Carrier 48MA-50ME016-040 User Manual

48MA/50ME016-040
Combination Multizone Heating/Cooling Units
Gas, Electric, or Glycol Heat
Installation, Start-Up
and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................2
INSTALLATION .............................2-34
General ......................................2
Unit Clearances ..............................2
Roof Curb ...................................2
Rigging Unit .................................5
Removing Shipping Shields ..................5
Field-Fabricated Ductwork ....................5
Condensate Drains ...........................9
Gas Piping (48MA) ...........................9
Optional Glycol Connections (50ME) .........10
Field Power Supply Wiring ..................10
• UNIT COMMON FEED MINIMUM CIRCUIT AMPS
• ZONE THERMOSTATS
• ZONE MODULE CONNECTIONS
• ACCESSORY REMOTE CONTROL PANEL
Reheat Humidity Control ....................34
Optional Economizer ........................34
Optional Exhaust Damper ...................34
START-UP ................................34-39
Evaporator Fan .............................34
Compressor Rail Shipping Bolts .............34
Refrigerant Valves ..........................34
Zone Module Gas Valves (48MA) .............34
Gas Heat Lighting Procedure (48MA) .........35
• TO SHUT OFF GAS HEAT
Intermittant Pilots (48MA) ...................35
• ADJUSTMENT
• PRESSURE ADJUSTMENT (NATURAL GAS)
Main Burner Adjustment (48MA) .............36
• ORIFICE ALIGNMENT
• PRIMARY AIR ADJUSTMENT
Outdoor-Air Thermostat Adjustment
(50ME With Electric Heat) ..................36
• UNITS WITH 2-ELEMENT HEATERS
• UNITS WITH 3-ELEMENT HEATERS
Optional Glycol Heating Coils ................38
Zone Airflow Adjustment ....................38
Sequence of Operation .....................38
• COOLING
• HEATING (48MA)
• HEATING (50ME WITH ELECTRIC HEAT)
• HEATING (50ME WITH GLYCOL HEATING COILS)
• OUTDOOR-AIR DAMPER
SERVICE ..................................39-43
Cabinet Panels and Grilles ..................39
• SIDE PANELS
• TOP PANELS
• HEATER ACCESS PANELS
• EVAPORATOR COILS (ZONE COOLING COILS) AND GLYCOL HEATING COILS
• CONDENSER AND OUTDOOR-AIR COOLING COILS
• CONDENSATE DRAINS
• INDOOR-AIR FILTERS
• OUTDOOR-AIR INLET SCREENS
• GAS HEATING SECTION
• COMBUSTION AIR FAN
Airflow Switches ............................39
• INDOOR AIRFLOW SWITCH (AFS1)
• COMBUSTION AIRFLOW SWITCH (AFS2)
Service Switch ..............................39
Time GuardT Control Circuit .................39
Capacity Control Pressure Switches (CCP)
(2-Compressor Units Only) ................39
Compressor Oil .............................39
• TO ADD OR REMOVE OIL
Compressor Capacity Control Unloader(s) ....40
• CONTROL SET POINT
• PRESSURE DIFFERENTIAL
Crankcase Heater(s) .........................40
Refrigerant Charge ..........................40
• NO CHARGE
• LOW CHARGE
Head Pressure Control ......................40
• MOTORMASTERt HEAD PRESSURE CONTROL
DEVICE
• FAN CYCLING PRESSURESTAT
Condenser Fans ............................41
• ADJUSTMENT
• FAN MOTOR REMOVAL
• LUBRICATION
Evaporator Fans and Motor ..................41
• MOTOR REMOVAL
• FAN SHAFT BEARING REMOVAL
• FAN SPEED ADJUSTMENT
• PULLEY REMOVAL
• PULLEY ALIGNMENT
• BELT TENSION ADJUSTMENT
• LUBRICATION
Forced-Draft Blower (48MA) .................42
• LUBRICATION
• AIR SHUTTER ADJUSTMENT
Zone Module Transformers ..................42
Optional Economizer ........................42
• THERMOSTAT SETTINGS
• DAMPER POSITION
• OPERATION
Optional Exhaust Damper ...................42
Replacement Parts ..........................42
START-UP CHECKLIST .....................CL-1
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 Tab 1c 1d
PC 111 Catalog No. 564-840 Printed in U.S.A. Form 48MA/50ME-3SI Pg 1 4-96 Replaces: 48MA/50ME-1SI
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, ob­serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
INSTALLATION
General —
stall unit, electrical wiring, gas supply line (48MA) and con­densate drain lines in accordance with all applicable codes.
Install unit on rooftop, outdoor site only. In-
Unit Clearances — See Fig. 1 and 2 for service and
airflow clearances. For 48MA gas-fired units, provide not less than 36-in. clearance to combustibles from top and all sides. Keep burner end free from any obstruction.
Locate exit terminals of mechanical draft system (48MA
flue outlet) as follows:
• Not less than 12 in. from any opening through which com­bustion products could enter the building.
• Not less than 2 ft from any adjacent building.
• Not less than 7 ft above grade when unit is adjacent to public walkways.
Before performing service or maintenance operations on unit, turn offmain power switch to unit. Electrical shock could cause personal injury.
Do not try to light any appliance. Do not touch any elec­trical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you can­not reach your gas supplier, call the fire department.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of the 48MA unit or any other gas-fired appliance.
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Re­fer to this manual. For assistance or additional infor­mation, consult a qualified installer, service agency, or the gas supplier.
Disconnect gas piping from 48MA unit when leak test­ing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pres­sure greater than 0.5 psig, it must be replaced. When pressure testing field-supplied gas piping at pressures of
0.5 psig or less, the unit connected to such piping must be isolated by manually closing the gas valve.
RoofCurb — Assemble and install per instructions shipped
with this accessory. Information required to field fabricate a roof curb and other curb data are shown in Fig. 3-5.
Install field-supplied insulation, cant strips, roofing and counter flashing as required. Seal all curb joints with mastic or other suitable roof cement to keep out moisture. Be sure that run-offpan at compressor end of curb is completely flashed and sealed.
Seal strip (Fig. 3) is shipped with accessory roof curb. In­stall as described in the roof curb installation instructions. The seal strip compresses under unit weight so that an air­tight seal and vibration isolation are provided between unit base and curb.
Roof Openings — Except for the compressor and con-
denser section, roof area under the unit need not be filled in as the curb-mounted unit encloses this space. Leaving this roof section open provides ample clearance for ductwork, piping, and power and control wiring.
If the roof area inside curb is to be filled in so that roof deck and bottom of base unit can be used as a return-air ple­num, any spaces under the curb flanges caused by corru­gated roofing or roof irregularities must be sealed to prevent water seepage. If spaces are not sealed, the negative pres­sure of return air may draw water under the unit and into the building structure.
If openings are cut in a finished roof, provide at least 6-in. space on each of the longer sides of the supply and return air openings. Due to interference from the roof curb structure, this additional clearance may not be possible on the short sides.
2
CONDENSER SECTION AIRFLOW
CONN — Connection
NOTES:
1. Space required for service and airflow all around and above unit is 36 inches.
2. For additional information see Fig. 4.
3. Centerof gravity is within 6in. radius of geo­metric center of unit.
4. Maximum allowable pitch of unit is 10 ft in any direction.
1
⁄2in. per
Certified dimension drawings available on request.
UNIT
48MA
016-030 7- 2
AB C DEFGHJKL
3
⁄43-05⁄
8
17-115⁄162-215⁄1613-51⁄20- 91⁄162-10 7-33⁄160-31⁄80-31⁄
034,040 7-11 3-915⁄16* 21- 91⁄164-25⁄
*Overall height; includes 13⁄4-in. for fan guards.
Fig. 1 — Base Unit Physical Data and Dimensions; 48MA Units
DIMENSIONS (ft-in.)
8
13-51⁄20-111⁄163- 45⁄168-63⁄40-31⁄320-215⁄160-71⁄
3
8
0-31⁄
8 4
CONDENSER SECTION AIRFLOW
CONN — Connection
NOTES:
1. Space required for service and airflow all around and above unit is 36 inches.
2. For additional information see Fig. 5.
3. Centerof gravity is within 6in. radius of geo­metric center of unit.
4. Maximum allowable pitch of unit is 10 ft in any direction.
1
⁄2in. per
Certified dimension drawings available on request.
UNIT
50ME
016-030 7- 2
A B C D EFGHJ
3
4
3-09⁄
16
17-115⁄
034,040 7-11 3-915⁄16* 21-91⁄
*Overall height; includes 13⁄4-in. for fan guards.
Fig. 2 — Base Unit Physical Data and Dimensions; 50ME Units
DIMENSIONS (ft-in.)
16
2-215⁄
16
13-51⁄
2
3-71⁄
16
7-33⁄
16
0-31⁄
8
0-31⁄
16
4-25⁄
8
13-51⁄
2
4-4 8-63⁄
4
0-215⁄
16
0-71⁄
8 4
4
AIRFLOW
*Factory supplied (with accessory roof curb). †Field supplied (when using accessory roof curb).
NOTE: Dimensions are in inches.
Fig. 3 — Roof Curb Detail
Rigging Unit — Inspect unit for shipping damage, and
file any damage claim immediately with transportation company.
Lift unit with cables and spreader bars, using lifting brack­ets provided (Fig. 1 and 2). Lift one unit at a time, keep unit upright, and do not drop. Unit weights are given in Table 1. Unit center of gravity is within 6 in. of unit’s geometric cen­ter. Eyebolts may be removed after unit is in final position.
IMPORTANT: Do not drill or punch holes in unit frame or panels; damage to internal components or wiring may result.
UnitPositioning — When lowering unit onto roof curb,
do not exceed the out-of-symmetry tolerances given in Fig. 4 and 5. Be sure unit is level or is pitched within speci­fied tolerances. Units have drains on both sides and may be pitched to either side.
Removing Shipping Shields (Fig. 6)
1. Remove shield over flue outlet grille (48MA only).
2. Remove shields (sheet metal covers) located in the outdoor-
air inlet screen tracks behind the louvers. If the screens are removed for this procedure, be sure to replace them before replacing the louvered assembly.
Field-Fabricated Ductwork — Supply- and return-
air openings are shown in Fig. 4 and 5. To simplify supply­air connection, a zone duct plenum may be field fabricated as shown in Fig. 7. It is recommended that this plenum be installed prior to unit positioning.
It is recommended that the unit be supported on blocks temporarily while the duct plenum is installed, rather than installing the plenum while the unit is suspended. The duct plenum may be installed once the unit is located in its final position, but it is much easier to install the plenum prior to unit final placement.
Zone supply-air duct openings on the base unit have tab slot connections similar to those shown in Fig. 7 except that the end partitions are hemmed. Hem is positioned so that the 1-in. flange at entering end of field-fabricated plenum will force-fit between hem and adjacent unit frame.
Standard flexible duct connections between duct plenum and duct system may be used. Follow applicable codes.
Insulate any supply-air ducts passing through uncondi­tioned spaces and cover with a vapor barrier. Separate ducts with insulation if they run parallel for more than 5 ft. This will prevent heat transfer between zones.
Install a manual balancing damper in each zone duct to provide the required zone airflow.
The return-air duct connection consists of 4 sheet metal flanges as shown in Fig. 1, 2, 4, and 5.
5
Table 1 — Physical Data
UNIT 48MA/50ME 016 024 028 030 034 040
Zone Modules (Quantity) 8 8 10 10 12 12 Nominal Cooling Capacity (tons) 15 20 25 28 30 37
OPERATING WEIGHT (lb)
Base Unit 48MA 3395 3815 4075 4080 5340 5710 Base Unit 50ME (with electric heat) 2995 3415 3675 3680 4900 5270
Roof Curb 506 506 506 506 630 630 REFRIGERANT CHARGE — R-22 (lb) 28 32 43 43 57 66.1 COMPRESSOR Reciprocating Hermetic, 1725 Rpm
No. 1 Type 06DE537 06DE824 06DE537 06DE537 06DE537 06EE250
Cylinders...Unloaders 6...2 6...2 6...2 6...2 6...2 4...1
No. 2 Type 06DA824 06DA824 06DA537 06DA537 06EA250
Cylinders (have no unloaders) —66664
System Oil Charge (pints) 11 18 18 18 18 31
Unloader Settings (psig) Compressor No. 1 Only
Unloader No. 2
Unloader No. 1
Capacity Steps (%) 100,67,33 CONDENSER FANS Propeller, Direct Drive
Motor Hp...Rpm...Frame (NEMA)
Nominal Cfm 16,500 15,000 15,000 15,000 24,000 23,000 EVAPORATOR FANS* Centrifugal, Belt Drive
Number...Size (in.) 2...15 × 15 2...15 × 15 2...15 × 15 2...15 × 15 3...15 × 9 3...15 × 9
Cfm (Nominal) 6000 8000 10,000 10,000 12,000 12,000
Motor Hp...Rpm
Fan Pulley
Outside Diameter (in.) 10.6 10.6 8.0 8.0 8.0 8.0 Bore (in.) 1
Fan Belt Number...Size
Motor Pulley Factory Installed
Outside Diameter (in.) Bore (in.) 1 Resulting Fan Rpm Shaft Center Line Distance (in.) 18 ± 2.5 18 ± 2.5 18 ± 2.5 18 ± 2.5 21 ± 2.5 21 ± 2.5
Maximum Fan Rpm 1300 1300 1300 1300 1550 1550
CONDENSER COOLING COIL Thermostatic Expansion Valve, Hot Gas Bypass
Face Area (sq ft) 6.8 6.8 6.8 6.8 10.2 10.2
Corrugated Fins/in. ...Rows 13...2 13...2 13...2 13...2 13...2 13...3
EVAPORATOR COILS (zone) Solenoid Valve and Capillary Tube for each
Number...Face Area (sq ft/ea) 8...2.12 8...2.12 10...2.12 10...2.12 12...2.01 12...2.01
Corrugated Fins/in. ...Rows 13...3 13...3 13...3 13...3 12...3 15...3
HEATING SECTION (48MA) One Heat Assembly in Each Zone Module
Rise Range 25 F to 55 F at 0.75 in. wg ESP
Input (1000 Btuh)
Bonnet Cap.† (1000 Btuh)
Burner Spud Qty...Size 2...38 2...38 2...38 2...38 2...38 2...38 OPTIONAL HEATING SECTION (50ME Electric)
Electric Heaters Nichrome, Open-Wire Resistance Element in Each Zone Module
Qty...Elements (each)** 8...2 or 3 8...2 or 3 10...2 or 3 10...2 or 3 12...2 or 3 12...2 or 3 OPTIONAL HEATING SECTION
(50ME Glycol Coil)
Maximum Allowable Inlet Temperature (F) 200
Maximum Allowable Flow, Each Coil (Gpm) 6
Solution Mixture 20% Glycol
Maximum Allowable Working Pressure (Psig) 30
Total Internal Volume (Gal) 2.61 2.61 3.15 3.15 3.76 3.76 PRESSURE SWITCHES
Low-Pressure (Psig)
High-Pressure (Psig)
Indoor Airflow Switch (AFS1)
Factory Setting (cfm) 6000 9000 Adjustment Range (cfm) 4000-6000 6000-9000
INDOOR AIR FILTERS
Standard Qty...Size (in.) 12...20 × 25 × 2
High Efficiency (optional)
Qty...Size (in.)
OUTDOOR AIR FILTERS
Qty...Size (in.) 2...20 × 25 × 1 2...32 × 35 × 1
LEGEND
ESP External Static Pressure NEMA — National Electrical Manufacturers Association
*Standard unit shipped with standard motor, pulley, and belt(s); alternate unit shipped with alternate motor, pulley, and belt(s).
†The heating efficiency rating is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system.
**See Field Power Supply Wiring section on page 10 and Table 4 for details.
Loads 71.0 ± 1.5 Unloads 57.5 ± 2.5 Loads 75.0 ± 1.5 75.5 ± 1.5 Unloads 62.5 ± 2.5 58.0 ± 2.5
No. 1 1...1075...56 (Single phase) No. 2 1...1140...56 (3 phase) No. 3 ————1...1140...56 (3 phase)
Std 5...1725 7 Alt ————20...1725 20...1725
3
Std 1...3V630 1...3V630 2...3V560 2...3V560 2...3V630 2...3V630 Alt ————3...3V670 3...3V670
Std 5.3 6.0 5.0 5.0 5.0 5.0 Alt ————6.06.0
Std 880 995 1095 1095 1095 1095 Alt ————1320 1320
Total 432 432 540 540 648 648 Each Module 54 54 54 54 54 54 Total 324 324 405 405 486 486 Each Module 40.5 40.5 40.5 40.5 40.5 40.5
16
1
8
100,83,67
50,33,17
1
⁄2...1725 10...1725 10...1725 15...1725 15...1725
13⁄
16
13⁄
8
100,80,60
40,20
13⁄
16
13⁄
8
100,80,60
40,20
13⁄
16
13⁄
8
100,83,67
50,33,17
111⁄
16
15⁄
8
One Heating Coil in Each Zone Module
Cutout 29±5 Cut-in 39±5 Cutout 400±5 Cut-in 300±5
12...20 × 25 × 2 (36.5% Efficient)
100,75,
50,25
111⁄
16
15⁄
8
6
EVAPORATOR (ZONE MODULE) AIRFLOW
CONN — Connection *Not used on 48MA016,024 (8 zone module units).
NOTES:
1. For additional information, see Table 1 and Fig. 1.
2. Maximum allowable unit pitch is
3. Remove shipping brace before assembling curb section (location shown).
1
⁄2in. per 10 ft in any direction.
UNIT
48MA
ABCDE F GHJ
016-030 18-2 034,040 21-97⁄
Fig. 4 — Roof Curb Physical Data and Dimensions; 48MA Units
1
8
7- 3 11-9 5-61⁄
8
7-113⁄
4
14-13⁄
DIMENSIONS (ft-in.)
4
7-27⁄
8
1-109⁄
16
2-29⁄
16
6-03⁄
8
0- 71⁄
4
6-77⁄
16
8-43⁄
16
2- 91⁄
8
3-1 6-81⁄
2
0-105⁄
2 16
7
(034,044 12-ZONE MODULES)
END DETAIL
EVAPORATOR (ZONE MODULE) AIRFLOW
CONN — Connection *Not used on 50ME016,024 (8 zone module units).
NOTES:
1. For additional information, see Table 1 and Fig. 2.
2. Maximum allowable unit pitch is
3. Remove shipping brace before assembling curb section (location shown).
1
⁄2in. per 10 ft in any direction.
UNIT
50ME
ABCDE F GHJ
016-030 18-2 034,040 21-97⁄
Fig. 5 — Roof Curb Physical Data and Dimensions; 50ME Units
1
8
7- 3 11-9 5-61⁄
8
7-113⁄
4
14-13⁄
DIMENSIONS (ft-in.)
4
7-27⁄
8
1-109⁄
16
2-29⁄
16
6-03⁄
8
0- 71⁄
4
6-77⁄
16
8-43⁄
16
2- 91⁄
8
3-1 6-81⁄
2
0-105⁄
2 16
8
CondensateDrains — Pipe nipples covered with foam
rubber insulation are shipped in unit return air filter section (6 nipples in units 48MA, 4 nipples in units 50ME). Install a nipple in each drain connection on both sides of unit. See Fig. 1 and 2 for drain locations. Be sure foam rubber seals space between nipple and base rail opening to prevent rain leaks.
Connect a drain line to drain connection under outdoor air inlet grilles on both sides of unit. These drains need not be trapped.
Install a trapped drain line on remaining connections on lowest side of unit depending on unit pitch. If unit is level, a trapped drain may be installed at each connection if de­sired. Cap or plug unused connections on high side of unit to prevent airflow between unit interior and outdoors.
OUTDOOR AIR INLET (ONE ON EACH SIDE OF UNIT) SHIPPING SHIELD (BEHIND LOUVERS)
FLUE OUTLET COVER (48MA ONLY)
Do not interconnect drains. Make each trap a minimum of 4 in. deep. Insulate trap against freeze-up or use flexible material.
Gas Piping (48MA) — Unit is equipped for use with
type of gas shown on nameplate. Refer to latest edition of ANSI Z223.1. Unit main gas connection and alternate gas connection locations are shown in Fig. 1, 4, and 8. Do not use gas supply pipe smaller than unit gas connection. Maxi­mum allowable natural gas supply pressure is 10.0 in. wg; minimum allowable natural gas supply pressure for full rate input is 5.0 in. wg.
1
Pitch pipe upward to risers and from risers upward to meter. Install a dirt and moisture pocket (drip leg) at each section of vertical pipe run. Use only ground joint unions to ensure leakfree joints. Use only pipe joint compounds that are resistant to the action of liquefied petroleum gases.
⁄4in. per 15 ft. Pitch all horizontal pipe runs
Fig. 6 — Shipping Shield Locations
(016-030 Units Shown)
NOTE: Dimension to suit job requirements. Twelve inches will bring duct plenum to bottom of roof curb.
Fig. 7 — Field-Fabricated Zone Duct Plenum Detail
*Typical; both ends.
9
UNIT
48MA,50ME
A* 7 B* 75⁄
DIMENSIONS (in.)
016,024 028,030 034,040
5
8 8
75⁄
8
73⁄
4
75⁄
53⁄
16
4
*Shutoff valve not used except where required by code.
All units have a main power supply terminal board in the power and condensing control box. The electric resistance heater power supply terminal board(s) (if unit is so equipped) on 50ME units is located in the heater control box at front of unit. See Fig. 2, 5, and 9.
All terminal boards are suitable for use with copper or aluminum wire.
Connect electrical conduit (a threaded pipe nipple) shipped with unit to threaded fitting in roof curb and bottom of main power and condensing section control box. Route main power wires through conduit to terminal board in box as shown on unit label wiring diagram and in Fig. 9.
When installing 48MA,50ME040 units with optional 20-hp motor,the electrical conduit interconnecting the curb and con­trol box power wire openings will not accommodate alumi­num wire of the size that may be required. If aluminum wire cannot be accommodated, an external transition box and short lengths of no. 300 kcmil, 75 C copper wire from the tran­sition box to the unit main power connection are recommended.
Voltage to compressor terminals during compressor op­eration must be within voltage range indicated on unit name­plate. Phases must be balanced within 2%.
Properly cap any gas connection not being used.
Fig. 8 — Suggested Gas Piping (48MA)
Unit has factory-installed gas shutoff valves. Install gas shutoff valve external to unit if required by code (Fig. 8). After piping is complete, pressurize gas line and check for leaks with soap and water solution.
Do not use an open flame when checking for gas leaks.
OptionalGlycol Connections (50ME) — Each zone
module has its own glycol heating coil and 115-v solenoid valve. Heating coils are connected in parallel to common sup­ply and return manifolds. Supply manifolds are equipped with bleed cocks. Supply and return connections are shown in Fig. 2 and 5. Unit does not have internal pressure relief for
part-load operation. Maximum allowable system working pres­sure is 30 psig. Unit ratings are based on 20% glycol solu-
tions. Install solution supply apparatus in accordance with application requirements, and mix glycol solution percent­age in accordance with glycol manufacturer’s recommenda­tions. Freeze-up protection is not factory installed.
Field Power Supply Wiring — When installed, unit
must be electrically grounded in accordance with local codes or,in the absence of local codes, with the National Electrical Code (NEC).
Unit has a circuit breaker for each compressor, each fan motor, and for each 50ME electric resistance heater assem­bly (if unit is so equipped). If required by local code, pro­vide an additional disconnect switch in accordance with code being followed.
LEGEND
EQUIP — Equipment GND Ground TB Terminal Board
*208/230 v units only.
Fig. 9 — Field Power Supply Details
10
Use the following formula to determine the percent volt-
age imbalance. % Voltage Imbalance:
= 100 ×
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
Determine maximum deviation from average voltage. (AB) 457 − 452=5v
(BC) 464 − 457=7v (AC) 457 − 455=2v
Maximum deviation is 7 v. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility com­pany immediately.
Unit failure as a result of operation on improper line volt­age or excessive phase imbalance constitutes abuse and may cause damage to electrical components. See Tables 2-5 for unit, electric heater, and 50ME electrical application elec­trical data.
Each 50ME electric heat unit is fitted with a heating lock­out circuit (if equipped with optional heat). If any zone mod­ule is operating on mechanical cooling (compressor is op­erating), the heating element in each zone module is locked out and cannot be energized.
On 50ME units, cooling power supply wires and electric heater power supply wires (if applicable) must be sized ac­cording to the cooling MCA (Minimum Circuit Amps) val­ues and heating MCA values shown on unit nameplate and in Tables 3-5. These wires may be powered by a common power supply (i.e., a pull-box junction), if desired. The com­mon power supply wires from the main power source to the junction must be sized according to the common MCA val­ues shown in Table 5.
UNIT COMMON FEED MINIMUM CIRCUIT AMPS — The unit common feed MCA is calculated on the basis of either: the sum of the cooling MCA plus
1
⁄2heating MCA on units with 2 heating elements per zone module (or2⁄3heat­ing MCA on units with 3 heating elements per zone module) or the sum of the evaporator fan motor full load amps, per NEC, plus the full heating MCA, whichever is larger. Field wiring must conform to NEC limitations for Type T wire.
UNIT
48MA
016
024
028
030
034
040
COMP — Compressor FLA Full Load Amps IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps
Voltage
(3 Ph, 60 Hz)
208/230 187 254 63.6 266
460 414 508 28.6 120 3.0 6.6 49.8 60 575 518 632 22.8 96 2.4 5.6 39.8 45
208/230 187 254 44.4 170 44.4 170
460 414 508 19.9 77 19.9 77 3.0 11.0 62.2 70 575 518 632 15.7 62 15.7 62 2.4 9.0 49.4 60
208/230 187 254 63.6 266 44.4 170
460 414 508 28.6 120 19.9 77 3.0 13.0 76.1 90 575 518 632 22.8 96 15.7 62 2.4 10.5 60.4 70
208/230 187 254 63.6 266 63.6 266
460 414 508 28.6 120 28.6 120 3.0 13.0 84.5 100 575 518 632 22.8 96 22.8 96 2.4 10.5 67.5 90
208/230 187 254 63.6 266 63.6 266
460 414 508 28.6 120 28.6 120 3.0 3.0
575 518 632 22.8 96 22.8 96 2.4 2.4
208/230 187 254 80.0 345 80.0 345
460 414 508 38.5 150 38.5 150 3.0 3.0
575 518 632 31.4 120 31.4 120 2.4 2.4
LEGEND
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA No. 1 No. 2 No. 3 FLA Hp FLA MCA MOCP
Table 2 — Unit 48MA Electrical Data
COMP
NO. 1
COMP
NO. 2
6.2
6.2
6.2
6.2
6.2
6.2
OFM
FLA
6.6
6.6
6.6
6.6
6.6 6.6
6.6 6.6
MOCP — Maximum Overcurrent Protection OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
NOTES:
1. Combustion air fan is a 115-1-60 motor on all units.
2. Condenser fan motor no. 1 is a 208/230-1-60 speed control motor
on all units.
COMBUSTION
FAN MOTOR
1.8 5
1.8 7.5
1.8 10
1.8 10
15 46.2 210.8 225 20 61.0 224.6 250
1.8
1.8
15 21.0 94.5 100 20 26.6 100.5 125 15 16.0 75.6 90 20 21.3 80.6 100 15 46.2 247.7 300 20 61.0 261.5 300 15 21.0 116.7 150 20 27.0 122.7 150 15 16.0 95 125 20 21.3 100 125
IFM
16.2 109.6 125
24.2 137.5 150
30.8 168.1 200
30.8 187.3 200
POWER SUPPLY
11
Table 3 — Unit 50ME Electrical Data
UNIT
50ME
016
024
028
030
034
040
COMP — Compressor FLA Full Load Amps IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
VOLTAGE
(3 Ph, 60 Hz)
208/230 187 254 63.6 266
460 414 508 28.6 120 3.0 6.6 49.5 60 575 518 632 22.8 96 2.4 5.6 39.6 45
208/230 187 254 44.4 170 44.4 170
460 414 508 19.9 77 19.9 77 3.0 11.0 61.9 70 575 518 632 15.7 62 15.7 62 2.4 9.0 49.2 60
208/230 187 254 63.6 266 44.4 170
460 414 508 28.6 120 19.9 77 3.0 13.0 75.8 90 575 518 632 22.8 96 15.7 62 2.4 10.5 60.2 70
208/230 187 254 63.6 266 63.6 266
460 414 508 28.6 120 28.6 120 3.0 13.0 84.5 100 575 518 632 22.8 96 22.8 96 2.4 10.5 67.3 90
208/230 187 254 63.6 266 63.6 266
460 414 508 28.6 120 28.6 120 3.0 3.0
575 518 632 22.8 96 22.8 96 2.4 2.4
208/230 187 254 80.0 345 80.0 345
460 414 508 39.3 150 39.3 150 3.0 3.0
575 518 632 31.4 120 31.4 120 2.4 2.4
LEGEND
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA No. 1 No. 2 No. 3 Hp FLA MCA MOCP
COMP
NO. 1
COMP
NO. 2
6.2
6.2
6.2
6.2
6.2
6.2
NOTE: Condenser fan motor no. 1 is a 208/230-1-60 speed control motor on all units.
OFM
FLA
6.6
6.6
6.6
6.6
6.6 6.6
6.6 6.6
IFM
16.2 109.6 125
—5
24.2 138.0 150
7.5
30.8 168.9 200
—10
30.8 188.0 200
—10
15 46.0 210.8 225 20 61.0 224.6 250 15 19.8 94.5 100 20 26.6 100.5 125 15 16.0 75.6 90 20 21.3 80.6 100 15 46.2 247.7 300 20 61.0 261.5 300 15 19.8 118.5 150 20 26.6 124.5 150 15 16.0 95 125 20 21.3 100 125
POWER SUPPLY
UNIT
50ME
016,024
028,030
034,040
FLA Full Load Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection
NOMINAL VOLTAGE
(3 Ph, 60 Hz)
208/230
460 575 106 3 7.7 133 150
208/230
460 575 132 3 7.7 166 175
208/230
460 575 158 3 7.7 199 200
LEGEND
ELECTRIC
HEAT kW
(Unit Total)
43/ 53 57/ 70 87/106
53 70
106
54/ 66 72/ 88
108/132
66 88
132
65/ 79 87/106
129/158
79 106 158
Table 4 — Electric Resistance Heater Data
HEATING ELEMENTS
PER ZONE MODULE
2 2 3
2 2 3
2 2 3
2 2 3
2 2 3
2 2 3
NOTES:
1. Heaters are rated at 230 v, 460 v, and 575 v.
2. Terminal boards provided for heater power wire connections are
FLA PER
HEATING ELEMENT
13.0/14.4
17.3/19.2
17.3/19.2
7.2
9.6
9.6
13.0/14.4
17.3/19.2
17.3/19.2
7.2
9.6
9.6
13.0/14.4
17.3/19.2
17.3/19.2
7.2
9.6
9.6
suitable for use with copper or aluminum wire.
MCA
(Each Circuit)
150/166 200/221 150/166
83 111 166
188/207 250/276 188/207
103 138 207
225/249 150/165 225/249
124 166 249
MOCP
(Each Circuit)
175/175 225/225 175/175
90 125 175
200/225 275/300 200/225
110 150 225
250/250 175/175 250/250
125 175 250
12
Table 5 — Unit 50ME Electrical Application Data
UNIT
50ME
Size
016 5
024 7.5
028 10
030 10
034
040
IFM — Indoor (Evaporator) Fan Motor MCA — Minimum Circuit Amps
IFM
Hp
15
20
15
20
LEGEND
NOMINAL VOLTAGE
208/230
460 575 106 39.6 132.5 138.1
208/230
460 575 106 49.2 132.5 141.5
208/230
460 575 132 60.2 165.6 176.1
208/230
460 575 132 67.3 165.6 177.7
208/230
460 575 158 75.6 198.8 214.8
208/230
460 575 158 80.6 198.8 220.1
208/230
460 575 158 95.0 198.8 227.5
208/230
460 575 158 100.0 198.8 232.5
kW
(Unit
Total)
43/ 53 57/ 70 87/106
53 70
106
43/ 53 57/ 70 87/106
53 70
106
54/ 66 72/ 88
108/132
66 88
132
54/ 66 72/ 88
108/132
66 88
132
65/ 79 87/106
129/158
79 106 158
65/ 79 87/106
129/158
79 106 158
65/ 79 87/106
129/158
79 106 158
65/ 79 87/106
129/158
79 106 158
Cooling
109.8/109.8
49.5
138.0/138.0
61.9
168.9
75.8
188.0
84.5
210.8
94.5
224.6
100.5
247.7
116.7
261.5
122.7
MCA
Heating
Circuit
12
150.0/165.6
200.0/220.9
150.0/165.8
82.9
110.5
165.8
150.0/160.6
200.0/220.9
150.0/165.8
82.9
110.5
165.8
188.0/207.1
250.0/276.1
188.0/207.1
102.8
138.0
207.1
188.0/207.1
250.0/276.1
188.0/207.1
102.8
138.0
207.1
225.0/248.5
150.0/165.6
225.0/248.5
124.3
165.1
248.5
225.0/248.5
150.0/165.1
225.0/248.5
124.3
165.6
248.5
225.0/248.5
150.0/165.1
225.0/248.5
124.3
165.6
248.5
225.0/248.5
150.0/165.1
225.0/248.5
124.3
165.6
248.5
— —
150.0/165.8 —
— —
150.0/165.8 —
— —
188.0/207.1 —
— —
188.0/207.1 —
150.0/165.1
225.0/248.5 —
150.0/165.1
225.0/248.5 —
150.0/165.1
225.0/248.5 —
150.0/165.1
225.0/248.5 —
Unit
Common
Feed
184.8/192.6
216.7/237.6
316.7/348.3
90.9
117.1
172.4
213.0/220.8
238.0/248.5
342.2/359.0
103.4
121.5
176.8
262.9/272.5
293.9/307.0
419.6/445.0
127.2
151.0
220.1
282.0/291.6
313.0/326.0
438.7/464.0
135.9
153.5
222.6
323.3/335.1
360.8/376.4
510.9/543.2
156.7
185.4
268.3
337.1/348.9
374.6/391.2
524.6/558.0
162.7
192.2
275.1
360.2/372.0
397.7/412.8
547.7/579.0
178.9
199.5
282.4
374.0/385.8
411.5/426.6
561.5/592.8
148.9
205.5
288.4
13
Field Control Wiring
ZONE THERMOSTATS — Install a Carrier approved ac­cessory zone thermostat assembly in each zone according to installation instructions included in the accessory.Locate each thermostat assembly in the space where it will sense average zone temperature.
Route thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire from thermo­stat subbase terminals through opening on base unit (Fig. 1, 2, 4, and 5) to low-voltage thermostat connections on zone control board (Fig. 10). Use no. 16 AWG wire for lengths exceeding 50 ft.
ZONE MODULE CONNECTIONS — Any module may be controlled independently or jointly with another module or modules. Modules are combined into nests that form indi­vidual Class II circuits (40 va) as follows:
Modules no. 1 and 2, 3 and 4, 5 and 6, 7 and 8, 9 and 10 (028-040 units), 11 and 12 (034,040 units).
The control signal can be transferred from one nest to another nest by using factory-supplied jumpers on
quick-connect type multiplexing terminals. This prevents over­loading the nest control transformers. Factory-supplied jump­ers with quick-connect terminals are shipped in the zone con­trol and thermostat panel compartment.
Under no circumstances shall the transformer power from
one Class II circuit be interconnected with any other circuit.
Thermostat heat anticipator settings are indicated for each permitted zone module connection arrangement illustrated in Fig. 11-28.
To Join Modules of the Same Nest Into the Same Zone (i.e., modules no. 1 and 2) — Install field-supplied jumpers on thermostat connections (screw terminals) Y to Y and W2 to W2 as shown in Fig. 11. Connect thermostat wires to ter­minal connections of first module in zone (for consistency). Two-stage cooling may be obtained in this example as shown in Fig. 12 (using a 2-stage thermostat).
To Join Modules Not of the Same Nest Into the Same Zone (i.e., modules no. 2 and 3) — Install the factory-supplied jump­ers on quick-connect terminals 6 to 1, 7 to 2, and 8 to 3 as shown in Fig. 13. Note that module no. 1 is independently controlled by its own thermostat (in Fig. 13).
LEGEND
AFS Airflow Switch CR Control Relay ECR Economizer Relay ECT Economizer Outdoor-Air Thermostat GV Gas Valve (not used on 50ME units) HC Heater Contactor HR Heater Relay IFC Indoor (Evaporator) Fan Contactor LLS Liquid Line Solenoid MC Master Cooling MCR — Master Cooling Relay MH Master Heating MHR — Master Heating Relay MU Master Unit MUR — Master Unit Relay NC Normally Closed NO Normally Open NS Night Setback SW Switch TRAN — Transformer
Quick-Connect Type Terminals (for multiplexing) Screw-Type Terminals
NOTE: Twelve-zone unit shown. Eight-zone units have modules 1-8 only. Ten-zone units have modules 1-10 only.
Fig. 10 — Zone Control Board Component Location
14
Fig. 10 — Zone Control Board Component Location (cont)
15
Loading...
+ 33 hidden pages