Carrier 58MCB, 58MVB, 58MTB User Manual

Page 1
MULTIPOISE, CONDENSING DIRECT VENT/NON-DIRECT VENT 58MCB, 58MTB, 58MVB, 58MXB
GAS FURNACE
USER’S INFORMATION MANUAL FOR OPERATION AND MAINTENANCE OF
YOUR GAS-FIRED FURNACE
NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.
!
WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neigh­bor’s phone. Follow the gas supplier’s instructions.
USER: Please read all instructions in the manual and retain all manuals for future reference.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a
qualied installer, service agency or the gas supplier.
!
WARNING:
CARBON MONOXIDE POISONING HAZARD Carbon Monoxide is invisible, odorless, and toxic! Carrier Corporation recommends a carbon mon­oxide alarm in your home, even if you do not own a gas appliance. Locate the carbon monoxide alarm in the living area of your home and away from gas appliances and doorways to attached garages. Follow the alarm manufacturer’s instruc­tion included with the alarm.
Do not use this furnace if any part has been under water. A ood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in re or explosion. A qualied service agency should be contacted to inspect the furnace and to replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
Page 2
®
• •
• •
•• • •
U
LT
R
A
H
I
G
H
E
F
F
I
C
I
E
N
C
Y
E
C
N
A
N
R
U
F
S
A
G
®
TABLE OF CONTENTS
WELCOME TO A NEW GENERATION OF COMFORT . . . . . . . 2
FURNACE COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
STARTING AND SHUTTING DOWN YOUR FURNACE . . . . . . . 5
Steps for Starting Your Furnace. . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Shutting Down Your Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
PERFORMING ROUTINE MAINTENANCE . . . . . . . . . . . . . . . . . . . 7
Filtering Out Trouble. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
COMBUSTION AREA AND VENT SYSTEM . . . . . . . . . . . . . . . . . . . 9
Heading South for the Winter . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
A CHECK-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
BEFORE YOU REQUEST A SERVICE CALL . . . . . . . . . . . . . . . . .11
INSTALLATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
WELCOME TO A NEW GENERATION OF COMFORT
Congratulations! In light of rising energy costs, the 58MCB, 58MXB, 58MTB, and WeatherMaker Innity, Multipoise, Gas­Fired Condensing Furnaces are among the soundest investments today’s homeowner can make.
Your new furnace is truly a triumph of technology in home heat­ing. A revolutionary design employs 2 heat exchangers to “squeeze” out the maximum amount of heat from the fuel con­sumed. In fact, your new furnace is so efficient, over 90%* of the heat generated during combustion is captured and delivered inside your home. That is more than a 33%* increase in heating effi- ciency over conventional furnaces.
These are among the most energy-efficient furnaces you can buy to- day. They also are among the safest and most dependable. We are proud of the technological advances incorporated into the design of these furnaces. With only minimal care, your new furnace will deliver many years of money-saving home comfort and enjoyment. Spend just a few minutes with this manual to learn the operation of your new furnace and the small amount of maintenance it takes to help keep it operating at peak efficiency year after year.
*The output capacity and any representations of efciency for this furnace are based on standard U.S. Department of Energy test procedures.
CERTIFIED
®
As an ENERGY STAR® partner, Carrier Corporation has determined that this product meets the ENERGY STAR® guidelines for energy efficiency.
1
MODELS 58MXB (SHOWN) AND 58MCB FIXED-CAPACITY FURNACES
2
MODEL 58MVB VARIABLE-CAPACITY AND MODEL 58MTB TWO-STAGE FURNACES
2
Page 3
FURNACE COMPONENTS
1
Combustion-air intake connection to ensure contami­nant-free air (right or left side).
2
Burner sight glass for viewing burner flame.
3
Burner assembly (inside). Operates with energy-saving inshot burners and hot surface igniter for safe, dependable heating.
4
Redundant gas valve. Safe and efficient. Features 1 gas control with 2 internal shutoff valves. Valve appearance varies with furnace model.
5
Vent outlet. Uses PVC pipe to carry flue gas from the fur­nace’s combustion system (right or left side).
6
Inducer motor. Pulls hot flue gases through the heat ex­changers, maintaining negative pressure for added safety.
7
Blower access panel safety interlock switch.
8
Air filter and retainer (location in furnace may vary).
9
Condensate drain connection. Collects moisture con­densed from burned gases for disposal into home drain system. (Location in furnace varies.)
17
2
3
1
4
12
18
5
11
5
14
16
6 9
need art
15
13 7
10
19
8
10
Heavy-duty blower. Circulates air across the heat ex­changers to transfer heat into the home.
11
Secondary condensing heat exchanger (inside). Wrings out more heat through condensation. Constructed with polypropylene-laminated steel to ensure durability.
12
Primary serpentine heat exchanger (inside). Stretches fuel dollars with the S-shaped heat-flow design. Solid con­struction of corrosion-resistant aluminized steel means re­liability.
13
Furnace control board.
14
3-amp fuse provides electrical and component protection.
15
Light emitting diode (LED) on furnace control board. Status code light is for diagnosing furnace operation and service requirements.
16
Pressure switch(es) ensure adequate flow of flue gas through furnace and out vent system.
17
Rollout switch (manual reset) to prevent overtemperature.
18
Junction box for 115-v electrical power supply. (May be located on right or left side)
19
Transformer (24v) behind furnace control board pro­vides low-voltage power to furnace control board and thermostat.
MODELS 58MCB, 58MXB, AND 58MTB FURNACES (UPFLOW POSITION)
2
12
1
5
11
16
9 8
3
17 3
4
18
6
5
15 14
13 7
19 10
MODEL 58MVB FURNACE (UPFLOW POSITION)
3
4
Page 4
SAFETY CONSIDERATIONS
Recognize safety information. This is the safety-alert sym-
!
bol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words—DANGER, WARNING, CAUTION and NOTE. DANGER, WARNING and CAUTION are used with the safety-alert symbol. DANGER identies the most serious hazards which personal injury or death. WARNING signies hazards which
could result in personal injury or death. CAUTION is used
to identify unsafe practices which sonal injury or product and property damage. NOTE is used to highlight suggestions which lation, reliability or operation.
To minimize the possibility of serious personal injury, re, furnace damage, or improper operation;
these safety rules:
• Your new gas furnace may have been installed in 1 of 2 ways, as a direct-vent (2-pipe) application or as a non-direct vent (1-pipe) application.
• In a direct-vent (2-pipe) application, your furnace uses air from outside the home for combustion and vents ue gas to the outdoors. This type of application will have 2 pipes run­ning from the furnace to the outdoors. (See Fig. 5.) In this application, the vent and air-intake pipes must terminate out­side the structure and must not be obstructed in any way. Do not block or obstruct air openings on furnace or spaces around furnace.
will result in enhanced instal-
will result in severe
may result in minor per-
carefully follow
6
• Keep the area around your furnace clear and free of com­bustible materials, gasoline, and other flammable liquids and vapors.
• In a non-direct vent (1-pipe) application, your furnace uses air from adjacent to the furnace for combustion and vents flue gas to the outdoors. This type of application will have only 1 pipe running from the furnace to the outdoors. (See Fig. 6) The other pipe will terminate in the same space as the furnace and is the source of combustion air for your furnace. There­fore, the furnace must not be enclosed in an airtight room or be sealed behind solid doors. It must have adequate airow for efcient combustion and safe ventilation. Do not obstruct the combustion-air pipe in any way. The vent pipe must ter­minate outside the structure and must not be obstructed in any way. Do not block or obstruct air openings or space around furnace.
• Do not cover the furnace, store trash or debris near it, or in any way block the ow of fresh air to the unit.
In addition to the safety rules above, make sure that the fol­lowing combustion-air requirements are met for non-direct vent applications.
• Combustion air must be clean and uncontaminated with chlorine or uorine. These compounds are present in many products around the home, such as water softener salts, laun­dry bleaches, detergents, adhesives, paints, varnishes, paint strippers, and plastics.
Make sure the combustion air for your furnace does not con­tain any of these compounds. During remodeling be sure the combustion air is fresh and uncontaminated. If these compounds are burned in your furnace, the heat exchangers may deteriorate.
5
• A furnace installed in an attic or other insulated space must be kept free and clear of insulating material. Examine the fur­nace area when the furnace is installed or when insulation is added. Some materials may be combustible.
• Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off electrical supply.
This furnace contains SAFETY DEVICES which must be MANUALLY RESET. If the furnace is left unattended for an extended period of time, have it checked periodically for proper operation. This precaution will prevent problems associated with no heat, such as frozen water pipes, etc. See “Before You Request a Service Call’’ section in this manual.
4
7
Page 5
!
WARNING
FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in fire, personal injury/death or property damage. Do not keep combustible materials, gasoline, and other flammable liquids or vapors around your furnace.
!
WARNING
FIRE AND UNIT OPERATION HAZARD Failure to follow this warning could result in fire, personal injury/death or property damage. For proper and safe operation the furnace needs air for combustion and ventilation. Do not block or obstruct the openings on the furnace, air openings to the area in which the furnace is in­stalled, and the space around the furnace.
Examine the furnace installation monthly to determine that:
1. All ue gas carrying areas external to the furnace (i.e. chimney, vent connector) are clear and free of obstructions.
2. The vent connector is in place, slopes upward and is phys­ically sound without holes or excessive corrosion.
3. The return-air duct connection(s) is physically sound, is sealed to the furnace casing, and terminates outside the space containing the furnace.
4. The physical support of the furnace is sound without sag­ging cracks, gaps, etc. around the base.
5. There are no obvious signs of deterioration of the furnace.
6. The burner ames are in good adjustment. (See Fig. 8.)
STARTING AND SHUTTING DOWN YOUR FURNACE
Instead of a continuously burning pilot ame which wastes valuable energy, your furnace uses an automatic, hot surface ignition system to light the burners each time the thermostat starts your furnace.
• Never attempt to manually light the burners with a match or other source of ame.
• Read and follow the operating instructions on inside of main furnace door, especially the item that reads as follows:
Wait 5 minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas, in the safety information above on this furnace label. If you don’t smell gas, go to the next step.
• If a suspected malfunction occurs with your gas control system, such as the burners do not light when they should, refer to the shutdown procedures on inside of main furnace door, or in the “Shutting Down Your Furnace” section and call your dealer as soon as possible.
FIRE HAZARD Failure to follow this warning could result in a fire or explosion, and personal injury/death or prop­erty damage. Should the gas supply fail to shut off or if over­heating occurs, turn off the manual gas valve to the furnace BEFORE turning off the electrical sup­ply. (See Fig. 11.)
CHECK AIR FILTER: Before attempting to start your
furnace, be sure the furnace lter is clean and in place. See “Performing Routine Maintenance” section in this manual. Then proceed as follows:
STEPS FOR STARTING YOUR FURNACE
1. Set your room thermostat to the lowest temperature set­ting. (See Fig. 10.)
2. Close the external manual gas valve. (See Fig. 11.)
Follow these important safeguards:
STOP! Follow “B’’
!
WARNING
9
8
®
10
5
Page 6
C
L
O
S
E
OFF
ON
OR
A04151
For 58MTB and 58MVB
11 12
3. Turn OFF electrical supply to the furnace. (See Fig. 12.)
4. Remove main furnace door. (See Fig. 13.)
13
5. The gas valve will have a control switch to turn off and on. Turn the control switch on the gas control to the OFF position and wait 5 minutes. (See Fig. 14 or 15.) Then smell for gas, including near the oor. If you smell gas, STOP! Follow “B” on furnace label. If you don’t smell gas, go to next step.
OFF
ON
16
1
M
O
F F
3
P
2
C
N
O
For 58MCB and 58MXB
17
6. After waiting 5 minutes, turn the control switch on the gas control to the ON position. (See Fig. 16 or 17.)
A05100
OR
18
O
P
E
N
For 58MTB and 58MVB
14
1
M
3
P
O F
F
2
C
ON
7. Replace main furnace door. (See Fig. 18.)
8. Turn ON the electrical supply to the furnace and wait 1 minute. (See Fig. 19.)
A05118
For 58MCB and 58MXB
9. Open the external manual gas valve. (See Fig. 20.)
10. Set the room thermostat to a temperature slightly above the room temperature. This will automatically signal the furnace to start.
11. When the furnace receives the start signal, the inducer is
15
started. When the pressure switch senses that there is suf­cient combustion air, the hot surface igniter is energized.
19 20
6
Page 7
After the hot surface igniter is heated for 17 seconds, the
ON
O F F
M
P
C
1
3
2
gas valve permits gas to flow to the main burners. After ignition and a time delay of about 60 sec, the furnace blower will start. Variable-capacity furnaces start at low speed until the control makes the necessary adjustments to operate the blower at either the low- or high-heat speed.
NOTE:
If the burners fail to ignite after 4 attempts, the fur­nace control system will lock out. If lockout occurs, main burners fail to light, or blower does not come on, shut down the furnace and call your dealer for service.
12. Set your thermostat to the temperature that satises your comfort requirements.
SUGGESTION: Setting the thermostat back a few degrees—and compensating for the difference with warmer clothing—can make a big difference in your fuel consumption. The few degrees at the top of your thermo­stat “comfort level’’ are the most costly degrees to obtain.
When the room temperature drops below the temperature selected on the thermostat, the furnace will switch on auto­matically. When the room temperature reaches the tempera­ture selected on the thermostat, the furnace will be switched off automatically.
Some thermostats have a FAN mode with 2 selections: AUTO and ON. When set on AUTO, the furnace blower cycles on and off. In the ON mode, the furnace blower runs continu­ously. Continuous fan keeps the temperature level in your home more evenly balanced. It also permits the indoor air to be continuously ltered. ComfortFan™ –On all but the 58MCB, the blower speed can be increased or decreased if desired due to change of seasons, large gatherings in your home, etc. Simply change your FAN from ON to OFF for 1 to 3 seconds (or AUTO depending on your thermostat), and then return to ON. The blower will switch to the next higher speed. There are at least 3 speeds to choose from. If the blower is running on its highest speed, a request to change will direct the blower to return to its lowest speed.
SHUTTING DOWN YOUR FURNACE
Should you ever need to shut down your furnace for service or maintenance, you will need to turn the furnace off. The following procedures must be followed:
1. Set your room thermostat to the lowest temperature setting. (See Fig. 21.)
OFF
ON
OR
For 58MTB and 58MVB
23
For 58MCB and 58MXB
24
6. Replace the main furnace door. (See Fig. 18.)
7. If the furnace is being shut down because of a malfunc­tion, call your dealer as soon as possible.
22
®
2. Close the external manual gas valve (See Fig. 11.)
3. Turn off electrical supply to the furnace. (See Fig. 22.)
4. Remove main furnace door. (See Fig. 13.)
5. Turn the switch on the gas control to the OFF position. (See Fig. 23 or 24.)
21
!
CAUTION
UNIT AND PROPERTY DAMAGE Failure to follow this caution may result in damage to the furnace and other property damage.
Furnace is not to be installed, operated, and then turned off and left turned off in an unoccupied structure during winter. (See “Heading South for the Winter” procedures in maintenance section on page 10).
PERFORMING ROUTINE MAINTENANCE
NOTE:
The qualified installer or agency must use only factory-authorized replacement parts, kits, and accessories when modifying this product.
Installing and servicing heating equipment can be hazard­ous due to gas and electrical components.
7
Page 8
8
Only trained and qualied personnel should install, repair, or ser-
28
vice heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters.
All other operations must be performed by trained and qual­ied service agency personnel. Observe safety precautions in this manual, on tags, and on labels attached to the furnace, and other safety precautions that may apply.
With proper maintenance and care, your furnace will operate economically and dependably. Instructions for basic mainte­nance are found on this and the following pages. However, before beginning maintenance, follow these safety precautions:
!
WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in per­sonal injury/death. Turn off electrical power supply to your furnace before removing the access doors to service or perform maintenance.
!
CAUTION
CUT HAZARD Failure to follow this caution may result in minor personal injury. Although special care has been taken to minimize sharp edges, be extremely careful when handling parts or reaching into the furnace.
• AIR FILTER LOCATED IN FILTER CABINET a. Remove lter cabinet door. (See Fig. 27 and 28.)
NOTE: It will be necessary to remove 1 thumbscrew
3. Remove air lter from furnace.
• AIR FILTER LOCATED IN BLOWER COMPARTMENT BOTTOM: a. Slide lter retainer sideways until it is free of latch. (See Fig. 29.) b. Slide air filter out of furnace. (See Fig. 30.)
• AIR FILTER(S) LOACTED IN BLOWER COMPART­MENT SIDE: a. Remove lter retainer from latch. (See Fig. 31.) b. Gently remove air lter and carefully turn the dirty side up (if dirty) to avoid spilling dirt from the filter. (See Fig. 32.)
• AIR FILTER LOCATED IN FILTER CABINET: a. Slide air lter out of furnace. Keep dirty side up (if dirty) to avoid spilling dirt. (See Fig. 33 and 34.)
4. Inspect the lter. If torn, replace it.
NOTE: If washable filter that was shipped with the furnace has
been replaced by: a) Factory specied disposable media filter–Do not clean. If dirty, replace only with media lter having the same part number and size. Install with airow direction arrow point­ing towards blower.
FILTERING OUT TROUBLE
!
CAUTION
UNIT PERFORMANCE HAZARD Failure to follow this caution may result in product damage. Never operate your furnace without a filter in place. Doing so may damage the furnace blower motor. An accumulation of dust and lint on internal parts of your furnace can cause a loss of efficiency.
A dirty air lter will cause a loss of airow in your duct system. When excessive loss of airow occurs, the furnace may cycle on its safety controls. If this condition is left unat­tended, the furnace will eventually lock out. It is recom­mended that the furnace air lter be checked every 3 or 4 weeks and cleaned if necessary.
If installed with factory-specied disposable media lter, check or replace lter before each heating and cooling sea­son. Replace disposable media lter at least once a year.
The air lter is normally located in the blower compartment (See Fig. 3 or 4.) or in the factory-supplied lter cabinet attached to the side or bottom of the furnace casing. If air lter has been installed in another location, contact your deal­er for instructions. To inspect, clean, and/or replace the air lter(s), follow these steps:
1. Turn off electrical supply to furnace. (See Fig. 22.)
2. Remove door/access panel
• AIR FILTERS(S) LOCATED IN BLOWER COMPART­MENT a. Remove main furnace door. (See Fig. 25.) b. Remove blower access panel. (See Fig. 26.)
NOTE: It will be necessary to remove 2 screws
A05099
25 26
27
29 30
Page 9
31 32
b) Electronic air cleaner (EAC) – Refer to EAC Owner’s Manual for maintenance information.
5. If washable lter, wash lter (if dirty) in sink, bathtub, or out­side with a garden hose. Always use cold tap water. A mild liquid detergent may be used if necessary. Spray water through filter in the opposite direction of airow. Allow lter to dry.
6. Reinstall clean air lter
7. Reinstall lter retainer (for blower compartment locations only)
8. Replace blower access panel and main furnace door (See Fig. 35 and 36.) or lter cabinet door (Fig. 37 and 38.)
9. Turn on electrical supply to furnace.
If your furnace air lter needs to be replaced, be sure to use a factory-authorized lter of the same size that was orginally sup­plied. Use the lter tables and compare your furnace size with the proper lter size.
37 38
FURNACE AIR FILTER TABLE
AIR FILTER LOCATED IN BLOWER COMPARTMENT
FURNACE
CASING
WIDTH (IN.)
17-1/2 (1) 16 x 25 x 1 (1) 16 x 25 x 1 Cleanable
21 (1) 16 x 25 x 1 (1) 20 x 25 x 1 Cleanable
24-1/2 (1 or 2) 16 x 25 x 1 (1) 24 x 25 x 1 Cleanable
AIR FILTER LOCATED IN FILTER CABINET
FILTER
CABINET
HEIGHT (IN)
16 (1) 16 x 25 x 1*
20 (1) 20 x 25 x 1*
24 (1) 24 x 25 x 1*
* Factory-provided with the furnace. Filters may be eld modied by cutting-
lter material and support rods (3) in lters. Upow only. Alternate sizes and additional lters may be ordered from your
dealer.
FILTER SIZE (IN)
FILTER
SIZE (IN)
or (1) 16 x 25 x 4-5/16
or (1) 20 x 25 x 4-5/16
or (1) 24 x 25 x 4-5/16
FILTER
TYPESide Return* Bottom Return*
FILTER
TYPE
Cleanable or
Disposable
Cleanable or
Disposable
Cleanable or
Disposable
33 34
A05100
35 36
!
WARNING
PERSONAL INJURY HAZARD Failure to follow this warning could result in per­sonal injury.
Use care when cutting support rods in filters to protect against flying pieces and sharp rod ends. Wear safety glasses, gloves, and appropriate protective clothing.
COMBUSTION AREA AND VENT SYSTEM
Visually inspect the combustion area and vent system before each heating season. Make sure that all PVC pipes leading into the combustion area and vent are free from any cracks and sags.
!
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in per­sonal injury or death. If holes are found in the pipes or if any portion has become disconnected, toxic fumes can escape into your home. DO NOT OPERATE YOUR FURNACE. Call your dealer for service.
9
Page 10
Check the combustion-air intake and vent pipe on the outside of your home for blockage.
When dirt, soot, scale, or rust is allowed to build up, your furnace can suffer a loss of efficiency and perform improperly. Accumu- lations on the main burners can result in ring out of normal sequence. This delayed ignition creates an alarmingly loud sound.
!
CAUTION
UNIT OPERATION HAZARD Failure to follow this caution may result in minor property damage. If your furnace makes an especially loud noise when the main burners light, shut down your fur­nace and call your dealer.
To inspect the combustion area and vent system, you will need a ashlight. Refer to Fig. 3 or 4, and proceed as follows:
1. Turn off the gas and electrical supplies to the furnace and remove the main furnace door. (See Fig. 11, 12, and 13.)
2. Remove burner enclosure front. (See Fig. 39 or 40.)
Inspect the gas burners, igniter area, and remainder of furnace for dirt, rust, soot, or scale.
!
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in per­sonal injury or death. If dirt, rust, soot, or scale accumulations are found, call your dealer. Do not operate your furnace.
3.
Inspect the combustion-air and vent PVC pipes for sags, holes, cracks, water leaks, blockage or disconnections. Horizontal portions of pipes must slope downward toward furnace.
HEADING SOUTH FOR THE WINTER?
DON’T FORGET YOUR FURNACE!
!
CAUTION
UNIT AND PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage. If the furnace is installed in an unconditioned space where the ambient temperatures may be 32°F or lower, freeze protection measures must be taken to prevent minor property or product damage.
Since the furnace uses a condensing heat exchanger, some water will accumulate in the unit as a result of the heat transfer process. Therefore, once it has been operated, it cannot be turned off and left off for an extended period of time when temperatures will reach 32°F or lower unless winterized. Follow these procedures to winterize your furnace:
1. Obtain propylene glycol (RV/swimming pool antifreeze or equivalent).
!
CAUTION
UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage. Do not use ethylene glycol (Prestone II antifreeze coolant or equivalent). Failure of plastic components may occur.
2. Turn off electrical supply to the furnace. (See Fig. 22.)
3. Remove main furnace door. (See Fig. 25.)
4. Remove upper inducer housing drain connection cap. (See Fig. 42.)
Upflow
Downflow
39 40
4. Reinstall burner enclosure front.
5. If your furnace is free of the above conditions, replace main furnace door and turn on electrical and gas supplies to the furnace. (See Fig. 18, 19, and 20.)
6. Start the furnace and observe its operation. Watch the burner flames to see if they are clear blue, almost transpar- ent. (See Fig. 41.) If you observe a suspected malfunction, or the burner ames are not clear blue, call your dealer.
41
5. Connect eld-supplied 1/2-in. ID tube to upper inducer
10
housing drain connection.
42
43
Page 11
6. Insert eld-supplied funnel into tube.
7. Pour 1 quart of antifreeze into funnel/tube. Antifreeze should run through inducer housing, overll condensate trap, and ow into open eld drain. (See Fig. 43.)
8. Remove funnel and tube from inducer housing and replace drain connection cap and clamp.
9. Replace main furnace door. (See Fig. 36.)
10. Propylene glycol need not be removed before restarting furnace.
A CHECK-UP CHECKLIST
Your furnace represents an important investment in your fami­ly’s comfort and your home’s value. To keep it performing properly and to prevent future problems, have a trained service specialist give your furnace a professional check-up annually. The following checklist can be used as a guideline to proper service:
• Inspect all ue gas passages, burners, heat exchangers, cou­pling box(es), and inducer assembly.
• Inspect all combustion-air and vent piping inside structure and vent pipe termination outside the structure.
• Check gas pipes leading to and inside of your furnace for leaks.
• Inspect and clean the blower motor and wheel. NOTE: The inducer and blower motors are pre-lubricated and
require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
• Inspect and change or clean air lters(s) if necessary.
• Inspect all supply- and return-air ducts for obstructions, air leaks, and insulation. Remedy any problem when necessary.
• Inspect the return-air duct connections(s) at the furnace to en­sure it is physically sound, sealed to the furnace casing, and ter­minates outside the space containing the furnace.
• Inspect electrical wiring, connections, and components for loose connections.
• Perform an operational checkout to determine whether your furnace is working properly and if it requires adjustments.
• Inspect all condensate drain tubes and condensate trap assem­bly for leaks. The condensate removal system should be cleaned annually by a qualied service agency. Refer to the Service and Maintenance Instructions for further information.
• Examine the physical support of the furnace. Support should be sound with not cracks, sagging, gaps, etc. around the base.
• Check furnace for any obvious signs of deterioration.
BEFORE YOU REQUEST A SERVICE CALL
If your furnace is not operating or not performing properly, you may save the expense of a service call by checking a few things yourself before calling for service.
FOR INSUFFICIENT AIRFLOW:
• Check for dirty air lter(s).
• Check for blocked return-air or supply-air grilles throughout your home. Ensure they are open and unobstructed.
If problem still exists, call your dealer for service. IF FURNACE FAILS TO OPERATE: Follow this checklist step by step, advancing to the next step
only if furnace fails to start.
• Check thermostat for proper temperature. Is thermostat set above room temperature?
• Is thermostat set on HEAT?
• Check fuses and circuit breakers. Is electrical supply on?
• Is manual shutoff valve in gas supply pipe in open position? (Follow start-up procedures if you open gas valve.)
NOTE: Turn off electrical supply before continuing with checklist.
• Is control switch on gas valve in ON position? (Follow start­up procedures if you must reset switch to ON position.)
• Check manual reset ame rollout switch located on the burner box. (See Fig. 3 or 4.) If furnace has experienced high temper­ature conditions, this switch will shut off the furnace. Reset it by pushing the button on the switch. If it trips again, shut down the furnace and call for service. See “Shutting Down Your Fur­nace” section in this manual.
• Check for obstructions around the vent termination outside the structure.
If the furnace still fails to operate, call your service representa­tive.
For your convenience, record the furnace product and serial numbers on back page. Should you ever require service, you will have ready access to the information needed by your ser­vice representative.
This furnace has a light-emitting-diode (LED) status code dis­play to aid the installer, service technician, or homeowner while installing or servicing the unit. The LED code can be seen by removing the main furnace door and viewing the LED through the view port in the blower access panel.
11
Page 12
INSTALLATION DATA
AIR CONDITIONER OR HEAT PUMP
Date Installed Dealer Name Address City State Zip Telephone
FURNACE
Product No. Model No. Serial No.
OUTDOOR UNIT: Product No. Model No. Serial No.
INDOOR COIL: Product No. Model No. Serial No.
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or the classified section of your local telephone directory under the
Manufacturer reserves the right to discontinue, or change at any time, specications or designs without notice and without incurring obligations.
Copyright 2005 Carrier Corporation Replaces: OM58-114 Printed in the U.S.A. a 8-05 PC 101 Catalog No. OM58-117
“Heating Equipment’’ or “Air Conditioning Contractors & Systems’’ heading for dealer listing by brand name.
Have available the Model No., Series Letter, & Serial No. of your equipment to ensure correct replacement part.
Carrier Corporation 7310 West Morris St. Indianapolis, IN 46231
Loading...