Carrier 58GSC User Manual

Page 1
58DRC,58GSC
HEATING A COOLING
Accessory Gas Conversion Kit
Installation Instructions
Gas Conversion Kit
Propane 100% Shutoff IID-To-Natural 100% Shutoff MD
For Gas-Fired Natural-Draft Furnaces
P/N 58GSC900-031-
NOTE: The definition of 100% shutoff refers to automatic
shutoff of the pilot and main burner gas when the ignition source is not proven.
NOTE: Read the entire instructions before starting the
installation. There are additional peirts shipped in the kit. When the installation is complete, discard the unused parts.
A WARNING
This conversion kit is to be installed by a Carrier factory-authorized Dealer, Dis tributor, or other qualified agency in accordance with the manufacturers instructions and all codes and require ments of the authority having jurisdic
tion. A failure to foUow instructions could result in serious injury or property dam age. The qualified agency performing this work assumes responsibility for this conversion.
A CAUTION
Do not use this kit to convert 58DR and 58GS units to natural gas apphcations.
A WARNING
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poison ing, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your Distributor or Branch for information or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when modi fying this product.
New NOx burners must be installed along with this kit. The burners are not supplied with the kit. Order the required number of burners for the furnace being converted. Order burner P/N 309472-751.
This kit contains the following items:
Table 1 —Kit Contents
DESCRiPTiON Naturai Conversion Kit—Reguiator Spring for
White-Rodgers 36E Gas Vaive (Siiver, 10 Turns)
Naturai Regulator Spring for BDP 646A Gas
Valve (Silver, 3-Ins. Long)
Pilot Orifice (Silver, 1/2-ln. Long, 0.018-In.
Orifice Diameter) 307123-701 1 Main Burner Orifice No. 45 Gas Control Conversion Label Conversion Responsibility Label 310167-312 Conversion Rating Plate 310168-312 installation Instructions
P/N
EF39ZW037 1
301248-101 1
LH32DB205 6 310148-302
58D, G-2SI
QTY
1 1 1 1

A. Installation of Pilot Orifice

1. Turn off gas and electric supplies to furnace.
2. Remove control access door.
3. Disconnect pilot gas tube from gas valve.
4. Unplug electrode wire from spark generator.
5. Remove pilot assembly from burner and furnace.
6. Using backup wrench, remove gas supply tube from pilot.
7. Remove and discard propane gas pilot orifice (silver, 5/8-in. long, 0.012-in. diameter orifice, knuHj gas supply opening of pilot.
SECONDARY AIR SHIELD
CONTROL
SHELF
UNIT RATING PLATE
CONVERSION RATING PLATE
MANIFOLD SUPPORT BRACKET
RETAINING SCREWS (2) EACH SIDE
-BURNER
LOCATING PIN
COMPARTMENT

Fig. 1—Gas Controls

MANIFOLD
A80129
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book] 1 I 4 PC 101 Catalog No. 565-817 Printed in U.S.A. Form 58D,G-2SI Pg 1 11-88 Replaces: 58SSB-4SI
Tab 16a 18a
Page 2
8. Install new natural gas pilot orifice (silver, 1/2-in. long,
0.018-in. orifice diameter).
9. Reinstall pilot gas supply tube bn pilot. When tighten ing pilot tube, use backup wrench and turn pilot so that it will be on the same angle as before. Do not rein stall pilot at this time.
B. Installation of Main Burner Orifices
1. Remove secondary air shield.
2. Remove main burners from manifold.
3. Remove and discard No. 55 (or field-installed per local application) orifices from manifold.
4. Install No. 45 main burner orifices provided in kit. Finger-tighten orifices at least one fxill turn so as not to cross-thread, then tighten with wrench. There are enough orifices in each kit for the largest furnace. Dis card extra orifices.
The full input rating with No. 45 main burner natural gas orifices is approved for altitudes up to 2000 ft. The input rating for altitudes above 2000 ft must be reduced by 4% for each 1000 ft above sea level. Consult the current edition of the National Fuel Gas Code NFPA No. 54/ANSI Z223.1, Part 8.1 and Appendix F Table F-4, for input adjustment for high altitude.
5. Install new burners with N0^ reduction screens on manifold. See Figs. 2 and 3 for proper orientation of burners and pilot.
6. Reinstall pilot assembly.
7. Reconnect pilot supply tube to gas valve.
8. Reconnect electrode wire to spark generator.
9. Reinstall secondary air shield.
C. Conversion of Gas Valve and Inlet Gas Pressure Check
1. Remove regulator seal cap. See Fig. 4 for BDP 646A or Fig. 5 for White-Rodgers 36E Gas Valve.
2. Remove adjustment screw and propane gas regulator spring (red for 646A and white for 36E).
3. Install proper natural gas regulator spring (silver) pro vided in kit, in proper gas valve. See Table 1.
4. Replace regulator adjustment screw. Do not reinstall regulator seal cap at this time.
5. Remove 1/8-in. pipe plug from inlet pressure tap on gas valve.
REGULATOR
Fig. 2—Pilot/Burner Relationship
Fig. 3—Position of Pilot Electrode to Pilot
A88463
-REGULATOR SEAL CAP
Fig. 5—White-Rodgers Model 36E Gas Valve
Page 3
6. Check inlet natural gas pressure.
NOTE: This kit is to be used only when inlet gas pressure is
between 4.5- and 13.6-ins. wc.
a. Attach manometer at inlet pressure tap on gas sup
ply side of furnace gas valve.
A CAUTION
Do not operate furnace more than one minute to check inlet gas pressure as conversion is not complete at this time.
b. Set room thermostat “call for heat.”
c. Turn gas supply manual shut-off valve on.
d. Turn furnace gas valve control knob to ON.
e. Turn electrical supply to ON.
f. When main burners have ignited, confirm proper
inlet gas pressure. g. Turn furnace gas valve control knob to OFF. h. Turn gas supply manual shut-off valve off.
i. Turn electric supply to furnace to OFF.
j. Remove manometer and replace plug in pressure
tap.
NOTE: Use propane gas-resistant pipe dope. Do not use
Teflon tape.
7. Attach gas control conversion label P/N 310148-302 to cell panel.
8. Attach conversion rating plate P/N 310168-312 near
existing rating plate. See Fig. 1.
D. Check Furnace Operation and Make Necessary
Adjustments
1. Be sure main gas and electric supplies to furnace are off.
2. Attach manometer at manifold pressure tap on down
stream side of gas valve.
3. Set room thermostat to “caU for heat.”
A WARNING
Never use a match or other open flame to check for leaks. Use a soap-and-water solution. A failure to heed this warning could result in personal injury or death.
4.
Turn gas supply manual shut-off valve on and check inlet pressure tap plug for leaks.
5.
Turn furnace gas valve control knob to ON and check all threaded pipe connections for gas leaks.
6.
Turn on electrical supply.
7. When pilot ignites, check pilot gas-supply tube connec tions for leaks. When main burners ignite, check mani fold orifices for gas leaks.
8. Determine gas input:
a. Turn off all other gas appliances and pilots.
b. Measure time (in seconds) for gas meter test dial to
complete one revolution.
c. Refer to Table 2 for cubic ft of gas per hour.
d. Multiply cubic ft/hour by Btu cubic ft. Obtain heat
ing value from local gas utihty.
NOTE: Be sure heating value of gas used for calculations is
correct for your altitude. Consult local gas utility for alti tude adjustment of gas heating value.
High altitude: The full input rating with No. 45 main burner natural gas
orifices is approved for altitudes up to 2000 ft. The input rating for altitudes above 2000 ft must be reduced by 4% for each 1000 ft above sea level. Consult the current edition of the National Fuel Gas Code NFPA No. 54/ANSI Z223.1, Part 8.1 and Appendix F Table F-4, for input adjustment for high altitude.
e. Refer to unit rating plate for gas input rate. The
measured input must be within 2 percent of the rat ing plate input.

EXAMPLE:

Btuh heating input = Btu/cubic ft times cubic ft/ hour
Heating value of gas = 1070 Btu/cubic ft. Time for one revolution of 2-cubic-ft dial = 72
seconds Gas rate = 100 cubic ft/hour (from Table 2)
Btu heating input = 1070x 100 = 107,000 Btuh
9. To adjust input rate: a. Remove cap that conceals adjustment screw for gas
valve regulator.
b.
Turn adjustment screw either counterclockwise (out) to decrease input or clockwise (in) to increase rate. When adjusting input rate, do not set manifold
pressure above 3.8 or below 3.2-ins. wc. Make
any major adjustments by changing main burner
orifices.
Table 2—Gas Rate (Cubic Ft/Hour)
Seconds
for One 1
Revolution cu ft
10 360 11 12 13 277 14 257 15 240 16 225 17 18 19
20 21 171 22 23 157 24 25 144 26 27 28 129 29 124 30 120
31 116
32 33 109 34
35
36 100 37
38 95 39 92 40 41 42 43 84 44 45 80 46 78 47 48 49
SIZE OF TEST DIAL
2 5
cu ft
cu ft
720 1800 50 ' 72 144 360
327
655 1636
300
600 1500 555 1385 53 68 136 340 514 1286 54 67 480 1200 55 65 131 327 450 1125
212
424 1059
200 189 379 947 59 61 122 305 180
164 150 138
133 267 667 74 48 97 243
113 225 563 84 43 86 214
106 103
97
90 88, 86
82
76 75 73 147 367
1000 58 62
400 360
343 327 818 313 300 288 277
257 643 76 47 248 621 78 46 92 240 600 80 45 90 225 232
218 545 86 42 84 209 212 529 88 41 82 205 206 514 90 40 200 500 92 39 195 486 94 38 189 474 96 185 462 98 37
450
180 176 439 102 35 71 178 172 429 104 35 167 419 106 34 164 409 108 33 67 167 160 400 110 33
157 391 112 32 64 161
383 116 31
153
375 120
150
Seconds SIZE OF TEST DIAL
for One
Revolution cu ft cu ft CU ft
51 71 52
56 64 57
900 60 60 857 62 58
783 66 54 750 68 53 720 70 51 692 72 50
581 82 44
64 56
100
69 138 346
63 126
38 75 188 36
30 60 150
1 2 5
141 355
133 129 124 120
116 112
109 106 103 100
95
88
80 78 76
74
72 180 69
68 65 62 155
333 321
316 310
300 290 281 273 265 257 250
237 231
220
200 196 192
184
173 170
164
Page 4
c. Measure adjusted gas input rate using method out
lined in step 8.
d. Replace regulator adjustment screw seal cap.
10. Inspect burner and pilot flame. The main burner flame should be clear blue, almost transparent. The pilot flame should be soft blue in color and it must provide good impingement on the pilot-sensing element. The
flame should extend above the burner carryover port to provide proper burner ignition. See Figs. 2 and 3. When the pilot flame requires adjustment:
a. Locate adjustment screw marked PILOT ADJ on
top of gas valve. See Figs. 4 and 5.
b. Remove cap and turn adjustment screw clockwise
to decrease pilot gas flow. Turn screw counter clockwise to increase pilot gas flow.
c. When proper adjustment is obtained, replace screw
cap.
11. Turn furnace gas valve control knob to OFF.
12. Remove manometer and replace manifold pressure tap plug.
13. Turn furnace gas valve control knob to ON.
14. With main burners ignited, check pressure tap plugs for gas leaks.
E. Check Lockout Timer Module (LOD) Operation
1. Turn off electrical supply.
2. With furnace off, remove wire from terminal No. 5 of gas valve.
3. Set room thermostat to “call for heat.”
4. Turn on electrical supply.
5. Let pilot spark until lockout timer breaks spark genera tor circuit (approximately 5 minutes).
6. Replace wire on terminal No. 5 of gas valve.
' 7. Electrically reset lockout timer by setting room ther
mostat below room temperature for approximately 30 seconds.
8. Sign and date conversion label P/N 310167-312 pro vided in kit, and attach to outside of blower compart ment door.
9. Replace control access door.
10. Reset room thermostat to desired temperature.
During normal operation, if the pilot flame is not proven within approximately 5 minutes, the lockout timer opens, deenergiziug the gas valve, and stopping the gas flow to the pUot. The lockout timer will remain open until it is electri cally reset.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
B°°k| 1 I 4 PC 101 Catalog No. 565-817 Printed in U.S.A. Form 58D,G-2SI Pg 4 11-88 Replaces: 58SSB-4SI
Tab I6al8a
Loading...