Carrier 58DR User Manual

58DP,DR

HEATING« COOLING

Downflow Gas-Fired Natural-Draft Furnaces

58DP Series 150 and 160
58DR Series 130
Installation, Start-Up and Service Instructions
NOTE: Read the entire instructions before starting the
installation.
Before installing the furnace, refer to “Procedures for Natural-Draft Gas-Fired Furnaces” (packaged with the equipment) for information concerning combustion, venting, piping, and other standeird installation practices. Further reference is made to the current edition of the National Fuel Gas Code NFPA No. 54-1988/ANSI Z223.1-1988.
Reference should also be made to the regulations of the
serving gas supplier and the local building, heating, plumb ing, or other codes in effect in the area in which the installa tion is made.
SAFETY CONSIDERATIONS
Installation and servicing of heating equipment can be haz ardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic meuntenance func tions such as cleaning and replacing air filters. AU other operations must be performed by trained service personnel, when working on heating equipment, observe precautions in the literature, tags, and labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes, including NFPA No. 54/ANSI
Z223.1-1988, National Fuel Gas Code. Wear safety glasses and work gloves. Have fire extinguisher available during startup and adjustment procedures and service call.
Recomized safety information: This is the safety-alert sym bol A. When you see this symbol on the furnace and in instructions or manueils, be alert to the potential for per sonal injury.
Understand the signal word—DANGER, WARNING, or CAUTION. These words are used with the safety-alert sym bol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING
on the other hand could result in personal injury or death.
CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Each furnace is shipped from the factory completely assem bled with multispeed direct-drive blower and wired ready for downflow indoor heating installation only. AU sizes feature a printed-circuit board control center with easy-to-read, 24­volt terminal strip to ensure proper connections.
Fig. 1—Model 58DP
Table 1—Clearances (In Inches)
(From Combustible Materials)
Sizes Sides—Single-Wall Vent
Type-B Double-Wall Vent 0 Back 0 0 Top of Plenum 1 Vent Connector—Single-Wall 6 6
Type-B Double-Wall
Front—Combustion Air* 6 6
Service
*The 6-inch front clearance is needed for combustion-air entry and
drafthood relief.
»■NOTE: The furnaces covered by these instructions are
050 075 thru 150
1 1
1
1
1 1
30 30
design-certified for use with the vent damper specified on the furnace rating plate. See instructions packaged with the vent deunper for its installation.

A CAUTION

Application of this furnace should be indoors with spe cial attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause premature com ponent failure.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
'' I ^ PC 101 Catalog No. 565-873 Printed in U.S.A. Form 58DP,DR-4Si 5/89 Pg 1 Replaces: 58DP,DR-2SI
Tab I6al8a
8 THERMOSTAT CONN
/
Table 2—Dimensions (In Inches)
A
14^6 12"/,e 12”/,6 17^2
M'k M'b
17Ya
21 19%
2A'k
1
5. ^
r'
— -?>•
o:a
KNOCKOUT AUX GAS
INLET
AIRFLOW
Size
050-BA 075-AA 075-BA 100-AA 100-BA 125-AA 21 19% 125-BA 150-BA
A78595

Fig. 2—Dimensional Drawing

Table 3—Ratings and Performance
Size 050-BA 075-AA
075-BA 100-AA 100-BA 125-AA 125-AA
150-BA
*The above gas input ratings are certified for eievations to 2000 ft. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea ievei. tDetermined by U.S. Government tests. tDeduct 1000 Btuh for Modei58DR. , ' ;
input
Btuh* 50,000 39,000t
75,000 58,000
100,000 78,000t
125,000 97,000t
150,000 116,000t
Capacity
Btuht*
Temp
Rise
Range
45—75 0.50 70—100 0.12 45—75 0.50 70—100 0.20 60—90 0.50 70—100 0.20 60—90 0.50
55—85 , 0.50
Ext Static
Pressure
Heating
CFM
600 0.5 630 895 850
960 1050 1195 0.5 1535
Ext Static
Pressure
0.5
0.5 1630 %-PSC
0.5 2075
Cooling
D E Vent
15^
15% 15% 15%
22%e
CFM
800 73-SP 129
1255 %-SP 157
1620 %-PSC 187
16 16 16 5 16 5
19Ya
19% 5
23 6
Motor
HP&
Type
%0-SP 148
Vs-SP 163
%-SP
Ya-PSC 227
Approx
Shipping
Weight
4 4 4
5
170 187
A73382
Fig. 3—Floor Opening for
Concrete Slab

Table 4—Opening Dimensions

Furnace Casing A B
Width Heat-Only Heat/Cool* 14%s
17%
21 19% 19%
24%
♦These dimensions appiy when a Model 28RC or RD Evaporator Coil cas
ing is to be installed.
13%
167,6
237,6
19=/s 197,6
19%
19%
. 197,6
197,6 197,6
This furnace is designed for a minimum continuous return air temperature of 60 degrees F DB or an intermittent oper ation down to 55 degrees F DB such as when used with a thermostat night setback. Return air temperature must not exceed a maximum of 85 degrees F DB.

A WARNING

Improper histaUation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poison ing, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier or your Distributor or Branch for information or assistance. The qualified installer or agency must use only factory authorized and listed kits or accessories when modifying this product. A failure to adhere to this warning can cause electrical shock, fire, personal injury, or death.
FURNACE
■PLENUM
A73383
Fig. 4—Furnace on a Concrete Siab
WA
Fig. 5—Furnace, Plenum, and
Base Installed on a Combustible Floor

A CAUTION

Do not insteill furnace in a damp, corrosive, or contami
nated atmosphere. Make sure all combustion and circu lating air requirements listed in “Procedures for Natured-Draft Gas-Fired Furnaces” are adhered to, in addition to all local codes and ordinances.
Do not use this furnace during construction when adhe sives, sealers and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which wiU cause corrosion of the heat exchangers and metal vent system. Some of these com pounds are paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process.
*IV. Venting
V. Supply-Air Plenum Installation
VI. Electrical
VII. Sequence of Operation
VIII. Füter
IX. Startup and Adjustment
X. Care and Maintenance
*To perform these sections (or installation steps), refer to the appropriate sections of “Procedures for Natural-Draft Gas-Fired Furnaces” booklet packaged with this unit.
For accessory installation details, refer to the applicable installation hterature. Terminals EAC-1 and EAC-2 in the control box are for direct connection of an electronic air cleaner.
V. SUPPLY-AIR PLENUM INSTALLATION
A. Installation on a concrete slab
1. See Fig. 2 for dimensions and location of supply-air opening in furnace bottom.
2. Construct hole in floor per dimensions in Fig. 3 and Table 4.
3. Place plenum and furnace as shown in Fig. 4.
The design of the downflow gas-fired furnace is A.G.A. cer tified for installation on noncombustible flooring. The fur nace may be installed on combustible flooring when installed with the accessory downflow subbase. This furnace is for installation in alcoves, basements, closets, or utility rooms. This furnace fine is not A.G.A. design certified for installation in a mobile home, recreation vehicle, or outdoors.
Installation comprises the following:
*1. Inspection
*11. Location, Ventilation, and Air for Combustion
*III. Gas Piping
Fig. 6—Amp Draw Check With Ammeter
A79077
Fig. 7—PrInted-CIrcult Control Center
- FIELD24-VOLTWIRlNC
FUSED DISCONNECT
SW ITCH (WHEN REQ'D)
CAP
(WHEN USED)
ILK SWITCH
TRAN
BREAKAWAY TAB REMOVED WHEN CONNECTING VENT DAMPER (SEE INSTALLATION INSTRUCT IONS)-
NOTES:
m DOWNFLOW FURNACES ONLY
I.
I
----
rz—I HEATING FAN RELAY CONTACT IS
•-rkF* NORMALLY CLOSED UNTIL 115V AC IS HFR APPLIED TO FURNACE.
TO CHANGE MOTOR SPEED, MOVE RED WIRE TO
2. DESIRED SPEED SETTING. IF ANY OF ORIGINAL WIRE AS SUPPLIED WITH
3. THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH AWM C105°C) WIRE OR ITS EQUIVALENT.
MOTOR IS THERMALLY OVERLOAD PROTECTED.
4. FACTORY SPEED SELECTION IS FOR AVERAGE
5.
CONDITIONS, SEE INSTALLATION INSTRUCTIONS FOR OPTIMUM SPEED SELECTION. MOTOR MAY BE 3 OR 4 SPEED.
SYMBOLS ARE ELECT. REPRESENTATION ONLY.
6.
FACTORY CONNECTED WHEN ACCESSORY NOT USED.
7.
LEGEND ALS
CAP CFR FL FU2 GV HFR
ILK LOD LS MTR PCB PI SP TRAN VSS5
/fy
AUXILIARY LIMIT SWITCH, MANUAL-RESET
C5PST-NC) RUN CAPACITOR COOLING FAN RELAY CDPDT FUSIBLE LINK FIELD FUSE GAS VALVE HEATING FAN RELAY CSPST-NC) SWITCH, BLOW. DOOR INTERLOCK CSPST-NO) LOCKOUt TIMER DEVICE CSPST-NO) LIMIT SWITCH, AUTO.-RESET CSPST-NC) MOTOR, BLOWER PRINTED CIRCUIT BOARD PILOT IGNITER SAFETY PILOT (FLAME SENSING) TRANSFORMER VENT SAFETY SHUTOFF SWITCH, MANUAL-
RESET CSPST-NC)
FIELD SPLICE PLUG RECEPTACLE JUNCTION UNMARKED TERMINAL
O
TERMINAL PCB FACTORY CONN. FACTORY WIRING. C120V AC)
FACTORY WIRING CLOW VOLTAGE) FIELD WIRING C120V AC)
FIELD WIRING C24V AC) CONDUCTOR ON PRINTED CIRCUIT BOARD
SCREW TERMINAL FOR FIELD WIRING
0
FIELD GROUND EQUIP. GROUND
TO THERMOSTAT
314296-401 REV. A

Fig. 9—Wiring Diagram (IID Pilot)

YEL
LOD-
CWHEN USED)
ELECTRONIC
AIR CLEANER
(WHEN USED)
EAC-2
A89168
Loading...
+ 8 hidden pages