Before the installation, READ THESE INSTRUCTIONS
CAREFULLY AND COMPLETELY. Also, make sure the
Owner’s Manual and Service Instructions are left with the
unit after installation.
50ZH024-060
Fig. 1 — Unit 50ZH (Size 030 Shown)
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical components. Only trained and qualified workers should install,
repair, or service air-conditioning equipment.
Untrained workers can performbasicmaintenancefunctions of cleaning coils and filters.All other operations should
be performed by trained service people. When working on
air-conditioning equipment, pay attention to precautions in
the literature, tags and labels attached to the unit, and other
safety precautions that may apply.
Follow all safety codes.Wearsafety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
Before performing service or maintenance operations on
system, turn off main power to unit. Turn off accessory
heater power switch if applicable. Electrical shock can
cause personal injury.
GENERAL
50ZH cooling units are fully self-contained and designed
for outdoor installation. See Fig. 1. As shown in Fig. 2-4,
units are shipped in a horizontal-discharge configuration for
installation on a ground-level slab.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 5a 5a
PC 111Catalog No. 535-007Printed in U.S.A.Form 50ZH-2SIPg 19-96Replaces: 50ZH-1SI
REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L
Top of Unit ...................................0
Duct Side of Unit ...............................0
Side Opposite Ducts .............................0
Bottom of Unit .................................0
NEC REQUIRED CLEARANCES
Between Units, Power Entry Side .................1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side ....... 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side ....................1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Outdoor Coil Access Side .......................762.0 (30.00)
Power Entry Side ............................762.0 (30.00)
(Except for NEC Requirements)
Unit Top ..................................914.0 (36.00)
Side Opposite Ducts ..........................762.0 (30.00)
NEC — National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
2. Dimensions are in millimeters. Dimensions in [ ] are in inches.
3.is the center of gravity.
LEGEND
fan discharge, with the exception of the outdoor coil (914 mm [36 in.]). A
removable fence or barricade requires no clearance.
Side of Unit with Duct Openings ......................0
Side of Unit Opposite Duct Openings ...................0
NEC REQUIRED CLEARANCES
Between Units, Power Entry Side .................1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side ....... 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side ....................1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Top of unit ................................914.0 (36.00)
Side of Unit Opposite Duct Openings ................762.0 (30.00)
Side of Unit with Power Entry ....................762.0 (30.00)
(Except for NEC Requirements)
NEC — National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
2. Dimensions are in millimeters. Dimensions in [ ] are in inches.
3.is the center of gravity.
LEGEND
fan discharge. A removable fence or barricade requires no clearance.
Millimeters (in.)
Millimeters (in.)
Millimeters (in.)
UNIT
50ZH060
ELECTRICAL
CHARACTERISTICS
208/230-1-60, 208/230-3-60,
V-Ph-Hz
460-3-60
Fig. 4 — Base Unit Dimensions, 50ZH060
UNIT WEIGHTCENTER OF GRAVITY mm (in.)
LbKgXYZ
368167356 (14.00)508 (20.00)406 (16.00)
4
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFYUNIT — The unit model number and serial number are stamped on the unit identification plate. Check this
information against shipping papers.
INSPECT SHIPMENT — Inspect for shipping damage while
unit is still on shipping pallet. If unit appears to be damaged
or is torn loose from its securing points, have it examined by
transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not
responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify
the nearest Carrier Air Conditioning office if any item is
missing.
To prevent loss or damage, leave all parts in original packages until installation.
Step 2 — Provide Unit Support
SLAB MOUNT — Place the unit on a rigid, level surface,
suitable to support the unit weight. The flat surface should
extend approximately 2-in. beyond the unit casing on the 2
outdoor coil sides. The duct connection side and condensate
drain connection sides should be flush with the edge of the
flat surface. A concrete pad or a suitable fiberglass mounting
pad is recommended.
A 6-in. wide gravel apron should be used around the flat
surface to prevent airflow blockage by grass or shrubs. Do
not secure the unit to the flat surface except where required
by local codes.
1
The unit should be level to within
⁄4inch. This is nec-
essary for the unit drain to function properly.
Step 3 — Provide Clearances — The required mini-
mum service clearances and clearances to combustibles are
shown in Fig. 2-4. Adequate ventilation and outdoor air must
be provided.
The outdoor fan pulls air through the outdoor coil and discharges it through the fan on the top cover. Be sure that the
fan discharge does not recirculate to the outdoor coil. Do not
locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang
(such as a normal house overhang) is 48 in. above the unit
top. The maximum horizontal extension of a partial overhang must not exceed 48 inches.
Do not restrict outdoor airflow. An air restriction at either the outdoor-air inlet or the fan discharge can be harmful to compressor life.
Do not place the unit where water, ice, or snow from
an overhang or roof will damage or flood the unit. The unit
may be installed on wood flooring or on Class A, B, or C
roof covering materials.
Step 4 — Place Unit — Unit can be moved with the
handholds provided in the unit basepan. Refer to Table 1 for
operating weights. Use extreme caution to prevent damage
when moving the unit. Unit must remain in an upright position during all moving operations. The unit must be level
for proper condensate drainage; the ground-level pad must
be level before setting the unit in place. When a fieldfabricated support is used, be sure that the support is level
and that it properly supports the unit.
Step 5 — Select and Install Ductwork — The de-
sign and installation of the duct system must be in accordance with:
• the standards of the NFPA (National Fire Protection
Association) for installation of nonresidence-type air conditioning and ventilating systems;
• NFPA90Aor residence-type, NFPA90B; and/or local codes
and residence-type, NFPA 90B;
• and/or local codes and ordinances.
Table 1 — Physical Data
UNIT 50ZH024030036042048060
OPERATING WEIGHT (lb)232254277295328368
COMPRESSOR TYPEScroll
REFRIGERANTR-22
Charge (lb)4.05.85.99.210.911.0
REFRIGERANT METERING DEVICEAcutrol™ System
OUTDOOR COILCopper Tubes, Aluminum Plate Fins
Return Air (in.)1413.9 × 27.8
FIELD-SUPPLIED RETURN AIR FILTER*
Throwaway (in.)24x2424x2424x2424x2424x3024×30
*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a
velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recommended filters are 1-in. thick.
1
⁄
8
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
2
1
⁄
4
1
⁄
2
1
⁄
4
3
⁄
4
1
⁄
2
1
5
Select and size ductwork, supply-air registers and
return-air grilles according to ASHRAE (American Society
of Heating, Refrigeration, and Air Conditioning Engineers)
recommendations.
Use the duct flanges provided on the supply- and returnair openings on the side of the unit. See Fig. 2-4 for connection sizes and locations. The 14-in. round duct collars are
shipped inside the 024-048 size units, attached to the indoor
blower. They are field-installed and must be removed from
the indoor cavity prior to start-up, even if they are not used
for installation.
INSTALLFLANGES FOR DUCTWORK CONNECTIONS
(50ZH060 Only) — The 50ZH060 units are shipped with
flanges which must be field-installed on the unit.
To install unit flanges:
1. Five pieces of flange are shipped on the return-air open-
ing of the unit. Remove the flanges from the shipping position. See Fig. 5. Screws are field-supplied.
2. One piece of flange is used as it is shipped (straight). Bend
the other 4 pieces at right angles.
3. Install the straight flange on the right side of the return
air opening in holes provided. See Fig. 6. Flanges should
stick out from unit to allow for connection of ductwork.
4. Install 2 hand-formed flanges onto return air opening in
holes provided to form a rectangle around the return air
opening.
5. Install remaining 2 hand-formed flanges around dis-
charge air opening in holes provided.
6. Ductwork can now be attached to flanges.
INSTALLING DUCTWORK — When designing and in-
stalling ductwork, consider the following:
• Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof
according to good construction practices.
Figure 8 shows a typical duct system with 50ZH unit
installed.
Table 2 — Minimum Airflow for Safe Electric
Heater Operation (Cfm)
SIZE
024030036042048060
600750900105012001500
When connecting ductwork to units, do not drill deeper
than3⁄4inch in shaded area shown in Fig. 7 or coil may
be damaged.
• All units should have field-supplied filters installed in the
return-air side of the unit. Recommended sizes for filters
are shown in Table 1.
• Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between
ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weathertight and
airtight seal.
• Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is
listed in Table2. Heater limit switches may trip at air quantities below those recommended.
• Insulate and weatherproof all external ductwork. Insulate
and cover with a vapor barrier all ductwork passing through
conditioned spaces. Follow latest Sheet Metal and Air
Conditioning Contractors National Association (SMACNA)
andAir Conditioning ContractorsAssociation (ACCA) minimum installation standards for residential heating and air
conditioning systems.
Fig. 5 — Shipping Location of Duct Flanges
(Size 060 Only)
Fig. 6 — Flanges Installed on 50ZH060 Units
6
19.17″3.92″
Fig. 7 — Area Not to Be Drilled More Than3⁄4-in.
Condensate water can be drained directly onto the roof in
rooftop installations (where permitted) or onto a gravel apron
in ground-level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper
drainage. Make sure that the outlet of the trap is at least
1 in. lower than the drain pan condensate connection to
prevent the pan from overflowing. See Fig. 9Aand 9B. Prime
the trap with water. When using a gravel apron, make sure
it slopes away from the unit.
If the installation requires draining the condensate water
away from the unit, install a 2-in. trap using
3
⁄4-in. tubing or
piping. See Fig. 9A and 9B. Make sure that the outlet of the
trap is at least 1 in. lower than the unit drain pan condensate
connection to prevent the pan from overflowing. Prime the
trap with water. Connect a drain tube using a minimum of
3
⁄4-in. PVC,3⁄4-in. CPVC, or3⁄4-in. copper pipe (all field supplied). Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 in. for every 10 ft of horizontal
run. Be sure to check the drain tube for leaks. Prime trap at
the beginning of the cooling season start-up. Allowable glues
for condensate trap connection are: Standard ABS, CPVC,
or PVC cement.
Step 7 — Install Electrical Connections
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground
may consist of an electrical wire connected to the unit
ground in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI
(American National Standards Institute)/NFPA (latest edition) (in Canada, Canadian Electrical Code CSA
[Canadian Standard Association] C22.1) and local electrical codes. Failure to adhere to this warning could result in personal injury or death.
Power Wiring
Control Wiring
Outdoor Airflow
Indoor Airflow
*Separate disconnect per NEC
(NationalElectrical Code) required
for electric heater when singlepoint connection is not used.
Fig.8—Typical Installation
CONVERTING HORIZONTAL DISCHARGE UNITS TO
DOWNFLOW (VERTICAL) DISCHARGE
Before performing service or maintenance operations on
the system, turn off the main power to the unit. Turn off
accessory heater power switch if applicable. Electrical
shock can cause personal injury.
Units are dedicated side-supply products. They are not convertible to vertical air supply. A field-supplied plenum must
be used to convert to vertical air discharge.
Step 6 — Provide for Condensate Disposal
NOTE: Be sure that condensate-water disposal methods comply with local codes, restrictions, and practices.
Unit removes condensate through a 1
(using3⁄4-in. OD piping or tubing) which is located at the
end of the unit. See Fig. 2-4 for location of condensate
connection.
3
⁄64-in. ID hole
Failure to follow these precautions could result in damage to the unit being installed:
1. Make all electrical connections in accordance with
NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all
electrical connections must be in accordance with CSA
Standard C22.1 Canadian Electrical Code Part 1
and applicable local codes. Refer to unit wiring
diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit.
DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate.
On 3-phase units, ensure that phases are balanced within
2%. Consult local power company for correction of
improper voltage and/or phase imbalance.
4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires
are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit, etc.
7
Fig. 9A — Condensate Trap (Using Tubing)
TRAP
OUTLET
1" MIN.
2" MIN.
Fig. 9B — Condensate Trap (Using PVC Piping)
CONNECTING GROUND LEAD TO UNIT GROUND
— Refer to Fig. 11 and 12. Connect the ground lead to the
chassis using the unit ground lug in the control box.
ROUTING CONTROL POWER WIRES — Form a driploop with the thermostat leads before routing them into the
unit. Route the thermostat leads through grommeted hole provided in unit (see Fig. 10) into unit control box. Connect
thermostat leads to unit control power leads as shown in
Fig. 13.
Route thermostat wires through grommet providing a drip
loop at the panel. Connect low-voltage leads to the thermostat as shown in Fig. 13.
The unit transformer supplies 24-v power for complete
system including accessory electrical heater. Transformer is
factory wired for 230-v operation. If supply voltage is
208 v, rewire transformer primary as described in the
Special Procedures for 208-v Operation section below.
ACCESSORY ELECTRIC HEAT WIRING — Refer to accessory electric heat installation instructions for information
on installing accessory electric heat.Accessory electric heat
wiring is shown in Fig. 14.
SPECIAL PROCEDURES FOR 208-V OPERATION
HIGH-VOLTAGE CONNECTIONS — The unit must have
a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from the
unit. Refer to the unit rating plate for maximum fuse/circuit
breaker size and minimum circuit amps (ampacity) for wire
sizing. See Table 3 for electrical data.
The field-supplied disconnect may be mounted on the unit
over the high-voltage inlet hole. See Fig. 2-4.
Operation of unit on improper line voltage constitutes
abuse and may cause unit damage that could affect
warranty.
ROUTING POWER LEADS INTO UNIT — Use only copper wire between disconnect and unit. The high-voltage leads
should be in a conduit until they enter the unit; conduit termination at the unit must be watertight. Run the highvoltage leads through the hole on the control box side of the
unit (see Fig. 10 for location). When the leads are inside the
unit, run leads to the control box (Fig. 11). For single-phase
units, connect leads to the black and yellow wires; for 3-phase
units, connect the leads to the black, yellow, and blue wires
(see Fig. 12).
Make sure that the power supply to the unit is switched
OFF before making any wiring changes. Electrical shock
can cause personal injury or death.
1. Disconnect the orange transformer-primary lead from the
contactor. See unit wiring label.
2. Remove the wirenut from the terminal on the end of the
red transformer-primary lead.
3. Save the wirenut.
4. Connect the red lead to the contactor terminal from which
the orange lead was disconnected.
5. Using the wirenut removed from the red lead, insulate
the loose terminal on the orange lead.
6. Wrap the wirenut with electrical tape so that the metal
terminal cannot be seen.
Indoor blower-motor speeds may need to be changed for
208-v operation. Refer to Indoor Airflow and Airflow
Adjustments section on page 14.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.