Carrier 50ZHA024-060 User Manual

Page 1
Visit www.carrier.com
Installation, Start-Up and Service Instructions
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................1
INTRODUCTION ..........................................................................2
Check Equipment......................................................................2
IDENTIFY UNIT ................................................................2
INSPECT SHIPMENT ........................................................2
Provide Unit Support ................................................................2
SLAB MOUNT ...................................................................2
GROUND MOUNT ............................................................2
Provide Clearances....................................................................2
Place Unit..................................................................................2
Select and Install Ductwork .....................................................2
CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DIS-
CHARGE ..................................................................4
Provide for Condensate Disposal .............................................4
Install Electrical Connections...................................................5
HIGH-VOLTAGE CONNECTIONS..................................5
ROUTING POWER LEADS INTO UNIT ........................6
CONNECTING GROUND LEAD TO UNIT GROUND .6
ROUTING CONTROL POWER WIRES ..........................6
ACCESSORY ELECTRIC HEAT WIRING .....................6
PRE-START-UP ............................................................................6
START-UP .....................................................................................7
Check for Refrigerant Leaks ....................................................8
LOCATE AND REPAIR REFRIGERANT LEAKS AND
CHARGE THE UNIT AS FOLLOWS: .............................8
Start-Up Cooling Section and Make Adjustments ..................8
CHECKING COOLING CONTROL OPERATION .........8
Refrigerant Charge....................................................................8
NO CHARGE......................................................................8
LOW CHARGE COOLING ...............................................9
HEATING MODE CHARGE.............................................9
Indoor Airflow and Airflow Adjustments................................9
FOR 208/230-V .................................................................13
Unit Controls...........................................................................13
HIGH-PRESSURE RELIEF VALVE...............................13
LOSS OF CHARGE SWITCH.........................................13
COMPRESSOR OVERLOAD..........................................13
Sequence of Operation............................................................13
FAN OPERATION............................................................13
COOLING..........................................................................14
HEATING..........................................................................14
CONTINUOUS FAN ........................................................14
DEFROST..........................................................................14
ELECTRIC RESISTANCE HEATING............................14
MAINTENANCE.........................................................................15
Air Filter..................................................................................15
Unit Top Removal (Outdoor-Coil Side) ................................15
50ZHA024-060
Packaged Heat Pump Units
A05194
Fig. 1—Unit 50ZHA
Indoor Blower and Motor.......................................................15
Outdoor Coil, Indoor Coil, and Condensate Drain Pan ........16
Outdoor Fan ............................................................................16
Electrical Controls and Wiring...............................................16
Refrigerant Circuit ..................................................................17
Indoor Airflow ........................................................................17
Metering Devices ....................................................................17
Lubrication ..............................................................................17
Liquid Line Strainer................................................................17
High Flow Valves...................................................................17
TROUBLESHOOTING ...............................................................17
START-UP CHECKLIST............................................................17
NOTE TO INSTALLER—Before installation, READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY. Also, make sure the User’s Manual and Replacement Guide are left with the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified workers should install, repair, or service air-conditioning equipment.
Untrained workers can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service people. When working on air-conditioning equipment, pay attention to precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 6 8
PC 101 Printed in U.S.A. Catalog No. 50ZHA-1SI Pg 1 9-05 Replaces: New
Page 2
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Before performing service or maintenance operations on system, turn off main power to unit and install lockout tag. Turn off accessory heater power switch if applicable.
Recognize safety information. This is the safety-alert symbol . When you see this symbol in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
INTRODUCTION
50ZHA heat pump units are fully self-contained and designed for outdoor installation (See Fig. 1). As shown in Fig. 2, units are shipped in a horizontal-discharge configuration for installation on a ground-level slab. All units can be field-converted to downflow discharge configurations for rooftop applications with a field­supplied plenum.
RECEIVING AND INSTALLATION
Step 1—Check Equipment
IDENTIFY UNIT
The unit model number and serial number are stamped on the unit identification plate. Check this information against shipping pa­pers. Verify that unit voltage and amperage listed on unit rating plate agree with power supplied for equipment.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its securing points, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Carrier Distributor if any item is missing.
To prevent loss or damage, leave all parts in original packages until installation.
Step 2—Provide Unit Support
SLAB MOUNT
Place the unit on a rigid, level surface, suitable to support the unit weight. A concrete pad or a suitable fiberglass mounting pad is recommended. The flat surface should extend approximately 2-in. beyond the unit casing on the 2 sides. The duct connection side and condensate drain connection sides should be flush with the edge of the flat surface.
A 6-in. wide gravel apron should be used around the flat surface to prevent airflow blockage by grass or shrubs. Do not secure the unit to the flat surface except where required by local codes.
The unit should be level to within 1/4 inch. This is necessary for the unit drain to function properly.
GROUND MOUNT
The unit may also be installed directly on the ground if local codes permit. Place unit on level ground prepared with gravel for condensate discharge.
HURRICANE HOLD DOWN
Contact you local distributor for specific hurricane hold down details and PE (Professional Engineer) certification when required.
Step 3—Provide Clearances
The required minimum service clearances and clearances to combustibles are shown in Fig. 2. Adequate ventilation and outdoor coil air must be provided.
The outdoor fan pulls air through the outdoor coil and discharges it through the fan on the top cover. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 inches.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials.
OPERATIONAL HAZARD Failure to follow this caution may result in unit component damage. Do not restrict outdoor coil airflow. An air restriction at either the outdoor-air inlet or the fan discharge can be harmful to compressor life.
Step 4—Place Unit
Unit can be moved with the rigging holds provided in the unit base. Refer to Table 2 for operating weights. Use extreme caution to
level with in 1/4” for proper condensate drainage; the ground-level pad must be level before setting the unit in place. When a field-fabricated support is used, be sure that the support is level and that it properly supports the unit.
Step 5—Select and Install Ductwork
The design and installation of the duct system must be in accordance with:
• the standards of the NFPA (National Fire Protection Associa­tion) for installation of nonresidence-type air conditioning and ventilating systems
• NFPA90A or residence-type, NFPA90B; and/or local codes and residence-type, NFPA 90B
• and/or local codes and ordinances
Select and size ductwork, supply-air registers and return-air grilles according to ASHRAE (American Society of Heating, Refrigera­tion, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply- and return-air openings on the side of the unit. See Fig. 2 for connection sizes and locations. The 14-in. round duct collars are shipped inside the unit attached to the base pan in the indoor blower compartment. They
2
Page 3
A05201
Fig. 2—Unit Base Dimensions, 50ZHA024-060
3
Page 4
Table 1—Unit Specifications
UNIT ELECTRICAL CHARACTERISTICS
50ZHA024 208/230-1-60 293 133 30.13 (765) 14.0 (356) 19.0 (483) 12.0 (305) 50ZHA030 208/230-1-60 324 147 34.13 (867) 14.0 (356) 19.0 (483) 12.0 (305) 50ZHA036 208/230-1-60 377 171 42.13 (1070) 14.0 (356) 19.0 (438) 19.8 (503) 50ZHA042 208/230-1-60 389 177 42.13 (1070) 14.0 (356) 19.0 (483) 21.9 (556) 50ZHA048 208/230-1-60 384 175 42.13 (1070) 14.0 (356) 19.0 (483) 19.8 (503) 50ZHA060 208/230-1-60 433 197 42.13 (1070) 14.0 (356) 19.0 (483) 21.9 (556)
UNIT WEIGHT
lb kg A XYZ
UNIT HEIGHT
IN. (MM)
CENTER OF GRAVITY IN. (MM)
are field-installed and must be removed from the indoor blower compartment prior to start-up, even if they are not used for installation.
When designing and installing ductwork, consider the following:
UNIT DAMAGE HAZARD Failure to follw this caution may result in damage to unit components. When connecting ductwork to units, do not drill deeper than 3/4 inch in shaded area shown in Fig. 3 or coil may be damaged.
• All units should have field-supplied filters installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 2.
• Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weathertight and airtight seal. When electric heat is installed, use fire proof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24–in. from the unit discharge connection flange into the ductwork.
• Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Table 3. Heater limit switches may trip at air quantities below those recommended.
• Insulate and weatherproof all external ductwork. Insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Condi­tioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum in­stallation standards for residential heating and air conditioning systems.
• Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof according to good construction practices.
Figure 4 shows a typical duct system with 50ZHA unit installed.
CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DISCHARGE
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before performing service or maintenance operations on system, turn off main power to unit and install lockout tag. Turn off accessory heater power switch if applicable.
Units are dedicated side supply products. They are not convertible to vertical air supply. A field-supplied plenum must be used to convert to vertical air discharge.
Step 6—Provide for Condensate Disposal
NOTE: Be sure that condensate-water disposal methods comply
with local codes, restrictions, and practices.
Unit removes condensate through a 1 3/64-in. ID hole (using 3/4-in. OD piping or tubing) which is located at the end of the unit. See Fig. 2 for location of condensate connection.
19.17
3.92
Fig. 3—Area Not to Be Drilled More Than 3/4-in.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground­level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a 2-in. trap using a 3/4-in. OD tubing or pipe. (See Fig. 5 and 6.) Make sure that the outlet of the trap is at least 1 in. lower than the unit drain-pan condensate connection to prevent the pan from overflowing. Prime the trap with water. Connect a drain tube using a minimum of 3/4-in. PVC, 3/4-in. CPVC, or 3/4-in. copper pipe (all field supplied). Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the beginning of the cooling season start-up. Allowable glues for condensate trap connection are: Standard ABS, CPVC, or PVC cement.
4
A05195
Page 5
Table 2—Physical Data
UNIT 50ZHA 024 030 036 042 048 060
OPERATING WEIGHT (lbs) 293 324 377 389 384 433
COMPRESSOR TYPE Scroll Ultra Tech Scroll
15.8
20
4.9 Direct Drive
R-22
Propeller
Round
14 14
2...21
15.8
3200
20
1/4 (1100)
4...17
6.1
1400
11x9
3/4 (1050)
2...21
13.3
3200
20
1/4 (1100)
4...17
4.9
1600
11x10
1 (1050)
2...21
15.8
3300
20
1/2 (1100)
4...17
6.1
1875
11x10
1 (1050)
REFRIGERANT Charge (lb)
REFRIGERANT METERING DEVICE
*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min
for high capacity type. Recommended filters are 1-in. thick.
Orifice ID (in.)
Orifice OD (in.) .049 .057 .059 .063 .070 .073
CONDENSER COIL
Rows...Fins/in.
Face Area (sq. ft.)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor HP (RPM)
EVAPORATOR COIL
Face Area (sq. ft.)
Evaporator Blower
Nominal Airflow (CFM)
Size (in.)
Motor HP (RPM)
CONNECTING DUCT SIZES
Supply Air (in.) Return Air (in.)
Return-Air Filters (in.)*
Throwaway
7.5 10.3 10.3 11.9 11.4 13.3 Accurater TXV
.067 .067 .082 .086
Copper Tubes, Aluminum Plate Fins
2...21
11.1
2600
20
1/8 (825)
3...17
4.3
800
10x8
1/2 (1050)
24x24 24x24 24x24 24x30 30x30 30x30
2...21
12.7
2600
20
1/8 (825)
3...17
4.9
1000
10x8
1/2 (1050)
2...21
3200
1/4 (1100)
Copper Tubes, Aluminum Plate Fins
4...17
1200
11x9
3/4 (1050)
Step 7—Install Electrical Connections
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI (American National Standards Institute)/NFPA (latest edition) (in Canada, Canadian Elec­trical Code CSA C22.1) and local electrical codes.
UNIT DAMAGE HAZARD Failure to follow these precautions may result in damage to the unit being installed:
1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connec­tions must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate.
4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. Consult local power company for correction of improper voltage.
HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field­supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Table 6 for electrical data.
The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole. (See Fig. 2.)
5
Page 6
INDOOR THERMOSTAT
RETURN AIR
TOP COVER
Power Wiring
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND LOW-VOLTAGE ENTRY
COMPOSITE RUST-PROOF BASEPAN
CONDENSATE DRAIN CONNECTION
*Separate disconnect per NEC (National Electrical Code) required for electric heater when single­point conection is not used.
FROM POWER SOURCE
DISCONNECT PER NEC* (UNIT AND ELECTRIC HEATER)
C00008
C00008
Fig. 4—Typical installation
1” (25mm) MIN.
TRAP OUTLET
2” (50mm) MIN.
C99013
Fig. 5—Condensate Trap (Using Tubing)
TRAP OUTLET
1" min.
2" min.
C00009
Fig. 6—PVC Condensate Trap
Table 3—Minimum Airflow for Safe Electric Heater
Operation (CFM)
SIZE 024 030 036 042 048 060
Cfm 600 750 900 1050 1200 1500
UNIT DAMAGE HAZARD Failure to follow this caution may result in unit component damage. Operation of unit on improper line voltage consti­tutes abuse and may cause unit damage that could affect warranty.
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high­voltage leads should be in a conduit until they enter the unit; conduit termination at the unit must be watertight. Run the high-voltage leads through the hole on the control box side of the unit (see Fig. 7 for location). When the leads are inside the unit, run leads to the control box (Fig. 8). For single-phase units, connect leads to the black and yellow wires (see Fig. 9).
CONNECTING GROUND LEAD TO UNIT GROUND
Refer to Fig. 8 and 9. Connect the ground lead to the chassis using the unit ground in the control box.
ROUTING CONTROL POWER WIRES
Form a drip-loop with the thermostat leads before routing them into the unit. Route the thermostat leads through grommeted hole provided in unit into unit control box (See Fig. 7). Connect thermostat leads and unit power leads as shown in Fig. 9, 10A & 10B.
Route thermostat wires through grommet providing a drip-loop at the panel. Connect low-voltage leads to the thermostat as shown in Fig. 10A & 10B.
The unit transformer supplies 24-v power for complete system including accessory electrical heater. Transformer is factory wired for 230-v operation.
ACCESSORY ELECTRIC HEAT WIRING
Refer to accessory electric heat installation instructions for infor­mation on installing accessory electric heat. Accessory electric heat wiring is shown in Fig. 11A, 11B, & 11C.
PRE-START-UP
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Failure to observe the following warnings could result in serious injury, death and/or property damage:
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electri­cal sources are disconnected and lockout tag is installed.
4. Relieve all pressure from both high- and low-pressure sides of the system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around com­pressor terminals. Use accepted methods to recover refrig­erant.
5. Never attempt to repair soldered connection while refrig­erant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as fol­lows: a. Shut off electrical power to unit and install lockout tag. b. Relieve all refrigerant from system using both high- and
low-pressure ports. Use accepted methods to recover refrigerant.
c. Cut component connecting tubing with tubing cutter and
remove component from unit.
d. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Use the Start-Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with unit.
Make the following inspections:
a. Inspect for shipping and handling damages such as broken
lines, loose parts, disconnected wires, etc.
6
Page 7
Table 4—Required Subcooling
REQUIRED SUBCOOLING °F (°C)
Model Size
048 17.5 (9.7) 17 (9.4) 16.5 (9.2) 16 8.9) 14 (7.8) 060 21 (11.7) 20.5 (11.4) 20 (11.1) 19 (10.6) 16 (8.9)
75 (24) 82 (28) 85 (29) 95 (35) 105 (41)
Outdoor Ambient Temperature
Table 5—Required Liquid Line Temperature
REQUIRED LIQUID LINE TEMPERATURE FOR A SPECIFIC SUBCOOLING (R-22)
Pressure (psig)
134 71 66 61 56 924 24 22 19 16 141 74 69 64 59 972 26 23 21 18 156 80 75 70 65 1075 30 27 24 21 163 83 78 73 68 1124 31 28 26 23 170 86 81 76 71 1172 33 30 27 24 177 89 84 79 74 1220 34 31 29 26 184 91 86 81 76 1268 36 33 30 27 191 94 89 84 79 1317 37 34 31 29 198 96 91 86 81 1365 38 36 33 30 205 98 93 88 83 1413 40 37 34 31 213 101 96 91 86 1468 41 38 36 33 221 104 99 94 89 1524 43 40 37 34 229 106 101 96 91 1579 44 41 38 36 237 108 103 98 93 1634 45 42 40 37 245 111 106 101 96 1689 47 44 41 38 253 113 108 103 98 1744 48 45 42 40 262 116 111 106 101 1806 49 46 44 41 271 118 113 108 103 1868 51 48 45 42 280 121 116 111 106 1930 52 49 46 44 289 123 118 113 108 1992 53 51 48 45 298 125 120 115 110 2054 55 52 49 46 307 128 123 118 113 2116 56 53 50 48 317 130 125 120 115 2185 57 54 52 49 327 132 127 122 117 2254 59 56 53 50 337 135 130 125 120 2323 60 57 54 52 347 137 132 127 122 2392 61 58 56 53 357 139 134 129 124 2461 62 60 57 54 367 142 137 132 127 2530 64 61 58 55 280 121 116 111 106 1930 52 49 46 44 289 123 118 113 108 1992 53 51 48 45 298 125 120 115 110 2054 55 52 49 46 307 128 123 118 113 2116 56 53 50 48 317 130 125 120 115 2185 57 54 52 49 327 132 127 122 117 2254 59 56 53 50 337 135 130 125 120 2323 60 57 54 52 347 137 132 127 122 2392 61 58 56 53 357 139 134 129 124 2461 62 60 57 54 367 142 137 132 127 2530 64 61 58 55
Required Subcooling (°F)
5 101520 36811
Pressure (kPa)
Required Subcooling (°C)
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, or liquid-soap solution. If a refrig­erant leak is detected, see following Check for Refrigerant Leaks section.
c. Inspect all field- and factory-wiring connections. Be sure
that connections are completed and tight. Ensure wires do not contact refrigerant tubing or sheet metal edges.
d. Inspect coil fins. If damaged during shipping and handling,
carefully straighten fins with a fin comb.
3. Verify the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned in
fan orifice. Top edge of blade should be 3.125 in. down from outdoor coil outlet grille (size 024–048, See Fig. 12) or hub should be 0.708-in. away from motor end bell (size 060, See Fig. 13). See Outdoor Fan Adjustment section.
b. Make sure that air filter is in place.
c. Make sure that condensate drain trap is filled with water to
ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts have
been removed.
7
Page 8
HIGH-VOLTAGEPOWER
WIRINGENTRYHOLE
LOW-VOLTAGEWIRING
ENTRYHOLE
A05198
Fig. 7—Unit Electrical Connection
C00011
Fig. 8—Control Box Wiring
START-UP
Use the Start-Up Checklist supplied at the end of this book and proceed as follows:
Step 1—Check for Refrigerant Leaks
LOCATE AND REPAIR REFRIGERANT LEAKS AND CHARGE THE UNIT AS FOLLOWS:
1. Using both high- and low-pressure ports, locate leaks and reclaim remaining refrigerant to relieve system pressure.
2. Repair leak following accepted practices.
NOTE: Install a liquid-line filter drier whenever the system has been opened for repair.
Step 2—Start-Up Cooling Section and Make Adjustments
UNIT DAMAGE HAZARD Failure to follow this caution may result in unit component damage. Complete the required procedures given in the Pre-Start- Up section this page before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor in cooling mode when the outdoor temperature is below 40 F. Do not rapid-cycle the compressor. Allow 5 minutes between ‘‘on’’ cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down within 60 seconds (for 024-042) or 90 seconds (for 048 and 060) when FAN switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, outdoor fan, and indoor blower motors start and that reversing valve shifts. Observe that cooling cycle shuts down when control setting is satisfied. Reversing valve (RV) remains energized.
3. Place system switch in HEAT position. Observe that compres­sor, indoor fan and outdoor fan energize (Reversing Valve is deenergized in heat pump heating mode). Set control above room temperature. Observe that heating cycle shuts down when control setting is satisfied.
4. When using an automatic changeover room thermostat, place both SYSTEM and FAN switches in AUTO. positions. Observe that unit operates in Cooling mode when temperature control is set to ‘‘call for cooling’’ (below room temperature), and unit operates in Heating mode when temperature control is set to “call for heating” (above room temperature).
Step 3—Refrigerant Charge
Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate and in Table 2. Refer to Carrier Refrigerant Service Techniques Manual, Refrigerants section. Unit panels must be in place when unit is operating during charging procedure. Unit must operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer to Carrier Refrigerant Service Techniques. Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 2).
UNIT GROUND
GROUND
LEAD
3-PHASE CONNECTIONS TO DISCONNECT PER NEC
Fig. 9—Line Power Connections
SINGLE-PHASE CONNECTIONS TO DISCONNECT PER NEC
L
L
L
BLK
YEL
BLU
C00012
8
Page 9
Thermostat
G
Y
W2
W3
R
RED
GREEN
O
ORANGE
C
BROWN
WHITE
VIOLET
G
Y
Y1
O
R
RED
GREEN
YELLOW
W2
PINK
W3
ORANGE
WHITE
VIOLET
C
BROWN
and subbase
Unit Control
Power
A05207
Fig. 10A—Control Connections (Sizes 024-042)
3. Insulate the temperature sensing device so that the outdoor ambient doesn’t affect the reading.
4. Locate the measured suction line pressure in the top row of Table 8 and the measured outdoor ambient temperature in the left column of the table. Based on the two values, determine the required suction line temperature.
5. If the measured suction line temperature is greater than the tabulated temperature, add charge in the system.
048 and 060 units:
1. Measure discharge line pressure by attaching a gauge to the service port.
2. Measure the liquid line temperature by attaching a temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor ambient doesn’t affect the reading.
4. Refer to the required subcooling in Tables 4 and 5 to find the required subcooling based on the model size and the outdoor ambient temperature.
5. Interpolate if the outdoor temperature lies in between the table values. Extrapolate if the temperature lies beyond the table range.
6. Find the pressure value corresponding to the measured pres­sure on the compressor discharge line.
7. Read across from the pressure reading to obtain the Liquid line temperature for a required subcooling.
8. Add charge if the measured temperature is higher than the liquid line temperature value in the table.
9. Add charge using the service connection on the suction line of the compressor.
HEATING MODE CHARGE
Do not attempt to adjust charge by cooling methods while in heat pump heating mode. Recover refrigerant and weigh in according to unit data plate refrigerant data.
Step 4—Indoor Airflow and Airflow Adjustments
NOTE: For cooling operation, the recommended airflow is 350 to
450 cfm per each 12,000 Btuh of rated cooling capacity.
Table 7 shows dry coil air delivery for horizontal discharge units. Tables 9-11 show pressure drops.
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly.
Thermostat
and subbase
Unit Control
Power
A05208
Fig.10B—Control Connections (Sizes 048-060)
LOW CHARGE COOLING
024-042 units:
1. Measure suction line pressure by attaching a gauge to the service port.
2. Measure the suction line temperature by attaching a tempera­ture sensing device to it.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect electrical power to the unit and install lockout tag before changing blower speed.
Airflow can be changed by changing the 24 volts lead connections of the blower motor.
Unit 50ZHA blower motors are factory wired for rated airflow operation.
FOR 208/230-V BLOWER MOTORS
The motor lead speed connections are as follows:
SIZE RATED AIRFLOW HIGH AIRFLOW
024 Tap 1 Tap 3 030 Tap 2 Tap 4 036 Tap 1 Tap 3 042 Tap 2 Tap 4
9
Page 10
Fig. 11A—Typical Unit Electrical Diagram (Sizes 024-042)
10
A05199
Page 11
Fig. 11B—Typical Unit Electrical Diagram (Sizes 048-060)
11
A05200
Page 12
A05209
Fig. 11C—Accessory Electric Heater Wiring
Table 6—Electrical Data—50ZHA
VOLTAGE
UNIT SIZE
50ZHA
024 208/230–1–60 187 253 10.9 54.0 0.9 4.1
030 208/230–1–60 187 253 13.5 72.5 0.9 4.1
036 208/230–1–60 187 253 17.5 88.0 1.5 6.0
042 208/230–1–60 187 253 19.4 104.0 1.5 6.0
048 208/230–1–60 187 253 24.7 116.0 1.5 7.7
060 208/230–1–60 187 253 28.0 118.0 3.0 7.7
FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection RLA Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be Power Supply fuse. The CGA (Canadian Gas Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC.
V-PH-HZ
RANGE
MIN MAX RLA LRA Nominal KW* FLA MCA
COMPRESSOR
OFM
FLA
IFM
FLA
ELECTRIC HEAT SINGLE POINT POWER SUPPLY
FUSE OR CKT BKR
—/—
3.8/5.0
7.5/10.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
18.6/18.6
41.2/44.7
63.8/70.7
51.1/56.1
21.8/21.8
44.4/47.9
57.0/73.9
89.5/100.0
54.3/59.3
29.4/29.4
52.0/55.4
74.5/81.5
97.1/107.5
61.9/66.9
31.7/31.7
54.3/57.8
76.9/83.8
99.4/109.9
122.0/135.9
63.2/69.2
40.0/40.0
62.6/66.1
85.1/92.1
107.7/118.1
130.3/144.2
72.5/77.5
45.7/45.7
68.2/71.7
90.8/97.8
113.4/123.8
135.9/149.9
78.2/83.2
25/25 45/50
50/50
30/30 50/50
— —
60/60
35/35 60/60
— — —
40/40
— — — — —
50/50
— — — — —
60/60
— — — — —
MOCP
— —
60/70
— —
70/70
90/100
— —
80/80
100/100
70/70
— 60/70 80/90
100/110 110/150
70/80
— 80/80
100/100 110/125 125/125
90/90
— 90/90
100/110 125/125 125/150
90/100
12
Page 13
Table 7—Dry Coil Air Delivery* Horizontal Discharge
(Deduct 10 percent for 208 Volt Operation)
50ZHA SPEED TAP WATTS/C.F.M
1
024
2
2
030
3
1
036
2
3
042
4
1
2
048
3
4
1
2
060
3
4
Air delivery values are based on operating voltage of 230-v., dry coil, without filter or electric heater. Deduct wet coil, filter, and electric heater pressure drops to obtain external static pressure availabe for ducting. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point. Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.
Watts -99100118130142----
C.F.M. -848793757698632----
Watts -----222233244257260
C.F.M -----970918861795729
Watts -155146157170-----
C.F.M - 1108 995 951 884 -----
Watts -----261275286291315
C.F.M. -----1117 1053 1014 980 877
Watts 180166179191204216----
C.F.M. 1344 1215 1172 1136 1095 1051 ----
Watts - - - 261 276 290 301 316 329 342
C.F.M. - - - 1343 1304 1272 1234 1190 1148 1100
Watts 269 283 305 321 336 349 360 - - -
C.F.M. 1440 1404 1369 1333 1301 1273 1239 - - -
Watts - - 418 432 450 465 480 490 503 518
C.F.M. - - 1572 1543 1504 1475 1441 1418 1380 1332
Watts 204 209 216 229 236 249
C.F.M. 1129 1087 1027 994 932 881
Watts 233 245 254 266 276 289
C.F.M. 1164 1122 1066 1025 954 906
Watts 386 398 409 418 425 435 438 441 451
C.F.M. 1680 1652 1625 1583 1555 1515 1477 1444 1403
Watts 440 448 457 462 469 477 480 485 486
C.F.M. 1745 1717 1684 1651 1612 1573 1537 1508 1470
Watts 224 235 251 266 277 291 298 - - -
C.F.M. 1334 1288 1259 1224 1181 1157 1117 - - -
Watts - - 286 301 311 325 333 344 370 -
C.F.M. - - 1333 1296 1261 1232 1199 1170 1062 -
Watts 608 626 643 660 668 685 697 - - -
C.F.M. 1931 1900 1878 1844 1817 1789 1755 - - -
Watts 737 755 770 787 799 817 826 812 782 -
C.F.M. 2093 2061 2028 2001 1971 1934 1899 1850 1757 -
0.1 0.2 .03 0.4 0.5 0.6 0.7 0.8 0.9 1.0
EXTERNAL STATIC PRESSURE
RATED AIRFLOW HIGH AIRFLOW
SIZE
048 Tap 1 Tap 3 Tap 2 Tap 4 060 Tap 1 Tap 3 Tap 2 Tap 4
Low
Stage
High
Stage
Low
Stage
High
Stage
Step 5—Unit Controls
All compressors have the following internal-protection controls.
HIGH-PRESSURE RELIEF VALVE
This valve opens when the pressure differential between the low and high side becomes excessive.
LOSS OF CHARGE SWITCH
Located on the outdoor liquid line is a low-pressure switch which functions as a loss-of-charge switch. This switch contains a Schrader core depressor. This switch opens at 7 psig and closes at 22 psig. No adjustment is necessary.
COMPRESSOR OVERLOAD
This overload interrupts power to the compressor when either the current or internal temperature become excessive, and automati­cally resets when the internal temperature drops to a safe level.
This overload may require up to 60 minutes (or longer) to reset; therefore, if the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit through the overload with an ohmmeter or continuity tester.
Step 6—Sequence of Operation
FAN OPERATION
The FAN switch on the thermostat controls indoor fan operation. When the FAN switch is placed in the ON position, the IFR (indoor-fan relay) is energized through the G terminal on the thermostat. The normally-open contacts close, which then provide power to the indoor (evaporator) fan motor (IFM). The IFM will run continuously when the FAN switch is set to ON.
When the FAN switch is set to AUTO, the thermostat deenergizes the IFR (provided there is not a call for cooling). The contacts open and the IFM is deenergized. The IFM will be energized only when there is a call for cooling, in heat pump heating mode or if the unit is equipped with accessory electric heat, the indoor-fan motor will also run while the accessory electric heat is energized.
NOTE: Some units are equipped with a time-delay relay. On these units, the indoor fan remains on for 30 seconds after G or Y is deenergized.
13
Page 14
Table 8—Cooling Charging Chart
SUCTION LINE TEMPERATURE (°F)
Suction Line Pressure (PSIG)
OD Temp. (°F) 52 54 56 59 61 64 67 70 73 76 79 82 85 89 92
45 51 55606469—————————— 55 — —5357626670———————— 65 — ———535762667175————— 75 — ——————5661667176——— 85 — ———————5358636772——
95 — ————————5054586266— 105 — —————————5053576064 115 — —————————4952555861 125 — ——————————50535659
SUCTION LINE TEMPERATURE (°C)
Suction Line Pressure (kPa)
OD Temp. (°C) 361 370 387 405 423 442 462 482 502 523 544 566 589 612 636
7 11 13151821—————————— 13 — —1214161921———————— 18 — ———121417192124————— 24 — ——————1316192224——— 29 — ———————1214172022—— 35 — ————————1012141719— 41 — —————————1012141618 46 — ————————— 9 11131416 52 — ——————————10111315
COOLING OPERATION (SIZES 024-042)
With a call for cooling (Y/Y2), the indoor fan energizes immedi­ately whereas the contactor energizes aftera5minute time delay (in case of initial start-up) starting the compressor and the outdoor fan motor. When the cooling demand is met, Y/Y2 de-energizes, shutting the compressor, indoor fan and the outdoor fan.
COOLING OPERATION (SIZES 048 AND 060)
These units utilize a 2 stage indoor thermostat. With a first stage call for cooling (Y1), the indoor fan (low stage) energizes immediately whereas the contactor energizes aftera5minute time delay (in case of an initial start-up) starting the compressor (low stage) and the outdoor fan motor. If the low stage operation cannot satisfy the cooling demand, the second stage cooling (Y2) ener­gizes switching the compressor into high stage cooling through energizing an internal solenoid valve inside the scroll compressor and switching the indoor fan into high stage. When second stage cooling is satisfied, Y2 de-energizes switching the compressor and the indoor fan into low stage cooling. When the low stage cooling demand is met, Y1 de-energizes shutting the compressor, indoor fan and the outdoor fan.
HEATING OPERATION (SIZES 024-042)
With a call for heating (Y1), the indoor fan (low stage) energizes immediately whereas the contactor energizes aftera5minute time delay (in case of initial start-up) starting the compressor and the outdoor fan motor. If Y/Y2 cannot satisfy the heating demand, the auxiliary or backup heat (W2) energizes. In case of staged heating, W3 is energized if the demand is not met. The highest airflow selected is run while the electric heat is in operation. When heating demand is met, W3, W2 and Y/Y2 sequentially de-energize shutting the compressor, indoor fan and the outdoor fan.
HEATING OPERATION (SIZES 048 AND 060)
With a first stage call for heating (Y1), the indoor fan (low stage) energizes immediately whereas the contactor energizes after a 5 minute time delay (in case of initial start-up) starting the compres­sor (low stage) and the outdoor fan motor. If the low stage oepration cannot satisfy the heating demand, the second stage
heating (Y2) energizes switching the compressor into high stage heating through energizing an internal solenoid valve inside the scroll compressor and switching the indoor fan into high stage. The auxiliary or backup heat is controlled by a third stage (W2). If the demand is not met, W3 is energized in case of staged heating. When heating demand is satisfied, W3, W2 and Y2 sequentially de-energize switching the compressor and the indoor fan into low stage heating. When the low stage heating demand is met, Y1 de-energizes shutting the compressor, indoor fan and the outdoor fan.
CONTINUOUS FAN
With the continuous Indoor fan option selected on the thermostat, G is continuously energized. In case of 024-042 units, the selected airflow setting is provided. In case of 048 and 060 units, the system runs low stage (Y1) airflow for continuous fan operation.
DEFROST
Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for defrost (30, 60, 90 and 120 minutes). The time period is factory-set at 60 minutes and should only be adjusted by a trained service person. Electronic timer and defrost cycle start only when contactor is energized and defrost thermostat (DFT) is closed.
Defrost mode is identical to Cooling mode. The outdoor fan motor stops because of “OF1” and “OF2” contacts opening on the defrost board, a bank of optional electric heat turns on to warm air supplying the conditioned space.
ELECTRIC RESISTANCE HEATING
If accessory electric heaters are installed, on a call for “Emergency Heat” the thermostat energizes W which energizes the heater relay and in turn energizes the electric heaters. The IFR is energized which starts the indoor-fan motor. If the heaters are staged, W2 is energized when the second stage of heating is required. When the need for heating is satisfied, the heater and IFM are de-energized.
MAINTENANCE
To ensure continuing high performance, and to reduce the possi­bility of premature equipment failure, periodic maintenance must
14
Page 15
be performed on this equipment. This cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot cooling of units, refer to Troubleshooting chart in back of book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death or property damage. The ability to properly perform maintenance on this equip­ment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the User’s Manual.
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, outdoor coil, drain pan, and condensate drain each cooling and heating season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling and heating season. Clean when necessary. For first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
4. Check electrical connections for tightness and controls for proper operation each cooling season. Service when neces­sary.
5. Check the drain channel in the top cover periodically for blockage (leaves, insects). Clean as needed.
FIRE, EXPLOSION, ELECTRICAL SHOCK, CUT HAZ­ARD Failure to follow these warnings could result in serious personal injury, death, and/or property damage:
1. Turn off electrical power to the unit and install lockout tag before performing any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts. As with any mechanical equipment, personal injury can result from sharp edges, etc.
3. Never place anything combustible either on, or in contact with, the unit.
Step 1—Air Filter NOTE: Never operate the unit without a suitable air filter in the
return-air duct system. Always replace the filter with the same size as originally installed. See Table 2 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice during each cooling season or whenever the filters become clogged with dust and lint.
Replace filters with the same dimensional size and type as originally provided, when necessary.
Step 2—Unit Top Removal (Outdoor-Coil Side) NOTE: When performing maintenance or service procedures that
require removal of the unit top, be sure to perform all of the routine maintenance procedures that require top removal, including coil inspection and cleaning, and condensate drain pan inspection and cleaning.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect and tag electrical power to the unit before removing top.
Only qualified service personnel should perform maintenance and service procedures that require unit top removal.
Refer to the following top removal procedures:
1. Remove screws on unit top cover surface. (Save all screws.)
2. Remove screws on unit top cover flange. (Save all screws.)
3. Lift top from unit carefully. Set top on edge and make sure that top is supported by unit side that is opposite duct (or plenum) side.
4. Carefully replace and secure unit top to unit, using screws removed in Steps 1 and 2, when maintenance and/or service procedures are completed.
Step 3—Indoor Blower and Motor
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect and tag electrical power to the unit before cleaning the blower wheel.
To clean the blower wheel follow the following steps:
1. Remove the blower housing:
a. Remove the screws on the external side of the duct panel
that fasten the housing to the duct panel assembly.
b. Remove the side access panel and unscrew the mounting
bracket that fastens the blower housing to the internal partition panel fo the control box assembly.
c. Make sure that the blower housing is supported by hand
before completely removing the mounting bracket.
d. Slide the blower housing from the rails of the duct panel
and place it outside the unit.
2. Remove the blower wheel from the housing:
a. Loosen the set screw which secures the wheel to the motor
shaft.
b. Loosen the three mounting legs of the motor by removing
the bolts that fasten themounting legs to the housing.
c. Slide out the motor assembly (motor, belly band and the 3
mounting legs) from the hub of the wheel.
d. Remove the filler panel at the discharge end of the blower
housing by removing the two screws that fasten it to the housing.
e. Remove the wheel form the housing.
3. Remove the caked on dirt from the wheel and the motor using a brush.
4. Remove lint and dirt accumulations from the wheel and housing with a vacuum cleaner, using a soft brush attachment.
5. Remove grease and oil with a mild solvent.
6. Reassemble
15
Page 16
Table 9—Wet Coil Pressure Drop
UNIT SIZE
024 .027.034040.047.053---------­030 - .036 .042 .050 .055 .063 .072 .081 - - - - - - ­036 - - - .050 .055 .063 .072 .081 .090 .097 - - - - ­042 - - - - .042 .049 .052 .059 .065 .071 .078 .085 .091 - ­048 - - - - - - .072 .081 .090 .097 .108 .120 .129 .139 ­060 - - - - - - - - - .071 .078 .085 .091 .098 .114
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
STANDARD CFM (S.C.F.M.)
a. Slip the wheel back in the housing with the hub set screw
parented in the correct direction.
b. Install the filler panel.
c. Reinsert the motor assembly in the wheel hub and align the
mounting legs with the housing mounting hold locations.
d. Tighten the mounting bolts to fasten the motor assembly
with the housing.
e. Center the wheel in the housing by sliding it, align the flat
end of the shaft with the set screw and tighten the set screw.
f. Slide back the blower housing into the mounting rails in the
duct panel and install the mounting bracket back in its position.
g. Install the screws on the external side of the duct panel to
fasten duct panel with the housing.
h. Replace the side access panel.
Step 4—Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the outdoor coil, indoor coil, and condensate drain pan at least once heating and cooling season. Proper inspection and cleaning requires the removal of the unit top. See Unit Top Removal section.
Table 10—Filter Pressure Drop (in. wg)
FILTER
UNIT SIZE
024-036 24 x 24 0.06 0.07 0.08 0.08 0.09 0.09 0.09 0.10 0.11 0.12
042-060 30x30----- - - -0.080.09
SIZE
500 600 700 800 900 1000 1100 1200 1300 1400
(IN.)
CFM
coil fins from inside to outside the unit. On units with an outer and inner outdoor coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a ‘‘plumbers snake’’ or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.
Step 5—Outdoor Fan
UNIT OPERATIONAL HAZARD Failure to follow this caution may result in damage to unit components. Keep the Outdoor fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit.
1. Shut off unit power supply and install lockout tag.
2. Remove outdoor-fan assembly (grille, motor, motor cover, and fan) by removing screws and flipping assembly onto unit top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 12 or 13.
5. Tighten setscrews.
6. Replace outdoor-fan assembly.
FILTER
UNIT SIZE
024-036 24x240.140.15-------
042-060 30 x 30 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
SIZE
1500 1600 1700 1800 1900 2000 2100 2200 2300
(IN.)
CFM
Table 11—Accessory Electric Heat Pressure Drop
(in. wg)
HEATER KW
5-20
600 800 1000 1200 1400 1600 1800 2000 2200
0.06 0.08 0.10 0.13 0.15 0.18 0.20 0.23 0.25
Remove all obstructions (including weeds and shrubs) that inter­fere with the airflow through the outdoor coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using a soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and-water-solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring or air filter(s). For best results, spray outdoor-
CFM
Step 6—Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag.
Remove the top panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
3.125 in.
C00021
Fig. 12—Outdoor-Fan Adjustment (024–048 Size)
Check to ensure no wires are touching refrigerant tubing or sharp sheet metal edges. Move and secure wires to isolate from tubing and sheet metal edges.
16
Page 17
0.708in.
C02017
Fig. 13—Outdoor-Fan Adjustment (060 Size)
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumenta­tion. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the Sequence of Operation section, as an aid in determining proper control operation.
Step 7—Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrig­erant leak.
If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing using an electronic leak-detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section. (See Table of Contents for page number.)
If no refrigerant leaks are found and low cooling performance is suspected, refer to Refrigerant Charge. (See Table of Contents for page number.)
Step 8—Indoor Airflow
The cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from obstructions,
and that the air filter is clean. When necessary, refer to Indoor
Airflow and Airflow Adjustments section to check the system airflow.
Step 9—Metering Devices
Refrigerant cooling metering device is an Accurator (024-042) or TXV (048 and 060) located upstream of the indoor coil distributor assembly. Refrigerant heating mode metering device is an Accu­rater located upstrem of the outdoor coil distributor assembly.
Step 10—Lubrication
COMPRESSOR—The compressor is charged with the correct amount of oil at the factory.
FAN MOTOR BEARINGS—Fan motor bearings are perma­nently lubricated. No further lubrication of outdoor or indoor fan motors is required.
Step 11—Liquid Line Strainer
The liquid line strainer (to protect metering device) is made of wire mesh and is located in the liquid line on the inlet side of the metering device.
Check valves are also located in the liquid lines near the strainers. The Strainers are the larger of the two components.
Step 12—High Flow Valves
Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves cannot be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.
TROUBLESHOOTING
Use the Troubleshooting Cooling and Heating guide if problems occur with these units.
START-UP CHECKLIST
Use the Start-Up checklist to ensure proper start-up procedures are followed.
17
Page 18
OUTDOOR COIL
INDOOR COIL
B
A
ACCUMULATOR
COMPRESSOR
Check Valves
A
Open
B
Closed
C
Open
D
Closed
LCS Loss of Charge Switch
LEGEND
Acutrol Metering Device
Check Valve (Arrow indicates direction of flow)
HEATING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is directed to thecooling liquid line check valve.It is then condensed and directed through subcooling circuits and out to the strainer and the check valve in the heating liquid line.
2. The refrigerant then feeds the outdoor coil through the Acutrol metering device on each circuit.
Fig. 14—Typical Heat Pump Operation, Heating Mode
OUTDOOR COIL
LCS
STRAINER
D
STRAINER
C
3. Each circuit evaporates the refrigerant and the circuits are com­bined in theoutdoor header with someof the circuits flowing through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.
INDOOR COIL
C95045
A
ACCUMULATOR
COMPRESSOR
Check Valves
A
Closed
B
Open
C
Closed
D
Open
LCS Loss of Charge Switch
LEGEND
Acutrol Metering Device
Check Valve (Arrow indicates direction of flow)
COOLING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is directed to the heating liquid line check valve. It is then con­densed and subcooledthrough converging circuits. Refrigerantleaves the outdoor coil by way of the strainer and the check valve in the cooling liquid line.
2. The refrigerant then feeds the indoor coil through the Acutrol metering device on each circuit.
Fig. 15—Typical Heat Pump Operation, Cooling Mode
B
LCS
STRAINER
D
STRAINER
C
3. Each circuit evaporates the refrigerant and the circuits are com­bined in the indoor coil header with some of the circuits flowing through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.
C95044
18
Page 19
Table 12—Troubleshooting—Cooling and Heating
SYMPTOM CAUSE REMEDY
Compressor and outdoor fan will not start.
Compressor will not start but outdoor fan
(other than normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
runs.
Compressor cycles
Compressor runs but outdoor fan does not.
Power Failure Call power company
Loss of Charge
Switch open
Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker
Defective thermostat, contractor, transformer, or
Faulty wiring or loose connections in compressor
Compressor motor burned out, seized, or internal
Defective run/start capacitor, overload, start relay Determine cause and replace
Refrigerant overcharge or undercharge
Defective run/start capacitor, overload or start
Faulty outdoor-fan motor or capacitor Replace
Restriction in refrigerant system Locate restriction and remove
Frosted outdoor coil with incorrect
Metering device or low side restricted Remove source of restriction
Insufficient indoor airflow (cooling)
Temperature too low in conditioned area (cooling) Reset thermostat
Outdoor ambient below 40°F (cooling) Install low-ambient kit
Field-installed filter-drier restricted Replace
control relay
Insufficient line voltage Determine cause and correct
Incorrect or faulty wiring Check wiring diagram and rewire correctly
Thermostat setting too high
circuit
overload open
Low input voltage
(20 percent low)
Loss of Charge
Switch open
Defective compressor Replace and determine cause
Insufficient line voltage Determine cause and correct
Blocked outdoor coil (cooling) Determine cause and correct
relay
Defective thermostat Replace thermostat
Dirty air filter Replace filter
Unit undersized for load Decrease load or increase unit size
Thermostat set too low Reset thermostat
Low refrigerant charge Locate leak, repair, and recharge
Leaking valves in compressor Replace compressor
defrost operation (heating)
Air in refrigerant system
outdoor coil dirty or restricted Clean coil or remove restriction
Dirty air filter Replace filter
Dirty outdoor coil Clean coil
Refrigerant overcharged Recover excess refrigerant
Air in refrigerant system
Outdoor or indoor air restricted
or air is recirculating
Low refrigerant charge Check for leaks, repair and recharge
Compressor valves leaking Replace compressor
Restriction in liquid tube Remove restriction
High heat load Check for source and eliminate
Compressor valves leaking Replace compressor
Refrigerant overcharged Recover excess refrigerant
Dirty air filter (cooling) Replace Filter
Low refrigerant charge Check for leaks, repair, and recharge
Normally closed contacts on
defrost board open
Evaluate unit for possible refrigerant leak
Replace component
Lower thermostat setting below room tempera-
Check wiring and repair or replace
Determine cause and correct
Recover refrigerant, evacuate system, and re-
charge to capacities shown on nameplate
Evaluate unit for possible refrigerant leak
Determine cause and replace
Check defrost time settings. Reset as necessary.
Check defrost temperature switch. Replace as necessary.
Recover refrigerant, evacuate system, and re-
Recover refrigerant, evacuate system, and re-
Determine cause and correct
Check filter- replace if necessary
Check condition of relay on board.
Replace board if necessary.
ture
Determine cause
Replace compressor
charge
charge
Increase air quantity
19
Page 20
START-UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No .............................................................................................................................................................
Serial No ..............................................................................................................................................................
Date ......................................................................................................................................................................
Technician ...........................................................................................................................................................
Customer Information(Name/Address) ...........................................................................................................................................................
II. PRE-START-UP
____ Verify that all packing materials have been removed from unit ____ Verify that condensate connection is installed per installation instructions ____ Check all electrical connections and terminals for tightness ____ Check wire proximity to refrigerant tubes and sheet metal edges ____ Check that indoor (indoor) air filter is clean and in place ____ Verify that unit installation is level ____ Check fan wheel propeller for location in housing and setscrew tightness
III. START-UP
Supply Voltage: L1-L2 __________ L2-L3 __________ L3-L1 __________ Compressor Amps: L1(C) __________ L2(S) __________ L3(R) __________ Indoor Fan Amps: __________ Outdoor Fan Amps: __________
TEMPERATURE-Cooling Mode
Outdoor Air Temperature: __________ DB ____________WB Return-Air Temperature: __________ DB __________ WB Cooling Supply Air: __________DB___________WB
PRESSURES-Cooling Mode
Refrigerant Suction __________ psig
Suction Line Temp* ___________
Refrigerant Discharge __________ psig
Discharge Temp†__________
TEMPERATURE-Heating Mode
Outdoor Air Temperature: __________ DB ____________WB Return-Air Temperature: __________ DB __________ WB Cooling Supply Air: __________DB___________WB
PRESSURES-Heating Mode
Refrigerant Suction __________ psig
Suction Line Temp* ___________
Refrigerant Discharge __________ psig
Discharge Temp†__________
____ Verify Refrigerant charge using charging tables
*Measured at suction inlet to compressor †Measured at liquid line leaving outdoor coil
Copyright 2005 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 50zha1si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 6 8
PC 101 Printed in U.S.A. Catalog No. 50ZHA-1SI Pg 20 9-05 Replaces: New
Loading...