NOTE: Read the entire instructions before starting the
installation.
INTRODUCTION
Before installing the furnace, refer to “Procedures for
Natural-Draft Gas-Fired Furnaces” (packaged with the
equipment) for information concerning combustion, venting,
piping, and other standeird installation practices. Further
reference is made to the current edition of the National Fuel
Gas Code NFPA No. 54-1988/ANSI Z223.1-1988.
Reference should also be made to the regulations of the
serving gas supplier and the local building, heating, plumb
ing, or other codes in effect in the area in which the installa
tion is made.
SAFETY CONSIDERATIONS
Installation and servicing of heating equipment can be haz
ardous due to gas and electrical components. Only trained
and qualified personnel should install, repair, or service
heating equipment.
Untrained personnel can perform basic meuntenance func
tions such as cleaning and replacing air filters. AU other
operations must be performed by trained service personnel,
when working on heating equipment, observe precautions in
the literature, tags, and labels attached to or shipped with
the unit and other safety precautions that may apply.
Follow all safety codes, including NFPA No. 54/ANSI
Z223.1-1988, National Fuel Gas Code. Wear safety glasses
and work gloves. Have fire extinguisher available during
startup and adjustment procedures and service call.
Recomized safety information: This is the safety-alert sym
bol A. When you see this symbol on the furnace and in
instructions or manueils, be alert to the potential for per
sonal injury.
Understand the signal word—DANGER, WARNING, or
CAUTION. These words are used with the safety-alert sym
bol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING
on the other hand could result in personal injury or death.
CAUTION is used to identify unsafe practices, which would
result in minor personal injury or product and property
damage.
Each furnace is shipped from the factory completely assem
bled with multispeed direct-drive blower and wired ready for
downflow indoor heating installation only. AU sizes feature
a printed-circuit board control center with easy-to-read, 24volt terminal strip to ensure proper connections.
Fig. 1—Model 58DP
Table 1—Clearances (In Inches)
(From Combustible Materials)
Sizes
Sides—Single-Wall Vent
Type-B Double-Wall Vent0
Back00
Top of Plenum1
Vent Connector—Single-Wall66
Type-B Double-Wall
Front—Combustion Air*66
Service
*The 6-inch front clearance is needed for combustion-air entry and
drafthood relief.
»■NOTE: The furnaces covered by these instructions are
050075 thru 150
11
1
1
11
3030
design-certified for use with the vent damper specified on
the furnace rating plate. See instructions packaged with the
vent deunper for its installation.
A CAUTION
Application of this furnace should be indoors with spe
cial attention given to vent sizing and material, gas
input rate, air temperature rise, and unit sizing.
Improper installation or misapplication of the furnace
can require excessive servicing or cause premature com
ponent failure.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
'' I ^ PC 101 Catalog No. 565-873 Printed in U.S.A. Form 58DP,DR-4Si 5/89 Pg 1 Replaces: 58DP,DR-2SI
*The above gas input ratings are certified for eievations to 2000 ft. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea ievei.
tDetermined by U.S. Government tests.
tDeduct 1000 Btuh for Modei58DR. , ' ;
♦These dimensions appiy when a Model 28RC or RD Evaporator Coil cas
ing is to be installed.
13%
167,6
237,6
19=/s197,6
19%
19%
. 197,6
197,6
197,6
This furnace is designed for a minimum continuous return
air temperature of 60 degrees F DB or an intermittent oper
ation down to 55 degrees F DB such as when used with a
thermostat night setback. Return air temperature must not
exceed a maximum of 85 degrees F DB.
A WARNING
Improper histaUation, adjustment, alteration, service,
maintenance, or use can cause carbon monoxide poison
ing, explosion, fire, electrical shock, or other conditions
which may cause personal injury or property damage.
Consult a qualified installer, service agency, local gas
supplier or your Distributor or Branch for information
or assistance. The qualified installer or agency must use
only factory authorized and listed kits or accessories
when modifying this product. A failure to adhere to this
warning can cause electrical shock, fire, personal injury,
or death.
FURNACE
■PLENUM
A73383
Fig. 4—Furnace on a Concrete Siab
WA
Fig. 5—Furnace, Plenum, and
Base Installed on a Combustible Floor
A CAUTION
Do not insteill furnace in a damp, corrosive, or contami
nated atmosphere. Make sure all combustion and circu
lating air requirements listed in “Procedures for
Natured-Draft Gas-Fired Furnaces” are adhered to, in
addition to all local codes and ordinances.
Do not use this furnace during construction when adhe
sives, sealers and/or new carpets are being installed. If
the furnace is required during construction, use clean
outside air for combustion and ventilation. Compounds
of chlorine and fluorine when burned with combustion
air form acids which wiU cause corrosion of the heat
exchangers and metal vent system. Some of these com
pounds are paneling and dry wall adhesives, paints,
thinners, masonry cleaning materials, and many other
solvents commonly used in the construction process.
*IV. Venting
V. Supply-Air Plenum Installation
VI. Electrical
VII. Sequence of Operation
VIII. Füter
IX. Startup and Adjustment
X. Care and Maintenance
*To perform these sections (or installation steps), refer to
the appropriate sections of “Procedures for Natural-Draft
Gas-Fired Furnaces” booklet packaged with this unit.
For accessory installation details, refer to the applicable
installation hterature. Terminals EAC-1 and EAC-2 in the
control box are for direct connection of an electronic air
cleaner.
V. SUPPLY-AIR PLENUM INSTALLATION
A. Installation on a concrete slab
1. See Fig. 2 for dimensions and location of supply-air
opening in furnace bottom.
2. Construct hole in floor per dimensions in Fig. 3 and
Table 4.
3. Place plenum and furnace as shown in Fig. 4.
The design of the downflow gas-fired furnace is A.G.A. cer
tified for installation on noncombustible flooring. The fur
nace may be installed on combustible flooring when
installed with the accessory downflow subbase. This furnace
is for installation in alcoves, basements, closets, or utility
rooms. This furnace fine is not A.G.A. design certified for
installation in a mobile home, recreation vehicle, or
outdoors.
Installation comprises the following:
*1. Inspection
*11. Location, Ventilation, and Air for Combustion
*III. Gas Piping
Fig. 6—Amp Draw Check With Ammeter
A79077
Fig. 7—PrInted-CIrcult Control Center
- FIELD24-VOLTWIRlNC
FUSED DISCONNECT
SW ITCH (WHEN REQ'D)
CAP
(WHEN USED)
ILK SWITCH
TRAN
BREAKAWAY TAB REMOVED WHEN CONNECTING VENT DAMPER (SEE INSTALLATION INSTRUCT IONS)-
NOTES:
m DOWNFLOW FURNACES ONLY
I.
I
----
rz—I HEATING FAN RELAY CONTACT IS
•-rkF* NORMALLY CLOSED UNTIL 115V AC IS
HFR APPLIED TO FURNACE.
TO CHANGE MOTOR SPEED, MOVE RED WIRE TO
2.
DESIRED SPEED SETTING.
IF ANY OF ORIGINAL WIRE AS SUPPLIED WITH
3.
THE APPLIANCE MUST BE REPLACED, IT MUST
BE REPLACED WITH AWM C105°C) WIRE OR ITS
EQUIVALENT.
MOTOR IS THERMALLY OVERLOAD PROTECTED.
4.
FACTORY SPEED SELECTION IS FOR AVERAGE
5.
CONDITIONS, SEE INSTALLATION INSTRUCTIONS
FOR OPTIMUM SPEED SELECTION. MOTOR MAY
BE 3 OR 4 SPEED.
SYMBOLS ARE ELECT. REPRESENTATION ONLY.
6.
FACTORY CONNECTED WHEN ACCESSORY NOT USED.
7.
LEGEND
ALS
CAP
CFR
FL
FU2
GV
HFR
ILK
LOD
LS
MTR
PCB
PI
SP
TRAN
VSS5
/fy
AUXILIARY LIMIT SWITCH, MANUAL-RESET
C5PST-NC)
RUN CAPACITOR
COOLING FAN RELAY CDPDT
FUSIBLE LINK
FIELD FUSE
GAS VALVE
HEATING FAN RELAY CSPST-NC)
SWITCH, BLOW. DOOR INTERLOCK CSPST-NO)
LOCKOUt TIMER DEVICE CSPST-NO)
LIMIT SWITCH, AUTO.-RESET CSPST-NC)
MOTOR, BLOWER
PRINTED CIRCUIT BOARD
PILOT IGNITER
SAFETY PILOT (FLAME SENSING)
TRANSFORMER
VENT SAFETY SHUTOFF SWITCH, MANUAL-
RESET CSPST-NC)
FIELD SPLICE
PLUG RECEPTACLE
JUNCTION
UNMARKED TERMINAL