• EVAPORATOR COILS (ZONE COOLING COILS)
AND GLYCOL HEATING COILS
• CONDENSER AND OUTDOOR-AIR COOLING
COILS
• CONDENSATE DRAINS
• INDOOR-AIR FILTERS
• OUTDOOR-AIR INLET SCREENS
• GAS HEATING SECTION
• COMBUSTION AIR FAN
Airflow Switches ............................39
• INDOOR AIRFLOW SWITCH (AFS1)
• COMBUSTION AIRFLOW SWITCH (AFS2)
Service Switch ..............................39
Time GuardT Control Circuit .................39
Capacity Control Pressure Switches (CCP)
(2-Compressor Units Only) ................39
Compressor Oil .............................39
• TO ADD OR REMOVE OIL
Compressor Capacity Control Unloader(s) ....40
• CONTROL SET POINT
• PRESSURE DIFFERENTIAL
Crankcase Heater(s) .........................40
Refrigerant Charge ..........................40
• NO CHARGE
• LOW CHARGE
Head Pressure Control ......................40
• MOTORMASTERt HEAD PRESSURE CONTROL
DEVICE
• FAN CYCLING PRESSURESTAT
Condenser Fans ............................41
• ADJUSTMENT
• FAN MOTOR REMOVAL
• LUBRICATION
Evaporator Fans and Motor ..................41
• MOTOR REMOVAL
• FAN SHAFT BEARING REMOVAL
• FAN SPEED ADJUSTMENT
• PULLEY REMOVAL
• PULLEY ALIGNMENT
• BELT TENSION ADJUSTMENT
• LUBRICATION
Forced-Draft Blower (48MA) .................42
• LUBRICATION
• AIR SHUTTER ADJUSTMENT
Zone Module Transformers ..................42
Optional Economizer ........................42
• THERMOSTAT SETTINGS
• DAMPER POSITION
• OPERATION
Optional Exhaust Damper ...................42
Replacement Parts ..........................42
START-UP CHECKLIST .....................CL-1
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1
Tab 1c 1d
PC 111Catalog No. 564-840Printed in U.S.A.Form 48MA/50ME-3SIPg 14-96Replaces: 48MA/50ME-1SI
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached
to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American
National Standards Institute) Z223.1. Wear safety glasses and
work gloves. Use quenching cloth for unbrazing operations.
Have fire extinguisher available for all brazing operations.
INSTALLATION
General —
stall unit, electrical wiring, gas supply line (48MA) and condensate drain lines in accordance with all applicable codes.
Install unit on rooftop, outdoor site only. In-
Unit Clearances — See Fig. 1 and 2 for service and
airflow clearances. For 48MA gas-fired units, provide not
less than 36-in. clearance to combustibles from top and all
sides. Keep burner end free from any obstruction.
Locate exit terminals of mechanical draft system (48MA
flue outlet) as follows:
• Not less than 12 in. from any opening through which combustion products could enter the building.
• Not less than 2 ft from any adjacent building.
• Not less than 7 ft above grade when unit is adjacent to
public walkways.
Before performing service or maintenance operations on
unit, turn offmain power switch to unit. Electrical shock
could cause personal injury.
Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department.
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of the 48MA unit or any other
gas-fired appliance.
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency, or
the gas supplier.
Disconnect gas piping from 48MA unit when leak testing at pressures greater than 0.5 psig. Pressures greater
than 0.5 psig will cause gas valve damage resulting in
a hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced. When
pressure testing field-supplied gas piping at pressures of
0.5 psig or less, the unit connected to such piping must
be isolated by manually closing the gas valve.
RoofCurb — Assemble and install per instructions shipped
with this accessory. Information required to field fabricate a
roof curb and other curb data are shown in Fig. 3-5.
Install field-supplied insulation, cant strips, roofing and
counter flashing as required. Seal all curb joints with mastic
or other suitable roof cement to keep out moisture. Be sure
that run-offpan at compressor end of curb is completely flashed
and sealed.
Seal strip (Fig. 3) is shipped with accessory roof curb. Install as described in the roof curb installation instructions.
The seal strip compresses under unit weight so that an airtight seal and vibration isolation are provided between unit
base and curb.
Roof Openings — Except for the compressor and con-
denser section, roof area under the unit need not be filled in
as the curb-mounted unit encloses this space. Leaving this
roof section open provides ample clearance for ductwork,
piping, and power and control wiring.
If the roof area inside curb is to be filled in so that roof
deck and bottom of base unit can be used as a return-air plenum, any spaces under the curb flanges caused by corrugated roofing or roof irregularities must be sealed to prevent
water seepage. If spaces are not sealed, the negative pressure of return air may draw water under the unit and into the
building structure.
If openings are cut in a finished roof, provide at least 6-in.
space on each of the longer sides of the supply and return air
openings. Due to interference from the roof curb structure,
this additional clearance may not be possible on the short
sides.
2
CONDENSER SECTION AIRFLOW
CONN — Connection
NOTES:
1. Space required for service and airflow all
around and above unit is 36 inches.
2. For additional information see Fig. 4.
3. Centerof gravity is within 6in. radius of geometric center of unit.
4. Maximum allowable pitch of unit is
10 ft in any direction.
Rigging Unit — Inspect unit for shipping damage, and
file any damage claim immediately with transportation
company.
Lift unit with cables and spreader bars, using lifting brackets provided (Fig. 1 and 2). Lift one unit at a time, keep unit
upright, and do not drop. Unit weights are given in Table 1.
Unit center of gravity is within 6 in. of unit’s geometric center. Eyebolts may be removed after unit is in final position.
IMPORTANT: Do not drill or punch holes in unit frame
or panels; damage to internal components or wiring
may result.
UnitPositioning — When lowering unit onto roof curb,
do not exceed the out-of-symmetry tolerances given in
Fig. 4 and 5. Be sure unit is level or is pitched within specified tolerances. Units have drains on both sides and may be
pitched to either side.
Removing Shipping Shields (Fig. 6)
1. Remove shield over flue outlet grille (48MA only).
2. Remove shields (sheet metal covers) located in the outdoor-
air inlet screen tracks behind the louvers. If the screens
are removed for this procedure, be sure to replace them
before replacing the louvered assembly.
Field-Fabricated Ductwork — Supply- and return-
air openings are shown in Fig. 4 and 5. To simplify supplyair connection, a zone duct plenum may be field fabricated
as shown in Fig. 7. It is recommended that this plenum be
installed prior to unit positioning.
It is recommended that the unit be supported on blocks
temporarily while the duct plenum is installed, rather than
installing the plenum while the unit is suspended. The duct
plenum may be installed once the unit is located in its final
position, but it is much easier to install the plenum prior to
unit final placement.
Zone supply-air duct openings on the base unit have tab
slot connections similar to those shown in Fig. 7 except that
the end partitions are hemmed. Hem is positioned so that the
1-in. flange at entering end of field-fabricated plenum will
force-fit between hem and adjacent unit frame.
Standard flexible duct connections between duct plenum
and duct system may be used. Follow applicable codes.
Insulate any supply-air ducts passing through unconditioned spaces and cover with a vapor barrier. Separate ducts
with insulation if they run parallel for more than 5 ft. This
will prevent heat transfer between zones.
Install a manual balancing damper in each zone duct to
provide the required zone airflow.
The return-air duct connection consists of 4 sheet metal
flanges as shown in Fig. 1, 2, 4, and 5.
5
Table 1 — Physical Data
UNIT 48MA/50ME016024028030034040
Zone Modules (Quantity)8810101212
Nominal Cooling Capacity (tons)152025283037
OPERATING WEIGHT (lb)
Base Unit 48MA339538154075408053405710
Base Unit 50ME (with electric heat)299534153675368049005270
Electric HeatersNichrome, Open-Wire Resistance Element in Each Zone Module
Qty...Elements (each)**8...2 or 38...2 or 310...2 or 310...2 or 312...2 or 312...2 or 3
OPTIONAL HEATING SECTION
(50ME Glycol Coil)
Maximum Allowable Inlet Temperature (F)200
Maximum Allowable Flow, Each Coil (Gpm)6
Solution Mixture20% Glycol
Maximum Allowable Working Pressure (Psig)30
Total Internal Volume (Gal)2.612.613.153.153.763.76
PRESSURE SWITCHES
Low-Pressure (Psig)
High-Pressure (Psig)
Indoor Airflow Switch (AFS1)
Factory Setting (cfm)60009000
Adjustment Range (cfm)4000-60006000-9000
INDOOR AIR FILTERS
Standard Qty...Size (in.)12...20 × 25 × 2
High Efficiency (optional)
Qty...Size (in.)
OUTDOOR AIR FILTERS
Qty...Size (in.)2...20 × 25 × 12...32 × 35 × 1
LEGEND
ESP— External Static Pressure
NEMA — National Electrical Manufacturers Association
*Standard unit shipped with standard motor, pulley, and belt(s); alternate unit shipped with alternate motor, pulley, and belt(s).
†The heating efficiency rating is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system.
**See Field Power Supply Wiring section on page 10 and Table 4 for details.
Total432432540540648648
Each Module545454545454
Total324324405405486486
Each Module40.540.540.540.540.540.5
16
1
⁄
8
100,83,67
50,33,17
1
⁄2...172510...172510...172515...172515...1725
13⁄
16
13⁄
8
100,80,60
40,20
13⁄
16
13⁄
8
100,80,60
40,20
13⁄
16
13⁄
8
100,83,67
50,33,17
111⁄
16
15⁄
8
One Heating Coil in Each Zone Module
Cutout29±5
Cut-in39±5
Cutout400±5
Cut-in300±5
12...20 × 25 × 2 (36.5% Efficient)
100,75,
50,25
111⁄
16
15⁄
8
6
EVAPORATOR (ZONE MODULE) AIRFLOW
CONN — Connection
*Not used on 48MA016,024 (8 zone module units).
NOTES:
1. For additional information, see Table 1 and Fig. 1.
2. Maximum allowable unit pitch is
3. Remove shipping brace before assembling curb section (location
shown).
1
⁄2in. per 10 ft in any direction.
UNIT
48MA
ABCDE F GHJ
016-03018-2
034,04021-97⁄
Fig. 4 — Roof Curb Physical Data and Dimensions; 48MA Units
1
⁄
8
7- 311-95-61⁄
8
7-113⁄
4
14-13⁄
DIMENSIONS (ft-in.)
4
7-27⁄
8
1-109⁄
16
2-29⁄
16
6-03⁄
8
0- 71⁄
4
6-77⁄
16
8-43⁄
16
2- 91⁄
8
3-16-81⁄
2
0-105⁄
2
16
7
(034,044 12-ZONE MODULES)
END DETAIL
EVAPORATOR (ZONE MODULE) AIRFLOW
CONN — Connection
*Not used on 50ME016,024 (8 zone module units).
NOTES:
1. For additional information, see Table 1 and Fig. 2.
2. Maximum allowable unit pitch is
3. Remove shipping brace before assembling curb section (location
shown).
1
⁄2in. per 10 ft in any direction.
UNIT
50ME
ABCDE F GHJ
016-03018-2
034,04021-97⁄
Fig. 5 — Roof Curb Physical Data and Dimensions; 50ME Units
1
⁄
8
7- 311-95-61⁄
8
7-113⁄
4
14-13⁄
DIMENSIONS (ft-in.)
4
7-27⁄
8
1-109⁄
16
2-29⁄
16
6-03⁄
8
0- 71⁄
4
6-77⁄
16
8-43⁄
16
2- 91⁄
8
3-16-81⁄
2
0-105⁄
2
16
8
CondensateDrains — Pipe nipples covered with foam
rubber insulation are shipped in unit return air filter section
(6 nipples in units 48MA, 4 nipples in units 50ME). Install
a nipple in each drain connection on both sides of unit. See
Fig. 1 and 2 for drain locations. Be sure foam rubber seals
space between nipple and base rail opening to prevent rain
leaks.
Connect a drain line to drain connection under outdoor air
inlet grilles on both sides of unit. These drains need not be
trapped.
Install a trapped drain line on remaining connections on
lowest side of unit depending on unit pitch. If unit is level,
a trapped drain may be installed at each connection if desired. Cap or plug unused connections on high side of unit
to prevent airflow between unit interior and outdoors.
OUTDOOR AIR INLET
(ONE ON EACH SIDE OF UNIT)
SHIPPING SHIELD
(BEHIND LOUVERS)
FLUE OUTLET
COVER
(48MA ONLY)
Do not interconnect drains. Make each trap a minimum of
4 in. deep. Insulate trap against freeze-up or use flexible
material.
Gas Piping (48MA) — Unit is equipped for use with
type of gas shown on nameplate. Refer to latest edition of
ANSI Z223.1. Unit main gas connection and alternate gas
connection locations are shown in Fig. 1, 4, and 8. Do not
use gas supply pipe smaller than unit gas connection. Maximum allowable natural gas supply pressure is 10.0 in. wg;
minimum allowable natural gas supply pressure for full rate
input is 5.0 in. wg.
1
Pitch pipe
upward to risers and from risers upward to meter. Install a
dirt and moisture pocket (drip leg) at each section of vertical
pipe run. Use only ground joint unions to ensure leakfree
joints. Use only pipe joint compounds that are resistant to
the action of liquefied petroleum gases.
⁄4in. per 15 ft. Pitch all horizontal pipe runs
Fig. 6 — Shipping Shield Locations
(016-030 Units Shown)
NOTE: Dimension to suit job requirements. Twelve inches will bring
duct plenum to bottom of roof curb.
Fig. 7 — Field-Fabricated Zone Duct Plenum Detail
*Typical; both ends.
9
UNIT
48MA,50ME
A*7
B*75⁄
DIMENSIONS (in.)
016,024028,030034,040
5
⁄
8
8
75⁄
8
73⁄
4
75⁄
53⁄
16
4
*Shutoff valve not used except where required by code.
All units have a main power supply terminal board in the
power and condensing control box. The electric resistance
heater power supply terminal board(s) (if unit is so equipped)
on 50ME units is located in the heater control box at front
of unit. See Fig. 2, 5, and 9.
All terminal boards are suitable for use with copper or
aluminum wire.
Connect electrical conduit (a threaded pipe nipple) shipped
with unit to threaded fitting in roof curb and bottom of main
power and condensing section control box. Route main power
wires through conduit to terminal board in box as shown on
unit label wiring diagram and in Fig. 9.
When installing 48MA,50ME040 units with optional 20-hp
motor,the electrical conduit interconnecting the curb and control box power wire openings will not accommodate aluminum wire of the size that may be required. If aluminum wire
cannot be accommodated, an external transition box and short
lengths of no. 300 kcmil, 75 C copper wire from the transition box to the unit main power connection are
recommended.
Voltage to compressor terminals during compressor operation must be within voltage range indicated on unit nameplate. Phases must be balanced within 2%.
Properly cap any gas connection not being used.
Fig. 8 — Suggested Gas Piping (48MA)
Unit has factory-installed gas shutoff valves. Install gas
shutoff valve external to unit if required by code (Fig. 8).
After piping is complete, pressurize gas line and check for
leaks with soap and water solution.
Do not use an open flame when checking for gas leaks.
OptionalGlycol Connections (50ME) — Each zone
module has its own glycol heating coil and 115-v solenoid
valve. Heating coils are connected in parallel to common supply and return manifolds. Supply manifolds are equipped with
bleed cocks. Supply and return connections are shown in
Fig. 2 and 5. Unit does not have internal pressure relief for
part-load operation. Maximum allowable system working pressure is 30 psig. Unit ratings are based on 20% glycol solu-
tions. Install solution supply apparatus in accordance with
application requirements, and mix glycol solution percentage in accordance with glycol manufacturer’s recommendations. Freeze-up protection is not factory installed.
Field Power Supply Wiring — When installed, unit
must be electrically grounded in accordance with local codes
or,in the absence of local codes, with the National Electrical
Code (NEC).
Unit has a circuit breaker for each compressor, each fan
motor, and for each 50ME electric resistance heater assembly (if unit is so equipped). If required by local code, provide an additional disconnect switch in accordance with code
being followed.
LEGEND
EQUIP — Equipment
GND— Ground
TB— Terminal Board
*208/230 v units only.
Fig. 9 — Field Power Supply Details
10
Use the following formula to determine the percent volt-
age imbalance.
% Voltage Imbalance:
= 100 ×
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452=5v
(BC) 464 − 457=7v
(AC) 457 − 455=2v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below
the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact your local electric utility company immediately.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may
cause damage to electrical components. See Tables 2-5 for
unit, electric heater, and 50ME electrical application electrical data.
Each 50ME electric heat unit is fitted with a heating lockout circuit (if equipped with optional heat). If any zone module is operating on mechanical cooling (compressor is operating), the heating element in each zone module is locked
out and cannot be energized.
On 50ME units, cooling power supply wires and electric
heater power supply wires (if applicable) must be sized according to the cooling MCA (Minimum Circuit Amps) values and heating MCA values shown on unit nameplate and
in Tables 3-5. These wires may be powered by a common
power supply (i.e., a pull-box junction), if desired. The common power supply wires from the main power source to the
junction must be sized according to the common MCA values shown in Table 5.
UNIT COMMON FEED MINIMUM CIRCUIT AMPS —
The unit common feed MCA is calculated on the basis of
either: the sum of the cooling MCA plus
1
⁄2heating MCA on
units with 2 heating elements per zone module (or2⁄3heating MCA on units with 3 heating elements per zone module)
or the sum of the evaporator fan motor full load amps, per
NEC, plus the full heating MCA, whichever is larger. Field
wiring must conform to NEC limitations for Type T wire.
UNIT
48MA
016
024
028
030
034
040
COMP — Compressor
FLA— Full Load Amps
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
FLA— Full Load Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
208/230
460
57510637.7133150
208/230
460
57513237.7166175
208/230
460
57515837.7199200
LEGEND
ELECTRIC
HEAT kW
(Unit Total)
43/ 53
57/ 70
87/106
53
70
106
54/ 66
72/ 88
108/132
66
88
132
65/ 79
87/106
129/158
79
106
158
Table 4 — Electric Resistance Heater Data
HEATING ELEMENTS
PER ZONE MODULE
2
2
3
2
2
3
2
2
3
2
2
3
2
2
3
2
2
3
NOTES:
1. Heaters are rated at 230 v, 460 v, and 575 v.
2. Terminal boards provided for heater power wire connections are
FLA PER
HEATING ELEMENT
13.0/14.4
17.3/19.2
17.3/19.2
7.2
9.6
9.6
13.0/14.4
17.3/19.2
17.3/19.2
7.2
9.6
9.6
13.0/14.4
17.3/19.2
17.3/19.2
7.2
9.6
9.6
suitable for use with copper or aluminum wire.
MCA
(Each Circuit)
150/166
200/221
150/166
83
111
166
188/207
250/276
188/207
103
138
207
225/249
150/165
225/249
124
166
249
MOCP
(Each Circuit)
175/175
225/225
175/175
90
125
175
200/225
275/300
200/225
110
150
225
250/250
175/175
250/250
125
175
250
12
Table 5 — Unit 50ME Electrical Application Data
UNIT
50ME
Size
0165
0247.5
02810
03010
034
040
IFM — Indoor (Evaporator) Fan Motor
MCA — Minimum Circuit Amps
IFM
Hp
15
20
15
20
LEGEND
NOMINAL
VOLTAGE
208/230
460
57510639.6132.5—138.1
208/230
460
57510649.2132.5—141.5
208/230
460
57513260.2165.6—176.1
208/230
460
57513267.3165.6—177.7
208/230
460
57515875.6198.8—214.8
208/230
460
57515880.6198.8—220.1
208/230
460
57515895.0198.8—227.5
208/230
460
575158100.0198.8—232.5
kW
(Unit
Total)
43/ 53
57/ 70
87/106
53
70
106
43/ 53
57/ 70
87/106
53
70
106
54/ 66
72/ 88
108/132
66
88
132
54/ 66
72/ 88
108/132
66
88
132
65/ 79
87/106
129/158
79
106
158
65/ 79
87/106
129/158
79
106
158
65/ 79
87/106
129/158
79
106
158
65/ 79
87/106
129/158
79
106
158
Cooling
109.8/109.8
49.5
138.0/138.0
61.9
168.9
75.8
188.0
84.5
210.8
94.5
224.6
100.5
247.7
116.7
261.5
122.7
MCA
Heating
Circuit
12
150.0/165.6
200.0/220.9
150.0/165.8
82.9
110.5
165.8
150.0/160.6
200.0/220.9
150.0/165.8
82.9
110.5
165.8
188.0/207.1
250.0/276.1
188.0/207.1
102.8
138.0
207.1
188.0/207.1
250.0/276.1
188.0/207.1
102.8
138.0
207.1
225.0/248.5
150.0/165.6
225.0/248.5
124.3
165.1
248.5
225.0/248.5
150.0/165.1
225.0/248.5
124.3
165.6
248.5
225.0/248.5
150.0/165.1
225.0/248.5
124.3
165.6
248.5
225.0/248.5
150.0/165.1
225.0/248.5
124.3
165.6
248.5
—
—
150.0/165.8
—
—
—
150.0/165.8
—
—
—
188.0/207.1
—
—
—
188.0/207.1
—
—
150.0/165.1
225.0/248.5
—
—
150.0/165.1
225.0/248.5
—
—
150.0/165.1
225.0/248.5
—
—
150.0/165.1
225.0/248.5
—
Unit
Common
Feed
184.8/192.6
216.7/237.6
316.7/348.3
90.9
117.1
172.4
213.0/220.8
238.0/248.5
342.2/359.0
103.4
121.5
176.8
262.9/272.5
293.9/307.0
419.6/445.0
127.2
151.0
220.1
282.0/291.6
313.0/326.0
438.7/464.0
135.9
153.5
222.6
323.3/335.1
360.8/376.4
510.9/543.2
156.7
185.4
268.3
337.1/348.9
374.6/391.2
524.6/558.0
162.7
192.2
275.1
360.2/372.0
397.7/412.8
547.7/579.0
178.9
199.5
282.4
374.0/385.8
411.5/426.6
561.5/592.8
148.9
205.5
288.4
13
Field Control Wiring
ZONE THERMOSTATS — Install a Carrier approved accessory zone thermostat assembly in each zone according to
installation instructions included in the accessory.Locate each
thermostat assembly in the space where it will sense average
zone temperature.
Route thermostat cable or equivalent single leads of no.
18 AWG (American Wire Gage) colored wire from thermostat subbase terminals through opening on base unit
(Fig. 1, 2, 4, and 5) to low-voltage thermostat connections
on zone control board (Fig. 10). Use no. 16 AWG wire for
lengths exceeding 50 ft.
ZONE MODULE CONNECTIONS — Any module may be
controlled independently or jointly with another module or
modules. Modules are combined into nests that form individual Class II circuits (40 va) as follows:
Modules no. 1 and 2, 3 and 4, 5 and 6, 7 and 8, 9 and 10
(028-040 units), 11 and 12 (034,040 units).
The control signal can be transferred from one nest
to another nest by using factory-supplied jumpers on
quick-connect type multiplexing terminals. This prevents overloading the nest control transformers. Factory-supplied jumpers with quick-connect terminals are shipped in the zone control and thermostat panel compartment.
Under no circumstances shall the transformer power from
one Class II circuit be interconnected with any other circuit.
Thermostat heat anticipator settings are indicated for each
permitted zone module connection arrangement illustrated
in Fig. 11-28.
To Join Modules of the Same Nest Into the Same Zone (i.e.,
modules no. 1 and 2) — Install field-supplied jumpers on
thermostat connections (screw terminals) Y to Y and W2 to
W2 as shown in Fig. 11. Connect thermostat wires to terminal connections of first module in zone (for consistency).
Two-stage cooling may be obtained in this example as shown
in Fig. 12 (using a 2-stage thermostat).
To Join Modules Not of the Same Nest Into the Same Zone
(i.e., modules no. 2 and 3) — Install the factory-supplied jumpers on quick-connect terminals 6 to 1, 7 to 2, and 8 to 3 as
shown in Fig. 13. Note that module no. 1 is independently
controlled by its own thermostat (in Fig. 13).
LEGEND
AFS— Airflow Switch
CR— Control Relay
ECR— Economizer Relay
ECT— Economizer Outdoor-Air Thermostat
GV— Gas Valve (not used on 50ME units)
HC— Heater Contactor
HR— Heater Relay
IFC— Indoor (Evaporator) Fan Contactor
LLS— Liquid Line Solenoid
MC— Master Cooling
MCR — Master Cooling Relay
MH— Master Heating
MHR — Master Heating Relay
MU— Master Unit
MUR — Master Unit Relay
NC— Normally Closed
NO— Normally Open
NS— Night Setback
SW— Switch
TRAN — Transformer
Quick-Connect Type Terminals (for multiplexing)
Screw-Type Terminals
NOTE: Twelve-zone unit shown. Eight-zone units have modules
1-8 only. Ten-zone units have modules 1-10 only.
Fig. 10 — Zone Control Board Component Location
14
Fig. 10 — Zone Control Board Component Location (cont)
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.