Carrier 48EJ, 48EW User Manual

48AJ,AK,AW,AY020-060
with Reciprocating Compressor
48EJ,EK,EW,EY024-068
Single Package Rooftop Units
Electric Cooling/Gas Heating
Installation, Start-Up and
Service Instructions
CONTENTS
Page
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-58
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
• ROOF CURB
• ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
• POSITIONING
• ROOF MOUNT
Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 2
Step 4 — Make Unit Duct Connections . . . . . . . . . . . 2
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . 28
Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . . . 28
Step 7 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . 28
Step 8 — Controls Options. . . . . . . . . . . . . . . . . . . . . . 29
• STAGED GAS UNIT APPLICATIONS
• THERMISTORS
• CONSTANT VOLUME APPLICATIONS
• VARIABLE AIR VOLUME (VAV) APPLICATIONS
Step 9 — Make Electrical Connections . . . . . . . . . . 33
•POWER WIRING
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 10 — Make Outdoor-Air Inlet
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
• ECONOMIZER
• ECONOMIZER SETTINGS
Step 11 — Position Power Exhaust/Barometric
Relief Damper Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Step 12 — Install All Accessories . . . . . . . . . . . . . . . 54
Step 13 — Field Modifications. . . . . . . . . . . . . . . . . . . 57
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58-89
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89-102
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . 103-115
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . CL-1,CL-2
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should in­stall, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh­bor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire department.
Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
INSTALLATION
Step 1 — Provide Unit Support
1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Ta b 1 a
PC 111 Catalog No. 534-739 Printed in U.S.A. Form 48A,E-1SI Pg 1 107 11-01 Replaces: 48E-6SI
ROOF CURB — For vertical discharge units, assemble or in­stall accessory roof curb in accordance with instructions shipped with this accessory. See Fig. 1-4. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb should be level. This is necessary to permit unit drain to func­tion properly. Unit leveling tolerance is shown in Fig. 1-3. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1-3. Improperly applied gasket can also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When the preferred curb or slab mount cannot be used, support unit with sleepers on pe­rimeter, using unit curb support area. If sleepers cannot be used, support long sides of unit (refer to Fig. 5-16) with a mini­mum number of 4-in. x 4-in. pads spaced as follows: 48AJ,AK,AW,AY020-030 and 48EJ,EK,EW,EY024-034 units require 3 pads on each side; 48AJ,AK,AW,AY035-050 and 48EJ,EK,EW,EY038-048 units require 4 pads on each side; 48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068 units re­quire 6 pads on each side. Unit may sag if supported by corners only.
Step 2 — Rig and Place Unit — Inspect unit for
transportation damage. See Tables 1A and 1B for physical data. File any claim with transportation agency.
Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Level by using unit frame as a reference; leveling tolerance is shown in Fig. 1-3. See Fig. 17 for additional information. Unit operating weight is shown in Table 2.
NOTE: On retrofit jobs, ductwork may be attached to old unit instead of roof curb. Be careful not to damage ductwork when removing old unit. Attach existing ductwork to roof curb instead of unit.
Four lifting lugs are provided on the unit base rails as shown in Fig. 5-16. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 5-16, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and venti­lation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the building, and at least 4 ft from any adjacent building.
When unit is located adjacent to public walkways, flue assem­bly must be at least 7 ft above grade.
ROOF MOUNT — Check building codes for weight distribu­tion requirements. See Fig. 17. Unit operating weight is shown in Table 2.
Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors be­tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
NOTE: Due to width of the horizontal supply/return ductwork, provisions should be made for servicing of the outdoor air fil­ters (i.e., catwalk over ductwork).
Ducts passing through an unconditioned space must be in­sulated and covered with a vapor barrier. Outlet grilles must not lie directly below unit discharge. The return duct must have a 90-degree elbow before opening into the building space if the unit is equipped with power exhaust.
To attach ductwork to roof curb, insert duct approximately 10 to 11 in. up into roof curb. Connect ductwork to 14-gage roof curb material with sheet metal screws driven from inside the duct.
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree elbow turn in the supply and return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space.
Step 4 — Make Unit Duct Connections
48AJ,AK,EJ,EK UNITS — Unit is shipped for through-the­bottom duct connections. Field-fabricated ductwork should be attached to the roof curb. Supply and return duct dimensions are shown in Fig. 5-7 and 11-13. Air distribution is shown in Fig. 18 and 19. Refer to installation instructions shipped with roof curb for more information.
48AW,AY,EW,EY UNITS — Remove shipping covers from supply and return air openings. Attach field-supplied ductwork to unit. Connect to the unit with a single duct for all supply openings and with a single duct for all return openings. Split­ting of the airflow into branch ducts should not be done at the unit. Sufficient duct length should be used prior to branching to ensure the air temperatures are well mixed within the duct­work. See Fig. 8-10 and 14-16 for duct opening dimensions. Secure all ducts to building structure. Air distribution is shown in Fig. 8-10 and 14-16.
Install accessory barometric relief or power exhaust in the field-fabricated return ductwork. Refer to Step 11 — Position Power Exhaust/Barometric Relief Damper Hood section on page 52 for more information.
Instructions continued on page 28.
2
Fig. 1 — Roof Curb — 48AJ,AK020-030 and 48EJ,EK024-034 Units
3
Fig. 2 — Roof Curb — 48AJ,AK034-050 and 48EJ,EK038-048 Units
4
Fig. 3 — Roof Curb — 48AJ,AK060 and 48EJ,EK054-068 Units
5
NOTES:
1. Unless otherwise specified, all dimensions are to outside of part.
2. Seal strip to be placed covering reference holes.
3. Phantom lines represent seal strip. Total length required is 75 linear ft.
length required is 62 linear ft.
self-tapping screws.
2.98 at indoor motor end and 15.08 at compressor end.
4. If existing seal strip around roof curb seems damaged, replace it. Total
5. Five crossrails are field located per dimensions shown and secured using
6. 48A and 48E series units will overhang existing “DD” or “DF” roof curbs by
7. Ductwork (field supplied) must be notched to clear three crossrails.
Fig. 4 — Roof Curb Adapter — (48AJ,AK060 and 48EJ,EK054-068 Units on 48DD,DF054-064 Retrofit, Part No. CRRCADPT005A00)
8. Dimensions in [ ] are millimeters.
6
1234
CORNER WEIGHT (lbs)
1082 1174 1502 1384
1126 1194 1494 1408
1135 1120 1516 1537
16
/
16
16
/
/
3
11
B
(ft-in.)
A
(ft-in.)
5
3-6
3-6
3-8 1103 1103 1511 1511
3-8
3-8 1123 1123 1539 1539
8
16
8
32
/
3
8
/
/
/
/
5
5
3
5
1234
1156 1140 1544 1565
16
/
5
3-8
32
/
3
5
CORNER WEIGHT (kg)
1156 1140 1544 1565
16
/
5
3-8 1123 1123 1539 1539
3-8
8
32
/
/
3
A (mm) B (mm)
(lbs)
WEIGHT*
OPERATING
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AJ (High Heat) 020 5222 6- 1
48AJ (High Heat) 025 5308 5-10
48AJ (High Heat) 027 5405 5-10
48AJ/AK (Low Heat) 020 5142 6- 0
48AJ/AK (Low Heat) 025 5228 5- 9
48AJ (High Heat) 030 5405 5-10
48AJ/AK (Low Heat) 027 5325 5- 9
48AJ/AK (Low Heat) 030 5325 5- 9
48AJ (High Heat) 020 2369 1862 1085 511 542 678 639
48AJ (High Heat) 025 2408 1781 1125 515 508 688 697
48AJ (High Heat) 027 2452 1781 1125 524 517 700 710
48AJ/AK (Low Heat) 020 2332 1839 1072 491 533 681 628
48AJ/AK (Low Heat) 025 2371 1768 1118 500 500 686 686
48AJ (High Heat) 030 2452 1781 1125 524 517 700 710
48AJ/AK (Low Heat) 027 2415 1768 1118 509 509 698 698
48AJ/AK (Low Heat) 030 2415 1768 1118 509 509 698 698
Fig. 5 — Base Unit Dimensions — 48AJ,AK020-030
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
NOTES:
1. Weights include economizer (standard).
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be sup-
ported by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
6. Dimensions are in inches [mm].
7
1234
1380 1209 1595 1820
1447 1251 1607 1859
(ft-in.)
(ft-in.)
1442 1264 1779 2030
8
16
8
/
/
/
7
3
7
3-10
3-11
3-10
8
16
/
/
16
1
/
11
5
CORNER WEIGHT (lbs)
B
A
123 4
1512 1307 1787 2068
16
/
3
1
3-11
16
/
13
11
CORNER WEIGHT (kg)
1449 1294 1878 2104
1519 1337 1886 2142
16
/
2
/
13
3-10
3-10
16
/
16
/
3
A (mm) B (mm)
OPERATING
(lbs)
WEIGHT*
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AJ (High Heat) 035 6164 7-10
48AJ (High Heat) 040 6674 7-6
48AJ/AK (Low Heat) 035 6004 7-8
48AJ (High Heat) 050 6885 7-5
48AJ/AK (Low Heat) 040 6514 7-5
48AJ/AK (Low Heat) 050 6725 7-3
48AJ (High Heat) 035 2796 2390 1199 656 567 729 843
48AJ (High Heat) 040 3027 2306 1199 686 593 811 938
48AJ/AK (Low Heat) 035 2723 2355 1191 626 548 723 826
48AJ (High Heat) 050 3123 2266 1189 689 607 856 972
48AJ/AK (Low Heat) 040 2955 2268 1191 654 573 807 921
48AJ/AK (Low Heat) 050 3050 2228 1181 657 587 852 954
NOTES:
Fig. 6 — Base Unit Dimensions — 48AJ,AK035-050
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be supported
by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
6. Dimensions are in inches [mm].
8
BASE UNIT WEIGHTS
(See Note 6) lbs (kg)
AT EACH CORNER
% OF TOTAL WEIGHT
3242 1184 21.7 19.3 27.7 31.2
3422 1235 23.9 19.4 25.4 31.3
32
/
19
32
/
19
3-10
060
48AJD/AKD 8930 (4051)
ft-in. Millimeters
CENTER OF GRAVITY
48AJE 9170 (4159)
UNIT SIZE
16
/
11
A B A B1234
48AJD/AKD060 10-7
4-
16
/
11
48AJE060 11-2
Fig. 7 — Base Unit Dimensions — 48AJ,AK060
on dunnage, it is recommended the ducts must be supported by cross braces as
done on accessory roof curb.
included). Add indoor motor, FIOPs and accessories for total operating weight.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted
NOTES:
1. Weights include economizer (standard).
VFD transducer and associated wiring.
6. Base unit weights include outdoor air hoods and filters (indoor fan motor is not
7. VAV motor weights include indoor motor, VFD, compressor electric unloaders,
8. Dimensions are in inches [mm].
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Filter Access Side: 15′-0″ [4572]. (For
charge facing economizer inlet.
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue dis-
removal of evaporator coil.)
ances contact Carrier Application Engineer-
ing Department.
4. For smaller service and operational clear-
9
1234
CORNER WEIGHT (lbs)
1090 1183 1514 1395
1134 1203 1505 1419
1144 1128 1527 1548
16
/
16
16
/
/
3
11
B
(ft-in.)
A
(ft-in.)
5
3-6
3-6
3-8 1111 1111 1523 1523
3-8
8
16
8
8
/
/
/
/
3
5
5
1
1234
1165 1149 1555 1577
16
/
5
3-8 1132 1132 1551 1551
3-8
8
8
/
/
5
1
5
CORNER WEIGHT (kg)
1165 1149 1555 1577
16
/
5
3-8 1132 1132 1551 1551
3-8
8
8
/
/
1
A (mm) B (mm)
OPERATING
(lbs)
WEIGHT*
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AW (High Heat) 020 5262 6- 1
48AW (High Heat) 025 5348 5-10
48AW (High Heat) 027 5445 5-10
48AW/AY (Low Heat) 020 5182 6- 0
48AW/AY (Low Heat) 025 5268 5- 9
48AW (High Heat) 030 5445 5-10
48AW/AY (Low Heat) 027 5365 5- 9
48AW/AY (Low Heat) 030 5365 5- 9
48AW (High Heat) 020 2387 1862 1085 515 546 683 644
48AW (High Heat) 025 2426 1781 1125 519 512 693 702
48AW (High Heat) 027 2470 1781 1125 528 521 705 715
48AW/AY (Low Heat) 020 2351 1839 1072 495 537 687 633
48AW/AY (Low Heat) 025 2390 1768 1118 504 504 691 691
48AW (High Heat) 030 2470 1781 1125 528 521 705 715
48AW/AY (Low Heat) 027 2434 1768 1118 513 513 704 704
48AW/AY (Low Heat) 030 2434 1768 1118 513 513 704 704
NOTES:
Fig. 8 — Base Unit Dimensions — 48AW,AY020-030
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
Application Engineering Department.
4. For smaller service and operational clearances contact Carrier
5. Dimensions are in inches [mm].
10
CORNER WEIGHT (lbs)
1234
1389 1217 1606 1832
1456 1259 1617 1871
1451 1271 1790 2042
1521 1315 1798 2080
1458 1301 1889 2117
1528 1345 1897 2155
16
8
16
/
/
B
7
3
(ft-in.)
3-10
3-11
16
/
8
/
11
1
A
(ft-in.)
/
8
16
2
/
/
/
7
3
1
13
3-10
3-11
3-10
3-10
16
16
16
/
/
/
16
/
11
13
11
3
CORNER WEIGHT (kg)
1234
A (mm) B (mm)
OPERATING
(lbs)
WEIGHT*
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AW (High Heat) 035 6204 7-10
48AW (High Heat) 040 6714 7- 6
48AW/AY (Low Heat) 035 6044 7- 8
48AW (High Heat) 050 6925 7- 5
48AW/AY (Low Heat) 040 6554 7- 3
48AW/AY (Low Heat) 050 6765 7- 3
48AW (High Heat) 035 2814 2390 1199 661 571 734 849
48AW (High Heat) 040 3045 2306 1199 690 596 816 944
48AW/AY (Low Heat) 035 2741 2355 1191 630 552 728 831
48AW (High Heat) 050 3141 2266 1189 693 610 860 977
48AW/AY (Low Heat) 040 2973 2268 1191 658 577 812 926
48AW/AY (Low Heat) 050 3069 2228 1181 661 590 857 960
NOTES:
Fig. 9 — Base Unit Dimensions — 48AW,AY035-050
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Min Clearances to be:
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet.
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
4. For smaller service and operational clearances contact Carrier Application Engineering Department.
5. Dimensions are in inches [mm].
11
% OF TOTAL WEIGHT
060
(See Note 6) lbs (kg)
BASE UNIT WEIGHTS
CENTER OF GRAVITY
48AWE 9210 (4178)
48AWD/AYD 8970 (4069)
AT EACH CORNER
19
ft-in. Millimeters
11
A B AB1234
UNIT SIZE
3242 1184 21.7 19.3 27.7 31.2
32
/
3-10
16
/
48AWD/AYD060 10-7
3422 1235 23.9 19.4 25.4 31.3
32
/
19
4-
16
/
11
48AWE060 11-2
included). Add indoor motor, FIOPs and accessories for total operating weight.
5. Base unit weights include outdoor air hoods and filters (indoor fan motor is not
NOTES:
1. Weights include economizer (standard).
transducer and associated wiring.
6. VAV motor weights include indoor motor, VFD, compressor electric unloaders, VFD
2. Center of Gravity.
7. Dimensions are in inches [mm].
8. For side-supply/return applications, a single return and supply ductwork connection
charge facing economizer inlet.
3. Do not locate adjacent units with flue dis-
is recommended for covering all three return and all three supply openings. The
entire area around the duct openings is available for a 1.5 duct flange attachment.
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Min Clearances to be:
Fig. 10 — Base Unit Dimensions — 48W,AY060
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Filter Access Side: 15-0 [4572]. (For
removal of evaporator coil.)
ances contact Carrier Application Engineer-
ing Department.
4. For smaller service and operational clear-
12
NOTES:
Fig. 11 — Base Unit Dimensions — 48EJ,EK024-034
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be supported
by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
6. Dimensions are in inches [mm].
13
NOTES:
Fig. 12 — Base Unit Dimensions — 48EJ,EK038-048
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be supported
by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
6. Dimensions are in inches [mm].
14
AT EACH CORNER
% OF TOTAL WEIGHT
CENTER OF GRAVITY
Inches Millimeters
UNIT SIZE
ABAB1234
48EJD/EKD054 130.9 46.9 3325 1192 22.4 19.6 27.0 30.9
48EJE054 133.8 47.4 3397 1204 23.1 19.8 26.3 30.7
48EJE058 139.5 49.6 3544 1260 25.3 19.6 24.1 31.1
48EJE064 132.2 47.2 3359 1199 22.8 19.7 26.7 30.8
48EJD/EKD058 132.1 47.5 3354 1207 22.9 19.5 26.5 31.1
48EJE068 134.7 48.6 3422 1235 23.9 19.4 25.4 31.3
48EJD/EKD064 125.3 45.2 3181 1149 20.7 19.6 29.1 30.7
48EJD/EKD068 127.7 46.6 3242 1184 21.7 19.3 27.7 31.2
BASE UNIT WEIGHTS
(See Note 6) lbs (kg)
054 058 064 068
48EJE 7045 (3196) 7295 (3309) 7545 (3422) 7720 (3502)
48EJD/EKD 6805 (3087) 7055 (3200) 7305 (3314) 7480 (3393)
Fig. 13 — Base Unit Dimensions — 48EJ,EK054-068
Filter Access Side: 15′-0″ [4572]. (For removal of evaporator
Adjacent Units: 15′-0″ [4572].
mizer inlet.
NOTES:
1. Weights include economizer (standard).
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing econo-
coil.)
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Application Engineering Department.
unit is mounted on dunnage, it is recommended the ducts must
be supported by cross braces as done on accessory roof curb.
fan motor is not included). Add indoor motor, FIOPs and acces-
sories for total operating weight.
4. For smaller service and operational clearances contact Carrier
5. Bottom ducts designed to be attached to accessory roof curb. If
electric unloaders, VFD transducer and associated wiring.
6. Base unit weights include outdoor air hoods and filters (indoor
7. VAV motor weights include indoor motor, VFD, compressor
8. Dimensions in are in inches [mm].
15
Fig. 14 — Base Unit Dimensions — 48EW,EY024-034
Filter Access Side: 15′-0″ [4572]. (For removal of evaporator
Adjacent Units: 15′-0″ [4572].
Min Clearances to be:
NOTES:
mizer inlet.
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing econo-
coil.)
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Application Engineering Department.
4. For smaller service and operational clearances contact Carrier
5. Dimensions in are in inches [mm].
16
NOTES:
Fig. 15 — Base Unit Dimensions — 48EW,EY038-048
Adjacent Units: 15′-0″ [4572].
Filter Access Side: 15′-0″ [4572]. (For removal of evaporator
coil.)
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Min Clearances to be:
mizer inlet.
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing econo-
4. For smaller service and operational clearances contact Carrier
Application Engineering Department.
5. Dimensions in are in inches [mm].
17
AT EACH CORNER
% OF TOTAL WEIGHT
CENTER OF GRAVITY
Inches Millimeters
UNIT SIZE
ABAB1234
48EWD/EYD054 130.9 46.9 3325 1192 22.4 19.6 27.0 30.9
48EWE054 133.8 47.4 3397 1204 23.1 19.8 26.3 30.7
48EWE058 139.5 49.6 3544 1260 25.3 19.6 24.1 31.1
48EWE064 132.2 47.2 3359 1199 22.8 19.7 26.7 30.8
48EWD/EYD058 132.1 47.5 3354 1207 22.9 19.5 26.5 31.1
48EWE068 134.7 48.6 3422 1235 23.9 19.4 25.4 31.3
48EWD/EYD064 125.3 45.2 3181 1149 20.7 19.6 29.1 30.7
48EWD/EYD068 127.7 46.6 3242 1184 21.7 19.3 27.7 31.2
BASE UNIT WEIGHTS
(See Note 6) lbs (kg)
054 058 064 068
48EWE 7085 (3214) 7335 (3327) 7585 (3441) 7760 (3520)
48EWD/EYD 6845 (3105) 7095 (3218) 7345 (3332) 7520 (3411)
Fig. 16 — Base Unit Dimensions — 48EW,EY054-068
Filter Access Side: 15′-0″ [4572]. (For
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
facing economizer inlet.
NOTES:
1. Weights include economizer (standard).
Min Clearances to be:
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge
removal of evaporator coil.)
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
contact Carrier Application Engineering Depart-
ment.
and filters (indoor fan motor is not included).
Add indoor motor, FIOPs and accessories for
total operating weight.
compressor electric unloaders, VFD transducer
and associated wiring.
return and supply ductwork connection is rec-
ommended for covering all three return and all
three supply openings. The entire area around
the duct openings is available for a 1.5 duct
4. For smaller service and operational clearances
5. Base unit weights include outdoor air hoods
6. VAV motor weights include indoor motor, VFD,
flange attachment
7. For side-supply/return applications, a single
8. Dimensions in are in inches [mm].
18
2
A
3
B
1
4
48AJ,AK,AW,AY UNITS
UNIT
CENTER OF GRAVITY
Inches Millimeters
PERCENT OF TOTAL WEIGHT
AT EACH CORNER (%)
ABAB1 2 3 4
48AJ,AKD020 72.4 42.2 1839 1072 21.0% 22.8% 29.2% 26.9%
48AJE020 73.3 42.7 1862 1085 21.6% 22.9% 28.6% 27.0%
48AW,AYD020 72.4 42.2 1839 1072 21.0% 22.8% 29.2% 26.9%
48AWE020 73.3 42.7 1862 1085 21.6% 22.9% 28.6% 27.0%
48AJ,AKD025 69.6 44.0 1768 1118 21.1% 21.1% 28.9% 28.9%
48AJE025 70.1 44.3 1781 1125 21.4% 21.1% 28.6% 29.0%
48AW,AYD025 69.6 44.0 1768 1118 21.1% 21.1% 28.9% 28.9%
48AWE025 70.1 44.3 1781 1125 21.4% 21.1% 28.6% 29.0%
48AJ,AKD027 69.6 44.0 1768 1118 21.1% 21.1% 28.9% 28.9%
48AJE027 70.1 44.3 1781 1125 21.4% 21.1% 28.6% 29.0%
48AW,AYD027 69.6 44.0 1768 1118 21.1% 21.1% 28.9% 28.9%
48AWE027 70.1 44.3 1781 1125 21.4% 21.1% 28.6% 29.0%
48AJ,AKD030 69.6 44.0 1768 1118 21.1% 21.1% 28.9% 28.9%
48AJE030 70.1 44.3 1781 1125 21.4% 21.1% 28.6% 29.0%
48AW,AYD030 69.6 44.0 1768 1118 21.1% 21.1% 28.9% 28.9%
48AWE030 70.1 44.3 1781 1125 21.4% 21.1% 28.6% 29.0%
48AJ,AKD035 92.7 46.9 2355 1191 23.0% 20.1% 26.6% 30.3%
48AJE035 94.1 47.2 2390 1199 23.5% 20.3% 26.1% 30.2%
48AW,AYD035 92.7 46.9 2355 1191 23.0% 20.1% 26.6% 30.3%
48AWE035 94.1 47.2 2390 1199 23.5% 20.3% 26.1% 30.2%
48AJ,AKD040 89.3 46.9 2268 1191 22.1% 19.4% 27.3% 31.2%
48AJE040 90.8 47.2 2306 1199 22.7% 19.6% 26.8% 31.0%
48AW,AYD040 89.3 46.9 2268 1191 22.1% 19.4% 27.3% 31.2%
48AWE040 90.8 47.2 2306 1199 22.7% 19.6% 26.8% 31.0%
48AJ,AKD050 87.7 46.5 2228 1181 21.6% 19.2% 27.9% 31.3%
48AJE050 89.2 46.8 2266 1189 22.1% 19.4% 27.4% 31.1%
48AW,AYD050 87.7 46.5 2228 1181 21.6% 19.2% 27.9% 31.3%
48AWE050 89.2 46.8 2266 1189 22.1% 19.4% 27.4% 31.1%
48AJ,AKD060 125.3 45.2 3181 1149 21.7% 19.3% 27.7% 31.2%
48AJE060 132.2 47.2 3359 1199 23.9% 19.4% 25.4% 31.3%
48AW,AYD060 127.7 46.6 3242 1184 21.7% 19.3% 27.7% 31.2%
48AWE060 134.7 48.6 3422 1235 23.9% 19.4% 25.4% 31.3%
Fig. 17 — Rigging Information
19
48EJ,EK,EW,EY UNITS
CENTER OF GRAVITY
UNIT
48EJ,EW,EK,EYD024 72.4 42.2 1839 1072 21.0 22.8 29.2 26.9
48EJ,EWE024 73.3 42.7 1862 1085 21.6 22.9 28.6 27.0
48EJ,EW,EK,EYD028 69.6 44.0 1768 1118 21.1 21.1 28.9 28.9
48EJ,EWE028 70.1 44.3 1781 1125 21.4 21.1 28.6 29.0
48EJ,EW,EK,EYD030 69.6 44.0 1768 1118 21.1 21.1 28.9 28.9
48EJ,EWE030 70.1 44.3 1781 1125 21.4 21.1 28.6 29.0
48EJ,EW,EK,EYD034 69.6 44.0 1768 1118 21.1 21.1 28.9 28.9
48EJ,EWE034 70.1 44.3 1781 1125 21.4 21.1 28.6 29.0
48EJ,EW,EK,EYD038 92.7 46.9 2355 1191 23.0 20.1 26.6 30.3
48EJ,EWE038 94.1 47.2 2390 1199 23.5 20.3 26.1 30.2
48EJ,EW,EK,EYD044 89.3 46.9 2268 1191 22.1 19.4 27.3 31.2
48EJ,EWE044 90.8 47.2 2306 1199 22.7 19.6 26.8 31.0
48EJ,EW,EK,EYD048 87.7 46.5 2228 1181 21.6 19.2 27.9 31.3
48EJ,EWE048 89.2 46.8 2226 1189 22.1 19.4 27.4 31.1
48EJ,EW,EK,EYD054 130.9 46.9 3325 1192 22.4 19.6 27.0 30.9
48EJ,EWE054 133.8 47.4 3397 1204 23.1 19.8 26.3 30.7
48EJ,EW,EK,EYD058 132.1 47.5 3354 1207 22.9 19.5 26.5 31.1
48EJ,EWE058 139.5 49.6 3544 1260 25.3 19.6 24.1 31.1
48EJ,EW,EK,EYD064 125.3 45.2 3181 1149 20.7 19.6 29.1 30.7
48EJ,EWE064 132.2 47.2 3359 1199 22.8 19.7 26.7 30.8
48EJ,EW,EK,EYD068 127.7 46.6 3242 1184 21.7 19.3 27.7 31.2
48EJ,EWE068 134.7 48.6 3422 1235 23.9 19.4 25.4 31.3
Inches Millimeters
ABAB1 2 3 4
PERCENT OF TOTAL WEIGHT
AT EACH CORNER (%)
RIGGING WEIGHTS
48AJ,AK,AW,AY UNITS
UNIT
48AJ,AKD 5142 5228 5325 5325 6004 6514 6725 8930 48AJ,AKE 5222 5308 5405 5405 6164 6674 6885 9170 48AW,AYD 5182 5268 5365 5365 6044 6554 6765 8970 48AW,AYE 5262 5348 5445 5445 6204 6714 6925 9210
*Includes outdoor-air hoods, filters, largest available indoor-fan
motor, modulating power exhaust, and the largest available variable frequency drive (VFD).
NOTES:
1. Center of gravity.
2. On 020-050 includes 500 lbs and on 060 725 lbs for modulating power exhaust.
020 025 027 030 035 040 050 060
MAXIMUM UNIT WEIGHTS (lb)*
3. On 020-050 includes 170 lbs and on 060 55 lbs for economizer hoods. Includes 45 lbs for the economizer hood packaging.
4. Add 220 lbs for copper coil on the 020-030 size.
5. Add 284 lbs for copper coil on the 035 size.
6. Add 380 lbs for copper coil on the 040-050 size.
7. Add 651 lbs for copper coil on the 060 size.
48EJ,EK,EW,EY UNITS
UNIT
48EJ,EKD 5142 5228 5304 5304 5943 6237 6622 8029 8377 8755 8930
48EJE 5222 5384 5384 5384 6103 6397 6782 8269 8617 8995 9170
48EW,EYD 5182 5404 5344 5344 5983 6277 6662 8069 8417 8795 8970
48EWE 5262 5492 5424 5424 6143 6437 6822 8309 8657 9035 9210
*Includes outdoor-air hoods, filters, largest available indoor-fan
motor, modulating power exhaust, and the largest available variable frequency drive (VFD).
NOTES:
1. Center of gravity.
2. Sizes 024-048 includes 500 lb and sizes 054-068 includes 725 lb for modulating power exhaust.
3. Sizes 024-048 includes 170 lb and sizes 054-068 includes 255 lb for economizer hoods.
024 028 030 034 038 044 048 054 058 064 068
MAXIMUM UNIT WEIGHTS (lb)*
4. Economizer hood packaging includes 45 lb.
5. For sizes 024-034 add 220 lb for copper coil.
6. For sizes 038-044 add 284 lb for copper coil.
7. For 048 size add 380 lb for copper coil.
8. For 054 size add 271 lb for copper coil.
9. For 058 size add 407 lb for copper coil.
10. For 064 size add 489 lb for copper coil.
11. For 068 size add 651 lb for copper coil.
Fig. 17 — Rigging Information (cont)
20
Table 1A — Physical Data — 48AJ,AK,AW,AY Units
UNIT 48AJ,AK,AW,AY 020D/E 025D/E 027D/E 030D/E NOMINAL CAPACITY (tons) 20 25 27 30 BASE UNIT OPERATING WEIGHT (lb) See Operating Weights Table 2. COMPRESSOR
Quantity...Type (Ckt 1 , Ckt 2) 1...06D328, 1...06D818 2...06D328 2...06D328 1...06D537, 1…06D328 Number of Refrigerant Circuits 2222 Oil (oz) (Ckt 1 , Ckt 2) 115, 88 115 ea. 115 ea. 115 ea.
REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Circuit 1 25-0 25-0 29-0 27-0 Circuit 2 31-0 25-0 28-0 29-0
CONDENSER COIL * Cross-Hatched Quantity 1111 Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 33.333.333.333.3
CONDENSER FAN Propeller Type Nominal Cfm 13,420 13,420 13,420 13,420 Quantity...Diameter (in.) 2...30 2...30 2...30 2...30 Motor Hp 1111
EVAPORATOR COIL Cross-Hatched Copper Tubes, Aluminum Plate Fins Tube Size (in.) Rows...Fins/in. 4...15 4...15 4...15 4... 5 Total Face Area (sq ft) 31.731.734.734.7
EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) 2...20 X 15 2... 20 X 15 2... 20 X 15 2... 20 X 15 Type Drive Belt Belt Belt Belt Nominal Cfm 8,000 10,000 11,000 12,000 Motor Hp 5 10 15 7.5 10 15 10 15 20 10 15 20 Motor Frame Size 184T 215T 254T 213T 215T 254T 215T 254T 256T 215T 254T 256T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 1200 Motor Pulley Pitch Diameter 4.9 4.4 5.7 5.4 6.1 5.5 4.4 4.9 5.9 4.4 5.7 5.9 Nominal Motor Shaft Diameter (in.) 11/ Fan Pulley Pitch Diameter (in.) 12.4 8.6 9.1 12.4 11.1 8.7 9.4 8.1 8.7 9.0 9.1 8.7 Nominal Fan Shaft Diameter (in.) 115/ Belt Quantity 122112222222 Belt Type BX56 BX50 5VX530 BX56 5VX590 5VX570 BX50 5VX500 5VX530 BX50 5VX530 5VX530 Belt Length (in.) 56 63 53 56 59 57 50 50 53 50 53 53 Pulley Center Line Distance (in.) 16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9 Factory Speed Setting (rpm) 717 924 1096 773 962 1106 848 1059 1187 884 1096 1187
FURNACE SECTION Rollout Switch Cutout Temp (F) † 225 225 225 225
Burner Orifice Diameter (in. ...drill size)
Natural Gas Std .111...34 .111...34 .111...34 .111...34 Liquid Propane Alt .089...43 .089...43 .089...43 .089...43 Thermostat Heat Anticipator Setting Stage 1 (amps) 0.10.10.10.1 Stage 2 (amps) 0.10.10.10.1 Gas Input (Btuh) Stage 1 262,500/394,000 262,500/394,000 262,500/394,000 262,500/394,000
Efficiency (Steady State) (%) 82 82 82 82 Temperature Rise Range 15-45/35-65 15-45/35-65 15-45/35-65 15-45/35-65 Manifold Pressure (in. wg) Natural Gas Std 3.53.53.53.5 Liquid Propane Alt 3.53.53.53.5 Gas Valve Quantity 2222
HIGH-PRESSURE SWITCH (psig) Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
LOW-PRESSURE SWITCH (psig) Cutout 27 27 27 27 Reset (Auto.) 67 67 67 67
RETURN-AIR FILTERS Quantity...Size (in.) 10...20 x 24 x 2 10...20 x 24 x 2 10...20 x 24 x 2 10...20 x 24 x 2
OUTDOOR AIR FILTERS 8...16 x 25 8...16 x 25 8...16 x 25 8...16 x 25
Quantity...Size (in.) 4...20 x 25 4...20 x 25 4..20 x 25 4...20 x 25
S t a g e 2 350,000/525,000 350,000/525,000 350,000/525,000 350,000/525,000
3
/
8
13/
8
8
16
LEGEND *Sizes 020-030: Circuit 1 uses the lower por tion of condenser coil, Circuit 2 uses the upper
Al Aluminum Bhp — Brake Horsepower Cu — Copper
3
/8" Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
3
/
8
13/
13/
8
13/
8
115/
15/
8
16
portion. Sizes 035-050: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
†Rollout switch is manual reset.
13/
8
3
/
8
15/
8
115/
15/
8
16
13/
8
3
/
8
15/
8
115/
15/
8
16
8
NOTE: High heat is for 48AJ,AW only.
21
Table 1A — Physical Data — 48AJ,AK,AW,AY Units (cont)
UNIT 48AJ,AK,AW,AY 035D/E 040D/E 050D/E 060D/E NOMINAL CAPACITY (tons) 35 40 50 60 BASE UNIT OPERATING WEIGHT (lb) See Operating Weights Table 2. COMPRESSOR
Quantity...Type (Ckt 1 , Ckt 2) 2...06D537 1...06D537, 1...06EA250 2…06EA250 2...06EA265 Number of Refrigerant Circuits 2222 Oil (oz) (Ckt 1 , Ckt 2) 115 ea. 115, 224 224 ea. 304 ea.
REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1 34-8 51-8 50-0 79-8 Circuit 2 34-8 49-8 50-0 79-8
CONDENSER COIL * Cross-Hatched Quantity 2222 Rows...Fins/in. 3...15 4...15 4...15 4…15 Total Face Area (sq ft) 58.3 66.7 66.7 100
CONDENSER FAN Propeller Type Nominal Cfm 27,064 27,064 27,064 43,900 Quantity...Diameter (in.) 4...30 4...30 4...30 6...30 Motor Hp 1111
EVAPORATOR COIL Cross-Hatched Copper Tubes, Aluminum Plate Fins Tube Size (in.) Rows...Fins/in. 4...15 6...15 6...15 4...17 Total Face Area (sq ft) 34.7 31.3 31.3 48.1
EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) 2...20 X 15 2...20 X 15 2...20 X 15 3...20 X 15 Type Drive Belt Belt Belt Belt Nominal Cfm 14,000 16,000 20,000 24,000 Motor Hp 10 15 20 15 20 25 20 25 30 25 30 40 Motor Frame Size 215T 254T 25 6T 254T 256T 284T 256T 284T 286T 284T 286T 324T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1200 1200 1300 1200 Motor Pulley Pitch Diameter 6.1 5.3 5.7 5.3 5.7 7.5 6.3 8.1 7.5 5.3 8.1 9.4 Nominal Motor Shaft Diameter (in.) 13/ Fan Pulley Pitch Diameter (in.) 13.7 9.5 9.5 9.5 9.5 11.1 11.1 12.5 11.1 9.1 12.5 13.6 Nominal Fan Shaft Diameter (in.) 115/ Belt Quantity 122222222332 Belt Type 5VX610 5VX530 5VX550 5VX530 5VX550 5VX590 5VX570 5VX630 5VX590 5VX530 5VX630 5VX650 Belt Length (in.) 61 53 55 53 55 59 57 63 59 53 63 65 Pulley Center Line Distance (in.) 15.6-18.4 15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 14.6-17.6 14.6-17.6 15.2-17.5 14.7-17.2 14.2-17.0 Factory Speed Setting (rpm) 779 976 1050 976 1050 1182 993 1134 1182 1019 1134 1214
FURNACE SECTION Rollout Switch Cutout Temp (F) † 225 225 225 225
Burner Orifice Diameter (in. ...drill size)
Natural Gas Std .120...31 .120...31 .120...31 .120...31 Liquid Propane Alt .096...41 .096...41 .096...41 .096...41 Thermostat Heat Anticipator Setting Stage 1 (amps) 0.1 0.1 0.1 0.1 Stage 2 (amps) 0.1 0.1 0.1 0.1 Gas Input (Btuh) Stage 1 300,000/600,000 300,000/600,000 300,000/600,000 582,000/ 873,000
Efficiency (Steady State) (%) 82 82 82 82 Temperature Rise Range 10-40/30-60 10-40/30-60 10-40/30-60 10-40/30-60 Manifold Pressure (in. wg) Natural Gas Std 3.5 3.5 3.5 3.3
Gas Valve Quantity 2223 HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
LOW-PRESSURE SWITCH (psig) Cutout 27 27 27 27 Reset (Auto.) 67 67 67 67
RETURN-AIR FILTERS Quantity...Size (in.) 10...20 x 24 x 2 10...20 x 24 x 2 10...20 x 24 x 2 16...20 x 24 x 2
OUTDOOR AIR FILTERS 8...16 x 25 8...16 x 25 8...16 x 25 12...16 x 25
Quantity...Size (in.) 4...20 x 25 4...20 x 25 4...20 x 25 6...20 x 25
S t a g e 2 400,000/800,000 400,000/800,000 400,000/800,000 776,000/1,164,000
3
/
8
15/
8
15/
8
16
LEGEND *Sizes 020-030: Circuit 1 uses the lower por tion of condenser coil, Circuit 2 uses the upper
Al Aluminum Bhp — Brake Horsepower Cu — Copper
3
/8" Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
1
/
2
15/
8
15/
8
115/
17/
8
16
portion. Sizes 035-050: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
†Rollout switch is manual reset.
15/
8
1
/
2
17/
8
115/
8
16
NOTE: High heat is for 48AJ,AW only.
1
/
2
17/
17/
8
17/
8
115/
21/
8
16
8
3.3 Liquid Propane Alt 3.5 3.5 3.5
22
Table 1B — Physical Data — 48EJ,EK,EW,EY Units
UNIT 48EJ,EK,EW,EY 024D/E 028D/E 030D/E 034D/E NOMINAL CAPACITY (tons) 20 25 27.5 30 OPERATING WEIGHT (lb) For Operating Weights see Table 2. COMPRESSOR
Typ e Ck t 1 06D328 06D328 06D537 06D537
Ckt 2 06D818 06D328 06D328 06D537 Number of Refrigerant Circuits 22 2 2 Oil (oz) (Ckt 1, Ckt 2) 115, 88 115 ea. 115 ea. 115 ea.
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1* 25-0 25-0 25-0 25-0 Circuit 2 31-0 25-0 25-0 25-0
CONDENSER COIL Cross-Hatched
Quantity 11 1 1 Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 33.3 33.3 33.3 33.3
CONDENSER FAN Propeller Type
Nominal Cfm 13,420 13,420 13,420 13,420 Quantity...Diameter (in.) 2...30 2...30 2...30 2...30 Motor Hp (1075 Rpm) 11 1 1
EVAPORATOR COIL Cross-Hatched 3/8″ Copper Tubes, Aluminum Plate Fins, Intertwined Circuits
Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 31.7 31.7 31.7 31.7
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...20x15 2...20x15 2...20x15 2...20x15 Type Drive Belt Belt Belt Belt Nominal Cfm 8,000 10,000 11,000 12,000 Motor Hp 5 10† 15 7.5 10† 15 10 15† 20 10 15† 20 Motor Frame Size (Standard) S184T S215T D254T S213T S215T D254T S215T D254T S256T S215T D254T S256T
(High Efficiency) S184T S215T S254T S213T S215T S254T S215T S254T S256T S215T S254T S256T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 1200 Motor Pulley Pitch Diameter 4.9 4.4 5.7 5.4 6.1 5.5 4.4 4.9 5.9 4.4 5.7 5.9 Nominal Motor Shaft Diameter (in.) 11/ Fan Pulley Pitch Diameter (in.) 12.4 8.6 9.1 12.4 11.1 8.7 9.4 8.1 8.7 9.0 9.1 8.7 Nominal Fan Shaft Diameter (in.) 115/ Belt, Quantity...Type 1...BX56 2...BX50 2...5VX530 1...BX56 1...5VX570 2...5VX530 2...BX50 2...5VX500 2...5VX530 2...BX50 2...5VX530 2...5VX530 Belt, Length (in.) 56 50 53 56 59 57 50 50 53 50 53 53 Pulley Center Line Distance (in.) 16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 Factory Speed Setting (rpm) 717 924 1096 773 962 1106 848 1059 1187 884 1096 1187
FURNACE SECTION
Rollout Switch Cutout Temp (F)** 225 225 225 225 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std .111...34 .111...34 .111...34 .111...34
Liquid Propane Alt .089...43 .089...43 .089...43 .089...43 Thermostat Heat Anticipator Setting (amps) Stage 1 0.1 0.1 0.1 0.1 Stage 2 0.1 0.1 0.1 0.1 Gas Input (Btuh) Stage 1 Low 265,600 265,600 265,600 265,600
Efficiency (Steady State) (%) 82 82 82 82 Temperature Rise Range 15-45/35-65 15-45/35-65 15-45/35-65 15-45/35-65 Gas Pressure to Unit Range (in. wg) 5-13.5 5-13.5 5-13.5 5-13.5 Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5 Gas Valve Quantity 22 2 2 Field Gas Connection Size
(in.-FPT) 1.5 1.5 1.5 1.5
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
LOW-PRESSURE SWITCH (psig)
Cutout 77 7 7 Reset (Auto.) 22 22 22 22
RETURN-AIR FILTERS (W x H x T)
Quantity...Size (in.) 10...20 x 24 x 2 10...20 x 24 x 2 10...20 x 24 x 2 10...20 x 24 x 2
OUTDOOR-AIR FILTERS 8...16 x 25 8...16 x 25 8...16 x 25 8...16 x 25
Quantity...Size (in.) 4...20 x 25 4...20 x 25 4...20 x 25 4...20 x 25
POWER EXHAUST Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired for High Speed) and Forward Curved Fan
Motor, Quantity...Hp 4...1 Fan, Diameter...Width (in.) 11...10
*Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper portion.
Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
†Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more information, see Table 3.
**Rollout switch is manual reset.
High 398,400 398,400 398,400 398,400 Stage 2 Low 350,000 350,000 350,000 350,000 High 525,000 525,000 525,000 525,000
13/
8
15/
8
16
NOTE: High heat is for 48EJ,EW only.
3
/8″ Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
13/
8
13/
8
115/
15/
8
16
13/
8
15/
8
115/
15/
8
16
13/
8
15/
8
115/
15/
8
16
8
23
Table 1B — Physical Data — 48EJ,EK,EW,EY Units (cont)
NOMINAL CAPACITY (tons) 35 40 45 OPERATING WEIGHT (lb) For Operating Weights see Table 2. COMPRESSOR
Typ e Ck t 1 06D537 06EA250 06EA265
Number of Refrigerant Circuits 22 2 Oil (oz) (Ckt 1, Ckt 2) 115 ea. 224 ea. 304, 224
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
CONDENSER COIL Cross-Hatched
Quantity 2211 Rows...Fins/in. 4...15 4...15 4...15 3...15 Total Face Area (sq ft) 58.3 58.3 66.7
CONDENSER FAN Propeller Type
Nominal Cfm 27,064 27,064 27,064 Quantity...Diameter (in.) 4...30 4...30 4...30 Motor Hp (1075 Rpm) 11 1
EVAPORATOR COIL Cross-Hatched 3/8″ Copper Tubes, Aluminum Plate Fins, Intertwined Circuits
Rows...Fins/in. 3...15 3...15 4...15 Total Face Area (sq ft) 34.7 34.7 34.7
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...20x15 2...20x15 2...20x15 Type Drive Belt Belt Belt Nominal Cfm 14,000 16,000 18,000 Motor Hp 10 15† 20 15 20† 25 20 25† 30 Motor Frame Size (Standard) S215T D254T S256T D254T S256T S284T S256T S284T S286T
Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 Motor Pulley Pitch Diameter 6.1 5.3 5.7 5.3 5.7 7.5 6.3 8.1 7.5 Nominal Motor Shaft Diameter (in.) 13/ Fan Pulley Pitch Diameter (in.) 13.7 9.5 9.5 9.5 9.5 11.1 11.1 12.5 11.1 Nominal Fan Shaft Diameter (in.) 115/ Belt, Quantity...Type 1...5VX610 2...5VX530 2...5VX550 2...5VX530 2...5VX550 2...5VX590 2...5VX570 2...5VX630 2...5VX590 Belt, Length (in.) 61 53 55 53 55 59 57 63 59 Pulley Center Line Distance (in.) 15.6-18.4 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 14.6-17.6 Factory Speed Setting (rpm) 779 976 1050 976 1050 1182 993 1134 1182
FURNACE SECTION
Rollout Switch Cutout Temp (F)** 225 225 225 Burner Orifice Diameter
(in. ...drill size)
Thermostat Heat Anticipator Setting (amps) Stage 1 0.1 0.1 0.1 Stage 2 0.1 0.1 0.1 Gas Input (Btuh) Stage 1 Low 303,500 303,500 303,500
Efficiency (Steady State) (%) 82 82 82 Temperature Rise Range 10-40/30-60 10-40/30-60 10-40/30-60 Gas Pressure to Unit Range (in. wg) 5-13.5 5-13.5 5-13.5 Manifold Pressure (in. wg)
Gas Valve Quantity 22 2 Field Gas Connection Size
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 Reset (Auto.) 320 320 320
LOW-PRESSURE SWITCH (psig)
Cutout 77 7 Reset (Auto.) 22 22 22
RETURN-AIR FILTERS (W x H x T)
Quantity...Size (in.) 10...20 x 24 x 2 10...20 x 24 x 2 10...20 x 24 x 2
OUTDOOR-AIR FILTERS 8...16 x 25 8...16 x 25 8...16 x 25
Quantity...Size (in.) 4...20 x 25 4...20 x 25 4...20 x 25
POWER EXHAUST Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired for High Speed) and Forward Curved Fan
Motor, Quantity...Hp 4...1 Fan, Diameter...Width (in.) 11...10
*Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper portion.
Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
†Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more information, see Table 3.
**Rollout switch is manual reset.
NOTE: High heat is for 48EJ,EW only.
UNIT 48EJ,EK,EW,EY 034D/E 044D/E 048D/E
Ckt 2 06D537 06EA250 06EA250
Circuit 1* 34-0 35-0 41-0 Circuit 2 34-0 35-0 41-0
3
/8″ Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
(High Efficiency) S215T S254T S256T S254T S256T S284T S256T S284T S286T
8
Natural Gas Std .120...31 .120...31 .120...31 Liquid Propane Alt .096...41 .096...41 .096...41
High 607,000 607,000 607,000 Stage 2 Low 400,000 400,000 400,000 High 800,000 800,000 800,000
Natural Gas Std 3.5 3.5 3.5 Liquid Propane Alt 3.5 3.5 3.5
15/
8
16
15/
8
15/
8
15/
115/
8
16
17/
8
15/
8
17/
115/
8
16
17/
(in.-FPT) 1.5 1.5 1.5
8
24
Table 1B — Physical Data — 48EJ,EK,EW,EY Units (cont)
UNIT 48EJ,EK,EW,EY 054D/E 058D/E 064D/E 068D/E NOMINAL CAPACITY (tons) 50 55 60 65 OPERATING WEIGHT (lb) For Operating Weights see Table 2. COMPRESSOR
Quantity...Type (Ckt 1, Ckt 2) 1...06EA265, 1...06EA250 1...06EA275, 1...06EA250 1...06EA275, 1...06EA265 2...06EA275 Number of Refrigerant Circuits 2222 Oil (oz) (Ckt 1, Ckt 2) 304, 224 304, 224 304, 304 304, 304
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1* 50-11 57-0 68-0 81-0 Circuit 2 46-8 48-6 68-0 73-0
CONDENSER COIL Cross-Hatched
Quantity 1 1 1 1 2 2 Rows...Fins/in. 3...15 2...15 3...15 2...15 3...15 4...15 Total Face Area (sq ft) 66.6 100.0 100 100
CONDENSER FAN Propeller Type
Nominal Cfm 30,000 43,900 43,900 43,900 Quantity...Diameter (in.) 4...30 6...30 6...30 6...30 Motor Hp (1075 Rpm) 1111
EVAPORATOR COIL Cross-Hatched 1/2″-in. Copper Tubes, Aluminum Plate Fins, Intertwined Circuits
Rows...Fins/in. 4...17 4...17 4...17 4...17 Total Face Area (sq ft) 45.0 45.0 48.1 48.1
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 3...20x15 3...20x15 3...20x15 3...20x15 Type Drive Belt Belt Belt Belt Nominal Cfm 20,000 22,000 24,000 26,000 Motor Hp 15 20† 25 20 25† 30 25 30† 40 25 30† 40 Motor Frame Size S254T S256T S284T S256T S284T S286T S284T S286T S324T S284T S286T S324T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 1200 Motor Pulley Pitch Diameter 4.7 6.1 8.1 5.9 6.7 7.5 5.3 8.1 9.4 6.7 5.9 9.4 Nominal Motor Shaft Diameter (in.) 15/ Fan Pulley Pitch Diameter (in.) 11.1 11.1 12.5 11.1 11.1 11.1 9.1 12.5 13.6 12.5 9.5 13.6 Nominal Fan Shaft Diameter (in.) 115/ Belt, Quantity...Type 2...5VX550 2...5VX570 2...5VX630 2...5VX570 2...5VX590 2...5VX590 3...5VX530 2...5VX630 2...5VX650 2...5VX610 3...5VX550 2...5VX650 Length (in.) 55 57 63 57 59 59 53 63 65 61 55 59 Pulley Center Line Distance (in.) 15.2-17.5 15.2-17.5 14.7-17.2 15.2-17.5 14.7-17.2 14.7-17.2 14.7-17.2 14.7-17.2 14.2-17.0 14.7-17.2 14.7-17.2 14.3-17.0 Factory Speed Setting (rpm) 741 962 1134 930 1056 1182 1019 1134 1214 938 1087 1214
FURNACE SECTION
Rollout Switch Cutout Temp (F)** 225 225 225 225 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std .120...31 .120...31 .120...31 .120...31
Liquid Propane Alt .096...41 .096...41 .096...41 .096...41 Thermostat Heat Anticipator Setting (amps) Stage 1 0.1 0.1 0.1 0.1 Stage 2 0.1 0.1 0.1 0.1 Gas Input (Btuh) Stage 1 441,000/ 873,000 441,000/ 873,000 441,000/ 873,000 441,000/ 873,000
Efficiency (Steady State) (%) 82 82 82 82 Temperature Rise Range 10-40/30-60 10-40/30-60 10-40/30-60 10-40/30-60 Gas Pressure to Unit Range (in. wg) 5 - 13.5 5 - 13.5 5 - 13.5 5 - 13.5 Manifold Pressure (in. wg)
Natural Gas Std 3.3 3.3 3.3 3.3
Liquid Propane Alt 3.3 3.3 3.3 3.3 Gas Valve Quantity 3333 Field Gas Connection Size
(in.-FPT) 2.5 2.5 2.5 2.5
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
LOW-PRESSURE SWITCH (psig)
Cutout 7777 Reset (Auto.) 22 22 22 22
RETURN-AIR FILTERS (W x H x T)
Quantity...Size (in.) 16...20 x 24 x 2 16...20 x 24 x 2 16...20 x 24 x 2 16...20 x 24 x 2
OUTDOOR-AIR FILTERS 12...16 x 25 12...16 x 25 12...16 x 25 12...16 x 25
Quantity...Size (in.) 6...20 x 25 6...20 x 25 6...20 x 25 6...20 x 25
POWER EXHAUST Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired for High Speed) and Forward Curved Fan
Motor, Quantity...Hp 6...1 Fan, Diameter...Width (in.) 11...10
*Circuit 1 uses the left condenser coil. Circuit 2 the right. All units have intertwined evaporator coils. †Motor and drive shown will deliver approximately 2.5 in. wg net external static pressure. For more information see Table 3.
**Rollout switch is manual reset.
Stage 2 662,400/1,164,000 662,400/1,164,000 662,400/1,164,000 662,400/1,164,000
15/
8
8
16
NOTE: High heat is for 48EJ,EW.
3
/8″-in. Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
17/
15/
8
17/
8
115/
17/
8
16
17/
8
17/
8
115/
21/
8
16
17/
8
17/
8
115/
21/
8
16
8
25
Table 2 — Operating Weights
48AJ,AK,AW,AY Units
UNIT
48AJD,AKD 4287 4373 4394 4394 5073 5515 5628 7480
48AJE 4367 4453 4474 4474 5233 5675 5788 7720
48AWD,AYD 4327 4413 4434 4434 5113 5555 5668 7520
48AWE 4407 4493 4514 4514 5273 5715 5828 7760
OPTION/
ACCE SSORY
Barometric Relief 300 300 300 300 300 300 300 450 Powe r Exhaust 450 450 450 450 450 450 450 675 Modulating Power Exhaust 500 500 500 500 500 500 500 725 Cu Tubing/Cu Fin Condenser Coil 220 220 220 220 285 285 380 651 Roof Curb (14-in. curb) 365 365 365 365 410 410 410 585
020 025 027 030 035 040 050 060
020 025 027 030 035 040 050 060
BASE UNIT WEIGHTS (Lb)*
OPTION/ACCESSORY WEIGHTS (Lb)
48EJ,EK,EW,EY Units
UNIT
48EJ,EKD 4287 4373 4373 4373 5012 5238 5525 6805 7055 7305 7480
48EJE 4367 4453 4453 4453 5172 5398 5685 7045 7295 7545 7720
48EW,EYD 4327 4413 4413 4413 5052 5278 5565 6845 7095 7345 7520
48EWE 4407 4493 4493 4493 5212 5438 5725 7085 7335 7585 7760
OPTION/
ACCE SSORY
Barometric Relief 300 300 300 300 300 300 300 450 450 450 450 Powe r Exhaust 450 450 450 450 450 450 450 675 675 675 675 Modular Power Exhaust 500 500 500 500 500 500 500 725 725 725 725 Cu Tubing/Cu Fin Condenser Coil 220 220 220 220 285 285 380 271 407 489 651 Roof Curb (14-in. curb) 365 365 365 365 410 410 410 585 585 585 585
024 028 030 034 038 044 048 054 058 064 068
024 028 030 034 038 044 048 054 058 064 068
BASE UNIT WEIGHTS (Lb)*
OPTION/ACCESSORY WEIGHTS (Lb)
CV MOTOR WEIGHTS (Lb)
MOTOR
HP
5
7.5
10
15
20
25
30
40
LEGEND
Cu Copper CV Constant Volume FIOP — Factory-Installed Option HP Horsepower IFM — Indoor Fan Motor VAV — Variable Air Volume VFD — Variable Frequency Drive
*Outdoor-air hoods and filters included in base unit weights; indoor-
fan motors are NOT included.
UNIT
VOLTAGE
230/460 78 94
575 78 92
230/460 107 135
575 107 136
230/460 118 164
575 118 156
230/460 150 217
575 150 220
230/460 212 250
575 212 258
230/460 240 309
575 240 319
230/460 283 355
575 283 359
230/460 372 415
575 372 410
STANDARD
EFFICIENCY
IFM
HIGH
EFFICIENCY
IFM
VAV MOTOR WEIGHTS (Lb)
MOTOR
HP
5
7.5
10
15
20
25
30
40
NOTES:
1. Base unit weight includes outdoor-air hoods. Base unit weight does NOT include indoor-fan motor. ADD indoor-fan motor, FIOPs, and accessories for TOTAL operating weight.
2. The VAV motor weights include indoor fan motor and the VFD (variable frequency drive), compressor electric unloaders, VFD transducers, and associated wiring.
UNIT
VOLTAGE
230/460 125 141
575 163 177
230/460 183 211
575 193 222
230/460 204 250
575 204 242
230/460 238 305
575 240 310
230/460 348 386
575 304 350
230/460 377 446
575 375 454
230/460 480 552
575 418 494
230/460 637 680
575 587 625
STANDARD
EFFICIENCY
IFM
HIGH
EFFICIENCY
IFM
26
Table 3 — Evaporator Fan Motor Data
UNIT SIZE
48AJ,AK,
AW,AY
020 024
025 028
027 030
030 034
035 038
040 044
050 048
054
058
060 064
068
NOTES:
1. Motor shaft speed is 1750 rpm. The fan shaft diameter is 115/16 inches.
2. All indoor fan motors meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT), effective October 24, 1997.
UNIT SIZE
48EJ,EK,
EW,EY
MOTOR
MOTOR
SHAFT DIA.
HP
5 1.125 717 BK55 4.9 NONE — 1.125 1B5V124 12.4 B—1.9375 BX56 8 10 1.375 924 2BK50 4.4 NONE — 1.375 2B5V86 8.6 B—1.9375 (2) BX50 8 15 1.625 1096 2B5V56 5.7 B — 1.625 2B5V90 9.1 B—1.9375 (2) 5VX530 9
7.5 1.375 773 BK60H 5.4 H — 1.375 1B5V124 12.4 B—1.9375 BX56 10 10 1.375 962 1B5V60 6.1 H — 1.375 1B5V110 11.1 B—1.9375 5VX570 11 15 1.625 1106 2B5V54 5.5 B — 1.625 2B5V86 8.7 B—1.9375 (2) 5VX530 9
10 1.375 848 2BK50 4.4 NONE — 1.375 2B5V94 9.4 B—1.9375 (2) BX50 8 15 1.625 1059 2B5V48 4.9 B — 1.625 2B5V80 8.1 B—1.9375 (2) 5VX500 10 20 1.625 1187 2B5V58 5.9 B — 1.625 2B5V86 8.7 B—1.9375 (2) 5VX530 11
10 1.375 884 2BK50 4.4 H — 1.375 2B5V90 9.0 B—1.9375 (2) BX50 8 15 1.625 1096 2B5V56 5.7 B — 1.625 2B5V90 9.1 B—1.9375 (2) 5VX530 9 20 1.625 1187 2B5V58 5.9 B — 1.625 2B5V86 8.7 B—1.9375 (2) 5VX530 11
10 1.375 779 1B5V60 6.1 NONE — 1.375 1B5V136 13.7 B—1.9375 5VX610 12 15 1.625 976 2B5V52 5.3 B — 1.625 2B5V94 9.5 B—1.9375 (2) 5VX530 10 20 1.625 1050 2B5V56 5.7 B — 1.625 2B5V94 9.5 B—1.9375 (2) 5VX550 11
15 1.625 976 2B5V52 5.3 B — 1.625 2B5V94 9.5 B—1.9375 (2) 5VX530 10 20 1.625 1050 2B5V56 5.7 B — 1.625 2B5V94 9.5 B—1.9375 (2) 5VX550 11 25 1.875 1182 2B5V74 7.5 B — 1.875 2B5V110 11.1 B—1.9375 (2) 5VX590 11
20 1.625 993 2B5V62 6.3 B — 1.625 2B5V110 11.1 B—1.9375 (2) 5VX570 11 25 1.875 1134 2B5V80 8.1 B — 1.875 2B5V124 12.5 B—1.9375 (2) 5VX630 11 30 1.875 1182 2B5V74 7.5 B — 1.875 2B5V110 11.1 B—1.9375 (2) 5VX590 13
15 1.625 741 2B5V46 4.7 B — 1.625 2B5V110 11.1 B—1.9375 (2) 5VX550 11 20 1.625 962 2B5V60 6.1 B — 1.625 2B5V110 11.1 B—1.9375 (2) 5VX570 12 25 1.875 1134 2B5V80 8.1 B — 1.875 2B5V124 12.5 B—1.9375 (2) 5VX630 12
20 1.625 930 2B5V58 5.9 B — 1.625 2B5V110 11.1 B—1.9375 (2) 5VX570 13 25 1.875 1056 2B5V66 6.7 B — 1.875 2B5V110 11.1 B—1.9375 (2) 5VX590 14 30 1.875 1182 2B5V74 7.5 B — 1.875 2B5V110 11.1 B—1.9375 (2) 5VX590 14
25 1.875 1019 3B5V52 5.3 B — 1.875 3B5V90 9.1 B—1.9375 (3) 5VX530 12 30 1.875 1134 2B5V80 8.1 B — 1.875 2B5V124 12.5 B—1.9375 (2) 5VX630 14 40 2.125 1214 2B5V94 9.4 B — 2.125 2B5V136 13.6 B—1.9375 (2) 5VX650 15
25 1.875 938 2B5V66 6.7 B — 1.875 2B5V124 12.5 B—1.9375 (2) 5VX610 14 30 1.875 1087 3B5V58 5.9 B — 1.875 3B5V94 9.5 B—1.9375 (3) 5VX550 13 40 2.125 1214 2B5V94 9.4 B — 2.125 2B5V136 13.6 B—1.9375 (2) 5VX650 15
(in.)
FAN SHAFT SPEED
(rpm)
MOTOR
SHEAVE
MOTOR
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
FAN
SHEAVE
FAN
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
BELT
(Quantity)
BELT
TENSION
(lb at .25 in.)
Fig. 18 — Air Distribution — Thru-the-Bottom
Fig. 19 — Air Distribution — Thru-the-Side
27
Step 5 — Install Flue Hood
48AJ,AK,AW,AY020-050 AND 48EJ,EK,EW,EY024-048 UNITS — Flue hood is shipped inside gas section of unit. To install, secure flue hood to access panel. See Fig. 20A.
48AJ,AK,AW,AY060 AND 48EJ,EK,EW,EY054-068 UNITS — Flue hood and wind baffle are shipped inside gas section of unit. To install, secure flue hood to access panel. In­stall the two pieces of the wind baffle over the flue hood. See Fig. 20B.
NOTE: When properly installed, flue hood will line up with combustion fan housing. See Fig. 21.
Fig. 21 — Combustion Fan Housing Location
Step 6 — Trap Condensate Drain — See Fig. 5-16
for drain location. Condensate drain is open to atmosphere and must be trapped. Install a trapped drain at the drain location. One 1-in. FPT coupling is provided inside the unit evaporator section for condensate drain connection. A trap at least 4-in. deep must be used. See Fig. 22. Trap must be installed to pre­vent freeze-up.
Condensate pans are sloped so that water will completely drain from the condensate pan to comply with indoor air quali­ty guidelines. The condensate drain pans are not insulated.
Fig. 20A — Flue Hood Location
(48AJ,AK,AW,AY020-050 and
48EJ,EK,EW,EY024-048 Units)
FLUE HOOD
WIND BAFFLE
TOP VIEW SIDE VIEW
Fig. 20B — Flue Hood Location
(48AJ,AK,AW,AY060 and
48EJ,EK,EW,EY054-068 Units)
GAS SECTION ACCESS PANEL
Fig. 22 — Condensate Drain Trap Piping Details
(Typical Roof Curb or Slab Mount Shown)
Step 7 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the Na­tional Fuel Gas Code, ANSI Z223.1.
Install manual gas shutoff valve with a tap for test gage connection at unit. Field gas piping must in­clude sediment trap and union. See Fig. 23. An also located on the gas manifold adjacent to the gas valve.
Do not pressure test gas supply while connected to unit. Always disconnect union before servicing.
1
/8-in. NPT pressure
1
/8-in. NPT is
28
IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
Fig. 23 — Field Gas Piping
Table 4 — 48A,E Series Staged Gas Implementation
OPTIONAL STAGED GAS UNITS — The staging pattern is selected based on Heat Stage Type (HTSTGTYP). Max Capacity per changes default value is selected based on Capac­ity Maximum Stage (CAPMXSTG). See Table 4.
For complete information and service instructions for Staged Gas Control Units, see Control Operation and Trouble­shooting literature.
Step 8 — Controls Options — The control options
that the units can provide are based on the following parame­ters: CV (constant volume) or VAV (variable air volume) oper­ation; stand-alone unit with field-supplied sensors installed (CV or VAV); as a system via Carrier Comfort System (TEMP or VVT® [Variable Volume and Temperature]); optional elec­tronic expansion board installed (CV or VAV); linked to the Carrier Comfort Network; availability of a computer and soft­ware (ComfortWORKS® Building Supervisor, and Service Tool) or remote enhanced display accessory installed to access the base control board; and optional factory-installed staged gas control. See Table 5.
NOTE: Access to the base control board allows unit occu­pancy schedules, unit timeclock, and various set points to be changed from their factory-defined default settings.
NUMBER OF STAGES
5 stages
7 stages
9 stages
11 stages
MODEL NUMBER POSITION POSITION
3 5 6,7,8 HTSTGTYP CAPMXSTG
024 028
ES
AS
ET
AT
ET
AT
ET
A T 060 Default=3 Default=15 High
ES
A S 060 Default=4 Default=15 Low
030 034 038 044 048
020 025 027 030 035 040 050
038 044 048
035 040 050
024 028 030 034
020 025 027 030
054 058 064 068
054 058 064 068
Default=1 Default=20 Low
Default=1 Default=20 Low
Default=1 Default=20 High
Default=1 Default=20 High
Default=2 Default=15 High
Default=2 Default=15 High
Default=3 Default=15 High
Default=4 Default=15 Low
HEAT SIZE
29
Table 5 — Controls Options and Configurations (Non-Thermostat Applications)
UNIT CONFIGURATION DEFAULT COOLING DEFAULT HEATING
CV or VAV Unit with SPT Sensor
CV Unit with SPT Sensor and Remote Start/Stop Switch
VAV Unit Remote Start/Stop Switch Only
VAV Unit with SPT Sensor and Remote Start/Stop Switch
LEGEND
CV Constant Volume NA Not Available RAT — Return-Air Temperature SAT — Supply-Air Temperature SPT Space Temperature VAV — Variable Air Volume
*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled). NOTE: Space temperature sensor and remote start/stop switch are field-supplied.
Unoccupied Cooling — 90 F (32 C) (SPT) Occupied Cooling — NA
Unoccupied Cooling — 90 F (32 C) (SPT) Occupied Cooling — 78 F (26 C) (SPT)
Unoccupied Cooling — 90 F (32 C)(SPT) Occupied Cooling — 55 F (13 C) SPT)
Unoccupied Cooling — 90 F (32 C) (SPT) Occupied Cooling — 55 F (13 C) (SAT)
Unoccupied Heating — 55 F (13 C) (SPT) Occupied Heating — NA
Unoccupied Heating — 55 F (13 C) (SPT) Occupied Heating — 68 F (20 C) (SPT)
Unoccupied Heating — 55 F (13 C) (RAT) Occupied Heating — 68 F (20 C) (RAT)*
Unoccupied Heating — 55 F (13C) (SPT) Occupied Heating — 68 F (20 C) (RAT)*
STAGED GAS UNIT APPLICATIONS — The rooftop units may be ordered with an optional factory-installed staged gas control system that monitors heating operation of the rooftop unit.
IMPORTANT: An accessory field-supplied Navigator dis­play module is required for all staged gas control units.
Install Supply-Air Thermistors (Staged Gas Units Only)
— Supply-air thermistors are a field-installed factory-provided component. Three supply-air thermistors are shipped with staged gas units and are inside the heating section. Thermistor wires must be connected to SGC (staged gas controller) in the heating section. See Table 6 and Fig 24. The supply-air ther­mistors should be located in the supply duct with the following criteria:
• downstream of the heat exchanger cells
• equally spaced as far as possible from the heat exchanger
cells
• a duct location where none of the supply air thermistors
are within sight of the heat exchanger cells
• a duct location with good mixed supply air portion of the
unit.
Table 6 — Thermistor Designations
THERMISTORS — All units are equipped with a supply air thermistor (SAT) located in the supply fan discharge and an outdoor air thermistor (OAT) located in the outdoor air hood. Variable air volume (VAV) units are supplied with a return air thermistor (RAT) located on the return air damper support.
CONSTANT VOLUME APPLICATIONS — The units, as shipped, are operable as stand-alone units, using either a stan­dard (mechanical or electronic) 2-stage heat, 2-stage cool ther­mostat, or with an electronic room sensor and a timeclock to establish unit start and stop times.
With a standard thermostat (programmable is optional),
heating and cooling operation is set by space temperature.
With a space sensor and timeclock, the machine will operate at default values unless they are changed using appropriate in­put devices. The space sensor senses space temperature and may be equipped with a timed override feature, which allows unit operation during unoccupied periods.
The space sensors may be used in multiples of 4 or 9 to achieve space temperature averaging. The use of a space sensor also allows the unit to be turned on and off from a remote signal.
THERMISTOR
SAT 1 J8 – 1,2 (SGC)
SAT 3 J8 – 5,6 (SGC)
CONNECTION
POINT
PIN
FUNCTION AND LOCATION
Thermistors
Supply Air Thermistor (SAT) — Inserted into supply section underneath the gas heat section (factory-provided, field-installed)
Supply Air Thermistor (SAT) — Inserted into supply section underneath the gas heat section (factory-provided, field-installed)
Supply Air Thermistor (SAT) — Inserted into supply section underneath the gas heat section (factory-provided, field-installed)
30
PART NO.
HH79NZ016SAT 2 J8 – 3,4 (SGC)
Loading...
+ 88 hidden pages