Carrier 50ZH024-060 User Manual

Single-Package Heat Pump Units
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
GENERAL ..................................1-5
RECEIVING AND INSTALLATION ............5-11
Step 1 — Check Equipment ...................5
• IDENTIFY UNIT
Step 2 — Provide Unit Support ...............5
• SLAB MOUNT
Step 3 — Provide Clearances .................5
Step 4 — Place Unit ..........................5
Step 5 — Select and Install Ductwork .........5
Step 6 — Provide for Condensate Disposal ....7
Step 7 — Install Electrical Connections .......7
• HIGH-VOLTAGE CONNECTIONS
• ROUTING POWER LEADS INTO UNIT
• CONNECTING GROUND LEAD TO UNIT GROUND
• ROUTING CONTROL POWER WIRES
• ACCESSORY ELECTRIC HEAT WIRING
• SPECIAL PROCEDURES FOR 208-V OPERATION
PRE-START-UP .............................11
START-UP ................................12-15
Check for Refrigerant Leaks .................12
Start-Up Cooling Section and
Make Adjustments ........................12
Refrigerant Charge ..........................12
MAINTENANCE ............................15-17
Air Filter ....................................15
Unit Top Removal (Outdoor Coil Side) ........16
Indoor Blower and Motor ....................16
Outdoor Coil, Indoor Coil,
and Condensate Drain Pan ................16
Outdoor Fan ................................16
Electrical Controls and Wiring ...............16
Refrigerant Circuit ..........................17
Indoor Airflow ..............................17
Metering Devices ...........................17
Liquid Line Strainers ........................17
TROUBLESHOOTING ......................18,19
START-UP CHECKLIST .....................CL-1
NOTE TO INSTALLER
Before the installation, READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY. Also, make sure the Owner’s Manual and Service Instructions are left with the unit after installation.
50ZH024-060
Fig. 1 — Unit 50ZH (Size 030 Shown)
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trained and qualified workers should install, repair, or service air-conditioning equipment.
Untrained workers can performbasicmaintenancefunc­tions of cleaning coils and filters.All other operations should be performed by trained service people. When working on air-conditioning equipment, pay attention to precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes.Wearsafety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire ex­tinguisher available for all brazing operations.
Before performing service or maintenance operations on system, turn off main power to unit. Turn off accessory heater power switch if applicable. Electrical shock can cause personal injury.
GENERAL
50ZH cooling units are fully self-contained and designed for outdoor installation. See Fig. 1. As shown in Fig. 2-4, units are shipped in a horizontal-discharge configuration for installation on a ground-level slab.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 5a 5a
PC 111 Catalog No. 535-007 Printed in U.S.A. Form 50ZH-2SI Pg 1 9-96 Replaces: 50ZH-1SI
REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L
Top of Unit ...................................0
Duct Side of Unit ...............................0
Side Opposite Ducts .............................0
Bottom of Unit .................................0
NEC REQUIRED CLEARANCES
Between Units, Power Entry Side .................1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side ....... 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side ....................1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Outdoor Coil Access Side .......................762.0 (30.00)
Power Entry Side ............................762.0 (30.00)
(Except for NEC Requirements)
Unit Top ..................................914.0 (36.00)
Side Opposite Ducts ..........................762.0 (30.00)
NEC — National Electrical Code NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
2. Dimensions are in millimeters. Dimensions in [ ] are in inches.
3. is the center of gravity.
LEGEND
fan discharge, with the exception of the outdoor coil (914 mm [36 in.]). A removable fence or barricade requires no clearance.
Millimeters (in.)
Millimeters (in.)
Millimeters (in.)
UNIT
50ZH024 208/230-1-60 232 106 356 (14.0) 483 (19.0) 305 (12.0) 50ZH030 208/230-1-60 254 116 356 (14.0) 483 (19.0) 305 (12.0)
ELECTRICAL
CHARACTERISTICS
V-Ph-Hz
UNIT WEIGHT CENTER OF GRAVITY mm (in.)
Lb Kg X Y Z
Fig. 2 — Base Unit Dimensions, 50ZH024 and 030
2
REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L
Top of Unit ...................................0
Duct Side of Unit ...............................0
Side Opposite Ducts .............................0
Bottom of Unit .................................0
NEC REQUIRED CLEARANCES
Between Units, Power Entry Side .................1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side ....... 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side ....................1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Outdoor Coil Access Side .......................762.0 (30.00)
Power Entry Side ............................762.0 (30.00)
(Except for NEC Requirements)
Unit Top ..................................914.0 (36.00)
Side Opposite Ducts ..........................762.0 (30.00)
NEC — National Electrical Code NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
2. Dimensions are in millimeters. Dimensions in [ ] are in inches.
3. is the center of gravity.
LEGEND
fan discharge, with the exception of the outdoor coil (914 mm [36 in.]). A removable fence or barricade requires no clearance.
Millimeters (in.)
Millimeters (in.)
Millimeters (in.)
UNIT
50ZH036 208/230-1-60, 208/230-3-60 277 126 356 (14.0) 483 (19.0) 381 (15.0) 50ZH042 208/230-1-60, 208/230-3-60 295 134 356 (14.0) 483 (19.0) 381 (15.0) 50ZH048 208/230-1-60, 208/230-3-60 328 149 356 (14.0) 483 (19.0) 381 (15.0)
ELECTRICAL
CHARACTERISTICS
V-Ph-Hz
UNIT WEIGHT CENTER OF GRAVITY mm (in.)
Lb Kg X Y Z
Fig. 3 — Base Unit Dimensions, 50ZH036-048
3
REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L
Top of Unit ...................................0
Bottom of Unit .................................0
Side of Unit with Duct Openings ......................0
Side of Unit Opposite Duct Openings ...................0
NEC REQUIRED CLEARANCES
Between Units, Power Entry Side .................1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side ....... 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side ....................1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Top of unit ................................914.0 (36.00)
Side of Unit Opposite Duct Openings ................762.0 (30.00)
Side of Unit with Power Entry ....................762.0 (30.00)
(Except for NEC Requirements)
NEC — National Electrical Code NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
2. Dimensions are in millimeters. Dimensions in [ ] are in inches.
3. is the center of gravity.
LEGEND
fan discharge. A removable fence or barricade requires no clearance.
Millimeters (in.)
Millimeters (in.)
Millimeters (in.)
UNIT
50ZH060
ELECTRICAL
CHARACTERISTICS
208/230-1-60, 208/230-3-60,
V-Ph-Hz
460-3-60
Fig. 4 — Base Unit Dimensions, 50ZH060
UNIT WEIGHT CENTER OF GRAVITY mm (in.)
Lb Kg X Y Z
368 167 356 (14.00) 508 (20.00) 406 (16.00)
4
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFYUNIT — The unit model number and serial num­ber are stamped on the unit identification plate. Check this information against shipping papers.
INSPECT SHIPMENT — Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its securing points, have it examined by transportation inspectors before removal. Forward claim pa­pers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original pack­ages until installation.
Step 2 — Provide Unit Support
SLAB MOUNT — Place the unit on a rigid, level surface, suitable to support the unit weight. The flat surface should extend approximately 2-in. beyond the unit casing on the 2 outdoor coil sides. The duct connection side and condensate drain connection sides should be flush with the edge of the flat surface. A concrete pad or a suitable fiberglass mounting pad is recommended.
A 6-in. wide gravel apron should be used around the flat surface to prevent airflow blockage by grass or shrubs. Do not secure the unit to the flat surface except where required by local codes.
1
The unit should be level to within
⁄4inch. This is nec-
essary for the unit drain to function properly.
Step 3 — Provide Clearances — The required mini-
mum service clearances and clearances to combustibles are shown in Fig. 2-4. Adequate ventilation and outdoor air must be provided.
The outdoor fan pulls air through the outdoor coil and dis­charges it through the fan on the top cover. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead ob­struction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. above the unit top. The maximum horizontal extension of a partial over­hang must not exceed 48 inches.
Do not restrict outdoor airflow. An air restriction at ei­ther the outdoor-air inlet or the fan discharge can be harm­ful to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials.
Step 4 — Place Unit — Unit can be moved with the
handholds provided in the unit basepan. Refer to Table 1 for operating weights. Use extreme caution to prevent damage
when moving the unit. Unit must remain in an upright po­sition during all moving operations. The unit must be level
for proper condensate drainage; the ground-level pad must be level before setting the unit in place. When a field­fabricated support is used, be sure that the support is level and that it properly supports the unit.
Step 5 — Select and Install Ductwork — The de-
sign and installation of the duct system must be in accor­dance with:
• the standards of the NFPA (National Fire Protection
Association) for installation of nonresidence-type air con­ditioning and ventilating systems;
• NFPA90Aor residence-type, NFPA90B; and/or local codes
and residence-type, NFPA 90B;
• and/or local codes and ordinances.
Table 1 — Physical Data
UNIT 50ZH 024 030 036 042 048 060 OPERATING WEIGHT (lb) 232 254 277 295 328 368 COMPRESSOR TYPE Scroll REFRIGERANT R-22
Charge (lb) 4.0 5.8 5.9 9.2 10.9 11.0 REFRIGERANT METERING DEVICE Acutrol™ System OUTDOOR COIL Copper Tubes, Aluminum Plate Fins
Rows...Fins/in. 1...17 2...17 1...17 2...17 2...17 2...17
Total Face Area (sq ft) 7.9 6.7 11.1 11.1 11.1 12.7 OUTDOOR-FAN MOTOR Propeller
Nominal Cfm 1800 2000 2600 2600 2600 3200
Nominal Rpm 825 1100 1100 1100 1100 1100
Motor Hp
Diameter (in.) 20 20 20 20 20 20 INDOOR COIL Copper Tubes, Aluminum Plate Fins
Rows...Fins/in. 2...15 3...15 3...15 3...15 4...15 4...15
Total Face Area (sq ft) 3.1 3.1 4.0 4.0 4.4 4.9 INDOOR-FAN MOTOR Direct Drive
Blower Motor Size (in.) 10x8 10x8 10x9 10x9 10x9 10×10
Nominal Cfm 800 1000 1200 1400 1600 2000
Rpm Range 550-1000 550-1000 800-1050 800-1050 1000-1100 950-1100
Number of Speeds 3333 2 3
Factory Speed Setting Low Med Low Med Low Low
Motor Hp CONNECTING DUCT SIZES Round Square
Supply Air (in.) 14 13.9 × 13.9
Return Air (in.) 14 13.9 × 27.8 FIELD-SUPPLIED RETURN AIR FILTER*
Throwaway (in.) 24x24 24x24 24x24 24x24 24x30 24×30
*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a
velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recommended filters are 1-in. thick.
1
8
1
4
1
4
1
4
1
4
1
2
1
4
1
2
1
4
3
4
1
2
1
5
Select and size ductwork, supply-air registers and return-air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply- and return­air openings on the side of the unit. See Fig. 2-4 for con­nection sizes and locations. The 14-in. round duct collars are shipped inside the 024-048 size units, attached to the indoor blower. They are field-installed and must be removed from the indoor cavity prior to start-up, even if they are not used for installation.
INSTALLFLANGES FOR DUCTWORK CONNECTIONS (50ZH060 Only) — The 50ZH060 units are shipped with flanges which must be field-installed on the unit.
To install unit flanges:
1. Five pieces of flange are shipped on the return-air open-
ing of the unit. Remove the flanges from the shipping po­sition. See Fig. 5. Screws are field-supplied.
2. One piece of flange is used as it is shipped (straight). Bend
the other 4 pieces at right angles.
3. Install the straight flange on the right side of the return
air opening in holes provided. See Fig. 6. Flanges should stick out from unit to allow for connection of ductwork.
4. Install 2 hand-formed flanges onto return air opening in
holes provided to form a rectangle around the return air opening.
5. Install remaining 2 hand-formed flanges around dis-
charge air opening in holes provided.
6. Ductwork can now be attached to flanges. INSTALLING DUCTWORK — When designing and in-
stalling ductwork, consider the following:
• Secure all ducts to building structure. Flash, weather­proof, and vibration-isolate duct openings in wall or roof according to good construction practices.
Figure 8 shows a typical duct system with 50ZH unit
installed.
Table 2 — Minimum Airflow for Safe Electric
Heater Operation (Cfm)
SIZE
024 030 036 042 048 060
600 750 900 1050 1200 1500
When connecting ductwork to units, do not drill deeper than3⁄4inch in shaded area shown in Fig. 7 or coil may be damaged.
• All units should have field-supplied filters installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1.
• Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibra­tion. Use suitable gaskets to ensure weathertight and airtight seal.
• Size ductwork for cooling air quantity (cfm). The mini­mum air quantity for proper electric heater operation is listed in Table2. Heater limit switches may trip at air quan­tities below those recommended.
• Insulate and weatherproof all external ductwork. Insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) andAir Conditioning ContractorsAssociation (ACCA) mini­mum installation standards for residential heating and air conditioning systems.
Fig. 5 — Shipping Location of Duct Flanges
(Size 060 Only)
Fig. 6 — Flanges Installed on 50ZH060 Units
6
19.17 3.92
Fig. 7 — Area Not to Be Drilled More Than3⁄4-in.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground-level installations. Install a field-supplied conden­sate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain pan condensate connection to prevent the pan from overflowing. See Fig. 9Aand 9B. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a 2-in. trap using
3
⁄4-in. tubing or piping. See Fig. 9A and 9B. Make sure that the outlet of the trap is at least 1 in. lower than the unit drain pan condensate connection to prevent the pan from overflowing. Prime the trap with water. Connect a drain tube using a minimum of
3
⁄4-in. PVC,3⁄4-in. CPVC, or3⁄4-in. copper pipe (all field sup­plied). Do not undersize the tube. Pitch the drain tube down­ward at a slope of at least 1 in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the beginning of the cooling season start-up. Allowable glues for condensate trap connection are: Standard ABS, CPVC, or PVC cement.
Step 7 — Install Electrical Connections
The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground in the control compartment, or conduit ap­proved for electrical ground when installed in accor­dance with NEC (National Electrical Code), ANSI (American National Standards Institute)/NFPA (latest edi­tion) (in Canada, Canadian Electrical Code CSA [Canadian Standard Association] C22.1) and local elec­trical codes. Failure to adhere to this warning could re­sult in personal injury or death.
Power Wiring Control Wiring
Outdoor Airflow Indoor Airflow
*Separate disconnect per NEC
(NationalElectrical Code) required for electric heater when single­point connection is not used.
Fig.8—Typical Installation
CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DISCHARGE
Before performing service or maintenance operations on the system, turn off the main power to the unit. Turn off accessory heater power switch if applicable. Electrical shock can cause personal injury.
Units are dedicated side-supply products. They are not con­vertible to vertical air supply. A field-supplied plenum must be used to convert to vertical air discharge.
Step 6 — Provide for Condensate Disposal
NOTE: Be sure that condensate-water disposal methods com­ply with local codes, restrictions, and practices.
Unit removes condensate through a 1 (using3⁄4-in. OD piping or tubing) which is located at the end of the unit. See Fig. 2-4 for location of condensate connection.
3
⁄64-in. ID hole
Failure to follow these precautions could result in dam­age to the unit being installed:
1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local elec­trical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA Standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within op­erating voltage range indicated on unit rating plate. On 3-phase units, ensure that phases are balanced within 2%. Consult local power company for correction of improper voltage and/or phase imbalance.
4. Insulate low-voltage wires for highest voltage con­tained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, con­duit, etc.
7
Fig. 9A — Condensate Trap (Using Tubing)
TRAP OUTLET
1" MIN.
2" MIN.
Fig. 9B — Condensate Trap (Using PVC Piping)
CONNECTING GROUND LEAD TO UNIT GROUND — Refer to Fig. 11 and 12. Connect the ground lead to the chassis using the unit ground lug in the control box.
ROUTING CONTROL POWER WIRES — Form a drip­loop with the thermostat leads before routing them into the unit. Route the thermostat leads through grommeted hole pro­vided in unit (see Fig. 10) into unit control box. Connect thermostat leads to unit control power leads as shown in Fig. 13.
Route thermostat wires through grommet providing a drip loop at the panel. Connect low-voltage leads to the thermo­stat as shown in Fig. 13.
The unit transformer supplies 24-v power for complete system including accessory electrical heater. Transformer is factory wired for 230-v operation. If supply voltage is 208 v, rewire transformer primary as described in the Special Procedures for 208-v Operation section below.
ACCESSORY ELECTRIC HEAT WIRING — Refer to ac­cessory electric heat installation instructions for information on installing accessory electric heat.Accessory electric heat wiring is shown in Fig. 14.
SPECIAL PROCEDURES FOR 208-V OPERATION
HIGH-VOLTAGE CONNECTIONS — The unit must have a separate electrical service with a field-supplied, water­proof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Table 3 for electrical data.
The field-supplied disconnect may be mounted on the unit
over the high-voltage inlet hole. See Fig. 2-4.
Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.
ROUTING POWER LEADS INTO UNIT — Use only cop­per wire between disconnect and unit. The high-voltage leads should be in a conduit until they enter the unit; conduit ter­mination at the unit must be watertight. Run the high­voltage leads through the hole on the control box side of the unit (see Fig. 10 for location). When the leads are inside the unit, run leads to the control box (Fig. 11). For single-phase units, connect leads to the black and yellow wires; for 3-phase units, connect the leads to the black, yellow, and blue wires (see Fig. 12).
Make sure that the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death.
1. Disconnect the orange transformer-primary lead from the
contactor. See unit wiring label.
2. Remove the wirenut from the terminal on the end of the
red transformer-primary lead.
3. Save the wirenut.
4. Connect the red lead to the contactor terminal from which
the orange lead was disconnected.
5. Using the wirenut removed from the red lead, insulate
the loose terminal on the orange lead.
6. Wrap the wirenut with electrical tape so that the metal
terminal cannot be seen.
Indoor blower-motor speeds may need to be changed for 208-v operation. Refer to Indoor Airflow and Airflow Adjustments section on page 14.
8
Loading...
+ 16 hidden pages