Carrier 58MCA User Manual

Page 1
Visit www.carrier.com
58MCA
4-Way Multipoise Fixed-Capacity
Direct-Vent Condensing Gas Furnace
Service and Maintenance Instructions
For Sizes 040—140, Series 131
®
ama
NOTE: Read the entire instruction manual before performing any service or maintenance.
This symbol indicates a change since the last issue. Index Page
SAFETY CONSIDERATIONS..................................................1-2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2
GENERAL......................................................................................2
CARE AND MAINTENANCE................................................2-11
Cleaning and/or Replacing Air Filter.......................................3
Blower Motor and Wheel Maintenance................................3-4
Cleaning Burners...................................................................4-5
Cleaning Heat Exchangers ....................................................5-7
Primary Heat Exchangers ................................................5-7
Secondary Heat Exchangers................................................7
Flushing Collector Box and Drainage System ........................7
Servicing Hot Surface Ignitor ...............................................7-8
Electrical Controls and Wiring .............................................8-9
Troubleshooting...................................................................9-10
Checking Heat Tape Operation (If Applicable) ....................10
Winterizing ........................................................................10-11
WIRING DIAGRAM...................................................................12
SERVICE LABEL .......................................................................13
TROUBLESHOOTING GUIDE ............................................14-15
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes, including NFPA 54/ANSI Z223.1-1996,
National Fuel Gas Code and ANSI/NFPA 90B, Installation Stan­dards, Warm Air Heating and Air Conditioning Systems. In Canada, refer to the current edition of the National Standard of
A93040
CANADIAN GAS ASSOCIATION
APPROVED
R
As an ENERGY STAR Partner, Carrier Corporation has determined that this prod­uct meets the ENERGY STAR guidelines for energy efficiency.
SM
A93278
CERTIFICATION OF MANUFACTURING SITE
Fig. 1—Multipoise Furnace in Upflow Orientation
Canada CAN/CGA-B-149. Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 6a 8a
PC 101 Catalog No. 565-879 Printed in U.S.A. Form 58MCA-4SM Pg 1 11-96 Replaces: 58MCA-3SM
Page 2
The ability to properly perform maintenance on this equip­ment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS PERSONAL INJURY, OR DEATH.
Never store anything on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning com­pounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products.
Failure to follow this warning can cause corrosion of the heat exchanger, fire, personal injury, or death.
GENERAL
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 2, you may need to revise your orientation to component location accordingly.
AIRFLOW
UPFLOW
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
HORIZONTAL
RIGHT
AIRFLOW
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre­vent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CON­TROL PRIOR TO DISCHARGING YOUR BODY’S ELEC­TROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
AIRFLOW
A93041
Fig. 2—Multipoise Orientations
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip­ment failure, it is essential that maintenance be performed annually on this equipment. Consult your local dealer for maintenance and maintenance contract availability.
Turn off the gas and electrical supplies to the unit before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace. Failure to follow this warning could result in personal injury or death.
The minimum maintenance that should be performed on this equipment is as follows:
1. Check and clean or replace air filter each month as required.
2. Check blower motor and wheel for cleanliness annually.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
4. Check for proper condensate drainage. Clean as necessary.
5. Check for blockages in combustion-air and vent pipes annu­ally.
6. Check burners for cleanliness annually.
Personal injury could result from sharp metal edges, etc. Use care when removing parts.
2
Page 3
WASHABLE FILTER
WASHABLE
FILTER
FILTER RETAINER
FILTER SUPPORT
FILTER RETAINER
A93046
Fig. 3—Bottom Filter Arrangement
Step 1—Cleaning and/or Replacing Air Filter
The air filter arrangement may vary depending on the application or orientation.
Never operate unit without a filter or with the blower access panel removed. Failure to follow this warning could result in a fire or personal injury.
To clean or replace the filters, proceed as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Release filter retainer wire. (See Fig. 3 and 4.)
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s). Clean filter by spraying cold tap water through filter in opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating of filter is not recommended.
7. Place filter in furnace.
8. Replace blower access panel and main furnace door.
9. Turn on electrical supply to furnace.
NOTE: If the filter has cross-mesh binding, the binding must face the blower. If the filter has an air direction arrow, the arrow must point toward the blower.
Step 2—Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean accumu­lated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
The following items should be performed by a qualified service technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires.
A93045
Fig. 4—Filter Installed for Side Inlet
All factory wires can be left connected, but field thermostat connections may need to be disconnected depending on their length and routing.
4. Position control box, transformer, and door switch assembly to right side of furnace casing.
5. If condensate trap is located in left- or right-hand side of furnace casing, proceed to item 6, otherwise remove trap and tubing as described below.
a. Disconnect field drain connection from condensate trap. b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace.
7. Clean blower wheel and motor by using a vacuum with soft brush attachment. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not bend wheel or blades as balance will be affected.
8. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly to
ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing and
slide motor and mounts out of housing. Disconnect capaci­tor and ground wire attached to blower housing before
removing motor. f. Remove blower wheel from housing. g. Clean wheel per instructions on degreaser cleaner.
9. Reassemble motor and blower wheel by reversing items 8b through 8f. Ensure wheel is positioned for proper rotation. Be sure to reattach ground wire.
10. Reinstall blower assembly in furnace.
3
Page 4
11. Reinstall condensate trap and tubing if previously removed. a. Reinstall condensate trap in hole in blower shelf. b. Connect condensate trap drain tubes. See Fig. 8 or tubing
diagram on main furnace door for proper tube location. (1.) Connect 1 tube (blue or blue and white striped) from
collector box.
(2.) Connect 1 tube (violet or unmarked) from inducer
housing.
(3.) Connect 1 tube (relief port, green or pink) from
collector box.
c. Connect field drain to condensate trap.
NOTE: Ensure tubes are not kinked or pinched, as this will affect operation.
12. Reinstall control box, transformer, and door switch assembly on blower shelf.
13. Reconnect wires. Refer to furnace wiring diagram, and connect thermostat leads
if previously disconnected. (See Fig. 16.)
NOTE: Refer to Table 1 for motor speed lead relocation if leads were not identified before disconnection.
Table 1—Speed Selector
COLOR SPEED
Black High Cool
Yellow (When Present) Medium High Spare
Blue Medium Low Heat
Red Low Spare
White Common Com
Heating speed selection MUST be adjusted to provide proper temperature rise as specified on the rating plate. Failure to adjust the heating speed may shorten heat exchanger life.
14. Turn on electrical supply. Manually close blower access panel door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed changes between heating and cooling by jumpering R to G and R to Y on control center thermostat terminals. (See Fig. 13.)
Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in personal injury or death.
15. If furnace is operating properly, release blower access panel door switch, replace blower access panel, and replace main furnace door.
Step 3—Cleaning Burners
The following items should be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
4. Using backup wrench, disconnect gas supply pipe from gas valve.
FACTORY
ATTACHED TO
5. Remove wires from gas valve. Note location for reassembly.
Label all wires prior to disconnection when servicing con­trols. Wiring errors can cause improper and dangerous operation.
6. Remove burner box pressure tube from gas valve regulator fitting.
7. Remove screws that secure manifold to burner box. (See Fig.
5.)
MANIFOLD MOUNTING SCREW
MANIFOLD
GAS VALVE REGULATOR FITTING
GAS VALVE
A93295
Fig. 5—Burner Box Assembly
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box. NOTE: All burners are attached to burner bracket and can be
removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly and burners fit over orifices.
13. Reconnect wires to gas valve. Refer to furnace wiring diagram for proper wire location.
14. Reinstall burner box pressure tube to gas valve regulator fitting.
15. Reinstall gas supply pipe to gas valve using backup wrench on gas valve to prevent rotation and improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape.
Gas valve switch or knob MUST be facing forward or tilted upward. Failure to follow this warning could result in property damage, personal injury, or death.
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
18. Check for gas leaks.
4
Page 5
Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
19. Replace main furnace door.
Step 4—Cleaning Heat Exchangers
The following items should be performed by a qualified service technician.
PRIMARY HEAT EXCHANGERS If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure: NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, improper vent termination, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger (primary or secondary). Action must be taken to correct the problem.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect wires or connectors to rollout switch, gas valve, ignitor, and flame sensor.
PRIMARY HX INLET OPENINGS
A93080
Fig. 6—Cleaning Inlet Openings of Primary Heat
Exchangers
NOTE: Inspect combustion-air intake housing. If foamed gasket
was removed, check for any damage. If gasket is damaged in any way, it must be repaired. To repair, remove damaged gasket section, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons) to burner box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to edge of combustion-air intake housing. (See Fig. 7.)
Label all wires prior to disconnection when servicing con­trols. Wiring errors can cause improper and dangerous operation.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from gas valve.
8. Disconnect pressure tubing from gas valve.
9. Remove 2 screws attaching top filler panel and rotate upwards to gain access to screws attaching burner box to cell panel.
10. Remove screws attaching burner box to cell panel. (See Fig.
5.)
NOTE: Burner box cover, manifold, gas valve, and burner assembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 6.)
NOTE: After cleaning, inspect the heat exchangers to ensure they are free of all foreign objects that may restrict flow of combustion products.
12. Reverse items 4 through 10 for reassembly.
The ground wire from the gas valve MUST be attached to the burner box attachment screw. Failure to attach this ground wire to an adequate casing ground will cause the furnace control to lock out.
RTV
PAM
A93087
Fig. 7—Combustion-Air Intake Housing Gasket
Repair
13. Refer to furnace wiring diagram and reconnect wires to rollout switch, gas valve, ignitor, and flame sensor.
14. Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door for proper tube location. Be sure tubes are not kinked. (See Fig.
8.)
15. Turn on gas and electrical supplies to furnace.
16. Check furnace operation through 2 complete heat operating cycles. Look through sight glass in burner enclosure to check burners. Burner flames should be clear blue, almost transpar­ent. (See Fig. 9.)
17. Check for gas leaks.
5
Page 6
INSTALLATION
LEVEL (0")
This appliance requires a special venting system. Refer to the installation instructions for parts list and method of installation.
TO
1/2" MAX
Furnace must be installed level, or pitched forward within 1/2 inch of level for proper drainage. Failure will result in equipment or property damage. See Installation Manual for IMPORTANT unit support details on horizontal applications.
UPFLOW OR DOWNFLOW
FRONT
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
Condensate Trap; Factory
Installed in Blower Shelf
(Blower access panel removed)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING (MOLDED )
DRAIN TUBE (BEHIND
COLLECTOR BOX DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE COUPLING
(LEFT DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
Condensate Trap on
LEFT Side
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX EXTENSION TUBE
CONDENSATE TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
Tube location when used on
HORIZONTAL - LEFT application
AUXILIARY "J" BOX
RELOCATED HERE
PLUG
CAP
CAP
Tube location when used in UPFLOW application
CAP
PLUG
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
CONDENSATE
TRAP
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE COUPLING
(RIGHT DRAIN OPTION)
FIELD-INSTALLED FACTORY-SUPPLIED 1/2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTIO N
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (BLUE)
CONDENSATE
TRAP
Tube location when used in DOWNFLOW application
COLLECTOR BOX
DRAIN TUBE (BLUE)
PLUGGED END
COLLECTOR
BOX DRAIN
TUBE (BLUE
PLUG
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
& WHITE
STRIPED) INDUCER
HOUSING DRAIN
TUBE (VIOLET)
DRAIN TUBE
COUPLING
Tube location when used on
HORIZONTAL - RIGHT application
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR
BOX
EXTENSION
DRAIN TUBE
PLUG
LEVEL (0")
TO
1/2" MAX
FRONT
HORIZONTAL
Condensate Trap on LEFT
Side Optional
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE
Condensate Trap on
RIGHT Side
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX EXTENSION TUBE
CONDENSATE TRAP
COLLECTOR BOX
GAS VALVE
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX EXTENSION TUBE
EXTENSION DRAIN
TUBE
COLLECTOR BOX TUBE (PINK)
CAP
PLUG
(VIOLET)
COLLECTOR
BOX TUBE
COLLECTOR BOX EXTENSION TUBE
CONDENSATE TRAP
EXTENSION DRAIN TUBE
NOTE:
COLLECTOR BOX
COLLECTOR BOX TUBE (PINK) RELOCATE TUBE
BETWEEN BLOWER SHELF AND INDUCER HOUSING
FOR 040,060, AND 080 HEATING INPUT FURNACES
DRAIN TUBE
COUPLING
(GREEN)
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX
DRAIN TUBE
(BLUE)
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
INDUCER HOUSING DRAIN
TUBE (VIOLET)
1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.
3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to prevent a trap. Refer to the Installation Instructions for further details.
322593-101 REV. A
Fig. 8—Furnace Pressure and Drain Tubing Diagram
6
COLLECTOR
BOX
EXTENSION
TUBE
CONDENSATE
TRAP
A96212
Page 7
BURNER FLAME
BURNER
MANIFOLD
A89020
Fig. 9—Burner Flame
Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
18. Replace main furnace door. SECONDARY HEAT EXCHANGERS
NOTE: The condensing side (inside) of the secondary heat exchangers CANNOT be serviced or inspected. A small number of bottom outlet openings can be inspected by removing the inducer assembly. See Flushing Collector Box and Drainage System section for details on removing inducer assembly.
Step 5—Flushing Collector Box and Drainage System
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or
connectors.
4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by loosen-
ing clamp.
6. Disconnect drain tube from inducer housing. (See Fig. 8.)
7. Remove inducer housing assembly by removing 4 bolts
attaching assembly to cell panel.
8. Flush inside of collector box with water until discharge from
condensate trap is clean and runs freely.
NOTE: Ensure the drain tube disconnected from the inducer housing is higher than the collector box opening or water will flow out tube.
9. Inspect inside area of collector box for any pieces of foreign
materials and remove if present.
DO NOT use wire brush or other sharp object to inspect or dislodge materials in secondary heat exchangers as failure of the secondary heat exchanger will occur. Flush with water only.
10. Reassemble inducer assembly by reversing items 5 through 7. NOTE: If seal between the inducer housing and the collector box
is damaged in any way, it must be repaired. To repair, apply sealant releasing agent such as PAM cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated hydrocarbons) to inducer housing. (See Fig. 10.) Apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove in collector box.
PAM
RTV
A93081
Fig. 10—Gasket on Collector Box
11. Refer to furnace wiring diagram and reconnect wires to inducer motor and pressure switch or connectors.
12. Reconnect pressure tubes to pressure switch. See diagram on main furnace door for proper location of tubes. Be sure tubes are not kinked. (See Fig. 8.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through 2 complete heat operating cycles. Check area below inducer housing, vent pipe, and condensate trap to ensure no condensate leaks occur. If leaks are found, correct the problem.
15. Check for gas leaks.
Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death.
16. Replace main furnace door.
Step 6—Servicing Hot Surface Ignitor
The ignitor does NOT require annual inspection. Check ignitor resistance before removal.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect ignitor wire connection.
4. Check ignitor resistance. a. Using an ohm meter, check resistance across both ignitor
leads in connector. b. Cold reading should be between 45 ohms and 90 ohms. c. If ohm reading is higher than 110 ohms, ignitor is cracked
and must be replaced.
5. Remove ignitor assembly.
7
Page 8
Allow ignitor to cool before removal. Normal operation temperatures exceed 2000°F.
a. Do not remove ignitor from retainer while assembly is in
furnace. Using a small pocket straight-blade screwdriver, slowly pry 1 edge of the spring retainer from burner box housing. While working ignitor assembly loose, grasp white ceramic block to wiggle assembly (ignitor and retainer) from its location.
The ignitor is fragile. DO NOT allow it to hit the side of the burner box opening while removing or replacing it.
b. Inspect ignitor for a white area indicating a crack may be
present. If found, replace ignitor.
NOTE: A small crack cannot be seen on a new ignitor. After a period of operation, a white area will be visible around the crack.
c. If replacement is required, replace ignitor on ignitor re-
tainer external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter.
d. To remove ignitor from ignitor retainer, apply pressure on
bottom/side clips to release pressure on ignitor ceramic block. Slowly work ceramic block out of spring retainer.
6. To replace ignitor/ignitor assembly, reverse items 5a through 5d. (See Fig. 11.)
7. Reconnect ignitor wire connection.
8. Turn on gas and electrical supplies to furnace.
9. Verify ignitor operation by initiating control board self-test feature or by cycling thermostat.
10. Replace main furnace door.
13
32
"
BURNER
BURNER BOX
CELL PANEL
IGNITOR ASSEMBLY
7
8
"
IGNITOR ASSEMBLY
11
32
C
L
C
L
"
IGNITOR
BURNER
A93260
Fig. 11—Hot Surface Ignitor Location and Burner
Assembly
Step 7—Electrical Controls and Wiring
There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electrical supplies.
BLK
WHT
WHT
GND
115-VOLT FUSED
DISCONNECT
SWITCH
(WHEN
REQUIRED)
THREE-WIRE
BLK
AUXILIARY J-BOX
FIVE
WIRE
HEATING-
ONLY
GND
CONTROL
BOX
FURNACE
NOTE 2
W
R
G
C Y
24-VOLT
TERMINAL
BLOCK
The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 12 for field wiring information and to Fig. 16 for unit wiring information.
FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING
WCR GY
NOTE 1
THERMOSTAT TERMINALS
CONDENSING
FIELD-SUPPLIED FUSED DISCONNECT
GND
UNIT
TWO WIRE
NOTES: Connect Y-terminal as shown for proper operation.
1.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
Fig. 12—Field Wiring
8
208/230- OR 460-VOLT THREE PHASE
208/230- VOLT SINGLE PHASE
A96415
Page 9
GRYW
24-V THERMOSTAT TERMINALS
TEST/TWIN
3-AMP FUSE
115-VAC (L1)
POWER SUPPLY
HOT SURFACE
IGNITOR CONNECTOR
SEC-1
COOL
HEAT
OM
24V
C
HUM
115-VAC (L2) NEUTRAL CONNECTION
INDUCER MOTOR CONNECTOR
HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX)
LED OPERATION & DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24-V TRANSFORMER SEC-2 SPARE-1 BLOWER SPEED
SELECTION TERMINALS SPARE-2
EAC-1 EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX) EAC-2
Fig. 13—Control Center
A95086
NOTE: If the polarity is not correct, the STATUS LED on the control center will flash rapidly and prevent the furnace from operating. The control system also requires an earth ground for proper operation of the control center and flame sensing.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the control center. (See Fig. 13.) Any direct shorts of the 24-v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a fuse of identical size.
With power to the unit disconnected, check all electrical connec­tions for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are found, disassemble the connection, clean all parts, strip wire, and reassemble properly and securely.
Reconnect electrical supply to unit and observe unit through 1 complete operating cycle. Electrical controls are difficult to check without proper instrumentation; if there are any discrepancies in the operating cycle, contact your dealer and request service.
Step 8—Troubleshooting
For an explanation of status codes, refer to service label located on back of main furnace door or Fig. 17, and the Troubleshooting Guide.
The control center stores 1 status code (representing the last fault to occur) for a period of 48 hr or until the 115- or 24-v power is interrupted.
NOTE: Removing blower access panel will open blower access panel door switch and terminate 115-v power to control center. The status code will be erased. Look into blower access panel sight glass for current LED status BEFORE removing blower access panel.
The unit’s component test is a useful troubleshooting tool since it displays the current status code of the furnace and functionally operates all furnace components except the gas valve. The com­ponent test and methods to initiate it are described below.
COMPONENT TEST SEQUENCE NOTE: All components are functionally operated except the gas
valve. When component test is initiated, the following sequence of events
occurs:
1. LED flashes a status code 4 times.
2. Inducer motor starts and continues to run for remainder of component test.
3. Hot surface ignitor is energized for 15 sec, then de-energized.
4. Main blower operates at cooling speed for 10 sec, then turns off.
5. Main blower operates at heating speed for 10 sec, then turns off.
6. Inducer motor stops.
INITIATING COMPONENT TEST AND RETRIEVING STA­TUS CODE BY REMOVING MAIN LIMIT SWITCH WIRE
NOTE: NO thermostat signal may be present at control center and all blower time delay off periods must be completed.
1. Leave 115-v power to furnace turned on.
2. Remove main furnace door.
3. Look into blower access panel sight glass for current LED status.
9
Page 10
NOTE: Leave blower access panel installed to maintain power to control center to view current LED status.
4. BRIEFLY remove either wire from the main limit switch until the LED goes out, then reconnect it.
Make sure limit switch wire does not contact any metallic component such as the gas valve. If wire is shorted, 3-amp fuse on control center will blow.
NOTE: If wire to main limit is disconnected longer than 4 sec, the control senses limit circuit is open. Main blower will start and retrieval request will be ignored.
5. When above items have been completed, the component test sequence will occur as described in the Component Test Sequence section above.
NOTE: Be sure to record the status code which is flashed 4 times at start of component test for further troubleshooting.
6. After component test is completed and LED is ON continu­ously indicating the furnace is ready to operate when a signal from the thermostat is received, replace main furnace door.
INITIATING COMPONENT TEST AND RETRIEVING STA­TUS CODE BY JUMPERING CONTROL TEST TERMINAL
1. Remove main furnace door.
2. Remove blower access panel.
3. Manually close blower access panel door switch. Use a piece of tape to hold switch closed.
Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in electrical shock, personal injury, or death.
32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
A93058
If this furnace is installed in an unconditioned space where the ambient temperatures may be 32°F or lower, freeze protection measures must be taken.
activated, and it is not practical to verify the actual heating of the tape. Check the following:
1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
Step 10—Winterizing
4. BRIEFLY short (jumper) TEST, 1/4-in. quick-connect termi­nal on control center (adjacent to the LED diagnostic light) and the C
OM terminal on thermostat connection block. (See
Fig. 13.)
NOTE: If TEST to C
OM terminals are jumpered longer than 2 sec,
LED will flash rapidly, and retrieval request will be ignored.
5. When above items have been completed, the component test sequence will occur as described in the Component Test Sequence section above.
NOTE: Be sure to record the status code which is flashed 4 times at start of component test for further troubleshooting.
6. After component test is completed and furnace is operating properly, release blower access panel door switch, replace blower access panel, and replace main furnace door.
Step 9—Checking Heat Tape Operation (If Applicable)
In applications where the ambient temperature around the furnace is 32°F or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it will operate when low temperatures are present.
NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature
Freezing condensate left in the furnace will damage the equipment.
If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32°F or below, winterize as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
3. Disconnect drain tube from inducer housing. (See Fig. 14.)
4. Insert funnel in drain tube and pour antifreeze, propylene glycol (RV, swimming pool antifreeze, or equivalent) into furnace until it is visible at point where condensate enters open drain. (See Fig. 15.)
5. Reconnect drain tube to inducer housing.
6. Replace main furnace door.
Do not use ethylene glycol (Prestone II antifreeze/coolant or equivalent automotive type). Failure of plastic components will occur.
10
Page 11
Fig. 14—Inducer Housing Drain Tube
A94208
A94209
Fig. 15—Funnel in Drain and Antifreeze Running
Through Trap
11
Page 12
TO 115VAC FIELD DISCONNECT
L2
CAP-1
START
SCHEMATIC DIAGRAM
(NATURAL GAS & PROPANE)
EQUIPMENT GROUND
NEUTRAL
L1
NOTE #4
LGPS
(WHEN USED)
PRS
OL
LO
HI
MED LO
MED HI
COM
NOTE #8
COM
COOL
SPARE-1
HI/LO
BLWR
L1
3-P
1-M
BLU
FRS
RED
LS
ILK
HEAT
SPARE-2
YEL
NOTE #6
IDM
BLWM
HSI
1
1
EAC-2
EAC-1
HSIR
GV
NOTE #5
2-C
GRN
RED
FSE
BRN
AUX
OL
M
2
PL52
PL2
IDR
WHT
BLK
BLU
CAP -2
BRN
PL4
1
3
PL3
1
3
PR2
115VAC
TRAN
PR1
GRN
WHT (COM)
BRN
TRAN
RED
OL
LS
2-C
(WHEN USED)
2
FRS
1
CAP -1
START
NOTE #7
FU1
TEST/TWIN
7
SEC-2
SEC-1
GVR-2
HUM
NOTE #12
BRN
BLWM
2
24VAC
NOTE #6
LGPS
PL1
4
HI/LO
BLWR
HSIR
R
W
FUSED DISCONNECT
BLK
WHT
GV
PRS
3-P
1-M
2
3
GVR
IDR
SWITCH (WHEN REQ’D)
JB
GVR-1
CPU
L1
NEUTRAL
NOTE #4
FU2
BLK
GRN
WHT
GRN
ILK
FSE
NOTE #5
8
5
Y
G
PL1 9-CIRCUIT CONNECTOR
9
6
OM
C
PL2 2-CIRCUIT PCB CONNECTOR
PL3 3-CIRCUIT IDM CONNECTOR
PL4 3-CIRCUIT IDM EXTENSION CO NN ECTOR
PL5 2-CIRCUIT HSI/PCB CONNECTOR
AUTO-RESET THERMAL OVERLOAD SWITCHES (OL).
INSTRUCTIONS FOR DETAILS ON OPTIMUM SPEED SELECTION.
FURNACE JUNCTION BOX (JB).
1. IF ANY OF THE ORIGINAL EQUIPMENT WIRE IS REPLACED USE WIRE RATED FOR 105°C.
FLAME.
2. INDUCER (IDM) AND BLOWER (BLWM) MOTORS CONTAIN INTERNAL
3. BLOWER MOTOR SPEED SELECTIONS ARE FOR AVERAGE CONDITIONS, SEE INSTALLATION
4. USE ONLY COPPER WIRE BETWEEN THE DISCONNECT SWITCH AND THE
5. THIS WIRE MUST BE CONNECTED TO FURNACE SHEETMETAL FOR CONTROL TO PROVE
NOTES:
JUNCTION
UNMARKED TERMINAL
PRS PRESSURE SWITCH, SPST-(N.O.)
SW1 & 2 BLOWER OFF DELAY
TEST/TWIN COMPONENT TEST & TWIN TERMINAL
TRAN TRANSFORMER-115VAC/24VAC
6. FACTORY CONNECTED WHEN LGPS NOT USED.
PCB TERMINAL
FACTORY WIRING (115VAC)
FACTORY WIRING (24VAC)
FIELD WIRING (115VAC)
HEAT PUMP 90 SECONDS. (135 SECONDS ONLY ON SOME MODELS)
7. REPLACE ONLY WITH A 3 AMP FUSE.
8. YELLOW LEAD NOT ON ALL MOTORS.
9. BLOWER-ON DELAY, GAS HEATING 60 SECONDS, COOLING OR HEAT PUMP 2 SECONDS.
10. BLOWER-OFF DELAY, GAS HEATING 90, 135, 180 OR 225 SECONDS, COOLING OR
11. IGNITION-LOCKOUT WILL OCCUR AFTER FOUR CONSECUTIVE UNSUCCESSFUL
FIELD WIRING (24VAC)
CONDUCTOR ON PCB
FIELD WIRING TERMINAL
FIELD GROUND
EQUIPMENT GROUND
A95087
322854-101 REV. C
TRIALS-FOR-IGNITION. CONTROL WILL AUTO-RESET AFTER THREE HOURS.
12. SOME MODELS MAY HAVE SPADE QUICK CONNECT TERMINALS.
PLUG RECEPTACLE
Fig. 16—Wiring Diagram
FIELD SPLICE
GRY
SW2
OFF
BLOWER
SEE NOTE #10
PCB
ORN
W
DELAY
SW1
(NOT ON ALL MODELS)
OM
C
HUM
BLOWER OFF DELAY
LED
TEST/TWIN
90 SEC
SELECTION CHART
RED
135 SEC
1 2 3
PL1
180 SEC
WHT
4
5 6
WHT
225 SEC
87 9
SEC-2
SEC-1
GVR
RED (LO)
NOTE #8
YEL (MED HI)
SPARE-1
COOL
SPEED
BLOWER
BLU (MED LO)
SPARE-2
EAC-1
HEAT
L2
SELECT
BLK (HI)
FUSE
24 VAC-3A
FU1
HI/LO
RELAY
HSIR IDR BLWR
PL3
123
PL2
WHT (COM)
1.5 AMP
OM
C
EAC-2
PR2
WHT
WHT GRN
BLK
2
1
PR1
VAC
L1
120
CAP -2
IDM
BRN
AUX
OL
M
BRN
WHT
BLK
GRN PL4 3 2 1
PL5
WHT
BLK BLK
BLK
12
HSI
(FIELD INSTALLED & SUPPLIED)
BLWR BLOWER MOTOR RELAY, SPST-(N.O.)
BLWM BLOWER MOTOR
CAP CAPACITOR
CPU MICROPROCESSOR AND CIRCUITRY
EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.)
EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON)
FRS FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)
FSE FLAME PROVING ELECTRODE
FU1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
FU2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUP T DE VI CE
GV GAS VALVE-REDUNDANT OPERATORS
GVR GAS VALVE RELAY, DPST-(N.O.)
HI/LO BLOWER MOTOR SPEED CHANGE RELAY, SPDT
HSI HOT SURFACE IGNITOR (115 VAC)
HSIR HOT SURFACE IGNITOR RELAY, SPST- (N.O.)
HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.)
IDM INDUCED DRAFT MOTOR
IDR INDUCED DRAFT RELAY, SPST-(N.O.)
ILK BLOWER ACCESS PANEL INTERLO CK SW I TCH, SPST-(N.O.)
JB JUNCTION BOX
LED LIGHT-EMITTING DIODE FOR STATUS CODES
LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.)
LS LIMIT SWITCH, AUTO RESET, SPST(N.C.)
OL AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW.
LEGEND
PCB PRINTED CIRCUIT BOARD
12
Page 13
SERVICE
LED CODE
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at CONTINUOUS ON - Control has 24V power.
RAPID FLASHING - Line voltage (115V) polarity reversed. If twinned, refer to
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE - Stored status codes are erased when power (115V or 24V)
to control is interrupted or 48 hours after each fault is cleared.
12 BLOWER ON AFTER POWER UP (115V or 24V) - Blower runs for 90 seconds,
if unit is powered up during a call for heat (R-W closed).
13 LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Auto reset after three hours.
For flame roll-out switch or fuse link, refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34. 21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Stuck gas valve relay on control or miswire to gas valve circuit.
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared. Check for:
- Stuck-open gas valve or leaky gas valve.
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing. - Defective pressure switch
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for: - Short circuit in secondary voltage (24V) wiring.
31 PRESSURE, DRAFT SAFEGUARD, AUXILIARY-LIMIT (when used), OR
BLOCKED VENT SHUTOFF (when used) SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes
before retry. Check for:
- Proper vent sizing and condensate pitch - Inadequate Combustion air supply. or sag. - Low inducer voltage.
- Vent restriction or high winds. - Disconnected or obstructed
- Defective inducer motor or start capacitor. pressure tubing.
- Defective pressure switch or connections. If it opens after trial for ignition period,
blower will come on for 90 second recycle delay.
33 LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than three
minutes,code changes to #13. Check for:
- Defective blower motor or start capacitor. - Dirty filter or restricted duct system.
- Loose blower wheel. - Defective switch or connections.
- Inadequate Combustion air supply Flame Roll-out Switch or fuse link.
- Open Flame Roll-out switch,or fuse link. Manual reset or replace.
34 IGNITION PROVING FAILURE - Control will try three more times before a lockout
#14 occurs. If flame signal lost after trial for ignition period, blower will come on for 90 second recycle delay. Check for:
- Oxide buildup on flame sensor (clean with fine sandpaper).
- Proper flame sense microamps (.5 microamps D.C. minimum).
- Gas valve turned off. - Manual shut-off valve. - Low inlet gas pressure.
- Green wire MUST be connected to furnace sheet metal.
- Inadequate flame carryover or rough ignition.
SEC-1 and SEC-2.
twinning kit instructions.
COMPONENT TEST
To initiate the component test sequence,shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the ’Com 24V’ terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15 seconds each.
3
6
9
STATUS
8
2
5
1
7
4
TEST
HUM
Fig. 17—Service Label
STATUS
(stuck closed).
Com
W
24V
Y
R
320615-102 REV. H
G
A96263
13
Page 14
NO
Close circuit breaker and
go back to start.
Close door switch and go to start.Is red LED status light on? Is door switch closed?
NO
NO
Troubleshooting Guide
YES
Is circuit breaker closed?
NO
YES
YES
Is there 115v going to switch?
Replace door switch.Replace control center.
NO
Check for continuity in wire from circuit
breaker to furnace.
Replace transformer.
NO
Check room thermostat or
interconnecting cable.
YES
Is 24 vac present at W, Y, or G
terminals on the control?
NO
YES
Does control respond to W, Y,
or G 24-vac thermostat signals?
NO
Replace control if it does not
respond to 24-vac signal at W, Y,
or G screw terminals.
Run system through a heating or
cooling cycle to check operation.
Status codes are erased after 48
hrs or whenever power (115v
or 24v) is interrupted.
YES
Is there 115v at L1 and L2?
Is there 24v at SEC-1 and SEC-2?
NO
YES
START
YES
Check for correct line voltage
polarity. If units are twinned,
check for proper low-voltage 
(24v) transformer phasing.
Check for previous fault by 
momentarily shorting the TEST
terminal and the C terminal until
the LED goes out. LED will flash
YES
NO
NO
Is red LED status light blinking
ON/OFF slowly with a
combination of short and long
Is red LED status light blinking
rapidly without a pause?
flashes?
the status code of any previous
fault or the code No. 11 (1 short
and 1 long flash) if no previous
fault. After the control repeats the
code 3 times, the control will go
through a brief component test
sequence. The inducer will start
and run for the entire component
test. The HSI, blower motor heat
speed, and blower motor cool 
speed will run for 10-15 sec each.
YES
Determine status code. The
status code is a 2 digit number
with the first digit determined by
the number of short flashes and
the second digit by the number of
long flashes.
Once status code is determined,
the control will go through a brief
14
YES
Was there a previous fault code
other than No. 11?
component test sequence. The 
inducer will start and run for the 
entire component test. The HSI,
blower motor heat speed, and 
blower motor cool speed will run
for 10-15 sec each.
Go to section with status code
determined.
Page 15
A96219
Replace control center.
NO
YES
Unplug ignitor harness from control
center and inititate another 
component test sequence. Check
for 115v between pins 1 and 2 on
the control center. Was 115v present
for the 17-sec period?
Check for continuity in the harness
and ignitor. Replace defective
component.
Check connections. If OK, replace
control center.
NO
Reconnect the R thermostat lead
and set thermostat to call for heat.
Connect voltmeter across gas valve
connections. Does gas valve
Check that all gas valves are turned
on. Replace valve.
NO
YES
receive 24v?
YES
Does gas valve open and allow gas
to flow?
NO
rough ignition.
• Low inlet gas pressure.
• Inadequate flame carryover on
Check for:
NO
YES
Do main burners ignite?
Repeat call for heat and check flame
sensor current during trial for ignition
NO
YES
Do main burners stay on?
Allow blower to come on and repeat
Check connections and retry. If 
current is near typical value and
control will not stay on, replace
control center.
YES
period. Is the DC microamps
below 0.5?
test to check for intermittent
operation.
Replace electrode.
NO
Clean flame sensor with fine
sandpaper and recheck current. 
Current is nominally 4.0 to 6.0 microamps.
Is current near typical value?
Replace control center.
NO
YES
YES
Will main burner ignite and stay on?
Fixed.
NOT CLOSE OR REOPEN - If
open longer than 5 minutes,
31 PRESSURE SWITCH WILL
are erased after 48 hrs or
11 NO PREVIOUS FAULT - Faults
sag.
inducer shuts off for 15 minutes
before retry. 
Check for:
• Proper vent sizing or pitch or
• Vent restrictions or high winds.
• Defective inducer motor.
whenever power (115v or 24v) is
interrupted. Run system through
a heating or cooling cycle to 
check system.
connections. If it opens after
trial for ignition period, blower
will come on for 90 sec
recycle delay.
• Low line voltage (115v).
• Motor start capacitor.
• Low inlet gas pressure.
• Defective pressure switch or
UP (115V OR 24V) - Normal 
operation. Blower will run for 90
sec when furnace power is
interrupted during a call for heat,
12 BLOWER ON AFTER POWER
• Inadequate combustion air.
R-W closed.
SWITCH LOCKOUT -
Limit switch was open longer
13 LIMIT OR FLAME ROLLOUT
manual reset.
SWITCH IS OPEN - If 
limit switch is open longer than 3
minutes, code changes to No. 13.
Check for:
33 LIMIT OR FLAME ROLLOUT 
than 3 minutes. Auto-reset will
occur after 3 hrs. Flame rollout
switch requires manual reset.
See No. 33
14 IGNITION LOCKOUT - System
Inadequate combustion air 
• Blower motor failure.
• Motor start capacitor.
• Open flame rollout switch, 
failed to ignite gas and prove
flame in 4 attempts. Control will
auto-reset in 3 hrs.
See No. 34
supply (flame rollout switch
connections.
only).
• Dirty filter.
• Defective limit switch or 
• Loose blower wheel. 34 IGNITION PROVING FAILURE -
wire.
on control.
• Miswire or short to gas valve
• Stuck closed gas valve relay
Turn off power and wait 5
minutes to retry.
Check for:
21 GAS HEATING LOCKOUT - 
If flame is not sensed during the
NO
trial for ignition period, the control
will repeat the ignition sequence
3 more times before going into
lockout, No. 14.
If flame signal is lost after trial for
ignition period, blower will come
on for 90-sec recycle delay.
Check for the following items first
before proceding to the next step.
• Gas valve turned off.
• Manual shut-off valve.
• Green wire must be connected
or leak.
SIGNAL - Flame was sensed
while gas valve was
de-energized. Inducer will run
22 ABNORMAL FLAME PROVING
• Defective control center.
until fault is cleared.
Check for:
• Stuck open gas valve solenoid
to furnace sheet metal.
To determine whether the
problem is in the gas valve,
ignitor, or flame sensor, the
system can be operated in the
component test mode to check
the ignitor. First, remove the
R thermostat connection from the
control center and initiate the
pressure tubing.
• Defective pressure switch.
NOT OPEN - Check for:
• Disconnected or obstructed
23 PRESSURE SWITCH WILL
OPEN - Check for:
• Short in low-voltage wiring
24 LOW-VOLTAGE FUSE IS
YES
component test sequence. Does
the ignitor glow orange/white hot
by the end of the 17-sec warm-up
period?
including thermostat leads
shorting to ductwork or
furnace cabinet. Disconnect
thermostat leads to isolate
short circuit.
15
Page 16
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:  • Unit Familiarization • Maintenance  • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.  Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. 
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
Copyright 1996 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 58mca4sm
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 6a 8a
PC 101 Catalog No. 565-879 Printed in U.S.A. Form 58MCA-4SM Pg 16 11-96 Replaces: 58MCA-3SM
Loading...