NOTE TO INSTALLER—Before installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,
make sure the User’s Manual and Replacement Guide are left with
the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified workers should install, repair, or service
air-conditioning equipment.
Untrained workers can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service people. When working on air-conditioning
equipment, pay attention to precautions in the literature, tags, and
labels attached to the unit, and other safety precautions that may
apply.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6 8
PC 101Printed in U.S.A.Catalog No. 50ZHA-1SIPg 19-05Replaces: New
Page 2
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage.
Before performing service or maintenance operations on
system, turn off main power to unit and install lockout tag.
Turn off accessory heater power switch if applicable.
Recognize safety information. This is the safety-alert symbol.
When you see this symbol in instructions or manuals, be alert to
the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residential construction practices. We require these instructions as a
minimum for a safe installation.
INTRODUCTION
50ZHA heat pump units are fully self-contained and designed for
outdoor installation (See Fig. 1). As shown in Fig. 2, units are
shipped in a horizontal-discharge configuration for installation on
a ground-level slab. All units can be field-converted to downflow
discharge configurations for rooftop applications with a fieldsupplied plenum.
RECEIVING AND INSTALLATION
Step 1—Check Equipment
IDENTIFY UNIT
The unit model number and serial number are stamped on the unit
identification plate. Check this information against shipping papers. Verify that unit voltage and amperage listed on unit rating
plate agree with power supplied for equipment.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet.
If unit appears to be damaged or is torn loose from its securing
points, have it examined by transportation inspectors before
removal. Forward claim papers directly to transportation company.
Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest Carrier Distributor if any item is missing.
To prevent loss or damage, leave all parts in original packages
until installation.
Step 2—Provide Unit Support
SLAB MOUNT
Place the unit on a rigid, level surface, suitable to support the unit
weight. A concrete pad or a suitable fiberglass mounting pad is
recommended. The flat surface should extend approximately 2-in.
beyond the unit casing on the 2 sides. The duct connection side and
condensate drain connection sides should be flush with the edge of
the flat surface.
A 6-in. wide gravel apron should be used around the flat surface to
prevent airflow blockage by grass or shrubs. Do not secure the unit
to the flat surface except where required by local codes.
The unit should be level to within 1/4 inch. This is necessary for
the unit drain to function properly.
GROUND MOUNT
The unit may also be installed directly on the ground if local codes
permit. Place unit on level ground prepared with gravel for
condensate discharge.
HURRICANE HOLD DOWN
Contact you local distributor for specific hurricane hold down
details and PE (Professional Engineer) certification when required.
Step 3—Provide Clearances
The required minimum service clearances and clearances to
combustibles are shown in Fig. 2. Adequate ventilation and
outdoor coil air must be provided.
The outdoor fan pulls air through the outdoor coil and discharges
it through the fan on the top cover. Be sure that the fan discharge
does not recirculate to the outdoor coil. Do not locate the unit in
either a corner or under an overhead obstruction. The minimum
clearance under a partial overhang (such as a normal house
overhang) is 48 in. above the unit top. The maximum horizontal
extension of a partial overhang must not exceed 48 inches.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. The unit may be installed on
wood flooring or on Class A, B, or C roof covering materials.
OPERATIONAL HAZARD
Failure to follow this caution may result in unit component
damage.
Do not restrict outdoor coil airflow. An air restriction at either
the outdoor-air inlet or the fan discharge can be harmful to
compressor life.
Step 4—Place Unit
Unit can be moved with the rigging holds provided in the unit base.
Refer to Table 2 for operating weights. Use extreme caution to
prevent damage when moving the unit. Unit must remain in an
upright position during all moving operations. The unit must be
level with in 1/4” for proper condensate drainage; the ground-level
pad must be level before setting the unit in place. When a
field-fabricated support is used, be sure that the support is level
and that it properly supports the unit.
Step 5—Select and Install Ductwork
The design and installation of the duct system must be in
accordance with:
• the standards of the NFPA (National Fire Protection Association) for installation of nonresidence-type air conditioning and
ventilating systems
• NFPA90A or residence-type, NFPA90B; and/or local codes
and residence-type, NFPA 90B
• and/or local codes and ordinances
Select and size ductwork, supply-air registers and return-air grilles
according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply- and return-air
openings on the side of the unit. See Fig. 2 for connection sizes and
locations. The 14-in. round duct collars are shipped inside the unit
attached to the base pan in the indoor blower compartment. They
are field-installed and must be removed from the indoor blower
compartment prior to start-up, even if they are not used for
installation.
When designing and installing ductwork, consider the following:
UNIT DAMAGE HAZARD
Failure to follw this caution may result in damage to unit
components. When connecting ductwork to units, do not drill
deeper than 3/4 inch in shaded area shown in Fig. 3 or coil
may be damaged.
• All units should have field-supplied filters installed in the
return-air side of the unit. Recommended sizes for filters are
shown in Table 2.
• Avoid abrupt duct size increases and reductions. Abrupt change
in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weathertight and airtight seal. When electric heat is
installed, use fire proof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24–in.
from the unit discharge connection flange into the ductwork.
• Size ductwork for cooling air quantity (cfm). The minimum air
quantity for proper electric heater operation is listed in Table 3.
Heater limit switches may trip at air quantities below those
recommended.
• Insulate and weatherproof all external ductwork. Insulate and
cover with a vapor barrier all ductwork passing through
conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air
Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning
systems.
• Secure all ducts to building structure. Flash, weatherproof, and
vibration-isolate duct openings in wall or roof according to
good construction practices.
Figure 4 shows a typical duct system with 50ZHA unit installed.
CONVERTING HORIZONTAL DISCHARGE UNITS TO
DOWNFLOW (VERTICAL) DISCHARGE
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before performing service or maintenance operations on
system, turn off main power to unit and install lockout tag.
Turn off accessory heater power switch if applicable.
Units are dedicated side supply products. They are not convertible
to vertical air supply. A field-supplied plenum must be used to
convert to vertical air discharge.
Step 6—Provide for Condensate Disposal
NOTE: Be sure that condensate-water disposal methods comply
with local codes, restrictions, and practices.
Unit removes condensate through a 1 3/64-in. ID hole (using
3/4-in. OD piping or tubing) which is located at the end of the unit.
See Fig. 2 for location of condensate connection.
19.17
3.92
Fig. 3—Area Not to Be Drilled More Than 3/4-in.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in groundlevel installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. lower than the drain-pan
condensate connection to prevent the pan from overflowing. Prime
the trap with water. When using a gravel apron, make sure it slopes
away from the unit.
If the installation requires draining the condensate water away
from the unit, install a 2-in. trap using a 3/4-in. OD tubing or pipe.
(See Fig. 5 and 6.) Make sure that the outlet of the trap is at least
1 in. lower than the unit drain-pan condensate connection to
prevent the pan from overflowing. Prime the trap with water.
Connect a drain tube using a minimum of 3/4-in. PVC, 3/4-in.
CPVC, or 3/4-in. copper pipe (all field supplied). Do not undersize
the tube. Pitch the drain tube downward at a slope of at least 1 in.
for every 10 ft of horizontal run. Be sure to check the drain tube
for leaks. Prime trap at the beginning of the cooling season
start-up. Allowable glues for condensate trap connection are:
Standard ABS, CPVC, or PVC cement.
4
A05195
Page 5
Table 2—Physical Data
UNIT 50ZHA024030036042048060
OPERATING WEIGHT (lbs)293324377389384433
COMPRESSOR TYPEScrollUltra Tech Scroll
15.8
20
4.9
Direct Drive
R-22
Propeller
Round
14
14
2...21
15.8
3200
20
1/4 (1100)
4...17
6.1
1400
11x9
3/4 (1050)
2...21
13.3
3200
20
1/4 (1100)
4...17
4.9
1600
11x10
1 (1050)
2...21
15.8
3300
20
1/2 (1100)
4...17
6.1
1875
11x10
1 (1050)
REFRIGERANT Charge (lb)
REFRIGERANT METERING DEVICE
*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min
for high capacity type. Recommended filters are 1-in. thick.
Orifice ID (in.)
Orifice OD (in.).049.057.059.063.070.073
CONDENSER COIL
Rows...Fins/in.
Face Area (sq. ft.)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor HP (RPM)
EVAPORATOR COIL
Face Area (sq. ft.)
Evaporator Blower
Nominal Airflow (CFM)
Size (in.)
Motor HP (RPM)
CONNECTING DUCT SIZES
Supply Air (in.)
Return Air (in.)
Return-Air Filters (in.)*
Throwaway
7.510.310.311.911.413.3
AccuraterTXV
.067.067.082.086——
Copper Tubes, Aluminum Plate Fins
2...21
11.1
2600
20
1/8 (825)
3...17
4.3
800
10x8
1/2 (1050)
24x2424x2424x2424x3030x3030x30
2...21
12.7
2600
20
1/8 (825)
3...17
4.9
1000
10x8
1/2 (1050)
2...21
3200
1/4 (1100)
Copper Tubes, Aluminum Plate Fins
4...17
1200
11x9
3/4 (1050)
Step 7—Install Electrical Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground in
the control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electrical Code), ANSI (American National Standards
Institute)/NFPA (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
UNIT DAMAGE HAZARD
Failure to follow these precautions may result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local
codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate.
4. Insulate low-voltage wires for highest voltage contained
within conduit when low-voltage control wires are run in
same conduit as high-voltage wires.
5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc.
Consult local power company for correction of improper
voltage.
HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a fieldsupplied, waterproof disconnect switch mounted at, or within sight
from the unit. Refer to the unit rating plate for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
wire sizing. See Table 6 for electrical data.
The field-supplied disconnect may be mounted on the unit over the
high-voltage inlet hole. (See Fig. 2.)
5
Page 6
INDOOR
THERMOSTAT
RETURN
AIR
TOP COVER
Power Wiring
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND
LOW-VOLTAGE
ENTRY
COMPOSITE
RUST-PROOF
BASEPAN
CONDENSATE
DRAIN
CONNECTION
*Separate disconnect per NEC
(National Electrical Code) required
for electric heater when singlepoint conection is not used.
FROM
POWER
SOURCE
DISCONNECT
PER NEC*
(UNIT AND
ELECTRIC
HEATER)
C00008
C00008
Fig. 4—Typical installation
1” (25mm) MIN.
TRAP
OUTLET
2” (50mm) MIN.
C99013
Fig. 5—Condensate Trap (Using Tubing)
TRAP
OUTLET
1" min.
2" min.
C00009
Fig. 6—PVC Condensate Trap
Table 3—Minimum Airflow for Safe Electric Heater
Operation (CFM)
SIZE024030036042048060
Cfm600750900105012001500
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage. Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect
warranty.
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The highvoltage leads should be in a conduit until they enter the unit;
conduit termination at the unit must be watertight. Run the
high-voltage leads through the hole on the control box side of the
unit (see Fig. 7 for location). When the leads are inside the unit,
run leads to the control box (Fig. 8). For single-phase units,
connect leads to the black and yellow wires (see Fig. 9).
CONNECTING GROUND LEAD TO UNIT GROUND
Refer to Fig. 8 and 9. Connect the ground lead to the chassis using
the unit ground in the control box.
ROUTING CONTROL POWER WIRES
Form a drip-loop with the thermostat leads before routing them
into the unit. Route the thermostat leads through grommeted hole
provided in unit into unit control box (See Fig. 7). Connect
thermostat leads and unit power leads as shown in Fig. 9, 10A &
10B.
Route thermostat wires through grommet providing a drip-loop at
the panel. Connect low-voltage leads to the thermostat as shown in
Fig. 10A & 10B.
The unit transformer supplies 24-v power for complete system
including accessory electrical heater. Transformer is factory wired
for 230-v operation.
ACCESSORY ELECTRIC HEAT WIRING
Refer to accessory electric heat installation instructions for information on installing accessory electric heat. Accessory electric
heat wiring is shown in Fig. 11A, 11B, & 11C.
PRE-START-UP
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to observe the following warnings could result in
serious injury, death and/or property damage:
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to
unit unless compressor terminal cover is in place and
secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected and lockout tag is installed.
4. Relieve all pressure from both high- and low-pressure sides
of the system before touching or disturbing anything inside
terminal box if refrigerant leak is suspected around compressor terminals. Use accepted methods to recover refrigerant.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure. To remove a
component, wear protective goggles and proceed as follows:
a. Shut off electrical power to unit and install lockout tag.
b. Relieve all refrigerant from system using both high- and
low-pressure ports. Use accepted methods to recover
refrigerant.
c. Cut component connecting tubing with tubing cutter and
remove component from unit.
d. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Use the Start-Up Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with unit.
Make the following inspections:
a. Inspect for shipping and handling damages such as broken
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using
electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, see following Check for Refrigerant
Leaks section.
c. Inspect all field- and factory-wiring connections. Be sure
that connections are completed and tight. Ensure wires do
not contact refrigerant tubing or sheet metal edges.
d. Inspect coil fins. If damaged during shipping and handling,
carefully straighten fins with a fin comb.
3. Verify the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned in
fan orifice. Top edge of blade should be 3.125 in. down
from outdoor coil outlet grille (size 024–048, See Fig. 12)
or hub should be 0.708-in. away from motor end bell (size
060, See Fig. 13). See Outdoor Fan Adjustment section.
b. Make sure that air filter is in place.
c. Make sure that condensate drain trap is filled with water to
ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts have
been removed.
7
Page 8
HIGH-VOLTAGEPOWER
WIRINGENTRYHOLE
LOW-VOLTAGEWIRING
ENTRYHOLE
A05198
Fig. 7—Unit Electrical Connection
C00011
Fig. 8—Control Box Wiring
START-UP
Use the Start-Up Checklist supplied at the end of this book and
proceed as follows:
Step 1—Check for Refrigerant Leaks
LOCATE AND REPAIR REFRIGERANT LEAKS AND
CHARGE THE UNIT AS FOLLOWS:
1. Using both high- and low-pressure ports, locate leaks and
reclaim remaining refrigerant to relieve system pressure.
2. Repair leak following accepted practices.
NOTE: Install a liquid-line filter drier whenever the system has
been opened for repair.
Step 2—Start-Up Cooling Section and Make Adjustments
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
Complete the required procedures given in the Pre-Start- Up
section this page before starting the unit. Do not jumper any
safety devices when operating the unit.
Do not operate the compressor in cooling mode when the
outdoor temperature is below 40 F.
Do not rapid-cycle the compressor. Allow 5 minutes between
‘‘on’’ cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as
follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down within 60 seconds (for
024-042) or 90 seconds (for 048 and 060) when FAN switch
is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in
AUTO position. Set cooling control below room temperature.
Observe that compressor, outdoor fan, and indoor blower
motors start and that reversing valve shifts. Observe that
cooling cycle shuts down when control setting is satisfied.
Reversing valve (RV) remains energized.
3. Place system switch in HEAT position. Observe that compressor, indoor fan and outdoor fan energize (Reversing Valve is
deenergized in heat pump heating mode). Set control above
room temperature. Observe that heating cycle shuts down
when control setting is satisfied.
4. When using an automatic changeover room thermostat, place
both SYSTEM and FAN switches in AUTO. positions.
Observe that unit operates in Cooling mode when temperature
control is set to ‘‘call for cooling’’ (below room temperature),
and unit operates in Heating mode when temperature control
is set to “call for heating” (above room temperature).
Step 3—Refrigerant Charge
Refrigerant Charge — Amount of refrigerant charge is listed on
unit nameplate and in Table 2. Refer to Carrier Refrigerant Service
Techniques Manual, Refrigerants section. Unit panels must be in
place when unit is operating during charging procedure. Unit must
operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer to Carrier Refrigerant Service Techniques. Use standard
evacuating techniques. After evacuating system, weigh in the
specified amount of refrigerant (refer to Table 2).
UNIT GROUND
GROUND
LEAD
3-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
Fig. 9—Line Power Connections
SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
L
L
L
BLK
YEL
BLU
C00012
8
Page 9
Thermostat
G
Y
W2
W3
R
RED
GREEN
O
ORANGE
C
BROWN
WHITE
VIOLET
G
Y
Y1
O
R
RED
GREEN
YELLOW
W2
PINK
W3
ORANGE
WHITE
VIOLET
C
BROWN
and subbase
Unit Control
Power
A05207
Fig. 10A—Control Connections (Sizes 024-042)
3. Insulate the temperature sensing device so that the outdoor
ambient doesn’t affect the reading.
4. Locate the measured suction line pressure in the top row of
Table 8 and the measured outdoor ambient temperature in the
left column of the table. Based on the two values, determine
the required suction line temperature.
5. If the measured suction line temperature is greater than the
tabulated temperature, add charge in the system.
048 and 060 units:
1. Measure discharge line pressure by attaching a gauge to the
service port.
2. Measure the liquid line temperature by attaching a temperature
sensing device to it.
3. Insulate the temperature sensing device so that the outdoor
ambient doesn’t affect the reading.
4. Refer to the required subcooling in Tables 4 and 5 to find the
required subcooling based on the model size and the outdoor
ambient temperature.
5. Interpolate if the outdoor temperature lies in between the table
values. Extrapolate if the temperature lies beyond the table
range.
6. Find the pressure value corresponding to the measured pressure on the compressor discharge line.
7. Read across from the pressure reading to obtain the Liquid line
temperature for a required subcooling.
8. Add charge if the measured temperature is higher than the
liquid line temperature value in the table.
9. Add charge using the service connection on the suction line of
the compressor.
HEATING MODE CHARGE
Do not attempt to adjust charge by cooling methods while in heat
pump heating mode. Recover refrigerant and weigh in according to
unit data plate refrigerant data.
Step 4—Indoor Airflow and Airflow Adjustments
NOTE: For cooling operation, the recommended airflow is 350 to
450 cfm per each 12,000 Btuh of rated cooling capacity.
Table 7 shows dry coil air delivery for horizontal discharge units.
Tables 9-11 show pressure drops.
NOTE: Be sure that all supply- and return-air grilles are open,
free from obstructions, and adjusted properly.
Thermostat
and subbase
Unit Control
Power
A05208
Fig.10B—Control Connections (Sizes 048-060)
LOW CHARGE COOLING
024-042 units:
1. Measure suction line pressure by attaching a gauge to the
service port.
2. Measure the suction line temperature by attaching a temperature sensing device to it.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect electrical power to the unit and install lockout tag
before changing blower speed.
Airflow can be changed by changing the 24 volts lead connections
of the blower motor.
Unit 50ZHA blower motors are factory wired for rated airflow
operation.
Fig. 11A—Typical Unit Electrical Diagram (Sizes 024-042)
10
A05199
Page 11
Fig. 11B—Typical Unit Electrical Diagram (Sizes 048-060)
11
A05200
Page 12
A05209
Fig. 11C—Accessory Electric Heater Wiring
Table 6—Electrical Data—50ZHA
VOLTAGE
UNIT SIZE
50ZHA
024208/230–1–6018725310.954.00.94.1
030208/230–1–6018725313.572.50.94.1
036208/230–1–6018725317.588.01.56.0
042208/230–1–6018725319.4104.01.56.0
048208/230–1–6018725324.7116.01.57.7
060208/230–1–6018725328.0118.03.07.7
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be Power Supply fuse. The CGA (Canadian Gas Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC.
V-PH-HZ
RANGE
MINMAXRLALRANominal KW*FLAMCA
COMPRESSOR
OFM
FLA
IFM
FLA
ELECTRIC HEATSINGLE POINT POWER SUPPLY
FUSE OR
CKT BKR
—/—
3.8/5.0
7.5/10.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
18.6/18.6
41.2/44.7
63.8/70.7
51.1/56.1
21.8/21.8
44.4/47.9
57.0/73.9
89.5/100.0
54.3/59.3
29.4/29.4
52.0/55.4
74.5/81.5
97.1/107.5
61.9/66.9
31.7/31.7
54.3/57.8
76.9/83.8
99.4/109.9
122.0/135.9
63.2/69.2
40.0/40.0
62.6/66.1
85.1/92.1
107.7/118.1
130.3/144.2
72.5/77.5
45.7/45.7
68.2/71.7
90.8/97.8
113.4/123.8
135.9/149.9
78.2/83.2
25/25
45/50
—
50/50
30/30
50/50
—
—
60/60
35/35
60/60
—
—
—
40/40
—
—
—
—
—
50/50
—
—
—
—
—
60/60
—
—
—
—
—
MOCP
—
—
60/70
—
—
—
70/70
90/100
—
—
—
80/80
100/100
70/70
—
60/70
80/90
100/110
110/150
70/80
—
80/80
100/100
110/125
125/125
90/90
—
90/90
100/110
125/125
125/150
90/100
12
Page 13
Table 7—Dry Coil Air Delivery* Horizontal Discharge
(Deduct 10 percent for 208 Volt Operation)
50ZHASPEED TAPWATTS/C.F.M
1
024
2
2
030
3
1
036
2
3
042
4
1
2
048
3
4
1
2
060
3
4
Air delivery values are based on operating voltage of 230-v., dry coil, without filter or electric heater. Deduct wet coil, filter, and electric heater pressure drops to obtain
external static pressure availabe for ducting.
Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.
Watts -99100118130142----
C.F.M. -848793757698632----
Watts -----222233244257260
C.F.M -----970918861795729
Watts -155146157170-----
C.F.M-1108995951884-----
Watts -----261275286291315
C.F.M. -----111710531014980877
Watts 180166179191204216----
C.F.M.134412151172113610951051----
Watts---261276290301316329342
C.F.M.---1343130412721234119011481100
Watts269283305321336349360---
C.F.M.1440140413691333130112731239---
Watts--418432450465480490503518
C.F.M.--15721543150414751441141813801332
Watts—204209216229236249———
C.F.M.—112910871027994932881———
Watts——233245254266276289——
C.F.M.——1164112210661025954906——
Watts386398409418425435438441451—
C.F.M.168016521625158315551515147714441403—
Watts—440448457462469477480485486
C.F.M.—174517171684165116121573153715081470
Watts224235251266277291298---
C.F.M.1334128812591224118111571117---
Watts--286301311325333344370-
C.F.M.--1333129612611232119911701062-
Watts608626643660668685697---
C.F.M.1931190018781844181717891755---
Watts737755770787799817826812782-
C.F.M.209320612028200119711934189918501757-
0.10.2.030.40.50.60.70.80.91.0
EXTERNAL STATIC PRESSURE
RATED AIRFLOWHIGH AIRFLOW
SIZE
048Tap 1Tap 3Tap 2Tap 4
060Tap 1Tap 3Tap 2Tap 4
Low
Stage
High
Stage
Low
Stage
High
Stage
Step 5—Unit Controls
All compressors have the following internal-protection controls.
HIGH-PRESSURE RELIEF VALVE
This valve opens when the pressure differential between the low
and high side becomes excessive.
LOSS OF CHARGE SWITCH
Located on the outdoor liquid line is a low-pressure switch which
functions as a loss-of-charge switch. This switch contains a
Schrader core depressor. This switch opens at 7 psig and closes at
22 psig. No adjustment is necessary.
COMPRESSOR OVERLOAD
This overload interrupts power to the compressor when either the
current or internal temperature become excessive, and automatically resets when the internal temperature drops to a safe level.
This overload may require up to 60 minutes (or longer) to reset;
therefore, if the internal overload is suspected of being open,
disconnect the electrical power to the unit and check the circuit
through the overload with an ohmmeter or continuity tester.
Step 6—Sequence of Operation
FAN OPERATION
The FAN switch on the thermostat controls indoor fan operation.
When the FAN switch is placed in the ON position, the IFR
(indoor-fan relay) is energized through the G terminal on the
thermostat. The normally-open contacts close, which then provide
power to the indoor (evaporator) fan motor (IFM). The IFM will
run continuously when the FAN switch is set to ON.
When the FAN switch is set to AUTO, the thermostat deenergizes
the IFR (provided there is not a call for cooling). The contacts open
and the IFM is deenergized. The IFM will be energized only when
there is a call for cooling, in heat pump heating mode or if the unit
is equipped with accessory electric heat, the indoor-fan motor will
also run while the accessory electric heat is energized.
NOTE: Some units are equipped with a time-delay relay. On
these units, the indoor fan remains on for 30 seconds after G or Y
is deenergized.
With a call for cooling (Y/Y2), the indoor fan energizes immediately whereas the contactor energizes aftera5minute time delay
(in case of initial start-up) starting the compressor and the outdoor
fan motor. When the cooling demand is met, Y/Y2 de-energizes,
shutting the compressor, indoor fan and the outdoor fan.
COOLING OPERATION (SIZES 048 AND 060)
These units utilize a 2 stage indoor thermostat. With a first stage
call for cooling (Y1), the indoor fan (low stage) energizes
immediately whereas the contactor energizes aftera5minute time
delay (in case of an initial start-up) starting the compressor (low
stage) and the outdoor fan motor. If the low stage operation cannot
satisfy the cooling demand, the second stage cooling (Y2) energizes switching the compressor into high stage cooling through
energizing an internal solenoid valve inside the scroll compressor
and switching the indoor fan into high stage. When second stage
cooling is satisfied, Y2 de-energizes switching the compressor and
the indoor fan into low stage cooling. When the low stage cooling
demand is met, Y1 de-energizes shutting the compressor, indoor
fan and the outdoor fan.
HEATING OPERATION (SIZES 024-042)
With a call for heating (Y1), the indoor fan (low stage) energizes
immediately whereas the contactor energizes aftera5minute time
delay (in case of initial start-up) starting the compressor and the
outdoor fan motor. If Y/Y2 cannot satisfy the heating demand, the
auxiliary or backup heat (W2) energizes. In case of staged heating,
W3 is energized if the demand is not met. The highest airflow
selected is run while the electric heat is in operation. When heating
demand is met, W3, W2 and Y/Y2 sequentially de-energize
shutting the compressor, indoor fan and the outdoor fan.
HEATING OPERATION (SIZES 048 AND 060)
With a first stage call for heating (Y1), the indoor fan (low stage)
energizes immediately whereas the contactor energizes after a 5
minute time delay (in case of initial start-up) starting the compressor (low stage) and the outdoor fan motor. If the low stage
oepration cannot satisfy the heating demand, the second stage
heating (Y2) energizes switching the compressor into high stage
heating through energizing an internal solenoid valve inside the
scroll compressor and switching the indoor fan into high stage. The
auxiliary or backup heat is controlled by a third stage (W2). If the
demand is not met, W3 is energized in case of staged heating.
When heating demand is satisfied, W3, W2 and Y2 sequentially
de-energize switching the compressor and the indoor fan into low
stage heating. When the low stage heating demand is met, Y1
de-energizes shutting the compressor, indoor fan and the outdoor
fan.
CONTINUOUS FAN
With the continuous Indoor fan option selected on the thermostat,
G is continuously energized. In case of 024-042 units, the selected
airflow setting is provided. In case of 048 and 060 units, the
system runs low stage (Y1) airflow for continuous fan operation.
DEFROST
Defrost board (DB) is a time and temperature control, which
includes a field-selectable time period between checks for defrost
(30, 60, 90 and 120 minutes). The time period is factory-set at 60
minutes and should only be adjusted by a trained service person.
Electronic timer and defrost cycle start only when contactor is
energized and defrost thermostat (DFT) is closed.
Defrost mode is identical to Cooling mode. The outdoor fan motor
stops because of “OF1” and “OF2” contacts opening on the defrost
board, a bank of optional electric heat turns on to warm air
supplying the conditioned space.
ELECTRIC RESISTANCE HEATING
If accessory electric heaters are installed, on a call for “Emergency
Heat” the thermostat energizes W which energizes the heater relay
and in turn energizes the electric heaters. The IFR is energized
which starts the indoor-fan motor. If the heaters are staged, W2 is
energized when the second stage of heating is required. When the
need for heating is satisfied, the heater and IFM are de-energized.
MAINTENANCE
To ensure continuing high performance, and to reduce the possibility of premature equipment failure, periodic maintenance must
14
Page 15
be performed on this equipment. This cooling unit should be
inspected at least once each year by a qualified service person. To
troubleshoot cooling of units, refer to Troubleshooting chart in
back of book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment, other than those
procedures recommended in the User’s Manual.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, outdoor coil, drain pan, and condensate
drain each cooling and heating season for cleanliness. Clean
when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling
and heating season. Clean when necessary. For first heating
season, inspect blower wheel bimonthly to determine proper
cleaning frequency.
4. Check electrical connections for tightness and controls for
proper operation each cooling season. Service when necessary.
5. Check the drain channel in the top cover periodically for
blockage (leaves, insects). Clean as needed.
FIRE, EXPLOSION, ELECTRICAL SHOCK, CUT HAZARD
Failure to follow these warnings could result in serious
personal injury, death, and/or property damage:
1. Turn off electrical power to the unit and install lockout tag
before performing any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts. As
with any mechanical equipment, personal injury can result
from sharp edges, etc.
3. Never place anything combustible either on, or in contact
with, the unit.
Step 1—Air Filter
NOTE: Never operate the unit without a suitable air filter in the
return-air duct system. Always replace the filter with the same size
as originally installed. See Table 2 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during
each cooling season or whenever the filters become clogged with
dust and lint.
Replace filters with the same dimensional size and type as
originally provided, when necessary.
Step 2—Unit Top Removal (Outdoor-Coil Side)
NOTE: When performing maintenance or service procedures that
require removal of the unit top, be sure to perform all of the routine
maintenance procedures that require top removal, including coil
inspection and cleaning, and condensate drain pan inspection and
cleaning.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect and tag electrical power to the unit before
removing top.
Only qualified service personnel should perform maintenance and
service procedures that require unit top removal.
Refer to the following top removal procedures:
1. Remove screws on unit top cover surface. (Save all screws.)
2. Remove screws on unit top cover flange. (Save all screws.)
3. Lift top from unit carefully. Set top on edge and make sure
that top is supported by unit side that is opposite duct (or
plenum) side.
4. Carefully replace and secure unit top to unit, using screws
removed in Steps 1 and 2, when maintenance and/or service
procedures are completed.
Step 3—Indoor Blower and Motor
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect and tag electrical power to the unit before
cleaning the blower wheel.
To clean the blower wheel follow the following steps:
1. Remove the blower housing:
a. Remove the screws on the external side of the duct panel
that fasten the housing to the duct panel assembly.
b. Remove the side access panel and unscrew the mounting
bracket that fastens the blower housing to the internal
partition panel fo the control box assembly.
c. Make sure that the blower housing is supported by hand
before completely removing the mounting bracket.
d. Slide the blower housing from the rails of the duct panel
and place it outside the unit.
2. Remove the blower wheel from the housing:
a. Loosen the set screw which secures the wheel to the motor
shaft.
b. Loosen the three mounting legs of the motor by removing
the bolts that fasten themounting legs to the housing.
c. Slide out the motor assembly (motor, belly band and the 3
mounting legs) from the hub of the wheel.
d. Remove the filler panel at the discharge end of the blower
housing by removing the two screws that fasten it to the
housing.
e. Remove the wheel form the housing.
3. Remove the caked on dirt from the wheel and the motor using
a brush.
4. Remove lint and dirt accumulations from the wheel and
housing with a vacuum cleaner, using a soft brush attachment.
a. Slip the wheel back in the housing with the hub set screw
parented in the correct direction.
b. Install the filler panel.
c. Reinsert the motor assembly in the wheel hub and align the
mounting legs with the housing mounting hold locations.
d. Tighten the mounting bolts to fasten the motor assembly
with the housing.
e. Center the wheel in the housing by sliding it, align the flat
end of the shaft with the set screw and tighten the set screw.
f. Slide back the blower housing into the mounting rails in the
duct panel and install the mounting bracket back in its
position.
g. Install the screws on the external side of the duct panel to
fasten duct panel with the housing.
h. Replace the side access panel.
Step 4—Outdoor Coil, Indoor Coil, and Condensate
Drain Pan
Inspect the outdoor coil, indoor coil, and condensate drain pan at
least once heating and cooling season. Proper inspection and
cleaning requires the removal of the unit top. See Unit Top
Removal section.
coil fins from inside to outside the unit. On units with an outer and
inner outdoor coil, be sure to clean between the coils. Be sure to
flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring,
or air filter(s). If the drain tube is restricted, clear it with a
‘‘plumbers snake’’ or similar probe device. Ensure that the
auxiliary drain port above the drain tube is also clear.
Step 5—Outdoor Fan
UNIT OPERATIONAL HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the Outdoor fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
1. Shut off unit power supply and install lockout tag.
2. Remove outdoor-fan assembly (grille, motor, motor cover,
and fan) by removing screws and flipping assembly onto unit
top cover.
Remove all obstructions (including weeds and shrubs) that interfere with the airflow through the outdoor coil. Straighten bent fins
with a fin comb. If coated with dirt or lint, clean the coils with a
vacuum cleaner, using a soft brush attachment. Be careful not to
bend the fins. If coated with oil or grease, clean the coils with a
mild detergent-and-water-solution. Rinse coils with clear water,
using a garden hose. Be careful not to splash water on motors,
insulation, wiring or air filter(s). For best results, spray outdoor-
CFM
Step 6—Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit and install lockout
tag.
Remove the top panel to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connections are
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.
3.125 in.
C00021
Fig. 12—Outdoor-Fan Adjustment (024–048 Size)
Check to ensure no wires are touching refrigerant tubing or sharp
sheet metal edges. Move and secure wires to isolate from tubing
and sheet metal edges.
16
Page 17
0.708in.
C02017
Fig. 13—Outdoor-Fan Adjustment (060 Size)
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the Sequence of Operation section, as an aid in
determining proper control operation.
Step 7—Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil
accumulations annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak-detector, or
liquid-soap solution. If a refrigerant leak is detected, refer to Check
for Refrigerant Leaks section. (See Table of Contents for page
number.)
If no refrigerant leaks are found and low cooling performance is
suspected, refer to Refrigerant Charge. (See Table of Contents for
page number.)
Step 8—Indoor Airflow
The cooling airflow does not require checking unless improper
performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from obstructions,
and that the air filter is clean. When necessary, refer to Indoor
Airflow and Airflow Adjustments section to check the system
airflow.
Step 9—Metering Devices
Refrigerant cooling metering device is an Accurator (024-042) or
TXV (048 and 060) located upstream of the indoor coil distributor
assembly. Refrigerant heating mode metering device is an Accurater located upstrem of the outdoor coil distributor assembly.
Step 10—Lubrication
COMPRESSOR—The compressor is charged with the correct
amount of oil at the factory.
FAN MOTOR BEARINGS—Fan motor bearings are permanently lubricated. No further lubrication of outdoor or indoor fan
motors is required.
Step 11—Liquid Line Strainer
The liquid line strainer (to protect metering device) is made of wire
mesh and is located in the liquid line on the inlet side of the
metering device.
Check valves are also located in the liquid lines near the strainers.
The Strainers are the larger of the two components.
Step 12—High Flow Valves
Located on the compressor hot gas and suction tubes are High
Flow Valves. Large black plastic caps distinguish these valves
with O-rings located inside the caps. These valves cannot be
accessed for service in the field. Ensure the plastic caps are in
place and tight or the possibility of refrigerant leakage could occur.
TROUBLESHOOTING
Use the Troubleshooting Cooling and Heating guide if problems
occur with these units.
START-UP CHECKLIST
Use the Start-Up checklist to ensure proper start-up procedures are
followed.
17
Page 18
OUTDOOR COIL
INDOOR COIL
B
A
ACCUMULATOR
COMPRESSOR
Check Valves
A
Open
B
Closed
C
Open
D
Closed
LCSLoss of Charge Switch
LEGEND
Acutrol Metering Device
Check Valve (Arrow indicates direction of flow)
HEATING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is
directed to thecooling liquid line check valve.It is then condensed
and directed through subcooling circuits and out to the strainer
and the check valve in the heating liquid line.
2. The refrigerant then feeds the outdoor coil through the Acutrol
metering device on each circuit.
Fig. 14—Typical Heat Pump Operation, Heating Mode
OUTDOOR COIL
LCS
STRAINER
D
STRAINER
C
3. Each circuit evaporates the refrigerant and the circuits are combined in theoutdoor header with someof the circuits flowing through
the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator,
and back to the compressor.
INDOOR COIL
C95045
A
ACCUMULATOR
COMPRESSOR
Check Valves
A
Closed
B
Open
C
Closed
D
Open
LCSLoss of Charge Switch
LEGEND
Acutrol Metering Device
Check Valve (Arrow indicates direction of flow)
COOLING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is
directed to the heating liquid line check valve. It is then condensed and subcooledthrough converging circuits. Refrigerantleaves
the outdoor coil by way of the strainer and the check valve in the
cooling liquid line.
2. The refrigerant then feeds the indoor coil through the Acutrol
metering device on each circuit.
Fig. 15—Typical Heat Pump Operation, Cooling Mode
B
LCS
STRAINER
D
STRAINER
C
3. Each circuit evaporates the refrigerant and the circuits are combined in the indoor coil header with some of the circuits flowing
through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator,
and back to the compressor.
C95044
18
Page 19
Table 12—Troubleshooting—Cooling and Heating
SYMPTOMCAUSEREMEDY
Compressor and outdoor fan will not start.
Compressor will not start but outdoor fan
(other than normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
runs.
Compressor cycles
Compressor runs but
outdoor fan does not.
Power FailureCall power company
Loss of Charge
Switch open
Fuse blown or circuit breaker trippedReplace fuse or reset circuit breaker
Defective thermostat, contractor, transformer, or
Faulty wiring or loose connections in compressor
Compressor motor burned out, seized, or internal
Defective run/start capacitor, overload, start relayDetermine cause and replace
Refrigerant overcharge or undercharge
Defective run/start capacitor, overload or start
Faulty outdoor-fan motor or capacitorReplace
Restriction in refrigerant systemLocate restriction and remove
Frosted outdoor coil with incorrect
Metering device or low side restrictedRemove source of restriction
Insufficient indoor airflow (cooling)
Temperature too low in conditioned area (cooling)Reset thermostat
Insufficient line voltageDetermine cause and correct
Incorrect or faulty wiringCheck wiring diagram and rewire correctly
Thermostat setting too high
circuit
overload open
Low input voltage
(20 percent low)
Loss of Charge
Switch open
Defective compressorReplace and determine cause
Insufficient line voltageDetermine cause and correct
Blocked outdoor coil (cooling)Determine cause and correct
relay
Defective thermostatReplace thermostat
Dirty air filterReplace filter
Unit undersized for loadDecrease load or increase unit size
Thermostat set too lowReset thermostat
Low refrigerant chargeLocate leak, repair, and recharge
Leaking valves in compressorReplace compressor
defrost operation (heating)
Air in refrigerant system
outdoor coil dirty or restrictedClean coil or remove restriction
Dirty air filterReplace filter
Dirty outdoor coilClean coil
Refrigerant overchargedRecover excess refrigerant
Air in refrigerant system
Outdoor or indoor air restricted
or air is recirculating
Low refrigerant chargeCheck for leaks, repair and recharge
Compressor valves leakingReplace compressor
Restriction in liquid tubeRemove restriction
High heat loadCheck for source and eliminate
Compressor valves leakingReplace compressor
Refrigerant overchargedRecover excess refrigerant
Dirty air filter (cooling)Replace Filter
Low refrigerant chargeCheck for leaks, repair, and recharge
Normally closed contacts on
defrost board open
Evaluate unit for possible refrigerant leak
Replace component
Lower thermostat setting below room tempera-
Check wiring and repair or replace
Determine cause and correct
Recover refrigerant, evacuate system, and re-
charge to capacities shown on nameplate
Evaluate unit for possible refrigerant leak
Determine cause and replace
Check defrost time settings. Reset as necessary.
Check defrost temperature switch. Replace as necessary.
Recover refrigerant, evacuate system, and re-
Recover refrigerant, evacuate system, and re-
Determine cause and correct
Check filter- replace if necessary
Check condition of relay on board.
Replace board if necessary.
ture
Determine cause
Replace compressor
charge
charge
Increase air quantity
19
Page 20
START-UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No .............................................................................................................................................................
Serial No ..............................................................................................................................................................
Date ......................................................................................................................................................................
____ Verify that all packing materials have been removed from unit
____ Verify that condensate connection is installed per installation instructions
____ Check all electrical connections and terminals for tightness
____ Check wire proximity to refrigerant tubes and sheet metal edges
____ Check that indoor (indoor) air filter is clean and in place
____ Verify that unit installation is level
____ Check fan wheel propeller for location in housing and setscrew tightness