Carrier 52SE, 52SC, 52SQ Installation, Operating And Maintenance Instructions

Page 1
52S
52S
SERIES
SERIES
INSTALLATION, OPERATING
AND MAINTENANCE INSTRUCTIONS
PACKAGED TERMINAL AIR CONDITIONERS
7,000-14,000 Btuh
CONTENTS
GENERAL UNIT INSPECTION ELECTRIC A L DATA
ALL UNITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
VOL TAGE SUPPLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LOW-VOLTAGE CO N NECTIONS — REMOTE CONTROL AND ENERGY
MANAGEMENT ACCESSORY . . . . . . . . . . . . . . . . . . 4
INSTALLATION
SLEEVE IN STALLATION REQUIREM ENTS . . . . . . . 5
ACCESSORY INSTALLATION . . . . . . . . . . . . . . . . . . . 9
ADJUSTMENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-11
Page
OPERATING INSTRUCTIONS
SWITCH SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
OPERATING CONTROLS . . . . . . . . . . . . . . . . . . . . . . 13
CARE AND MAINTENANCE
AIR INLET FIL TER . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OUTDOOR VENT FILTER . . . . . . . . . . . . . . . . . . . . . . 14
EXTERNAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
INTERNAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
ACCESSORIES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
. . . . . . . . . . . . . . . . 12-13
. . . . . . . . . . . . . . . . . 13-17
1•800•894•6449
For Service/
Technical Assistance
Page
Page 2
52S
SERIES
GENERAL
These installati on instructions provide easy-to­understand information for installing, operating, and maintaini ng these packaged air cond itio n er s and he at pumps. The following models are covered in this book:
52SC Cooling only . . . . . . . . . . . . . . . . . . . . . . . . .60 Hz
52SE Cooling with electric heat . . . . . . . . . . . . . . 60 Hz
52SQ Cooling, electric heat, and heat pump . . . .60 Hz
All models are designed for through-the-wall instal­lation. Separate install a tion instructions are inc lud ed with all accessory comp onent s.
UNIT INSPECTION
Examine unit for dam age inc ur red d uri ng sh ip m e nt. File a claim immediately with the transit company if damage is found.
The data information plate (Fig ur e 1) lists the model number, volta ge ranges, and other important el ectrical information about this produc t. Readin g and und er­standing this material is important for proper use of this unit. To access th e infor m ation plate, the front panel must be removed; see Figure 2.
To remove the front panel:
1. Grasp panel firmly near top of both sides.
2. Pull panel up the n forw ard. IMPORTANT: The front panel has to be off the unit
to complete futu re ch eck s and installation proce­dures. Do not reinstall front panel at this time.
FIGURE 1 — SA MP LE DATA
INFORMATION PLATE
Using Figures 1 and 3 as reference, verify that the packaged termi nal pro duc t or de red will o perate p rop ­erly in your facility. If you do not understand the in­formation given or have questions about the product, please call your lo cal de aler o r distr ibutor.
FIGURE 2 — REMOVING FRONT PANEL
2
Page 3
FIGUR E 3 — MODEL NUM B ER NOMENCLATURE
ELECTRICAL DATA
ALL UNITS
ELECTRICAL SHOCK HAZARD
DO NOT alter cord or plug, and DO NOT us e an extension cord. Personal injury or damage to the unit may resu lt.
Be sure that your outlet matches the appropria t e blade configuration of the supplied plug and that it is within reach of the se rvice cord. A ha rd w ire kit is available as an accessory to change cord-con nect ed units to hardw ire d units. The junc tio n b ox ca n b e mounted with manu fact urer ’s non-e lectr ic su bbase ac­cess ory. (See A ccess o ries s ection, pa ge 18.)
IMPORTANT : All packaged termin al 265-v un its can either be hardwired or cord-connecte d with accessory kits. Both accessories must be purchased separately through your order correspondent.
WIRE SIZE —
Use recommended wire size given in Table 1 and install a single branch circuit. All wiring must comply with loca l and national codes. All units
are designed to operate off single branch cir­cuits only.
NOTE: Use coppe r conductors onl y.
GROUNDING
— For safet y an d protec tio n, th e uni t is grounded thr o ugh the service co rd p lug o r th ro ugh separate ground wir e pr ov i ded on hardwired units. Be sure that the branch circuit or general purpose outlet is grounded.
TABLE 1 — SUGGESTED BRANCH CIRCUIT
WIRE SIZES*
NAMEPLATE AMPS AWG WIRE SIZE
7.0 to 12
12.1 to 16
16.1 to 24
LEGEND
AWG —
*Single circuit from main box. †Based on copper wire at 60 C temperature rating.
American Wire Gage
14 12 10
3
Page 4
52S
SERIES
VOLTAGE SUPPLY
Check voltage supply at outlet. For satisfactory re­sults, the voltag e range must al way s be within the ranges found on the data information plate (Figure 1).
208/230-v CORD-CONNECTED UNITS
supplied outlet must match the plug and be within reach of the service cord. Refer to Table 2 for proper receptacle and fuse type.
TABLE 2 — RECEPTACLES AN D FUSE TYP ES,
250 VOLTS
RATED VOLTS 250
AMPS
BLADE CONFIGURATION
MFG PART NO.
Hubbell P & S GE Arrow-Hart
TIME-DELAY TYPE FUSE
(or HACR Circuit Breaker)
LEGEND
HACR —
*May be used for 15-amp applications if fused for 15 amp.
Heating, Air Conditioning, Refrigeration
265-v ACCESSOR Y CORD-CONNECTED UNITS —
15 20 30
5661 5461 8330 5661 5871 5930
GE4069-1 GE4182-1 GE4139-3
5661 5861 5700
15 20* 30
The field-supplied outlet must match the plug and be within re ac h of the servi ce cord. Refer to Ta ble 3 for the proper receptacle and fuse type.
TABLE 3 — RECEPTACLES AN D FUSE TYP ES,
265 VOLTS
— The field-
FIGURE 4 — SUBBA SE ASSEMBLY
LOW-VOLTAGE CONNECTIONS — REMOTE CONTROL AND ENERGY MANAGEMENT ACCESSORY
Energy Man a ge m e nt Ac ce ss o ry m ust be ordered sep a ­rately and field-installed. Low-vo ltag e con nect io ns must be made fo r Energy Management Units . Refer to page 10.
Remote control units are supplied with a low-voltage termin a l b o a rd f o r direct int e rf a c e w i th a f ield­supplied low-voltage, manual changeover thermo­stat or a programmable thermostat (both are Manufacturer-recommended). When properly wired, the unit operation is cont rolled by either wall-mou nted thermostat.
RATED VOLTS 265
AMPS 15/20 30
BLADE CONFIGURATION
MFG PART NO.
Hubbell Eagle
TIME-DELAY TYPE FUSE
(or HACR Circuit Breaker)
LEGEND
HACR —
*May be used for 15-amp applications if fused for 15 amp.
Heating, Air Conditioning, Refrigeration
—9315
834B-BOX
20*
IMPORTANT: The 265-v cord-connected units re­quire an accessory subbase, Part No. SUB-BASE, with a field-installed receptac le . See Table 3 and Figure 4.
30
4
Page 5
INSTALLATION
SLEEVE INSTALLATION REQUIREMENTS
Reminder: Units are shipped with out sleeve.
INSPECT WALL SLEEVE INSTALLATION
replacement or retr ofit situation, it is recom m end ed that a sleeve be used with a chassis from the same manufac tu rer. R efer to Figu re s 5 a nd 6 f or t y pica l w all installation and uni t dime n sio ns.
— In a
1. For lateral airflo w app lica tio ns, an acce sso r y lat­eral duct must be used. Refer to Figure 7.
2. The sleeve mu st be mou nted so that it is leve l in all directions. A
1
/4-in. pitch is built into th e unit chassis for proper condensate drainage. An acces­sory drain kit is available if needed .
IMPORTANT: If more than 4 in. of the sleeve projects into the room or the wall is less than 2 in. thick, an accessor y subb ase mu st be used for sup ­port . R e f er to Fig u re 8 .
3. The sleeve should be caulked on all sides, includ­ing both inside and o uts id e of the building.
TYPICAL WALL INSTALLATION (52SC,SE,SQ)
NOTES:
1. Sleeve may be flush mounted to floor, and front panel may have to be notched to accommodate service cord.
2. If more than 4 in. of sleeve projects into room an accessory subbase must be used.
3. If wall is less than 2 in. thick, an accessory subbase must be used.
TYPICAL CURTAIN WALL INSTALLATION
(All Models)
FIGURE 5 — TYPICAL WALL INSTALLATIONS
WALL SLEEVE AND SLEEVE EXTENSION
(Field-Fabricated) (All Models)
NOTES:
1. Unit sleeve and sleeve extension (field-fabricated) should b e connected before installing in wall opening.
2. Sleeve extension is water-bearing. It must be water tight when installed against unit sleeve. Use quality grade sealant on all butting flanges. Attach both sections with bolts and nuts or self-tapping screws installed from unit sleeve to extension. Cut drain slots in front and rear flanges of extension to line up with drain openings in unit sleeve.
3. Install 2 center baffles inside sleeve extension to prevent recirculation of out­door air circuit.
3
4. Leave
5. Paint sleeve extension and seal corner and lap joints; clear all drain holes of
6. Install quality flashing under unit sleeve and extension using quality sealant
7. Install unit casing/extension assembly following standard practices. Seal
8. Make provision for a condensate drain extension tube for routing excess con-
9. Attach grille to the outside of the sleeve extension (using field-supplied
10. Seal any gaps between grille and sleeve extension on all sides.
/8-in. roomside projection of extension and 5/8-in. outdoor projection of sleeve. This allows for unit casing clearance to finished wall plus ample edging to apply weather sealant between unit sleeve/extension assembly and wall opening.
excess sealant, paint, etc., to permit free drainage.
between flashing and wall.
assembly to wall on all 4 sides, indoors and outdoors.
densate from the wall sleeve through the sleeve extension to the building exte ri or.
fasteners).
5
Page 6
52S
SERIES
SLEEVE INSTALLATION REQUIREMENTS (cont)
FIGURE 6 — DI ME NS ION DRAWING — 52SC,S E, SQ
NOTES FOR FIGURES 6-8
1. Minimum opening sizes apply to all wall openings.
2. Installed wall sleeve must be level from side to side and front to back.
3. Sleeve can be flush mounted to floor, but front panel may have to be notched to accommodate service cord, except for units with subbase (see Note 4).
4. When using subbase accessory, wall sleeve must extend 3 minimum into room and 31/4 in. minimum to 51/2 in. maximum above floor.
1
/4-in.
5. Dimensions in parentheses are in millimeters.
6. For all applications with an accessor y lateral duct, sleeve must ex­tend into the room 1 in. minimum.
7. If wall sleeve extends into room more than 4 in., an accessory sub­base must be used for support.
8. If wall is less than 2 in. thick, an accessory subbase must be used for suppor t.
6
Page 7
FIGURE 7 — 52S LATERAL DUCT
FIGURE 8 — 52S WITH SUBBASE
PREPARE SLEEVE FOR CHASSIS
INSTALLATION
1. Remove cardboard center support and rear clo­sure panel from wall sleeve. Refer to Figur e 9.
2. Install outdo or gr ille as described in the installa­tion instructio ns supplied with the gr ille .
Only a Carrier outdo or gr ille should be used with the 52S unit air conditio ne r . Use of any othe r gr ille must be app roved by Ca rrier i n Syracu se, New Yor k. In deep-wall applications, if an existing grille is used on an outdoor wall opening, do not install an addi- tional outdoor grille o n un it sle eve .
FIGUR E 9 — REMOVING CENTER SUPPORT
AND CLOSURE PANEL FROM
CARRIER WALL SLEEVE
7
Page 8
52S
SERIES
3. See Figure 10 for typical deep wall application. Inspect accessory outdoor gril le s.
IMPORTANT: Be sure that the foam strips and/or baffles provide a good seal between the grille and condenser coil tube sheets. These foam strips or baffles provide a barrier to separate condense r air from the major components (compressor and fan motor).
If baffles are not installed properly, loss of perfor­mance and premature damage to the major compo­nents can result.
INSTALL CHASSIS IN SLEEVE
1. Inspect foam gaskets (top, bottom, bo th side s) on chassis. (See Figur e 11.) Replac e foam gask e ts if torn or missing.
FIGURE 11 — 52S SERIES CHASSIS
(Cord Connected Unit Shown)
Chassis weighs between 118 and 138 lbs. For per­sonal protection , seek help when lifting the unit. Lift unit by holding unit basepan.
NOTES:
1. To permit outdoor grille to be attached to and supported by unit sleeve, fabricate a sleeve extension so unit sleeve and baffles can reach outdoor grille. Be sure to provide flashing for proper con­denser run-off to avoid water damage to room interior. Internal or external drain system may be required.
2. Baffles may be part of the sleeve extension or fixed directly to con­denser coil tube sheets.
3. Caulk all joints between sleeve or baffles and opening in wall.
4. If grille is used on outdoor wall opening, outdoor grille on unit sleeve.
install an additional
do not
FIGUR E 10 — TYP ICAL DEEP WALL
INSTALLATION — ALL MODELS
(Baffle s are Fie l d Fabric ated)
2. Lift chassis level with wall sleeve.
3. Slide chassis into wa ll slee ve until foam gaskets on chassis mounting flang e res t firmly ag ains t front of wall sleeve.
3
4. Screw chassis to wall sleeve with fou r 1
/4-in. long screws taped to the control box. Four screw holes are located on both sides of t he mount ing angles of the chassis. Use o nly th e top and bo ttom scr e w holes on each side for a plastic sleeve. Use two middle screw hol es on each side for a met a l s l eeve.
NOTE: If the gasket behind the chassis mounting angle covers screw holes, push a nail through each hole before inserting screws to facilitate assembly.
IMPORTANT: The ga skets combi ne w ith the s leev e face to create a weather barrier. If the chassis is installed in a non-Carrier sleeve, this weather bar­rier may not be effective.
8
Page 9
ACCESSORY INSTALLATION
IMPORT AN T : On ly trai ne d , qua lifie d person ne l and service m echan ics sho uld install electrical accessories on Carrier 52S series products per Carrier’s installation instructions. Please contact your local electrical contractor, dealer, or distribu­tor for assistance.
INSTALL ACCESSORY HARDWIR E KIT OR 2 65- v
ACCESSORY CORD-CONNECTED KIT —
Carrier accessory hardwire kit according to the instructions provided with the accessory. The acces­sory cord-connected kit is for 265-v units only, and requires an accessory subbase, Part No. SUBBASE, with a field-installed re ceptacle.
INSTALL THERMOSTAT —
All remote con trol
units.
1. Check to be sure power to unit is disconnected.
2. Remove termina l board cover from right sid e of chassis (see Figure 12).
3. Insert field-s upp lie d low -vo ltag e th erm ostat wire through bushing on the cover.
4. Connect wires from terminals on the thermostat to terminals on cha ssis te r m inal bo ar d . See Fig­ures 13A and 13B .
5. Reinstall cove r with two screws.
6. Mount field-supplied thermostat to wall.
7. Set thermostat ant icipat or at 0.8 amp (ma nua l thermostat only).
Install
LEGEND
Terminal Board
TB —
NOTE: B to B connection for heat pump only.
FIGURE 13A — WIRING CONNECTIONS,
LOW-VOLTAGE MANUAL CHANGEO VER
THERMOSTAT
FIGURE 12 — LOW-VOLTAGE TERMIN AL BOAR D
LEGEND
Terminal Board
TB —
NOTE: B to B connection for heat pump only.
FIGURE 13B — RC WIRING CONNECTIONS,
PROGRAM MABLE THE RMOSTAT
9
Page 10
52S
SERIES
INSTALL ENERGY MANAGEMENT (EM) ACCES-
SORY KIT —
units to be turned off from a remote location such as a hotel control desk t o conser ve energy w hen the room is unoccupied. Freeze guard protection prevents the room temperature from dropping below 40° F, overr i d­ing any OFF command, including front desk control.
IMPORTANT: In order for freeze guard to operate, the unit must be put into the HEAT mode.
Electric heat will remain activated until the tempera­ture rea ches app ro ximately 60° F.
IMPORTANT: The manufacturer currently does not supply any central desk equipment. This type of equipment should be handled through your local electrical contractor.
This accessory kit permits individual
See Figure 1 4 f or a cc es s o ry kit lo ca tion in control box. After EM accessor y kit has be en pro p erly ins talle d , connect low-voltage (24 VAC) field-supplied wires from chassis terminal board to your central desk panel (see Figure 15).
FGT —
NEC — SW — TB
NOTES:
1. All wiring must conform with NEC and local codes.
2. Field control wiring suitable for NEC Class 2 control circuit, at 24 volts.
Freeze Guard Thermostat National Electrical Code Field Control Wiring Switch Terminal Board
LEGEND
PR
Terminal Board Connection
Primary Relay
FIGURE 15 — EM ACCESSORY KIT
SCHEMATIC DIAGRAM
ADJUSTMENTS
ADJUST AIRFLOW DIRECTION
air grille is mount ed on the un it so that th e air dis ­charges forward. If upward discharge is required, remove the gr ille, in ve rt it, a nd re ins tall o n the chassis.
ADJUST VENT —
The VENT knob is lo c a te d on the side of the unit . S l i de VENT knob manually to o pen or close vent. Vent r emains in the positi on se lecte d .
— The discharge
FIGURE 14 — EM ACCESSORY KIT
10
Page 11
ADJUST L IMITS ON ECONO ZONE® II CON-
TROL
— (This adjustment is optional and is not ap­plicable to remote-control units.) Econo Zone II control permits adjustment of the temperature range available to the user by restri cting rotation of the TEMPERATURE control knob.
To adjust:
1. Remo ve thermos ta t control knob and t he co ntrol panel. To detach the control panel, remove two screws at base of panel and gently pull off panel. Once removed , th e temp erature limiter is exposed. (See Figure 16.)
2. Orient the sh aft of the the r m o stat so that the rib on the ven t control lever assem b ly, which i s located under the limiter, is positioned between the temperature limits desired.
NOTE: The numbers stamped on the limiter repre­sent degrees F and are approximate.
3. To set minimum cool s etting , remove cl ip from the hole marked 60 and relocate to hole with desired setting. Repeat with clip from hole marked 90 to set maximum heat setting desired.
IMPORTANT: Clips must be fully inserted.
4. Reinstall the con trol p ane l and the thermostat control knob. If adjusted prop erly, the indica tor on the control knob should al ways s win g through the top section of the temperature markin gs on the control p ane l .
FIGURE 16 — ECONO ZONE II
TEMPER ATURE LIMITE R
11
Page 12
52S
SERIES
OPERATING INSTRUCTIONS
SWITCH SETTINGS
For 52S remote control (RC) units, all switches are located on the wall-mounted thermostat. (See Figures 17 and 18.)
For all other 52S units, roo m contr o ls are loc ated on the unit cont ro l pa ne l. Ref e r to Fig ure 19, A and B.
A. 52S COOLING ONLY UNIT
B. 52S COOLING/HEATING UNIT
C. 52S COOLING/HEATING UNIT
WITH REMOTE CONTROL (BLANK PLATE)
FIGURE 17 — STANDARD MANUAL
CHANGEOVER THERMOSTAT (FOR RC UNITS)
NOTE: Thermostat cover swings open to left for additional programming options.
FIGURE 18 — PROGRAMMABLE THERMOSTAT
(FOR RC UNITS)
FIGURE 19 — UNIT CONTROL PANELS
OUTSIDE A IR —
vent lever to OPEN position.
OFF —
FAN ONLY
without heating or cooling.
HIGH HEAT OR HIGH COOL
rotate temperature knob to desi red c omfort level. Th is function provides maximum heating or cooling, and is recommended to raise or lower the room temperature quickly. Once the occupi ed space has reached the desired comfo rt leve l, this se tt ing is no t r eq uired. See Finding Temp e ra tur e Sett ing se c tio n belo w f or mor e information.
LOW HEAT OR LOW COOL —
rotate temperature knob to desi red c omfort level. Th is function provides minimum heati n g or coolin g with maximum dehumidification.
FINDING TEMPERA TURE SETTING FOR YOUR
COMFORT LEVEL —
number 5 and number 6. Push Hig h or Low H eat or Cool button and allow unit to run 15 to 30 min utes. If room is not comfortable, turn knob one number at a time. When room is comfortable, keep control knob at that position.
The OFF button terminates unit operation.
— Push button for air circulation
Push FAN ONLY butt on and slide
— Push button, and
Push button and
Set temperature knob between
12
Page 13
OPERATING CONTROLS
HEAT PUMP
ELECTRIC
HEAT
VENT
CLOSED
OPEN
CON
CYC
OUTDOOR THERMOSTAT (ON HEAT PUMP ONLY)
FAN CYCLE SWITCH (NOT ON RC UNITS)
VENT LEVER
The following control s are locat ed on the rig ht side of the chassis. (See Figur e 20.) To obt ain ac cess to op­erating controls, remove the unit front panel as shown on page 2.
IMPORTANT: When unit is first started, high humidi ty condit i o ns can cause co nd e nsation to form on grille. Keep door s and win d ow s close d . Room humidity decreases and moisture evaporates.
HEAT PUMP
OPEN/CLOSED
HEAT MODE
VENT
ELECTRIC
NOTE: ELECTRIC HEAT MODE WILL DISABLE COMPRESSOR OPERATING.
52SQ506082 REV-
FAN CYCLE SWITCH
— (Not available on RC
units.) This allows the fan to operate i n two modes:
— This setting allow s the fan to run co ntin u-
CON ously, circulating air even when the temperature set­ting has been satisf ied . This switch helps to main tain the room temperatu re clos er to th e thermos tat sett ing. Use this switch position when maximum comfort is desired.
— This setting allows the fan to cycle on and off
CYC with the compr essor d uring heating or c ooling. Th e fan stops when the te m per atu re se tting is satisfied. This results in longer unit off-time and wider variations in room temperature and humidity.
OUTDO O R TH ERMOSTAT (52 S Q HE AT PUMP
UNITS ONLY)
— If the setscrew is left at the factory setting (in the fully clo ckwise position) , the un it will operate in the revers e cycle heat i ng mode. The control is the defrost ther mo stat in this m o de. Th e 52SQ the r ­mostat sensing capillar y is lo cat ed be tw een the fins of the outdoor coil. When the temperature at the capil­lary reaches 2 5° F, th e outdoor frost t hermost at clos es, shutting off the compre ssor and energi zing the elec tric heater. The electric heater remains on until the tem­perature at the outdo o r ther m o stat ca p illar y reach e s 40° F; then the electric heater is shut off and the com­pressor is energize d. To set unit t o operate in electric heat mode only, turn the setscrew to the fully counter­clockwise positi on. Once in electric heat mode, the compressor is disabled for heatin g and coo lin g.
VENT CONTROL
— See Adjustments on page 10
for vent operatin g info r m atio n.
FIGURE 20 — TYPICAL 52S SERIES
OPERATING CONTROLS
CARE AND MAINTENANCE
In order to maintain proper performance of your pack­aged terminal air con d itione r or heat pu m p, it is very important that the fan and outdoor coils , the blower wheel, blower scroll, electric heater, and all drain pas­sages are thoroughly cleaned at least once per year. Carrier recommends tha t as a minimum, the cleaning should be cond uc te d pri or to th e start o f eac h he atin g season. The air inlet filter should be cleaned every month.
Depending on local conditions, more frequent clean­ing of the unit may be required to ensure optimum performance and long operating life. Examples of these special conditions include areas where construc­tion dust or heavy airborne dirt is found, or environ­ments that promote the growth of fungus.
Some local condit ion s and environments can cause fungi to grow inside the air conditioner, especially on indoor blower se cti on . D ried fungi, dirt and other foreign ma terial are fire hazards. B e sure to cle a n unit accordin g to the instr uc tio ns th at foll ow .
AIR INLET FILTER
AIR INLET FILTER
month.
1. If front panel has not been remo ved, remove panel as shown in Figure 2. To remove filter, grasp two filter tabs and pull the filte r fo rwa rd (Figure 21).
should be cleaned once each
13
Page 14
52S
SERIES
INTERNAL PARTS
FIGURE 21 — REMOVING FILTER
2. Clean by va cuum ing or washing. T o reinstall the filter, fit it into the basepan, making sure the notch in the filter fits aro un d the th e rmo stat cap ­illary. The filter media is plastic fram ed for ad­ditional support. Take care not to rip the media when cleaning. Additional filters are available in multi-packs.
3. Flex the filter, and fit it under the discharge deck.
OUTDOOR VENT FILTER
OUTDOOR V ENT FILTER
cleaned in the same manner as the air inlet filter , but only once during a cooling or heating sea so n. Remove chassis from sleeve to access vent filter . Dirty f ilters restrict airflo w, which c a n re d uce majo r component life.
(Figure 22) should be
INTERNAL PARTS
should be cleaned at least once
each year.
Before cleaning, servi cing, perf o rming maintenanc e or removing the chassis from the sleeve, disconnect all power to the unit to avoid the possibility of elec­trical shock and personal injury.
DISCONNECT POWER TO U NIT:
CORD-CONNECTED UNITS
1. REMOTE CONTROL UNITS — Set switch on wall mounted thermostat to OFF.
ALL OTHER UNITS — Push OFF button on unit control p ane l .
2. Disconnect power at main power supply.
3. Unplug the unit service cord.
HARDWIRED UNITS
1. REMOTE CONTROL UNITS — Set switch on wall mounted thermostat to OFF.
ALL OTHER UNITS — Push OFF button on unit control p ane l .
2. Disconnect power at main power supply . Ta g dis­connect to ensure no one restores power to the unit. If front panel has not been removed, remove panel as shown in Figure 2. Remove access cover on side of unit chassis. Pull out plug assembly and disconnect (see Figure 23).
CONTROL BOX
WIRING DIAGRAM
ACCESS COVER
VENT DOOR
FIGURE 22 — OUTDOOR VENT FILTER LOCATION
(Left Side of Chassis)
EXTERNAL PARTS
EXTERNAL PARTS
grilles. The sleeve manufacturer recommends cleaning the surface, including the grilles, with household detergent and water.
inclu de the poly m er sl eeve a nd
VENT FILTER
14
PLUG ASSEMBLY
FIGUR E 2 3 — DISCONNE CTING PLU G
ASSEMBLY ON HARDWIRED UNITS
Page 15
DISA SSEMBLE UNIT
L
TOP COVER SCREW
TOOLS REQUIRED include: a low-pressure tank with wand and/or spray bottl e , a coil cleaner (Calgon, Hydrob al ance, et c.), a vacu um cl e aner, percolato r brush, standard spr ay bo ttle, rubber glove s, sa fety glasses,
5
/16-in. nut driver, and a stand ard Phillips-
head screw d riv er.
1. If front panel has not been remo ved, remove panel as shown in Figure 2 .
2. Remove scr ew s (two eac h side ) fa ste nin g ch assis to sleeve.
For uni ts with late ral duct accessory — remove four screws fastening chassi s to sleeve, a nd two screws on top of duct adapter. See Figure 24.
Chassis weighs between 118 and 138 lbs. For per­sonal protection, seek help when lifting the unit.
3. Slide out chassis. Lift by holding the unit basepan.
4. Remove aluminum top panel (one screw each side). See Figure 25. On left-hand side, remove the screw clo sest to the parti ti o n.
5. Remove the air dischar ge grille (two sc rews ). See Figure 26.
6. Remove the top cover (one screw). See Figure 27.
FIGURE 25 — ALUMINUM TOP PANEL
TOP PANE SCREW
FIGURE 24 — REMOVING CHASSIS WITH
DUCT ADAPTER FROM SLEEVE
FIGURE 26 — REMOVING AIR
DISCHARGE GRIL LE
FIGURE 27 — TOP COVER SCREW
15
Page 16
52S
CONDENSER ORIFICE
SERIES
7. Remove the gusset (two screws inside the parti­tion, one screw at condens er orifi ce). Push con­denser orifice outward. Pu ll the gusset up and out of orifice. See Figure 28.
8. Unsnap the condenser orifice from the tube sheets.
9. Remove the stator by moving the condenser ori­fice toward the partition and by pulling the stator straight up. See Figure 29.
10. Remove the air inlet filter (see removal instruc­tions under AIR INLET FILTER, page 13).
11. Remove thermostat sensing bulb from the indoor coil by pulling two bulb re tain ing clips out of the coil fins and carefully moving the bulb away from the face of the coil.
GUSSET
PARTITION
CLEANING DISASSEMBLED UNIT
1. Clean the indoor coil and stator side of the out­door coil by washing or vacuuming.
Fins are sha rp a n d can cut hands. Wear heavy gloves when cleaning coil s . Whe n using clea nin g tools, be careful not to bend or damage coil fins.
2. Clean vent screen by washing or vacuuming. Open vent door and pull s cr een out. See Fi gure 30.
3. Clean basepan, including drain passages and area inside the condenser orifi ce, by washing or vacu­uming. See Figure 30.
4. To clean indoor blower wheel and scroll, insert a piece of 9.0 x 9.0-in. cardboard between the blower wheel and the opening in the blower scroll. This will also prevent fungus and other debris from falling into the coil.
VENT
DOOR
DRAIN PASSAGE
FIGURE 28 — REMOVING GUSSET
STAT OR
CONDENSER ORIFICE
CONDENSER COIL
FIGURE 29 — REMOVING STATOR
DRAIN V
ALVE
OVERFLOW NOTCH (1) EACH SIDE
FIGURE 30 — BASEPAN SECTION
16
Page 17
5. Bend a soft, spiral wound, long bristle bru sh to confor m t o th e inner curve of the bl ower whee l blades. See Figure 31.
6. Insert the brush into every blower wheel blade and gently brush out dried mate r ial.
7. Cl ean the wa l l s of t he blo w er scroll by carefull y brushing with the bristle brush. Vacuum loose debris that may have fallen into the bottom of the scroll during the cleaning process.
8. Use the spray bottle to spray the blower whee l blades and the inner surfac e of the blowe r scroll with a 3% solution of hy dro gen p e roxide to kill any fungus spores. Wipe up excess solution in the bottom of the blower scroll with a clean cloth. See Figure 32.
9. Clean the inside of the wall sleeve and rear grille by washing or vacuuming. Test wall sleeve dra in holes and accessory drains (if used) for proper drainage. Pour water (approximately 2 quarts) into the sleeve. Water should drain freely.
FIGURE 32 — SPRAYING BLOWER WHEEL BLADES
REASSEM BL E UN IT
1. Reassemble components by reversing disassembly procedures described on page 15.
2. Reinstall un it into sle e ve.
3. Turn on all power to the unit.
FIGURE 31 — CLEANING INDOOR FAN
AND FAN SCROL L
17
Page 18
52S
SERIES
ACCESSORIES
Corrosion-Protected Pol ymer Sle ev e
Standard Non-Electrical Subbase
Standard Grille
Standard Architectural Grille in Aluminum or Plastic
Lateral Duct Kit
Hardwire Kit
External Drain Kit Application
Energy Management Kit
GE Metal Sleeve Retro-Fit Kit
265-v Cord Kit
Locking Control Door Kit
60
70
80
90
ON
AUTO
FAN
COOL
O
FF
HEA
T
Standard Manual Changeover Thermostat
18
Programmable Thermostat
Page 19
19
Page 20
52S
SERIES
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 9a 11a
PC 132 Catalog No. 535-232 Printed in U.S.A. Form 52S-47SI Pg 20 12-99 Replaces: 52S-46SI
Loading...