Carrier 52C, 52P User Manual

52C,P
SERIES
SERVICE TECHNICIAN GUIDE
PACKAGED TERMINAL AIR CONDITIONERS
AND HEAT PUMPS
CONTENTS
INTRODUCTION
SUMMARY OF DANGERS, WARNINGS,
AND CAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
UNIT DISASSEMBLY
TOOLS NEEDED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REMOVE FRONT P ANEL . . . . . . . . . . . . . . . . . . . . . . . 3
DISCONNECT POWER FOR
CORD-CONNECTED UNIT . . . . . . . . . . . . . . . . . . . . . 3
DISCONNECT POWER FOR PERMANE N TLY
CONNECTED (HARDWIRED) UNITS . . . . . . . . . . . . 3
OPEN THE CONTROL BOX. . . . . . . . . . . . . . . . . . . . . 4
REMOVE THE UNIT FROM THE W ALL SLEEVE . . 4
ACCESSING UNIT COMPONENTS
ACCESSING INDOOR-AIR SECTION
COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ACCESSING OUTDOOR-AIR SECTION
COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
REINSTALL FRONT PANEL. . . . . . . . . . . . . . . . . . . . . 8
GENERAL CLEANING
CLEANING AND SAFETY . . . . . . . . . . . . . . . . . . . . . . 9
TOOLS NEEDED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
MONTHLY CLEANING. . . . . . . . . . . . . . . . . . . . . . . . 10
SEASONAL CLEANING . . . . . . . . . . . . . . . . . . . . . . . 11
COMPRESSOR
COMPRESSOR TROUBLESHOOTING. . . . . . . . . . . 14
BASIC HERMETIC COMPRESSOR
ELECTRICAL MEASUREMENTS . . . . . . . . . . . . . . . 14
COMPRESSOR REPLACEMENT. . . . . . . . . . . . . . . . 15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,3
. . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
. . . . . . . . . . . . . .5-8
. . . . . . . . . . . . . . . . . . . . . . . . .9-12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-17
HEATERS
COMMON CAUSES OF HEATER FAILURE. . . . . . .18
HEATER REMOVAL . . . . . . . . . . . . . . . . . . . . . . . . . . .18
OPERATING CONTROLS
UNIT-MOUNTED CONTROLS. . . . . . . . . . . . . . . . . .20
WALL-MOUNTED THERMOSTAT CONTROLS. . . 21 REMOTE THERMOSTAT
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . .21
DESCRIPTION OF SELECTOR
SWITCH SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . .23
NON-USER ADJUSTABLE CONTROLS . . . . . . . . . .23
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . .24
COMPONENT OPERATION AND
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . .24
ELECTRICAL COMPONENTS REMOVAL
AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . .27
FAN MOTOR
FAN MOTOR TROUBLESHOOTING. . . . . . . . . . . . .29
BASIC FAN MOTOR ELECTRICAL TESTS. . . . . . . . 29
FAN MOTOR REPLACEMENT. . . . . . . . . . . . . . . . . .31
FIELD TEMPERATURE CHARTS WIRING DIAGRAMS MOST FREQUENT PTAC SERVICE
QUESTIONS ACCESSORIES 52C PERFORMANCE AND PHYSICAL DATA 52P PERFORMANCE AND PHYSICAL DATA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18,19
. . . . . . . . . . . . . . . . . . . . . 20-28
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-31
. . . . . . . . . . . . . . 32-40
. . . . . . . . . . . . . . . . . . . . . . . . 41-45
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
. . . . . .48
. . . . . .49
Page
PTAC Customer Support Center
1•800•894•6449
52C,P
CANADIAN INSTALLATION
SERIAL 3701X11520 DATE OF MFG. 09/12/2001 VOLT RANGE 187-253 VOLTS 230/208 PH 1
MODEL 52PQA312301AA
HZ
60
MIN CKT AMPACITY 19.3 R-22 OZ 34
DESIGN PSIG 350 HIGH SIDE, 150 LOW SIDE
COOLING
HEATING
BTU/HR 12,100/12,000 AMPS 4.8/5.3
WATTS 1090/1122 EER 11.1/10.7
MOTOR
FAN
COMP
HP
FLA
RLA LRA
6.1 29
0.75 1/8
BTU/HR 11,000/11,000 AMPS 15.6/14.5 WATTS 3570/2997 COP 3.2/3.2
HEATER
BTU/HR
AMPS 14.8/13.7 WATTS 3400/2850 WATER
STEAM
20
20
20
USE
TIME DELAY FUSE
OR HACR TYPE
CIRCUIT BREAKER
AMP
AMP AMP
MAX FUSE
MAX BREAKER
SERIES
INTRODUCTION
The focus of this manual is to provide basic information on service procedures, safety, troubleshooting, clean­ing, and component replacement for service techni­cians. It is intended for use only by HVAC service
technicians who have successfully completed instruction and received Type I Certification from the U.S. Environmental Protection Agency.
The instructions in this manual are general in nature and are not to be substituted for installation and ser­vice instructions shipped with the unit. No attempt to install, ope rate, adju st, re pair , or di smant le any equi p­ment should be made until the manufacturer’s i nstruc­tions are read and thoroughly understood by the service technician. Even equipment that seems famil­iar may have specific model diffe rences from year to year. Always review manufacturer’s instructions.
Model 52C,P packaged terminal air conditioner (PTAC) and heat pump units are self-contained for installation through the wall for individual room heat­ing and cooling. The Model 52C,P polymer and metal sleeves are permanently fastened to the wall; the unit chassis slides out of the sleeve to allow the service technician easy access. Many accessories are offered to complement the unit’s performance and comfort control.
Before beginning any service procedu res, it is impor­tant to check the unit model number. See Figure 1 and
2. Units that seem similar may have subtle differences that could affect service procedures. The following units are covered in this manual:
52CE — 60 Hz cooling with electric heat units 52CQ — 60 Hz heat pump with electric heat units 52PE — 60 Hz cooling with electric heat units 52PQ — 60 Hz heat pump with electric heat units 52PC — 60 Hz cooling only units
Knowing which model is being serviced will help deter­mine if the unit is performing at optimum levels. The model number is located on the data informatio n plate beneath the front panel of the unit. See Figure 1. The data information plate also lis ts voltage ranges and other important electric al information about the unit.
SUMMARY OF DANGERS, WARNINGS, AND CAUTIONS
The terms DANGER, WARNING, and CAUTION have specific meanings that identify the degree of hazard. Typically in the HVAC industry, these specific mean­ings are:
There is an immediate hazard which WILL result in severe personal injury or death.
Potential hazards or unsafe practices which COULD result in minor personal injury or equip­ment damage.
FIGURE 1 — SAMPLE DATA INFORMATION
PLATE
Hazards or unsafe practices which COULD result in severe personal injury or death.
2
52 PQ A 3 12 3 0 1 AA
Series Designation
PTAC (Packaged Terminal Air Conditioner)
CE – Cooling with Electric Heat CQ – Heat Pump with Electric Heat PC – Cooling Only PE – Cooling with Electric Heat PQ – Heat Pump with Electric Heat
Latest Revision
A – Z
Electric Heater Size
0 – No Heating (Cooling Only Model) 2 – 2.3 kW 3 – 3.4 kW 5 – 5.0 kW
Cooling Capacity (nominal)
07 – 7,000 Btuh 09 – 9,000 Btuh 12 – 12,000 Btuh 15 – 15,000 Btuh
FIGURE 2 — MODEL NUMBER NOMENCLATURE
UNIT DISASSEMBLY
This section includes common procedures for disas­sembly and re-assembly of u nit.
IMPORTANT: Follow manufacturer’s instruc­tions when disassembling and re-assembling a unit for cleaning, maintenance, or part replace­ment. When disassembling wiring, it is strongly recommended that numbered stickers be attached to identify leads and terminals to aid in the re-assembly process. Always review safety procedures prior to the start of a job.
Prior to servicing electrical equipment, discon­nect all power to avoid electric shock! Tag all dis­connects. Never alter cord or plug and do not use extension cords.
TOOLS NEEDED
The following field-supplied items are recommended for general disassembly of the unit:
• Flat head screw driver
5
/16-in. nut driver
• Safety glasses
• Needle nose pliers
REMOVE FRONT PANEL
NOTE: Before removing front panel, remove 2 locking screws (if installed) located behind the filter handles.
Chassis Options
Blank or AA – Standard
CP – Corrosion Protection RC – Wall Thermostat Control RP – Wall Thermostat Control with
Corrosion Protection
Packaging
1 – Domestic
Non-Performance
Changes 0-9
Electrical Data
3 – 230/208-v, 60 Hz 4 – 265-v, 60 Hz
See Figure 3. If a lateral duct accessory is installed, the plenum must be removed before removing the front panel. Refer to Remove Lateral Duct Extension section for removal instructions.
1. Grasp the front panel firmly at the center of the top and bottom of the panel.
2. Pull the panel upward at the bottom and forward at the top to release magnetic latches and partition hooks. See Figure 4.
DISCONNECT POWER FOR CORD-CONNECTED UNIT
1. Turn selector switch to OFF position.
2. Open the disconnect swi tch at main power supply. Use proper Lockout and Tag procedures.
3. Unplug the unit service cord.
DISCONNECT POWER FOR PERMANENTLY CONNECTED (HARDWIRED) UNITS
1. Turn selector switch to OFF position.
2. Open the disconnect swi tch at main power supply. Use proper Lockout and Tag procedures.
3. Remove screw from access cover and remove access cover.
4. Pull out the plug assembly and disconnect. See Figure 5.
3
52C,P
SERIES
OPEN THE CONTROL BOX
The control box is factory wired. To open the box, remove the 2 screws on the top of the control box and lower the front hinged panel. See Figure 6.
REMOVE THE UNIT FROM THE WALL SLEEVE
1. Remove the four moun tin g scr e ws tha t secu re th e PTAC unit to the wall sleeve (2 screws per side). See Figure 7.
2. Grasp the sides of the unit and slide it from the sleeve.
NOTE: The mounting screws ma y be in a differen t location depending on brand of wall sleeve attached.
REMOVABLE FILTER
LOCATION OF REMOVED FILTER
LOCKING SCREW (NOTE: 2nd LOCKING SCREW IS LOCATED BEHIND 2nd FILTER)
FIGURE 3 — LOCATION OF LOCKING SCREWS
BEHIND FILTERS
FIGURE 4 — REMOVING FRONT PANEL
eplacement Package Terminal Air Conditioner, LASSIFIED BY UNDERWRITERS LABORATO­IES INC., AS TO ELECTRIC SHOCK, FIRE AND ASUALTY HAZARDS ONLY. FOR FIELD INSTAL­ATION WITH EXISTING WALL SLEEVES, OUT-
OOR, LOUVERS, AND INDOOR PANELS AS
PECIFIED ON THE PRODUCT.
The chassis weighs between 110 and 150 lbs. Take proper safety precautions to avoid personal injury when lifting and moving the chassi s.
The unit basepan may have water in it. Tilt the unit back slightly whe n removing it fro m th e sl e eve to drain some of the water into the sleeve.
CONDUIT
ACCESS PANEL
MOLEX PLUGS
FIGURE 5 — PLUG ASSEMBLY ON
HARDWIRE UNITS
4
POWER
GE WALL SLEEVE HOLES
AMANA, TRANE (SLOTTED HOLES) WALL SLEEVE HOLES
VARIOUS ATTACHMENT
HOLE LOCATIONS
CARRIER, BRYANT WALL SLEEVE HOLES
CORD ACCESS COVER
POWER CORD
FIGURE 6 — CONTROL BOX COVER
CONTROL BOX SCREWS
FIGURE 7 — PTAC UNIT TO WALL
SLEEVE MOUNTING SCREWS
ACCESSING INDOOR-AIR SECTION COMPONENTS
REMOVE LATERAL DUCT EXTENSION
ACCESSORY FOR UNITS EQUIPPED WITH THE LATERAL DUCT
1. Remove the 2 top screws that secure the lateral
2. Locate and remove the 2 bottom bracket screws
3. Carefully lift the plenum up and away from front
REMOVE THE DISCHARGE DECK ASSEMBLY
1. Remove the front panel. Re fer to Remove Front
2. Remove discharge screen screw using a
3. Remove th e dischar ge deck assembly screws using
4. Gently pull the deck/grille up and away from the
5. Reassemble by reversing steps above.
ACCESSING UNIT COMPONENTS
duct plenum to the top of the lateral duct exten­sion. See Figure 8.
(located opposite extension duct) that secure the lateral duct plenum to the bracket flange. See Figure 8.
panel and duct extension.
Panel section and Figure 4.
5
/16-in. nut
driver. See Figure 9.
5
a
/16-in. nut driver. See Fi gure 9.
unit.
ACCESSING THE HEATER ASSEMBLY
— Once the discharge deck assembly is removed, the Heater Assembly should now be accessible. See Figure 10.
1. Using pliers, carefully remove all wires connected to the heater assembl y. Label ea ch wire for ea se of re-assembly.
2. Gently pull the heater assembly up and away from scroll. See Figure 11.
3. Reassemble by reversing steps above.
ACCESSING OUTDOOR-AIR SECTION COMPONENTS
REMOVE THE GUSSETS (See Figure 12)
1. Remove the 2 screws on each side that secure the gussets to the partition.
2. Remove the 2 screws that secure the gussets to the plastic condenser orifice and remove the gussets.
5
52C,P
SERIES
END CAP
BRACKET SCREWS
PLENUM LATERAL DUCT
LEFT BRACKET
TOP SCREWS (2)
EXTENSION
RIGHT BRACKET
FIGURE 8 — PTAC UNIT WITH LATERAL
DUCT ACCESSORY INSTALLED
ATTACHMENT SCREWS
WALL
BRACKET SCREWS
DISCHARGE DECK
FIGURE 10 — ACCESSING HEAT ER
HEATER PLATE ASSEMBLY
PLATE ASSEMBLY
DISCHARGE SCREEN
DISCHARGE DECK
FIGURE 9 — LOCATION OF ATTACHMENT
SCREWS ON DISCHARGE DECK OF UNIT
DETACH THE CONDENSER ORIFICE FROM THE
CONDENSER COIL
1. Remove top half of condenser orifice. a. Unscrew the top half of the condens er orifi ce b y
backing off the 4 captive screws. See Figure 13.
b. Using a flat head screwdriver, gently pry the
top half of the orifice from the tube sheets. See Figure 14.
c. Remove top of condenser orifice. See Figure 15.
2. Remove bottom half of condenser orifice. a. Using a flat head screwdriver, gently pry the
bottom half of the orifice from the tube sheets. See Figure 14.
b. Remove 2 outdoor coil tube sheet screws using a
Phillips head screwdriver. See Figure 16.
c. Carefully lift condenser up and away from con-
denser fan. Rest con d e nse r on bas epan . Se e Figure 17.
FIGURE 11 — REMOVAL OF HEATER
PLATE ASSEMBLY
d. Using Needle Nose Pliers remove co ndenser fan
hub clamp. See Figure 18. e. Pull condenser fan off fan motor shaft. f. Remove bottom half of condenser orifice.
3. Reassemble by reversing steps above.
REMOVE THE AIR DISCHARGE GRILLE
1. Remove the front panel from the unit, reference Remove Front Panel section.
2. Flip the front panel over to the backside. Remove the 2 screws on each end of the air discharge grille and remove grille. See Figure 19.
The grille can be positioned to direct the discharge air up or out by simply rotating the grille 180 degrees.
6
GUSSET
GUSSET SCREWS
CONDENSER ORIFICE (PLASTIC)
PARTITION GUSSET
GUSSET SCREWS
FIGURE 12 — GUSS ET RE M O VAL
CONDENSER ORIFICE
CAPTIVE SCREWS (2)
CAPTIVE SCREWS (2)
FIGURE 13 — LOCATION OF CAPTIVE SCREWS
ON CONDENSER ORIFICE
FIGURE 14 — PRYING CONDENSER ORIFICE
AWAY FROM TUBE SHEET
FIGURE 15 — REMOVING TOP OF
CONDENSER ORIFICE
7
52C,P
SERIES
OUTDOOR COIL TUBE SHEET SCREWS
FIGURE 16 — LOCATION OF OUTDOOR
COIL TUBE SHEET SCREWS
CONDENSER FAN
HUB CLAMP
FIGURE 18 — REMOVING COND EN SER
FAN HUB CLAMP
FIGURE 17 — REMOVING OUTDOOR COIL
FROM CONDENSER FAN
CONTROL DOOR HINGE PINS
FRONT PANEL (BACK VIEW)
SCREW SCREW
DISCHARGE GRILLE
FIGURE 19 — LOCATION OF SCREWS ON
DISCHARGE GRILLE
REINSTALL FRONT PANEL
1. Grasp the front panel firmly at the center of the top and bottom of the panel, tilti ng it fo rwar d 5 to 10 degrees from the vertical. See Figure 4.
2. Place the top of the front panel onto the unit, making sure the top engagement posts have engaged the slots on the unit. The top edge of the front panel should be flat against the top of the unit.
3. Gently lower the front panel onto the chassis, ensuring the conduit/cord is routed through the panel notch. Magnetic latches at the bottom of the front panel will secure the front panel to the unit.
8
GENERAL CLEANING
Maintaining proper performance of 52C,P systems requires conscientious cleaning and care of compo­nents. See Figure 20. Specific components require periodic cleaning and/or replacement, including the following:
COMPONENT CLEANING SCHEDULE
Indoor Air Filter
Vent Air Filter
Indoor Coil Indoor Fan
Outdoor Coil
Monthly
Monthly Seasonally Seasonally Seasonally
CLEANING AND SAFETY
Before starting to clean a unit, read the instructions thoroughly and gather the necessary tools for the job. Review all safety information on unit and in literature.
Before cleaning, servicing, performing maintenance, or removing the chassis from the wall sleeve, discon­nect all power to the unit to avoid the possibility of electrical shock and personal injury. Only trained and qualified service personnel should perform installation and service procedures on these units. Untrained personnel may perform basic mainte­nance tasks such as cleaning and replacing filters. Refer to General Disassembly section of this ma nual for proper procedures to disconnect power to 52C,P units.
Consider the following safety issues before beginning:
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as safety glasses and work gloves, should be used.
• The floor around the work area shoul d be clea n and free of debris.
• The 52C,P unit weighs up to 150 pounds. Use a lift­ing device or ask for assistance if the unit must be moved.
• Make sure tools are the correct tools for the job, and that they are working properly and in good condition.
FRONT PANEL (STANDARD)
CHASSIS (STANDARD)
FIGURE 20 — STANDARD 52C UNIT
EXTERIOR GRILLE (ACCESSORY)
WALL SLEEVE (ACCESSORY)
9
52C,P
SERIES
TOOLS NEEDED
The following list includes the recommended tools, devices, and cleaning solutions for use in cleaning the 52C,P unit and components.
Vacuum Cleaner with Crevice Tool Attachment,
Lifting Device (or another person for assistance)
Trigger Spray Extension Tube (Part No. P9029000)
Vent Air Filter Replacement (Part No. 52CQ500144)
Condenser Coil Cleaning Solution (Part No. P9020501)
Evaporator Coil Cleaning Solution (Part No. P90221001)
3% Solution of Hydrogen Peroxide in Spray Bottle
MONTHLY CLEANING
AIR FILTERS
should be cleaned once per month. Filt ers tha t are not cleaned become clogged and will restrict airflow. This may lead to major component damage. If a filter becomes torn, has holes, or other damage, replace it with a new one. Replacement filters are available through Carrier Finished Goods and Carrier Replace­ment Component Division.
CLEANING THE INDOOR AIR FILTER
filters are located in the unit’s front panel. To remove each filter simply grasp each filter handle with both hands and gently pull the filter up and away from the unit. See Figure 21.
or Soft Plastic Bristle Brush
Mild Household Detergent Phillips Head Screwdriver
5
/16-in. Nut Driver
Flat Head Screw Driver
Needle Nose Pliers, 90° Bend
Tank Sprayer (Part No. P9021001) or
Compressed Air Tank
Clean Water Supply
Indoor Air Filter Replacement
(Part No. AIR-FILTER-10PK)
10-in. by 29-in. Piece of Clean Cardboard
Clean Cloth
Safety Glasses
Protective Gloves
— The indoor and vent air filters
Two air
REPLACING THE INDOOR AIR FILT ER
Remove the indoor air filter as detailed in Cleaning the Indoor Air Filter. If damaged, use a filter replace­ment with the Carrier Part No. AIR-FILTER-10PK, available through Carrier Finished Goods and Carrier Replacement Component Division.
NOTE: Both filters are completely interchangeable.
CLEANING THE OUTDOOR AIR VENT FILTER
1. Remove the unit chassis from wall sleeve as described in the General Disassembly section of this manual. Refer to Remove the Unit from the Wall Sleeve section.
2. Swing open vent door. The filter is located directly behind the vent door. See Figure 22.
3. Once the filter is accessed, it may be cleaned using either a vacuum cleaner, or a soft bristle brush and a small amount of mild dish detergent. If detergent is used, remove detergent residue with a gentle, clean water stream. Allow the filter to air dry.
REPLACING THE OUTDOOR AIR VENT FIL TER —
If vent filter requires replacement:
1. Open vent door to access vent filter.
2. Remove vent door from hinges.
3. Using a small flat head screwdriver, pry the filter from the partition.
4. Replace vent filter using Carrier Part No. 52CQ500144.
5. Reverse Steps 1-3 to reattach vent door.
CHASSIS
Occasional cleaning of the e xterior surfaces of the PTAC unit optimizes the unit’s appearance and removes particles that may enter the air system. See Figure 23. Mild detergents clean and reduce electro­static charges on the plastic components of the PTAC unit.
Use a clean cloth or brush to gently wipe exterior s ur­faces. Be careful not to push dirt or other fibers into the unit’s interior components. Accessible wall sleeve surfaces should also be wiped clean.
10
SEASONAL CLEANING
VENT DOOR
OUTDOOR AIR FILTER
The indoor and outdoor coils should be cleaned at least once during every season. Refer to ACCESSING UNIT COMPONENTS section to prepare unit.
CLEANING THE INDOOR AND OUTDOOR
COILS
Coil fins are sharp and may cut hands. Wear heavy protective gloves when cleaning coils.
Use only cleaning solutions that meet local codes.
1. Use a vacuum cleaner or soft bristle brush to remove surface fibers and dirt from the interior surface of evaporator coil and both surfaces of con­denser coil. See Figure 24. It is important to apply the tool in the same direction of the fins, not against them. Applying the tool against the fins may cause damage (fin edges may bend over).
2. With a tank sprayer or a trigger spray extension tube, spray coil cleaning solution evenly across the coils, making sure coils are thoroughly satu­rated. See Figure 25. Refer to instructions on the cleaning solution containers for best results. Do
not use a high-pressure sprayer.
3. Rinse the coils thoroughly with low-velocity, clean warm water (less than 200 F).
4. Repeat steps 2 and 3 for each coil surface.
5. Drain water and cleaning solution that may have collected in the basepan during the cleaning pro­cess by carefully tilting the chassis. This allows excess water to flow out of the overflow notches.
Do not set unit on end to drain water from basepan, or at any other time. Oil will drain from the com­pressor sump, which could cause compressor failure.
6. Thoroughly clean t he base pan an d drain pa ssages by rinsing with clean water. Be sure all debris is removed from the drain valve. Se e Fig ure 26.
7. Thoroughly clean outdoor fan assembly and all other mechanical components located in outdoor coil area. Be sure to remove all dirt and debris.
8. Clean wall sleeve.
CLEANING THE INDOOR FAN AND FAN
SCROLL —
Dried debris and build-up on the blower wheel and fan scroll can reduce the efficiency of the unit.
1. ACCESS AND CLEAN INDOOR FAN AND
FAN SCROLL
a. Reach behind the indoor coil and vacuum any
loose debris from the condensat e drai n pan, fan and other areas accessible to the fan scroll, being careful to avoid damage to the coil fins.
b. Use mild detergent and a damp cl oth to remov e
stubborn debris from surfaces around scroll and fan blades.
2. CLEAN HEATER ASSEMBLY — Use com­pressed air to blow off any dirt or dust that has accumulated on the heater coils.
NOTE: Do not direct air at the bi-metal discs on the temperature limiter switches.
FIGURE 21 — LOCATION OF
TWO-PIECE INDOOR FILTER
FIGURE 22 — LOCATION OF OUTDOOR AIR
VENT FILTER
11
52C,P
SERIES
FIGURE 23 — PTAC EXTERIOR SURFACES
FIGURE 25 — CLEANING COILS
FIGURE 24 — VACUUMING EVAPORATOR
COIL
DRAIN VALVE
FIGURE 26 — BASEPAN SECTION
12
COMPRESSOR
A cutaway view of the rotary compressor with key components labeled is shown in Figure 27. The motor stator is rigidly attached to the compressor shell. The rotor is pressed onto the eccentric shaft, which is sup­ported by 2 bearings. Both the discharge valve and dis­charge muffler are attached to the motor bearing. The
DISCHARGE TUBE
SUCTION INLET
pump bearing provides a thrust surface for the shaft and the rolling piston. Compressed gas is separated from the suction gas by the vane. Discharge gas pres­sure and the vane spring keep the vane in contact with the rolling piston.
SHELL
STAT OR
SUCTION MUFFLER/ ACCUMULATOR
PISTON
VANE
OIL TUBE
ECCENTRIC SHAFT
ROTOR
MOTOR BEARING
DISCHARGE MUFFLER
DISCHARGE VALVE CYLINDER
PUMP BEARING
MOUNTING PLATE
FIGURE 27 — ROTARY COMPRESSOR COMPONENTS
13
52C,P
SERIES
The rotary compression process (Figure 28), starts at top dead center as shown in (1). Suction gas flows through the suction inlet and into the cylinder area. As the shaft rotates through 90 degrees, the rolling piston moves to positio n A as shown in (2). The su ction volume is now the area defined by point A and the tip of the vane. Gas in the remaining volume has been compressed above suction pressure. After another 90 degrees of shaft rotation, the rolling piston has moved to position B as shown in (3 ). Both the com­pressed gas and suction gas volumes are now equal. Another 90 degrees of shaft rotation is shown in (4 ). Compressed gas has reached a pressure sufficient to open the discharge valve, and flows from the cylinder into the compressor shell. After another 90 degrees of shaft rotation, the entire process begins again. Contin­uous suction and discharge allows for a smooth com­pression process.
The rolling piston is not in actual contact with the cyl­inder wall, vane, or bearing faces. Hydrodynamic seal­ing prevents leakage from the compressed gas volume to the suction volume via these paths. Precise control of machining tolerances, surfaces, finishes, and assem­bly clearances is critical to achieve high efficiency per­formance. In addition, the line contact between the vane tip and the rolling piston requires careful selec­tion and control of materials to provide wear resis­tance and reliable long-term operation.
BASIC HERMETIC COMPRESSOR ELECTRICAL MEASUREMENTS
There are 2 basic electrical te st s for herme tic compres ­sors that will determine the electrical state of the motor. The first test requires checking the electrical resistance of each of the electric al motor windin gs. The second test requires checking the electrical resistance of each of the electrical motor windings to ground. These tests may be accomplished by performing the following steps:
1. DISCONNECT ALL POWER TO THE UNIT.
2. Remove the unit chassis from the sleeve as detailed in the UNIT DISASSEMBLY section.
3. Open the control box as detailed in the UNIT DISASSEMBLY section, then locate, label, and remove the 3 compressor wires from the following locations: the RUN wire (BLACK) from the capac­itor, the START wire (BLUE) from the capacitor. The third wi re, C OM M O N wire (YELLOW ) ma y be connected to one of the following locations: for
PC units the wire is on the indoor thermostat, for CE, PE Remote Control Units the wi r e is on the RC Control Board, for all other CE, PE Units the wire is located on the rotary selector
switch. For ALL CQ, PQ Units the wire is on the outdoor frost thermostat.
COMPRESSOR TROUBLESHOOTING
Refer to Figure 29 for a basic compressor troubleshoot­ing chart.
FIGURE 28 — ROTARY COMPRESSOR
COMPRESSION PROCESS
For compressors that are known to be dam­aged: Remove refrigerant prior to disconnecting
compressor wires. Damaged hermetic compressor terminals may become loose a nd eject f rom the com­pressor. Wear safety glasses and keep your face away from the area above the terminals when removing compressor wires.
4. Perform a shorted/open windings test to measure the resistance between the windings of the com­pressor motor. Use a volt-ohmmeter set to the lowest ohm reading level then read and record the resistance between the RUN and START, START and COMMON, and RUN and COMMON wires. See Figure 30. The typical resistance readings will be about 4, 3, and 1 ohms respectively. The smaller values should add to equal the larger value. If this is not true then the compressor is likely shorted winding to winding.
NOTE: The rotary compressor has the compressor overload located under the terminal cover. If the over­load is open it can show ohm readings that are infinite. The unit should be off for at least an hour to give this overload time to reset if it is open.
14
POSSIBLE CAUSE
COILS/FILTERS DIRTY OR PLUGGED AIR OR NONCONDENSABLE GASES
IN SYSTEM SYSTEM REFRIGERANT OVERCHARGED DISCHARGE LINE RESTRICTED CAPILLARY TUBE OR STRAINER
RESTRICTED OR PLUGGED FAN BLADE OR MOTOR DEFECTIVE FAN BLADE OR BLOWER WHEEL STUCK SYSTEM REFRIGERANT UNDERCHARGED EVAPORATOR AIRFLOW RECIRCULATION UNIT OVERSIZED FOR APPLICATION COMPRESSOR REQUIRES START ASSIST NO POWER TO UNIT LOW VOLTAGE TO UNIT OVERLOAD PROTECTOR OPEN OVERLOAD PROTECTOR INCORRECT
OR DEFECTIVE CAPACITOR INCORRECT OR DEFECTIVE THERMOSTAT CONTACTS ARE OPEN THERMOSTAT IS SET TOO HIGH OR LOW SELECTOR SWITCH IS OPEN
OR DEFECTIVE WIRING IS INCORRECT OR DEFECTIVE SYSTEM PRESSURES NOT EQUALIZED COMPRESSOR MOTOR OR
MECHANISM DEFECTIVE COMPRESSOR GROUNDED
SYMPTOM
Compressor
Starts and
Runs But
Cycles On the
Overload
X
XX
X X XX
XX X
X X X X X X
XX X X
XXX
XX X X
XXXX
XX X XX
Compressor
Starts After Cycling the
Overload
Several Times
XX
XX X
Compressor
Will Not
Start. It Hums
and Cycles On
the Overload
X
Compressor
Will Not Start
and Makes No
Noise
X
X
X X
X
Compressor
Cycles Off
(Not On
Overload)
X X
FIGURE 29 — BASIC COMPRESSOR TROUBLESHOOTING GUIDE
5. Next, perform a grounded windings test to test the resistance individually of each wire to the shell of the compressor. The paint on t he compres ­sor can prevent good contact between the probe and the metal. The paint should be removed from a small section of th e shell of the compressor to ensure good contact by the meter probe. The volt­ohmmeter should be set to at least the 100X ohm level. The measured resistance between each wire and ground should be infinite or O.L. on the readout. If there is measurable resistance one of the windings is likely shorted to ground. See Figure 31.
6. A compressor that has a winding to winding short or a winding to compressor shell short is electri­cally failed and needs to be replaced. See the Compressor Replacement section for details.
COMPRESSOR REPLACEMENT
Before working on the compressor, read the instruc­tions thoroughly and gather t he necessar y tools fo r the job. Review all safety information on unit and in liter­ature. Always turn off all power to unit to avoid the possibility of electrical shock.
Consider the following safety issues before beginning:
• New and unfamiliar tasks should be performed under the supervision of an experienced service technician.
• Personal protective equipment, such as work gloves and safety glasses, should be worn.
• The floor around the work area should be clean and free of debris.
• Make sure tools are th e cor r ect to ol s for the jo b a nd that they are working properly and in good condition.
• Never replace a blown fuse without correcting the cause of the original fail u re. If thermally operated circuit breakers or overloads are tripping, make sure the trip is not due to excessi vely high tempera­tures or loose connections.
• When brazing suction and discharge lines, cool the lines with a damp, clean cloth to prevent injury.
• Oil may be present in the compressor accumulator and interconnecting tubing. Use caution when removing tubing.
15
52C,P
SERIES
FIGURE 30 — SHORTED/OPEN WINDINGS TEST
FIGURE 31 — GROUNDED WINDINGS TEST
REMOVING THE COMPRESSOR
— Follow the
steps below to remove the compressor:
1. Disconnect all power to unit.
2. Remove unit from wall sleeve as detailed in the UNIT DISASSEMBLY section. The unit weighs up to 150 pounds. Seek assistance or use a lifting device when removing unit from wall sleeve.
3. If the unit is a heat pump: Disconnect the wire plug on the reversing valve solenoid and carefully remove the outdoor thermostat capillary from the outdoor coil. See Figure 32.
4. Attach the piercing va lve to the suction side pro­cess tube below the crimps. Attach Carrier TOTALTEST® kit (Part No. TT1-001), to the piercing valve to verify acidity of the s ystem. After verifying the system acidity, remove the refriger­ant using a certified refrigerant recovery system.
5. When all the refrigerant has been recovered, remove the terminal cover from the compressor with a nut driver. Disconnect th e 3 wire s from the compressor and label the location of each. Once the wires are labeled, replace the terminal cover to protect the compressor terminals.
6. Remove the air system components by following the procedure detailed in the ACCESSING UNIT COMPONENTS section.
7. Remove the piercing valve and cut the crimped portion of both process tubes off with a small tub­ing cutter. Braze an access valve on each process tube. Using a torch, disconnect the suction and discharge tubes from the compressor connections.
8. Remove the compressor mounting bolts, and remove the compressor.
For compressors that are known to be dam­aged: Remove refrigerant prior to disconnecting
compressor wires. Damaged hermetic compressor terminals may become l oos e and eje ct f r om the com­pressor. Wear safety glasses and keep your face away from the area above the terminals when removing compressor wires.
TOOLS NEEDED
— The following list inclu des the recommended tools and devices for removing and replacing the compressor.
1
/2-in. and 3/8-in. Tube Benders
1
/2-in. Nut Driver
5
/16-in. Nut Driver Flat Head Screwdriver Piercing Valve 2 Parker Access Valves (Part No. AVUSE-5) Pinch Off Tool Filter Drier — All Units (Part No. P504-80845) Carrier TOTALTEST Kit (Part No. TT1-001) Totalclaim System Charging Cylinder or an Electronic Scale Refrigerant-22 Tubing Cutter To rch Nitrogen Cylinder with Regulator Strainers Capillary Tubes
The compressor may still be hot from the brazing process.
IMPORTANT: Any time the compressor is replaced, the strainer and capillary tubes must be removed and replaced also.
9. For all units: Remove and replace the strainer and capillary tubes from the system. See Figure 32 for strainer and capillary tube location.
10. For Heat/Cool Units: Use an in-line filter drier (P/N P504-80845). The filter drier can be installed in any location in suction line. See Figure 33A for general installation location.
For Heat Pump Units: Use an in-line filter drier (P/N P504-80845) and install between the
reversing valve and the compressor accumu­lator. There are several suction tube configura-
tions and the in-line filter drier will be field piped and brazed in to the su ction tube for your uni t. See Figure 33B for a general installation location.
11. Remove the grommets from the existing compres­sor and install them onto the new compressor.
16
Loading...
+ 36 hidden pages