Unit Report
Unit Parameters
Unit
Model:
Unit Size:
Volts-Phase-Hertz:
50VT-C60---5
60 (5 Tons)
208-3-60
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length:
Unit Width:
Unit Height:
4' 0.25''
3' 8.1875''
4' 0.75''
Heating Type:
Heat Pump
*** Weights and Dimensions are approximate. Weight does not include
Duct Cfg:
Horizontal Supply / Horizontal Return
factory installed options. Approximate dimensions are provided
primarily for shipping purposes. For exact dimensions and
weights, refer to appropriate product data catalog.
Base Unit Weight (Does not include any accessories):
487
lb
Warranty Information
1 year warranty on parts
5 yearwarranty on compressor
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Packaged Rooftop Builder 1.72 Page 4 of 8
roof curbs, unit packaging, field installed accessories or

Certified Drawing
Packaged Rooftop Builder 1.72 Page 5 of 8

Performance Summary
Part Number:50VT-C60---5
ARI SEER:
Base Unit Dimensions
Unit Length:
Unit Width:
Unit Height:
Base Unit Weight (Does not include any accessories): 487
lb
Unit
Unit Voltage-Phase-Hertz:
Air Discharge:
Fan Drive Type:
Actual Airflow:
Site Altitude:
Cooling Performance
Condenser Entering Air DB:
Evaporator Entering Air DB:
Evaporator Entering Air WB:
Entering Air Enthalpy:
Evaporator Leaving Air DB:
Evaporator Leaving Air WB:
Evaporator Leaving Air Enthalpy:
Net Cooling Capacity:
Net Sensible Capacity:
Total Unit Power Input:
Coil Bypass Factor:
Heating Performance
Outdoor Ambient Temperature:
Entering Air Indoor Coil DB:
Leaving Air Indoor Coil DB:
Total Heating Capacity:
Integrated Heating Capacity:
Heating Power Input:
Supply Fan
External Static Pressure:
Options / Accessories Static Pressure
Wet Coil:
Application External Static (ESP + Unit Opts/Acc.):
Fan Motor Size, hp:
NOTE:
208-3-60
Horizontal
Direct
2140
0
95.0
80.0
67.0
31.44
61.0
58.5
25.33
58.82
43.90
5.13
0.252
47.0
70.0
95.3
58.57
58.57
4.76
0.50
0.10
0.60
1
High Motor Speed, Horz
CFM
ft
F
F
F
BTU/lb
F
F
BTU/lb
MBH
MBH
kW
F
F
F
MBH
MBH
kW
in wg
in wg
in wg
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.
Electrical Data
Minimum Voltage:
Maximum Voltage:
Compressor RLA:
Compressor LRA:
Outdoor Fan FLA (ea):
Indoor Fan Motor FLA (Total):
Power Supply MCA:
Power Supply MOCP (Fuse or HACR):
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
197
253
16
110
1
7.6
28.7
40
Packaged Rooftop Builder 1.72 Page 6 of 8

Sound Rating:
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA
NA
125 Hz NA NA 59.3
250 Hz NA NA 62.2
500 Hz NA NA 62.1
1000 Hz NA NA 64.1
2000 Hz NA NA 59.4
4000 Hz NA NA 55.8
8000 Hz NA NA 50.2
Advanced Acoustics
Advanced Accoustics Parameters
1. Unit height above ground:
2. Horizontal distance from unit to receiver:
3. Receiver height above ground:
4. Height of obstruction:
5. Horizontal distance from obstruction to receiver:
6. Horizontal distance from unit to obstruction:
Detailed Acoustics Information
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
30.0
50.0
5.7
0.0
0.0
0.0
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is
knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This
program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the
real system being estimated. Because of this, no assurances can be offered that this software will always generate
Octave Band Center Freq. Hz

Packaged Rooftop Builder 1.72 Page 7 of 8

an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
Packaged Rooftop Builder 1.72 Page 8 of 8