valve.
Close the purge valve when the water runs air free. Close
the zone service valve.
3. Repeat step 2 for all remaining zones.
4. Open all service valves. Any air remaining trapped in the
return lines between the service valves and the boiler will
be pushed towards the air vent when the boiler is placed in
operation.
5. Inspect piping system. Repair any leaks immediately.
STEP 3 —Filling Boiler with Water and Purging Air for
Systems with Conventional Closed Type Expansion Tanks
Refer to appropriate “NEAR BOILING PIPING” diagrams.
1. Close all zone service valves on the supply and return
piping and close the expansion tank service valve. Drain
expansion tank. Open the feed valve and fill boiler with
water. Hold relief valve open until water runs air free for
five seconds to rapidly bleed air from boiler, then let the
relief valve snap shut.
2. Open the zone service valve on the supply pipe for the
first zone. Open the purge valve on the first zone. Feed
water will fill the zone, pushing air out the purge valve.
Close the purge valve when the water runs air free. Close
the zone service valve.
3. Repeat step 2 for all remaining zones.
4. Open the expansion tank service valve and the tank vent.
Fill the tank to the proper level and close the tank vent.
Remove the handle from the expansion tank service valve
so the homeowner doesn’t accidentally close it.
5. Open all service valves. Any air remaining trapped in the
return lines between the service valves and the boiler will
be pushed towards the expansion tank when the boiler is
placed in operation.
6. Inspect piping system. Repair any leaks immediately.
NOTE: DO NOT use stop leak compounds. Leaks in threaded
connections in the aluminum boiler sections must be repa ired
immediately. Aluminum threads will not seal themselves.
DIAGNOSTIC INDICATOR LAMPS
POWER
A
PURGE
B
IGNITER
C
VALVE
D
FLAME
E
UT-1013 INTEGRATED BOILER CONTROL
40 VA TRANSFORMER CONTROL
CONTROL PANEL
A04062
Fig. 18 --- Indicator Lights
17
STEP 4 —Placing Boiler in Operation
READ BEFORE OPERATING APPLIANCE
1. This appliance does not have a pilot. It is equipped with an
ignition device which automatically lights the burner. Do
NOT try to light this burner by hand.
2. Before operating, smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch or use any phone in the building.
Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
If you cannot contact your gas supplier, call the fire department.
3. Use only your hand to turn the gas ball valve. Never use
tools. If the valve will not turn by hand, do not try to
repair it, call a qualified service technician. Force or
attempted repair may cause fire or explosion.
4. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
OPERATING
INSTRUCTIONS
1. STOP! Read the safety information above before
operating this appliance.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the appliance.
4. This appliance does not have a pilot. It is equipped with an
ignition device which automatically lights the burner. Do
NOT try to light this burner by hand.
5. Remove the front jacket panel.
6. Turn off the gas ball valve. Valve handle should be
perpendicular to the gas pipe.
7. Wait five minutes for any gas to clear. Then smell for gas,
including near the floor. If you smell gas STOP! Follow
instructions under “WHAT TO DO IF YOU SMELL
GAS” above. If you do not smell gas, go to next step.
8. Turn the gas ball valve to the “on” position. The handle on
the valve should be parallel to the gas pipe.
9. Replace the front jacket panel.
10. Turn on all electrical power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions
“TO TURN OFF GAS TO APPLIANCE” and call your
service technician or gas supplier.
IF BURNER APPEARS TO PULSATE DURING
IGNITION
1. Turn off boiler power and shut off gas supply to the boiler.
2. Take the burner assembly apart by removing the
combustion air blower and gas valve/venturi assembly
from the boiler and visually inspect the inside of the
burner. Look for any debris (PVC shavings, etc.) and if
anything is present, remove it.
3. Reassemble burner assembly, turn gas supply and boiler
power back on, and relight boiler.
IF BURNER STILL PULSATES OR FAILS TO
LIGHT
1. Check for proper vent and intake pipe sizing and for
proper vent lengths and vent configuration by referring to
Step 2, “Before Installing the Boiler,” and Step 5,
“Combustion Air and Vent Pipe,” located in the
INSTALLATION section in this manual.
2. Check for proper gas supply pressure and proper gas line
sizing to the boiler by referring to Step 6, “Gas Supply
Piping,” located in the INSTALLATION section in this
manual.
3. Check for orifice in negative pressure hose at gas valve
and 2” air intake pipe upstream of gas valve.
4. Relight boiler.
5. If boiler still does not light, the air inlet pipe may need to
be disconnected to allow the boiler to start in order to
verify the boiler firing rate and combustion properties.
The inlet air pipe can be disconnected by removing the
PVC inlet air piping from the Femco fitting located on the
air inlet of the gas valve/venturi assembly. Relight boiler.
6. When the boiler lights, the firing rate and combustion
should be checked per the “Adjustments and Checkout”
procedure in Step 5 of the START--UP AND
CHECK--OUT PROCEDURES section of this manual. If
the air inlet piping was disconnected in step 4 (above),
leave it disconnected and make the first adjustment.
Reconnect air inlet piping, recheck combustion CO
,and
2
adjust again if necessary.
7. If burner pulsation continues or boiler fails to light after
performing the above procedures, please contact Technical
Service at 1--800--325--5479 for further assistance.
TO TURN OFF GAS TO
APPLIANCE
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Remove the front jacket panel.
4. Turn gas ball valve off. The handle should be
perpendicular to the gas pipe.
5. Replace the front jacket panel.
Safe lighting and other performance criteria were met with the gas
manifold and control assembly provided on the boiler when the
boiler underwent tests specified in ANSI Z21.13-- latest revision.
STEP 5 —Check Out Procedure and Adjustments
VERIFY PROPER SEQUENCE OF OPERA
TION
The sequence can be followed via the diagnostic indicator lamps
on the integrated boiler control in Fig. 18. This is the normal
sequence of operation. (See Table 4.) A more detailed sequence
of operation containing potential faults can be found in the
service hints section.
INSPECT VENTING AND AIR INTAKE
SYSTEM
Operate the boiler and verify that all vent/air intake connections
are gastight and watertight. Repair any leaks immediately.
INSPECT CONDENSATE
DRAIN
Verify that all connections are watertight, and that condensate
flows freely. Repair any leaks immediately.
INSPECT SYSTEM
PIPING
Verify that all connections are watertight. Repair any leaks
immediately.
TEST IGNITION SYSTEM SAFETY SHUTOFF
DEVICE
1. Turn off manual gas ball valve.
2. Set thermostat to call for heat.
3. Boiler begins normal sequence of operation.
4. After approximately 30 seconds (prepurge and igniter
warm--up period), lamp D illuminates, indicating gas valve
is powered.
5. After 4 seconds, gas valve closes, lamp D goes out as
integrated boiler control senses that flame is not present.
6. To restart system, follow operating instructions under
“Step 4-- Placing Boiler in Operation.”
NOTE: The boiler automatically derates input as altitude increases. No alterations to boiler are required for altitudes above sea level.
These low pressure gas --- fired h ot water boilers are design certified by CSA International, for use with natural and propane gases. T h e boilers are constructed
and hydrostatically tested for a maximum working pressure of 50 psig (pounds per square inch gauge) in accordance with A .S.M.E. (American Society of
Mechanical Engineers) Boiler and Pressure Vessel Code Section IV Standards f or heating boilers.
Vent LengthsVent LengthsVent LengthsVent Lengths
MinMaxMinMaxMinMaxMinMax
TEST HIGH LIMIT CONTROL AND ADJUST
While burner is operating, Adjust setting on high limit control
below actual boiler water temperature. Burner should go off while
circulator continues to operate. Raise limit setting above boiler
water temperature and burner should reignite after pre purge and
igniter warm--up period. Set the high limit control to the design
temperature requirements of the system. Maximum high limit
setting is 200_F. Minimum high limit setting is 100_F. Return
high limit differential to original setting of 20_F.
TEST OTHER SAFETY
CONTROLS
If the boiler is equipped with a low water cut off, a manual reset
high limit, or additional safety controls, test for operation as
outlined by the control manufacturer. Burner should be operating
and should go off when controls are tested. When safety controls
are restored, burner should reignite.
SETTHERMOSTATHEATANTICIPATOR(IF
AND VERIFY THERMOSTAT OPERA
TION
USED)
For a single thermostat connected to the yellow thermostat lead
wires in the furnished field wiring junction box, the heat
anticipator should be set at 0.7 amps. For other wiring
configurations, refer to the instructions provided by the
thermostat manufacturer regarding adjustment of heat anticipator.
Cycle boiler with thermostat. Raise the thermostat to the highest
setting and verify boiler goes through normal start up cycle.
Lower thermostat to lowest setting and verify boiler goes off.
MEASURE THE NATURAL GAS INPUT RA
TE
Correct input rate is essential for proper and efficient operation of
the burner and boiler.
1. Determine elevation at installation site.
2. See Table 5 and 6 to determine the correct approximate
input rate for the local elevation.
3. Obtain the yearly average heating value of the local gas
supply from the gas utility. At sea level elevation, it should
be approximately 1000 Btu’s per standard cubic foot.
4. Operate boiler for 5 minutes.
5. Turn off all other gas appliances, extinguishing standing
pilots where applicable.
6. At gas meter, measure time in seconds required to use one
cubic foot of gas.
7. Calculate “input rate” according to the following formula:
Btuh input rate = 3600 x heating value from step 3
time from step 6
8. The measured input rate should be within +/--2 percent of
the input rating from step 2. If not, see the
ADJUSTMENTS section.
19
ADJUSTMENTS AND
CHECKOUT
NOTE: It is important that this appliance operate between 8.5
and 10% CO
. To verify that the appliance is operating in this
2
range, follow the steps below:
1. Check incoming gas pressure to the appliance using a
water column manometer with resolution of 0.1 inch w.c.
or better and a range of 0 to 14 inches of w.c. Connect the
positive side of the manometer to the inlet pressure tap on
the gas valve by loosening the inlet pressure tap screw
from the raised port on the gas valve and sliding the
manometer hose over the port. (See Fig. 19.)
2. Drill a hole in the plastic CPVC vent pipe or exhaust tee,
just large enough to allow access for the sample probe of
your combustion analyzer.
3. Turn the thermostat to the closed position so the appliance
is activated.
4. Allow the appliance to run for approximately 5 minutes.
5. Insert the sample probe of your combustion analyzer into
the hole you drilled in step 2, about halfway into the
exhaust gas stream. Take a flue gas reading and observe
the CO
value. Adjust the throttle screw until the CO
2
value is between 8.5 and 10%. Turning the throttle screw
clockwise decreases the rate and the CO
value. Turning
2
the throttle screw (See Fig. 19) counterclockwise increases
therateandtheCO
value.Allow the appliance to
2
stabilize for approximately 1 minute after adjusting the
throttle screw before you take a reading with your
combustion analyzer.
6. After adjustments are made, turn the gas and electric
supplies to the boiler off. Remove the manometer hose
from the gas valve and tighten the screw on the inlet
pressure tap. Remove the CO meter and plug the hole in
the CPVC with 400_F high temperature silicone.
7. Return the thermostat switch to its original position.
THROTTLE ADJUSTMENT SCREW
Turn clockwise to decrease rate and CO
Counterclockwise to increase rate and CO
INLET
PRESSURE
TAP
INLET
MOLEX
PIN
HEADER
2
VENTURI VALVE
2
OUTLET
A06100
Fig. 19 --- Gas Valve
Final Checkout of the Installation
After any adjustment to the appliance, observe several complete
cycles to ensure that all components function correctly.
SETTHERMOSTATTODESIRED
TEMPERA
TURE
ROOM
Observe several operating cycles to verify proper operation.
REVIEW ALL
INSTRUCTIONS
Review all instructions shipped with this boiler with owner or
maintenance person. Instructions must be affixed on or adjacent
to the boiler.
COMPLETE AND SIGN THE INSTALLATION AND
CHECK--OUT CERTIFICATE AT THE END OF THIS
MANUAL.
CARE AND MAINTENANCE
Maintenance as outlined below can be performed by the
owner unless otherwise noted.
The acidic nature of flue gases condensing on the aluminum
boiler sections will cause the formation of aluminum oxide. This
oxide formation is normal, is generally uniform throughout the
boiler sections, and represents a negligible mass of aluminum that
is consumed by oxidation during the life of the boiler. If left
unchecked, this buildup may eventually cause blockage of the
flue gas passages in the boiler sections, reducing efficiency, and
ultimately shutting down the boiler due to lack of combustion air
flow. Regular service and maintenance by a qualified service
agency must be performed to assure safe trouble free operation
and maximum efficiency. It is recommended to service the
appliance at least once every 12 months.
STEP 1 —Beginning of Each Heating Season
1. Schedule an annual service call by a qualified service
agency, which includes:
a. Examine flue passages between boiler sections, burner,
and condensate lines, and clean, if necessary, following
2
the annual examination and cleaning instructions listed
in Procedure 6.
b. Visually inspect venting and air intake system for
proper operation. If the vent or air intake show any
signs of deterioration or leakage, repair or replace them
immediately. Insure proper reassembly and resealing of
the vent and air intake system.
c. Check for and remove any obstruction to the flow of
combustion air or venting of flue gases.
d. Follow instructions for “PLACING BOILER IN
OPERATION.”
e. Follow instructions for “CHECK OUT PROCEDURE
AND ADJUSTMENTS.”
f. Visually inspect condensate drain line for proper
operation. Check for deteriorated or plugged
condensate drain line.
g. Check all gasketed joints for leakage, and tighten bolts
or replace gaskets, if necessary.
h. Remove jacket front and top panels and check for
piping leaks around relief valve and other fittings.
Repair, if found. DO NOT use stop leak compounds.
2. Check that boiler area is free from combustible materials,
gasoline, and other flammable vapors and liquids.
3. Circulator pump and blower motor furnished with boiler
are permanently lubricated from the factory and require no
further lubrication. Additional or non-- factory supplied
pumps and/or motors should be lubricated according to
the pump and/or motor manufacturer’s instruction.
STEP 2 —Daily During Heating Season
1. Check for and remove any obstruction to the flow of
combustion air or venting of flue gases.
2. Check that boiler area is free from combustible materials,
gasoline, and other flammable vapors and liquids.
STEP 3 —Monthly During Heating Season
1. Remove jacket front and top panels and check for piping
leaks around relief valve and other fittings. If found,
contact a qualified service agency to repair. DO NOT use
stop leak compounds.
2. Test relief valve. Refer to valve manufacturer’s
instructions packaged with relief valve.
3. Visually inspect venting and air intake system for proper
function. If the vent or air intake show any signs of
deterioration or leakage, contact a qualified service agency
to repair or replace them immediately and to insure proper
reassembly and resealing of the vent and air intake system.
20
4. Visually inspect the PVC condensate drain pipe for proper
operation. If the drain pipe shows any signs of blockage,
leakage, or deterioration contact a qualified service agency
to clean, repair, or replace it immediately.
5. Check air vent(s) for leakage.
STEP 4 —Periodically During Heating Season
Where low water cut offs are used, a periodic inspection of the
low water cut off is necessary, including flushing of float type
devices. Refer to low water cut off manufacturer’s specific
instructions.
STEP 5 —End of Heating Season--Annual Shutdown
Procedure
1. Follow instructions “TO TURN OFF GAS TO
APPLIANCE.”
2. If heating system is to remain out of service during
freezing weather, and does not contain antifreeze, drain
system completely. If boiler will be exposed to freezing
temperatures, drain condensate lines. Otherwise, do not
drain system or boiler.
STEP 6 —Annual Examination and Cleaning of Boiler
Components
The following service procedures must be performed only by a
qualified service agency. Boiler owner should not attempt these
procedures.
1. Before Servicing, turn off electrical power to boiler at
service switch. Close manual gas valve to turn off gas
supply to boiler.
2. Flue passages are examined by removing the blower
assembly from the casting. Refer to the repair parts
diagram for the boiler block and piping assembly at the
end of this manual. The procedure for examining and
cleaning the burner is described below.
Any buildup of sediment or aluminum oxide (white
powdery or flaky substance) in the flue passages must be
cleaned as follows:
a. Remove jacket front and top panels.
b. Confirm that manual gas valve is closed and
disconnect gas line to gas valve at union.
c. Disconnect wires to gas valve and igniter.
d. Remove air inlet assembly from gas valve.
e. Loosen but do not remove five (5) nuts attaching
blower adapter assembly to boiler.
f. Remove two (2) igniter screws and very carefully
remove the igniter. Use care when removing theigniter, it is very brittle! Do not touch the igniter
element with your fingers or hands as oil or debris will
cause premature failure to the igniter.
g. Remove five (5) nuts and remove blower adapter
assembly. Remove burner and gaskets.
h. Aluminum oxide deposits are water soluble and may
be rinsed away with spraying or running water.
i. Use a flexible handle nylon brush to loosen sediment
and aluminum oxide on all heating surfaces of boiler.
Refer to the repair parts diagrams. Be sure that you
do not get brush stuck in heat exhanger!
j. After brushing and rinsing, remove any remaining
loosened sediment using a shop vacuum with a snorkel
attachment.
k. Inspect burner for any foreign matter in the flame ports
or inside the burner. Any foreign matter should be
removed by blowing with compressed air or
vacuuming.
l. Reinstall burner and gaskets and position blower
adapter assembly over studs. Install five (5) nuts but
do not tighten. Reinstall igniter and igniter gasket and
fasten with two (2) screws. Use care when installingthe igniter. It is very brittle! Do not touch the igniter
element with your fingers or hands as oil or debris will
cause premature failure to the igniter. Tighten five (5)
nuts holding blower adapter assembly.
m. Connect:
(1.) gas line to gas valve
(2.) air inlet assembly to gas valve using 2” x 1--1/2”
flexible coupling
(3.) pressure switch hose to gas valve and air inlet
assembly
(4.) 2 inch flexible coupling to boiler exhaust port
(5.) igniter wires
(6.) gas valve wires
3. Visually inspect the condensate trap. Refer to repair parts
diagrams. Any foreign material or debris that is visible in
the condensate lines needs to be cleaned out as described
below.
a. Remove 1/2” PVC cap from 1/2” PVC tee.
b. Inspect for sediment or blockage.
c. Flush out with water or vacuum.
d. Follow the instructions under “NEAR BOILER
PIPING” for filling condensate trap with water.
e. Replace 1/2” PVC cap.
4. Inspection of the flue connector requires the following
steps (Refer to the repair parts diagram.)
a. Loosen the clamp on the draft inducer end of the 2
inch flexible coupling that connects the vent tee to the
exhaust port.
b. Inspect interior of vent tee. Any buildup of sediment
on the inside surface must be cleaned.
c. Reconnect the 2 inch flexible coupling to the draft
inducer outlet.
STEP 7 —Differential Air Pressure Switch Check
The following steps and diagram indicate the locations of the
connection points required to check the differential air pressure.
The differential air pressure switch is a safety device which will
prevent the boiler from firing if there is an air intake, boiler heat
exchanger or vent blockage.
Turn off service switch, or lower thermostat setting.
Remove vinyl caps from tee. Install testing lines as shown to
inclined manometer or differential pressure gauge with the ability
to read 0.01” to 5.0” w.c.
Turn on service switch and set thermostat to call for heat. (See
Fig. 20.)
If manometer readings do not correspond to the chart above,
check for possible causes:
SBlockage or moisture in suction lines to switch.
SBlockage in air intake or vent pipes.
SUndersized air intake or vent pipes.
SLoose blower wheel on motor shaft.
SIncorrect pressure switch or pressure switch setpoint
When pressure reading is proper and the pressure switch is
operating properly, remove testing lines and reinstall vinyl caps to
Tee and 3--way connector.
SERVICE HINTS AND TROUBLESHOOTING
See Fig. 21--32.
21
BOILER STATUSDIFFERENTIAL PRESSURESWITCH CONTACTS
Not Running0”
Running without Blockage (Approximate)
Running with BlockageLess Than or Equal to Setpoints
Closed at 3.5”
Closed at 0.5”
1.00” For Model --125Closed at 3.5”
1.50” For Model --150Closed at 0.5”
1.50” For Model --175
2.00” For Model --200
Open at 3.5”
Closed at 0.5”
SIGHT GLASS
& ADAPTER
3
2
2"
1
3"
1
AIR INLET
CONNECTION
7
6"
4
13 1/4"
5 1/2"
4
1
Fig. 20 --- Differential Air Pressure
5
4"
4
4"
1
2 @ 2" EA.
4
6
8
GAS VALVE
9
9
4
16 1/2"
A06107
22
PO WER ON
STANDBY
NORMAL SEQUENCE OF OPERATION
THERMOSTAT
CALLS FOR HEAT
CIRCULATOR
ENERGIZES THRU
2K1 CONTACTS
IBC SELF CHECK OF
INTERNAL CIRCUITRY
1-2 SEC
IBC
CHECKS
N.O. AIR
PRESSURE
SWITCH
CONTACTS
OPEN
DRAFT INDUCER
ENERGIZES THRU
1K1 CONTACTS
CLOSED
FALSE POSITIVE
PROOF OF
AIRFLOW. IBC WAITS
FOR 45 SEC FOR
AIR PRESSURE
SWITCH
CONTACTS TO
OPEN
OPEN
IF MAIN BURNER DOES NOT PROVE FLAME IN 3
TRIALS, CONTROL LOCKOUT. VALVE/FLAME
LIGHT BLINKS. RESET IS REQUIRED. THIS
PROBLEM IS A RESULT OF NOT ESTABLISHING
FLAME SIGNAL.
CONTROL WILL ATTEMPT 2 ADDITIONAL
IGNITION SEQUENCES STARTING WITH
PREPURGE
NO
DOES MAIN
CLOSED
BURNER
PROVE FLAME
WITHIN INITIAL
FOR IGNITION
PERIOD
YES
NORMAL
OPERATION
IBC
WAITS FOR
UP TO 5 MINUTES
CLOSED
CONTROL LOCKOUT. PURGE LIGHT BLINKS.
MANUAL RESET REQUIRED OR CONTROL
WILL AUTOMATICALLY RESET AFTER 15
MINUTES. CIRCULATOR REMAINS ENERGIZED
AS LONG AS THERE IS A CALL FOR HEAT
PURGE LIGHT ON. AIRFLOW APPROVED.
DRAFT INDUCER RUNS FOR 15 SEC PREPURGE
FOR AIR PRESSURE
SWITCH CONTACTS
TO CLOSE
INDICATING FAN
SUCTION PRESENT
OPEN
DURING THE LAST 2 SEC OF THE 5 SEC IGNITION
TRIAL, MAIN BURNER FLAME IS PROVED BY FLAME
RECTIFICATION THRU HOT SURFACE IGNITER,
PROVIDING A FLAME SIGNAL TO IBC. GAS VALVE
REMAINS ENERGIZED. BOILER RUNS.
2 SEC INTO THE 5 SEC IGNITION TRIAL, POWER
IS TURNED OFF TO THE HOT SURFACE IGNITER.
IGNITER LIGHT OFF.
GAS VALVE OPENS FOR 5 SEC TRIAL FOR
IGNITION, BLUE ORANGE GLOW OF THE BURNER
CAN BE SEEN THRU OBSERVATION PORT.
GAS VALVE ENERGIZED THRU 3K1 AND 4K1.
CONTACTS. VALVE LIGHT ON.
PURGE LIGHT GOES OUT. HOT SURFACE IGNITER
POWERED THRU 5K1 AND 5K2 CONTACTS FOR 20
SEC IGNITER WARMUP. BRIGHT YELLOW
ORANGE GLOW OF THE HOT SURFACE IGNITER
CAN BE OBSERVED THRU THE OBSERVATION
PORT IN FRONT OF BOILER SECTION JUST
ABOVE IGNITER. IGNITER LIGHT ON.
DETAILED SEQUENCE OF OPERATION
Fig. 21 --- Normal Sequence of Operation
A06101
23
LOSS OF FLAME SIGNAL
IF AN ESTABLISHED FLAME SIGNAL IS LOST
WHILE CONTROL EXPECTS THAT THE BURNER
IS OPERATING, CONTROL WILL IMMEDIATELY
DE-ENERGIZE GAS VALVE. (VALVE LIGHT GOES OUT)
CASTING TEMPERATURE SAFETY SWITCH
IF BURNER OPERATES WHEN BOILER HAS NO
WATER, ALUMINUM BOILER SECTIONS
HEAT UP RAPIDLY.
DRAFT INDUCER RUNS THRU 30 SECOND POST
CONTROL WILL ATTEMPT TO RE-LIGHT BOILER
3 TIMES. IF FLAME IS NOT PROVEN. CONTROL
LOCKOUT - PROBLEM ESTABLISHING A FLAME
SIGNAL. VALVE LIGHT IS BLINKING.
PURGE
LOSS OF COMBUSTION AIRFLOW
IF COMBUSTION AIRFLOW IS LOST WHILE BURNER
IS FIRING ( DIFFERENTIAL AIR PRESSURE
SWITCH CONTACTS OPEN) GAS VALVE WILL
BE DE-ENERGIZED. (VALVE LIGHT GOES OUT)
DRAFT INDUCER RUNS THRU 30 SECOND POST
IF CALL FOR HEAT REMAINS, IBC WAITS
5 MINUTES FOR AIRFLOW TO BE RE-ESTABLISHED
IF AIRFLOW DOES NOT RE-ESTABLISH, CONTROL WILL
LOCKOUT - PROBLEM WITH COMBUSTION AIRFLOW.
PURGE LIGHT BLINKS. CONTROL WILL AUTOMATICALLY
RESET AFTER 15 MINUTES
PURGE
CASTING TEMPERATURE SAFETY SWITCH
CONTACTS WILL OPEN BREAKING 24 VOLT POWER
TO IBC. POWER INDICATOR LIGHT GOES OUT.
REQUIRES MANUAL RESET TO RE-CLOSE
CONTACTS
POWER LIGHT GOES OUT.
HI LIMIT CONTROL
IF BOILER WATER TEMPERATURE REACHES
HI LIMIT (AQUASTAT) SETPOINT, HI LIMIT
N.C. CONTACTS OPEN IMMEDIATELY,
CLOSING GAS VALVE. (VALVE LIGHT GOES OUT)
DRAFT INDUCER CONTINUES TO RUN FOR 30
SECOND POST PURGE AND SWITCH OFF.
CIRCULATOR RUNS AS LONG AS THERMOSTAT
WHEN HI LIMIT CONTACTS REMAKE BEFORE END
OF CALL FOR HEAT - CONTROL GOES INTO
CALLS FOR HEAT.
A NORMAL LIGHT OFF SEQUENCE
CIRCULATOR PUMP
CIRCULATOR WILL BE ENERGIZED AS LONG AS
THERMOSTAT CALLS FOR HEAT DURING LOCKOUT
RECOVERY FROM ANY LOCKOUT REQUIRES RESET
WHICH IS ACCOMPLISHED BY REMOVING AND
REAPPLYING THE THERMOSTAT CALL FOR HEAT
Fig. 22 --- Safety Sequences During Operation
OR POWER TO CONTROL
A06102
24
GAS VALVE AND CIRCULATOR PUMP
ARE DE-ENERGIZED. VALVE LIGHT GOES OUT.
BLOWER RUNS FOR 30 SECOND POST
PURGE. PURGE LIGHT ON.
AFTER 30 SECONDS. PURGE LIGHT SHUTS OFF.
BLOWER IS DE-ENERGIZED
A04066
Fig. 23 --- End of Normal Sequence of Operation
25
!
FIRE, EXPLOSION OR SHOCK HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
Do not attempt to modify the physical or electrical
characteristics of this boiler in any way.
WARNING
IMPORTANT
1. IN A RESET FROM LOCKOUT CONDITION, ALL ELECTRICAL METER READINGS AT THE GAS
CONTROL VALVE (24 VAC) MUST BE TAKEN WITHIN THE TRIAL FOR IGNITION PERIOD.
2. IF ANY COMPONENT DOES NOT FUNCTION PROPERLY, MAKE SURE IT IS CORRECTLY INSTALLED
AND WIRED BEFORE REPLACING IT.
3. STATIC ELECTRICITY DISCHARGE CAN DAMAGE THE INTEGRATED BOILER CONTROL (IBC).
TOUCH METAL SURFACE TO DISCHARGE STATIC ELECTRICITY BEFORE TOUCHING IBC.
4. THE IBC CANNOT BE REPAIRED. IF IT MALFUNCTIONS IT MUST BE REPLACED.
5. ONLY TRAINED, EXPERIENCED SERVICE TECHNICIANS SHOULD SERVICE THE IBC SYSTEMS.
FOLLOWING TROUBLESHOOTING, CHECK OUT THE SYSTEM FOLLOWING THE SEQUENCE OF
OPERATION SECTION OF THIS CHAPTER FOR A NORMAL LIGHT OFF SEQUENCE.
6. ALL CONTROLS ARE FACTORY TESTED IN THE ASSEMBLY PROCESS AND A DEFECTIVE CONTROL
IS GENERALLY THE LEAST LIKELY CAUSE. IF YOU SUSPECT YOU HAVE A DEFECTIVE CONTROL,
READ THROUGH THE TROUBLESHOOTING CHART BEFORE YOU REPLACE IT.
7. IT IS EXTREMELY UNLIKELY THAT THE TWO CONSECUTIVE CONTROLS ARE DEFECTIVE. IF IT
SEEMS TO BE HAPPENING, CHANCES ARE THAT EITHER THERE IS NOTHING WRONG WITH THE
CONTROL OR IT IS BEING DAMAGED BY SOME OTHER PROBLEM (AN ELECTRICAL SHORT
BURNING OUT A TRANSFORMER, FOR EXAMPLE).
INITIAL SERVICE CHECKS
1. BEFORE TROUBLESHOOTING:
A. MAKE SURE THAT CIRCUIT BREAKER IS ON OR FUSE IS OK AT ELECTRICAL PANEL.
B. MAKE SURE THAT SERVICE SWITCH IS ON.
C. MAKE SURE THAT GAS IS ON AT THE GAS METER, AT ALL APPROPRIATE MANUAL
SHUTOFF VALVES AND AT THE GAS CONTROL VALVE.
D. MAKE SURE THAT THE THERMOSTAT IS CALLING FOR HEAT.
E. CHECK THAT WIRE CONNECTORS AT THE INTEGRATED BOILER CONTROL AND AT THE
ORIGINATING CONTROL ARE SECURELY PLUGGED IN OR CONNECTED.
F.CHECK THAT HOSES ARE SECURELY CONNECTED AND ARE NOT PLUGGED IN OR
DAMAGED.
2. TROUBLESHOOTING TOOLS:
A. VOLTMETER TO CHECK 120 VAC AND 24 VAC
B. CONTINUITY TESTER.
C. INCLINED MANOMETER OR PRESSURE GAUGE WITH 0-5.0 RANGE (0.01 SCALE) FOR
MEASURING SUCTION PRESSURES AT PRESSURE SWITCH.
D. U-TUBE MANOMETER OR DIFFERENTIAL PRESSURE GAUGE WITH 0-14 RANGE (0.1
SCALE) FOR MEASURING INLET AND MANIFOLD GAS PRESSURES.
3. WHAT IS SYSTEM STATUS?
A. CONSULT THE CHART ON THE FOLLOWING PAGE.
B. FIGURE 18
INDICATOR LAMPS.
SHOWS
DETAILED SEQUENCE OF OPERATION
THE LOCATION ON THE BOILER OF THE DIAGNOSTIC
A06156
Fig. 24 --- Initial Service Checks
26
SYSTEM STATUS
OPERATING SEQUENCE. IF THE SYSTEM LOCKS OUT, THE LIGHTS
THE INDICATOR LIGHTS TRACK THE
INDICATE THE POINT IN THE SEQUENCE OF OPERATION WHERE LOCKOUT
OCCURS. IF THIS TABLE DOES NOT READILY PROVIDE THE REASON FOR
BOILER MALFUNCTION OR NON-OPERATION, REFER TO THE FOLLOWING
PAGES FOR MORE DETAILED TROUBLESHOOTING PROCEDURES.
LIGHTSTATUSINDICATES
POWER
PURGE
IGNITER
VALV E
ON
OFF
BLINKING
ON
OFF
BLINKING
ON
OFF
ON
OFF
IBC IS ENERGIZED THROUGH 24 VOLT TRANSFORMER.
IBC IS NOT ENERGIZED.
IBC RECEIVES MORE THAN 40 VAC
IBC IS ENERGIZING THE DRAFT INDUCER AND AIR
FLOW IS PROVEN.
OFF DURING PURGE CYCLE DRAFT INDUCER IS NOT
POWERED OR AIR FLOW IS NOT PROVEN.
OFF DURING IGNITER AND RUN CYCLE NORMAL
OPERATION, PURGE CYCLE COMPLETE
IBC IS LOCKED OUT. PROBLEM COULD INDICATE
FALSE POSITIVE PROOF OF AIR FLOW, BLOCKED
VENT OR INTAKE AIR PIPE OR FLUE WAY.
IBC IS ENERGIZING IGNITER
IGNITER IS NOT ENERGIZED
IBC IS ENERGIZING GAS CONTROL VALVE
TO OPEN.
GAS CONTROL VALVE IS CLOSED.
FLAME
BLINKING
ON BRIGHT
OFF
ON DIM
IBC IS LOCKED OUT. FLAME HAS NOT BEEN PROVEN IN 3 IGNITION
ATTEMPTS. MAY BE DUE TO BROKEN IGNITER LACK OF OR LOW
FLAME SIGNAL OR NO GAS.
FLAME PROVEN
FLAME UNPROVEN
CHECKING FOR FLAME SIGNAL (DURING TRIAL FOR IGNITION)
TROUBLESHOOTING
Fig. 25 --- System Status Symbols
A06103
27
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
The following procedures may expose you to
dangerous line voltage. Use caution to avoid touching
live electrical contacts. Service must be performed by a
trained, experienced service technician.
What to do if you smell gas:
--Do not try to light any appliance
--Do not touch any electrical switch; do not use any
phone in your building
--Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions
--If you cannot reach your gas supplier, call the fire
department
Should overheating occur or the gas supply fail to shut
off, do not turn off or disconnect the electrical supply to
the pump. Instead, shut off the gas at a location external
to the appliance.
Do not use the boiler if any part of the gas control
system has been under water.A qualified service
technician should inspect the boiler and replace any part
of the control system and any gas control which has
been under water.
Use only your hand to turn the gas control knob. Never
use tools. If the knob will not turn by hand, do not try
to repair it. Force or attempted repair may result in a
fire or explosion.
WARNING
Fig. 26 --- Electrical Shock Hazard Warning
28
A04070
Fig. 27 --- Troubleshooting Chart No. 1
29
NO
CHART 1
TROUBLESHOOTING CHART 2
CHECK THAT CIRCUIT BREAKERS IS ON OR
FUSES ARE OK AT THE ELECTRICAL PANEL
OK
CHECK THAT SERVICE SWITCH IS ON
ON
CHECK CASTING TEMPERATURE SAFETY
SWITCH. PUSH RESET BUTTON ON SWITCH.
CONTACTS OPEN (BUTTON UP) OR CLOSED
CHECK WIRING TO IBC. I20 VAC BETWEEN
TERMINALS 1 AND 3 AT WIRING HARNESS
120 VAC BETWEEN TERMINALS 1 AND 3 AT
120 VAC AT TRANSFORMER PRIMARY
24 VAC AT TRANSFORMER SECONDARY
24 VAC AT WIRING HARNESS PLUG CN2?
(BUTTON DOWN)?
CLOSED
PLUG CN7?
YES
CONNECTOR CN3 OR IBC?
YES
TERMINALS?
YES
TERMINALS?
YES
YES
REPLACE IBC
OPEN
NO
NO
NO
NO
NO
CHECK WATER LEVEL IN BOILER. CHECK
FOR AIR TRAPPED IN TOP OF BOILER.
CONTACTS WILL NOT STAY CLOSED UNTIL
REPLACE/REPAIR WIRING FROM SERVICE
PUSH RESET BUTTON ON CASTING TEMP
SAFETY SWITCH. CHECK CONTINUITY OF
CASTING TEMP. SAFETY SWITCH CONTACTS.
BOILER COOLS OFF.
SWITCH TO IBC
REPLACE IBC
REPAIR WIRING TO TRANSFORMER
REPLACE TRANSFORMER
CONACTS OPEN OR CLOSED?
CLOSED
REPLACE CAST. TEMP.
SAFETY SWITCH.
OPEN
NO
CHART 1
CHECK FOR 120 VAC BETWEEN TERMINALS 1
AND 3 AT CONNECTOR CN5 ON IBC?
YES
CHECK FOR 120 VAC AT CIRCULATOR
YES
REPAIR/REPLACE CIRCULATOR
TROUBLESHOOTING
Fig. 28 --- Troubleshooting Chart No. 2
NO
NO
REPLACE/REPAIR WIRING FROM
TRANSFORMER TO IBC
REPLACE IBC
REPLACE/REPAIR WIRING FROM IBC TO
CIRCULATOR
A99352
30
CHART 1
OPEN
TROUBLE SHOOTING CHART 3
BLOWER STARTS
YES
PURGE LIGHT ON?
YES
CHECK FOR 120 VAC
BETWEEN TERMINALS 1
NO
AND 3 AT CONNECTOR
CN4 ON IBC
CHECK FOR 120 VAC AT
BLOWER LEADS
ON WIRING HARNESS
REPAIR/REPLACE
BLOWER
IBC WAITS UP TO 5
MINUTES FOR NORMALLY
OPEN AIR PRESSURE
NO
SWITCH CONTACTS TO
CLOSE, INDICATING
BLOWER SUCTION
IS PRESENT
YES
YES
NO
NO
REPLACE IBC
REPAIR/REPLACE
WIRING FROM IBC
TO DRAFT INDUCER
CONTACTS OPEN
ARE ORIFICES IN
NEGATIVE PRESSURE
HOSE CLEAR?
ARE VENT PIPE AND
AIR INTAKE PIPE CLEAR
(NO BLOCKAGE)
CHECK AIR PRESSURE
SWITCH PER
INSTRUCTIONS ON
FOLLOWING PAGES. ARE
SAMPLING LINES CLEAR
AND CONNECTED
PROPERLY?
YES
YES
YES
CLEAN OUT BLOCKAGE
AT ORIFICES
CLEAN OUT VENT PIPE
AND/OR AIR INTAKE PIPE.
NO
CHECK FOR SAGS OR
LOW SPOTS WHERE
CONDENSATE MAY PUDDLE
AND BLOCK THE VENT
CLEAN OUT SAMPLING
NO
LINES OR REPLACE
DEFECTIVE SWITCH
15 SECOND PRE PURGE COMPLETE.
PURGE LIGHT OFF. SIMULTANEOUSLY
IGNITER LIGHT IS ON AS IGNITOR
CIRCUIT IS ENERGIZED
YES
CHART 4
CHECK FLUE PASSAGES
IN BOILER PER
MAINTENANCE AND
CLEANING. ARE FLUE
PASSAGES IN BOILER
CLEAN?
YES
CHECK DRAFT INDUCER
MOTOR RPM. IS IT
3400-3600?
YES
CHECK FOR BROKEN OR
LOOSE IMPELLER ON
DRAFT INDUCER AND
REPLACE BLOWER
IF FOUND TO BE
BROKEN OR LOOSE
NO
REPLACE IBC
TROUBLESHOOTING
Fig. 29 --- Troubleshooting Chart No. 3
NO
NO
CLEAN BOILER FLUE
PASSAGES PER
MAINTENANCE AND
CLEANING INSTRUCTIONS
REPLACE BLOWER
A06155
31
CHART 3
YES
IGNITER/SENSOR WARMS
UP AND GLOWS YELLOW/
ORANGE DURING 20
SECOND WARM UP
YES
TROUBLESHOOTING CHART 4
CHECK FOR 120 VAC
BETWEEN TERMINALS 1
NO
AND 2 AT CONNECTOR
CN1 ON IBC (DURING
IGNITER WARM UP)
YES
NO
REPLACE IBC
AFTER 20 SECOND
IGNITER WARM UP, GAS
VALVE IS ENERGIZED
VALVE LIGHT ON.
1 SECOND LATER POWER
IS REMOVED FROM
IGNITER/SENSOR
POWER LIGHT IS OFF.
DOES MAIN BURNER LIGHT?
YES
CHECK FOR 120 VAC AT
IGNITER/SENSOR LEADS
ON WIRING HARNESS
(DURING IGNITER
WARM UP)
YES
CHECK FOR 24 VAC
ACROSS TERMINALS MV
ON THE GAS
CONTROL. WHILE VALVE/
FLAME INDICATOR LIGHT
SENSOR POSITION IS OK?
TIP SHOULD BE SLANTED
IS ON
YES
CHECK IF IGNITER/
TOWARDS BURNER
YES
REPAIR/REPLACE WIRING
NO
FROM IBC TO IGNITER/
SENSOR
REPLACE IGNITER/SENSOR
CHECK FOR 24 VAC
ACROSS TERMINALS
NONONO
CN6-Z AND CN6-5 ON
IBC, WHILE THE VALVE/
FLAME LED IS LIT
REPAIR/REPLACE WIRING
BETWEEN IBC AND
GAS CONTROL
RESTORE IGNITER/SENSOR
NO
TO CORRECT POSITION
DO NOT RELOCATE
REPLACE IBC
YES
CHECK GAS SUPPLY
PRESSURE AT INLET
PRESSURE TAPPING ON
GAS CONTROL. IS GAS
PRESSURE GREATER
THAN 4.0" W.C.?
YES
CHART 5CHART 5
TROUBLESHOOTING
Fig. 30 --- Troubleshooting Chart No. 4
ARE ALL MANUAL SHUT-
NO
OFFS IN THE GAS
SUPPLY LINE AND ON
THE GAS CONTROL IN
THE OPEN OR ON
CONTACT THE GAS
UTILITY TO TURN THE
POSITION?
YES
GAS ON
NO
OPEN OR TURN ON ALL
MANUAL SHUTOFFS
A04072
32
A04073
Fig. 31 --- Troubleshooting Chart No. 5
33
REPLACE GAS CONTROL
CHECK GAS ORIFACE SIZE
IS GAS ORIFICE SIZE CORRECT.
CHECK REPAIR PARTS LIST
FOR CORRECT SIZE. IS GAS
ORIFICE CLEAR OF BLOCKAGE.
THEN TURNS OFF.
CHECK FIRING RATE OF UNIT.
IS UNIT FIRING AT THE CORRECT RATE?
DOES THIS UNIT USE LP GAS.
ADJUST RATE AS DESCRIBED IN
THE CHECK OUT PROCEDURE
AND ADJUSTMENT SECTION OF
THE MANUAL.
VALVE LIGHT OFF.
DOES DRAFT BLOWER
STOP AFTER 30
SECOND POST PURGE?
A04074
Fig. 32 --- Troubleshooting Chart No. 6
34
REPAIR PART S
2
3
4
19
5
6
7
8
11a
11b
9
12
10
15
16
1
16
13
14
18
17
A04076
Fig. 33 --- Jacket and Base Assembly
35
*Not Shown
JACKET AND BASE AS SEMBLY
ItemPart No.DescriptionQuantity
12272144Base Replacement Kit1
2650001028Control Panel1
3146622803Integrated Boiler Control1
455000133940 VA Transformer Kit1
5146313164” x 4” x 2 - -- 1/8” J--- Box1
614631319Switch P & S1
714631318J --- B o x P l a t e C o v e r1
82272152AB
92272151AB
10750701031ABJacket Panel, Back1
11a2370007ABJacket Panel, Top Left1
11b2370008ABJacket Panel, Top Right1
1212695074Screw 10 x 1/2” ZP12
13750001034Jacket Tie Bar1
1414695060Screw 10 x 1/2” Tech14
151225013Tap B u m p e r1
161225012Latch and Clip Kit1
1714631095Door Pull
18
192485001Pressure Switch Mounting Plate1
*1263010Harness Low Water Cutoff1
*1263020Wiring Harness1
*146311742--- 1/2” Plug1
*
2272150AB
2272164AB
Jacket Panel Left Side Kit
(Includes Items 15 and 16)
Jacket Panel Right Side Kit
(Includes Items 15 and 16)
Jacket Service Door Replacement Kit
(Includes Items 16 and 17)
Jacket, Complete Replacement Kit
(Includes Items 8, 9, 11a, and 18)
1
1
1
1
36
1
29 1/2" LONG
*Not Shown
2
3
7" LONG
4
10
3 3/4" LONG
11
12" LONG
1 3/8" LONG
8
7
9
2" LONG
6
5
7
8
3 3/4" LONG
7
Fig. 34 --- Exhaust Tee and Condensate Assembly
EXHAUST TEE AND CONDENSATE ASSEMBLY
ItemPart NumberDescriptionQuantity
11400008
Vent Pipe 2” C PVC
S C H --- 4 0 x 2 9 --- 1 / 2 ” L o n g
214631305Te e 2 ” C P V C S C H --- 801
31400008Vent Pipe 2” CPVC SCH---40 x 7” Long1
4240005852Cleanout PVC 2”1
51001002
PVC Fitting 1/2” NPT Male x 1/2”
Slip Female
6140014Pipe 1/2” PVC SCH---40 x 1--- 3/8”1
71190005Elbow 1/2” x 90 deg. PVC SCH ---403
81400014Pipe 1/2” PVC SCH--- 40 x 3- -- 3/4”2
91400014Pipe 1/2” PVC SCH---40 x 2”1
101510012Tee 1/2” x 1/2” x 1/2” PVC SCH---401
111400014Pipe 1/2” PVC SCH --- 40 x 12”1
*KGAVT0601CVT3” Concentric Vent1
1
1
A06154
37
24
25
2322
21
20
19
26
27
28
18
17
30
16
15
29
14
13
1
11
12
2
30
3
4
10
31
5
6
7
8
9
Fig. 35 --- Boiler Block and Piping Assembly
A06153
38
* Not Shown
BOILER BLOCK AND PIPING ASSEMBLY
ItemPart NumberDescriptionQuantity
12272160Replacement Block Kit
(Includes Items 2 and 30)
213950021--- 1/4” Plug Cast Iron Square Head Plug12
314631301Hose 3” Long x 2--- 3/8 I.D. x 2 ---3/4” O.D.1
41400008Vent Pipe 2” CPVC SCH ---40 x 7” Long1
51310015Nipple, Black 1 --- 1/2” Close1
614622000Valve BLR DR 3/4”1
71510010Reducing Tee 1-- -1/2” x 1---1/4” x 3/4”1
811900041--- 1/4” Street Elbow BLK 90_1
91310002Nipple Std Black 1--- 1/4” x 3/4”1
101190002Elbow 1--- 1/4” x 90_1
1114631004Sight Glass Adapter1
1214619002Observation Port 3/4”1
131230010Fitting, Brass 1/8” NPT x 3/16” Straight Barb1
1414631324Aquastat1
1514662804Well Control ½”1
1614693004¾” x ½” Std. Black Bushing1
17146932041½” x 1¼” Std. Black Bushing1
18PF065011¼” x 7” NPT Std. Black Pipe Nipple1
191260006SPTemp/Pressure Gauge 2” Shank1
201060002¾” x ¼” Std. Black Iron Bushing1
21PF059011¼” x 1¼” x ¾” Std. Black Tee1
22146930013/4” x 1/8” Black Bushing1
231580006AirPurgerw/CheckValve1
2414622011¾” Relief Valve1
2514607002¾” x 6½” Std. Black Nipple1
2614695802Screw Soc HD Cap 8---32 x 3/16”2
271500005Casting Temperature Switch1
282272137Replacement LWCO Kit1
29146930051” x ¾” Black Bushing1
3013950041” Cast Iron Square Head Solid Plug2
3114631302Clamp, Stainless Steel #442
*CI---001.03Circulator Pump w/Flange, Taco1
1
39
6
* Not Shown
2
1
7
8
3
4
5
Fig. 36 --- Burner Assembly
BURNER ASSEMBLY
ItemPart NumberDescriptionQuantity
12272149
21250009Burner/Casting Gasket1
31250008Burner/Flue Adapter Gasket1
41210122Flue Adapter1
514695810Hex Nut w/Serrated Washer ¼” x 205
61450011Threaded Stud ¼” x 20 x 1½”5
71250010Igniter/Mixer Gasket1
81264005Hot Surface Igniter1
914695809Sc r e w 1 0 --- 3 2 x 3 / 8 ”2
*2272133
Burner Replacement Kit
(Includes Items 2 and 3)
Hot Surface Igniter Kit
(Includes Items 7, 8 and 9)
1
1
9
A04079
40
3
2
2"
1
3"
1
AIR INLET
CONNECTION
7
9
6"
4
SIGHT GLASS
& ADAPTER
13 1/4"
5 1/2"
4
1
Fig. 37 --- Mixer and Air Pressure Switch Assembly