Supply Fan Control with IGV Option .............28
Supply Fan Control with VFD Option ............28
Modulating Power Exhaust
(Option or Accessory) .......................30
START UNIT ................................31-34
Quick Test Program ...........................31
OPERATING INFORMATION ...................34-43
Digital Display ...............................34
CODES 0 THROUGH 8, CAPACITY STEPS
•
.................................25-30
• CODES 20 THROUGH 30 AND 88, OPERATIONAL
STATUS
• CODES 51 THROUGH 87, DIAGNOSTIC
INFORMATION
Operating Sequence
..........................35
• SIZE 034, 038 AND 048-088 UNITS
• SIZE 044 UNITS
• SIZE 104 UNITS
Head Pressure Control
Supply Fan Control with IGV ...................38
Supply Fan Control with VFD ...................38
Modulating Power Exhaust (Option or
Accessory Except FY,JY Units) ...............38
Unit Staging .................................38
TROUBLESHOOTING ........................44-57
Checking Display Codes .......................44
Complete Unit Stoppage .......................44
Single Circuit Stoppage .......................44
Restart Procedure ............................44
Diagnostic Codes .............................45
CODES 51, 52, 55, 56: COMPRESSOR FAILURE
•
........................36
Page
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1
Tab 1a 1b
PC 111Catalog No. 534-716Printed in U.S.A.Form 48/50F,J-1TPg 14-99Replaces: 48/50D,F,J-1T
CONTENTS (cont)
Page
CODES 59 AND 60: LOW-PRESSURE SWITCH
•
• CODES 63 AND 64: OIL PRESSURE SWITCH
• CODE 70: ILLEGAL UNIT CONFIGURATION
• CODES 71 TO 76: THERMISTOR/RESISTOR
FAILURE
• CODE 81: RESET THERMISTOR OR
POTENTIOMETER FAILURE
• CODE 82: LEAVING-AIR TEMPERATURE SET POINT
POTENTIOMETER FAILURE
• CODE 83: ECONOMIZER FEEDBACK
POTENTIOMETER FAILURE
• CODE 84: RESET LIMIT POTENTIOMETER
FAILURE
• CODE 85: DEMAND LIMIT POTENTIOMETER (P4)
FAILURE
• CODE 86: MINIMUM POSITION ECONOMIZER
POTENTIOMETER FAILURE
• CODE 87: WARM-UP TEMPERATURE SET POINT
FAILURE
Thermistor Troubleshooting
Electronic Controls Checkout ..................47
....................47
• PROCESSOR BOARD CHECKOUT
• RELAY BOARD TROUBLESHOOTING
• DISPLAY BOARD CHECKOUT
• ACCESSORY BOARD CHECKOUT
• TWO-STEP DEMAND LIMIT CONTROL MODULE
(DLCM) TROUBLESHOOTING
Enthalpy Sensor Checkout
Economizer Motor ............................52
Variable Frequency Drive ......................52
.....................51
• STANDARD TRANSDUCER CONTROL
• EXTERNAL SIGNAL CONTROL
• SUPPLY FAN MOTOR OVERLOAD PROTECTION
VFD Operation
VFD Operational Status ........................54
Restoring Factory VFD Defaults ................54
Unit Wiring ..................................54
START-UP CHECKLIST ..................CL-1, CL-2
...............................54
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components; and equipment location (roof, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature; on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all
safety codes. Wear safety glasses and work gloves. Use care
in handling, rigging, and setting this equipment, and in handling all electrical components.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not
to restore power until work is completed.
GENERAL
IMPORTANT: This literature contains controls,
operation, and troubleshooting data for 48FK,JK and
50FK,FY,JK,JY variable air volume rooftop units. Use
this guide in conjunction with the separate Installation
Instructions literature packaged with the unit.
Carrier 48FK,JK and 50FK,FY,JK,JY units provide ventilation, cooling, and heating (when equipped) in Variable
Air Volume (VAV) applications. These units contain factoryinstalled controls which provide full system management.
The unit controls also perform self diagnostic tests at unit
start-up, monitor operation of the unit, and provide alarms.
Information on system operation and status are sent to the
central processors by various sensors that are located at the
unit and in the conditioned space. Each unit is equipped with
a display board.
Rooftop Information — The rooftop controls cycle
supply-fan motor, compressors, and unloaders to maintain
the proper temperature conditions. The controls also cycle
condenser fans to maintain suitable head pressure. Safeties
are continuously monitored to prevent the unit from operating under abnormal conditions. The controls provide control of economizer and cycle or control heating as required.
The controls also allow the service person to operate a
‘quick test’so that all the controlled components can be checked
for proper operation.
IMPORTANT:The field-supplied and installed switch
(or timeclock) MUST BE CLOSED to put unit into
the Occupied mode. Unit WILLNOT START until this
is accomplished. See base unit installation instructions
literature for details.
VAV Control System — The 30 to 100-ton VAV roof-
top units contain a microprocessor-based electronic control
system that controls and monitors the rooftop unit functions.
TheVAV control system is composed of several components:
• processor board
• relay board
• display board
• thermistors
• compressor operation feedback (control relay)
• accessory board
• temperature reset package*
• single-step demand limit*
• two-step demand limit control module*
*Field-installed accessories.
The VAV control system monitors and controls the following functions of the rooftop unit:
• supply-air temperature (unit capacity)
• morning warm-up or electric heat (if equipped)
• head pressure control, fan cycling
• economizer position
• diagnostic display
• unit check-out (quick test)
• supply air temperature reset (if equipped)
• demand limiting (if equipped)
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short
out components, or to bypass or otherwise depart from
recommended procedures. Any short-to-ground of the
control board or accompanying wiring may destroy the
electronic modules or electrical components.
Processor Board — The processor board, shown in
Fig. 1, contains the logic and the necessary hardware to drive
the outputs and the display board. The processor board is
enclosed by a sheet metal cover and a heater. The heater is
controlled by a thermostat to keep the processor temperature
above 32 F (0° C). All electrical connections are made to the
processor board through wire and ribbon cables.
Do not remove label covering EPROM. Removal causes program to be erased.
Fig. 1 — Processor Board
*EPROM HT204485-1-XX where ‘‘XX’’ is the current revision
number.
NOTE: Processor Board is positioned in unit with J3 and J10 connections at the bottom.
Several temperature inputs are connected to the processor. There are either 4 or 5 thermistors (depending on the
field-installed accessories) which input temperature data
into the processor through pin terminal connector J1. See
Table 1 and Fig. 2.
Several status switches are also monitored. These switches
are connected to the processor at pin terminal connector J2.
See Fig. 3 and Table 2.
Table 1 — Pin Terminal Connector J1
Thermistor Inputs
CONNECTOR J1
TERMINAL NO.
1,2Reset Temperature*T10
14,15
16,17
18,19Return-Air TemperatureT2
20,21Supply-Air TemperatureT1
LEGEND
T—Thermistor
*If equipped with accessory temperature reset package.
NOTE: Terminal numbers 3-13 are not used on these units.
TEMPERATURE
INPUT
Saturated Condensing
Temp., Circuit 2
Saturated Condensing
Temp., Circuit 1
UNIT SIZE
034-104
T4
T3
In addition to the unit status switch inputs, the processor
board also accepts inputs from several potentiometers. These
potentiometers control various operational characteristics of
the system. Inputs are received by the processor through pin
terminal connector J3. See Fig. 4.
All of the potentiometers must be set before the unit is
started in order for the unit to function properly. See StartUp, Potentiometers section on page 28 for information on
establishing set points. Each of the potentiometers has a valid
range that is used by the control. The valid range is defined
as the potentiometer’s resistance value that the control will
not consider to be in error. This is usually between 10% and
90% of the potentiometer’s total resistance. The control has
been programmed to accept an operational range for the potentiometer, which may not be the same as the valid range.
3
LEGEND
T—Thermistor
Field Wiring
Accessory
Fig. 2 — Pin Terminal Connector J1
Thermistor Inputs
LEGEND
CR — Control Relay
EC— Enthalpy Control
LPS — Low-Pressure Switch
Fig. 3 — Pin Terminal Connector J2
Status Switch Inputs
Table 2 — Pin Terminal Connector J2
Status Switch Inputs
CONNECTOR J2
TERMINAL NO.
1,2
3,4
7,8
9,10
13,14
15,20
15,24
LEGEND
CR — Control Relay
EC— Enthalpy Control
LPS — Low-Pressure Switch
NOTE: Terminal numbers 5, 6, 11,12, 16-19, and 21-23 are not used
The potentiometer locations and functions are as follows:
P1 — SUPPLY-AIR SET POINT — This potentiometer is
located on the display board. The supply-air set point is the
cooling mode control temperature which the VAV control
system will attempt to maintain at Thermistor T1 by control of economizer position and/or cycling unloaders and
compressors.
P2 — ECONOMIZER POSITION — Economizer feedback
potentiometer is located on the economizer motor.The microprocessor is programmed to indicate an alarm if the travel
during initialization is less than 10% of the total potentiometer’s resistance. An alarm condition will also be signaled if
the potentiometer fails during operation, indicating that the
damper blades are stuck. If either situation occurs, the processor will try to drive the economizer dampers closed.
P3 — RESET LIMIT — This potentiometer is located on
the accessory board (provided standard from the factory) in
the unit main control box and establishes the maximum amount
of reset that can be applied to the supply-air set point (P1).
Reset is limited by the P1 default of 70 F. This potentiometer is used only when accessory, field-installed temperature
reset is used. If temperature reset is used, DIP (dual, in-line
package) switch 2 must be in the ON position.
P4 — DEMAND LIMIT — This potentiometer is located
near TRAN4 in the unit control box. The demand limit potentiometer is used only if accessory, field-installed demand
limit is used, and if DIP switch 5 is in the ON position. For
single-step demand limit, a field-installed 5 to 20 Kohm potentiometer and switch must be used.
P5 — ECONOMIZER MINIMUM POSITION — This potentiometer is on the accessory board (provided standard from
the factory) located in the unit main control box. This potentiometer specifies the minimum opening position for the
optional economizer. If a fault condition is detected by the
processor,an alarm condition will be signaled and the economizer dampers will close.
P6 — WARM-UP SET POINT — This potentiometer is on
the accessory board (provided standard from the factory)
located in the unit main control box. This potentiometer
establishes the set point temperature for the Morning
Warm-Up function. When the temperature is reached, Morning Warm-Up is terminated and VAV operation begins. DIP
switch 4 must be in the ON position if morning warm-up
heat is to be used.
P7 — SASP (SUPPLY AIR SET POINT) RESET TEMPERATURE — This 10 Kohm potentiometer is used only if
the accessory, field-installed temperature reset package is installed.This potentiometer determines the temperature at which
reset will begin. It is located on the accessory temperature
reset board. DIP switch 2 must be in the ON position to enable SASP reset.
PROCESSOR BOARD OUTPUTS — The processor board
also controls outputs through the relay board. The relay board
plugs into the processor board using a ribbon cable.
In addition, the processor board controls the display board.
The display board is connected to the processor board by a
ribbon cable, and has an LED (light-emitting diode) display
showing the status of the unit and diagnostic information.
CONFIGURATION HEADERAND DIP SWITCHASSEMBLY — The processor board is programmed to control a variety of air conditioning units. To tailor the processor to the
particular unit being controlled, 2 devices are used. One is
the configuration header, and the other is the DIP switch
assembly.
The configuration header (part no. 30GB660001) is a
series of 8 small wires that are broken or unbroken in a
pattern to indicate several unique characteristics of the unit.
The configuration header is factory set and should not be
changed. Changing the factory setting may cause the unit to
malfunction.
The DIP switches configure the unit for several fieldinstalled options, as well as for several other options that
may be unique to the unit. The DIP switches are located under a plastic enclosure which must be removed for access.
The switches can be field adjusted, but must be adjusted only
when the unit control circuit breaker is off.
Relay Board — The relay board is used to control 24-v
and 115-v loads. See Fig. 5. The relay board is connected to
the processor board by a ribbon cable at pin J9. Electrical
connections to the relay board are made through pins J5
(115 v) and J6 (24 v). The relay board has eight 24-v relays
and five 115-v relays. See Table 3.
Display Board — The display board is located in the
main unit control box and is connected to the J10 port of the
processor board through a ribbon cable. The display board
contains the supply-air set point potentiometer P1; a 2-digit,
LED display; and the display button (see Fig. 6). The LED
display is used to convey the operating information and operational error codes.
Thermistors — The processor uses up to 5 thermistors
to sense the temperatures at various points in the system.
See Table 1 and Fig. 7-14. All the thermistors have identical
temperature versus resistance and voltage drop characteristics, and are monitored by the processor for a short or open
circuit. The valid range for a thermistor is 362,640 to
219 ohms. Thermistor details and locations are as follows:
T1 — SUPPLY-AIR TEMPERATURE THERMISTOR —
This thermistor is located in the unit supply fan discharge.
It provides information for the processor to stage the number of capacity steps required to maintain a desired supplyair temperature.
T2 — RETURN-AIR TEMPERATURE THERMISTOR —
This thermistor is located in the mixed-air portion of the unit
cabinet. The thermistor’sprimary function is to provide morning warm-up information. This sensor will also provide differential information for the processor during cooling operation (such as the rate of change for a capacity step).
T3 — SATURATEDCONDENSINGTEMPERATURE, CIRCUIT 1 — This thermistor is located on the condenser coil
return bend. See Fig. 13 and 14. It controls the staging of the
unit condenser fans based on the condensing temperature of
the refrigerant at the designated position on the condenser
coil.
T4 — SATURATEDCONDENSINGTEMPERATURE, CIRCUIT 2 — This thermistor is located on the condenser coil
return bend. See Fig. 13 and 14. It controls the staging of the
unit condenser fans based on the condensing temperature of
the refrigerant at the designated position on the condenser
coil.
T10 — RESET TEMPERATURE — This thermistor is used
only if the accessory temperature reset package is used. It
provides occupied space temperature information to the processor, which determines whether or not reset is required.
The thermistor is remotely mounted outside the unit in the
conditioned space.
5
Table 3 — Output Pin and Terminal Assignments
OUTPUT PIN-
TERMINAL
J6-1
J6-2
J6-3
J6-4
J6-5
J6-6
J6-7Economizer Open Relay (K7)EOR
J6-8Economizer Close Relay (K8)ECR
J5-1Supply Fan Relay (K9)
J5-2Morning Warm-Up Relay (K10)HIR
J5-3
J5-4
J5-5External Alarm Relay (K13)ALM
LEGEND
ALM — Alarm
CR— Control Relay
ECR — Economizer Close Relay
EOR — Economizer Open Relay
HIR — Heat Interlock Relay
IFC— Indoor (Evaporator) Fan Contactor
OFC — Outdoor (Condenser) Fan Contactor
U—Unloader
Stage 1
Compressor Relay (K1)*
Stage 2
Compressor Relay (K2)*
Stage 3
Compressor Relay (K3)*
Stage 4
Compressor Relay (K4)†
Stage 5
Compressor Relay (K5)†
Stage 6
Compressor Relay (K6)†
Stage 1 Condenser
Fan Relay (K11)
Stage 2 Condenser
Fan Relay (K12)
NAMERATINGDEVICE
CR1
U2**
U1
24 vac
115 vac
*Circuit 1.
†Circuit 2.
**U2 is not used on 044 units.
††OFC2 on 034-048 units; OFC3 on 054-104 units.
\ Used on 054-104 units only.
Not Used
CR2
Not Used
IFC
OFC2/OFC3 ††
OFC4 \
LEGEND
CR — Control Relay
J—Terminal Pin Connectors
K—Relay
Fig. 5 — Relay Board
6
P1 SUPPLY AIR
SET POINT
POTENTIOMETER
TWO-DIGIT
DISPLAY
DISPLAY
BUTTON
Fig. 6 — Display/Set Point Board
Compressor Operation
CONTROL RELAY (CR) — This relay provides information to the processor about compressor operation (one control relay per compressor). The relay controls and protects
the compressor and also controls the crankcase heater.
A control signal to check the safety statuses and to start
the compressor is sent from the relay board. This signal travels through all of the safeties: the high-pressure switch, and
the internal protector (where used) and on to the control relay coil. Once the control relay coil has been energized, the
control relay completes a feedback circuit for the processor,
informs the processor of the status of the compressor safeties, energizes the compressor contactor coil, and deenergizes the crankcase heaters. A fault will be detected by the
processor if the control relay opens during operation or startup. The processor will lock the compressor or the circuit off
by deenergizing the appropriate relay(s) on the relay board
and energizing an alarm signal.
Accessory Board — The accessory board is standard
(factory supplied) in the VAV rooftop units. See Fig. 15. This
board is located in the control box of each unit. Each board
has a prewired connector supplied with it to connect directly
to the processor board. It has 3 potentiometers: P3, P5, and
P6.
P3 — RESET LIMIT — The processor board is programmed
for occupied space temperature reset. In order for reset to
work, the accessory temperature reset board must be used.
Potentiometer P3 is the maximum set point temperature to
which the supply air can be reset.
P5 — ECONOMIZER MINIMUM POSITION — This potentiometer controls the set point for the minimum position
of the economizer.
P6 — MORNING WARM-UP TEMPERATURE—This potentiometer controls the morning warm-up temperature set
point.
Single-Step Demand Limit — The single step de-
mand limit provides a means to limit the capacity of the V AV
unit using an external switch. Single step demand limit will
limit the compressor displacement based on the ratio of the
wiper arm to the full scale resistance. The exact percentage
of capacity reduction differsdepending on the number of capacity steps.
A3-wire, 5 to 20 Kohm, field-supplied potentiometer (P4)
is required for this option. The potentiometer should be wired
to the processor J3 connections. In order to control the demand limit, the wiper arm of the potentiometer should be
switched open and closed based on the demand limit
requirement. The control switch is also field-supplied and
installed.
If the wiper arm wire is open, all capacity stages can be
used. When the wiper arm wire is closed, the capacity is
reduced by the amount set on potentiometer P4.
Demand Limit Control Module (DLCM) — The
DLCM provides a 2-step demand limit control using an external switch. The first step is between 50% and 100% of the
maximum compressor displacement. See Fig. 16. The second step is between 0% and 49% of the maximum compressor displacement. The exact percentage differs depending on
the number of capacity steps.
Two adjustable potentiometers are used to set the 2 demand limit points. Potentiometer P1 is used to set a demand
limit between 50% and 100% of the unit capacity. Potentiometer P2 is used to set a demand limit between 0% and
49% of unit capacity.
If no power is supplied to the demand limit control module, all capacity stages can be used. When power is supplied
to terminal IN1 only, the first step of the demand limit control is energized and the capacity is reduced by the amount
set on potentiometer P1. When power is supplied to terminal
IN2 only,or to both IN1 and IN2, the capacity is reduced by
the amount set on potentiometer P2.
7
GAS SECTIONHORIZONTAL SUPPLY SECTION
(48FK,JK ONLY)(50FY,JY ONLY) AND EXTENDED
PLENUM SECTION (50FKX,FKY,JKX,JKY)
Fig. 7 — Thermistor T1 Location, 48FK,JK, 50FY,JY and 50FKX,FKY,JKX,JKY 034-048 Units
FAN DISCHARGE/ELECTRIC HEAT SECTION
Fig. 8 — Thermistor T1 Location, 50FK,JK034-048 Units
8
GAS SECTIONHORIZONTAL DISCHARGE SECTION (50FY,JY)
(48FK,JK)AND EXTENDED
PLENUM SECTION (50FKX,FKY,JKX,JKY)
Fig. 9 — Thermistor T1 Location, 48FK,JK, 50JY and
50JKX,JKY 054-074 Units and 50FKX,FKY and 50FY054-104 Units
FAN DISCHARGE/ELECTRIC HEAT SECTION
Fig. 10 — Thermistor T1 Location, 50FK,JK054-074 Units
9
STANDARD
FILTERS
BAG
FILTERS
Fig. 11— Thermistor T2 Location, Size 034-048 Units
STANDARD FILTERSBAG FILTERS
(054-074 Only)
Fig. 12 — Thermistor T2 Location, Size 054-104 Units
Economizer — Economizer control is used to control
the outside and return air dampers of the unit, to satisfy space
cooling demand using all outside air (when permitted), and
to satisfy cooling in conjunction with compressor operation
(when conditions permit). During Occupied periods without
cooling demand, the outside-air dampers will be at the userconfigured Minimum Damper Position (at P5 on accessory
board). During Unoccupied periods, the outside-air dampers
will be closed.
The economizer is available as a factory-installed option.
The user can install an accessory differentialenthalpy sensor
to enhance economizer control. Refer to the installation section for field wiring of the sensor.
Fig. 13 — Thermistor T3 and T4 Locations,
Size 034-048 Units
ENTHALPY CONTROL — Outside air enthalpy control is
standard with the factory-installed economizer option. Enthalpy is sensed by a controller located behind the end outside air hood. The control can be accessed by removing the
upper hood filter. See Fig. 17.
DIFFERENTIALENTHALPY— Added efficienciesin economizer control can be gained by installing a differential enthalpy sensor in the return air duct. When differential enthalpy
control is installed, the economizer control will use the air
stream with lower enthalpy (outside air or return air) to provide for lower compressor operating costs during integrated
economizer cycle operation. The differential enthalpy sensor is installed in the return-air duct.
10
054 UNITS
064, 074, 078 UNITS
088, 104 UNITS
Fig. 14 — Thermistor T3 and T4 Locations, Size 054-104 Units
VFD is used to modulate supply fan airflow to maintain duct
static pressure on VAV applications. The VFD is located in
the supply fan section (see Fig. 18 and 19), and can be accessed by opening the fan section access door.
The unit is supplied with a pressure transducer capable of
measuring from 0.0 to 5.0 in. wg. The pressure transducer
will senda4to20mAsignal to the VFD to modulate the
speed of the indoor fan motor to precisely control the fan to
the desired static pressure set point. The VFD is factory set
at 2.5 in. wg duct static pressure. Refer to the Operating Sequence section for more information on the VFD.
The VFD has been programmed and wired at the factory
for this application. No further adjustments (except for Duct
Static Pressure Set Point) should be necessary at start-up.
Factory jumper wire configurations are shown in the Supply
Fan Control with VFD Option section on page 28.
A separate service manual for the factory-installed VFD
is supplied with each unit. Refer to the VFD manual for more
information on the VFD controls.
Temperature Reset — Accessory temperature reset al-
lows the unit to automatically adjust (‘‘reset’’) the supplyair temperature set point to a higher value once most of the
space cooling load has been met. When the space conditions
are satisfied, the VAV terminals will close to the minimum
position.All VAV units will sense the decrease in actual supplyair temperature and the unit controls respond by reducing
capacity stages to maintain user-established supply-air set
point temperature. When VAV units are also equipped with
optional supply duct pressure controls (either inlet guide vanes
[IGV] or variable frequency drive package), the unit also senses
an increase in duct static pressure and responds by closing
IGV dampers or slowing fan wheel speed to maintain userconfigured set points for supply duct pressure. Allowing the
supply-air temperature to be reset to a higher value maintains air circulation in the space without costly overcooling.
The accessory package is required for temperature reset.
The accessory includes:
• thermistor T10, to monitor space temperature
• reset temperature potentiometer P7, to establish start temperature for reset operation
• reset limit potentiometer P3, to establish maximum level
of modified supply-air temperature
More than one space sensor may be used if an average
space temperature is desired for initiating temperature reset.
Refer to installation section for sensor part number and wiring schematic.
Temperature reset will start when space temperature (at
T10) drops to the set point at P7. When Temperature Reset
is active, the LED (light-emitting diode) display will show
code. Automatic adjustment of supply-air temperature
21
set point will end when modified SASP equals reset limit set
point at P3. (See formula for automatic modification of SASP
in Controls Installation, Space Temperature Reset section on
this page.)
CONTROLS INSTALLATION
The VAV units may be used in applications with additional control features, options, or accessories. Refer to the
appropriate accessory installation instructions for more information on installing that accessory.Unit control box component arrangement is shown in Fig. 20-22. Control options
and accessories available for VAV units are:
• smoke control modes
• differential enthalpy sensor
• electric heaters (sizes 034-074 only)
• modulating power exhaust
• Motormastert I control
• space temperature reset
• night setback thermostat (field-supplied)
• single step demand limit
• two-step demand limit
• inlet guide vanes
• variable frequency drive
• variable frequency drive remote display kit
Control Wiring — A switch or timeclock (field sup-
plied) must be wired in to control when unit will go into and
out of Occupied mode. Connect switch or timeclock between terminals 1 and 2 on terminal block 3 (sizes 034-048)
or terminal block 4 (sizes 054-104) in unit control box. See
Fig. 23. The circuit potential is 24 v.
Variable air volume units equipped with warm-up heat require that room terminals be controlled to go fully open when
unit goes into the Heating mode. Heating interlock relay (HIR)
is provided for this function. The relay is located in the unit
control box. When unit goes into Heating mode, interlock
relay is energized providing switch closure or opening (depending on how field power source is set up) to open the
room terminals. Field connections for interlock relays are
terminals 3 and 4 (for normally open contacts) and terminals
3 and 7 (for normally closed contacts) on terminal block 3
(sizes 034-048) or terminals block 4 (sizes 054-104). See
Fig. 24. Note that a field-supplied power source is required.
There are no required 115-volt field wiring connections,
therefore no provisions have been made in the unit for running 115-volt wiring. If any of the field-installed options requiring 115-volt connections are desired, the unit must be
modified in the field for 115-volt wiring.
NIGHT SETBACK THERMOSTAT — Wire field-supplied
thermostat (suitable for 24-v circuit) between terminals 1 and
2 on terminal block 3 (sizes 034-048) or terminal block 4
(sizes 054-104). This thermostat is used to bypass the timeclock occupied/unoccupied switch and is used to operate unit
during unoccupied times at more economical temperatures.
(See Fig. 23.)
SPACETEMPERATURERESETACCESSORY
(50DJ900021) — Consists of a thermistor (T10) and a reset
board with a potentiometer (P7) that is used to set space temperature at which reset starts. Mount reset board in unit
control box or other convenient place. Wire thermistor in series with P7 and connect to terminals 12 and 15 on terminal
block 3 (sizes 034-048) or terminal block 4 (sizes 054-104)
in unit control box. If there is a long run to conditioned space,
it is necessary to splice additional wire to thermistor. The
reset board has 2 pressure connectors for field wiring. (See
Fig. 25).
Space Temperature Reset
INSTALLATION — Install the accessory temperature reset
package in accordance with instructions provided with the
accessory kit.
Mount the reset board in the unit control box (or other
suitable location) per instructions.
Locate the thermistor T10 in a suitable location in the occupied space per instructions.
Wire T10 to the reset board and to the unit control terminal block per Fig. 25. Wire the other terminal on the reset
board to the unit control terminal block per Fig. 25.
If multiple sensors are required to average the space temperature, see Fig. 26. Use only Carrier Part Number
HH79NZ014 sensor, in arrangements of 4 or 9 sensors, with
total wiring not to exceed 1000 ft.
To enable reset function, change DIP (dual in-line package) switch 2 to position ON. (Disconnect control power before changing DIP switch positions; reconnect power after
all changes have been made.)
CONFIGURATION — Set points for reset operation are established at potentiometers P7 and P3 (on the reset board).
Potentiometer P7 — Reset temperature set point (temperature at which reset function will start). Maximum of 80 F,
minimum 0° F .Set below normal room cooling set point level
to sense overcooling in the occupied space.
NOTE: It is difficult to accurately set the P7 potentiometer
to the desired set point. Use the procedure below.
Proper setting of the P7 potentiometer may be made on a
resistance basis. The microprocessor initiates reset when it
detects a resistance of the thermistor plus the potentiometer
of 13,084 ohm. The potentiometer set point may be calculated using the following formula:
P7
= 13,084 – T10
R
Where:
P7
= the desired set point of the P7 potentiometer in ohms
R
T10R= the resistance of the T10 thermistor for the desired
set point
R
13
Fig. 20 — Unit Control Box Arrangement, Sizes 034-04814Fig. 21 — Unit Control Box Arrangement, Sizes 054-078
15
16
Fig. 22 — Unit Control Box Arrangement, Sizes 088 and 104
034-048: TB3
054-104: TB4
12
034-048: TB3
054-104: TB4
Control will automatically adjust leaving air temperature by
the following formula:
MSP = SP + [(P3 - SP) / 3] x (P7 − T10)
where:
MSP = Modified Leaving-Air Set Point
OCCUPIED/UNOCCUPIED
SWITCH
SP= Supply-Air Set Point
P3= Maximum Supply-Air Temperature (reset limit)
P7= Reset Initiation Temperature (reset set point)
NIGHT SETBACK THERMOSTAT
T10 = Actual Space Temperature
3= Ratio for reset (F) (fixed parameter)
Table 4 — Thermistor Resistance and
NOTES:
1. Occ/Unocc switch closes when occupied.
2. Night setback thermostat closes when in night setback heating.
Fig. 23 — Occupied/Unoccupied Switch with
Night Setback Thermostat
034-048: TB3
054-104: TB4
3
4
6
5
4
7
V
N.O.
N.C.
FIELD
SUPPLIED
POWER
SOURCE
SIGNAL
TO ROOM
TERMINALS
Fig. 24 — Heat Interlock Relay
034-048: TB3
054-104: TB4
12
15
T10
P7
RESET
BOARD
Fig. 25 — Accessory Reset Board
EXAMPLE:
T10 desired set point is 70 F.
from Table 4 for 70 F is 5929 ohms.
T10
R
P7R= 13,084 – 5929
P7R= 7155 ohms
Using an ohmmeter, set the P7 potentiometer to
7155 ohms to achieve a reset initiation set point of 70 F.
Potentiometer P3 — Reset limit set point (maximum tem-
perature value for modified supply air set point). Maximum
of 70 F, minimum 40 F. Set between leaving air set point
(P1) and 70 F (maximum range permitted by control).
OPERATING SEQUENCE — If space temperature is above
Voltage Drop Characteristics
TEMP
(F)
31.016813.83.582
32.016345.73.553
33.015892.23.523
34.015452.73.494
35.015026.73.464
36.014613.93.434
37.014213.63.404
38.013825.53.373
39.013449.23.343
40.013084.23.312
41.012730.13.281
42.012386.63.250
43.012053.33.219
44.011730.03.187
45.011416.13.156
46.011111.53.124
47.010815.83.093
48.010528.73.061
49.010250.03.029
50.09979.32.997
51.09716.52.965
52.09461.32.933
53.09213.42.901
54.08972.62.869
55.08738.62.837
56.08511.42.805
57.08290.62.772
58.08076.12.740
59.07867.72.708
60.07665.12.676
61.07468.32.644
62.07277.12.612
63.07091.22.581
64.06910.62.549
65.06735.12.517
66.06564.42.486
67.06398.62.454
68.06237.52.423
69.06080.82.391
70.05928.62.360
71.05780.62.329
72.05636.82.299
73.05497.02.268
74.05361.22.237
75.05229.12.207
76.05100.82.177
77.04976.02.147
78.04854.82.117
79.04736.92.088
80.04622.42.058
reset set point (T10 > P7), no reset will occur.
If space temperature is equal to or less that reset set point
(T10 < P7), the LED will displayand reset will begin.
20
RESISTANCE
(Ohms)
VOLTAGE
DROP (v)
17
SIZES 034-048
TB3
12
15
TO ACCESSORY SPACE
TEMPERATURE RESET
CONTROL BOARD
SIZES 054-104
TB4
12
15
SIZES 034-048
TB3
12
15
TO ACCESSORY SPACE
TEMPERATURE RESET
CONTROL BOARD
SIZES 054-104
TB4
12
15
RED
BLK
RED
BLK
RED
BLK
RED
BLK
SENSOR 1SENSOR 2SENSOR 3SENSOR 4
RED
BLK
SPACE TEMPERATURE RESET — 4 SENSOR AVERAGING APPLICATION
RED
BLK
BLK
SENSOR 1
RED
RED
BLK
SENSOR 2
RED
BLK
RED
BLK
SENSOR 3
RED
BLK
SENSOR 4
NOTE:Sensorpart number is HH79NZ014.
BLK
RED
SPACE TEMPERATURE RESET — 9 SENSOR AVERAGING APPLICATION
Fig. 26 — Space Temperature Sensor Averaging
Demand Limit — The demand limit function provides
a means to limit the cooling capacity of the VAV unit using
an external discrete switch function. When enabled by the
closure of the external switch, the control will limit the available compressor staging capacity according to user set points
established at demand limit potentiometer(s).
The unit controls support two types of demand limit: single-
step and 2-step control.
SINGLE-STEPDEMAND LIMIT — This function will limit
the total compressor staging based on the ratio of the set point
potentiometer’s wiper arm position to the full scale resistance of the potentiometer.The exact percentage of capacity
reduction differs depending on the number of capacity steps.
A field-supplied potentiometer and control switch are required for this function. See installation section for specification on potentiometer and field wiring.
TWO-STEP DEMAND LIMIT — Two-step demand limit is
provided with the installation of the accessory Demand Limit
SENSOR 6SENSOR 5
RED
BLK
SENSOR 8SENSOR 7SENSOR 9
RED
BLK
Control Module kit plus installation of 2 field-supplied control switches (SPST-NO each). This accessory control provides for a first step reduction of 50% to 100% of the maximum compressor staging; the second step provides for reduction
between 0% and 49%. The exact percentage of capacity reduction differs depending on the number of capacity steps.
When demand limit is active, the LED display will show
22
code.
INSTALLATION
Single-Step Demand Limit — A 3-wire 5 to 20 K-ohm potentiometer must be field-supplied and installed. A singlepole normally open switch is also required (field-supplied
and -installed). Locate the potentiometer (designated P4) and
the switch in a suitable location (external from the unit or in
the unit control box).
18
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.