Carrier 52S User Manual

52S
SERIES
SERVICE TECHNICIAN GUIDE
PACKAGED TERMINAL AIR CONDITIONERS
AND HEAT PUMPS
CONTENTS
INTRODUCTION
SUMMARY OF DANGERS, WARNINGS, AND CAUTIONS
GENERAL DISASSEMBLY
TO DISCONNECT POWER FOR CORD-CONNECTED UNIT TO DISCONNECT POWER FOR PERMANENTLY CONNECTED (HARDWIRED) UNITS TO OPEN THE CONTROL BOX TO REMOVE THE UNIT FROM THE WALL SLEEVE TO REMOVE THE LATERAL DUCT EXTENSION, FOR
UNITS EQUIPPED WITH THE LATERIAL DUCT ACCESSORY PACKAGE
TO ACCESS INDOOR-AIR SECTION COMPONENTS TO ACCESS OUTDOOR-AIR SECTION COMPONENTS
GENERAL CLEANING
CLEANING AND SAFETY TOOLS NEEDED MONTHLY CLEANING SEASONAL CLEANING
COMPRESSOR
COMPRESSOR TROUBLESHOOTING BASIC HERMETIC COMPRESSOR ELECTRICAL MEASUREMENTS COMPRESSOR REPLACEMENT
.................................2,3
...........................4-9
...................4
.......................4
............................5
............................10-15
..........................10
.................................11
............................11
...........................13
..................................16-21
..................17
................................17
......................19
Page
..4
........4
.......6
......8
HEATERS
COMMON CAUSES OF HEATER FAILURE HEATER REMOVAL
OPERATING CONTROLS
DESCRIPTION OF SWITCH SETTINGS NON-USER ADJUSTABLE SWITCHES SEQUENCE OF OPERATION COMPONENT OPERATION AND TROUBLESHOOTING ELECTRICAL COMPONENTS REMOVAL AND
REPLACEMENT
FAN MOTOR
FAN MOTOR TROUBLESHOOTING BASIC FAN MOTOR ELECTRICAL TESTS FAN MOTOR REPLACEMENT
FIELD TEMPERATURE CHARTS WIRING SCHEMATICS MOST FREQUENT PTAC SERVICE QUESTIONS
......................................22,23
..............22
..............................22
.........................24-31
.................25
.................25
........................26
.................................30
...................................32-34
...................32
...............32
.......................34
....................35-50
...........................51-55
..........56
PTAC Customer Support Center
1
800•894•6449
....27
Page
52S
SERIES
INTRODUCTION
The focus of this manual is to provide basic information on service procedures, safety, troubleshooting, clean­ing, and component replacement for service technicians.
It is intended for use only by HVAC service tech­nicians who have successfully completed instruc­tion and received Type I Certification from the U.S. Environmental Protection Agency.
The instructions in this manual are general in nature and are not to be substituted for installation and service instructions shipped with the unit. No attempt to in­stall, operate, adjust, repair, or dismantle any equipment should be made until the manufacturer’s instructions are read and thoroughly understood by the service tech­nician. Even equipment that seems familiar may have specific model differences from year to year. Always review manufacturer’s instructions.
The Model 52S packaged terminal air conditioner and heat pump units are self-contained for installation through the wall for individual room heating and cool­ing. The Model 52S polymer sleeve is permanently fastened to the wall; the unit chassis slides out of the sleeve to allow the service technician easy access. An accessory louvered rear grille may be mounted on the sleeve. Many accessories are offered to complement the unit’s comfort control.
Before beginning any service procedures, it is important to check the unit model number. Even units that seem similar may have subtle differences that could affect service procedures. The 52S units covered in this book are the 52SC (Cooling Only model); the 52SE (Cooling with Electric Heat model); and the 52SQ (Cooling, Elec­tric Heat, and Heat Pump model).
Knowing which model is being serviced will help deter­mine if the unit is performing at optimum levels. The model number is located on the data information plate beneath the front panel of the unit. The data infor­mation plate also lists voltage ranges and other impor­tant electrical information about the unit. To access the data information plate, remove the front panel of unit by grasping panel on each side and gently pulling upward and out (Figure 1). See Figure 2 for model num­ber nomenclature and Figure 3 for a sample data infor­mation plate.
SUMMARY OF DANGERS, WARNINGS, AND CAUTIONS
The terms DANGER, WARNING, and CAUTION have specific meanings that identify the degree of haz­ard. Typically in the HVAC industry, these specific meanings are:
There is an immediate hazard which WILL result in severe personal injury or death.
Hazards or unsafe practices which COULD result in severe personal injury or death.
Potential hazards or unsafe practices which COULD result in minor personal injury or equipment damage.
FIGURE 1 — REMOVING FRONT PANEL
2
FIGURE 2 — MODEL NUMBER NOMENCLATURE
FIGURE 3 — SAMPLE DATA INFORMATION PLATE
3
52S
SERIES
GENERAL DISASSEMBLY
This section includes common procedures for disassem­bly and reassembly of 52S units. These instructions are general in nature and include procedures the tech­nician may be called upon to perform when accessing certain components of the 52S unit.
It is important to carefully follow manufacturer’s instruc­tions when disassembling or reassembling a unit for cleaning, maintenance, or part replacement. When dis­assembling wiring, it is strongly recommended that numbered stickers be attached to identify leads and ter­minals to aid in the reassembly process.Always review safety procedures prior to the start of a job.
Prior to servicing electrical equipment, disconnect all power to avoid electric shock! Never alter cord or plug and do not use extension cords.
TO DISCONNECT POWER FOR CORD­CONNECTED UNIT
1. Push OFF button.
2. Open the disconnect switch at main power supply.
Use proper Lockout and Tag procedures.
3. Unplug the unit service cord.
CONTROL BOX
.
.
ACCESS COVER
PLUG ASSEMBLY
FIGURE 4 — DISCONNECTING PLUG
ASSEMBLY ON HARDWIRED UNITS
TO DISCONNECT POWER FOR PERMANENTLY CONNECTED (HARDWIRED) UNITS
1. Push OFF button.
2. Open the disconnect switch at main power supply.
Use proper Lockout and Tag procedures.
3. Remove screw from access cover and remove ac­cess cover.
Pull out the plug assembly and disconnect (see
4.
Figure 4).
TO OPEN THE CONTROL BOX
The control box is factory wired. To open the control box, remove the 2 screws on the front of the control box and lower the front hinged panel. See Figure 5.
TO REMOVE THE UNIT FROM THE WALL SLEEVE
1. Remove the four, 1
cure the unit to the wall sleeve. There are 2 screws on each side (Figure 6).
2. Grasp the sides of the unit and slide it from the sleeve.
The chassis weighs between 110 and 150 pounds. Take proper safety precautions to avoid personal in­jury when lifting and moving the chassis.
3
⁄4-in. mounting screws that se-
FIGURE 5 — OPEN CONTROL BOX
The unit basepan may have water in it. Tilt the unit back slightly when removing it from the sleeve to drain some of the water into the sleeve.
FIGURE 6 — UNIT TO WALL SLEEVE
MOUNTING SCREWS
4
TO REMOVE THE LATERAL DUCT EXTENSION, FOR UNITS EQUIPPED WITH THE LATERAL DUCT ACCESSORY PACKAGE
1. Remove the front panel as shown in Figure 1.
2. Remove the four 1
chassis to the wall sleeve (see Figure 6). There are 2 screws on each side.
3. Remove the 2 screws that secure the lateral duct ex-
tension to the top of the lateral duct adapter as shown in Figure 7.
4. Locate and remove the 2 screws that secure the
lateral duct extension to the bracket flange as shown in Figure 8.
5. Carefully slide the chassis away from the extension
duct and remove from the sleeve (as shown in Figure 9).
3
⁄4-in. screws that secure the
FIGURE 7 — DUCT EXTENSION SCREWS
The unit basepan may have water in it. Tilt the unit back slightly when removing it from the sleeve to drain some of the water into the sleeve.
The chassis weighs between 110 and 150 pounds. Take proper safety precautions to avoid personal in­jury when lifting and moving the chassis.
FIGURE 8 — BRACKET FLANGE SCREWS
FIGURE9—PARTIAL REMOVAL OF CHASSIS
FROM WALL SLEEVE
5
52S
SERIES
TO ACCESS INDOOR-AIR SECTION COMPONENTS
n DISASSEMBLING THE LATERAL DUCT ADAPTER, FOR UNITS EQUIPPED WITH THE LATERAL DUCT ACCESSORY PACKAGE
Remove the lateral duct adapter end cap, shown in
1.
Figure 10, by removing the two
2. Remove the adapter top panel by removing one screw
at each end of unit as shown in Figure 11. Rotate the front of the panel up and back and lift free.
3. Rotate and lift the air baffle out of the unit. See
Figure 12.
4. Remove the 2 screws holding the duct adapter to the
chassis discharge air opening flanges, as shown in Figure 13, and remove the duct adapter.
1
⁄2-in. screws
FIGURE 12 — REMOVING THE AIR BAFFLE
FIGURE 10 — WALL SLEEVE, DUCT ADAPTER,
AND EXTENSION LOCATION
(RIGHT-HAND EXTENSION)
FIGURE 11 — DISCHARGE PLENUM ASSEMBLY
FIGURE 13 — REMOVING THE DUCT ADAPTER
6
n TO REMOVE THE AIR DISCHARGE GRILLE
L
1. Remove the 2 screws on each end of the air discharge
grille as shown in Figure 14.
2. Lift and rotate back the bottom edge of the discharge
grille and remove it.
n TO REMOVE THE ALUMINUM TOP PANEL
— Remove one screw from each end of the aluminum top panel (located on the underside of the panel) as shown in Figure 15. On the left side of the unit, remove the screw closest to the side of the unit.
FIGURE 14 — REMOVING AIR DISCHARGE GRILLE
n TO REMOVE THE TOP COVER — Remove the screw
located in the middle of the top cover and remove the cover. See Figure 16.
FIGURE 15 — ALUMINUM TOP PANEL
FIGURE 16 — TOP COVER SCREW
TOP PANE SCREW
7
52S
SERIES
n TO REMOVE THE DISCHARGE DECK
1. Remove the 2 discharge deck screws shown in
Figure 17. Also remove the screw located at the top left corner of the outdoor coil tube sheet.
2. Gently pull the left side panel out and lift the
end of the discharge deck that the screws were re­moved from, up and forward, to remove.
TO ACCESS OUTDOOR-AIR SECTION COMPONENTS
n TO REMOVE THE GUSSET
1. Remove the 2 screws that secure the gusset to the
partition.
2. Remove the screw that secures the gusset to the
plastic condenser orifice and remove the gusset. See Figure 18.
DISCHARGE
SCREWS
DECK
FIGURE 17 — DISCHARGE DECK REMOVAL
CONDENSER ORIFICE
GUSSET
PARTITION
n TO DETACH THE CONDENSER ORIFICE FROM
THE CONDENSER COIL — Using a flat head screw driver, gently pry the plastic condenser orifice tabs away from both condenser coil tube sheets and pull the con­denser orifice away as shown in Figure 19.
FIGURE 18 — GUSSET REMOVAL
COIL ASSEMBLY
COIL FINS
COIL MOUNTING SCREWS
CONDENSER ORIFICE
CONDENSER ORIFICE TABS
BASEPAN
FIGURE 19 — REMOVING CONDENSER ORIFICE
8
STATOR
n TO REMOVE THE STATOR — After pulling the top
of the condenser orifice away from the condenser coil, grasp the top of the stator and slide it up and out of the stator track. See Figure 20.
CONDENSER ORIFICE
CONDENSER COIL
FIGURE 20 — REMOVING STATOR
9
52S
SERIES
GENERAL CLEANING
Maintaining proper performance of 52S systems (Figure 21) requires conscientious cleaning and care of components. Specific components require periodic clean­ing and/or replacement, including the following:
COMPONENT CLEANING SCHEDULE
Indoor Air Filter Monthly
Vent Air Filter Monthly
Indoor Coil Seasonally Indoor Fan Seasonally
Outdoor Coil Seasonally
Before cleaning, servicing, performing maintenance, or removing the chassis from the wall sleeve, discon­nect all power to the unit to avoid the possibility of electrical shock and personal injury. Only trained and qualified service personnel should perform installation and service procedures on these units. Untrained personnel may perform basic maintenance tasks such as cleaning and replacing filters. Refer to General Disassembly section of this manual for proper procedures to disconnect power to 52S units.
CLEANING AND SAFETY
Before starting to clean a unit, read the instructions thoroughly and gather the necessary tools for the job. Review all safety information on unit and in literature.
Consider the following safety issues before beginning:
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as safety glasses and work gloves, should be used.
• The floor around the work area should be clean and free of debris.
• The 52S unit weighs up to 150 pounds. Use a lifting device or ask for assistance if the unit must be moved.
• Make sure tools are the correct tools for the job, and that they are working properly and in good condition.
ON
OFF
WALL SLEEVE
CHASSIS
FRONT COVER
FIGURE 21 — FRONT PANEL, CHASSIS, AND SLEEVE
10
TOOLS NEEDED
The following list includes the recommended tools, de­vices, and cleaning solutions for use in cleaning the 52S unit components.
Vacuum Cleaner with Crevice Tool Attachment,
Lifting Device (or another person for assistance)
Trigger Spray Extension Tube (Part No. P9029000)
Vent Air Filter Replacement (Part No. 52SQ500204) Condenser Coil Cleaning Solution (Part No. P9020501) Evaporator Coil Cleaning Solution (Part No. P9021001)
3% Solution of Hydrogen Peroxide in Spray Bottle
or Soft Plastic Bristle Brush
Mild Household Detergent Phillips Head Screwdriver
5
⁄16-in. Nut Driver
Flat Head Screw Driver
Tank Sprayer (Part No. P9021001) or
Compressed Air Tank
Clean Water Supply
Indoor Air Filter Replacement
(Part No. AIR-FILTER-25PAK)
9.5-in. by 9.5-in. Piece of Clean Cardboard
Clean Cloth
Safety Glasses
Protective Gloves
MONTHLY CLEANING
n AIR FILTERS — The indoor and vent air filters should
be cleaned once per month. Filters that are not cleaned become clogged and will restrict airflow. This may lead to major component damage. If a filter becomes torn, has holes, or other damage, replace it with a new one. Re­placement filters are available through Carrier Finished Goods and Carrier Replacement Component Division.
n CLEANING THE INDOOR AIR FILTER — Remove
the indoor air filter as follows:
1. Remove the front panel to access the indoor air filter.
To remove front panel, grasp panel firmly near the top of each side. Lift upward and pull forward. It is not necessary to use excessive force. See Figure 1.
2. To remove the indoor air filter, gently grasp the
2 filter tabs, push down, and pull out. See Figure 22.
Once the indoor air filter has been removed, use a vacuum cleaner, or a soft bristle brush and a small amount of mild dish detergent to gently wash the filter. If detergent is used, remove detergent residue with a gentle, clean water stream. Let the filter air dry. Be sure to reinsert the filter into the unit.
FIGURE 22 — REMOVING FILTER
n REPLACING THE INDOOR AIR FILTER — Access
and remove indoor air filter as detailed above in Clean­ing the Indoor Air Filter. Use a filter replacement with the Carrier Part No. AIR-FILTER-25PAK, available through Carrier Finished Goods and Carrier Replace­ment Component Division.
11
52S
SERIES
n CLEANING THE VENT AIR FILTER
1. Remove the unit chassis from wall sleeve as described
in the General Disassembly section of this manual. See Figure 6.
2. Swing open vent door. The filter is located directly
behind the vent door. See Figure 23.
3. Remove the vent air filter by gently pushing on the
filter slot.
Once the vent air filter is removed, it may be cleaned using either a vacuum cleaner, or a soft bristle brush and a small amount of mild dish detergent. If deter­gent is used, remove detergent residue with a gentle, clean water stream. Let the filter air dry. Be sure to rein­sert the filter into the unit.
n REPLACING THE VENT AIR FILTER
Access and remove the vent air filter as detailed above in Cleaning the Vent Air Filter. Use a filter replacement with the Carrier Part No. 52SQ500204, available through Replacement Components Division.
n CHASSIS
As-needed cleaning of the unit’s exterior surfaces (Figure 24) optimizes the unit’s appearance and removes particles that may enter the air system. The 52S units are built to resist corrosion. The indoor front panel and wall sleeve are created from non-metallic compounds that do not rust. Additional corrosion protection may be factory installed on the partition, control box, and out­side coil for use in highly corrosive environments. Mild detergents reduce electrostatic charges on plastic sec­tions on the grille and are good cleaners. Use such deter­gent cleaners sparingly.
Use a clean cloth or brush to gently wipe exterior sur­faces. Be careful not to push dirt or other fibers into the unit’s interior.Accessible sleeve surfaces should also be wiped clean.
VENT FILTER
VENT DOOR
FIGURE 23 — ACCESSING VENT AIR FILTER
FIGURE 24 — UNIT FRONT PANEL AND SLEEVE
12
SEASONAL CLEANING
n ACCESSING THE INDOOR AND OUTDOOR
COILS — The minimum cleaning recommendation for indoor and outdoor coils is once per season. To access the coils for a thorough cleaning, it is necessary to remove the Air System. To accomplish this task, per­form the following steps:
1. DISCONNECT ALL POWER TO UNIT!
2. Remove the unit chassis from the sleeve as described
in the General Disassembly section of this manual. See Figure 6.
3. Remove each side angle from unit with a
driver. See Figure 25.
4. Locate and disconnect wires from the compressor.
Label each wire for easy reassembly.
For compressors that are known to be dam­aged: Remove refreigerant prior to disconnecting
compressor wires. Damaged hermetic compressor ter­minals may become loose and eject from the com­pressor. Wear safety glasses and keep your face away from the area above the terminals when removing compressor wires.
5. For Heat Pump Units — Disconnect the wire plug
on the reversing valve and carefully remove the out­door thermostat capillary from the outdoor coil.
6. With a
8 screws mounting the fan section to the chassis. See Figures 26 and 27.
5
⁄16-in. nut driver, locate and remove the
7. Using a flat head screw driver, gently pry the plastic
condenser orifice tabs away from both outdoor coil tube sheets and pull the condenser orifice away as shown in Figure 19. See GENERAL DISASSEMBLY section.
8. Carefully remove the fan section from the chassis
by lifting fan section straight up and out. The fan deck is awkward; 2 people may be needed for its removal.
5
⁄16-in. nut
9. Remove the stator from the outdoor coil. See
GENERAL DISASSEMBLY section. After cleaning, reassemble by reversing steps1-8.
IMPORTANT: During reassembly of the fan section, carefully align the rubber seal around the tubing where it passes through the partition.
FIGURE 25 — SIDE ANGLE SCREWS
FIGURE 26 — PARTITION FLANGE SCREWS
FIGURE 27 — FAN SECTION SCREW LOCATIONS
13
52S
SERIES
n CLEANING THE INDOOR AND OUTDOOR COILS
Coil fins are sharp and may cut hands. Wear heavy protective gloves when cleaning coils.
1. Use a vacuum cleaner or soft bristle brush to remove
surface fibers and dirt from each of the faces of the coil. Both the inner and outer surfaces of the coils must be cleaned. It is important to apply the tool in the same direction of the fins, not against them. Applying the tool against the fins may cause damage (fin edges may bend over).
2. With a tank sprayer or a trigger spray extension tube,
spray coil cleaning solution evenly across the coils, making sure coils are thoroughly saturated. See Figure 28. Refer to instructions on the cleaning solu­tion containers for best results. Do not use a high
pressure sprayer.
3. Rinse the coils thoroughly with low-velocity, clean
water.
4. Repeat steps 2 and 3.
5. Drain water and cleaning solution that may have
collected in the basepan during the cleaning pro­cess by carefully tilting the chassis. This allows excess water to flow out of the overflow notches.
FIGURE 28 — CLEANING THE COILS
Do not set unit on end to drain water from basepan, or at any other time. Oil will drain from the compres­sor sump, which could cause compressor failure.
6. Thoroughly clean the basepan and drain passages
by rinsing with clean water. Be sure all debris is re­moved from the drain valve. See Figure 29.
7. Allow unit components to air dry before reassem-
bling the unit. Once dry, reassemble by reversing Steps1-9from the Accessing Indoor and Outdoor
Coils section.
n ACCESSING THE INDOOR FAN AND INDOOR
FAN SCROLL — Dried debris and build-up on the blower wheel and blower scroll can reduce the efficiency of the unit. To properly access the indoor fan and in­door fan scroll for cleaning, refer to the GENERAL DISASSEMBLY section under To Access Indoor-Air
Section Components on page 6.
FIGURE 29 — BASEPAN SECTION
14
n CLEANING THE INDOOR FAN AND FAN
SCROLL — Once the indoor fan wheel and the indoor fan scroll have been accessed, proceed with the cleaning instructions detailed below:
1. Insert a piece of 9.5-in. by 9.5-in. cardboard between
the blower wheel and the opening in the blower scroll to prevent fungus and other debris from falling into the coil.
2. Bend a soft, spiral wound, long bristle brush, to con-
form to the inner curve of the blower wheel blades. See Figure 30.
3. Insert the brush into every blower wheel blade and
gently brush out dried material.
4. Clean the walls of the blower scroll by carefully brush-
ing with the bristle brush. Vacuum loose debris that may have fallen into the bottom of the scroll dur­ing the cleaning process.
5. Use the spray bottle to spray the blower wheel blades
and the inner surface of the blower scroll with a 3% solution of hydrogen peroxide to kill any fungus spores. Wipe up excess solution in the bottom of the blower scroll with a clean cloth. See Figure 31.
6. Reassemble components by reversing the steps used
to disassemble the unit as detailed in the GENERAL DISASSEMBLY section under To Access Indoor-
Air Section Components.
n ACCESSING THE HEATER ASSEMBLY — To access
the heater assembly for cleaning, perform the follow­ing steps:
1. DISCONNECT ALL POWER TO THE UNIT.
2. Remove the unit front panel, the discharge air grille,
and the discharge air deck as described and shown in Figure 1 and the GENERAL DISASSEMBLY section.
3. Once the discharge air deck is removed, the heater
assembly is accessible.
n CLEANING THE HEATER ASSEMBLY — Once the
heater assembly is accessed, use compressed air to blow off any dust that has accumulated on the heater coils. Do not direct the air at the bi-metal discs of the tempera­ture limit switches. Reassemble the unit by reversing Steps1-3.
FIGURE 30 — CLEANING INDOOR FAN
AND FAN SCROLL
Do not touch the heater coils or the temperature limit switches. Touching or depressing the bi-metal discs on the temperature limit switches may affect the set point or cause the secondary temperature limit switch to electrically open, requiring it to be replaced.
FIGURE 31 — SPRAYING BLOWER WHEEL BLADES
15
52S
SERIES
COMPRESSOR
A cutaway view of the rotary compressor with key com­ponents labeled is shown in Figure 32. The motor sta­tor is rigidly attached to the compressor shell. The rotor is pressed onto the eccentric shaft, which is supported by 2 bearings. Both the discharge valve and discharge muffler are attached to the motor bearing. The pump
DISCHARGE TUBE
SUCTION INLET
SUCTION MUFFLER/ ACCUMULATOR
bearing provides a thrust surface for the shaft and the rolling piston. Compressed gas is separated from the suction gas by the vane. Discharge gas pressure and the vane spring keep the vane in contact with the rolling piston.
SHELL
STATOR ECCENTRIC SHAFT
ROTOR
PISTON VANE
OIL TUBE
MOTOR BEARING DISCHARGE MUFFLER
DISCHARGE VALVE CYLINDER
PUMP BEARING
MOUNTING PLATE
FIGURE 32 — ROTARY COMPRESSOR COMPONENTS
16
The rotary compression process (Figure 33), starts at top dead center as shown in (1). Suction gas flows through the suction inlet and into the cylinder area. As the shaft rotates through 90 degrees, the rolling pis­ton moves to position A as shown in (2). The suction vol­ume is now the area defined by point A and the tip of the vane. Gas in the remaining volume has been com­pressed above suction pressure. After another 90 degrees of shaft rotation, the rolling piston has moved to posi­tion B as shown in (3). Both the compressed gas and suction gas volumes are now equal. Another 90 degrees of shaft rotation is shown in (4). Compressed gas has reached a pressure sufficient to open the discharge valve, and flows from the cylinder into the compressor shell. After another 90 degrees of shaft rotation, the entire process begins again. Continuous suction and discharge allows for a smooth compression process.
The rolling piston is not in actual contact with the cyl­inder wall, vane, or bearing faces. Hydrodynamic sealing prevents leakage from the compressed gas vol­ume to the suction volume via these paths. Precise con­trol of machining tolerances, surfaces, finishes, and assembly clearances is critical to achieve high efficiency performance. In addition, the line contact between the vane tip and the rolling piston requires careful selection and control of materials to provide wear resistance and reliable long-term operation.
COMPRESSOR TROUBLESHOOTING
Refer to Figure 34 for a basic compressor troubleshoot­ing chart.
BASIC HERMETIC COMPRESSOR ELECTRICAL MEASUREMENTS
There are 2 basic electrical tests for hermetic compres­sors that will determine the electrical state of the mo­tor. The first test requires checking the electrical resistance of each of the electrical motor windings. The second test requires checking the electrical resistance of each of the electrical motor windings to ground. These tests may be accomplished by performing the following steps:
1. DISCONNECT ALL POWER TO THE UNIT.
2. Remove the unit chassis from the sleeve as detailed
in the GENERAL DISASSEMBLY section.
3. Open the control box as detailed in the GENERAL
DISASSEMBLY section, then locate, label, and re­move the 3 compressor wires from the following loca­tions: the RUN wire (BLACK) from the capacitor, the START wire (BLUE) from the capacitor. The third wire, COMMON wire (YELLOW) may be connected to one of the following locations: for SC units the wire is on the indoor thermostat, for SE Remote Control Units the wire is on the indoor frost ther­mostat, for all other SE Units the wire is located on the push button switch, for ALL SQ Units the wire is on the outdoor frost thermostat.
FIGURE 33 — ROTARY COMPRESSOR
COMPRESSION PROCESS
For compressors that are known to be dam­aged: Remove refrigerant prior to disconnecting com-
pressor wires. Damaged hermetic compressor terminals may become loose and eject from the com­pressor. Wear safety glasses and keep your face away from the area above the terminals when remov­ing compressor wires.
4. To measure the resistance between the windings of
the compressor motor, use a volt-ohmmeter set to the lowest ohm reading level then read and record the resistance between the RUN and START, START and COMMON, and RUN and COMMON wires. See Figure 35. The typical resistance readings will be about 4, 3, and 1 ohms respectively. The smaller values should add to equal the larger value. If this is not true then the compressor is likely shorted wind­ing to winding.
NOTE: The rotary compressor has the compressor over­load located under the terminal cover. If the overload is open it can show ohm readings that are infinite. The unit should be off for at least an hour to give this over­load time to reset if it is open.
17
Loading...
+ 39 hidden pages