Carrier 50EW, 50EY, 50EJ, 50EK User Manual

50EJ,EK,EW,EY024-048
Single-Package Rooftop Units
Electric Cooling with Electric Heat Option
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS .................. 1
INSTALLATION ............................ 1-31
Step 1 — Provide Unit Support .............. 1
• ROOF CURB
• ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit ................. 8
• ROOF MOUNT
Step 3 — Field Fabricate Ductwork ...........11
Step 4 — Make Unit Duct Connections .......11
Step5—TrapCondensate Drain .............11
Step 6 — Controls Options ..................12
• CONSTANT VOLUME APPLICATIONS
• VARIABLE AIR VOLUME (VAV) APPLICATIONS
Step 7 — Make Electrical Connections .......15
• POWER WIRING
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 8 — Make Outdoor-Air Inlet
Adjustments ...............................25
• ECONOMIZER
• ECONOMIZER SETTINGS
Step 9 — Position Power Exhaust/
Barometric Relief Damper Hood .............29
Step 10 — Install Accessories ...............30
START-UP ................................32-42
SERVICE ..................................42-45
TROUBLESHOOTING ......................46-51
START-UP CHECKLIST ...............CL-1, CL-2
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trained andqualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, ob­serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes.W earsafetyglasses and work gloves. Use quenching cloth for unbrazing operations. Have fire ex­tinguishers available for all brazing operations.
IMPORTANT — READ BEFORE INSTALLING
IMPORTANT: Due to upgrades in unit control soft­ware and hardware, units produced currently are slightly different than original design units. The unit control software (which has changed) is designated with a sticker on the unit control board, chip U8 (the large chip in the center of the board), which states the software Ver­sion number. Version 1.0 is the original version. Ver­sion 2.0 is the current version. Differences in instal­lation, configuration, and start-up procedures in this manual will be identified by Version number.
INSTALLATION
Step 1 — Provide Unit Support
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with the curb. Ac­cessory roof curb and information required to field fabricate a roof curb or horizontal adapter are shown in Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be secured to roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a leak-proof seal. Install gasket sup­plied with the roof curb as shown in Fig. 1. Improp­erly applied gasket can result in air leaks and poor unit performance.
Curb should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is shown in Fig 1 and 2. Refer to Accessory Roof Curb Installation In­structions for additional information as required. When ac­cessory roof curb is used, unit may be installed on class A, B, or C roof covering material.
ALTERNATEUNITSUPPORT—When the curb or adapter cannot be used, support unit with sleepers using unit curb or adapter support area. If sleepers cannot be used, support long sides of unit (refer to Fig. 3-6) with a minimum number of equally spaced 4-in. x 4-in. pads as follows: 50EJ,EK,EW,EY024-034 units require 3 pads on each side; 50EJ,EK,EW,EY038-048 require 4 pads on each side. Unit may sag if supported by corners only.
Before performing service or maintenance operations on unit, turn offmain power switch to unit. Electrical shock could cause personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 1b
PC 111 Catalog No. 535-006 Printed in U.S.A. Form 50E-3SI Pg 1 8-96 Replaces: 50E-1SI
NOTE: To prevent standing water in the drain pan of the indoor section and the heat exchangers, UNIT CAN ONLY BE PITCHED AS SHOWN.
NOTES:
1. Unlessotherwisespecified,alldimensions are to out­side of part.
2. Roof curb accessory is shipped disassembled.
3. All roof curb parts are to be 16 ga galvanized steel.
4. Dimensions are in inches.
Fig. 1 — Roof Curb (Sizes 024-034)
UNIT LEVELING TOLERANCES DIMENSIONS*
*From edge of unit to horizontal.
(Degrees and Inches)
AB
Deg. in. Deg. in.
1.0 2.9 .50 .75
2
NOTES:
1. Unlessotherwisespecified,alldimensions are to out­side of part.
2. Roof curb accessory is shipped disassembled.
3. All roof curb parts are to be 16 ga galvanized steel.
4. Dimensions are in inches.
Fig. 2 — Roof Curb (Sizes 038-048)
NOTE: To prevent standing water in the drain pan of the indoor section and the heat exchangers, UNIT CAN ONLY BE PITCHED AS SHOWN.
UNIT LEVELING TOLERANCES DIMENSIONS*
*From edge of unit to horizontal.
(Degrees and Inches)
AB
Deg. in. Deg. in.
1.0 2.9 .50 .75
3
NOTES:
1. Weights include economizer (Std)
2. Center of gravity.
3. Do not locate adjacent units with dis­charge facing economizer inlet. Mini­mum clearances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for re­moval of evaporator coil)
4. For smaller service and operational clearances, contact Carrier Applica­tion Engineering department.
5. Bottom ducts designed to be attached toaccessoryroof curb. If unitismounted on dunnage, it is recommended the ductsbe supported by cross braces as done on accessory roof curb.
6. Dimensions are in inches. Dimen­sions in [ ] are in millimeters.
7. For units with electric heat, a field­supplied 90° elbow must be installed in the supply ductwork below the unit discharge.
LEGEND
VFD — Variable Frequency Drive
UNIT SIZE
50EJ/EK
OPERATING
WEIGHT
(lb)
024 4016 5-11 028 4102 5- 8 030 4102 5- 8 034 4102 5- 8
AB
ft-in. ft-in. 1 2 3 4
3
⁄83-511⁄16823 914 1199 1080
1
⁄23-75⁄8844 859 1210 1189
1
⁄23-75⁄8844 859 1210 1189
1
⁄23-75⁄8844 859 1210 1189
CORNER WEIGHT
Fig. 3 — Base Unit Dimensions, 50EJ/EK024-034
4
(lb)
NOTES:
1. Weights include economizer (Std)
2. Center of gravity.
3. Do not locate adjacent units with discharge facing economizer inlet. Mini­mum clearances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for removal of evaporator coil)
4. For smaller service and operational clearances, contact Carrier Applica­tion Engineering department.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is mountedondunnage,itisrecommendedtheductsbesupportedbycross braces as done on accessory roof curb.
6. Dimensions are in inches. Dimensions in [ ] are in millimeters.
7. For units with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discharge.
LEGEND
VFD — Variable Frequency Drive
UNIT SIZE
50E
OPERATING
WEIGHT
(lb)
J038 4282 7-7 J/K044 4508 7-3 J048 4795 7-2
AB
ft-in. ft-in. 1 2 3 4
5
⁄163-101⁄2961 858 1162 1302
13
⁄163-111⁄2973 868 1258 1409
3
⁄163-103⁄321007 915 1368 1505
CORNER WEIGHT
(lb)
Fig. 4 — Base Unit Dimensions, 50EJ038-048 and 50EK044
5
NOTES:
1. Weights include economizer (Std)
2. Center of gravity.
3. Donotlocateadjacent units with discharge facing econo­mizer inlet. Minimum clearances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for removal of evaporator coil)
4. For smaller service and operational clearances, con­tact Carrier Application Engineering department.
5. Dimensions are in inches. Dimensions in [ ] are in millimeters.
6. For units equipped with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork be­low the unit discharge.
7. For side-supply/return applications, a single return and supply ductwork connection is recommended for cov­ering both return and both supply openings.
Fig. 5 — Base Unit Dimensions, 50EW/EY024-034
UNIT SIZE
50EW/EY
OPERATING
WEIGHT
(lb)
024 4016 5-11 028 4102 5- 8 030 4102 5- 8 034 4102 5- 8
6
LEGEND
VFD — Variable Frequency Drive
AB
CORNER WEIGHT
(lb)
ft-in. ft-in. 1 2 3 4
3
⁄83-511⁄16823 914 1199 1080
1
⁄23-75⁄8844 859 1210 1189
1
⁄23-75⁄8844 859 1210 1189
1
⁄23-75⁄8844 859 1210 1189
NOTES:
1. Weights include economizer (Std)
2. Center of gravity.
3. Do not locate adjacent units with discharge facing economizer inlet. Minimum clearances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Filter Access Side: 108-09 (for removal of evaporator coil)
4. For smaller service and operational clearances, contact Carrier Application Engineering department.
5. Dimensions are in inches. Dimensions in [ ] are in millimeters.
6. For units equipped with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discharge.
7. For side-supply/return applications, a single return and supply duct­work connection is recommended for covering both return and both supply air openings.
Fig. 6 — Base Unit Dimensions, 50EW038-048 and 50EY044
UNIT SIZE
50E
W038 4282 7-7 W/Y044 4508 7-3 W048 4795 7-2
7
OPERATING
WEIGHT
(lb)
LEGEND
VFD — Variable Frequency Drive
AB
CORNER WEIGHT
(lb)
ft-in. ft-in. 1 2 3 4
5
⁄163-101⁄2961 858 1162 1302
13
⁄163-111⁄2973 868 1258 1409
3
⁄163-103⁄321007 915 1368 1505
Step2 — Rig and Place Unit — Inspect unit for trans-
portation damage. File any claim with transportation agency. Keep unit upright, and do not drop. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is shown in Fig. 1 and 2. See Fig. 7 for additional information. Unit weight is shown in Table 1.
NOTE: On retrofit jobs, ductwork may be attached to old unit instead of roof curb. Be careful not to damage ductwork when removing unit. Attach existing ductwork to roof curb instead of unit.
Four lifting lugs are provided on the unit base rails as shown
in Fig. 7. Refer to rigging instructions on unit. POSITIONING — Provide clearance around and above unit
for airflow, safety, and service access (Fig. 3-6).
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE
WHEN RIGGING.
NOTE: Rig with four cables and spread with two 92 in. (2337 mm) spreader bars. Maintain a dis­tance of 74 in. (1880 mm) from top of unit to eyehook.
NOTE:
Add 32 lb (14.5 kg) for domestic crating. Add 312 lb (142 kg) for export crating (024-034 units). Add 346 lb (157 kg) for export crating (038-048 units). Add 250 lb (113 kg) for power exhaust. Add 220 lb (100 kg) for copper condenser coil (024-034 units). Add 285 lb (129 kg) for copper condenser coil (038-044 units). Add 380 lb (172 kg) for copper condenser coil (048 unit).
MODEL
50EJ/EK/EW/EY
024 4016 1822 87.68 2227 71.4 1814 41.7 1059 028
034 038* 4282 1942 044 4508 2045 87.8 2230 46.5 1181 048* 4795 2175 86.2 2189 46.1 1171
*Sizes 038 and 048 are 50EJ,EW units only.
WEIGHT A B C
lb kg in. mm in. mm in. mm
4102 1860 87.68 2227 68.5 1740 43.6 1107030
91.3 2319 46.5 1181
150 3810
Fig. 7 — Rigging Label
8
Table 1 — Physical Data
UNIT 50EJ,EK,EW,EY 024 028 030 034 NOMINAL CAPACITY (tons) 20 25 27 30 OPERATING WEIGHT (lb)*
Unit
Al/Al† 4016 4102 4102 4102 Al/Cu† 4236 4322 4322 4322
Roof Curb (14-in. curb) 365 365 365 365
COMPRESSOR
Type Ckt 1 06D328 06D328 06D537 06D537
Ckt 2 06D818 06D328 06D328 06D537 Number of Refrigerant Circuits 22 2 2 Oil (oz) (Ckt1, Ckt 2) 115, 88 115 ea. 115 ea. 115 ea.
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1** 25-0 25-0 25-0 25-0 Circuit 2 31-0 25-0 25-0 25-0
CONDENSER COIL Cross-Hatched
Quantity 11 1 1 Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 33.3 33.3 33.3 33.3
CONDENSER FAN Propeller Type
Nominal Cfm 13,420 13,420 13,420 13,420 Quantity...Diameter (in.) 2...30 2...30 2...30 2...30 Motor Hp (1075 Rpm) 11 1 1
EVAPORATOR COIL Cross-Hatched
Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 31.7 31.7 31.7 31.7
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...20x15 2...20x15 2...20x15 2..20x15 Type Drive Belt Belt Belt Belt Nominal Cfm 8,000 10,000 11,000 12,000 Motor Hp 5 10†† 15 7.5 10†† 15 10 15†† 20 10 15†† 20 Motor Frame Size S184T S215T S254T S213T S215T S254T S215T S254T S256T S215T S254T S256T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 1200 Motor Pulley Pitch Diameter 4.6 6.6 6.9 4.9 6.1 7.1 6.6 6.7 7.5 6.4 6.9 7.5 Nominal Motor Shaft Diameter (in.) 1 Fan Pulley Pitch Diameter (in.) 11.1 12.5 11.1 11.1 11.1 11.1 13.7 11.1 11.1 12.5 11.1 11.1 Nominal Fan Shaft Diameter (in.) 111⁄ Belt, Quantity...Type 1...BX59 1...BX60 1...5VX590 1...BX56 1...BX56 1...5VX590 1...BX62 1...5VX590 1...5VX600 1...BX60 1...5VX590 1...5VX600 Belt, Length (in.) 62 63 59 59 59 59 65 59 60 63 59 60 Pulley Center Line Distance (in.) 16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 Factory Speed Setting (rpm) 725 924 1088 773 962 1119 843 1056 1182 896 1088 1182
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
LOW-PRESSURE SWITCH (psig)
Cutout 77 7 7 Reset (Auto.) 22 22 22 22
RETURN-AIR FILTERS
Quantity...Size (in.) 10...20x24x2 10...20x24x2 10...20x24x2 10...20x24x2
OUTDOOR-AIR FILTERS 8...16x25 8...16x25 8...16x25 8...16x25
Quantity...Size (in.) 4...20x25 4...20x25 4...20x25 4...20x25
POWER EXHAUST Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired For High Speed) and Forward Curved Fan
Motor, Quantity...Hp 4...1 Fan, Diameter...Width (in.) 11...10
1
8
13⁄
8
15⁄
8
13⁄
8
16
LEGEND
Al — Aluminum Cu — Copper
*Weightof unit does not includevariable frequencydrive (VFD), barometric relief, orpower
exhaust. If a VAV unit (a VFD is installed), add the VFD weight in the table at right.
†Evaporator coil fin material/condenser coil fin material.
**Sizes 024-034: Circuit 1uses the lower portion ofcondenser coil,Circuit 2 uses the upper
portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right.All units have intertwined evaporator coils.
††Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more
drive information, see Table 2.
3
⁄89 Copper Tubes, Aluminum Lanced or Copper Fins
3
⁄89 Copper Tubes, Aluminum or Copper Plate Fins, Intertwined Circuits
13⁄
8
15⁄
8
13⁄
8
15⁄
8
15⁄
8
111⁄
16
NOTES:
1. See Table 2 for evaporator fan motor data.
2. Sizes 038 and 048 are 50EJ,EW units only.
VFD (Hp)
111⁄
16
VFD WEIGHTS (lb)
208/230 v 460 v 575 v
5 20 22 60
7.5 51 37 64 10 51 61 64 15 61 63 109 20 63 111 109 25 105 112 174 30 172 118 180
13⁄
8
15⁄
8
15⁄
8
111⁄
16
9
Table 1 — Physical Data (cont)
UNIT 50EJ,EK,EW,EY 038 044 048 NOMINAL CAPACITY (tons) 35 40 45 OPERATING WEIGHT (lb)*
Unit
Al/Al† 4282 4508 4795 Al/Cu† 4567 4793 5175
Roof Curb (14-in. curb) 410 410 410
COMPRESSOR
Type Ckt 1 06D537 06EA250 06EA265
Ckt 2 06D537 06EA250 06EA250 Number of Refrigerant Circuits 22 2 Oil (oz) (Ckt1, Ckt 2) 115 ea. 224 ea. 304, 224
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1** 34-0 35-0 41-0 Circuit 2 34-0 35-0 41-0
CONDENSER COIL Cross-Hatched
Quantity 2211 Rows...Fins/in. 3...15 3...15 4...15 3...15 Total Face Area (sq ft) 58.3 58.3 66.7
CONDENSER FAN Propeller Type
Nominal Cfm 27,064 27,064 27,064 Quantity...Diameter (in.) 4...30 4...30 4...30 Motor Hp (1075 Rpm) 11 1
EVAPORATOR COIL Cross-Hatched
Rows...Fins/in. 3...15 3...15 4...15 Total Face Area (sq ft) 34.7 34.7 34.7
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2..20x15 2...20x15 2...20x15 Type Drive Belt Belt Belt Nominal Cfm 14,000 16,000 18,000 Motor Hp 10 15†† 20 15 20†† 25 20 25†† 30 Motor Frame Size S215T S254T S256T S254T S256T S284T S256T S284T S286T Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 Motor Pulley Pitch Diameter 4.1 6.9 7.5 6.9 8.1 9.1 5.3 5.9 7.5 Nominal Motor Shaft Diameter (in.) 1 Fan Pulley Pitch Diameter (in.) 9.1 12.5 12.5 12.5 13.7 13.7 9.1 9.1 11.1 Nominal Fan Shaft Diameter (in.) 111⁄ Belt, Quantity...Type 1...BX51 1...5VX630 1...5VX650 1...5VX630 1...5VX670 2...5VX680 1...5VX550 2...5VX560 2...5VX610 Belt, Length (in.) 54 63 65 63 67 68 55 56 59 Pulley Center Line Distance (in.) 15.6-18.4 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 14.6-17.6 14.6-17.6 Factory Speed Setting (rpm) 788 966 1050 1066 1035 1162 1019 1135 1182
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 Reset (Auto.) 320 320 320
LOW-PRESSURE SWITCH (psig)
Cutout 77 7 Reset (Auto.) 22 22 22
RETURN-AIR FILTERS
Quantity...Size (in.) 10...20x24x2 10...20x24x2 10..20x24x2
OUTDOOR-AIR FILTERS 8...16x25 8...16x25 8...16x25
Quantity...Size (in.) 4...20x25 4...20x25 4...20x25
POWER EXHAUST Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired For High Speed) and Forward Curved Fan
Motor, Quantity...Hp 4...1 Fan, Diameter...Width (in.) 11...10
3
8
15⁄
8
16
15⁄
8
LEGEND
Al — Aluminum Cu — Copper
*Weightof unit does not includevariable frequencydrive (VFD), barometric relief, orpower
exhaust. If a VAV unit (a VFD is installed), add the VFD weight in the table at right.
†Evaporator coil fin material/condenser coil fin material.
**Sizes 024-034: Circuit 1uses the lower portion ofcondenser coil,Circuit 2 uses the upper
portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right.All units have intertwined evaporator coils.
††Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more
drive information, see Table 2.
3
⁄89 Copper Tubes, Aluminum Lanced or Copper Fins
3
⁄89 Copper Tubes, Aluminum or Copper Plate Fins, Intertwined Circuits
15⁄
8
NOTES:
1. See Table 2 for optional evaporator fan motor data.
2. Sizes 038 and 048 are 50EJ,EW units only.
VFD (Hp)
111⁄
15⁄
8
16
11⁄
8
15⁄
8
VFD WEIGHTS (lb)
208/230 v 460 v 575 v
5 20 22 60
7.5 51 37 64 10 51 61 64 15 61 63 109 20 63 111 109 25 105 112 174 30 172 118 180
111⁄
17⁄
8
16
17⁄
8
10
Table 2 — Evaporator Fan Motor Data
UNIT
MOTOR
SIZE
024
028
030
034
038
044
048
NOTE: Motor shaft speed is 1750 rpm. The fan shaft diameter is 1
HP
10 1.38 924 BK72 6.6 None-1.375 1B5V124 12.5 B-1.6875 BX60 63 7.05 15 1.62 1088 1B5V68 6.9 B-1.625 1B5V110 11.1 B-1.6875 5VX590 59 9.38
7.5 1.38 773 BK55H 4.9 H-1.375 1B5V110 11.1 B-1.6875 BX56 59 6.87 10 1.38 962 BK67H 6.1 H-1.375 1B5V110 11.1 B-1.6875 BX56 59 7.26 15 1.62 1119 1B5V70 7.1 B-1.625 1B5V110 11.1 B-1.6875 5VX590 59 9.17
10 1.38 843 BK72 6.6 None-1.375 1B5V136 13.7 B-1.6875 BX62 65 6.96 15 1.62 1056 1B5V66 6.7 B-1.625 1B5V110 11.1 B-1.6875 5VX590 59 9.60 20 1.62 1182 1B5V74 7.5 B-1.625 1B5V110 11.1 B-1.6875 5VX600 60 11.67
10 1.38 896 BK70H 6.4 H-1.375 1B5V124 12.5 B-1.6875 BX60 63 7.20 15 1.62 1088 1B5V68 6.9 B-1.625 1B5V110 11.1 B-1.6875 5VX590 59 9.38 20 1.62 1182 1B5V74 7.5 B-1.625 1B5V110 11.1 B-1.6875 5VX600 60 11.17
10 1.38 788 2BK47 4.1 None-1.375 2B5V90 9.1 B-1.6875 BX51 54 5.49 15 1.62 966 1B5V68 6.9 B-1.625 1B5V124 12.5 B-1.6875 5VX630 63 9.22 20 1.62 1050 1B5V74 7.5 B-1.625 1B5V124 12.5 B-1.6875 5VX650 65 10.02
15 1.62 966 1B5V68 6.9 B-1.625 1B5V124 12.5 B-1.6875 5VX630 63 9.54 20 1.62 1035 1B5V80 8.1 B-1.625 1B5V136 13.7 B-1.6875 5VX670 67 10.37 25 1.88 1162 1B5V90 9.1 B-1.875 1B5V136 13.7 B-1.6875 5VX680 68 10.88
20 1.62 1019 2B5V52 5.3 B-1.625 2B5V90 9.1 B-1.6875 5VX550 55 7.93 25 1.88 1135 2B5V58 5.9 B-1.875 2B5V90 9.1 B-1.6875 5VX560 56 8.66 30 1.88 1182 2B5V76 7.5 B-1.875 2B5V110 11.1 B-1.6875 5VX610 59 9.07
MOTOR
SHAFT
DIAMETER
(in.)
5 1.12 725 BK52 4.6 None-1.125 1B5V110 11.1 B-1.6875 BX59 62 5.02
FAN SHAFT SPEED
(rpm)
MOTOR
SHEAVE
MOTOR
SHEAVE
PITCH
DIAMETER
(in.)
11
BUSHING
DIAMETER
⁄16inches.
ROOF MOUNT — Check building codes for weight distri­bution requirements.
(in.)
FAN
SHEAVE
FAN
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
BELT
OUTSIDE
BELT
LENGTH
BELT
TENSION
(Lb @
.24 in.)
Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors be­tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
To attach ductwork to roof curb, insert ductwork approxi­mately 10 to 11 in. up into the curb. Connect ductwork to 14-gage roof curb material using sheet metal screw driven from inside the duct.
The units with electric heat require a 1-in. clearance for the first 24 in. of ductwork.
NOTE: A 90-degree elbow must be provided in the duct­work to comply with UL (Underwriters’ Laboratories) codes for use with electric heat.
Outlet grilles must not lie directly below unit discharge.
Step 4 — Make Unit Duct Connections
50EJ,EK UNITS — Unit is shipped for through-the-bottom duct connections. Ductwork openings are shown in Fig. 3 and 4. Attach all ductwork to roof curb. Air distribution is shown in Fig. 8. Refer to installation instructions shipped with accessory roof curb for more information.
50EW,EY UNITS — Remove shipping covers from supply and return air openings. Attach field-supplied ductwork to unit. Use a single duct over both return openings and a single duct over both supply openings. See Fig. 5 and 6 for duct opening dimensions. Secure all ducts to the building struc­ture. See Fig. 9. Use flexible duct connectors between unit and ducts as required.
Install accessory barometric relief or power exhaust in the field-fabricated return ductwork. Refer to Position Power Exhaust/Barometric Relief Damper Hood Section on page 29 for more information.
Step5—TrapCondensate Drain — See Fig. 3-6
and 10 for drain location. Condensate drain is open to the atmosphere and must be trapped. Install a trapped drain at
Fig. 8 — Air Distribution — Thru-the-Bottom
Fig. 9 — Air Distribution — Thru-the-Side
the drain location. One 1-in. FPT coupling is provided in­side unit evaporator section for condensate drain connec­tion. A trap at least 4-in. deep must be used. Trap must be installed to prevent freeze-up.
Condensate pans are sloped so that water will completely drain from the condensate pan to comply with indoor air qual­ity guidelines.
11
Fig. 10 — Condensate Drain Connections
(Typical Roof Curb or Slab Mount Shown)
Step 6 — Controls Options — The control options
that the units can provide are based on the following param­eters: CV (constant volume) or VAV (variable air volume) operation; stand-alone unit with field-supplied sensors in­stalled (CV or VAV); as a system via the Carrier Comfort System (TEMP or VVT); optional electronic expansion board installed (CV or VAV); linked to the Carrier Comfort Net­work; and availability of a computer and software (Comfort Works, Building Supervisor, and Service Tool) to access the base control board. See Table 3.
NOTE: Access to the base control board allows unit occu­pancy schedules, unit timeclock, and various set points to be changed from their factory-defined default settings.
CONSTANT VOLUME APPLICATIONS — The standard CV unit is capable of being operated with either a Carrier­approved thermostat or a field-supplied sensor. (See Price Pages for ordering information.)
Features with Thermostat Control of Unit
• two-stage heating (if installed)
• two-stage cooling
• control of unit using Y1, Y2, W1, W2, and G thermostat inputs
• control of the indoor fan
• outdoor air temperature/supply air temperature monitoring
• control of an outdoor air condenser fan based on outdoor air temperature
• control of modulating economizer damper to provide free cooling when outdoor conditions are suitable, using sup­ply air temperature as a control point
• control of the economizer damper and indoor fan to obtain unoccupied free cooling
• provide power exhaust output to an external power ex­haust controller
• support a field test for field checkout
• control of 2 stages of CV power exhaust
• compressor Time Guardt (power up and minimum offand on times)
Additional features are provided by accessing the stand­ard unit control board via software with a computer. These features are:
• electronic expansion board features (if installed)
• compressor lockout during low supply air temperature
• control board diagnostics
• ability to change supply air set point (economizer control)
• ability to change high outdoor air temperature lockout set
point (economizer control)
• ability to change power exhaust set points NOTE: A CV unit without a thermostat requires a field-
supplied sensor for operation. Features with Sensor Control of Unit (Stand-Alone Appli-
cations — Unit control is limited to CV unoccupied default set points, 90 F for cooling, 55 F for heating. There are 3 sensor options available:
• T-57 sensor will monitor room temperature
• T-55 sensor will monitor room temperature and provide
unoccupied override capability (1 hour)
• T-56 sensor will monitor room temperature, provide un-
occupied override capability (1 hour), and provide a tem­perature offset of 5° F.
Standard features are:
• support of remote occupied/unoccupied input to start and
stop the unit
• cooling capacity control of 3 stages using economizer and
2 compressors to maintain space temperature to an occu­pied or unoccupied set point
• enable heating (if installed) or cooling during unoccupied
periods as required to maintain space temperature within the unoccupied set points
• adjustment of space temperature set points of ± 5° F when
using a T-56 sensor
Table 3 — Controls Options and Configurations (Non-Thermostat Applications)
UNIT CONFIGURATION DEFAULT COOLING DEFAULT HEATING
UNITS RUNNING VERSION 1.0 UNIT CONTROL SOFTWARE CV or VAV Unit with SPT Sensor CV Unit with SPT Sensor and Remote
Start/Stop Switch VAV Unit Remote Start/Switch Only VAV Unit with SPT Sensor and Remote
Start/Stop Switch UNITS RUNNING VERSION 2.0 UNIT CONTROL SOFTWARE
CV or VAV Unit with SPT Sensor CV Unit with SPT Sensor and Remote
Start/Stop Switch VAV Unit Remote Start/Stop Switch Only VAV Unit with SPT Sensor and Remote
Start/Stop Switch
CV Constant Volume SAT — Supply-Air Temperature NA — Not Available SPT — Space Temperature RAT — Return-Air Temperature VAV — Variable Air Volume
LEGEND
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — NA
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — 78 F (SPT)
Unoccupied Cooling — NA Occupied Cooling — 55 F (SAT)
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — 55 F (SAT)
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — NA
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — 78 F (SPT)
Unoccupied Cooling — 90 F (RAT) Occupied Cooling — 55 F (SAT)
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — 55 F (SAT)
Unoccupied Heating — 55 F (SPT) Occupied Heating — NA
Unoccupied Heating — 55 F (SPT) Occupied Heating — 68 F (SPT)
Unoccupied Heating — NA Occupied Heating — NA
Unoccupied Heating — 55 F (SPT) Occupied Heating — NA
Unoccupied Heating — 55 F (SPT) Occupied Heating — NA
Unoccupied Heating — 55 F (SPT) Occupied Heating — 68 F (SPT)
Unoccupied Heating — 55 F (RAT) Occupied Heating — 68 F (RAT)*
Unoccupied Heating — 55 F (SPT) Occupied Heating — 68 F (RAT)*
*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled). NOTE: Space temperature sensor and remote stop/switch are field-supplied.
12
Features with sensor control of unit with computer access
are:
• 365 day timeclock with backup (supports minute, hour, day of week, date, month, and year)
• daylight savings time function
• occupancy control with 8 periods for unit operation
• holiday table containing up to 18 holiday schedules
• ability to initiate timed override from T-55 or T-56 sensors
• ability to use multiple space temperature sensors to aver­age the space temperature
• supply air temperature reset for the supply air temperature set point
• temperature compensated start to calculate early start times before occupancy
• access to the Display, Maintenance, Configuration, Serv­ice, and Set Point data table through network software
When the unit is equipped with a field-supplied space tem­perature sensor and a remote contact closure (remote start/ stop) on the base control board, the occupied default set points will monitor unit operation. The occupied default set points are 78 F cooling and 68 F heating (if electric heat is in­stalled). See Fig. 11 for remote start/stop wiring.
NOTE: For units which have not had the base unit control board accessed via software to set an occupancy schedule, the remote start/stop closure will allow the unit to operate in the pre-configured occupied default set points (based on return­air temperature) of 78 F cooling and 68 F heating. Without this feature, the unit will control to the unoccupied default set points of 90 F cooling and 55 F heating (if electric heat is installed).
An electronic expansion board may be field-installed to provide the following features:
• control of modulating economizer damper to maintain
indoor air quality (IAQ) when outdoor conditions are suitable
• provide discrete inputs for fan status, filter status, field-
applied status, and demand limit
• provide an output for the external alarm light indicator
When the unit is connected to the CCN (Carrier Comfort Network), the following expansion board features can be utilized.
• perform Demand Limit functions based on CCN loadshed
commands or the state of the discrete input
• alarm monitoring of all key parameters
• CCN protocol
• provides power exhaust fire outputs for direct control of
modulated power exhaust stages during fire or smoke modes
• smoke control modes including evacuation, smoke purge,
pressurization, and fire shutdown (modulating power ex­haust required)
• provides CCN IAQ participation
See Carrier TEMP or VVTt (Variable Volume and Tem­perature) literature for complete TEMP (single zone) or VVT (multi-zone) application information.
or during unexpected power outages. For complete Carrier Comfort System (CCS) or Carrier Comfort Network (CCN) features and benefits, refer to the product literature.
VARIABLE AIR VOLUME (VAV) APPLICATIONS Features with Stand-Alone Applications — A VAV unit is
capable of providing unoccupied cooling controlling to a 90 F return-air temperature utilizing the factory-supplied return­air thermistor located below the return-air damper in the return­air section for unit control. The unit will provide unoccupied heating (if electric heat is installed) controlling to a 55 F return-air temperature. Also provided is a morning warm-up which is initiated by the Occupied mode (if electric heat is installed) and continues until the return-air temperature rises to 68 F. The unit will provide occupied cooling with a de­fault temperature of 55 F for the supply air. The supply-air temperature is measured by the supply-air thermistor, lo­cated in the indoor fan compartment.
Standard features of a VAV unit with a remote start/stop
switch are:
• control of an outdoor condenser fan based upon outdoor air temperature
• control of modulating economizer to provide free cooling when outdoor conditions are suitable, using supply air tem­perature as a set point
• support of remote occupied/unoccupied input to start or stop the unit
• provide power exhaust output to an external power ex­haust controller
• support supply air temperature reset to offset supply air set point
• support a field test for field check out
• support linkage to DAV systems
• cooling capacity control of 6 stages plus economizer with compressors and unloaders to maintain supply air tem­perature set point during occupied periods
• control of one stage of heat to maintain supply air tem­perature at supply air set point during occupied periods
• provide a variable frequency drive high voltage relay out­put to enable VFD
• control of heat interlock relay
With the addition of a remote start/stop switch heating or cooling is enabled during unoccupied periods as required to maintain space temperature to within unoccupied set points.
Features with Sensor Control of Unit (Network Applica­tions) — The base control board provides, as standard, a con­nection for use with a Carrier VVT system and can also be integrated into a Carrier Comfort Network.
When the unit is accessed via a PC equipped with Com­fort Works, Building Supervisor, or Service Tool, the fol­lowing features can be accessed:
• on-board timeclock can be programmed
• occupancy schedules can be programmed
• unit set points can be changed
• alarms can be monitored
This access is available on the base control board via a RJ-11 phone jack or a 3-wire connection to the communi­cation bus. See Fig. 12. The timeclock has a 10-hour minimum back-up time to provide for unit power off for servicing unit
NOTE: On units running Version 1.0 of the Unit Control Software, the remote start/stop switch is connected to R and Y1. On units running Version 2.0 of the Unit Control Software, the remote start/stop switch is connected to R and W1.
Fig. 11 — Field Control Remote Start/Stop
13
LEGEND
CCN — Carrier Comfort Network R—Relay
COM — Common SIO — Serial Input/Output
D—Diode SW — Switch
N.C. — Normally Closed T—Terminal
N.O. — Normally Open
*Where X is the unit control software version (1 or 2).
Fig. 12 — Control Board Diagram
14
For units running Version1.0 of the unit control software, network access software is required to enable occupied heat­ing. For units running Version 2.0 of the unit control soft­ware, occupied heating is enabled or disabled by the posi­tion of DIP switch no. 5.
Additional features may be provided with electronic ac­cess to Unit Control Board. These features are:
• control board diagnostics
• compressor time guard override (power up, minimum off
and on times)
• compressor lockout during low supply-air temperature
• electronic expansion board features (if installed)
• field test capability
• control of the economizer damper and indoor fan to op-
tion unoccupied free cooling
• 365 day timeclock with backup (supports minute, hour, day,
month, and year)
• holiday table containing up to 18 holiday schedules
• occupancy control with 8 periods for unit operation
• support a set of display, maintenance, configuration, serv-
ice, and set point data tables for interface with Building Supervisor, Comfort Works, or Service Tool
When a VAV unit with a space temperature sensor is ac­cessed via a computer, the following additional features are available:
• ability to initiate timed override from T-55 sensors
• ability to use multiple space temperature sensors to aver-
age space temperature
• temperature compensated start to calculate early start time
before occupancy
• provide space temperature reset to reset the supply air set
point upward when the temperature falls below the occu­pied cooling set point
An electronic expansion board may be field-installed to provide the following features:
• fan status
• filter status
• field-applied status
• demand limiting
• IAQ sensor
• OAQ sensor
• alarm light
When the unit is connected to the CCN (Carrier Comfort Network), the following expansion board features can be utilized:
• CCN IAQ (indoor air quality) participation
• CCN OAQ (outdoor air quality) participation
• CCN demand limit participation
• fire unit shutdown
• fire pressurization
• fire evacuation
• fire smoke purge
• modulated power exhaust override
Afield-supplied space temperature sensor can be added to provide the following:
• T-57 sensor will monitor room temperature
• T-55 sensor will monitor room temperature and provide
unoccupied override capability (1 hour)
When the unit is equipped with a field-supplied space tem­perature sensor and a remote contact closure (remote start/ stop), the occupied default set points will monitor unit op­eration. The occupied default set points are 55 F (supply air) cooling and 68 F (space temperature) heating (if electric heat is installed). See Fig. 11 for remote start/stop wiring.
NOTE: For units without a space temperature sensor and which have not had the base unit control board accessed via soft­ware to set an occupancy schedule, the remote start/stop clo­sure will allow the unit to operate in the pre-configured oc­cupied default set points of 55 F (supply-air temperature) cooling and 68 F (return-air temperature) heating. Without
an occupancy schedule, the unit will control to the unoccu­pied default set points of 90 F (return air) cooling and 55 F (return air) heating (if electric heat is installed).
Features with Network Applications — The base control board provides, as standard, a connection for use with a Carrier Comfort System and can also be integrated into a Carrier Comfort Network. When the unit is accessed via a PC equipped with Comfort Works, Building Supervisor, or Service Tool software, the following features can be accessed:
• on-board timeclock can be programmed
• occupancy schedules can be programmed
• unit set points can be changed
• alarms can be monitored This access is available on the base control board via a
RJ-11 phone jack or a 3-wire connection to the communi­cation bus. See Fig. 12. The timeclock has a 10-hour mini­mum back-up time to provide for unit power off for servic­ing unit or during unexpected power outages. For complete Carrier Comfort System (CCS) or Carrier Comfort Network (CCN) features and benefits, refer to the product literature.
Step 7 — Make Electrical Connections
POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate. The main terminal block is suitable for use with aluminum or copper wires and is sized for single-point electric heat.
When installing units, provide a disconnect per NEC (Na-
tional Electrical Code) of adequate size (MOCP [maximum overcurrent protection] of unit is on the informative plate). All field wiring must comply with NEC and all local codes. Size wire based on MCA (minimum circuit amps) on the unit informative plate. See Fig. 13 for power wiring con­nections to the unit power terminal block and equipment ground.
The main power terminal block is suitable for use with
aluminum or copper wire. See Fig. 13. Units have circuit breakers for compressors, fan motors, and control circuit. If required by local codes, provide an additional disconnect, per NEC and local codes requirements, of adequate size (Table 4). Whenever external electrical sources are used, unit must be electrically grounded in accordance with local codes, or in absence of local codes, with NEC, ANSI (American National Standards Institute) C1-latest year.
All field wiring must comply with NEC and local code
requirements. FIELD POWER SUPPLY — Unit is factory wired for volt-
age shown on nameplate. See Table 4 for electrical data.
Field wiring can be brought into the unit from bottom
(through basepan and roof curb) or through side of unit (cor­ner post next to control box).
EQUIP — Equipment GND Ground NEC National Electrical Code TB Terminal Block
NOTE: Maximum wire size for TB1 is 500 MCM.
Fig. 13 — Field Power Wiring Connections
15
LEGEND
A31⁄2-in. NPT coupling for field power wiring and a
3
⁄4-in. NPT coupling for 24-v control wiring are provided in basepan. In the side post, there are two 21⁄2-in. (024-034) or 3-in. (038-048) knockouts for the field power wiring. See Fig. 3-6. If control wiring is to be brought in through the side of unit, a7⁄8-in. diameter hole is provided in the con­denser side post next to the control box.
If disconnect box is mounted to corner post, be careful
not to drill any screws into the condenser coil. Routing Through Bottom of Unit — If wiring is brought in
through bottom of unit, use field-supplied watertight conduit to run power wiring from basepan out through bottom 31⁄2-in. hole to the disconnect box and back into unit to the main control box.
1
Use strain relief going into control box through 2
⁄2-in. diameter hole provided. After wires are in unit control box, connect to power terminal block (see Power Wiring section on this page 15).
Low-voltage wiring must be run in watertight conduit from
the basepan to control box and through
7
⁄8-in. diameter hole provided in bottom of unit control box. Field-supplied strain relief must be used going into the box. After wiring is in control box, make connections to proper terminals on ter­minal blocks (see Field Control Wiringsection on this page).
Install conduit connector in unit basepan or side panel open­ings provided. Route power and ground lines through con­nector to connections in unit control box as shown on unit wiring diagram and Fig. 13.
Routing Through Side of Unit — Route power wiring in field-supplied watertight conduit into unit through 21⁄2-or 3-in. hole. Strain relief (field supplied) must be used in hole. See Fig. 13.
Use field-supplied strain relief going into control box through
1
⁄2- or 3-in. diameter hole provided. After wires are in unit
2 control box, connect to power terminal block (see Power Wir­ing section on page 15).
Bring low-voltage control wiring through factory-drilled
7
⁄8-in. diameter hole in condenser side post. Use strain relief
going into7⁄8-in. diameter hole in bottom of unit control box.
After wiring is in control box, make connection to proper terminals on terminal blocks (see Field Control Wiring sec­tion on this page).
IMPORTANT: THE VAV (variable air volume) units incorporateVFD (variable frequency drives) which gen­erate, use, and can radiate radio frequency energy. If units are not installed and used in accordance with these instructions, they may cause radio interference. They have been tested and found to comply with limits of a Class A computing device as defined by FCC (Federal Communications Commission) regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment.
The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association).
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2% and the current must be balanced within 10%.
Use the formula in Table 4 to determine the percentage of voltage imbalance.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility com­pany immediately.
Unit failure as a result of operation on improper line volt­age or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
On 208/230-v units, transformer no. 1 is wired for 230-v. If 208/230-v unit is to be run with 208-v power supply, the transformer must be rewired as follows:
1. Remove cap from red (208-v) wire.
2. Remove cap from spliced orange (230-v) wire. Discon-
nect orange wire from black unit power wire.
3. Cap orange wire.
4. Splice red wire and black unit power wire. Cap wires.
IMPORTANT: Be certain unused wires are capped. Failure to do so may damage the transformers.
FIELD CONTROL WIRING — Install either a Carrier­approved accessory thermostat or a CCN (Carrier Comfort Network) compatible temperature sensor.Thermostats are used on CV (constant volume) units only. Control box diagrams are shown in Fig. 14 and 15.
Thermostat Wiring (CV Only) — Install a Carrier-approved accessory thermostat assembly (per current price pages) ac­cording to the installation instructions included with the ac­cessory or these instructions. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of col­ored wire from subbase terminals to low-voltage connec­tions as shown on unit label wiring diagram and in Fig. 16.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (Ameri­can Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly con­nected to the thermostat and will require a junction box and splice at the thermostat.
Set heat anticipators settings to 0.1 for all voltages. Set­tings may be changed slightly to provide a greater degree of comfort for a particular installation.
Sensor Wiring (CV or VAV) — The temperature sensor is wired into the unit control board. See Fig. 17.
The unit is controlled with a T55, T56 (CV only), or T57 zone sensor. Terminal TH on the sensor is connected to T1 of the base module board. Terminal COM on the sensor is connected to T2 on the base module board. If a T56 set point override sensor is used, the override connection SW on the sensor is connected to T3 on the base module board.
VAV units using Version 1.0 of the unit control software may operate without a space temperature sensor during oc­cupied schedules, but unit will not provide unoccupied heat­ing or cooling.
VAV Units — VAV units require a field-supplied heat inter­lock relay (HIR) to drive the air terminal wide open when in heat mode. The HIR part number is HN61KK041.
Remote Field Control (Units Running Version 1.0 of Unit Control Software) — A switch closure across terminals R
and Y1 on TB-3 will initiate the Occupied mode. This can be done manually as well as through a field-supplied timeclock.
16
Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048
NOMINAL
UNIT
VOLTAGE
SIZE
(3 Ph 60 Hz)
208/230 187 254 39.1 228 25.6 160 2 1 5.3
024
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.
If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker. NOTES:
1. In compliance with NEC requirements formultimotor and combination load equip­ment (referto NEC Articles 430 and 440), theovercurrent protective device forthe unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
% Voltage Imbalance = 100 x EXAMPLE: Supply voltage is 460-3-60.
460 414 508 19.9 114 11.5 80 2 1 2.7
575 518 632 16.0 91 9.6 64 2 1 2.4
Use the following formula to determine the percent of voltage imbalance.
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP†
LEGEND
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
COMPRESSOR
No. 1 No. 2
average voltage
452 + 464 + 455
3
1371
=
3
= 457
OFM IFM
5
10
15
5 7.6
10 14
15 21
5 6.1
10 11
15 17
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v (BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA).
POWER
EXHAUST
101.8/100.3 125/125
23.6 41.6 125.4/123.9 150/150
16.7/
29/36 75.1/ 86.6 114.7/127.3 125/150
23.6 41.6 29/36 75.1/ 86.6 144.2/156.8 150/175
15.2 — 59/72 150.1/173.2 171.0/192.2 200/225
23.6 41.6 59/72 150.1/173.2 200.5/221.7 225/225 — 115.9/113.1 150/150
23.6 41.6 139.5/136.7 175/175
30.8/
29/36 75.1/ 86.6 132.3/143.3 150/150
23.6 41.6 29/36 75.1/ 86.6 161.8/172.8 175/175
28.0 — 59/72 150.1/173.2 188.6/208.2 220/225
23.6 41.6 59/72 150.1/173.2 218.1/237.7 250/250 — 131.3/127.1 150/150
23.6 41.6 154.9/150.7 175/175
46.2/
29/36 75.1/ 86.6 151.6/160.8 175/175
23.6 41.6 29/36 75.1/ 86.6 181.1/190.3 200/200
42.0 — 59/72 150.1/173.2 207.9/225.7 250/250
23.6 41.6 59/72 150.1/173.2 237.4/255.2 275/275 — 49.4 60
12.6 23.6 62.0 80 — 36 43.3 63.6 70
12.6 23.6 36 43.3 79.4 80 — 72 86.6 96.1 110
12.6 23.6 72 86.6 111.9 125 — 55.8 70
12.6 23.6 68.4 80 — 36 43.3 71.6 80
12.6 23.6 36 43.3 87.4 90 — 72 86.6 104.1 110
12.6 23.6 72 86.6 119.9 125 — 62.8 80
12.6 23.6 75.4 90 — 36 43.3 80.4 90
12.6 23.6 36 43.3 96.1 100 — 72 86.6 112.9 125
12.6 23.6 72 86.6 128.6 150 — 40.5 50
12.6 23.6 53.1 60 — 36 34.6 50.9 60
12.6 23.6 36 34.6 66.7 70 — 72 69.3 76.9 80
12.6 23.6 72 69.3 92.7 100 — 45.4 60
12.6 23.6 58.0 70 — 36 34.6 57.1 60
12.6 23.6 36 34.6 72.8 80 — 72 69.3 83.0 90
12.6 23.6 72 69.3 98.8 100 — 51.4 60
12.6 23.6 64.0 80 — 36 34.6 64.6 70
12.6 23.6 36 34.6 80.3 90 — 72 69.3 90.5 100
12.6 23.6 72 69.3 106.3 110
= 1.53%
7
457
ELECTRIC
HEAT*
POWER SUPPLY
17
Loading...
+ 39 hidden pages