Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of 0.5 psig or
less, a unit connected to such piping must be isolated by
closing the manual gas valve(s).
INSTALLATION
Step 1 — Provide Unit Support
1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Ta b 1 a
PC 111Catalog No. 534-739Printed in U.S.A.Form 48A,E-1SIPg 1107 11-01Replaces: 48E-6SI
ROOF CURB — For vertical discharge units, assemble or install accessory roof curb in accordance with instructions
shipped with this accessory. See Fig. 1-4. Install insulation,
cant strips, roofing, and counter flashing as shown. Ductwork
can be installed to roof curb before unit is set in place. Curb
should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is shown in Fig. 1-3.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required. When accessory roof curb
is used, unit may be installed on class A, B, or C roof covering
material.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket with the roof
curb as shown in Fig. 1-3. Improperly applied gasket can
also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When the preferred curb
or slab mount cannot be used, support unit with sleepers on perimeter, using unit curb support area. If sleepers cannot be
used, support long sides of unit (refer to Fig. 5-16) with a minimum number of 4-in. x 4-in. pads spaced as follows:
48AJ,AK,AW,AY020-030 and 48EJ,EK,EW,EY024-034 units
require 3 pads on each side; 48AJ,AK,AW,AY035-050 and
48EJ,EK,EW,EY038-048 units require 4 pads on each side;
48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068 units require 6 pads on each side. Unit may sag if supported by corners
only.
Step 2 — Rig and Place Unit — Inspect unit for
transportation damage. See Tables 1A and 1B for physical data.
File any claim with transportation agency.
Do not drop unit; keep upright. Use spreader bars over unit
to prevent sling or cable damage. Level by using unit frame as
a reference; leveling tolerance is shown in Fig. 1-3. See Fig. 17
for additional information. Unit operating weight is shown in
Table 2.
NOTE: On retrofit jobs, ductwork may be attached to old unit
instead of roof curb. Be careful not to damage ductwork when
removing old unit. Attach existing ductwork to roof curb
instead of unit.
Four lifting lugs are provided on the unit base rails as shown
in Fig. 5-16. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 5-16, around
and above unit to provide minimum distance from combustible
materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contaminated
air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air
for Combustion and Ventilation) of the National Fuel Gas
Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft
from any opening through which combustion products could
enter the building, and at least 4 ft from any adjacent building.
When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
ROOF MOUNT — Check building codes for weight distribution requirements. See Fig. 17. Unit operating weight is shown
in Table 2.
Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all
external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
NOTE: Due to width of the horizontal supply/return ductwork,
provisions should be made for servicing of the outdoor air filters (i.e., catwalk over ductwork).
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. Outlet grilles must not
lie directly below unit discharge. The return duct must have a
90-degree elbow before opening into the building space if the
unit is equipped with power exhaust.
To attach ductwork to roof curb, insert duct approximately
10 to 11 in. up into roof curb. Connect ductwork to 14-gage
roof curb material with sheet metal screws driven from inside
the duct.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree
elbow turn in the supply and return ductwork between the
unit and the conditioned space. If a 90-degree elbow cannot
be installed, then a grille of sufficient strength and density
should be installed to prevent objects from falling into the
conditioned space.
Step 4 — Make Unit Duct Connections
48AJ,AK,EJ,EK UNITS — Unit is shipped for through-thebottom duct connections. Field-fabricated ductwork should be
attached to theroof curb. Supply and return duct dimensions
are shown in Fig. 5-7 and 11-13. Air distribution is shown in
Fig. 18 and 19. Refer to installation instructions shipped with
roof curb for more information.
48AW,AY,EW,EY UNITS — Remove shipping covers from
supply and return air openings. Attach field-supplied ductwork
to unit. Connect to the unit with a single duct for all supply
openings and with a single duct for all return openings. Splitting of the airflow into branch ducts should not be done at the
unit. Sufficient duct length should be used prior to branching to
ensure the air temperatures are well mixed within the ductwork. See Fig. 8-10 and 14-16 for duct opening dimensions.
Secure all ducts to building structure. Air distribution is shown
in Fig. 8-10 and 14-16.
Install accessory barometric relief or power exhaust in the
field-fabricated return ductwork. Refer to Step 11 — Position
Power Exhaust/Barometric Relief Damper Hood section on
page 52 for more information.
Instructions continued on page 28.
2
Fig. 1 — Roof Curb — 48AJ,AK020-030 and 48EJ,EK024-034 Units
3
Fig. 2 — Roof Curb — 48AJ,AK034-050 and 48EJ,EK038-048 Units
4
Fig. 3 — Roof Curb — 48AJ,AK060 and 48EJ,EK054-068 Units
5
NOTES:
1. Unless otherwise specified, all dimensions are to outside of part.
2. Seal strip to be placed covering reference holes.
3. Phantom lines represent seal strip. Total length required is 75 linear ft.
length required is 62 linear ft.
self-tapping screws.
2.98″ at indoor motor end and 15.08″ at compressor end.
4. If existing seal strip around roof curb seems damaged, replace it. Total
5. Five crossrails are field located per dimensions shown and secured using
6. 48A and 48E series units will overhang existing “DD” or “DF” roof curbs by
7. Ductwork (field supplied) must be notched to clear three crossrails.
Fig. 4 — Roof Curb Adapter — (48AJ,AK060 and 48EJ,EK054-068 Units on 48DD,DF054-064 Retrofit, Part No. CRRCADPT005A00)
8. Dimensions in [ ] are millimeters.
6
1234
CORNER WEIGHT (lbs)
1082 1174 1502 1384
1126 1194 1494 1408
1135 1120 1516 1537
16
/
16
16
/
/
3
11
B
(ft-in.)
A
(ft-in.)
5
3-6
3-6
3-81103 1103 1511 1511
3-8
3-81123 1123 1539 1539
8
16
8
32
/
3
8
/
/
/
/
5
5
3
5
1234
1156 1140 1544 1565
16
/
5
3-8
32
/
3
5
CORNER WEIGHT (kg)
1156 1140 1544 1565
16
/
5
3-81123 1123 1539 1539
3-8
8
32
/
/
3
A (mm) B (mm)
(lbs)
WEIGHT*
OPERATING
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AJ (High Heat) 02052226- 1
48AJ (High Heat) 02553085-10
48AJ (High Heat) 02754055-10
48AJ/AK (Low Heat) 02051426- 0
48AJ/AK (Low Heat) 02552285- 9
48AJ (High Heat) 03054055-10
48AJ/AK (Low Heat) 02753255- 9
48AJ/AK (Low Heat) 03053255- 9
48AJ (High Heat) 020236918621085511 542 678 639
48AJ (High Heat) 025240817811125515 508 688 697
48AJ (High Heat) 027245217811125524 517 700 710
48AJ/AK (Low Heat) 020233218391072491 533 681 628
48AJ/AK (Low Heat) 025237117681118500 500 686 686
48AJ (High Heat) 030245217811125524 517 700 710
48AJ/AK (Low Heat) 027241517681118509 509 698 698
48AJ/AK (Low Heat) 030241517681118509 509 698 698
Fig. 5 — Base Unit Dimensions — 48AJ,AK020-030
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
NOTES:
1. Weights include economizer (standard).
Min Clearances to be:
2.Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be sup-
ported by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
6. Dimensions are in inches [mm].
7
1234
1380 1209 1595 1820
1447 1251 1607 1859
(ft-in.)
(ft-in.)
1442 1264 1779 2030
8
16
8
/
/
/
7
3
7
3-10
3-11
3-10
8
16
/
/
16
1
/
11
5
CORNER WEIGHT (lbs)
B
A
123 4
1512 1307 1787 2068
16
/
3
1
3-11
16
/
13
11
CORNER WEIGHT (kg)
1449 1294 1878 2104
1519 1337 1886 2142
16
/
2
/
13
3-10
3-10
16
/
16
/
3
A (mm) B (mm)
OPERATING
(lbs)
WEIGHT*
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AJ (High Heat) 03561647-10
48AJ (High Heat) 04066747-6
48AJ/AK (Low Heat) 03560047-8
48AJ (High Heat) 05068857-5
48AJ/AK (Low Heat) 04065147-5
48AJ/AK (Low Heat) 05067257-3
48AJ (High Heat) 035279623901199656 567 729 843
48AJ (High Heat) 040302723061199686 593 811 938
48AJ/AK (Low Heat) 035272323551191626 548 723 826
48AJ (High Heat) 050312322661189689 607 856 972
48AJ/AK (Low Heat) 040295522681191654 573 807 921
48AJ/AK (Low Heat) 050305022281181657 587 852 954
NOTES:
Fig. 6 — Base Unit Dimensions — 48AJ,AK035-050
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2.Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be supported
by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
6. Dimensions are in inches [mm].
8
BASE UNIT WEIGHTS
(See Note 6) lbs (kg)
AT EACH CORNER
% OF TOTAL WEIGHT
3242 1184 21.7 19.3 27.7 31.2
3422 1235 23.9 19.4 25.4 31.3
32
/
19
32
/
19
3-10
060
48AJD/AKD8930 (4051)
ft-in.Millimeters
CENTER OF GRAVITY
48AJE9170 (4159)
UNIT SIZE
16
/
11
AB A B1234
48AJD/AKD060 10-7
4-
16
/
11
48AJE06011-2
Fig. 7 — Base Unit Dimensions — 48AJ,AK060
on dunnage, it is recommended the ducts must be supported by cross braces as
done on accessory roof curb.
included). Add indoor motor, FIOPs and accessories for total operating weight.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted
NOTES:
1. Weights include economizer (standard).
VFD transducer and associated wiring.
6. Base unit weights include outdoor air hoods and filters (indoor fan motor is not
7. VAV motor weights include indoor motor, VFD, compressor electric unloaders,
8. Dimensions are in inches [mm].
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Filter Access Side: 15′-0″ [4572]. (For
charge facing economizer inlet.
Min Clearances to be:
2.Center of Gravity.
3. Do not locate adjacent units with flue dis-
removal of evaporator coil.)
ances contact Carrier Application Engineer-
ing Department.
4. For smaller service and operational clear-
9
1234
CORNER WEIGHT (lbs)
1090 1183 1514 1395
1134 1203 1505 1419
1144 1128 1527 1548
16
/
16
16
/
/
3
11
B
(ft-in.)
A
(ft-in.)
5
3-6
3-6
3-81111 1111 1523 1523
3-8
8
16
8
8
/
/
/
/
3
5
5
1
1234
1165 1149 1555 1577
16
/
5
3-81132 1132 1551 1551
3-8
8
8
/
/
5
1
5
CORNER WEIGHT (kg)
1165 1149 1555 1577
16
/
5
3-81132 1132 1551 1551
3-8
8
8
/
/
1
A (mm) B (mm)
OPERATING
(lbs)
WEIGHT*
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AW (High Heat) 02052626- 1
48AW (High Heat) 02553485-10
48AW (High Heat) 02754455-10
48AW/AY (Low Heat) 02051826- 0
48AW/AY (Low Heat) 02552685- 9
48AW (High Heat) 03054455-10
48AW/AY (Low Heat) 02753655- 9
48AW/AY (Low Heat) 03053655- 9
48AW (High Heat) 020238718621085515 546 683 644
48AW (High Heat) 025242617811125519 512 693 702
48AW (High Heat) 027247017811125528 521 705 715
48AW/AY (Low Heat) 020235118391072495 537 687 633
48AW/AY (Low Heat) 025239017681118504 504 691 691
48AW (High Heat) 030247017811125528 521 705 715
48AW/AY (Low Heat) 027243417681118513 513 704 704
48AW/AY (Low Heat) 030243417681118513 513 704 704
NOTES:
Fig. 8 — Base Unit Dimensions — 48AW,AY020-030
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2.Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
Application Engineering Department.
4. For smaller service and operational clearances contact Carrier
5. Dimensions are in inches [mm].
10
CORNER WEIGHT (lbs)
1234
1389 1217 1606 1832
1456 1259 1617 1871
1451 1271 1790 2042
1521 1315 1798 2080
1458 1301 1889 2117
1528 1345 1897 2155
16
8
16
/
/
B
7
3
(ft-in.)
3-10
3-11
16
/
8
/
11
1
A
(ft-in.)
/
8
16
2
/
/
/
7
3
1
13
3-10
3-11
3-10
3-10
16
16
16
/
/
/
16
/
11
13
11
3
CORNER WEIGHT (kg)
1234
A (mm)B (mm)
OPERATING
(lbs)
WEIGHT*
UNIT SIZE
(kg)
WEIGHT*
OPERATING
UNIT SIZE
48AW (High Heat) 03562047-10
48AW (High Heat) 04067147- 6
48AW/AY (Low Heat) 03560447- 8
48AW (High Heat) 05069257- 5
48AW/AY (Low Heat) 04065547- 3
48AW/AY (Low Heat) 05067657- 3
48AW (High Heat) 035281423901199661571734849
48AW (High Heat) 040304523061199690596816944
48AW/AY (Low Heat) 035274123551191630552728831
48AW (High Heat) 050314122661189693610860977
48AW/AY (Low Heat) 040297322681191658577812926
48AW/AY (Low Heat) 050306922281181661590857960
NOTES:
Fig. 9 — Base Unit Dimensions — 48AW,AY035-050
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Min Clearances to be:
1. Weights include economizer (standard).
2.Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet.
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
4. For smaller service and operational clearances contact Carrier Application Engineering Department.
5. Dimensions are in inches [mm].
11
% OF TOTAL WEIGHT
060
(See Note 6) lbs (kg)
BASE UNIT WEIGHTS
CENTER OF GRAVITY
48AWE9210 (4178)
48AWD/AYD8970 (4069)
AT EACH CORNER
19
ft-in.Millimeters
11
AB AB1234
UNIT SIZE
3242 1184 21.7 19.3 27.7 31.2
32
/
3-10
16
/
48AWD/AYD060 10-7
3422 1235 23.9 19.4 25.4 31.3
32
/
19
4-
16
/
11
48AWE06011-2
included). Add indoor motor, FIOPs and accessories for total operating weight.
5. Base unit weights include outdoor air hoods and filters (indoor fan motor is not
NOTES:
1. Weights include economizer (standard).
transducer and associated wiring.
6. VAV motor weights include indoor motor, VFD, compressor electric unloaders, VFD
2.Center of Gravity.
7. Dimensions are in inches [mm].
8. For side-supply/return applications, a single return and supply ductwork connection
charge facing economizer inlet.
3. Do not locate adjacent units with flue dis-
is recommended for covering all three return and all three supply openings. The
entire area around the duct openings is available for a 1.5″ duct flange attachment.
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Min Clearances to be:
Fig. 10 — Base Unit Dimensions — 48W,AY060
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
Filter Access Side: 15′-0″ [4572]. (For
removal of evaporator coil.)
ances contact Carrier Application Engineer-
ing Department.
4. For smaller service and operational clear-
12
NOTES:
Fig. 11 — Base Unit Dimensions — 48EJ,EK024-034
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2.Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be supported
by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
6. Dimensions are in inches [mm].
13
NOTES:
Fig. 12 — Base Unit Dimensions — 48EJ,EK038-048
Adjacent Units: 15′-0″ [4572].
Top of Units: No Overhang.
Condenser Coil: 4′-0″ [1219].
Economizer Side: 6′-0″ [1829].
Heat Side: 4′-0″ [1219].
inlet.
1. Weights include economizer (standard).
Min Clearances to be:
2.Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
Filter Access Side: 10′-0″ [3048]. (For removal of evaporator coil.)
cation Engineering Department.
mounted on dunnage, it is recommended the ducts must be supported
by cross braces as done on accessory roof curb.
4. For smaller service and operational clearances contact Carrier Appli-
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
CONDENSER COIL *Cross-Hatched
Quantity1111
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)33.333.333.333.3
CONDENSER FANPropeller Type
Nominal Cfm13,42013,42013,42013,420
Quantity...Diameter (in.)2...302...302...302...30
Motor Hp1111
EVAPORATOR COILCross-Hatched Copper Tubes, Aluminum Plate Fins
Tube Size (in.)
Rows...Fins/in.4...154...154...154... 5
Total Face Area (sq ft)31.731.734.734.7
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...20 X 152... 20 X 152... 20 X 152... 20 X 15
Type DriveBeltBeltBeltBelt
Nominal Cfm8,00010,00011,00012,000
Motor Hp510157.51015101520101520
Motor Frame Size184T215T254T213T215T254T215T254T256T215T254T256T
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm1200120012001200
Motor Pulley Pitch Diameter4.94.45.75.46.15.54.44.95.94.45.75.9
Nominal Motor Shaft Diameter (in.)11/
Fan Pulley Pitch Diameter (in.)12.48.69.112.411.18.79.48.18.79.09.18.7
Nominal Fan Shaft Diameter (in.)115/
Belt Quantity122112222222
Belt TypeBX56BX505VX530BX565VX5905VX570BX505VX5005VX530BX505VX5305VX530
Belt Length (in.)566353565957505053505353
Pulley Center Line Distance (in.)16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9
Factory Speed Setting (rpm)717924109677396211068481059118788410961187
CONDENSER COIL *Cross-Hatched
Quantity2222
Rows...Fins/in.3...154...154...154…15
Total Face Area (sq ft)58.366.766.7100
CONDENSER FANPropeller Type
Nominal Cfm27,06427,06427,06443,900
Quantity...Diameter (in.)4...304...304...306...30
Motor Hp1111
EVAPORATOR COILCross-Hatched Copper Tubes, Aluminum Plate Fins
Tube Size (in.)
Rows...Fins/in.4...156...156...154...17
Total Face Area (sq ft)34.731.331.348.1
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...20 X 152...20 X 152...20 X 153...20 X 15
Type DriveBeltBeltBeltBelt
Nominal Cfm14,00016,00020,00024,000
Motor Hp101520152025202530253040
Motor Frame Size215T254T25 6T254T256T284T256T284T286T284T286T324T
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm1200120013001200
Motor Pulley Pitch Diameter6.15.35.75.35.77.56.38.17.55.38.19.4
Nominal Motor Shaft Diameter (in.)13/
Fan Pulley Pitch Diameter (in.)13.79.59.59.59.511.111.112.511.19.112.513.6
Nominal Fan Shaft Diameter (in.)115/
Belt Quantity122222222332
Belt Type5VX6105VX5305VX5505VX5305VX5505VX5905VX5705VX6305VX5905VX5305VX6305VX650
Belt Length (in.)615355535559576359536365
Pulley Center Line Distance (in.)15.6-18.4 15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 14.6-17.6 14.6-17.6 15.2-17.5 14.7-17.2 14.2-17.0
Factory Speed Setting (rpm)77997610509761050118299311341182101911341214
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)31.731.731.731.7
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...20x152...20x152...20x152...20x15
Type DriveBeltBeltBeltBelt
Nominal Cfm8,00010,00011,00012,000
Motor Hp510†157.510†151015†201015†20
Motor Frame Size (Standard)S184TS215TD254TS213TS215TD254TS215TD254TS256TS215TD254TS256T
(High Efficiency)S184TS215TS254TS213TS215TS254TS215TS254TS256TS215TS254TS256T
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm1200120012001200
Motor Pulley Pitch Diameter4.94.45.75.46.15.54.44.95.94.45.75.9
Nominal Motor Shaft Diameter (in.)11/
Fan Pulley Pitch Diameter (in.)12.48.69.112.411.18.79.48.18.79.09.18.7
Nominal Fan Shaft Diameter (in.)115/
Belt, Quantity...Type1...BX56 2...BX50 2...5VX530 1...BX56 1...5VX570 2...5VX530 2...BX50 2...5VX500 2...5VX530 2...BX50 2...5VX530 2...5VX530
Belt, Length (in.)565053565957505053505353
Pulley Center Line Distance (in.)16.0-18.7 15.6-18.4 15.0-17.915.6-18.415.0-17.9 15.6-18.415.0-17.915.6-18.415.0-17.9
Factory Speed Setting (rpm)717924109677396211068481059118788410961187
Efficiency (Steady State) (%)82828282
Temperature Rise Range15-45/35-6515-45/35-6515-45/35-6515-45/35-65
Gas Pressure to Unit Range (in. wg)5-13.55-13.55-13.55-13.5
Manifold Pressure (in. wg)
Natural GasStd3.53.53.53.5
Liquid Propane Alt3.53.53.53.5
Gas Valve Quantity22 2 2
Field Gas Connection Size
(in.-FPT)1.51.51.51.5
HIGH-PRESSURE SWITCH (psig)
Cutout426426426426
Reset (Auto.)320320320320
LOW-PRESSURE SWITCH (psig)
Cutout77 7 7
Reset (Auto.)22222222
RETURN-AIR FILTERS (W x H x T)
Quantity...Size (in.)10...20 x 24 x 210...20 x 24 x 210...20 x 24 x 210...20 x 24 x 2
OUTDOOR-AIR FILTERS8...16 x 258...16 x 258...16 x 258...16 x 25
Quantity...Size (in.)4...20 x 254...20 x 254...20 x 254...20 x 25
POWER EXHAUSTDirect Drive, 3-Speed, Single-Phase Motor (Factory-Wired for High Speed) and Forward Curved Fan
Rows...Fins/in.3...153...154...15
Total Face Area (sq ft)34.734.734.7
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...20x152...20x152...20x15
Type DriveBeltBeltBelt
Nominal Cfm14,00016,00018,000
Motor Hp1015†201520†252025†30
Motor Frame Size (Standard)S215TD254TS256TD254TS256TS284TS256TS284TS286T
Motor Bearing TypeBallBallBall
Maximum Allowable Rpm120012001200
Motor Pulley Pitch Diameter6.15.35.75.35.77.56.38.17.5
Nominal Motor Shaft Diameter (in.)13/
Fan Pulley Pitch Diameter (in.)13.79.59.59.59.511.111.112.511.1
Nominal Fan Shaft Diameter (in.)115/
Belt, Quantity...Type1...5VX610 2...5VX5302...5VX5502...5VX5302...5VX5502...5VX5902...5VX5702...5VX6302...5VX590
Belt, Length (in.)615355535559576359
Pulley Center Line Distance (in.)15.6-18.415.0-17.915.0-17.914.6-17.615.0-17.914.6-17.6
Factory Speed Setting (rpm)77997610509761050118299311341182
Efficiency (Steady State) (%)828282
Temperature Rise Range10-40/30-6010-40/30-6010-40/30-60
Gas Pressure to Unit Range (in. wg)5-13.55-13.55-13.5
Manifold Pressure (in. wg)
Gas Valve Quantity22 2
Field Gas Connection Size
HIGH-PRESSURE SWITCH (psig)
Cutout426426426
Reset (Auto.)320320320
LOW-PRESSURE SWITCH (psig)
Cutout77 7
Reset (Auto.)222222
RETURN-AIR FILTERS (W x H x T)
Quantity...Size (in.)10...20 x 24 x 210...20 x 24 x 210...20 x 24 x 2
OUTDOOR-AIR FILTERS8...16 x 258...16 x 258...16 x 25
Quantity...Size (in.)4...20 x 254...20 x 254...20 x 25
POWER EXHAUSTDirect Drive, 3-Speed, Single-Phase Motor (Factory-Wired for High Speed) and Forward Curved Fan
*Circuit 1 uses the left condenser coil. Circuit 2 the right. All units have intertwined evaporator coils.
†Motor and drive shown will deliver approximately 2.5 in. wg net external static pressure. For more information see Table 3.
/8″-in. Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
17/
15/
8
17/
8
115/
17/
8
16
17/
8
17/
8
115/
21/
8
16
17/
8
17/
8
115/
21/
8
16
8
25
Table 2 — Operating Weights
48AJ,AK,AW,AY Units
UNIT
48AJD,AKD42874373439443945073551556287480
48AJE43674453447444745233567557887720
48AWD,AYD43274413443444345113555556687520
48AWE44074493451445145273571558287760
OPTION/
ACCE SSORY
Barometric Relief300300300300300300300450
Powe r Exhaust450450450450450450450675
Modulating Power Exhaust500500500500500500500725
Cu Tubing/Cu Fin Condenser Coil220220220220285285380651
Roof Curb (14-in. curb)365365365365410410410585
Barometric Relief300300300300300300300450450450450
Powe r Exhaust450450450450450450450675675675675
Modular Power Exhaust500500500500500500500725725725725
Cu Tubing/Cu Fin Condenser Coil220220220220285285380271407489651
Roof Curb (14-in. curb)365365365365410410410585585585585
024028030034038044048054058064068
024028030034038044048054058064068
BASE UNIT WEIGHTS (Lb)*
OPTION/ACCESSORY WEIGHTS (Lb)
CV MOTOR WEIGHTS (Lb)
MOTOR
HP
5
7.5
10
15
20
25
30
40
LEGEND
Cu— Copper
CV— Constant Volume
FIOP — Factory-Installed Option
HP— Horsepower
IFM — Indoor Fan Motor
VAV — Variable Air Volume
VFD — Variable Frequency Drive
*Outdoor-air hoods and filters included in base unit weights; indoor-
fan motors are NOT included.
UNIT
VOLTAGE
230/4607894
5757892
230/460107135
575107136
230/460118164
575118156
230/460150217
575150220
230/460212250
575212258
230/460240309
575240319
230/460283355
575283359
230/460372415
575372410
STANDARD
EFFICIENCY
IFM
HIGH
EFFICIENCY
IFM
VAV MOTOR WEIGHTS (Lb)
MOTOR
HP
5
7.5
10
15
20
25
30
40
NOTES:
1. Base unit weight includes outdoor-air hoods. Base unit weight
does NOT include indoor-fan motor. ADD indoor-fan motor,
FIOPs, and accessories for TOTAL operating weight.
2. The VAV motor weights include indoor fan motor and the VFD
(variable frequency drive), compressor electric unloaders, VFD
transducers, and associated wiring.
UNIT
VOLTAGE
230/460125141
575163177
230/460183211
575193222
230/460204250
575204242
230/460238305
575240310
230/460348386
575304350
230/460377446
575375454
230/460480552
575418494
230/460637680
575587625
STANDARD
EFFICIENCY
IFM
HIGH
EFFICIENCY
IFM
26
Table 3 — Evaporator Fan Motor Data
UNIT
SIZE
48AJ,AK,
AW,AY
020024
025028
027030
030034
035038
040044
050048
—054
—058
060064
—068
NOTES:
1. Motor shaft speed is 1750 rpm. The fan shaft diameter is 115/16 inches.
2. All indoor fan motors meet the minimum efficiency requirements
as established by the Energy Policy Act of 1992 (EPACT), effective
October 24, 1997.
48AJ,AK,AW,AY020-050 AND 48EJ,EK,EW,EY024-048
UNITS — Flue hood is shipped inside gas section of unit. To
install, secure flue hood to access panel. See Fig. 20A.
48AJ,AK,AW,AY060 AND 48EJ,EK,EW,EY054-068
UNITS — Flue hood and wind baffle are shipped inside gas
section of unit. To install, secure flue hood to access panel. Install the two pieces of the wind baffle over the flue hood. See
Fig. 20B.
NOTE: When properly installed, flue hood will line up with
combustion fan housing. See Fig. 21.
Fig. 21 — Combustion Fan Housing Location
Step 6 — Trap Condensate Drain — See Fig. 5-16
for drain location. Condensate drain is open to atmosphere and
must be trapped. Install a trapped drain at the drain location.
One 1-in. FPT coupling is provided inside the unit evaporator
section for condensate drain connection. A trap at least 4-in.
deep must be used. See Fig. 22. Trap must be installed to prevent freeze-up.
Condensate pans are sloped so that water will completely
drain from the condensate pan to comply with indoor air quality guidelines. The condensate drain pans are not insulated.
Fig. 20A — Flue Hood Location
(48AJ,AK,AW,AY020-050 and
48EJ,EK,EW,EY024-048 Units)
FLUE HOOD
WIND
BAFFLE
TOP VIEWSIDE VIEW
Fig. 20B — Flue Hood Location
(48AJ,AK,AW,AY060 and
48EJ,EK,EW,EY054-068 Units)
GAS SECTION
ACCESS PANEL
Fig. 22 — Condensate Drain Trap Piping Details
(Typical Roof Curb or Slab Mount Shown)
Step 7 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local
building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.
Install manual gas shutoff valve with a
tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 23. An
also located on the gas manifold adjacent to the gas valve.
Do not pressure test gas supply while connected to unit.
Always disconnect union before servicing.
1
/8-in. NPT pressure
1
/8-in. NPT is
28
IMPORTANT: Natural gas pressure at unit gas connection
must not be less than 5 in. wg or greater than 13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
Fig. 23 — Field Gas Piping
Table 4 — 48A,E Series Staged Gas Implementation
OPTIONAL STAGED GAS UNITS — The staging pattern
is selected based on Heat Stage Type (HTSTGTYP). Max
Capacity per changes default value is selected based on Capacity Maximum Stage (CAPMXSTG). See Table 4.
For complete information and service instructions for
Staged Gas Control Units, see Control Operation and Troubleshooting literature.
Step 8 — Controls Options — The control options
that the units can provide are based on the following parameters: CV (constant volume) or VAV (variable air volume) operation; stand-alone unit with field-supplied sensors installed
(CV or VAV); as a system via Carrier Comfort System (TEMP
or VVT® [Variable Volume and Temperature]); optional electronic expansion board installed (CV or VAV); linked to the
Carrier Comfort Network; availability of a computer and software (ComfortWORKS® Building Supervisor, and Service
Tool) or remote enhanced display accessory installed to access
the base control board; and optional factory-installed staged
gas control. See Table 5.
NOTE: Access to the base control board allows unit occupancy schedules, unit timeclock, and various set points to be
changed from their factory-defined default settings.
NUMBER OF STAGES
5 stages
7 stages
9 stages
11 stages
MODEL NUMBER POSITIONPOSITION
356,7,8HTSTGTYPCAPMXSTG
024
028
ES
AS
ET
AT
ET
AT
ET
AT060Default=3Default=15High
ES
AS060Default=4Default=15Low
030
034
038
044
048
020
025
027
030
035
040
050
038
044
048
035
040
050
024
028
030
034
020
025
027
030
054
058
064
068
054
058
064
068
Default=1Default=20Low
Default=1Default=20Low
Default=1Default=20High
Default=1Default=20High
Default=2Default=15High
Default=2Default=15High
Default=3Default=15High
Default=4Default=15Low
HEAT SIZE
29
Table 5 — Controls Options and Configurations (Non-Thermostat Applications)
UNIT CONFIGURATIONDEFAULT COOLINGDEFAULT HEATING
CV or VAV Unit with SPT Sensor
CV Unit with SPT Sensor and Remote
Start/Stop Switch
VAV Unit Remote Start/Stop Switch Only
VAV Unit with SPT Sensor and Remote
Start/Stop Switch
LEGEND
CV— Constant Volume
NA— Not Available
RAT — Return-Air Temperature
SAT — Supply-Air Temperature
SPTSpace Temperature
VAV — Variable Air Volume
*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled).
NOTE: Space temperature sensor and remote start/stop switch are field-supplied.
Unoccupied Cooling — 90 F (32 C) (SPT)
Occupied Cooling — NA
Unoccupied Cooling — 90 F (32 C) (SPT)
Occupied Cooling — 78 F (26 C) (SPT)
Unoccupied Cooling — 90 F (32 C)(SPT)
Occupied Cooling — 55 F (13 C) SPT)
Unoccupied Cooling — 90 F (32 C) (SPT)
Occupied Cooling — 55 F (13 C) (SAT)
Unoccupied Heating — 55 F (13 C) (SPT)
Occupied Heating — NA
Unoccupied Heating — 55 F (13 C) (SPT)
Occupied Heating — 68 F (20 C) (SPT)
Unoccupied Heating — 55 F (13 C) (RAT)
Occupied Heating — 68 F (20 C) (RAT)*
Unoccupied Heating — 55 F (13C) (SPT)
Occupied Heating — 68 F (20 C) (RAT)*
STAGED GAS UNIT APPLICATIONS — The rooftop units
may be ordered with an optional factory-installed staged gas
control system that monitors heating operation of the rooftop
unit.
IMPORTANT: An accessory field-supplied Navigator display module is required for all staged gas control units.
Install Supply-Air Thermistors (Staged Gas Units Only)
—
Supply-air thermistors are a field-installed factory-provided
component. Three supply-air thermistors are shipped with
staged gas units and are inside the heating section. Thermistor
wires must be connected to SGC (staged gas controller) in the
heating section. See Table 6 and Fig 24. The supply-air thermistors should be located in the supply duct with the following
criteria:
• downstream of the heat exchanger cells
• equally spaced as far as possible from the heat exchanger
cells
• a duct location where none of the supply air thermistors
are within sight of the heat exchanger cells
• a duct location with good mixed supply air portion of the
unit.
Table 6 — Thermistor Designations
THERMISTORS — All units are equipped with a supply air
thermistor (SAT) located in the supply fan discharge and an
outdoor air thermistor (OAT) located in the outdoor air hood.
Variable air volume (VAV) units are supplied with a return air
thermistor (RAT) located on the return air damper support.
CONSTANT VOLUME APPLICATIONS — The units, as
shipped, are operable as stand-alone units, using either a standard (mechanical or electronic) 2-stage heat, 2-stage cool thermostat, or with an electronic room sensor and a timeclock to
establish unit start and stop times.
With a standard thermostat (programmable is optional),
heating and cooling operation is set by space temperature.
With a space sensor and timeclock, the machine will operate
at default values unless they are changed using appropriate input devices. The space sensor senses space temperature and
may be equipped with a timed override feature, which allows
unit operation during unoccupied periods.
The space sensors may be used in multiples of 4 or 9 to
achieve space temperature averaging. The use of a space sensor
also allows the unit to be turned on and off from a remote
signal.
THERMISTOR
SAT 1J8 – 1,2 (SGC)
SAT 3J8 – 5,6 (SGC)
CONNECTION
POINT
PIN
FUNCTION AND LOCATION
Thermistors
Supply Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided, field-installed)
Supply Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided, field-installed)
Supply Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided, field-installed)
30
PART NO.
HH79NZ016SAT 2J8 – 3,4 (SGC)
Loading...
+ 88 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.