The focus of this manual is to provide basic information
on service procedures, safety, troubleshooting, cleaning, and component replacement for service technicians. It is intended for use only by HVAC service
technicians who have successfully completed
instruction and received Type I Certification
from the U.S. Environmental Protection Agency.
The instructions in this manual are general in nature
and are not to be substituted for installation and service instructions shipped with the unit. No attempt to
install, ope rate, adju st, re pair , or di smant le any equi pment should be made until the manufacturer’s i nstructions are read and thoroughly understood by the
service technician. Even equipment that seems familiar may have specific model diffe rences from year to
year. Always review manufacturer’s instructions.
Model 52C,P packaged terminal air conditioner
(PTAC) and heat pump units are self-contained for
installation through the wall for individual room heating and cooling. The Model 52C,P polymer and metal
sleeves are permanently fastened to the wall; the unit
chassis slides out of the sleeve to allow the service
technician easy access. Many accessories are offered
to complement the unit’s performance and comfort
control.
Before beginning any service procedu res, it is important to check the unit model number. See Figure 1 and
2. Units that seem similar may have subtle differences
that could affect service procedures. The following
units are covered in this manual:
52CE — 60 Hz cooling with electric heat units
52CQ — 60 Hz heat pump with electric heat units
52PE — 60 Hz cooling with electric heat units
52PQ — 60 Hz heat pump with electric heat units
52PC — 60 Hz cooling only units
Knowing which model is being serviced will help determine if the unit is performing at optimum levels. The
model number is located on the data informatio n plate
beneath the front panel of the unit. See Figure 1. The
data information plate also lis ts voltage ranges and
other important electric al information about the unit.
SUMMARY OF DANGERS, WARNINGS,
AND CAUTIONS
The terms DANGER, WARNING, and CAUTION have
specific meanings that identify the degree of hazard.
Typically in the HVAC industry, these specific meanings are:
There is an immediate hazard which WILL result
in severe personal injury or death.
Potential hazards or unsafe practices which
COULD result in minor personal injury or equipment damage.
FIGURE 1 — SAMPLE DATA INFORMATION
PLATE
Hazards or unsafe practices which COULD
result in severe personal injury or death.
2
52 PQ A 3 12 3 0 1 AA
Series Designation
PTAC (Packaged Terminal Air Conditioner)
CE – Cooling with Electric Heat
CQ – Heat Pump with Electric Heat
PC – Cooling Only
PE – Cooling with Electric Heat
PQ – Heat Pump with Electric Heat
Latest Revision
A – Z
Electric Heater Size
0 – No Heating (Cooling Only Model)
2 – 2.3 kW
3 – 3.4 kW
5 – 5.0 kW
This section includes common procedures for disassembly and re-assembly of u nit.
IMPORTANT: Follow manufacturer’s instructions when disassembling and re-assembling a
unit for cleaning, maintenance, or part replacement. When disassembling wiring, it is strongly
recommended that numbered stickers be
attached to identify leads and terminals to aid in
the re-assembly process. Always review safety
procedures prior to the start of a job.
Prior to servicing electrical equipment, disconnect all power to avoid electric shock! Tag all disconnects. Never alter cord or plug and do not use
extension cords.
TOOLS NEEDED
The following field-supplied items are recommended
for general disassembly of the unit:
• Flat head screw driver
5
•
/16-in. nut driver
• Safety glasses
• Needle nose pliers
REMOVE FRONT PANEL
NOTE: Before removing front panel, remove 2 locking
screws (if installed) located behind the filter handles.
Chassis Options
Blank or AA – Standard
CP – Corrosion Protection
RC – Wall Thermostat Control
RP – Wall Thermostat Control with
Corrosion Protection
Packaging
1 – Domestic
Non-Performance
Changes 0-9
Electrical Data
3 – 230/208-v, 60 Hz
4 – 265-v, 60 Hz
See Figure 3. If a lateral duct accessory is installed, the
plenum must be removed before removing the front
panel. Refer to Remove Lateral Duct Extension section
for removal instructions.
1. Grasp the front panel firmly at the center of the
top and bottom of the panel.
2. Pull the panel upward at the bottom and forward
at the top to release magnetic latches and partition
hooks. See Figure 4.
DISCONNECT POWER FOR
CORD-CONNECTED UNIT
1. Turn selector switch to OFF position.
2. Open the disconnect swi tch at main power supply.
Use proper Lockout and Tag procedures.
3. Unplug the unit service cord.
DISCONNECT POWER FOR
PERMANENTLY CONNECTED
(HARDWIRED) UNITS
1. Turn selector switch to OFF position.
2. Open the disconnect swi tch at main power supply.
Use proper Lockout and Tag procedures.
3. Remove screw from access cover and remove
access cover.
4. Pull out the plug assembly and disconnect. See
Figure 5.
3
52C,P
SERIES
OPEN THE CONTROL BOX
The control box is factory wired. To open the box,
remove the 2 screws on the top of the control box and
lower the front hinged panel. See Figure 6.
REMOVE THE UNIT FROM THE
WALL SLEEVE
1. Remove the four moun tin g scr e ws tha t secu re th e
PTAC unit to the wall sleeve (2 screws per side).
See Figure 7.
2. Grasp the sides of the unit and slide it from the
sleeve.
NOTE: The mounting screws ma y be in a differen t
location depending on brand of wall sleeve
attached.
REMOVABLE
FILTER
LOCATION OF
REMOVED FILTER
LOCKING SCREW
(NOTE: 2nd LOCKING SCREW
IS LOCATED BEHIND
2nd FILTER)
FIGURE 3 — LOCATION OF LOCKING SCREWS
BEHIND FILTERS
FIGURE 4 — REMOVING FRONT PANEL
eplacement Package Terminal Air Conditioner,
LASSIFIED BY UNDERWRITERS LABORATOIES INC., AS TO ELECTRIC SHOCK, FIRE AND
ASUALTY HAZARDS ONLY. FOR FIELD INSTALATION WITH EXISTING WALL SLEEVES, OUT-
OOR, LOUVERS, AND INDOOR PANELS AS
PECIFIED ON THE PRODUCT.
The chassis weighs between 110 and 150 lbs. Take
proper safety precautions to avoid personal injury
when lifting and moving the chassi s.
The unit basepan may have water in it. Tilt the
unit back slightly whe n removing it fro m th e sl e eve
to drain some of the water into the sleeve.
CONDUIT
ACCESS
PANEL
MOLEX
PLUGS
FIGURE 5 — PLUG ASSEMBLY ON
HARDWIRE UNITS
4
POWER
GE WALL
SLEEVE
HOLES
AMANA, TRANE
(SLOTTED
HOLES) WALL
SLEEVE HOLES
VARIOUS ATTACHMENT
HOLE LOCATIONS
CARRIER, BRYANT
WALL SLEEVE
HOLES
CORD
ACCESS
COVER
POWER
CORD
FIGURE 6 — CONTROL BOX COVER
CONTROL
BOX
SCREWS
FIGURE 7 — PTAC UNIT TO WALL
SLEEVE MOUNTING SCREWS
ACCESSING INDOOR-AIR SECTION
COMPONENTS
REMOVE LATERAL DUCT EXTENSION
■
ACCESSORY FOR UNITS EQUIPPED WITH THE
LATERAL DUCT
1. Remove the 2 top screws that secure the lateral
2. Locate and remove the 2 bottom bracket screws
3. Carefully lift the plenum up and away from front
REMOVE THE DISCHARGE DECK ASSEMBLY
■
1. Remove the front panel. Re fer to Remove Front
2. Remove discharge screen screw using a
3. Remove th e dischar ge deck assembly screws using
4. Gently pull the deck/grille up and away from the
5. Reassemble by reversing steps above.
ACCESSING UNIT COMPONENTS
duct plenum to the top of the lateral duct extension. See Figure 8.
(located opposite extension duct) that secure the
lateral duct plenum to the bracket flange. See
Figure 8.
panel and duct extension.
Panel section and Figure 4.
5
/16-in. nut
driver. See Figure 9.
5
a
/16-in. nut driver. See Fi gure 9.
unit.
ACCESSING THE HEATER ASSEMBLY
■
— Once the
discharge deck assembly is removed, the Heater
Assembly should now be accessible. See Figure 10.
1. Using pliers, carefully remove all wires connected
to the heater assembl y. Label ea ch wire for ea se of
re-assembly.
2. Gently pull the heater assembly up and away
from scroll. See Figure 11.
3. Reassemble by reversing steps above.
ACCESSING OUTDOOR-AIR SECTION
COMPONENTS
REMOVE THE GUSSETS (See Figure 12)
■
1. Remove the 2 screws on each side that secure the
gussets to the partition.
2. Remove the 2 screws that secure the gussets to
the plastic condenser orifice and remove the
gussets.
5
52C,P
SERIES
END CAP
BRACKET
SCREWS
PLENUMLATERAL DUCT
LEFT
BRACKET
TOP
SCREWS (2)
EXTENSION
RIGHT
BRACKET
FIGURE 8 — PTAC UNIT WITH LATERAL
DUCT ACCESSORY INSTALLED
ATTACHMENT
SCREWS
WALL
BRACKET
SCREWS
DISCHARGE DECK
FIGURE 10 — ACCESSING HEAT ER
HEATER PLATE
ASSEMBLY
PLATE ASSEMBLY
DISCHARGE
SCREEN
DISCHARGE
DECK
FIGURE 9 — LOCATION OF ATTACHMENT
SCREWS ON DISCHARGE DECK OF UNIT
DETACH THE CONDENSER ORIFICE FROM THE
■
CONDENSER COIL
1. Remove top half of condenser orifice.
a. Unscrew the top half of the condens er orifi ce b y
backing off the 4 captive screws. See Figure 13.
b. Using a flat head screwdriver, gently pry the
top half of the orifice from the tube sheets. See
Figure 14.
c. Remove top of condenser orifice. See Figure 15.
2. Remove bottom half of condenser orifice.
a. Using a flat head screwdriver, gently pry the
bottom half of the orifice from the tube sheets.
See Figure 14.
b. Remove 2 outdoor coil tube sheet screws using a
Phillips head screwdriver. See Figure 16.
c. Carefully lift condenser up and away from con-
denser fan. Rest con d e nse r on bas epan . Se e
Figure 17.
FIGURE 11 — REMOVAL OF HEATER
PLATE ASSEMBLY
d. Using Needle Nose Pliers remove co ndenser fan
hub clamp. See Figure 18.
e. Pull condenser fan off fan motor shaft.
f. Remove bottom half of condenser orifice.
3. Reassemble by reversing steps above.
REMOVE THE AIR DISCHARGE GRILLE
■
1. Remove the front panel from the unit, reference
Remove Front Panel section.
2. Flip the front panel over to the backside. Remove
the 2 screws on each end of the air discharge grille
and remove grille. See Figure 19.
The grille can be positioned to direct the
discharge air up or out by simply rotating
the grille 180 degrees.
6
GUSSET
GUSSET
SCREWS
CONDENSER
ORIFICE (PLASTIC)
PARTITIONGUSSET
GUSSET
SCREWS
FIGURE 12 — GUSS ET RE M O VAL
CONDENSER
ORIFICE
CAPTIVE
SCREWS (2)
CAPTIVE
SCREWS (2)
FIGURE 13 — LOCATION OF CAPTIVE SCREWS
ON CONDENSER ORIFICE
FIGURE 14 — PRYING CONDENSER ORIFICE
AWAY FROM TUBE SHEET
FIGURE 15 — REMOVING TOP OF
CONDENSER ORIFICE
7
52C,P
SERIES
OUTDOOR COIL TUBE
SHEET SCREWS
FIGURE 16 — LOCATION OF OUTDOOR
COIL TUBE SHEET SCREWS
CONDENSER
FAN
HUB CLAMP
FIGURE 18 — REMOVING COND EN SER
FAN HUB CLAMP
FIGURE 17 — REMOVING OUTDOOR COIL
FROM CONDENSER FAN
CONTROL DOOR
HINGE PINS
FRONT PANEL
(BACK VIEW)
SCREWSCREW
DISCHARGE
GRILLE
FIGURE 19 — LOCATION OF SCREWS ON
DISCHARGE GRILLE
REINSTALL FRONT PANEL
1. Grasp the front panel firmly at the center of the
top and bottom of the panel, tilti ng it fo rwar d 5 to
10 degrees from the vertical. See Figure 4.
2. Place the top of the front panel onto the unit,
making sure the top engagement posts have
engaged the slots on the unit. The top edge of the
front panel should be flat against the top of the
unit.
3. Gently lower the front panel onto the chassis,
ensuring the conduit/cord is routed through the
panel notch. Magnetic latches at the bottom of the
front panel will secure the front panel to the unit.
8
GENERAL CLEANING
Maintaining proper performance of 52C,P systems
requires conscientious cleaning and care of components. See Figure 20. Specific components require
periodic cleaning and/or replacement, including the
following:
COMPONENT CLEANING SCHEDULE
Indoor Air Filter
Vent Air Filter
Indoor Coil
Indoor Fan
Outdoor Coil
Monthly
Monthly
Seasonally
Seasonally
Seasonally
CLEANING AND SAFETY
Before starting to clean a unit, read the instructions
thoroughly and gather the necessary tools for the job.
Review all safety information on unit and in literature.
Before cleaning, servicing, performing maintenance,
or removing the chassis from the wall sleeve, disconnect all power to the unit to avoid the possibility of
electrical shock and personal injury. Only trained
and qualified service personnel should perform
installation and service procedures on these units.
Untrained personnel may perform basic maintenance tasks such as cleaning and replacing filters.
Refer to General Disassembly section of this ma nual
for proper procedures to disconnect power to 52C,P
units.
Consider the following safety issues before
beginning:
• New and unfamiliar tasks should be performed
under the supervision of an experienced service
technician.
• Personal protective equipment, such as safety
glasses and work gloves, should be used.
• The floor around the work area shoul d be clea n and
free of debris.
• The 52C,P unit weighs up to 150 pounds. Use a lifting device or ask for assistance if the unit must be
moved.
• Make sure tools are the correct tools for the job,
and that they are working properly and in good
condition.
FRONT
PANEL
(STANDARD)
CHASSIS
(STANDARD)
FIGURE 20 — STANDARD 52C UNIT
EXTERIOR
GRILLE
(ACCESSORY)
WALL SLEEVE
(ACCESSORY)
9
52C,P
SERIES
TOOLS NEEDED
The following list includes the recommended tools,
devices, and cleaning solutions for use in cleaning the
52C,P unit and components.
should be cleaned once per month. Filt ers tha t are not
cleaned become clogged and will restrict airflow. This
may lead to major component damage. If a filter
becomes torn, has holes, or other damage, replace it
with a new one. Replacement filters are available
through Carrier Finished Goods and Carrier Replacement Component Division.
CLEANING THE INDOOR AIR FILTER
■
filters are located in the unit’s front panel. To remove
each filter simply grasp each filter handle with both
hands and gently pull the filter up and away from the
unit. See Figure 21.
or Soft Plastic Bristle Brush
Mild Household Detergent
Phillips Head Screwdriver
5
/16-in. Nut Driver
Flat Head Screw Driver
Needle Nose Pliers, 90° Bend
Tank Sprayer (Part No. P9021001) or
Compressed Air Tank
Clean Water Supply
Indoor Air Filter Replacement
(Part No. AIR-FILTER-10PK)
10-in. by 29-in. Piece of Clean Cardboard
Clean Cloth
Safety Glasses
Protective Gloves
— The indoor and vent air filters
— Two air
REPLACING THE INDOOR AIR FILT ER
■
—
Remove the indoor air filter as detailed in Cleaning
the Indoor Air Filter. If damaged, use a filter replacement with the Carrier Part No. AIR-FILTER-10PK,
available through Carrier Finished Goods and Carrier
Replacement Component Division.
NOTE: Both filters are completely interchangeable.
CLEANING THE OUTDOOR AIR VENT FILTER
■
1. Remove the unit chassis from wall sleeve as
described in the General Disassembly section of
this manual. Refer to Remove the Unit from the Wall Sleeve section.
2. Swing open vent door. The filter is located directly
behind the vent door. See Figure 22.
3. Once the filter is accessed, it may be cleaned using
either a vacuum cleaner, or a soft bristle brush
and a small amount of mild dish detergent. If
detergent is used, remove detergent residue with
a gentle, clean water stream. Allow the filter to
air dry.
REPLACING THE OUTDOOR AIR VENT FIL TER —
■
If vent filter requires replacement:
1. Open vent door to access vent filter.
2. Remove vent door from hinges.
3. Using a small flat head screwdriver, pry the filter
from the partition.
4. Replace vent filter using Carrier Part No.
52CQ500144.
5. Reverse Steps 1-3 to reattach vent door.
■
CHASSIS
Occasional cleaning of the e xterior surfaces of the
PTAC unit optimizes the unit’s appearance and
removes particles that may enter the air system. See
Figure 23. Mild detergents clean and reduce electrostatic charges on the plastic components of the PTAC
unit.
Use a clean cloth or brush to gently wipe exterior s urfaces. Be careful not to push dirt or other fibers into
the unit’s interior components. Accessible wall sleeve
surfaces should also be wiped clean.
10
SEASONAL CLEANING
VENT DOOR
OUTDOOR
AIR FILTER
The indoor and outdoor coils should be cleaned at least
once during every season. Refer to ACCESSING UNIT COMPONENTS section to prepare unit.
CLEANING THE INDOOR AND OUTDOOR
■
COILS
Coil fins are sharp and may cut hands. Wear heavy
protective gloves when cleaning coils.
Use only cleaning solutions that meet local codes.
1. Use a vacuum cleaner or soft bristle brush to
remove surface fibers and dirt from the interior
surface of evaporator coil and both surfaces of condenser coil. See Figure 24. It is important to apply
the tool in the same direction of the fins, not
against them. Applying the tool against the fins
may cause damage (fin edges may bend over).
2. With a tank sprayer or a trigger spray extension
tube, spray coil cleaning solution evenly across
the coils, making sure coils are thoroughly saturated. See Figure 25. Refer to instructions on the
cleaning solution containers for best results. Do
not use a high-pressure sprayer.
3. Rinse the coils thoroughly with low-velocity, clean
warm water (less than 200 F).
4. Repeat steps 2 and 3 for each coil surface.
5. Drain water and cleaning solution that may have
collected in the basepan during the cleaning process by carefully tilting the chassis. This allows
excess water to flow out of the overflow notches.
Do not set unit on end to drain water from basepan,
or at any other time. Oil will drain from the compressor sump, which could cause compressor failure.
6. Thoroughly clean t he base pan an d drain pa ssages
by rinsing with clean water. Be sure all debris is
removed from the drain valve. Se e Fig ure 26.
7. Thoroughly clean outdoor fan assembly and all
other mechanical components located in outdoor
coil area. Be sure to remove all dirt and debris.
8. Clean wall sleeve.
CLEANING THE INDOOR FAN AND FAN
■
SCROLL —
Dried debris and build-up on the blower
wheel and fan scroll can reduce the efficiency of the
unit.
1. ACCESS AND CLEAN INDOOR FAN AND
FAN SCROLL
a. Reach behind the indoor coil and vacuum any
loose debris from the condensat e drai n pan, fan
and other areas accessible to the fan scroll,
being careful to avoid damage to the coil fins.
b. Use mild detergent and a damp cl oth to remov e
stubborn debris from surfaces around scroll and
fan blades.
2. CLEAN HEATER ASSEMBLY — Use compressed air to blow off any dirt or dust that has
accumulated on the heater coils.
NOTE: Do not direct air at the bi-metal discs on
the temperature limiter switches.
FIGURE 21 — LOCATION OF
TWO-PIECE INDOOR FILTER
FIGURE 22 — LOCATION OF OUTDOOR AIR
VENT FILTER
11
52C,P
SERIES
FIGURE 23 — PTAC EXTERIOR SURFACES
FIGURE 25 — CLEANING COILS
FIGURE 24 — VACUUMING EVAPORATOR
COIL
DRAIN VALVE
FIGURE 26 — BASEPAN SECTION
12
COMPRESSOR
A cutaway view of the rotary compressor with key
components labeled is shown in Figure 27. The motor
stator is rigidly attached to the compressor shell. The
rotor is pressed onto the eccentric shaft, which is supported by 2 bearings. Both the discharge valve and discharge muffler are attached to the motor bearing. The
DISCHARGE TUBE
SUCTION INLET
pump bearing provides a thrust surface for the shaft
and the rolling piston. Compressed gas is separated
from the suction gas by the vane. Discharge gas pressure and the vane spring keep the vane in contact with
the rolling piston.
SHELL
STAT OR
SUCTION MUFFLER/
ACCUMULATOR
PISTON
VANE
OIL TUBE
ECCENTRIC SHAFT
ROTOR
MOTOR BEARING
DISCHARGE MUFFLER
DISCHARGE VALVE
CYLINDER
PUMP BEARING
MOUNTING PLATE
FIGURE 27 — ROTARY COMPRESSOR COMPONENTS
13
52C,P
SERIES
The rotary compression process (Figure 28), starts at
top dead center as shown in (1). Suction gas flows
through the suction inlet and into the cylinder area.
As the shaft rotates through 90 degrees, the rolling
piston moves to positio n A as shown in (2). The su ction
volume is now the area defined by point A and the tip
of the vane. Gas in the remaining volume has been
compressed above suction pressure. After another
90 degrees of shaft rotation, the rolling piston has
moved to position B as shown in (3 ). Both the compressed gas and suction gas volumes are now equal.
Another 90 degrees of shaft rotation is shown in (4 ).
Compressed gas has reached a pressure sufficient to
open the discharge valve, and flows from the cylinder
into the compressor shell. After another 90 degrees of
shaft rotation, the entire process begins again. Continuous suction and discharge allows for a smooth compression process.
The rolling piston is not in actual contact with the cylinder wall, vane, or bearing faces. Hydrodynamic sealing prevents leakage from the compressed gas volume
to the suction volume via these paths. Precise control
of machining tolerances, surfaces, finishes, and assembly clearances is critical to achieve high efficiency performance. In addition, the line contact between the
vane tip and the rolling piston requires careful selection and control of materials to provide wear resistance and reliable long-term operation.
BASIC HERMETIC COMPRESSOR
ELECTRICAL MEASUREMENTS
There are 2 basic electrical te st s for herme tic compres sors that will determine the electrical state of the
motor. The first test requires checking the electrical
resistance of each of the electric al motor windin gs. The
second test requires checking the electrical resistance
of each of the electrical motor windings to ground.
These tests may be accomplished by performing the
following steps:
1. DISCONNECT ALL POWER TO THE UNIT.
2. Remove the unit chassis from the sleeve as
detailed in the UNIT DISASSEMBLY section.
3. Open the control box as detailed in the UNITDISASSEMBLY section, then locate, label, and
remove the 3 compressor wires from the following
locations: the RUN wire (BLACK) from the capacitor, the START wire (BLUE) from the capacitor.
The third wi re, C OM M O N wire (YELLOW ) ma y
be connected to one of the following locations: for
PC units the wire is on the indoor thermostat,
for CE, PE Remote Control Units the wi r e is on the RC Control Board, for all other CE, PE
Units the wire is located on the rotary selector
switch. For ALL CQ, PQ Units the wire is on the
outdoor frost thermostat.
COMPRESSOR TROUBLESHOOTING
Refer to Figure 29 for a basic compressor troubleshooting chart.
FIGURE 28 — ROTARY COMPRESSOR
COMPRESSION PROCESS
For compressors that are known to be damaged: Remove refrigerant prior to disconnecting
compressor wires. Damaged hermetic compressor
terminals may become loose a nd eject f rom the compressor. Wear safety glasses and keep your face
away from the area above the terminals when
removing compressor wires.
4. Perform a shorted/open windings test to measure
the resistance between the windings of the compressor motor. Use a volt-ohmmeter set to the
lowest ohm reading level then read and record the
resistance between the RUN and START, START
and COMMON, and RUN and COMMON wires.
See Figure 30. The typical resistance readings will
be about 4, 3, and 1 ohms respectively. The
smaller values should add to equal the larger
value. If this is not true then the compressor is
likely shorted winding to winding.
NOTE: The rotary compressor has the compressor
overload located under the terminal cover. If the overload is open it can show ohm readings that are infinite.
The unit should be off for at least an hour to give this
overload time to reset if it is open.
14
POSSIBLE CAUSE
COILS/FILTERS DIRTY OR PLUGGED
AIR OR NONCONDENSABLE GASES
IN SYSTEM
SYSTEM REFRIGERANT OVERCHARGED
DISCHARGE LINE RESTRICTED
CAPILLARY TUBE OR STRAINER
RESTRICTED OR PLUGGED
FAN BLADE OR MOTOR DEFECTIVE
FAN BLADE OR BLOWER WHEEL STUCK
SYSTEM REFRIGERANT UNDERCHARGED
EVAPORATOR AIRFLOW RECIRCULATION
UNIT OVERSIZED FOR APPLICATION
COMPRESSOR REQUIRES START ASSIST
NO POWER TO UNIT
LOW VOLTAGE TO UNIT
OVERLOAD PROTECTOR OPEN
OVERLOAD PROTECTOR INCORRECT
OR DEFECTIVE
CAPACITOR INCORRECT OR DEFECTIVE
THERMOSTAT CONTACTS ARE OPEN
THERMOSTAT IS SET TOO HIGH OR LOW
SELECTOR SWITCH IS OPEN
OR DEFECTIVE
WIRING IS INCORRECT OR DEFECTIVE
SYSTEM PRESSURES NOT EQUALIZED
COMPRESSOR MOTOR OR
5. Next, perform a grounded windings test to test
the resistance individually of each wire to the
shell of the compressor. The paint on t he compres sor can prevent good contact between the probe
and the metal. The paint should be removed from
a small section of th e shell of the compressor to
ensure good contact by the meter probe. The voltohmmeter should be set to at least the 100X ohm
level. The measured resistance between each wire
and ground should be infinite or O.L. on the
readout. If there is measurable resistance one of
the windings is likely shorted to ground. See
Figure 31.
6. A compressor that has a winding to winding short
or a winding to compressor shell short is electrically failed and needs to be replaced. See the
Compressor Replacement section for details.
COMPRESSOR REPLACEMENT
Before working on the compressor, read the instructions thoroughly and gather t he necessar y tools fo r the
job. Review all safety information on unit and in literature. Always turn off all power to unit to avoid the
possibility of electrical shock.
Consider the following safety issues before
beginning:
• New and unfamiliar tasks should be performed
under the supervision of an experienced service
technician.
• Personal protective equipment, such as work gloves
and safety glasses, should be worn.
• The floor around the work area should be clean and
free of debris.
• Make sure tools are th e cor r ect to ol s for the jo b a nd
that they are working properly and in good condition.
• Never replace a blown fuse without correcting the
cause of the original fail u re. If thermally operated
circuit breakers or overloads are tripping, make
sure the trip is not due to excessi vely high temperatures or loose connections.
• When brazing suction and discharge lines, cool the
lines with a damp, clean cloth to prevent injury.
• Oil may be present in the compressor accumulator
and interconnecting tubing. Use caution when
removing tubing.
15
52C,P
SERIES
FIGURE 30 — SHORTED/OPEN WINDINGS TEST
FIGURE 31 — GROUNDED WINDINGS TEST
REMOVING THE COMPRESSOR
■
— Follow the
steps below to remove the compressor:
1. Disconnect all power to unit.
2. Remove unit from wall sleeve as detailed in the
UNIT DISASSEMBLY section. The unit weighs
up to 150 pounds. Seek assistance or use a lifting
device when removing unit from wall sleeve.
3. If the unit is a heat pump: Disconnect the wire
plug on the reversing valve solenoid and carefully
remove the outdoor thermostat capillary from the
outdoor coil. See Figure 32.
4. Attach the piercing va lve to the suction side process tube below the crimps. Attach Carrier
TOTALTEST® kit (Part No. TT1-001), to the
piercing valve to verify acidity of the s ystem. After
verifying the system acidity, remove the refrigerant using a certified refrigerant recovery system.
5. When all the refrigerant has been recovered,
remove the terminal cover from the compressor
with a nut driver. Disconnect th e 3 wire s from the
compressor and label the location of each. Once
the wires are labeled, replace the terminal cover
to protect the compressor terminals.
6. Remove the air system components by following
the procedure detailed in the ACCESSING UNIT COMPONENTS section.
7. Remove the piercing valve and cut the crimped
portion of both process tubes off with a small tubing cutter. Braze an access valve on each process
tube. Using a torch, disconnect the suction and
discharge tubes from the compressor connections.
8. Remove the compressor mounting bolts, and
remove the compressor.
For compressors that are known to be damaged: Remove refrigerant prior to disconnecting
compressor wires. Damaged hermetic compressor
terminals may become l oos e and eje ct f r om the compressor. Wear safety glasses and keep your face
away from the area above the terminals when
removing compressor wires.
TOOLS NEEDED
■
— The following list inclu des the
recommended tools and devices for removing and
replacing the compressor.
1
/2-in. and 3/8-in. Tube Benders
1
/2-in. Nut Driver
5
/16-in. Nut Driver
Flat Head Screwdriver
Piercing Valve
2 Parker Access Valves (Part No. AVUSE-5)
Pinch Off Tool
Filter Drier — All Units (Part No. P504-80845)
Carrier TOTALTEST Kit (Part No. TT1-001)
Totalclaim System
Charging Cylinder or an Electronic Scale
Refrigerant-22
Tubing Cutter
To rch
Nitrogen Cylinder with Regulator
Strainers
Capillary Tubes
The compressor may still be hot from the brazing
process.
IMPORTANT: Any time the compressor is
replaced, the strainer and capillary tubes must
be removed and replaced also.
9. For all units: Remove and replace the strainer
and capillary tubes from the system. See Figure 32
for strainer and capillary tube location.
10. For Heat/Cool Units: Use an in-line filter drier
(P/N P504-80845). The filter drier can be installed
in any location in suction line. See Figure 33A for
general installation location.
For Heat Pump Units: Use an in-line filter drier
(P/N P504-80845) and install between the
reversing valve and the compressor accumulator. There are several suction tube configura-
tions and the in-line filter drier will be field piped
and brazed in to the su ction tube for your uni t. See
Figure 33B for a general installation location.
11. Remove the grommets from the existing compressor and install them onto the new compressor.
16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.