Carrier 48-50PD05 User Manual

Page 1
48/50PD05,06 Single Package Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling/Gas Heating with PURONR (R--410A) Refrigerant and COMFORTLinkt 1.x Controls
Controls, Start--Up, Operation, Service and
Troubleshooting Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2.........................
GENERAL 3.........................................
BASIC CONTROL USAGE 3...........................
ComfortLinkt Control 3..............................
Scrolling Marquee 3..................................
Accessory Navigator Display 3..........................
Operation 3.........................................
System Pilott Device 4...............................
CCN Tables and Display 4.............................
Conventions Used in This Manual 5......................
START--UP 5.........................................
Unit Preparation 5....................................
Compressor Mounting 5...............................
Refrigerant Service Ports 5.............................
Crankcase Heater(s) 5.................................
Compressor Rotation 5................................
Power Supply 6.....................................
Internal Wiring 6.....................................
Evaporator Fan 6....................................
Condenser Fans and Motors 6...........................
Return--Air Filters 6..................................
Outdoor--Air Inlet Screens 6............................
Accessory Installation 7...............................
Orifice Change (48PD Only) 7..........................
Gas Heat (48PD Only) 7...............................
CONTROLS QUICK SET--UP 7.........................
Control Set Point and Configuration Log 7................
Standard Unit Control 7...............................
CCN Communication 8...............................
Accessories 8.......................................
Programming Operating Schedules 10....................
SERVICE TEST 10....................................
Independent Outputs 10...............................
Fan Test 10.........................................
Cooling Test 11.....................................
Heating Test 11......................................
THIRD PARTY CONTROL 11..........................
Remote Occupancy 11................................
Fire Shutdown 11....................................
Alarm Output 11.....................................
Economizer Monitoring 11.............................
Economizer Damper Control 11.........................
CONTROLS OPERATION 11...........................
Display Configuration 11..............................
Modes 12..........................................
Unit Configuration 12.................................
General Operating Sequence 13.........................
Occupancy Determination 13
Compressor Operation 14..............................
Indoor Fan Operation 14...............................
Outdoor Fan Operation 15.............................
Economizer Operation 15..............................
Indoor Air Quality (IAQ) 16............................
Cooling Modes 17...................................
Heating Modes 20....................................
Temperature Compensated Start 22.......................
Carrier Comfort Network (CCN)R Configuration 23.........
Demand Limit 23....................................
Alarm Handling 24...................................
TROUBLESHOOTING 2 4..............................
Complete Unit Stoppage 24............................
Restart Procedure 24..................................
Control Module Communication 24......................
Communication Failures 25............................
Alarms and Alerts 25.................................
Cooling Troubleshooting 30............................
Digital Scroll Controller (DSC) Troubleshooting 31..........
Economizer Troubleshooting 33.........................
Heating Troubleshooting 34............................
Variable Frequency Drive (VFD) Troubleshooting 34........
Phase Loss Protection 34..............................
Thermistor Troubleshooting 37.........................
Transducer Troubleshooting 38.........................
Forcing Inputs and Outputs 38..........................
MAJOR SYSTEM COMPONENTS 42....................
General 42.........................................
Main Base Board (MBB) 47............................
Economizer Control Board (ECB) 49.....................
Modulation Board (AUX1) 51..........................
Digital Scroll Control Board (DSC) 52....................
...........................
Page 2
Variable Frequency Drive (VFD) 53......................
Integrated Gas Control (IGC) Board 54...................
Low Voltage Terminal Strip (TB1) 55.....................
Scrolling Marquee Display 56..........................
Accessory Navigatort Display 56.......................
Carrier Comfort Network (CCN)R Interface 56.............
Field--Installed Accessories 56..........................
SERVICE 59.........................................
Cleaning 60........................................
Lubrication 62......................................
Evaporator Fan Service and Replacement 62...............
Evaporator Fan Performance Adjustment 62...............
Evaporator Fan Belt Tension Adjustment 63...............
Variable Frequency Drive (VFD) Replacement 63...........
Condenser--Fan Adjustment 63..........................
Verify Sensor Performance 64..........................
48/50PD
Economizer Operation During Power Failure 64............
Evacuation 64.......................................
Refrigerant Charge 64.................................
Gas Valve Adjustment (48PD Units Only) 65...............
High Altitude (48PD Units Only) 66.....................
Main Burners (48PD Units Only) 66.....................
Filter Drier 66.......................................
Protective Devices 66.................................
Relief Devices 67....................................
Compressor Sound Shield 67...........................
Control Circuit, 24--V 67..............................
Replacement Parts 67.................................
Diagnostic LEDs 67..................................
APPENDIX A -- LOCAL DISPLAY AND
CCN TABLES 68.....................................
APPENDIX B -- STARTUP DATA 81.....................
APPENDIX C -- ADDITIONAL STARTUP DATA 91.........
APPENDIX D -- ADDITIONAL STARTUP DATA 100.......
UNIT START--UP CHECKLIST 105......................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions of replacing filters. Trained service personnel should perform all other operations.
When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Follow all safety codes. Wear safety glasses and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may cause equipment damage.
This unit uses a microprocessor--based electronic control system. Do not use jumpers or other tools to short out components or to bypass or otherwise depart from recommended procedures. Any short--to--ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in your building.
3.IMMEDIATELY call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
.
2
Page 3
GENERAL
This publication contains Start--Up, Controls, Operation, Service, and Troubleshooting information for the 48/50PD rooftop units. (See Table 1.) These units are equipped with ComfortLinkt controls version 1.X or higher and use Puronr refrigerant. The specific base unit installation instructions and/or wiring label diagram may also be required in conjunction with this book as a guide to a specific unit on the roof. All the units in Table 1 are Displacement Ventilation or Single Zone Variable Airflow units that provide stand--alone or network operation.
Table 1 — Rooftop Units
MODEL SIZE NOMINAL TONS
48/50PD
05 4 06
5
BASIC CONTROL USAGE
ComfortLink Control
The ComfortLink control is a comprehensive unit-management system. The control system is easy to access, configure, diagnose and troubleshoot.
The ComfortLink control is fully communicating and cable-ready for connection to the Carrier Comfort Network® (CCN) building management system. The control provides high-speed communications for remote monitoring via the Internet. Multiple units can be linked together (and to other ComfortLink control equipped units) using a 3-wire communication bus.
The ComfortLink control system is easy to access through the use of a unit-mounted display module. There is no need to bring a separate computer to this unit for start-up. Access to control menus is simplified by the ability to quickly select from 11 menus. A scrolling readout provides detailed explanations of control information. Only four, large, easy-to-use buttons are required to maneuver through the entire controls menu. The display readout is designed to be visible even in bright sunlight.
For added service flexibility, an accessory hand-held Navigatormodule is also available. This portable device has an extended communication cable that can be plugged into the unit’s communication network at the main control box. The Navigator display provides the same menu structure, control access and display data as is available at the unit-mounted Scrolling Marquee display.
S Service Test S Temperatures S Pressures S Set points S Inputs S Outputs S Configuration S Timeclock S Operating Modes S Alarms
Through the Scrolling Marquee, the user can access all of the inputs and outputs to check on their values and status, configure operating parameters plus evaluate the current decision status for operating modes. The control also includes an alarm history which can be accessed from the display. In addition, through the Scrolling Marquee, the user can access a built-in test routine that can be used at start-up commissioning and to diagnose operational problems with the unit.
Accessory Navigator Display
The accessory hand-held Navigator display can be used with the 48/50PD units. (See Fig. 2.) The Navigator display operates the same way as the Scrolling Marquee device. The Navigator display is plugged into the LEN (local equipment network) port on either TB1 or the J3 port on the ECB (economizer control board).
C
o
m
f
o
r
t
L
N
in
A
V
I
k
G
A
T
O
T
IM
E
W
L
W
S
E
T
M
O
D
Ru
n Sta
S
e
rv
ice
T
em
p
era
P
res
s
ure
s
S
e
tpo
in
ts
In
pu
ts
O
utp
uts
C
on
fig
u
ra
tion
T
im
e C
lo
ck
O
p
er
ating
M
od
es
A
la
rm
s
E
N
T
E
R
R
E
1
2
T
.
5
8
5
4
T
.
6
°
F
4
4
P
.1
°
F
4
4
.
0
°
F
E
Ala
rm
Sta
tus
tu
s
Te
s
t
ture
s
E
S
C
48/50PD
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ESCAPE
ENTER
C06320
Fig. 1 -- Scrolling Marquee
Scrolling Marquee
This device is the keypad interface used to access the control information, read sensor values, and test the unit. The Scrolling Marquee is located in the main control box and is standard on all units. The Scrolling Marquee display is a 4-key, 4-character, 16-segment LED (light-emitting diode) display module. The display also contains an Alarm Status LED. (See Fig. 1.)
The display is easy to operate using 4 buttons and a group of 11 LEDs that indicate the following menu structures:
S Run Status
C06321
Fig. 2 -- Accessory Navigator Display
Operation
All units are shipped from the factory with the Scrolling Marquee display, which is located in the main control box. (See Fig. 1.) In addition, the ComfortLink control also supports the use of the handheld Navigator display.
Both displays provide the user with an interface to the ComfortLink control system. The displays have up and down arrow keys, an ESCAPE key and an ENTER key. These keys are used to navigate through the different levels of the display structure. The Navigator display and the Scrolling Marquee operate in the same manner, except that the Navigator display has multiple lines of display and the Scrolling Marquee has a single line. All further discussions and examples in this document will be based on the Scrolling Marquee display. See Table 2 for the menu structure.
The four keys are used to navigate through the display structure, which is organized in a tiered mode structure. If the buttons have not been used for a period, the display will default to the AUTO VIEW display category as shown under the RUN STATUS category. To show the top-level display, press the ESCAPE key until a blank display is shown. Then use the up and
3
Page 4
down arrow keys to scroll through the top-level categories. These are listed in Appendix A and will be indicated on the Scrolling Marquee by the LED next to each mode listed on the face of the display.
When a specific mode or sub-mode is located, push the ENTER key to enter the mode. Depending on the mode, there may be additional tiers. Continue to use the up and down keys and the ENTER keys until the desired display item is found. At any time, the user can move back a mode level by pressing the ESCAPE key. Once an item has been selected the display will flash showing the item, followed by the item value and then followed by the item units (if any).
Items in the Configuration and Service Test modes are password protected. The display will flash PASS and WORD when required. Use the ENTER and arrow keys to enter the four digits of the password. The default password is 1111.
Pressing the ESCAPE and ENTER keys simultaneously will scroll an expanded text description across the display indicating the full meaning of each display point. Pressing the ESCAPE and ENTER keys when the display is blank (MODE LED level) will return the display to its default menu of rotating AUTO VIEW display items.
48/50PD
In addition, the password will need to be entered again before changes can be made.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. If the display is in rotating auto-view, press the ENTER key to stop the display at the desired item. Press the ENTER key again so that the item value flashes. Use the arrow keys to change the value of state of an item and press the ENTER key to accept it. Press the ESCAPE key and the item, value or units display will resume. Repeat the process as required for other items.
There are some points that can be forced from the Scrolling Marquee or the Navigator. If the user needs to force a variable, follow the same process as when editing a configuration parameter. A forced variable, regardless where the force has come from will be displayed with a blinking “.” on a Scrolling Marquee and a blinking “f” on a Navigator following its value. For example, if
economizer commanded position (EC.CP) is forced, the Navigator display shows “80f”, where the “f” is blinking to signify a force on the point. The Scrolling Marquee display shows “80.” Where the “.” is blinking to signify a force on the point. Remove the force by selecting the point that is forced with the key ENTER and then pressing the up and down arrow keys simultaneously.
Depending on the unit model, factory-installed options and field-installed accessories, some of the items in the various Mode categories may not apply.
System Pilott and Touch Pilot Devices
The System Pilot device (33PILOT--01) and Touch Pilot device (33CNTPILOT) can be used as CCN communication user--interfaces. These devices can be put on the CCN bus and addressed to communicate with any other device on the network. Unlike the Scrolling Marquee and Navigator, these pilots read the 48/50PD’s CCN tables and the units CCN points can be monitored, forced, or configured.
IMPORTANT: Multiple zoning application is NOT recommended at this time with the PD products.
Additionally, the System Pilot device can serve as a wall--mounted temperature sensor for space temperature measurement. The occupant can use the System Pilot device to change set points. A security feature is provided to limit access of features for unauthorized users. See Fig. 3 for System Pilot device details.
CCN Tables and Display
In addition to the unit--mounted Scrolling Marquee display, the user can also access the same information through the CCN tables by using the Service tool or other CCN programs/devices. The variable names used for the CCN tables and the Scrolling Marquee menus may be different and more items may be displayed in the CCN tables. Details on the CCN tables are included with the local display menus in Appendix A. Appendix A is structured towards the organization of the local display (Scrolling Marquee) menus. Because of the variety of CCN programs and devices, the CCN tables, sub-- tables, and points are referenced within that organization.
RUN
STATUS
Auto View
of
Run Status
(VIEW)
Software
Version
Numbers
(VERS)
Control
Modes
(MODE)
Cooling
Status
(COOL)
Heating
Status
(HEAT)
Economizer
Status
(ECON)
Component
Run Hours
(HRS)
Component
Starts
(STRT)
SERVICE
TEST
Service Test
Mode
(TEST)
Test Independent
Outputs
(INDP)
Tes t Fa n s
(FANS)
Test Cooling
(COOL)
Test Heating
(HEAT)
Table 2 — Scrolling Marquee Mode and Menu Display Structure
TEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURATION
Air
Temperatures
(AIR.T)
Refrigerant
Temperatures
(REF.T)
General
Inputs
(GEN.I)
Current
Sensor Inputs
(CS.IN)
Air Quality
Inputs
(AIR.Q)
Fan Outputs (FANS)
Cool Outputs (COOL)
Heat Outputs (HEAT)
Economize
r Outputs (ECON)
Alarm
Relay
(ALRM)
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Cooling
Configuration
(COOL)
Heating
Configuration
(HEAT)
Economizer
Configuration
(ECON)
Air Quality
Cfg.
(AIR.Q)
Alarm Relay
Config.
(ALM.O)
PID
Configuration
(PID)
Sensor
Calibration
(TRIM)
CCN
Configuration
(CCN)
TIME
CLOCK
Tim e o f Da y
(TIME)
Month, Date
Day an d
Year
(DATE)
Daylight
Savings
Tim e
(DST)
Local Time
Schedule (SCH.L)
Local
Holiday
Schedules
(HOL.L)
OPERATIN
G
MODES
Control
Modes
(MODE)
Cool Mode
Diagnostic
(COOL)
Heat Mode
Diagnostic
(HEAT)
Economizer
Diagnostic
(ECON)
Demand
Listing
(DMD.L)
ALARMS
Reset All
Current Alarms
(R.CURR)
Reset
Alarm
History
(R.HIST)
Currently
Active
Alarms
(CURR)
Alarm
HIstory
(HIST)
4
Page 5
NAVIGATE/
/
EXIT
SCROLL
Fig. 3 -- System Pilott User Interface
+
-
PAGE
MODIFY SELECT
C06322
Force Hierarchy
There is a hierarchy in CCN with regards to forcing a point. Programs and devices write a force at different priority levels. A higher level (smaller number, 1 being the highest) will override a lower level force. The Scrolling Marquee uses a Control Force at level 7. The Navigator writes a Service Force which is level 3. System Pilots and Touch Pilots write Supervisor Forces at level 4. Network programs can be set to write different level priority forces.
Generic Status Display Table
The GENERIC points table allows the service/installer the ability to create a custom table in which up to 20 points from the 5 CCN categories (Points, Config, Service--Config, Set Point, and Maintenance) may be collected and displayed.
In the Service-- Config table section, there is a table named “GENERICS.” This table contains placeholders for up to 20 CCN point names and allows the user to decide which points are displayed in the GENERIC points sub--table under the status display table. Each one of these placeholders allows the input of an 8--character ASCII string. Using a CCN interface, enter the Edit mode for the Service--Config table “GENERICS” and enter the CCN name for each point to be displayed in the custom points table in the order they will be displayed. When done entering point names, download the table to the rooftop unit control.
IMPORTANT: The computer system software (ComfortVIEWt, Service Tool, etc.) that is used to interact with CCN controls, always saves a template of items it considers as static (e.g., limits, units, forcibility, 24--character text strings, and point names) after the software uploads the tables from a control. Thereafter, the software is only concerned with run time data like value and hardware/force status. With this in mind, it is important that any time a change is made to the Service--Config table “GENERICS” (which in turn changes the points contained in the GENERIC point table), that a complete new upload be performed. This requires that any previous table database be completely removed first. Failure to do this will not allow the user to display the new points that have been created and the CCN interface will have a different table database than the unit control.
Conventions Used in This Manual
The following conventions for discussing configuration points for the local display (Scrolling Marquee or Navigatoraccessory) will be used in this manual.
Point names will be written with the Mode name first, then any submodes, then the point name, each separated by an arrow symbol (). Names will also be shown in bold and italics. As an example, the Fan Status Switch which is located in the Configuration mode, and Unit sub-mode would be written as Configuration
UNITFN.SW.
This path name will show the user how to navigate through the local display to reach the desired configuration. The user would scroll through the modes and sub-modes using the up and down keys. The arrow symbol in the path name represents pressing ENTER to move into the next level of the menu structure.
When a value is included as part of the path name, it will be shown at the end of the path name after an equals sign. If the value represents a configuration setting, an explanation will be shown in parenthesis after the value. As an example, ConfigurationUNITFN.SW = 1 (Normal Open).
Pressing the ESCAPE and ENTER keys simultaneously will scroll an expanded text description of the point name across the display. The expanded description is shown in the local display tables but will not be shown with the path names in text.
The CCN point names are also referenced in the local display tables for users configuring the unit with CCN software instead of the local display. See Appendix A of this manual.
START-UP
IMPORTANT: Do not attempt to start unit, even momentarily,
until all items on the Start--Up Checklist (last page) and the following steps have been completed.
Unit Preparation
Check that unit has been installed in accordance with these installation instructions and all applicable codes.
Compressor Mounting
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
Refrigerant Service Ports
Each independent refrigerant system has a total of 3 Schrader-type service gauge ports per circuit. One port is located on the suction line, one on the compressor discharge line, and one on the liquid line. Be sure that caps on the ports are tight.
Crankcase Heater(s)
Compressor crankcase heater operation varies depending on the unit size and type. In general for all units, the crankcase heaters are energized if there is power to the unit, the compressor is not operating, and the ambient temperature is below 75_F.
IMPORTANT: Unit power must be on for 24 hours prior to start--up. Otherwise, damage to compressor may result.
Compressor Rotation
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
Improper wiring will cause compressor stoppage and alarm. Correct wiring by switching leads as indicated below.
48/50PD
5
Page 6
CONTROL BOX
AND
COMPRESSOR
ELECTRICAL
OPTIONS PANEL
OUTDOOR AIR
SCREEN
(HIDDEN)
48/50PD
INDOOR MOTOR
ACCESS DOOR
GAS SECTION ACCESS
CONDENSER COIL ACCESS PANEL
BASEPAN CONNECTIONS
ACCESS PANEL
Fig. 4 -- Panel and Filter Locations
On 3-phase units, it is important to be certain the compressors are rotating in the proper direction. To determine whether or not compressors are rotating in the proper direction, use a phase-rotation meter on the unit input power to check for L1-L2-L3 or clockwise rotation or use the Service Test mode to energize a compressor. If the compressor is rotating in the wrong direction, the controls will stop the compressor and display alarm for “Circuit A Failure to Pressurize.”
IMPORTANT: Indoor or outdoor fan rotation direction may not indicate proper input power phase sequence, as some 3-phase units use single-phase fan motors.
To correct the wrong compressor rotation direction, perform the following procedure:
1. Turn off power to the unit and lock out the power.
2. Switch any two of the incoming unit power leads.
3. Turn on power to the unit.
4. Verify corrected compressor rotation.
Power Supply
All 208/230-v units are factory wired for 230-v power supply. If the 208/230-v unit is to be connected to a 208-v power supply, the transformers (TRAN1 and TRAN2) must be rewired by moving the wire from the 230-volt connection and moving to the 200-volt terminal on the primary side of the transformer. Refer to unit label diagram for additional information.
Internal Wiring
Check all electrical connections in unit control boxes; tighten as required.
Evaporator Fan
Fan belt and variable pulleys are factory-- installed, but may need to be adjusted for specific applications. Be sure that the fans rotate in the proper direction. See Appendix C for unit specific fan performance data. See Appendix D for unit specific air quality
FILTER ACCESS DOOR
C07002
limits, evaporator fan motor specifications, FIOP static pressures, and fan RPM for various motor pulley settings. Appendix C and D are based on 100% fan speed (VFD at 60Hz). To alter fan performance, see Evaporator Fan Performance Adjustment in the Service section.
The Supply Fan Minimum Speed (ConfigurationUNITFS.MN) and the Supply Fan Maximum Speed (ConfigurationUNITFS.MX) can also be used to alter fan performance. The fan should run at the maximum fan speed when setting up the application design point. The unit is equipped with a Variable Frequency Drive (VFD). The VFD’s settings should not be used for adjusting fan performance. Specific VFD information can be found in Appendix B.
IMPORTANT: When setting up and starting the unit, the heating minimum CFM requirements must be upheld when changing belts, pulleys, and configurations. During heating mode, the fan speed is always set to Supply Fan Maximum Speed (FS.MX).
Condenser Fans and Motors
Condenser fans and motors are factory set. Refer to Condenser-Fan Adjustment section as required.
Return--Air Filters
Check that correct filters are installed in filter tracks (see Physical Data table in Installation Instructions). Do not operate unit without return-air filters.
IMPORTANT: For units with 4-in. filter option, units are shipped with standard 2-in. filters. To install 4-in. filters, the filter spacers must be removed.
Outdoor--Air Inlet Screens
Outdoor-air inlet screens must be in place before operating unit.
6
Page 7
Accessory Installation
Check to make sure that all accessories including sensors have been installed and wired as required by the instructions and unit wiring diagrams.
Orifice Change (48PD Only)
This unit is factory assembled for heating operation using natural gas at an elevation from sea level to 2000 ft.
Use accessory high altitude kit when installing this unit at an elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer to High Altitude section to identify the correct orifice size for the elevation. Purchase these orifices from your local Carrier dealer. Follow instructions in accessory Installation Instructions to install the correct orifices.
Use accessory LP (liquid propane) gas conversion kit when converting this unit for use with LP fuel usage for elevations up to 7000 ft. For elevations above 7000 ft, refer to High Altitude section to identify the correct orifice size for the elevation. Purchase these orifices from your local Carrier dealer. Follow instructions in accessory Installation Instructions to install the correct orifices.
Gas Heat (48PD Only)
Verify gas pressures before turning on heat as follows:
1. Turn off field-supplied manual gas stop, located external to unit.
2. Connect pressure gauge to supply gas tap, located on field-supplied manual shutoff valve. (See F ig. 5.)
3. Connect pressure gauge to manifold pressure tap.
4. Turn on field-supplied manual gas stop. Enter Service Test mode by setting Service TestTEST to “ON” using the Scrolling Marquee display. Use the Service Test feature to set Service TestHEATHT.1 to ON (first stage of heat) using the Scrolling Marquee.
C06323
Fig. 5 -- Field Gas Piping
5. After the unit has run for several minutes, verify the supply gas pressure is between 5.5--in. wg to 13.0-- in. wg, and the manifold pressure is 3.50--in. wg on sizes 03-- 14 and 3.00 on size 16. If manifold pressure must be adjusted, refer to Gas Valve Adjustment section.
IMPORTANT: Supply gas pressure must not exceed 13.0--in. wg.
6. Set Service TestHEATHT.1 to OFF using Scrolling Marquee.
7. Exit Service Test mode by setting Service TestTEST to “OFF” using the Scrolling Marquee.
CONTROLS QUICK SET--UP
The following information will provide a quick guide to setting up and configuring the 48/50PD series units with ComfortLink controls. Unit controls are pre-configured at the factory for factory-installed options. Field-installed accessories will require configuration at start-up. Service Test is recommended for initial start--up. Additionally, specific job requirements may require changes to default configuration values. See the CCN and Display parameter tables and other sections of these instructions for more details.
Control Set Point and Configuration Log
During start up, accessory installation, and equipment service set points and/or configuration changes might have to be made. When setting set points or changing configuration settings, documentation is recommended. The Control Log starting on page 106 should be filled out and left with the unit at all times. A copy should also be provided to the equipment owner.
Standard Unit Control
There are two different applications these units can be applied to, Displacement Ventilation and Single Zone VAV. F o r ei th er application a direct wired space sensor can be used or a communicating sensor/thermostat can be used. Installation of an accessory supply air temperature (SAT) sensor in the supply duct is recommended when using a communication type control. A supply duct SAT measurement is valid for heating mode display, while the factory--standard internal SAT is not valid for heating due to its location upstream of the heating section. When installing the supply duct SAT, the heating mode display is enabled by setting ConfigurationHEATSATSAT.H to ENBL.
There are several configurations that should be considered for Displacement Ventilation or Single Zone VAV applications. Table 3 shows these configuration defaults and specific application settings. These settings typical values and should be adjusted for each actual specific unit application. Refer to the Operation section for more detail on these configurations and how they effect the units operation.
IMPORTANT: Multiple zoning application is not recommended at this time with the PD product.
Space Temperature Sensor Control—Direct Wired (T--55, T--56, or
Wire accessory space temperature sensor(s) to the T--55 terminals on the field connection terminal board located at the unit control box. No configuration is required when installing a T--55, T--56, or T--59. Refer to Field-Installed Accessories section for additional information.
T--58 Communicating Thermostat
Install the T -- 58 communicating thermostat. Connect the CCN communication bus from the T--58 to the CCN terminals on the field connection terminal board located at the unit control box. Configure the unit’s CCN communication element number, bus number, and baud rate. Configure the T --58’s CCN communication bus number and baud rate the same as the unit, while the element number has to be different. Configure the T--58 to send SPT to the unit’s element number. Refer to the Field--Installed Accessories section for additional information.
T--59)
48/50PD
7
Page 8
Table 3 — Application Specific Configurations
ITEM EXPANSION DEFAULT UNITS
SASP Cool Supply Air Setpoint 65 dF 65 55
FS.MX Supply Fan Maximum Speed 100 % 100 100
FS.MN Supply Fan Maximum Speed 20 % 20 70
FS.VM Vent Mode Fan Speed 50 ∧F 50 50
MIN.C Min Compressor Capacity 70 % 15 70
FS.CD Fan Speed Control Demand 3 F 3 3
SA.MU SASP Maximum Reset Up 10 ∧F 3 5
SA.MD SASP Maximum Reset Down --- 1 0 ∧F --- 3 --- 5
MP.MX Econ Min at Max Fanspeed 30 % 30 30
PE1.C Power Exhaust Stage 1 CFM 600 cfm 600 600
IDF.C Indoor Fan Max Speed CFM
System Pilot -- Communication Space Sensor
Install the System Pilot and connect the CCN communication bus from it to the units CCN connection on the low voltage terminal
48/50PD
board. Configure the unit’s CCN communication element number, bus number, and baud rate. Refer to the System Pilot’s installation instructions for configuring it to be used as a space temperature and attaching it to a unit.
Gen III TEMP Monitor -- Linkage Communication Thermostat
Install the linkage thermostat. Connect the CCN communication bus from the Stat to the CCN terminals on the field connection terminal board located at the unit control box. Configure the unit’s CCN communication element number, bus number, and baud rate. Refer to the Linkage Thermostat’s installation instructions for configuring the Stat and additional information about it.
(33CSTMT--01)
Space Humidistat Control
The humidistat input is provided on the field connection terminal board. The Space Humidity Switch configuration, ConfigurationUNITRH.SW, identifies the normally open or normally closed status of this input at LOW humidity. Humidistat 1 terminal is the 24 VAC source for dry contact and the Humidistat 2 terminal is the signal input.
Relative Humidity Sensor Control
For units with the economizer option (with the ECB--economizer control board), the humidity sensor input is provided on the field connection terminal board. The sensor can be used in addition to or instead of a humidistat. The RH Sensor on OAQ Input configuration, ConfigurationUNITRH.S=YES, identifies that the sensor is being used instead of an OAQ sensor. Terminal 1 is the 24vdc loop power and Terminal 4 is the 4 --20 mA signal input. Refer to the Field Installed Accessories for more information.
CCN Communication
Configure ConfigurationCCNCCN.A to desired element number (Default is 1). Configure ConfigurationCCNCCN.B to desired bus number (Default is 0). Configure ConfigurationCCNBAUD to desired code number for baud rate (Default is 3 = 9600 baud).
Accessories
Below are quick configuration settings for field installed accessories. If these accessories were installed by the factory, they will already be configured. See the Field-- Installed Accessories section, third party control, control connection tables, and CCN or Display parameter tables for any accessories not mentioned below and any additional information on accessories.
Economizer
If an Economizer accessory was field installed, the unit must be configured for it by setting ConfigurationECONEC.EN to YES. The default settings for the other economizer configurations
1600 (05) 2000 (06)
cfm
should be satisfactory. If they need to be changed, additional information about these configuration settings can be found in the Economizer section.
Power Exhaust
If a Power Exhaust accessory was field installed, the unit must be configured for it by setting ConfigurationECONPE.EN to ENBL. The default settings for the other power exhaust configurations should be satisfactory. If they need to be changed, additional information about these configurations can be found in the Power Exhaust section.
Electric Heat
If an Electric Heat accessory was field installed, the unit must be configured for it by setting ConfigurationHEATHT.TY to a value of 2. The number of electric heat stages must be configured by setting ConfigurationHEATN.HTR per the installed heater.
Fire Shutdown
If a Fire Shutdown or Smoke Detector accessory was field installed, the unit must be configured for it by setting ConfigurationUNITFS.SW to normally open (1) or normally closed (2) when there is not a fire alarm. Normally open (1) is the preferred configuration.
IMPORTANT: On standard units, the fire shutdown input is the terminals Fire Shutdown 1 and 2.
Outdoor Enthalpy
If an Outdoor Enthalpy accessory was field installed, the unit must be configured for it by setting ConfigurationECONEN.SW, identifies the normally open or normally closed status of this input when the outdoor enthalpy is low.
IAQ Switch
If an IAQ Switch accessory was field installed, the unit must be configured for it by setting ConfigurationAIR.QII.CF, identifies the normally open or normally closed status of this input when the indoor air quality value is low (good) and also selects the unit response to this input.
IMPORTANT: An IAQ switch cannot be used if an enthalpy switch is already on this input.
IAQ Sensor
If an CO2Sensor accessory was field installed, the unit must be configured for it by setting ConfigurationAIR.QIA.CF selects the unit response to this input. Default conversion to 0 to 2000 ppm.
OAQ Sensor
If an Outdoor Air Quality Sensor accessory was field installed, the unit must be configured for it by setting ConfigurationAIR.Q OA.CF selects the unit response to this input. Default conversion to 0 to 2000 ppm.
DISPLACEMENT
VENTILATION
1600 (05) 2000 (06)
SINGLE ZONE
VAV
1600 (05) 2000 (06)
8
Page 9
Fan Status
If a Fan Status accessory was field installed, the unit must be configured for it by setting ConfigurationUNITFN.SW to normally open (1) or normally closed (2). Normally open (1) is the preferred configuration.
IMPORTANT: Fan Status input is not on the terminals marked Fan Status.
Table 4 — Setting an Occupied Time Schedule - Weekdays Only for 7:30 to 22:30
Filter Status
If a Filter Status accessory was field installed, the unit must be configured for it by setting ConfigurationUNITFL.SW to normally open (1) or normally closed (2). Normally open (1) is the preferred configuration.
DISPLAY
MENU
TIMECLOCK
SCH.L
SUB SUB
MODE
PER.1
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
Y
ENTER
Y
ENTER
ESCAPE
B
ENTER
ENTER
Y
ENTER
Y
ENTER
ESCAPE
B
ENTER
Y
ENTER
ESCAPE
B
ENTER
Y
ENTER
ESCAPE
B
ENTER
Y
ENTER
ESCAPE
B
ENTER
Y
ENTER
ESCAPE
B
ENTER
Y
ENTER
ESCAPE
ESCAPE
ESCAPE
ITEM DISPLAY ITEM EXPANSION COMMENT
Local Occupancy Schedule
OCC.1 Period Occupied Time
00.00
00.00
07.00
07.00
07.30
07.30
OCC.1 07.30 Period Occupied Time
UNC.1 00.00 Period Unoccupied Time
00.00
00.00
22.00
22.00
22.30
22.30
UNC.1 22.30 Period Unoccupied Time
MON.1 NO Monday In Period
NO
YES
YES
MON.1 YES Monday In Period
TUE.1 NO Tuesday In Period
NO
YES
YES
TUE.1 YES Tuesday In Period
WED.1 NO Wednesday In Period
NO
YES
YES
WED.1 YES Wednesday In Period
THU.1 NO Thursday In Period
NO
YES
YES
THU.1 YES Thursday In Period
FRI.1 NO Frida y In Perio d
NO
YES
YES
FRI.1 YES Friday In Period
Scrolling stops
Hours Flash
Select 7
Change accepted, minutes flash
Select 30
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Hours Flash
Select 22
Change accepted, minutes flash
Select 30
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
48/50PD
9
Page 10
Programming Operating Schedules
The ComfortLinkt controls will accommodate up to eight different schedules (Periods 1 through 8), and each schedule is assigned to the desired days of the week. Each schedule includes an occupied on and off time. As an example, to set an occupied schedule for 8 AM to 5 PM for Monday through Friday, the user would set days Monday through Friday to ON for Period 1. Then the user would configure the Period 1 Occupied From point to 08:00 and the Period 1 Occupied To point to 17:00. To create a different weekend schedule, the user would use Period 2 and set days Saturday and Sunday to ON with the desired Occupied On and Off times.
IMPORTANT: By default, the time schedule periods are programmed for 24 hours of occupied operation.
To create a schedule, perform the following procedure:
1. Scroll to the Configuration mode, and select CCN CONFIGURATION (CCN). Scroll down to the Schedule Number (ConfigurationCCNSCH.O=SCH.N). If password protection has been enabled, the user will be prompted to enter the password before any new data is
48/50PD
accepted. SCH.N has a range of 0 to 99. The default value is 1. A value of 0 is always occupied, and the unit will control to its occupied set points. A value of 1 means the unit will follow a local schedule, and a value of 65 to 99 means it will follow a CCN schedule. Schedules 2-- 64 are not used as the control only supports one internal/local schedule. If one of the 2--64 schedules is configured, then the control will force the number back to 1. Make sure the value is set to 1 to use a local schedule.
2. Enter the Time Clock mode. Scroll down to the LOCAL TIME SCHEDULE (SCH.L) sub--mode, and press ENTER. Period 1 (PER.1) will be displayed.
3. Scroll down to the MON.1 point. This point indicates if schedule 1 applies to Monday. Use the ENTER command to go into Edit mode, and use the Up or Down key to change the display to YES or NO. Scroll down through the rest of the days and apply schedule 1 where desired. The schedule can also be applied to a holiday.
4. Configure the beginning of the occupied time period for Period 1 (OCC). Press ENTER to go into Edit mode, and the first two digits of the 00.00 will start flashing. Use the Up or Down key to display the correct value for hours, in 24--hour (military) time. Press ENTER and hour value is saved and the minutes digits will start flashing. Use the same procedure to display and save the desired minutes value.
5. Configure the unoccupied time for period 1 (UNC). Press ENTER to go into Edit mode, and the first two digits of the
00.00 will start flashing. Use the Up or Down key to display the correct value for hours, in 24--hour (military) time. Press ENTER and hour value is saved and the minutes digits will start flashing. Use the same procedure to display and save the desired minutes value.
6. The first schedule is now complete. If a second schedule is needed, such as for weekends or holidays, scroll down and repeat the entire procedure for period 2 (PER.2). If additional schedules are needed, repeat the process for as many as are needed. Eight schedules are provided. See Table 4 for an example of setting the schedule.
The Service Test function can be used to verify proper operation of compressors, heating stages, indoor fan, outdoor fans, power exhaust fans, economizer, crankcase heaters, and the alarm relay. Use of Service Test is recommended at initial system start up and during troubleshooting (See Table 5 for point details).
Service Test mode has the following changes from normal operation:
S Outdoor air temperature limits for cooling circuits, economizer,
and heating are ignored. Normal compressor time guards and
other staging delays are reduced to 30 seconds or less.
S Circuit alerts are limited to 1 strike (versus 3) before changing to
alarm shut down state.
S The status of ALM.N is ignored so all alerts and alarms are
broadcast on CCN.
S The words “SERVICE TEST” are inserted into every alarm
message.
Service test can only be turned ON/OFF at the unit display. Once turned ON, other entries may be made with the display or through CCN. To turn Service Test on, change the value of TEST to ON. To turn service test off, change the value of TEST to OFF.
IMPORTANT: Service Test mode may be password protected. Refer to Basic Control Usage section for more information. Depending on the unit model, factory--installed options, and field--installed accessories, some of the Service Test functions may not apply.
Independent Outputs
The independent (INDP) submenu is used to change output status for the economizer, power exhaust stages, crankcase heaters, and the alarm relay. These independent outputs can operate simultaneously with other Service Test modes. All outputs return to normal operation when Service Test is turned off. When the economizer is using the factory default Digital Control Type (ConfigurationECONE.CTL is 1 or 2) then the Economizer Calibration feature may be used to automatically check and reset the economizer actuator range of motion. Refer to the economizer operation section of more details.
IMPORTANT: If a network force is applied to CCN points: ECONOCMD, PE_1, PE_2, or ALMOUT, their respective test mode functions will not be usable. Those forces are at a higher level than test mode; therefore they will still be honored when in test mode.
Fan Test
The fans (FANS) submenu is used to change output status for the indoor fan and outdoor fan stages. The VFD power can be turned on and off via IDF (Supply VFD Power Test). The indoor fan speed test (F.SPD) runs the fan at the desired speed entered. The outdoor fan relay test (OFC.1) only tests the relay for switching between high and low speeds. The actual outdoor fan will not run unless cool test is on. The cooling (COOL) and heating (HEAT) service test outputs are reset to OFF for the fans service test.
SERVICE TEST
10
Page 11
Cooling Test
The cooling (COOL) submenu is used to change output status for testing the cooling function. The fans (FANS) and heating (HEAT) service test outputs are reset to OFF for the cooling service test. The digital scroll controller power test (CTLR) turns on and off the compressor controller. The compressor capacity test (CPAC) is used to run the compressor at a desired capacity of 15% to 100%. If a capacity is chosen between 1 and 14, the capacity will be set to 15%. The outdoor fan will turn on to high speed when the compressor capacity is 15% or greater. The indoor fan speed will default to supply fan maximum speed (FS.MX) when the compressor capacity test is first activated. The cool test fan speed (F.SPD) is used to change the fan speed while the compressor is running. All normal cooling alarms and alerts are functional.
IMPORTANT: When charging the unit, both the compressor capacity test and the cool test fan speed should be set to 100%.
Heating Test
The heating (HEAT) submenu is used to change output status for the individual heat stages, gas or electric. The fans (FANS) and cooling (COOL) service test outputs are reset to OFF for the heating service test. Indoor and outdoor fans are controlled normally to maintain proper unit operation. The indoor fan speed will run at the configured max speed FS.MX. All normal heating alarms and alerts are functional.
Table 5 — Service Test Modes and Submodes Directory
DISPLAY MENU/ SUB--MENU/ NAME SERVICE TEST
TEST
INDP Test Independent Outputs
ECON Economizer Position Test 0 to 100% E.CAL Calibrate Economizer On/Off PE.1 Power Exhaust 1 Test On/Off PE.2 Power Exhaust 2 Test On/Off ALRM Alarm Relay Test On/Off CCH Crankcase Heat Test On/Off
FANS SUPPLY Te st Fan s
IDF VFD Power Test On/Off F.SPD Indoor Fan Speed Test 0 to 100% OFC.1 Outdoor Fan Relay Test On/Off
COOL Test Cooling
CTLR DigScrollCtrlPwrTest On/Off CAPC Compressor Capacity Test 0 to 100% F.SPD Cool Test Fan Speed 0 to 100%
HEAT Test Heating
HT.1 Heat Stage 1 Test On/Off HT.2 Heat Stage 2 Test On/Off
EXPANDED NAME VALUES
Field Service Test Mode On/Off
THIRD PARTY CONTROL
Third party controls may interface with the unit ComfortLinkt controls through the connections described below. See other sections of these instructions for more information on the related unit control and configurations.
Remote Occupancy
The remote occupancy input is provided on the field connection terminal board (TB1). The Remote Occupancy Switch configuration, ConfigurationUNITRM.SW, identifies the normally open or normally closed status of this input when unoccupied.
S 5 = 24 VAC signal input S 6 = 24 VAC source for dry contact
Fire Shutdown
The fire shutdown input is provided for unit shutdown in response to a fire alarm or smoke detector. The Fire Shutdown Switch configuration, ConfigurationUNITFS.SW, identifies the normally open or normally closed status of this input when there is no fire alarm.
Input at field connection terminal board (TB1)
S Fire Shutdown 1 = 24 VAC source for dry contact S Fire Shutdown 2 = 24 VAC signal input
Alarm Output
The alarm output is provided on the field connection terminal board (TB1) to indicate a current alarm status. The output will be 24VAC if a current alarm exists.
S C=24VACcommon S X = 24 VAC signal output
Economizer Monitoring
On field terminal board (TB1), terminals 8, 9, and 10 can be used to monitor economizer position from a third party control system. See economizer operation section for additional information.
In digital mode (E.CTL = 1 or 2), the economizer commanded position can be read as a 2--10v or 4--20mA signal. TB1--8 and TB1--9 are used as follows:
S To read a 2--10v signal, disconnect the violet wire on
TB1--J10--8 and place volt meter device across TB1--8 and
TB1--9.
S To read a 4--20mA signal, disconnect the violet wire on
TB1--J10--8 and the 500resister at TB1--J10--6. Place amp
meter device between TB1--8 and TB1--9.
In analog mode (E.CTL = 3), the economizer position can be read as a 2--10v feedback signal across TB1 -- 10 and TB1--9 at any time.
IMPORTANT: The violet wire and 500resister must be connected at the J10 connector as originally wired to operate the economizer in analog mode.
Economizer Damper Control
For units with the economizer option or accessory and the ECB control board, the damper position can be directly controlled through the IAQ sensor input provided on the field connection terminal board. The IAQ Analog Input configuration, ConfigurationAIR.QIA.CF will have to set to 3 (Control Minimum Position). When IA.CF = 3, an external 4 to 20 mA source is used to move the damper 0% to 100% directly.
Terminal 2 = 4-- 20mA + signal Terminal 3 = 4-- 20mA -- common
IMPORTANT: In this mode preset minimum positions configurations are not valid. The damper position may exceed the input position to provide economizer cooling and CO
sensor input
2
can not be used for DCV control. Refer to the Indoor Air Quality operation section for more information.
CONTROLS OPERATION
Display Configuration
The ConfigurationDISP submenu is used to configure the local display settings.
Metric Display (METR)
This variable is used to change the display from English units to Metric units.
Language Selection (LANG)
This variable is used to change the language of the ComfortLink display. At this time, only English is available.
48/50PD
11
Page 12
Password Enable (PROT)
This variable enables or disables the use of a password. The password is used to restrict use of the control to change configurations.
Service Password (PSWD)
This variable is the 4-digit numeric password that is required if enabled.
Test Display LEDs (TEST)
This is used to test the operation of the ComfortLinkt display.
Modes
The ComfortLink controls operate under a hierarchy of command structure as defined by four main elements: the System Mode, the HVAC Mode, the Occupied status, and the Unit Control Type.
The System Mode is the top level that defines three main states of the control system: Disabled, Enabled, or Test.
The HVAC Mode is the next level that defines four main states of functional operation: Disabled, Fan Only, Cool, and Heat.
The Occupied status affects set points for cooling and heating in Space Sensor control mode and operation of the economizer for
48/50PD
indoor air quality ventilation and free cooling. The general operating mode of the control and the status of some
related operation lockouts are located on the display at two locations: Run StatusMODE and Operating ModesMODE.
System Mode (SYS)
In Run Status and Operating Modes, the current system mode is displayed with expandable text. This is an overall state of the unit. Three states are: Unit Operation Disabled, Unit Operation Enabled, or Service Test Enabled.
HVAC Mode (HVAC)
In Run Status and Operating Modes, the current allowed HVAC mode is displayed with expandable text. This is the mode the unit decides to run in based on its inputs. There are four main HVAC modes; cooling has three different expanded texts. These modes are shown below.
HVAC
Mode
Disabled HVAC Operation
Fan Only Ventilation
Cooling
Heating Heating Heating mode
Expanded Text Brief Description
Disabled
(fan--only) Cooling Mechanical cooling Free Cooling Only economizer used for cooling Unoccupied Free
Cooling
Unit is in test mode or System mode is disabled
Fan may run for ventilation
Only economizer use for cooling (occupied coo ling set point active)
Remote HV AC Mode Disabled (HV.DN)
Allow disabling of HVAC mode. This is only available on a network connection.
Cool Setpoint in Effect (EFF.C)
This shows the actual setpoint that is being used for control during cooling mode.
Heat Setpoint in Effect (EFF.H)
This shows the actual setpoint that is being used for control during heating mode.
Currently Occupied (OCC)
Displays the current state of assumed space occupancy based on unit configuration and inputs.
Timed Override in Effect (T.OVR)
Displays if the state of occupancy is currently occupied due to an override.
Linkage Active (LINK)
Displays if Linkage communication is established between the unit and a Linkage source.
IMPORTANT: The 48/50PD unit only supports the Gen III TEMP Monitor Thermostat.
Demand Limit in Effect (D.LMT)
Displays if a demand limit has been placed on the unit’s capacity.
Circuit OAT Lockout (C.LOC)
Displays if one or more refrigerant circuits operation is prevented due to outdoor temperature limit lockout.
Heat OAT Lockout (H.LOC)
Displays if heating operation is prevented due to outdoor temperature limit lockout.
Econo Cool OAT Lockout (E.LOC)
Displays if economizer operation for cooling is prevented due to outdoor temperature limit lockout.
Unit Configuration
Many configurations that indicate what factory options and/or field accessories are installed and other common operation variables are included in Unit Configuration (ConfigurationUNIT). Configuration will be done at the factory for any factory-installed option (FIOP).
Start--Up Delay (S.DLY)
This configuration sets the control start-up delay after the power is interrupted. This can be used to stagger the start-up of multiple units.
FanOnWhenOccupied(OC.FN)
A YES value will operate the indoor fan whenever the unit is in the Occupied mode. A NO value will operate the indoor fan only when heating or cooling is necessary. The factory default value is YES.
Shut Down on IDF Failure (IDF.F)
This configuration applies only if a fan switch is installed and configured. A YES value will enable diagnostic Alert T409 to shut down the unit when incorrect fan status is sensed. A NO value will still permit Alert T409 but will not cause unit shutdown. The factory default value is YES.
Supply Fan Maximum Speed (FS.MX)
This configuration sets the limit for the highest speed the fan can run out of 100%. This max speed limit applies to the unit at all times except for fan test.
Supply Fan Minimum Speed (FS.MN)
This configuration sets the limit for the lowest speed the fan can run out of 100%. This minimum speed limit applies to the unit during cooling mode and cooling test.
Vent Mode Fan Speed (FS.VM)
This configuration sets the speed the fan will run during the ventilation mode. The fan speed does not vary during ventilation so it will remain at this speed throughout vent mode.
Fan Status Switch (FN.SW)
This configuration identifies if a fan status switch is installed, and what status (normally open, normally closed) the input is when the indoor fan is OFF.
Filter Status Switch (FL.SW)
This configuration identifies if a filter status switch is installed, and what status (normally open, normally closed) the input is when the filter is CLEAN.
Fire Shutdown Switch (FS.SW)
This configuration identifies if a fire shutdown switch is installed, and what status (normally open, normally closed) the input is when the fire or smoke alarm is OFF (no alarm).
Remote Occupancy Switch (RM.SW)
This configuration identifies if a remote occupancy switch is installed, and what status (normally open, normally closed) the input is when UNOCCUPIED.
12
Page 13
RH Sensor On OAQ Input (RH.S)
This configuration identifies if a space relative humidity sensor is installed on the outdoor air quality (OAQ) input. A YES value enables SP.RH display. A NO value disables SP.RH display and use.
Space Humidity Switch (RH.SW)
This configuration identifies if a space relative humidity switch is installed on the ENTHALPY input, and what status (normally open, normally closed) the input is when the space humidity is LOW.
Temperature Compensated Start Cooling Factor (TCS.C)
This factor is used in the equation of the Temperature Compensated Start Time Bias for cooling. A setting of 0 minutes indicates Temperature Compensated Start in Cooling is not permitted.
Temperature Compensated Start Heating Factor (TCS.H)
This factor is used in the equation of the Temperature Compensated Start Time Bias for heating. A setting of 0 minutes indicates Temperature Compensated Start in Heating is not permitted.
General Operating Sequence
The PD unit must be connected to a space temperature sensor T--55, T--56, T58 or T59 and will not operate with a conventional R, Y1, Y2, W1, W2, G, C thermostat. When a T--55, T--56, T58 or T59 space temperature sensor is connected to the low voltage terminal board as shown in the Installation Instructions Manual, the PD unit will try to maintain the Space Temperature (TemperaturesAIR.TSPT) at one of four set points: The Occupied Cool Set Point (SetpointsOCSP), the Unoccupied Cool Set Point (SetpointsUCSP), Occupied Heat Set Point (SetpointsOHSP), or the Unoccupied Heat Set Point (SetpointsUHSP).
Occupancy Determination
When the building is in occupied mode, the occupied set points are active. When the building is in unoccupied mode, the unoccupied set points are active. The PD control will switch automatically between cooling and heating to maintain temperature. However, to minimize unnecessary cool to heat and heat to cool changes, there is a 10--minute delay after the last stage turns off before the control will switch modes. The heating and cooling set points are also separated by a Heat--Cool Set Point Gap (SetpointsGAP)thatis user configurable from 2 to 10 degrees F. This parameter prevents the unit from over cooling the conditioned space to where heating mode is required or over heating the conditioned space to where cooling mode is required.
The T55 space temperature sensor senses the temperature in the conditioned space with no provisions for adjusting the space temperature set point at the sensor. The T--56 space temperature sensor senses the temperature in the conditioned space and allows for adjustment of the space temperature set point by a configurable number of degrees F higher or a configurable number of degrees F lower at the space temperature sensor. The T58 space temperature sensor communicates with the PD unit control board through a CCN RS--485 +, -- , and ground connection. The T59 space temperature sensor is a T56 sensor with an integrated temperature display. A jumper wire is not needed between R and W1 when using space temperature sensors T55, T56, T58 or T59.
The building’s occupancy is affected by a number of different factors. When the unit is operating with a space temperature sensor (T--55, T-- 56, T--58 or T--59), occupancy affects the unit set points and the operation of the economizer. The factors affecting occupancy are listed below from highest to lowest priority.
Level 1 Priority
The CCN point OCCUPIED is forced via an external device such as a ComfortIDt controller: when OCCUPIED is forced to YES, the unit is considered occupied, when OCCUPIED is forced to NO, the unit is considered unoccupied. If OCCUPIED is not being forced, proceed to the level 2 priority.
Level 2 Priority
Remote Occupancy Switch should be configured to either Normally Open or Normally Closed when the user would like to control the occupancy with an external switch. This switch is field-- supplied (24v, single pole, single throw [SPST]). There are three possible configurations for the remote occupancy switch:
1. (ConfigurationUNITRM.SW = 0) No Switch
2. (ConfigurationUNITRM.SW = 1) Normally Open
Switch
3. (ConfigurationUNITRM.SW = 2) Normally Closed
Switch
If the switch is configured to No Switch (0), the switch input value will be ignored and software will proceed to level 3 priority. For each type of switch, the appropriate configuration and states are listed in the table below.
TYPE OF SWITCH
Occupied when
Closed or
Unoccupied when
Open
Occupied when Open Normal Closed (2)
Unoccupied when
Closed
SWITCH
CONFIGURATION
Normal Open (1)
Normal Closed (2)
STATE OF
SWITCH AND
STATE OF
OCCUPANCY
Open and
Unoccupied
Closed and
Occupied
Open and Occupied
Closed and
Occupied
IMPORTANT: To perform remote occupancy, an Economizer Control Board must be installed in the unit.
Level 3 Priority
The following occupancy options are determined by the state of Occupancy Schedule Number (ConfigurationCCNSCH.OSCH.N) and the Global Schedule Broadcast (ConfigurationCCNBRODB.GS).
1. (ConfigurationCCNSCH.OSCH.N = 0) The unit is
always considered occupied and the programmed schedule is ignored. This is the factory default.
2. (ConfigurationCCNSCH.OSCH.N = 1- 64) Follow
the local programmed schedule. Schedules 1 to 64 are local within the controller. The 48/50PD unit can only store one local schedule and therefore changing this number only changes the title of the schedule table.
3. (ConfigurationCCNSCH.OSCH.N = 65- 99)
Follow the global programmed schedule. If the 48/50PD unit is configured as a Global Schedule Broadcaster (ConfigurationCCNRODB.GS = YES), the unit will follow the unit’s programmed schedule and broadcast the schedule so that other devices programmed to follow this schedule number can receive the schedule. If the 48/50PD unit is not programmed as a Global Schedule Broadcaster (ConfigurationCCNBRODB.GS = NO), the unit will receive broadcasted schedules from the unit programmed to broadcast this schedule number. While using the programmed schedule, occupancy can be temporarily switched from unoccupied to occupied by pressing the override button for approximately 3 seconds on the T--55, T-- 56, T -- 58 or T --59 space temperature sensor. Override will only occur if SPT Override Enabled
48/50PD
13
Page 14
(ConfigurationCCNSCH.OOV.SP) is set to YES. The length of the override period is determined by the Timed Override Hours setting (ConfigurationCCNSCH.OOV>EX).
Compressor Operation
The 48/50 PD units use a Copeland Digital Scroll Compressor that can vary the refrigerant capacity between 100 and 15%. This is accomplished by a mechanism in the compressor that separates the two scroll spirals which stops the pumping of the refrigerant gas. This mechanism is operated by the differential pressure between the suction and discharge of the compressor. The pressure to operate the unloading mechanism is controlled by a small solenoid situated in a refrigerant line between the top of the compressor and the suction line. When the solenoid is energized the compressor is unloaded. The solenoid coil is controlled by the Copeland Digital Scroll Controller (DSC) that operates on a 1 to 5V signal from the ComfortLink Auxiliary Board (AUX1) and converts this into a Pulse Width Modulated (PWM) signal to the solenoid valve. The pulse width modulated signal is an on and off signal that repeats every 15 seconds with the off time portion of the 15 seconds representing the % loading of the compressor.
48/50PD
The Compressor Capacity (OutputsCOOLCAPC) can be monitored on the ComfortLink Scrolling Marquee Display. The Compressor Capacity value is determined by a Proportional, Integral, Derivative (PID) algorithm that controls the Supply Air Temperature (TemperaturesAIR.TSAT) to the Supply Air Control Point (Run StatusCOOLSA.CP).
The Compressor Minimum Capacity (ConfigurationCOOLMIN.C) is configured at the factory to 70%. This is the minimum compressor capacity that gives the highest SEER rating for a 48 series unit with the highest gas heat option and no economizer per AHRI standard 210/240. Since the AHRI rating standard does not account for energy savings that can be realized by displacement ventilation air distribution system and extending economizer cooling operation at higher supply air temperature set points, a complete energy analysis should be conducted before changing the Compressor Minimum Capacity (ConfigurationCOOLMIN.C) setting to determine the energy savings at a lower Compressor Minimum Capacity (ConfigurationCOOLMIN.C) setting.
Indoor Fan Operation
The indoor fan is controlled by the Indoor Fan VFD Power Relay (OutputsFANSIDF) on the MBB (main base board) control, which then operates the indoor fan contactor (IFC). On the 48/50PD units the Indoor Fan VFD Power Relay (OutputsFANSIDF) is always on so that power is supplied to the VFD electronic boards. This prevents the formation of condensation on the VFD electronic boards and provides power to the remote VFD display so that error codes and VFD configuration parameters can be verified.
The 48/50PD unit controls require an accurate supply duct CFM at the unit design point where the indoor fan will run at the Supply Fan Maximum Speed (ConfigurationUNITFS.MX).The Supply Fan Maximum Speed (ConfigurationUNITFS.MX) is used for operation of the economizer and power exhaust. The supply duct CFM is configured by the Indoor Fan Max Speed CFM (ConfigurationECONIDF .C). Default values for Indoor Fan Max Speed CFM (ConfigurationECONIDF.C) are at 400 CFM per ton or 1600 CFM for the 05 size and 2000 CFM for the 06 size. It is preferred to use the supply duct CFM from an air balance report to configure the Indoor Fan Max Speed CFM (ConfigurationECONIDF.C). If an air balance report is not available then use the fan tables supplied in this book to determine Fan Max Speed CFM (ConfigurationECONIDF.C). When using the fan tables to determine Fan Max Speed CFM
(ConfigurationECONIDF.C) set Economizer Position Test
(Service TestINDPECON) to 0 (Economizer Damper Closed) and Indoor Fan Speed Test (Service TesFAN S F. S P D ) equal to (ConfigurationUNITFS.MX). Measure the supply to return
duct static pressure difference and indoor fan RPM. Make correction to static pressure for all options installed in the unit per the accessory pressure drop table. Determine Indoor Fan Max Speed CFM (ConfigurationECONIDF.C) where the corrected static pressure and RPM cross.
The supply fan speed range is configured by the Supply Fan Maximum Speed (ConfigurationUNITFS.MX) and the Supply Fan Minimum Speed (ConfigurationUNITFS.MN). These configuration values are in units of % speed referenced to a 2 to 10VDC signal to the VFD AI1 input with 2VDC representing 0% speed and 10VDC representing 100% speed or 0 to 60HZ VFD frequency output to the motor.
The Supply Fan Minimum Speed (ConfigurationUNITFS.MN) can be user configured between 10 and 70%. The Supply Fan Minimum Speed default value is 70%, this provides the greatest energy efficiency rating for a unit without an economizer in a mixed air type duct application.
The Supply Fan Maximum Speed (ConfigurationUNITFS.MX) can be configured between 80 and 100%. The Supply Fan Maximum Speed default value is 100%. Set the indoor fan pulley to the application design point CFM for heating and cooling at 100% fan speed so that the CFM is not lower than the minimum CFM allowed in the product data. If the exact CFM can not be set by the half turn pulley settings then adjust the Supply Fan Maximum Speed (ConfigurationUNITFS.MX) to fine tune the CFM to the application requirements. The Supply Fan Maximum Speed (ConfigurationUNITFS.MX) RPM must now produce supply CFM that is not lower that the minimum CFM allowed in the product data for heating and cooling.
The indoor fan may operate during cooling with compressors mode, free cooling with outdoor air mode, heating mode, or for ventilation with outdoor air mode.
The indoor fan operation can be affected by the following:
S FanOnWhenOccupied(ConfigurationUNITOC.FN) S IAQ Analog Fan Config (ConfigurationAIR.QIA.FN) S IAQ Switch Fan Config (ConfigurationAIR.QII.FN) S Fan Status Switch (ConfigurationUNITFN.SW)
When the unit is in occupied or unoccupied cooling mode the supply fan will modulate to maintain the space temperature sensor set point between the configured Supply Fan Maximum Speed (ConfigurationUNITFS.MX) and the Supply Fan Minimum Speed (Configuration
When the 40PD or 50 PD unit is in occupied or unoccupied heating mode (gas heat or electric heat mode) the indoor fan will operate at the Supply Fan Maximum Speed (ConfigurationUNITFS.MX) setting.
For 48PD gas heating units, the IGC control fan output is also monitored by the MBB control. This can result in additional modifications of fan delays or other operation due to safety functions of the IGC control.
When the PD unit is in free cooling mode the indoor fan will modulate to maintain The Occupied Cool Set Point
(SetpointsOCSP), the Unoccupied Cool Set Point (SetpointsUCSP), Occupied Heat Set Point (SetpointsOHSP), or the Unoccupied Heat Set Point (SetpointsUHSP).
When the PD unit is in ventilation mode and Fan On When Occupied (ConfigurationUNITOC.FN) the indoor fan will operate at the Vent Mode Fan Speed
(ConfigurationUNITFS.VM). Vent Mode Fan Speed (ConfigurationUNITFS.VM) factory default is 50% and can
be user configured between 40 and 100%.
UNITFS.MN).
on the fan table
14
Page 15
Outdoor Fan Operation
The 48/50 PD units use a multi--speed outdoor fan motor to control the head pressure within an acceptable range at low outdoor ambient temperatures. On the 48 and 50 PD--05 and 06 size units the outdoor fan contactor is powered on the load side of the compressor contactor so the outdoor fans will run only when the compressor contactor is energized. When the outdoor fan contactor is not energized the outdoor fan runs at high speed.
When the outdoor fan contactor is energized the outdoor fan runs at low speed.
The outdoor fan speed is controlled by a system three of fan levels set up in the control software. Table 6 shows the three levels and fan speeds for each level. The fan levels are determined by Outdoor Air Temperature (TemperaturesAIR.TOAT) but can be overridden by Condenser Pressure A (PressuresSCP.A) inputs to the Main Base Board.
FAN
LEVEL
0 OFF N/A
1 LOW 1. Compressor Contactor is OFF
2 HIGH
FAN
SPEED
CONDITIONS TO TRANSITION TO NEXT
LOWER LEVEL
1 . O u t s i d e A i r Te m p e r a t u r e C o n t r o l --- --- F a n Lev2 Off Temperature 45 F or below (Confi-
gurationCOOLOFC2.OFF <=45F)*
2. Condenser Pressure A Override --- --- Fan Lev2 Min Pressure 200 psig or below (Config-
urationCOOLOFC2.MNP<= 200 psig)*
CONDITIONS TO TRANSITION TO NEXT
HIGHER LEVEL
1. Compressor Contactor is ON
(on initial start up outdoor fan runs at Level 2 for 10 seconds before moving to correct level based on outside air temperature or Condenser Pres­sure A)
1. Outside Air Temperature Control — Fan Lev2 On Temperature 55 F or above (Configu-
rationCOOLOFC2.ON >=55F)*
2. Condenser Pressure A Override — Fan Lev1 Max Pressure 450 psig or above (Config-
urationCOOLOFC1.MXP>= 450 psig)*
N/A
Table 6 — Fan Level Control of Outdoor Fan
*Configuration parameters 1.MXP, 2.MNP, 2.ON and 2.OFF factory default configuration should not be changed. The default configurations have been qualified over a wide range of conditions and are provided in case a field replacement of the control board o ccurs and the settings need to be check ed or manually conf igured.\
Economizer Operation
If an economizer is installed, then Economizer Installed (ConfigurationUNITEC.EN) should be set to YES. The economizer is controlled by the Econo Commanded Position (OutputsECONEC.CP) on the Economizer Control Board (ECB). Feed back from the economizer actuator is output on configuration parameter Econo Actual Position (OutputsECONEC.AP).
Economizer Actuator
The economizer actuator used with the 48/50PD units is a Multi--Function Technology (MFT) actuator. This allows the ComfortLink system to communicate with the actuator through a feedback signal. The configuration Economizer Control Type (ConfigurationECONE.CTL) determines the communication method, either digital or analog, used to communicate between the Economizer Control Board and the economizer actuator.
The power to the unit must be cycled after the Economizer Control Type (Configuration ECONE.CTL) configuration parameter is changed.
E.CTL = 1 or 2 (Digital/Position or Digital/Command)
When Economizer Control Type (ConfigurationECONE.CTL) is set to 1, the Economizer Control Board will communicate with the economizer actuator using the digital protocol, from Economizer Control Board plug J7--1 to actuator pin 5. The commanded position and the actuators actual position are communicated back and forth between the actuator and the Economizer Control Board. When the Economizer Control Board and actuator first initiate communication, a Control Angle Economizer Control Type (Operating Modes ECONC.ANG) is provided to the Economizer Control Board and defines the actuator’s range of motion. The control angle must be greater than the Min Actuator Ctrl Angle (ConfigurationECONM.ANG). During this digital control, the Economizer Control Board analog 4 to 20 mA output will represent the actuator’s actual position when E.CTL = 1 or
Communication
commanded position when E.CTL = 2. Because the wiring has a built--in 500 -- ohm resistor, the 4 to 20mA signal is converted to a 2 to 10VDC signal that is accessible via a field connected terminal board TB--8 and TB-- 9. However, before this signal can be read remotely, the violet wire that connects the actuator to field connection terminal board TB--J10--8 must be removed or cut.
E.CTL = 3 (Analog Control)
When E.CTL is set to 3, the Economizer Control Board will NOT communicate with the economizer actuator directly with the 4 to 20mA analog signal wired to TB--8 and TB -- 9 along with the 500--ohm resistor producing a 2 to 10VDC signal for the actuator. While in this mode, the actuator’s built--in 2 to 10VDC feedback signal s accessible via TB--9 and TB--10 any time because it is not used by the Economizer Control Board.
Cooling
Free
The economizer will be allowed to help with cooling if the Outdoor Air Temperature (TemperaturesAIR.TOAT) is less than the configured Econo Cool Hi Temp Limit (ConfigurationECONEH.LO) and greater than the configured Econo Cool Lo Temp Limit (ConfigurationECONEL.LO). If an enthalpy sensor is installed, the outdoor temperature must be below the Econo Cool Hi Temp Limit (ConfigurationECONEH.LO) and the Outdoor Enthalpy Switch (InputsGEN.IENTH) must be LOW.
Unoccupied Free Cooling
The unoccupied free cooling algorithm attempts to maintain the building space half way between the Occupied Cool Set Point
(SetpointsOCSP) and Occupied Heat Set Point (SetpointsOHSP) using only the economizer when the
conditions in the building and the outdoors are suitable., during UNoccupied periods if the air in the building and the outdoor air are suitable. Three different configurations define this algorithm:
1. Unoccupied Free Cooling
(ConfigurationECONUEFC)
48/50PD
15
Page 16
a. (ConfigurationECONUEFC = 0) -- D i s a b l e d
When UEFC = 0, unoccupied free cooling is disabled. Cooling will only occur if the space exceeds the unoccupied setpoints.
b. (ConfigurationECONUEFC = 1) -- Unoccupied
When UEFC is set to 1, unoccupied free cooling can occur throughout the entire unoccupied period. The space temperature must be higher then the mid--point between the occupied cooling and heating set points.
c. (ConfigurationECONUEFC = 2) -- Preoccupancy
When UEFC is set to 2, unoccupied free cooling can only occur when the time until the next occupied period is less than the Free Cool PreOcc Time (FC.TM) in minutes.
2. Free Cool PreOcc Time
(ConfigurationECONFC.TM)
FC.TM is the configuration that determines how many minutes before occupancy that free cooling can occur when set for Preoccupancy (UEFC = 2).
3. 1.Free Cool Low Temp Limit
(ConfigurationECONFC.LO)
48/50PD
Unoccupied free cooling cannot occur if the Outdoor Air Temperature (TemperatureAIR.TOAT) is less than FC.LO.
Exhaust
Power
To enable power exhaust set Power Exhaust Installed (ConfigurationECONPE.EN) to YES. On the 48/50PD--05 and 06 size units both power exhaust fans are wired together and are controlled by the configuration Power Exhaust Stage1 CFM (ConfigurationECONPE1.C). When the Indoor Fan Max Speed CFM (ConfigurationECONIDF.C) is set to the correct supply duct CFM (either by fan tables or air balance report) the control will calculate the outside air CFM based on outside air damper position and Commanded Fan Speed (OutputsFANSF. S P D ) to turn on the power exhaust when the calculated outside air CFM reaches Power Exhaust Stage1 CFM (ConfigurationECONPE1.C). The power exhaust will turn off when the calculated outside air CFM falls below Power Exhaust Stage1 CFM (ConfigurationECONPE1.C).The Power Exhaust Stage2 CFM (ConfigurationECONPE2.C) is not currently used on the 48/50PD--05 and 06 units.
Indoor Air Quality (IAQ)
The ComfortLink TM control has the capability for several methods of demand ventilation control. Indoor air quality is typically measured using a CO2 sensor whose measurements are displayed in parts per million (ppm). Outdoor air quality may be measured with a CO2 sensor for indoor--outdoor differential demand ventilation control, or with other sensor types for the outdoor air lockout function. The factory--installed indoor air quality CO2 sensor is mounted in the return section. A field-- installed indoor air quality CO2 sensor may be mounted in the return or directly in the occupied space, per job requirements. The indoor air quality modes of operation can be affected by the IAQ Analog Input Config (ConfigurationAIR.QIA.CF), IAQ Switch Input Config (ConfigurationAIR.QIA.CF), OAQ Analog Input Config (ConfigurationAIR.QOA.CF) and other related fan and limit configurations as described below.
IAQ (Analog
The ComfortLink TM control is configured for indoor air quality sensors which provide 4 to 20 mA signal for 0 to 2000 ppm CO2. If the sensor being used has a different range, the ppm display range must be reconfigured by entering new values for the IAQ Sensor Value at 4mA (ConfigurationAIR.QI.4M) and IAQ Sensor Value at 20mA (ConfigurationAIR.QI.20M).
IA.CF = 0 (No IAQ)
IA.CF = 0 signifies that there is no IAQ sensor installed. The damper will operate at the Econ Min at Max Fan Speed
Input)
(ConfigurationECONMP.MX) when the fan is at Supply Fan Maximum Speed (ConfigurationUNITFS.MX) and the damper position will vary at other fan speeds as described in the Cooling Mode with Economizer section below when the space is occupied and the indoor fan is on.
IA.CF = 1 (DCV)
When IA.CF = 1 the IAQ algorithm is set for Demand Control Ventilation (DCV). During DCV, the damper modulates between two user configurations depending upon the relationship between the Indoor Air Quality (IAQ) and the Outdoor Air Quality (OAQ). The lower of these two positions is referred to as the Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) while the higher is referred to as the Econ Min at Max Fan Speed (ConfigurationECONMP.MX). The Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) should be set to an economizer position that brings in enough fresh air to remove contaminates and CO2 generated by sources other than people. The Econ Min at Max Fan Speed (ConfigurationECONMP.MX) should be set to an economizer position that brings in fresh air to remove contaminates and CO2 generated by all sources including people when the indoor fan is operating at the Supply Fan Maximum Speed (ConfigurationUNITFS.MX). The Econ Min at Max Fan Speed (ConfigurationECONMP.MX) value is the design value for maximum occupancy.
The ComfortLink TM control will begin to open the damper from the Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) position when the IAQ level begins to exceed the Outdoor Air Quality (OAQ) level by a configurable amount. This amount is referred to as AQ Differential Low (ConfigurationAIR.QAQD.L). When the differential between IAQ and OAQ reaches AQ Differential High (ConfigurationAIR.QAQD.H), the economizer position will be at the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) when the indoor fan speed is at Supply Fan Maximum Speed (ConfigurationUNITFS.MX). When the IAQ/OAQ differential is between AQ Differential Low
(ConfigurationAIR.QAQD.L) and AQ Differential High (ConfigurationAIR.QAQD.H), the control will modulate the
damper between Econ Min at Max Fan Speed
(ConfigurationECONMP.MX) and Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) in a linear manner as shown
in Figure 3. At other fan speeds the economizer damper will operate in the shaded area between the two economizer position curves but at the actual fan speed as indicated by Commanded Fan Speed (OutputsFANSF. S P D ) .
IA.CF = 2 (Override IAQ)
When IA.CF = 2, the IAQ algorithm maintains the damper at Econ Min at Max Fan Speed (ConfigurationECONMP.MX) wh en the indoor fan speed is at Supply Fan Maximum Speed (ConfigurationUNITFS.MX) or in the shaded area of Figure 3 when the indoor fan speed is at the Commanded Fan Speed (OutputsFANSF. S P D ) until the override condition triggers. The override triggers when the IAQ/OAQ differential is greater than AQ Differential High The IAQ Override Position (ConfigurationAIR.QOVR.P). The economizer damper will return to the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) or MP.MX curve at other fan speeds when the IAQ/OAQ differential is less than the AQ Differential Low (ConfigurationAIR.QAQD.L).
The override algorithm will operate whenever the building is occupied and the indoor fan is operating or whenever the IAQ algorithm has caused the indoor fan to operate. The IAQ Analog Fan Config (ConfigurationAIR.QIA.FN) determines whether or not the IAQ algorithm can turn on the indoor fan.
If the indoor fan is not operating, the economizer position will be zero. If the override is not active and the building is unoccupied, the economizer position will be zero. The damper position may
(ConfigurationAIR.QAQD.H).
16
Page 17
exceed Econ Min at Max Fan Speed
(ConfigurationECONMP.MX) or IAQ Override Position (ConfigurationAIR.QOVR.P) to provide economizer
cooling.
IA.CF = 3 (Control Minimum Position)
When IA.CF = 3, an external 4 to 20 mA source is used to set the minimum position. The 4mA signal corresponds to 0% and the 20 mA signal corresponds to 100%. In this mode, configuration such as Econ Min at Max Fan Speed
(ConfigurationECONMP.MX), Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) and the economizer minimum
position and DCV minimum position curves in figure 3 are not used.
If the indoor fan is not operating, the economizer position will be zero. The damper position may exceed the economizer minimum position to provide economizer cooling.
IAQ (Switch
Indoor air quality can also be measured using a switch input. For the purpose of specifying the type of switch input, low CO2 levels are considered normal. The IAQ switch input is defined by the IAQ Switch Input Config (ConfigurationAIR.QII.CF). Enthalpy and IAQ are controlled by the same switch input and therefore cannot be used simultaneously.
II.CF = 0 (NO IAQ)
The II.CF = 0, configuration signifies that there is no IAQ switch input. The damper will operate at the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) and corresponding damper position curve based on indoor fan speed when the space is occupied and the indoor fan is on.
II.CF = 1 (DCV Normally Open) II.CF = 2 (DCV Normally Closed)
The Demand Control Ventilation (DCV) allows the economizer minimum position to be decreased when there is no IAQ problem. If IAQ is low, the economizer minimum position is Econo Min IAQ Position (ConfigurationAIR.QAQ.MN) when the indoor fan is operating at Supply Fan Maximum Speed (ConfigurationUNITFS.MX). If IAQ is high, the economizer minimum position is Econ Min at Max Fan Speed (ConfigurationECONMP.MX) when the indoor fan is operating at Supply Fan Maximum Speed (ConfigurationUNITFS.MX).
II.CF = 3 (Override Normally Open) II.CF = 4 (Override Normally Closed)
The damper override function permits absolute positioning of the economizer damper for ventilation purposes. The override is active when IAQ is high and inactive when IAQ is low. The override position is configured by the IAQ Override Position (ConfigurationAIR.QOVR.P).
Outdoor Air Quality (Analog
The ComfortLink TM control is configured for outdoor air quality sensors which provide a 4 to 20 mA signal corresponding to 0 to 2000 ppm CO2. If a field supplied sensor has a different range, the ppm display range must be reconfigured by entering new values for the OAQ Sensor Value at 4mA (ConfigurationAIR.QO.4M) and OAQ Sensor Value at 20mA (ConfigurationAIR.QO.20M).
OA.CF = 0 (NO OAQ)
This signifies that there is no outdoor air sensor installed. The default value of OAQ is 400 ppm CO2.
OA.CF = 1 (DCV)
The outdoor air quality sensor analog input is the value of OAQ.
OA.CF = 2 (OAQ Lockout)
The outdoor air quality analog input is only used to lock out the outdoor ventilation. The economizer commanded position is set to 0% when the CO2 ppm exceeds the OAQ lockout value configured for the OAQ Lockout Limit (ConfigurationAIR.QAQ.L). The default value for OAQ
Input)
Input)
Lockout Limit (ConfigurationAIR.QOAQ.L) is 600 ppm CO2.
Fan Enable (Analog IAQ
The DCV algorithm will operate whenever the building is occupied and the indoor fan is operating or whenever the IAQ algorithm has caused the indoor fan to operate. The IAQ Analog Fan Config (ConfigurationAIR.QIA.FN) determines whether or not the IAQ algorithm can turn on the indoor fan. If the indoor fan is not operating, the economizer position will be zero. The damper position may exceed Econ Min at Max Fan Speed (ConfigurationECONMP.MX) and corresponding damper position curve to provide economizer cooling.
IA.FN = 0 (Never)
When IA.FN =0, the IAQ algorithm can never turn on the fan.
IA.FN = 1 (Occupied)
When IA.FN =1, the IAQ algorithm will turn on the indoor fan whenever the building is occupied and IAQ/OAQ differential is greater than the Fan On AQ Differential (ConfigurationAIR.QDF.ON). The indoor fan will turn off when the IAQ/OAQ differential is less than the Fan Off AQ Differential (ConfigurationAIR.QDF.OF).
IA.FN = 2 (Always)
The indoor fan operation for IA.FN =2,isthesameasthe operation when IA.FN =1, except the algorithm is not limited to the occupied periods only. The fan can be triggered on when the space is occupied or unoccupied.
Fan Enable (Analog Switch
The DCV algorithm will operate whenever the building is occupied and the indoor fan is operating or whenever the IAQ algorithm has caused the indoor fan to operate. The IAQ Switch Fan Config (ConfigurationAIR.QII.FN) determines whether or not the IAQ algorithm can turn on the indoor fan. If the indoor fan is not operating, the economizer position will be zero. The damper position may exceed Econ Min at Max Fan Speed (ConfigurationECONMP.MX) and corresponding damper position curve to provide economizer cooling.
II.FN = 0 (Never)
When II.FN =0, the IAQ algorithm can never turn on the fan.
II.FN = 1 (Occupied)
When II.FN =1, the IAQ algorithm will turn on the indoor fan whenever the building is occupied and IAQ is high. The indoor fan will turn off when the IAQ returns to normal.
II.FN = 2 (Always)
The indoor fan operation for II.FN =2, is the same as the operation when IA.FN =1, except the algorithm is not limited to the occupied periods only. The fan can be triggered on when the space is occupied or unoccupied.
Sensor)
Input)
Cooling Modes
Cooling Mode Using Space Temperature Sensor T55, T56, T58 or T59
In cooling mode the PD control will maintain the Occupied Cool Set Point (SetpointOCSP) or the Unoccupied Cool Set Point (SetpointsUCSP) by modulating the indoor fan speed to supply more or less airflow to the conditioned space at the Supply Air Temperature (TemperaturesAIR.TSAT).
Cooling Supply Air Set
The Cool Supply Air Set Point (SetpointSASP)can be configured between 45F and 75F. The compressor modulates to maintain a Supply Air Temperature
(TemperaturesAIR.TSAT)at the Cool Supply Air Set Point (SetpointSASP).
Cooling Speed Demand W
When the temperature in the conditioned space is higher than the Occupied Cool Set Point (SetpointsOCSP) plus the Fan Speed Control Demand (ConfigurationCOOL?FS.CD) configuration
Point
indow
48/50PD
17
Page 18
variable or Unoccupied Cool Set Point (SetpointsUCSP) plus the Fan Speed Control Demand (ConfigurationCOOLFS.CD) configuration variable the indoor fan will run at 100%. When the temperature in the conditioned space is between the Occupied Cool Set Point
(SetpointsOCSP) and Occupied Cool Set Point (SetpointsOCSP) plus the Fan Speed Control Demand (ConfigurationCOOLFS.CD) configuration variable the
indoor fan modulates to satisfy the Occupied Cool Set Point
(SetpointsOCSP) or Unoccupied Cool Set Point (SetpointsUCSP). When the temperature in the conditioned
space falls to 0.5F below the Occupied Cool Set Point
(SetpointsOCSP) or Unoccupied Cool Set Point (SetpointsUCSP) for 5 minutes the controls will run unit in
ventilation mode. See ventilation mode sequence of operation.
can be set to --10 and the SASP Maximum Reset Up (ConfigurationCOOLSATSA.MU) configuration variable can be set to 0 giving the range of Cool Supply Air Set Point (SetpointSASP) reset of +0 and --10 F.
In normal operation when the Space Temperature is within the speed demand window the unit control will modulate the indoor fan speed and supply air temperature along a defined curve to bring the Space Temperature to Occupied or Unoccupied Cool Set Point. Since this curve is independent of the conditioned space load the control scheme will adapt to any load present in the conditioned space by adjusting the fan speed and supply air temperature and move the space temperature along the defined time temperature curve to Occupied or Unoccupied Cool Set Point.
When the space temperature rises above the Occupied Cool Set Point (SetpointsOCSP) + Fan Speed Control Demand (ConfigurationCOOLFS.CD) for over 2 minutes or is outside the speed demand window and there is some amount of SASP Maximum Reset Down (ConfigurationCOOL?SATSA.MD) configured the indoor fan will be locked at 100% and the unit controls will subtract a calculated amount of temperature reset to the Cool Supply Air Set Point (Setpoint
48/50PD
speed will be locked at 100% as long as reset is applied. The Supply Air Temperature will now adjust to this new Supply Air
SASP). The indoor fan
Control Point (Run StatusCOOLSA.CP). The controls will continue to subtract a calculated amount of temperature reset cumulatively to a value equal to the Supply Air Temperature Set
C09143
Fig. 6 -- Cooling Speed Demand Window
Cooling Supply Air Set Point
Reset
The PD unit can be configured to allow for reset of the Cool Supply Air Set Point (SetpointSASP). This is needed for applications where a high Cool Supply Air Set Point (SetpointSASP) is required or where dramatic load changes occur over short time periods. In these situations a high supply air temperature may not provide enough cooling to reduce the Space
Point (SetpointSASP) + SASP Maximum Reset Down (ConfigurationCOOLSATSA.MD). When the reset is no longer needed the control will remove Down Reset until all reset is removed and the Supply Air Control Point (Run StatusCOOLSA.CP) is back to the original Supply Air Set Point (SetpointSASP). The indoor fan will then modulate lower than 100% to move the Space Temperature (TemperaturesSPT) along the defined time temperature curve to Cool Supply Air Set Point (SetpointSASP) or Unoccupied Cool Set Point (SetpointsUCSP). See Fig. 6 and 7.
Temperature (TemperaturesAIR.TSPT) to the Occupied Cool Set Point (SetpointsOCSP) or the Unoccupied Cool Set Point (SetpointsUCSP) over a reasonable time period.
The compressor or economizer operation supplying cooling to the conditioned space controls to the Supply Air Control Point (Run
StatusCOOLSA.CP). The Supply Air Control Point (Run StatusCOOLSA.CP) which is a calculated value that is equal
to the Cool Supply Air Set Point (SetpointSASP) plus the calculated amount of reset required up to the values set by configuration variables SASP Maximum Reset Down (ConfigurationCOOLSATSA.MD) and SASP Maximum Reset Up (ConfigurationCOOLSATSA.MU).
Reset of the Cool Supply Air Set Point (SetpointSASP) is
Fig. 7 -- Cool Supply Air Set Point
C09144
limited by the configuration variables SASP Maximum Reset Down (ConfigurationCOOLSATSA.MD) and SASP Maximum Reset Up (ConfigurationCOOLSATSA.MU). The SASP Maximum Reset Down
(ConfigurationCOOLSATSA.MD)
configuration variable
can be set from --20 to 0 F and will allow the Cool Supply Air Set Point (SetpointSASP) to be reset to as much as 20 F below the Cool Supply Air Set Point (SetpointSASP). The SASP Maximum Reset Up (ConfigurationCOOL?SATSA.MU) configuration variable can be set from 0 to 20 F and will allow the Supply Air Temperature to be Reset to as much as 20 F above the Cool Supply Air Set Point (SetpointSASP). The SASP Maximum Reset Down (ConfigurationCOOL SATSA.MD) and SASP Maximum Reset Up (ConfigurationCOOLSATSA.MU) configuration variables can be set independently and do not need to be equal values above
Cooling Mode with Economizer Using Space Temperature Sensor T55, T56, T58 or T59
If an economizer is installed, the Economizer Installed configuration (ConfigurationECONEC.EN) should be set to YES. The economizer is controlled by the Econo Commanded Position (OutputsECONEC.CP) on the Economizer Control Board. If the indoor fan is off or the building is unoccupied, the economizer position is zero.
When the space temperature is above the Occupied Cool Set Point (SetpointsOCSP) and the economizer is installed, configured and working correctly the unit controls will always try to meet space cooling demand using the economizer before turning on the compressor. The economizer will provide free cooling when the following outside air conditions are true.
and below the Cool Supply Air Set Point (SetpointSASP).For example, the SASP Maximum Reset Down (ConfigurationCOOLSAT?SA.MD) configuration variable
18
Page 19
For all units with Economizers:
1. 1.The outdoor temperature is below the Econo Cool Hi Temp Limit (ConfigurationECONEH.LO) and above the Econo Cool Lo Temp Limit (ConfigurationECONEL.LO).
For units with Enthalpy Control
2. 1.The outdoor enthalpy is low and the outdoor temperature is below the Econo Cool Hi Temp Limit (ConfigurationECONEH.LO) and above the Econo Cool Lo Temp Limit (ConfigurationECONEL.LO).
If the conditions above are true and the economizer is available for cooling the economizer outside air and return air dampers will modulate to allow proportions of outside air and return air to mix and produce a temperature equal to the Cool Supply Air Set Point (SetpointSASP). If reset is applied to the Supply Air Temperature Set Point (SetpointSASP) the dampers will control to the Supply Air Control Point (Run StatusCOOLSA.CP).
If the conditions above are true but the economizer dampers are not able to satisfy the Cool Supply Air Set Point (SetpointSASP) with Reset (if applied), the compressor will turn on and modulate to provide additional cooling to satisfy the Cool Supply Air Set Point (SetpointSASP) with Reset if applied.
If the conditions above are not true, the economizer will move to a user Configurable Econ Min at Max Fan Speed (ConfigurationECONMP.MX) where the minimum economizer damper position is based on the Supply Fan Maximum Speed (ConfigurationUNITFS.MX). This is done to maintain a constant airflow through the economizer by opening the dampers more as the indoor fan speed is reduced or closing the dampers more as the indoor fan speed increases.
The shape of the Economizer Minimum Position vs. Fan Speed curve is determined by the configuration parameters: Econ Min at 25% Fan speed (ConfigurationECONMP.25), Econ Min at 50% Fan speed (ConfigurationECONMP.50), Econ Min at 75% Fan speed (ConfigurationECONMP.75) and Econ Min at Max Fan speed (ConfigurationECONMP.MX).
The Econ Min at 25% Fan speed
(ConfigurationECONMP.25), Econ Min at 50% Fan speed (ConfigurationECONMP.50) and Econ Min at 75% Fan
speed (ConfigurationECONMP.75) damper positions are calculated based on the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) and Supply Fan Maximum Speed (ConfigurationUNITFS.MX).
The Econ Min at 25% Fan speed
(ConfigurationECONMP.25), Econ Min at 50% Fan speed (ConfigurationECONMP.50) and Econ Min at 75% Fan
speed (ConfigurationECONMP.75) damper position are user configurable and can be determined by setting the fan speed at 25, 50 and 75% and determining the damper position required to maintain the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) Outside air CFM through the economizer outside air dampers. The default calculations programmed into the PD controls is based on a side shot economizer at 400 CFM/TON Supply Air flow with negative 0.25
O pressure in the return duct.
in H
2
Econ Min at Max fan Speed (ConfigurationUNITFS.MN) is set by user based on minimum required outside air ventilation CFM required for the application. This procedure would be the same as if this were a CV unit with the unit running at the design point CFM. This determines the minimum position amount of outside air CFM required when the fan is running at maximum speed.
Configure the Indoor Fan Max Speed CFM (ConfigurationECONIDF.C) either to the supply CFM determined from the fan performance tables or air balance reports. If using fan performance tables make corrections for all installed accessory pressure loss and use measured RPM, power and static
pressure readings to determine the actual Indoor Fan Max Speed CFM (ConfigurationECONIDF.C).
ECON MIN
AT MAX
FANSPEED
POSITION
(MINP_MAX)
VENTILATION FOR PEOPLE
MINIMUM
IAQ
DAMPER
POSITION
(AQ. MN)
INCREASING VENTILATION
VENTILATION FOR SOURCES
100
AQ DIFFERENTIAL LOW (AQD.L)
700
AQ DIFFERENTIAL HIGH (AQD.H)
INSIDE/OUTSIDE CO DIFFERENTIAL
C09145
Fig. 8 -- Economizer Minimum Position
If the indoor fan is not operating, the economizer will be fully closed, 0% open.
Ventilation
Mode
If the space temperature falls 0.5F below the Occupied Cool Set Point (SetpointsOCSP) the compressor will turn off, the indoor fan speed will be set to the Vent Mode Fan Speed (ConfigurationUNITFS.VM) and the economizer will open to the position that will supply minimum ventilation air at the configured Vent Mode Fan Speed
(ConfigurationUNITFS.VM). Default V ent Mode Fan Speed (ConfigurationUNITFS.VM) is 50%. Configuring the Vent
Mode Fan Speed (ConfigurationUNITFS.VM) lower will provide additional energy savings in vent mode but may not supply the required ventilation air to the conditioned space at lower fan speeds.
Demand Control V
The 48PD units can also be equipped with optional CO
entilation
sensors
2
for additional indoor air quality control. When unit is equipped with a return duct CO outside air CO
sensor the Economizer minimum position vs. fan
2
speed curve will be recalculated based on the CO
sensor or return duct CO2sensor and
2
level of the
2
return and/or outside air as shown in Fig. 8. See the Indoor Air
48/50PD
2
19
Page 20
Quality (IAQ) section of the Economizer Operation section above for more details on Demand Control Ventilation (DCV).
Economizer Operation for Units Equipped with Return CO
Sensor Only
2
When the CO
(Inputs→AIR.Q→IAQ) below the AQ Differential Low (ConfigurationAIR.QAQD.L) value the MP.25, MP.50,
MP .75 and MP.MX points will be recalculated to new values for MP .25, MP.50, MP.75 based on the Econ Min IAQ Position (ConfigurationAIR.QAQ.MN). The economizer outside air damper will close and reduce the amount of outside air CFM to the conditioned space based on the lower IAQ sensor readings and indoor fan speed. The economizer outside air damper will continue to close and reduce the amount of outside air CFM to the conditioned space until the damper reaches user configurable Econ Min IAQ Position (ConfigurationAIR.QAQ.MN). This will happen when the Commanded Fan Speed
(OutputsFANSF. S P D ) is at the Supply Fan Maximum Speed (ConfigurationUNITFS.MX). When the Commanded Fan
Speed (OutputsFANSF. S P D ) is between Supply Fan Maximum Speed (ConfigurationUNITFS.MX) and the
48/50PD
Supply Fan Minimum Speed (ConfigurationUNITFS.MN) the damper will operate in the shaded area of Figure 8 based on the IAQ Level (InputsAIR.QIAQ).
Economizer Operation for Units Equipped with Return CO
Sensor and outside air CO2Sensor
2
The Economizer will operate similar to Economizer Operation for Units Equipped with Return Air CO Level (InputsAIR.QIAQ) will be determined by actual outside air CO value for OAQ.
sensor detects a CO2level or IAQ Level
2
Sensor Only but the IAQ
2
measurements instead of the 400 ppm CO2default
2
Air
Air
Cooling Mode Using Space Temperature Sensor T55, T56, T58 or T59 and Humidistat (HL38MG029 or TSTATCCPLH01--B)
Enhanced dehumidifying will be provided when a humidistat (HL38MG029 or TSTATCCPLH01--B) is connected the PD unit terminal strip across the R and W2 terminals (since the PD unit does not support the use of conventional thermostat inputs the W2 terminal is reconfigured for humidity input) and Space Humidity Switch (ConfigurationUNITRH.SW) configuration variable is set to 1 (Normally Open-- no call to dehumidify). Relative humidity set point is set by adjusting the dial on the HL38MG029 or TSTATCCPLH01 --B device. When the humidistat contacts close and provide 24VAC to the W2 terminal the PD unit will reset the Supply Air Control Point (Run StatusCOOLSA.CP) by one degree F lower than the Supply Air Set Point (SetpointSASP) or the current control point if the Supply Air Set Point (SetpointSASP) has already been modified. After 5 minutes if the humidistat contacts are still closed and 24 VAC is being supplied to the W2 terminal the PD unit will reset the Supply Air Control Point (Run StatusCOOLSA.CP) lower by one more degree F. This reset cycle will continue to lower the supply air temperature every 5 minutes until the Supply Air Control Point (Run StatusCOOLSA.CP) is equal to the Supply Air Set Point (SetpointSASP) + SASP Maximum Reset Down (ConfigurationCOOLSATSA.MD). The unit will continue to operate at this reduced supply air temperature control point until the humidistat contacts open and 24VAC is no longer supplied to the W2 terminal. When 24VAC is no longer supplied to the W2 terminal the supply air control point will be reset higher by one degree F. After 3 minutes if the humidistat contacts are still open and 24VAC is not being supplied to the W2 terminal PD unit will reset the Supply Air Control Point (Run StatusCOOLSA.CP) higher by one more degree F. This reset cycle will continue to raise the Supply Air Control Point (Run StatusCOOLSA.CP) every 3 minutes until the Supply Air Control Point (Run
StatusCOOLSA.CP) is equal to the Supply Air Set Point (SetpointSASP) or the supply air control point if reset was being
applied due to cooling requirements that reset the Supply Air Set Point (SetpointSASP). Whenever Relative Humidity Reset is applied the space temperature is controlled by modulating the fan speed even if the fan was locked at 100% due to (Setpoint reset.
SASP)
Cooling Mode Using Space Temperature Sensor T55, T56, or T58 and Humidity Sensor (HL39ZZ007 or 33ZCSENRH--01)
Enhanced dehumidifying will be provided when a humidly sensor (HL39ZZ007 or 33ZCSENRH --01) 4 to 20 ma control is connected the PD unit terminal strip across the TB1 -- J10 pin 3 and 4, power to humidity sensor is connected to R and C, the RH Sensor on OAQ Input (ConfigurationUNITRH.S) is set to YES and Space Humidity Switch (ConfigurationUNITRH.SW) configuration variable is set to
0. Relative humidity set point is set by changing the value of Space RH Set point (SetpointRH.SP). When the relative humidity in the space is above the Space RH Set point (SetpointRH.SP) the PD unit controls will reset the supply air temperature by one degree F lower than the Supply Air Set Point (SetpointSASP) or the current control point if the Supply Air Set Point (SetpointSASP) has already been modified. After 5 minutes the PD unit will reset the Supply Air Control Point (Run StatusCOOLSA.CP) lower by one more degree F. This reset cycle will continue to lower the Supply Air Control Point (Run StatusCOOLSA.CP) every 5 minutes until the Supply Air Control Point (Run StatusCOOLSA.CP) is equal to the Supply Air Set Point (SetpointSASP) +SASPMaximumReset Down (ConfigurationCOOLSATSA.MD). When the relative humidity in the space goes below the Space RH Set Point
(SetpointRH.SP) -- the Space RH Deadband (SetpointRH.DB) the supply air control point will be reset
higher by one degree F. After 3 minutes if the humidity sensor reading is still below the Space RH Set Point (SetpointRH.SP) -- the Space RH Deadband (SetpointRH.DB), the PD unit will reset the Supply Air Control Point (Run
StatusCOOL cycle will continue to raise the Supply Air Control Point (Run StatusCOOLSA.CP) every 3 minutes until the supply air
temperature control point is equal to the Supply Air Set Point (SetpointSASP) or the supply air control point if reset was being applied due to cooling requirements that reset the Supply Air Set Point (SetpointSASP).
SA.CP) higher by one more degree F. This reset
Heating Modes
Gas Heating Mode Using Space Temperature Sensor T55, T56, or T58 (48PD Units Only)
For gas units, the Type of Heat Installed (ConfigurationHEATHT.TY) will be factory set to a value of
1. Heat will not operate if the outdoor temperature is greater than the
value configured for the Heating Lockout Temperature
(ConfigurationHEATHT.LO), Heat Minimum On Time (ConfigurationHEATMRT.H) and Heat Minimum Off Time (ConfigurationHEATMOT.H). Timeguards apply to both
stages of heating. Factory defaults values are 2 minute s ON and 2 minutes OFF. The Integrated Gas Controller (IGC) minimum on--time of 1 minute will be followed even if Heat Minimum On Time (ConfigurationHEATMRT.H) is lower and during Service Test.
If the indoor fan control is configured to cycle with the heating demand by setting Fan ON When Occupied Heat Minimum On Time (ConfigurationUNITOC.FN) to NO, the fan will stop after a delay configured by Fan--off Delay, Gas Heat (ConfigurationHEATFOD.G). The factory default for Fan--off Delay, Gas Heat (ConfigurationHEATFOD.G) is 45 seconds. If the IGC temperature limit switch opens within 10 minutes of the end of the gas heat cycle, the next fan off delay will
20
Page 21
be extended by 15 seconds. The maximum delay is 3 minutes. Once modified by the IGC, the fan off delay will not change back to the configured Fan--off Delay, Gas Heat (ConfigurationHEATFOD.G) unless power is reset to the control.
A light emitting diode (LED) is provided on the IGC to indicate status. During normal operation the LED is continuously on. See the Troubleshooting section if the LED is off or flashing. The IGC is located behind the gas section access panel door. See Figure 8 or 9 for location.
The 48/50PD unit control will switch automatically between cooling and heating to maintain space temperature. To minimize unnecessary changes there is a 10 minute Mode Select Timeguard (Operating ModesHEATMS.TG) after the last stage of cooling turns off and before the heating is allowed.
The unit tries to maintain the space temperature at the Occupied Heat Setpoint (SetpointOHSP) or the Unoccupied Heat Setpoint (SetpointUHSP). See the Occupancy Determination section for factors that affect the Currently Occupied (Run
StatusVIEWOCC) parameter. Heating Demand (Operating ModesHEATSPTDMD.H) is equal to the occupied or unoccupied set point minus the Space Temperature (Operating ModesHEATSPTSPT) [DMD.H = Setpoint -- SPT].
Two methods are used to add and remove stages of heating for 48PD units. The first method causes the unit to operate around its steady state number of stages. For example, if the correct number of stages is between 0 and 1, this method will cause the first stage to cycle. If the correct number of stages is between 1 and 2, this method will cause the second stage to cycle. The second method causes the unit to find the steady--state number of stages. Details of these methods are provided below.
The control uses two methods to add a stage of heating. The first method will add a stage of heating when the Heating Demand (Operating ModesHEATSPTDMD.H) plus the change in Spacetemp Trend (Operating ModesHEATSPTTRND) times the Heat Thermal Lag Factor (Operating
ModesHEAT
SPTH.LAG) is greater than the SPT Heat
Demand (+) Level (Operating ModesHEATSPTHT.PD)
[DMD.H + change TRND * H.LAG > HT.PD]. The second method will add a stage of heating when Heat Demand
(Operating ModesHEATSPTDMD.H) is greater that the SPT Heat Demand (+) Level (Operating
ModesHEATSPTHT.PD) plus 0.5 degrees F [DMD.H > HT.PD + 0.5] and the heat demand is changing at a rate greater
than 0.3 degrees F per minute.
The control uses two methods to remove a stage of heating. The first method will remove a stage of heating when the Heating Demand (Operating ModesHEATSPTDMD.H) plus the change in Spacetemp Trend (Operating ModesHEATSPTTRND) times the Heat Thermal Lag Factor (Operating ModesHEATSPTH.LAG)islessthan the SPT Heat Demand (--) Level (Operating
ModesHEATSPTHT.ND) [DMD.H + change TRND * H.LAG < HT.ND].
The second method will remove a stage of heating when Heat Demand (Operating ModesHEAT
SPTDMD.H) is less that
the SPT Heat Demand (--) Level (Operating
ModesHEATSPTHT.ND) minus 0.5 degrees F [DMD.H < HT.PD -- 0.5] and the heat demand is changing at a rate greater
than 0.3 degrees F per minute. Configurable delays also apply when adding stages per Heat Stage
Increase Time (ConfigurationHEATH.INC) or removing stages per Heat Stage Decrease Time
(ConfigurationHEATH.DEC). Heat Minimum On Time (ConfigurationHEATMRT.H) and Heat Minimum Off Time (ConfigurationHEATMOT.H) also apply.
Supply--Air Temperature Sensor (SA
T)
The SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) affects the Supply Air Temperature (TemperaturesAIR.TSAT) value displayed. This configuration is accessible via the Scrolling Marquee on the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H).
When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) =DSBL, the Supply Air Temperature (T emperaturesAIR.TSAT) value on the Scrolling Marquee and the CCN tables will be forced to zero when heat outputs come ON and for 5 minutes after. The default Supply Air Temperature (TemperaturesAIR.TSAT) location is at the fan inlet, upstream of the heat section.
When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) =ENBL, the Supply Air Temperature (TemperaturesAIR.TSAT) sensor reading is displayed at the Scrolling Marquee and the CCN tables during heating mode. This setting should only be used if the original SAT sensor wires are removed from the Main Base Board (MBB) and replaced by an accessory SAT sensor located in the supply duct downstream of the heat section. There are then two supply air temperature limits that become active, the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L) the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U). Any time the supply air temperature rises above the Maximum SAT Lower Level (ConfigurationHEATSAT
SAM.L) the
heat staging will be limited to what is currently on and no additional stages can be added until the supply air temperature falls below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L). If the supply air temperature rises above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then heating will be reduced by removing a heat stage. That stage can not be added again until the Supply Air Temperature (TemperaturesAIR.TSAT) falls below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L).Ifthe supply air temperature stays above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then another stage will be removed after the Heat Stage Decrease Time (ConfigurationHEATH.DEC).
In heating mode the PD control will maintain the Occupied Heat Set Point (SetpointOHSP) or the Unoccupied Heat Set Point (SetpointUHSP) by turning on or off the Stage 1 and Stage 2 Gas Heat at the Supply Fan Minimum Speed (ConfigurationUNITFS.MN).
When the space temperature sensor detects the space temperature below the Occupied Heat Set Point (SetpointOHSP) or Unoccupied Heat Set Point (SetpointUHSP) and power is sent to the Integrated Gas Unit Controller (IGC) board. The heat staging is determined as described above and the Integrated Gas Controller (IGC) initiates the gas heat module start-- up.
Gas Heat
Start--Up
An LED (light-emitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed and the induced--draft motor is running. The induced-draft motor is then energized, and when speed is proven with the Hall Effect sensor on the motor, the ignition activation period begins. The burners will ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, if the burners still have not lit, heating is locked out. When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the Hall Effect sensor, as well as the flame sensor. If for some reason the over temperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas
48/50PD
21
Page 22
will not be interrupted to the burners and heating will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control. When the indoor fan turns on after the 40 or 45 second delay the indoor fan will run at 100% fan speed.
Gas Heat
When additional heat is required, power is supplied to the second stage of the main gas valve. When the space temperature is 0.5F above the Occupied Heat Set Point (SetpointOHSP) or Unoccupied Heat Set Point (SetpointUHSP) power is removed from the second stage of the main gas valve and to the IGC W1 terminal. Both stage 1 and stage 2 of the gas valve closes, interrupting the flow of gas to the main burners.
Gas Heat Shut
If power to the IGC W1 terminal lasted less than 1 minute, the heating cycle will not terminate until 1 minute after power is applied to the W1 terminal of the IGC board. If the over temperature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 minutes.
48/50PD
Once modified, the fan off delay will not change back to 45 seconds unless power is reset to the control. A LED indicator is provided on the IGC to monitor operation. The IGC is located in the gas burner section and can be accessed by opening the gas access door. During normal operation, the LED is continuously on.
Gas Heat with
When there is a call for heat as described above the indoor fan will operate at the Supply Fan Maximum Speed (ConfigurationUNITFS.MX) configuration setting and the economizer outdoor air damper will move to the Econ Min at Max Fan Speed (ConfigurationECONMP.MX) position. The economizer outdoor air damper is closed when the indoor fan is not operating.
Staging
Down
Economizer
Electric Heating Mode Using Space Temperature Sensor T55, T56, or T58 (50PD Units Only)
For electric heat units with factory installed electric heat, the Type of Heat Installed (ConfigurationHEATHT.TY) will be factory set to a value of 2 and the Number of Heat Stages (ConfigurationHEATN.HTR) will be factory set to match the installed heater. If electric heat is installed in the field the value for Number of Heat Stages (ConfigurationHEATN.HTR) must be changed to match the number of heat stages installed.
Heat will not operate if the outdoor temperature is greater that the value configured for the Heating Lockout Temperature
(ConfigurationHEATHT.LO), Heat Minimum On Time (ConfigurationHEATMRT.H) and Heat Minimum Off Time (ConfigurationHEATMOT.H). Timeguards apply to both
stages of heating. Factory defaults values are 2 minute s ON and 2 minutes OFF.
If the indoor fan control is configured to cycle with the heating demand by setting Fan ON When Occupied Heat Minimum On Time (ConfigurationUNITOC.FN) to NO, the fan will stop after a delay configured by Fan--off Delay, Elect Heat (ConfigurationHEATFOD.E). The factory default for Fan--off Delay, Elect Heat (ConfigurationHEATFOD.E) is 30 seconds.
The electronic control uses information from the space sensor to determine the number of heat stages required. Once the number of stages needed for heating is determined, either Heat Stage 1 Relay
(OutputsHEATHT.1), or Heat Stage 1 Relay (OutputsHEATHT.1) and Heat Stage 2 Relay (OutputsHEATHT.2) outputs will be turned on. See Gas
Heating Mode Using Space Temperature Sensor for more information.
Supply--Air Temperature Sensor (SA
The SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) affects the Supply Air Temperature (TemperaturesAIR.TSAT) value displayed. This configuration is accessible via the Scrolling Marquee on the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H).
When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) =DSBL, the Supply Air Temperature (T emperaturesAIR.TSAT) value on the Scrolling Marquee and the CCN tables will be forced to zero when heat outputs come ON and for 5 minutes after. The default Supply Air Temperature (TemperaturesAIR.TSAT) location is at the fan inlet, upstream of the heat section.
When the SAT Heat Mode Sensing (ConfigurationHEATSATSAT.H) = ENBL, the Supply Air Temperature (TemperaturesAIR.TSAT) sensor reading is displayed at the Scrolling Marquee and the CCN tables during heating mode. This setting should only be used if the original SAT sensor wires are removed from the Main Base Board (MBB) and replaced by an accessory SAT sensor located in the supply duct downstream of the heat section. There are then two supply air temperature limits that become active, the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L) the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U). Any time the supply air temperature rises above the Maximum SAT Lower Level (ConfigurationHEATSAT heat staging will be limited to what is currently on and no additional stages can be added until the supply air temperature falls below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L). If the supply air temperature rises above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then heating will be reduced by removing a heat stage. That stage can not be added again until the Supply Air Temperature (TemperaturesAIR.TSAT) falls below the Maximum SAT Lower Level (ConfigurationHEATSATSAM.L).Ifthe supply air temperature stays above the Maximum SAT Upper Level (ConfigurationHEATSATSAM.U), then another stage will be removed after the Heat Stage Decrease Time (ConfigurationHEATH.DEC).
Temperature Compensated Start
This logic is used when the unit is in the unoccupied state. The control will calculate early Start Bias time based on Space Temperature deviation from the occupied cooling and heating set points. This will allow the control to start the unit so that the space is at conditioned levels when the occupied period starts. This is required for ASHRAE 90.1 compliance.
Setting Up the System
The settings for temperature compensated start can be found in the local display under ConfigurationUNIT.
ITEM EXPANSION RANGE UNITS CCN POINT
TCS.C
TCS.H
Temp Comp Strt Cool Factr (TCS.C)
This is the factor for the start time bias equation for cooling.
Temp Comp Strt Heat Factr (TCS.H)
This is the factor for the start time bias equation for heating.
IMPORTANT: Temperature compensated start is disabled when these factors are set to 0.
Temp.Cmp.Strt.Cool Factr 0 --- 6 0 min TCSTCOOL
Temp.Cmp.Strt.Heat Factr 0 --- 6 0 min TCSTHEAT
T)
SAM.L) the
22
Page 23
Temperature Compensated Start Logic
The following conditions must be met for the algorithm to run:
S Unit is in unoccupied state. S Next occupied time is valid. S Current time of day is valid. S Valid space temperature reading is available (sensor or CCN
network).
The algorithm will calculate a Start Bias time in minutes using the following equations:
If (space temperature > occupied cooling set point)
Start Bias Time = (space temperature -- occupied cooling set point)*TCS.C
If (space temperature < occupied heating set point)
Start Bias Time = (occupied heating set point -- space temperature)*TCS.H
When the Start Bias Time is greater than zero the algorithm will subtract it from the next occupied time to calculate the new start time. When the new start time is reached, the Temperature Compensated Start mode is set, the fan is started and the unit controlled as in an occupied state. Once set, Temperature Compensated mode will stay on until the unit goes into the Occupied mode. The Start Bias Time will be written into the CCN Linkage Equipment Table if the unit is controlled in DAV mode. If the Unoccupied Economizer Free Cool mode is active when temperature compensated start begins, the Unoccupied Free Cool mode will be stopped.
IMPORTANT: The maximum minutes Start Bias can be is 180.
Carrier Comfort Network (CCN)R Configuration
It is possible to configure the ComfortLinkcontrol to participate as an element of the Carrier Comfort Network (CCN) system directly from the local display. This section will deal with explaining the various programmable options which are found under the CCN sub-menu in the Configuration mode.
The major configurations for CCN programming are located in the local displays at ConfigurationCCN. See Appendix A.
CCN Address (CCN.A)
This configuration is the CCN address the rooftop is assigned.
CCN Address (CCN.B)
This configuration is the CCN bus the rooftop is assigned.
CCN Baud Rate (BAUD)
This configuration is the CCN baud rate.
CCN Time/Date Broadcast (BRODB.TIM)
If this configuration is set to ON, the control will periodically send the time and date out onto the CCN bus once a minute. If this device is on a CCN network then it will be important to make sure that only one device on the bus has this configuration set to ON. If more than one time broadcaster is present, problems with the time will occur.
IMPORTANT: Only the time and date broadcaster can perform
daylight savings time adjustments. Even if the rooftop is stand alone, the user may want to set this to ON to accomplish the daylight/savings function.
CCN OAT Broadcast (BRODB.OAT)
If this configuration is set to ON, the control will periodically broadcast its outside-air temperature at a rate of once every 30 minutes.
Global Schedule Broadcast (BRODB.GS)
If this configuration is set to ON and the schedule number (SCH.N) is between 65 and 99, then the control will broadcast the internal time schedule once every 2 minutes.
CCN Broadcast Acknowledger (BRODB.ACK)
If this configuration is set to ON, then when any broadcasting is done on the bus, this device will respond to and acknowledge. Only one device per bus can be configured for this option.
Schedule Number (SCH.OSCH.N)
This configuration determines what schedule the control may follow.
SCH.N = 0 The control is always occupied.
SCH.N = 1 The control follows its internal time
schedules. The user may enter any number between 1 and 64 but it will be overwritten to “1” by the control as it only has one internal schedule.
SCH.N = 65--99 The control is either set up to
receive to a broadcasted time
schedule set to this number or the
control is set up to broadcast its
internal time schedule (B.GS)tothe
network and this is the global
schedule number it is broadcasting.
If this is the case, then the control
still follows its internal time
schedules.
Accept Global Holidays? (SCH.OHOL.G)
If a device is broadcasting the time on the bus, it is possible to accept the time yet not accept the global holiday from the broadcast message.
Override Time Limit (SCH.OOV.TL)
This configuration allows the user to decide how long an override occurs when it is initiated. The override may be configured from 1 to 4 hours. If the time is set to 0, the override function will become disabled.
Timed Override Hours (SCH.OOV.EX)
This displays the current number of hours left in an override. It is possible to cancel an override in progress by writing “0” to this variable, thereby removing the override time left.
SPT Override Enabled? (SCH.OOV.SP)
If a space sensor is present, then it is possible to override an unoccupied period by pushing the override button on the T55 or T56 sensor. This option allows the user to disable this function by setting this configuration to NO.
Demand Limit
Demand Limit Control may override the cooling algorithm to limit or reduce cooling capacity during run time. The term Demand Limit Control refers to the restriction of machine capacity to control the amount of power that a machine will use. This can save the owner money by limiting peaks in the power supply. Demand limit control is intended to interface with an external network system. This is through a CCN Loadshed POC Device or writing to network points.
To limit stages through network writes, the points Run Status COOLMAX.C and Run StatusHEATMAX.H are forced on the network through CCN points MAX_CAPC and MAXHSTGS respectively. Force these to the desired maximum cooling/dehumidification capacity and the maximum heating stages, respectively. When there is no force on these points, they automatically reset to allow full cooling/dehumidification capacity and all heating stages to be used. These points are reset at power-- on/reset (POR).
When using the Loadshed POC to do Demand Limiting, the cool capacity and heat stage limits under both Redline and Loadshed conditions can be set individually with configuration decisions. If the active stages are greater then the loadshed or redline configurations when a loadshed or redline command is given, the unit will reduce capacity or remove stages. The configuration points can be found in ConfigurationCCNLDS.
23
48/50PD
Page 24
Loadshed Group Number (S.GRP)
This corresponds to the loadshed supervisory devices that reside elsewhere on the CCN network and broadcast loadshed and redline commands to its associated equipment parts. This variable will default to zero which is an invalid group number. This allows the loadshed function to be disabled until configured.
Redline Max Capacity (R.MXC)
This configuration tells the unit the maximum cooling/dehumidification capacity allowed active during a loadshed condition.
Redline Max Heat Stages (R.MXH)
This configuration tells the unit the maximum heating stages allowed to be on during a redline condition.
Loadshed Max Heat Stages (R.MXH
This configuration tells the unit the maximum heating stages allowed to be on during a loadshed condition.
The two Demand Limiting methods can be active simultaneously. The lowest cool capacity and heat stage limits imposed by either method are applied, and these “effective limits” are shown in the
48/50PD
points CAPLIMIT (Run StatusCOOLLMT.C)and HSTGLIMT (Run StatusHEATLMT.H), respectively. In normal running mode, these limits will prevent capacity/stages from being added, or capacity/stages to be removed, as applicable. In test mode, these limits are ignored, and the user may continue to operate at full load.
The point MODEDMDL (Run StatusMODED.LMT)isused to show if any Demand Limiting is in effect that prevents the unit from operating either cooling or heating at full--capacity.
IMPORTANT: MODEDMDL may reflect that staging is NOT limited even though Loadshed is active or the network points are being forced, if the capacity/stage limits in effect are not less than the capacity/stages present in the unit.
If a more drastic mode of Demand Limiting is required, the network point HVACDOWN (Run StatusMODEHV.DN) can be used to prohibit the unit from selecting any HVAC mode, thus preventing the operation of the supply fan, compressors, condenser fans, and heat stages. This point must also be forced, and is reset automatically when not forced, and at POR.
Alarm Handlin g
There are a variety of different alerts and alarms in the system. Alerts are indicated by TXXX (where XXX is the alert number) on the display and generally signify that the improperly functioning circuit can restart without human interaction. If an alarm occurs, indicated by AXXX (where XXX is the alarm numb er), the damaged circuit will generally not restart without an alarm reset via the Scrolling Marquee display or CCN.
The response of the control system to various alerts and alarms depends on the seriousness of the particular alert or alarm. In the mildest case, an alert does not affect the operation of the unit in any manner. An alert can also cause a “strike.” A “striking” alert will cause the circuit to shut down for 15 minutes. This feature reduces the likelihood of false alarms causing a properly working system to be shut down incorrectly. If three strikes occur before the circuit has an opportunity to show that it can function properly, the circuit will strike out, causing the shutdown alarm for that particular circuit. Once activated, the shutdown alarm can only be cleared via an alarm reset.
However, circuits with strikes will be given an opportunity to reset their strike counter to zero. As discussed above, a strike typically causes the circuit to shut down. Fifteen minutes later, that circuit will once again be allowed to run. If the circuit is able to run for 1 minute, its replacement circuit will be allowed to shut down (if not required to run to satisfy requested stages). However, the “troubled” circuit must run continuously for a user defined time (ConfigurationCOOLRST.C) with no detectable problems
before the strike counter will be reset to zero. Default value is 5 minutes.
CCN Alarm Broadcast
Operators of CCN networks might not want to be notified of “striking” alerts for refrigerant circuits until the circuit has been shut down due to 3 strikes. Set the cooling configuration of Alert Each Strike (ConfigurationCOOLALM.N on display, ALM_NOW on CCN) to YES to broadcast each circuit strike alert. Set Alert Each Strike to NO to broadcast only circuit shut down. Alert Each Strike configuration is ignored during Service Test and all alerts are broadcast.
Alarm Relay Output
The alarm relay output is a normally open 24 vac output between field connection terminal board terminals C and X. Selection of which alerts and alarms will result in closing of the alarm relay may be set in the Alarm Relay Configuration (ConfigurationALM.O). Setting a configuration to YES will result in the alarm output relay, ALRM, status of ON and 24 vac between C and X when that particular condition is in an alarm state. Setting a configuration to NO will result in no action by the alarm output relay for that particular condition.
IMPORTANT: An accessory filter switch can be used along with the alarm relay output function to indicate dirty filter service need.
See the Troubleshooting section for more information on viewing, diagnosing, and clearing alerts and alarms.
TROUBLESHOOTING
The Scrolling Marquee display shows the actual operating conditions of the unit while it is running. If there are alarms or there have been alarms, they will be displayed in either the current alarm list or the history alarm list. (See Table 8.) The Service Test mode allows proper operation of the compressors, fans, and other components to be checked while the unit is not operating. See Service Test.
Complete Unit Stoppage
There are several conditions that can cause the unit not to provide heating or cooling:
S If an alarm is active which causes the unit to shut down,
diagnose the problem using the information provided in Alarms
and Alerts section below.
S Cooling and heating loads are satisfied. S Programmed occupancy schedule. S General power failure. S Tripped CB1 or CB2 (24-volt transformer circuit breakers). S Unit is turned off through the CCN network. S If outdoor-air temperature is less than the Compressor Lockout
Temperature (CA.LO) configuration value, unit cannot cool.
S If outdoor-air temperature is greater than the Heating Lockout
Temperature (HT.LO) configuration value, unit cannot heat.
Restart Procedure
Before attempting to restart the machine, check the alarm list to determine the cause of the shut down. If the shutdown alarm for a particular control function has occurred, determine and correct the cause before allowing the unit to run under its own control again. When there is problem, the unit should be diagnosed in Service Test mode. The alarms must be reset before the control function can operate in either Normal mode or Service Test mode.
Control Module Communication
Red LED
Proper operation of the MBB, ECB and AUX1 control boards can be visually checked by looking at the red status LEDs. When operating correctly, the red status LEDs should blink in unison at a rate of once every 2 seconds. If the red LED on the ECB and
24
Page 25
AUX1 is not blinking, check the DIP switch positions on the board. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. A blinking red LED at the rate of once per second means that software is not loaded on the board. Also, be sure that the board is supplied with the current software. If necessary, reload current software. A board LED that is lit continuously should be replaced.
Green LED
The MBB, ECB and AUX1 each have one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. If LEN LED is not blinking, check LEN connections for potential communication errors (MBB J3, J4, and J5). Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB also provides both power and communication directly to the Scrolling Marquee display. The J5
Table 7 — LEN and CCN Communication Resistances
connector on the MBB provides a LEN interface at the field connection terminal (TB).
Yellow LED
The MBB has one yellow LED which is used to indicate CCN communication activity. The Carrier Comfort Network® (CCN) LED will blink during times of network communication.
Communication Failures
If the Scrolling Marquee or Navigator display Communication Failure or the green or yellow LED’s do not flash on the boards then the problem could be the communication chip on one of the control boards (MBB, ECB or AUX1). Use an ohm meter to measure the resistance on the communication pins of the boards to determine if the board is bad. If the reading is less than half the value indicated in Table 7, then the board needs to be replaced.
Device
MBB
ECB
AUX1 ---
Board Serial
Number
Prior to 4702N
Starting 4702N
Prior to 0803N
Starting 0803N
(LEN) Resistance between Pins/
Pins 1 to 3 Pins 1 to 2 Pins 2 to 3 Pins 5 to 7 Pins 5 to 6 Pins 6 to 7
15K
J3, J4, & J5
18.9K
J3, J4, & J5
5.9K J2
18.9K J2
29K
J9
Connector
7.5K
J3, J4, & J5
9.9K
J3, J4, & J5
5.2K J2
9.9K J2
16K
J9
7.5K
J3, J4, & J5
9.9K
J3, J4, & J5
5K
J2
9.9K J2
13.5K J9
(CCN) Resistance between Pins/
15K
J5
18.9K J5
--- --- ---
--- --- ---
--- --- ---
IMPORTANT: The resistive values should be read when the board is powered off and the unit is locked out.
Alarms and Alerts
Viewing and Clearing Unit Alarms
Presence of active alarms will be indicated on the Scrolling Marquee display by the Alarm Status light turning on and by the number of active alarms being displayed in the automatic View of Run Status. Presence of active alarms may also be signaled on the Alarm Output terminals. Each alarm may also be broadcast on the CCN network. Active alarms and past alarm history can be reviewed and cleared via the local display or a CCN device. The following menu locations are used for the local display:
AlarmsR.CURR (Reset All Current Alarms)
Change to YES to reset all active alarms. Turning unit power off will also reset all current alarms.
AlarmsR.HIST (Reset Alarm History)
Change to YES to reset the alarm history. Turning unit power off will not reset the alarm history.
AlarmsCURR (Currently Active Alarms)
Use the ENTER key, then scroll through any alarm numbers using the up and down arrow keys. Alarms are displayed in numerical order.
AlarmsHIST (Alarm History)
Use the ENTER key, then scroll through any alarm numbers using the up and down arrow keys. Up to 20 alarms are displayed in order of occurrence, with time and date.
The description for an alarm can be viewed on the Scrolling Marquee display by pressing ESCAPE and ENTER keys simultaneously while displaying the alarm code number. Be sure to expand description for each code, because in some cases there are different possible descriptions and causes for the same code number.
Diagnostic Alarm Codes and Possible Causes
Alert Code T051
There are 5 different texts for this alert code. There are three different alerts, two of which have corresponding test mode alerts indicated with “Service Test” in the expanded text. Pressing enter and esc on the marquee or navigator to expand the T051 alert will show you one of the below alerts. Make sure the expanded text is read correctly before troubleshooting.
S Digital Compressor Control Board Alarm
This alert occurs when the Digital Scroll Controller (DSC)
energizes its alarm relay. Refer to the DSC’s LED diagnostic to
determine which of the nine codes are present. Power cycle will
clear the DSC’s LED code. When the DSC’s alarm clears, this
alert will automatically clear.
S Compressor A1 Safety Trip
This Alert indicates that Current Sensing A1 (CS.A1) has been
enabled. The unit does not support the use of a current sensor at
this time. Change the CS.A1 to disable and this alert will clear
and not return.
(ConfigurationCOOLCS.A1)
S Compressor A1 Current Detected After Turnoff
This Alert indicates that Current Sensing A1 (CS.A1) has been
enabled. The unit does not support the use of a current sensor at
this time. Change the CS.A1 to disable and this alert will clear
and not return.
(ConfigurationCOOLCS.A1)
Alert Code T064 -- Circuit A Saturated Condensing Temperature Thermistor Failure
This alert occurs when the temperature is outside the range -- 40_ to 240_F(--40_ to 116_C). When this occurs, the control will use
Connector
7.5K J5
9.9K J5
7.5K J5
9.9K J5
48/50PD
25
Page 26
only the outdoor temperature to control the outdoor fans. If both the SCT and OAT fail, then circuit shutdown alarm will occur also. The cause of the alert is usually a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection.
Alert Code T066 -- Circuit A Saturated Suction Temperature Thermistor Failure
This alert occurs when the unit’s suction transducers are turned off internally. Cooling will not operate. This is usually due to a network force on a non exposed CCN point. Reload factory defaults or reinstall software o n the MBB. Consult the network manager if alert continues.
Alert Code T073 -- Outdoor Air Temperature Thermistor Failure
This alert occurs when the temperature is outside the range -- 40_ to 240_F(--40_ to 116_C). For all units, all ambient temperature lockout limits for cooling and heating are ignored. For all units, if both SCT and OAT fail, then circuit shutdown alarm will also occur. For economizer equipped units, the economizer will not operate to provide cooling. The economizer will still operate for ventilation. The control will use condenser temperatures for outdoor fan control. For units with CCH crankcase heat relay
48/50PD
control, the crankcase heat relay will be turned on if any compressor is off. This alert resets automatically. The cause of the alert is usually a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection.
Alert Code T074 -- Space Temperature Thermistor Failure
This alert occurs when the temperature is outside the range -- 40_ to 240_F(--40_ to 116_C). Cooling and heating will not operate. For economizer equipped units, the economizer will still operate for ventilation. This alert resets automatically. The cause of the alert is usually a faulty thermistor in the T--55, T--56, or T--58 device, a shorted or open thermistor caused by a wiring error, or a loose connection.
Alert Code T075 -- Supply Air Temperature Thermistor Failure
This alert occurs when the temperature is outside the range -- 40_ to 240_F(--40_ to 116_C). Economizer cooling and compressor operation cannot occur while this alert is active. The unit will not be allowed to enter cooling mode. This alert resets automatically. The cause of the alert is usually a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection.
Alert Code T076 -- Return Air Thermistor Failure
This alert occurs when the temperature is outside the range -- 40_ to 240_F(--40_ to 116_C). Differential dry bulb crossover control can not occur. Free cooling can only be controlled by the OAT and enthalpy. This alert resets automatically. The cause of the alert is usually a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection.
Alert Code T077 -- Space Relative Humidity Sensor Failure
This alert occurs when the input is less than 3.5 mA and the sensor is configured as installed. If a humidistat is not installed, then dehumidification will not be functional. Check sensor and wiring. This alert clears automatically.
IMPORTANT: An ECB must be installed to use the space relative humidity sensor.
Alert Code T092 -- Circuit A Suction Pressure Transducer Failure
This alert occurs when the board does not properly read the transducer voltage. A circuit cannot run when this alert is active. Use the Scrolling Marquee to reset the alarm. The cause of the alert is usually a faulty transducer, faulty 5 -- v power supply, or a loose connection.
Alert Code T102 -- Compressor A1 Current Sensor Failure
This Alert indicates that Current Sensing A1 (CS.A1) has been enabled. The unit does not support the use of a current sensor at
this time. Change the CS.A1 to disable and this alert will clear and not return. (ConfigurationCOOLCS.A1)
Alert Code T110 -- Circuit A Lo ss of Charge
This alert has “Service Test” text that will be displayed if the alert occurred during service test. This alert occurs when the compressor is OFF and the suction pressure is less than 5 psig and OAT is greater than -- 5_F for 1 continuous minute. Use the Scrolling Marquee to reset the alert. The cause of the alert is usually low refrigerant pressure or a faulty suction pressure. This alert only occurs when the compressor is OFF because the low refrigerant pressure alarms (alert T133) handle this situation when the compressor is operating.
Alert Code T126 -- Circuit A High Discharge Pressure
This alert has “Service Test” text that will be displayed if the alert occurred during service test. This alert occurs when alert T051 is active while the appropriate condensing temperature is greater than 150_F. This alert reset automatically. The cause of the alert is usually an overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil, plugged filter drier, or a faulty high--pressure switch. See Alert T051 for diagnostic procedure.
Alert Code T133 -- Circuit A Low Refrigerant Pressure
This alert has “Service Test” text that will be displayed if the alert occurred during service test. This alert occurs when the compressor is operating and the evaporating temperature (converted from the suction pressure) is less than configured low suction control levels, ConfigurationCOOLSSTSST.1 (Low Suction - Level 1) or SST.2 (Low Suction - Level 2) or SST.3 (Low Suction Level 3). The circuit SST value must be less than SST.1 (for 5 minutes), SST.2 (for 4 minutes), or SST.3 (for 3 minutes when using the economizer and 1.5 minutes when not using the economizer) for the alert to occur. When the outdoor temperature is less than 40_F, the above values are reduced 1_Ffor every 2_F the OAT is below 40_F. An alert will also occur if the circuit SST value is less than SST.3 --5_F for 20 seconds and the outdoor temperature is above 40_F. All the above timers will reset if the suction temperature rises above SST.O for 1 minute. This alert causes a strike for the respective circuit. This alert will activate when the coil becomes frosted. However, during the 15--minute reset period, the coils will thaw and strike should clear and restart if there is nothing else wrong with the circuit. The alert resets automatically. The cause of the alert is usually low refrigerant charge, dirty filters, evaporator fan operating backwards, loose or broken belt, plugged filter drier, faulty transducer, excessively cold return air, or stuck open economizer when the ambient temperature is low.
Alert Code T143 -- Circuit A Failure to Pressurize
This alert has “Service Test” text that will be displayed if the alert occurred during service test. This alert occurs when the compressor turns on and the difference between suction and discharge pressure is less then the Ckt A Minimum Pressure (ConfigurationCOOLSSTPSI.D). The pressure difference must be greater then PSI.D (default is 20 psi) after 60 seconds and stay above it while running the compressor. This alert causes a strike for the respective circuit. The alert resets automatically. The cause of the alert is usually compressor wiring causing reverse rotation or a faulty compressor.
Alert Code T153 -- Real Time Clock Hardware Failure
This alert occurs when the RTC clock chip on the MBB is not responding. Time and date functions will not operate, such as local occupancy schedules. The unit will default to 24/7 unoccupied mode. Recovery is automatic but MBB board replacement may be necessary. Cycling power to the control and reconfiguring the time and date should be tried before board replacement.
Alarm Code A154 -- Serial EEPROM Hardware Failure
The unit will completely shut down. The serial EEPROM chip on the MBB, which stores the unit’s configuration, is not responding.
26
Page 27
Recovery is automatic but MBB board replacement may be necessary. Cycling the power to the control should be tried before board replacement.
Alarm Code T155 -- Serial EEPROM Storage Failure Error
Configuration data in the serial EEPROM chip can not be verified. The unit will run to last know good values or defaults, and therefore operating errors may occur. Recovery is automatic but MBB board replacement may be necessary. Cycling power to the control and reconfiguring the control points should be tried before board replacement.
Alarm Code A156 -- Critical Serial EEPROM Storage Fail Error
The unit will completely shut down. Critical configuration data in the serial EEPROM chip can not be verified. Recovery is automatic but MBB board replacement may be necessary. Cycling power to the control and reconfiguring the critical control points should be tried before board replacement. There are no critical configurations in the 48/50PD.
Alert Code A157 -- A/D Hardware Failure
The unit will completely shut down. The analog to digital conversion chip on the MBB has failed. Recovery is automatic but MBB board replacement may be necessary. Cycling power to the control should be tried before board replacement.
Alert Code A163 -- Circuit A Down due to Failure
This alarm occurs when a circuit has 3 strikes. Use the Scrolling Marquee display to reset the alarm. Investigate the alarm that caused the strikes to occur.
Alert Code T178 -- Loss of Communication with the Capacity Control Board
This alert occurs when the MBB cannot communicate with the AUX1 board. Unit operation will b e disabled. This is usually caused by a wiring problem. Investigate using the Low Voltage Schematic, check that the AUX1 address is correct, and verify the resistance between pins on the LEN connections.
Alert Code T179 -- Loss of Communication with the Economizer Control Board
This alert occurs when the MBB cannot communicate with the ECB. Economizer operation will be disabled. This is usually caused by a wiring problem. If a relative humidity sensor is installed and configured but there is not an ECB installed on the unit, this alert will be generated (the ECB is required for RH sensor operation). Investigate using the Low Voltage Schematic, check that the ECB address is correct, and verify the resistance between pins on the LEN connections.
Alert Code T180 -- Loss of Communication with the Economizer Actuator
This alert occurs when the ECB cannot communicate with the Belimo Actuator. If the analog signal is connected properly, the economizer will still be controlled through it. This is usually caused by a wiring problem, actuator failure, or the wrong actuator. Investigate using the Low Voltage Schematic, make sure the actuator is a MFT communication actuator, and verify the feedback signal from the actuator is correct.
Alarm Code A200 -- Linkage Timeout -- Comm Failure
This alarm occurs when the MBB fails to communicate with a Linkage device. This only occurs when the MBB has previously communicated with a Linkage device since last power cycle. If a back up sensor was not installed the T074 alert will occur shortly after this one. Reset power to the unit and verify Linkage is communicating.
Alarm Code A404 -- Fire Shutdown
This alarm occurs when the shutdown input is either open or closed depending upon its configuration. This alarm is usually caused by an auxiliary device that is trying to shut down the unit, e.g., smoke detector. The configuration for this switch input can be
found at variable ConfigurationUNITFS.SW. Verify that the configuration is set correct, verify the wiring and auxiliary device. This alarm resets automatically.
Alert Code T408 -- Dirty Air Filter
This alert occurs when the Filter Status switch senses a plugged filter for 120 continuous seconds after the indoor fan has been running for 10 seconds. Because the Dirty Air Filter switch can be configured normally opened or closed, the switch might be open or closed. The configuration for this switch input can be found at variable ConfigurationUNITFL.SW. Verify that the configuration is set correct and verify the wiring and filter status switch. The hose should be connected to the low side of the switch. This alert resets automatically.
Alert Code T409
There are 2 different texts for this alert code. Pressing enter and esc on the marquee or navigator to expand the T409 alert will show you one of the below alerts. Make sure the expanded text is read correctly before troubleshooting.
S Fan Status Switch On, Fan Contactor Off
This alarm occurs when the fan status switch has sensed that the
indoor fan has been on for 10 seconds and the indoor fan
feedback has determined that the indoor fan should be off.
Because the Fan Status switch can be configured normally
opened or closed, the switch might be open or closed. The
configuration for this switch input can be found at
ConfigurationUNITFN.SW. Verify that the configuration
is set correctly. Verify the wiring and fan status switch. The hose
should be connected to the high side of the switch. If the IDF is
configured to shut down the unit when this alarm occurs
(ConfigurationUNITIDF.F = YES), then this alarm can
only be reset manually and the unit is shut down. If the IDF is
not configured to shut the unit down when this alarm occurs
(IDF.F = NO), then this alarm resets automatically and no
specific control action is taken.
S Fan Status Switch Off, Fan Contactor On
This alert occurs when the fan status switch has sensed that the
indoor fan has been off for 10 seconds and the indoor fan
feedback has determined that the indoor fan should be on.
Because the Fan Status switch can be configured normally
opened or closed, the switch might be open or closed. The
configuration for this switch input can be found at
ConfigurationUNITFN.SW. Verify that the configuration
is set correctly. Verify the wiring and fan status switch. The hose
should be connected to the high side of the switch. If the IDF is
configured to shut down the unit down when this alert occurs
(ConfigurationUNITIDF.F = YES), then this alarm can
only be reset manually and the unit is shut down. If the IDF is
not configured to shut the unit down when this alert occurs
(IDF.F = NO), then this alert resets automatically and no specific
control action is taken.
Alert Code T414
There are 6 different alerts under this one alert code. Pressing enter and esc on the marquee or navigator to expand the T414 alert will show you one of the below alerts. All these alerts are generated by the Belimo actuator and reported to the ECB. These alerts can only occur if the ECB is controlling the actuator digitally through MFT.
S Economizer Damper Actuator Out of Calibration
This alert occurs when the economizer actuator reports a control
angle (Operating ModesECONC.ANG) less than the
minimum control angle (ConfigurationECONM.ANG).
27
48/50PD
Page 28
Initiate economizer calibration (Service TestINDPE.CAL)
using the Service Test menu. The economizer calibration
procedure will try to find new maximum open and closed
positions. If the alert does not clear automatically after the
calibration procedure is complete, investigate what is limiting
economizer rotation. After that step, run another calibration, but
first power off unit (spring return the damper), loosen the
actuator clamp, and while pushing the damper closed tighten the
clamp. This alert resets automatically.
S Economizer Damper Actuator Torque Above Load Limit
This alert occurs when the actuator load is too high. Investigate
to determine what is increasing damper load and verify that the
actuator is the correct size for the unit. This alert resets
automatically.
S Economizer Damper Actuator Hunting
This alert occurs when the commanded damper position is
changing too rapidly. The stop jog ration must be less than 21%
to clear this alert. Leave the actuator powered with no signal for
a few hours to allow the ratio to decrease (may have to wait
longer than a few hours). If the alert continues, determine if the
ECB or actuator is bad. This alert resets automatically.
S Economizer Damper Stuck or Jammed
This alarm occurs when the actuator senses it can no longer
move. Investigate what is stopping the rotation of the actuator
and fix. This alert resets automatically.
S Economizer Damper Actuator Mechanical Failure
This alert occurs when the actuator senses a catastrophic failure.
Investigate actuator and replace if necessary. This alert resets
Excessively
automatically.
S Economizer Damper Actuator Direction Switch Wrong Position
This alert occurs when the economizer damper direction switch
48/50PD
is in the wrong position. The direction switch should be in the
clockwise position and the actuator should be mounted so that
the CW face of the actuator is accessible. Correct if necessary.
This alert clears automatically.
Alert Code T415 -- IAQ Input Out of Range
This alert occurs when the IAQ input (on ECB) is less than 3.5 mA and the sensor is configured as installed. IAQ operation will be disabled. Check sensor and wiring. This alert clears automatically.
Alert Code T416 -- OAQ Input Out of Range
This alert occurs when the OAQ input (on ECB) is less than 3.5 mA and the sensor is configured as installed. OAQ operation will be disabled. Check sensor and wiring. This alert clears automatically.
28
Page 29
Table 8 — ComfortLinkAlarm Codes
ALARM
OR
ALERT
NUMBER
T051
T064
T066
T073 Outdoor Air Temperature Thermistor Failure
T074 Space Temperature Thermistor Failure No heating or cooling Automatic
T075 Supply Air Temperature Thermistor Failure No cooling mode Automatic
T076 Return Air Thermistor Failure
T077 Space Relative Humidity Sen sor Failur e
T092
T102 Compressor A1 Current Sensor Failure
T110
T126
T133
T143
T153 Real Timeclock Hardware Failure
A154 Serial EEPROM Hardware Failure Unit Shutdown Automatic Software failure or MBB failure
T155 Serial EEPROM Storage Failure Error Unit operation errors Automatic Software failure or MBB failure A156 Critical Serial EEPROM Storage Fail Error Unit Shutdown Automatic Software failure or MBB failure A157 A/D Hardware Failure Unit Shutdown Automatic Software failure or MBB failure
A163
* See Legend on next page
Digital Compressor Control Board Alarm No action Automatic See the DSC’s LEDs for troubleshooting
Compressor A1 Safety Trip Add Strike for Circu it A Automatic
Service Test --- Compressor A1 Safety Trip Add Strike for Circuit A Automatic
Compressor A1 Current Detected After Turnof f Service Test --- Compressor A1 Current Detected After Turnoff Circuit A Saturated Condensing Temp Thermistor Failure Circuit A Saturated Suction Temperature Thermistor Failure
Circuit A Suction Pressure Transducer Failure
Circuit A Loss of Charge Shutdown Circuit A Manual Low refrigerant or faulty suction pressure transducer Service Test --- Circuit A Loss of Charge Shutdown Circuit A Manual Low refrigerant or faulty suction pressure transducer
Circuit A High Discharge Pressure Shutdown Circuit A Automatic
Service Test --- Circuit A High Discharge Pressure
Circuit A Low Refrigerant Pressure Add Strike for Circuit A Automatic
Service Test --- Circuit A Low Refrigerant Pressure
Circuit A Failure To Pressurize Add Strike for Circuit A Automatic Wiring causing reverse rotation or faulty compressor Service Test --- Circuit A Failure To Pressurize
Circuit A Down Due to Failure Shutdown Circuit A Manual
Service Test --- Circuit A Down Due to Failure
DESCRIPTION
ACTION TAKEN BY
CONTROL
Turn o f f all
compressors
Turn o f f all
compressors
Use OAT to control
Outdoor fans
No Cooling Automatic Suction transducers internally forced inactive
No cooling with
economizer
No differential DB
crossover
If RH.S = Yes, then no
indoor hu midity control
Shutdown Circuit A Manual
If C S.A1 = Enable,
then no T051 current
alarm
Shutdown Circuit A Automatic
Add Strike for Circuit A Automatic
Add Strike for Circuit A Automatic Wiring causing reverse rotation or faulty compressor
No time and date
schedul e operation
Shutdown Circuit A Manual
RESET
METHOD
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
PROBABLE CAUSE
Current Sensing turned on (CS.A1 = Enable) and should be off Current Sensing turned on (CS.A1 = Enable) and should be off Current Sensing turned on (CS.A1 = Enable) and should be off Current Sensing turned on (CS.A1 = Enable) and should be off Faulty, shorted, or open thermistor caused by wiring error or loose connection.
Faulty, shorted, or open thermistor caused by wiring error or loose connection. Faulty, shorted, or open thermistor caused by wiring error or loose connection. Faulty, shorted, or open thermistor caused by wiring error or loose connection. Faulty, shorted, or open thermistor caused by wiring error or loose connection. Faulty, shorted, or open sensor caused by wiring error or loose connection. Faulty transducer, faulty 5 ---V power supply, or loose connection
Current Sensing turned on (CS.A1 = Enable) and should be off
An overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil, plugged filter drier, or a faulty high --- pressure switch. An overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil, plugged filter drier, or a faulty high --- pressure switch. Low refrigerant charge, dirty filters, evaporator fan turning backwards, loose or broken fan belt, plugged filter drier, faulty transducer, excessively cold return air, or stuck open economizer when the ambient temperature is low. Low refrigerant charge, dirty filters, evaporator fan turning backwards, loose or broken fan belt, plugged filter drier, faulty transducer, excessively cold return air, or stuck open economizer when the ambient temperature is low.
No time/date configured, software failure, or MBB failure
Circuit has 3 strikes or has been locked out by another alarm Circuit has 1 strike or has been locked out by another alarm
48/50PD
29
Page 30
Table 8 — ComfortLinkAlarm Codes (cont)
ALARM
OR
ALERT
NUMBER
T178
T179
T180
A200 Linkage Timeout Error --- Comm Failure
A404 Fire Shutdown Unit Shutdown Automatic Smoke detected by smoke detector
T408 Dirty Filter Alert Generated Automatic Dirty Filter
T409
48/50PD
T414
T415 IAQ Input Out of Range No IAQ Operations Automatic
T416 OAQ Input Out of Range No OAQ Operations Automatic
LEGEND
ECB -- Economizer Control Board IGC -- Integrated Gas Controller MBB -- Main Base Board OAT -- Outdoor--Air Thermistor
Loss of Communication with the Capacity Control Board Loss of communication with the Economizer Control Board Loss of communication with the Economizer Actuator
Fan Status Switch ON, Fan Contactor OFF
Fan Status Switch OFF, Fan Contactor ON
Economizer Damper Actuator Out of Calibration Economizer Damper Actuator Torque Above Load Limit Economizer Damper Actuator Hunting Excessively
Economizer Damper Stuck or Jammed Alert Generated Automatic
Economizer Damper Actuator Mechanical Failure Economizer Damper Actuator Direction Switch Wrong
DESCRIPTION
ACTION TAKEN BY
CONTROL
Unit shutdown ---HVAC
disable
No economizer
operation
No economizer
operation
No Linkage Operation
fall back to local SPT
If IDF.F = Yes, then Unit
Shutdown
If IDF.F = Yes, then Unit
Shutdown
Alert Generated Automatic
Alert Generated Automatic Actuator load too high. Check damper load.
Alert Generated Automatic Damper position changing too quickly.
Alert Generated Automatic Check actuator and replace if necessary.
Alert Generated Automatic Actuator direction control switch (CCW, CW) wrong.
RESET
METHOD
Automatic
Automatic
Automatic Communication wiring problem with actuator.
Automatic
If IDF.F =
YES, then
Manual, otherwise automatic
If IDF.F =
YES, then
Manual, otherwise automatic
Communication wiring problem with AUX1 or faulty MBB, ECB, or AUX1 Communication wiring problem with ECB or faulty MBB, ECB, or AUX1
Received a table write from Linkage before, now not receiving any linked commands
Bad Fan Status Switch. Configuration incorrect.
Tripped Circuit Breaker. Broken belt. Bad indoor fan motor. Configuration incorrect. Bad fan status switch.
Calibrate economizer (E.CAL). If problem still exist then determine what is limiting economizer rotation.
No economizer motion. Check damper blades, gears, and actuator.
Bad sensor, bad wiring, or sensor configured incorrectly. Bad sensor, bad wiring, or sensor configured incorrectly.
PROBABLE CAUSE
Cooling Troubleshooting
Use the Scrolling Marquee display or a CCN device to view the cooling status display and the cooling diagnostic display (see Appendix A) for information on the cooling operation. Check the current alarms and alarm history for any cooling alarm codes and correct any causes. (See Table 9.)
Verify any unique control configurations per installed site requirements or accessories. If alarms conditions are corrected and cleared, operation of the compressors and fans may be verified by using the Service Test mode. (See Table 5.) See Table 9 for general cooling service analysis.
30
Page 31
Table 9 — Cooling Service Analysis
Compressor and Fan Will Not Start Power failure. Call power company.
CompressorCycles(otherthan normally satisfying demand).
Compressor Operates Continuously.
Excessive Condenser Pressures. Loose condenser thermistors. Tighten thermistors.
Condenser Fans Not Operating. No Power to contactors. Fuse blown or plug at motor loose. Excessive Suction Pressure. High heat load. Check for sources and eliminate
Suction Pressure Too Low. Dirty air filters. Replace air filters.
PROBLEM CAUSE REMEDY
LEGEND
CB -- Circuit Breaker DSC -- Digital Scroll Controller TXV -- Thermostatic Expansion Valve VFD -- Variable Frequency Drive
Fuse blown or circuit breaker tripped. Check CB1 and CB2.
Disconnect off. Power disconnect. Compressor time guard to prevent short cycling. Check time guards using ComfortLinkt Scrolling
Occupancy schedule set point or supply set point not calling for Cooling.
Outdoor temperature too low. Check Compressor Lockout Temperature using
Active alarm. Check active alarms using ComfortLink Scrolling
Insufficient line voltage. Determine cause and correct. Active alarm. Check active alarms using ComfortLink Scrolling
Unit undersized for load. Decrease load or increase size of unit. Occupancy schedule set point or supply set point too
low. Compressor running at lowest capacity Compressor contactor stuck on Check cooling demand using ComfortLink Scrolling
Dirty air filters. Replace filters. Low refrigerant charge. Check pressure, locate leak, repair, evacuate, and
Condenser coil dirty or restricted. Clean coil or remove restriction.
Dirty condenser coil. Clean coil. Refrigerant overcharge. Recover excess refrigerant. Faulty TXV.
Condenser air restricted or air short cycling. Determine cause and correct. Restrictioninliquidtube. Remove restriction.
Faulty TXV.
Refrigerant overcharged. Recover excess refrigerant.
Low refrigerant charge. Check pressure, locate leak, repair, evacuate, and
Faulty TXV.
Insufficient evaporator airflow. Check belt tension. Check for other restrictions. Indoor Fan Running to slow or off while compressor isonCheck VFD display is illuminated and shows Auto
Temperature too low in conditioned area (low return --- air temperature).
Replace fuse or reset circuit breaker.
Marquee also the DSC has a 2 minute anti--- short time Check cooling demand using ComfortLink Scrolling
Marquee.
ComfortLink Scrolling Marquee.
Marquee and DSC alert flash codes
Marquee and DSC alert flash codes
Check and adjust set points if needed.
Marquee and DSC alert flash codes.
recharge.
1.Check TXV bulb mounting and secure tightly to suction line and insulate.
2.Replace TXV (and filter drier) if stuck open or closed.
1.Check TXV bulb mounting and secure tightly to suction line and insulate.
2.Replace TXV (and filter drier) if stuck open or closed.
recharge.
1.Check TXV bulb mounting and secure tightly to suction line and insulate.
2.Replace TXV (and filter drier) if stuck open or closed.
mode. Power supplied to VFD. Check 0 --- 10vdc signal present at AUX1 board.
Reset thermostat or occupancy schedule.
48/50PD
Digital S croll Controller (DSC) Troubleshooting
The 48/50PD units are equipped with a digital scroll compressor. The compressor has a solenoid unloader that is controlled by the digital scroll controller (DSC). This DSC turns the unloader on and off within a 20 second window. The amount of time the unloader is on verses off within that 20 seconds depends on the desired capacity. This means that the ComfortLink control does not have direct control of the compressor, but it does however control the power to the DSC and the signal for commanded capacity.
The DSC has three LED lights to help during troubleshooting; green, yellow, and red The DSC will run the compressor unloaded for a half a second on start up and one second on shutdown to prevent reverse rotation. A two minute anti-- short time guard is applied by the DSC after shutting the compressor off. The DSC has an alarm relay output that is connected to the MBB. When this MBB input switch is closed, the MBB activates the T051 alert. Check the LED status on the DSC for flash alarm
codes and correct any problems. Table 10 shows the DSC’s Red LED flash codes.
POWER LED (green) ⎯ indicates voltage is present at the 24VAC power terminal. When the 2 minute anti--short cycle timer is active, the green LED will flash.
UNLOADED LED (yellow) ⎯ indicates the unloader solenoid status. The LED is on when the unloader solenoid is energized.
ALERT LED (red) ⎯ communicates an abnormal system condition through a unique flash code.
All LEDs Flashing at the Same Rate ⎯ indicates 24VAC supply is too low for operation.
All LEDs On Solid at the Same Time ⎯ indicates Digital Scroll Controller failure.
Flash Code 1 Reserved for future use Flash Code 2 High Discharge Temperature
This occurs when the discharge temperature thermistor (DTT) has
31
Page 32
measured a temperature above 268 F (131 C) or the thermistor has short circuited (jumpered out).
The DSC will de--energize the compressor contactor and unloader solenoid, and the alarm relay contacts will close causing a T051 alert on the ComfortLink Control. The compressor will be allowed to restart after 30 minute delay and after the DTT reads below 250 F (120 C). The flash code and alarm relay contacts will be reset after the compressor has run for 60 minutes without any other ALERTs. If five discharge temperature ALERTs have occurred within four hours, the DSC will lock out the compressor. The lockout can only be reset by cycling the 24VAC power off and on.
Flash Code 3 ⎯ Compressor Protector Trip This occurs when the demand signal from the system controller is greater than 1.44VDC and there is no compressor current detected. This could be due to the compressor’s internal overload protector being open, fuse or breaker open, power disconnected to compressor contactor, compressor power wiring not run through DSC current transformer port or a compressor contactor failure. The DSC will de--energize the compressor contactor and unloader solenoid and the alarm relay contacts will close causing a T051
48/50PD
alert on the ComfortLink Control. The DSC will wait for the two minute anti--short cycle timer to time out and if the system controller demand signal is still greater than 1.44VDC, energize the compressor contactor again. If compressor current is detected on the restart, the ALERT code and alarm relay output will reset. The DSC will attempt to restart compressor as long as the system controller demand is above 1.44VDC. There is no lockout feature for this ALERT.
Flash Code 4 ⎯ Locked Rotor A locked rotor condition in the compressor is sensed by the DSC on four consecutive start ups. The DSC will de--energize the compressor contactor and unloader solenoid and the alarm relay contacts will close causing a T051 alert on the ComfortLink Control. This code results in a lockout and can only be reset by cycling the 24VAC power off and on.
Flash Code 5 ⎯ Demand Signal Loss This occurs when the demand signal input has dropped below
0.5VDC. The demand input signal wire may be disconnected or
the system controller providing the signal may not be powered. The DSC will de--energize the compressor contactor and unloader solenoid and the alarm relay contacts will close causing a T051 alert on the ComfortLink Control. Once the system controller demand signal input has risen above 0.5VDC, the ALERT code and alarm relay output will reset. If the demand signal is above
1.44VDC and the anti--short cycle timer has timed out, the compressor will restart.
Flash Code 6 ⎯ Discharge Thermistor Fault This occurs when the DSC is not receiving a signal from the discharge temperature thermistor (DTT). The thermistor may be missing, disconnected or a wire broken. The alarm relay contacts will close and the DSC will not increase the capacity of the compressor beyond 50% loading. This ALERT code and alarm relay output are reset by reconnecting the DTT.
Flash Code 7 Reserved for future use
Flash Code 8 Compressor Contactor Fault
This occurs when the compressor current is detected when the system controller demand signal is below 1.44VDC. The compressor contactor may have welded contacts or the contacts may be mechanically jammed. The compressor will continue to run in this condition since the DSC cannot open the compressor contactor. The DSC will energize the compressor contactor and the alarm relay contacts will close causing a T051 alert on the ComfortLink Control. The unloader solenoid will remain energized causing the compressor to run unloaded as long as the system controller demand signal is less than 1.44VDC. If the system controller demand is greater than 1.44VDC, the unloader solenoid will de--energize causing the compressor to run loaded. The ALERT code and alarm relay output are reset when current is no longer detected while system controller demand signal is below
1.44VDC. Flash Code 9 ⎯ Low 24VAC Supply
This occurs when the supply voltage to the DSC has dropped below 18.5VDC. The DSC will de-- energize the compressor contactor and unloader solenoid. The alarm relay contacts may close if the voltage is high enough for the alarm relay to pull in. The ALERT code and alarm relay output are reset when the supply voltage to the DSC rises above 19.5VAC.
LED Flash
Code
1
Flash
2
Flash
3
Flash
4
Flash
5
Flash
6
Flash
7
Flash
8
Flash
9
Flash
Table 10 — DSC Red LED Flash Codes
Description Action Taken
by Control
Reserved for Future Use N/A N/A N/A
High Discharge Temperature Compressor
shutdown
Compressor Protector Trip Compressor
shutdown
Locked Rotor Compressor
lockout
Demand Signal Loss Compressor
shutdown
Discharge Thermistor Fault Capacity Limited Automatic DTT may be missing, disconnected or a wire broken
Reserved for Future Use N/A N/A N/A
Compressor Contactor Fault Keep capacity
at 15%
Low 24VAC Supply Compressor
shutdown
Reset
Method
Automatic Compressor discharge temperature is greater then 268
degrees F or the DTT is shorted.
Automatic Compressor’s internal overload protector being open,
fuse or breaker open, power disconnected to compres­sor contactor, compressor power wiring not run through DSC current transformer port or a compressor contactor failure.
Manual Four consecutive start ups with locked rotor.
Automatic Signal wire may be disconnected or the system control-
ler providing the signal may not be powered
Automatic Compressor contactor may have welded contacts or the
contacts may be mechanically jammed
Automatic Bad connection or transformer.
Probable Cause
32
Page 33
Economizer Troubleshooting
Use the unit Scrolling Marquee display or a CCN device to view the economizer status display and the economizer diagnostic display (see Appendix A) for information on the economizer operation. Check the current alarms and alarm history for any economizer alarm codes and correct any causes. (See Table 11.)
Verify any unique control configurations per installed site requirements or accessories. If alarms conditions are corrected and cleared, operation of the economizer may be verified by using the Service Test mode (see Service Test section and T able 5). The following steps specify how to test the economizer using the Scrolling Marquee display. See Table 11 for general economizer service analysis.
1. Enter the Service Test main menu on the display.
2. Enter TEST and turn ON test mode. A password may be needed in order to turn ON the Service Test. The default password is 1111.
3. Return to the main level of Service Test.
4. Enter the INDP submenu and enter an initial value for ECON. This will drive the economizer damper to the specified position. Continue to adjust the ECON value to make sure the economizer opens and closes.
5. Because of a mechanical problem with the economizer, the actuator might acquire a new degree of rotation which is less than M.ANG. If this occurs, a “T414 Economizer Damper Actuator Out of Calibration” alert will be generated. This alert can only occur if the economizer is using digital communications (Configuration ECONE.CTL = 1or2). The economizer calibration procedure (Service TestIND.PE.CAL) will reconfigure the actuator to the new fully closed and fully open positions. To implement the calibration procedure, change E.CAL from OFF to ON. E.CAL will remain ON as long as the calibration procedure is being implemented (as long as 5 minutes). During the calibration procedure the actuator will close fully and then open fully. After the calibration is complete, the degree of rotation should be greater than M.ANG, causing the T414 alert to clear. If the T414 alert does not clear, check the economizer damper for other mechanical problems.
6. Return to Service TestTEST and turn OFF test mode. This will cause the unit to return to normal operation.
Table 11 — Economizer Service Analysis
Damper Does Not Move. Indoor Fan is off. Check for proper VFD connections. Check that
Economizer Operation is Limited to Minimum Position.
Economizer Position is Less Than Minimum Position.
Economizer Does Not Return to Minimum Position.
Damper Does Not Close on Power Loss.
Outdoor Damper Does Not Fully Close at 0% or Fully Open at 100%.
Economizer is not a configured minimum position
LEGEND
CCN -- Carrier Comfort Network IAQ -- Indoor Air Quality VFD -- Variable Frequency Drive
PROBLEM POSSIBLE CAUSE REMEDY
VFD is illuminated and in Auto mode. Unit is not configured for continuous fan operation
and there are no cooling or heating demands. Unit is in Unoccupied mode and there is no call for
heating or cooling. Tripped circuit breaker. No power to the unit.
Actuator is unplugged at motor or at economizer board. Check wiring connections. Unit is not configured for economizer. Configure unit for economizer per the
Outdoor--- air temperature is above economizer high temperature lockout.
Outdoor---air temperature is below economizer low temperature lockout.
Communication loss to economizer board. Check wiring connections. Damper is jammed. Identify the obstruction and safely remove. Minimum position is set incorrectly. Adjust minimum position setting. Outdoor--- air temperature is above economizer
high temperature lockout.
Outdoor---air temperature is below economizer low temperature lockout.
Outdoor---air thermistor is faulty. Replace outdoor--- air thermistor. Low suction pressure problem with a compressor. Economizer is operating correctly, identify
IAQ is controlling minimum damper position. Adjust the IAQ settings if incorrect,
Unit is in Unoccupied mode. Adjust unit occupied schedule if incorrect,
Damper is jammed. Identify the obstruction and safely remove. Unit is operating under free cooling. Economizer is operating correctly.
Damper is jammed or spring return is backwards. Identify the obstruction and safely remove.
Economizer actuator is out of calibration. Enter Service Test mode and run the Calibrate
Unit is operating under free cooling. Economizer is operating correctly. Unit fan speed is offsetting the economizer minimum
position to maintain proper ventilation.
Unit is off via CCN command.
instructions. Adjust the high temperature lockout setting if it is
incorrect, otherwise, economizer is operating correctly.
Adjust the low temperature lockout setting if it is incorrect, otherwise, economizer is operating correctly.
Adjust the high temperature lockout setting if it is incorrect, otherwise, economizer is operating correctly.
Adjust the low temperature lockout setting if it is incorrect, otherwise, economizer is operating correctly.
compressor problem.
otherwise, the economizer is operating correctly.
otherwise, economizer is operating correctly.
Remove actuator, flip it over and re---install.
Economizer (E.CAL) procedure.
Economizer is operating correctly.
48/50PD
33
Page 34
Heating Troubleshooting
Use the unit Scrolling Marquee display or a CCN device to view the heating status display and the heating diagnostic display (see Appendix A) for information on the heating operation. Check the current alarms and alarm history for any heating alarm codes and correct any causes. (See Table 12.) Verify any unique control configurations per installed site requirements or accessories. If alarms conditions are corrected and cleared, operation of the heat stages and indoor fan may be verified by using the Service Test mode. (See Table 5.)
Gas Heat (48PD Units Only)
See Table 12 for general gas heating service analysis. See Fig. 9 for service analysis of the IGC board logic. Check the status LED on the IGC board for any flashing alarm codes and correct any causes. (See Table 13.)
Electric Heat (50PD Units Only)
See Table 14 for electric heating service analysis.
Variable Frequency Drive (VFD) Troubleshooting
The VFD must be in “Auto” mode and when commanding it to
48/50PD
100% the voltage signal should be 10vdc across AI1 and AIGND. Verify all parameters are correct to factory defaults. See Appendix B for parameters and additional troubleshooting.
Phase Loss Protection
The phase loss protection option will monitor the three-phase electrical system to provide phase reversal and phase loss
Phase Reversal Protection
If the control senses an incorrect phase relationship, the relay (K1) will be de-energized (opening its contact). If the phase relationship is correct, the relay will be energized. The control has a self-bypass function after a pre-set time. If the control determines that the three phases stay in a correct relationship for 10 consecutive minutes, the relay will stay energized regardless of the phase sequence of three inputs as long as 24-vac control voltage is applied. This self-bypass function will be reset if all three phases are restored in a phase loss event.
Phase Loss Protection
If the reverse rotation board senses any one of the three phase inputs has no AC voltage, the relay will be de--energized (opening its contact). This protection is always active as long as 24-vac control voltage is applied, and is not affected by the self by-pass function of the phase sequence monitoring function. However, in the event of phase loss, the relay will be re-energized only if all three phases are restored and the three phases are in the correct sequence.
A red LED is provided to indicate the function of the board. See the table below.
LED STATUS FUNCTION
On Continuously Relay contact closed (normal operation).
Blinking
Off 24 vac control power not present (off).
Relay contact open (phase loss or phase reversal has occurred) --- No power will be supplied to the control system.
protection.
Table 12 — Gas Heating Service Analysis
Burners Will Not Ignite. Unit is not configured for heat. Check heating configurations using ComfortLinkt Scrolling
Inadequate Heating. Dirty air filters. Replace air filters.
Poor Flame Characteristics.
Burners Will Not Turn Off. Unit is in Minimum on---time. Check using ComfortLinkt Scrolling Marquee and the IGC alert
PROBLEM CAUSE REMEDY
Active alarm. Check active alarms using ComfortLinkt Scrolling Marquee and
No power to unit. Check power supply, fuses, wiring, and circuit breakers. No power to IGC. Check fuses and plugs. Heaters off due to time guard to prevent short
cycling. Occupancy schedule set point not calling for
Heating. No gas at main burners. Check gas line for air and purge as necessary. After purging gas
Water in gas line . Drain water and install drip.
Gas input too low. Check gas pressure at manifold. Refer to gas valve adjustment in
Occupancy schedule set point set too low. Check setpoints and adjust if necessary. Unit undersized for load. Decrease load or increase of size of unit. Restricted or low airflow. Remove restriction, verify proper fan speed operation, and check
Too much outdoor air. Check economizer position and configuration. Adjust minimum
Limitswitchcyclesmainburners. Check rotation of blower and temperature rise of unit. Adjust as
Incomplete combustion (lack of combustion air) results in: Aldehyde odors, CO, sooting flame, or floating flame.
Unit running in Service Test mode. Check using ComfortLinkt Scrolling Marquee. Main gas valve stuck. Turn off gas supply and unit power. Replace gas valve.
LEGEND
IGC -- Integrated Gas Controller SAT -- Supply Air Temperature
Marquee.
the IGC alert flash codes.
Check active alarms using ComfortLinkt Scrolling Marquee and the IGC alert flash codes.
Check using ComfortLinkt Scrolling Marquee.
line of air, allow gas to dissipate for at least 5 minutes before attempting to re---light unit.
the Service section.
SAT compared to the SAT heating limits.
position if needed using ComfortLink Scrolling Marquee. Verify proper fan speed operation.
needed. Check all screws around flue outlets and burner compartment.
Tighten as necessary. Cracked heat exchanger, replace. Unit is over---fired, reduce input. Adjust gas line or manifold
pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment.
flash codes.
34
Page 35
48/50PD
LEGEND
IDM -- Induced-Draft Motor IGC -- Integrated Gas Unit Controller
NOTE: Thermostat Fan Switch in the “AUTO” position.
C07014
Fig. 9 -- IGC Service Analysis Logic
35
Page 36
Table 13 — IGC Board LED Alarm Codes
LED
FLASH
CODE
On Normal Operation Off Hardware Failure No gas heating.
1Flash Indoor Fan On/Off Delay
2Flashes Limit Switch Fault Gas valve and igniter Off.
3Flashes Flame Sense Fault Indoor fan and inducer On. Flame sense normal.
4Flashes Four Consecutive Limit Switch
5Flashes Ignition Fault No gas heating. Heat call (W) Off.
48/50PD
6Flashes Induced Draft Motor Fault If heat off: no gas heating.
7Flashes Rollout Switch Lockout Gas valve and igniter Off.
8Flashes Internal Control Lockout No gas heating. Power reset. IGC has sensed internal hardware or software error.
9Flashes Temporary Software Lockout No gas heating. 1 hour auto reset, or
LEGEND
IGC -- Integrated Gas Unit Control LED -- Light--Emitting Diode NOTES:
1. There is a 3-- second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
DESCRIPTION
Modified
Fault
ACTION TAKEN BY
CONTROL
RESET METHOD PROBABLE CAUSE
5 seconds subtracted from On delay. 5 seconds added to Off delay (3 min max).
Indoor fan and inducer On.
No gas heating. Heat call (W) Off.
If heat on: gas valve Off and inducer On.
Indoor fan and inducer On.
Power reset. High temperature limit switch opens during heat
Limit switch closed, or heat call (W) Off.
Power reset for LED reset.
Power reset for LED reset.
Power reset for LED reset.
Inducer sense normal, or heat call (W) Off.
Power reset. Rollout switch has opened. Check gas valve
power reset.
Loss of power to the IGC. Check 5 amp fuse on IGC, power to unit, 24V circuit breaker, transformer, and wiring to the IGC.
exchanger warm-up period before fan-on delay expires. High temperature limit switch opens within 10 minutes of heat call (W) Off. See Limit Switch Fault.
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is within the range on the unit nameplate. Check wiring and limit switch operation.
TheIGCsensedaflamewhenthegasvalveshould be closed. Check wiring, flame sensor, and gas valve operation.
4 consecutive limit switch faults within a single call for heat. See Limit Switch Fault.
Unit unsuccessfully attempted ignition for 15 minutes. Check igniter and flame sensor electrode spacing, gaps,etc.Checkflamesenseandigniterwiring. Check gas valve operation and gas supply.
Inducer sense On when heat call Off, or inducer sense Off when heat call On. Check wiring, voltage, and operation of IGC motor. Check speed sensor wiring to IGC.
operation. Check induced-draft blower wheel is properly secured to motor shaft.
If fault is not cleared by resetting 24 v power, replace the IGC.
Electrical interference is disrupting the IGC software.
Table 14 — Electric Heat Service Analysis
Heat Will Not Turn On. Unit is not configured for heat. Check heating configurations using ComfortLinkt
Inadequate Heating. Dirty air filters. Replace air filters.
Heat Will Not Turn Off. Unit is in minimum heat on---time. Check using ComfortLinkt Scrolling Marquee.
PROBLEM CAUSE REMEDY
Scrolling Marquee.
Marquee.
Check using ComfortLinkt Scrolling Marquee.
ServiceTestmodeoff.
switches on heater, and manual --- reset limit switches (LS) on indoorfan housing.
replace if not.
resistance of element, replace if open.
check SAT compared to the SAT heating limits.
minimum position if needed using ComfortLinkt Scrolling Marquee. Verify proper fan speed operation.
minimum airflow. Adjust as needed.
Check using ComfortLinkt Scrolling Marquee.
LEGEND SAT -- Supply Air Temperature
Active alarm. Check active alarms using ComfortLinkScrolling
No power to unit. Check power supply, fuses, wiring, and circuit breakers. Unit is in minimum heat off ---time, or minimum
cool--- heat changeover time. Heat forced off in Service Test. Check using ComfortLinkt Scrolling Marquee. Turn
No 24 vac at heater contactor. Check transformer, circuit breaker, auto --- reset limit
Open temperature limit switch on heater. Check minimum airflow. Check limit switch when it is cool,
Bad heater elements. Power off unit and remove high voltage wires. Check
Occupancy schedule set point set too low. Check setpoints and adjust if necessary. Heat undersized for load. Decrease load or increase size of heater. Restricted or low airflow. Remove restriction, verify proper fan speed operation, and
Too much outdoor air. Check economizer position and configuration. Adjust
Limit switch cycles heaters. Check rotation of blower, temperature rise of unit, and
Occupancy schedule set point still calling for Heating.
Unit running in Service Test mode. Check using ComfortLinkt Scrolling Marquee. Heater contactor failed. Power off unit. Check contactor and replace if closed.
36
Page 37
Thermistor Troubleshooting
The electronic control uses thermistors to sense temperatures used to control operation of the unit. Resistances at various temperatures are listed in Table 15-- 17. Thermistor pin connection points are shown in the Major System Components section. The general locations of the thermistors are shown the Major System Components section.
Air Temperatures
Air temperatures are measured with 10 kilo-ohm thermistors. This includes supply-air temperature (SAT), outdoor-air temperature (OAT), space temperature sensors (T55, T56, T58), and return air temperature (RAT).
The supply air temperature (SAT), return air temperature (RAT) and outdoor air temperature (OAT) thermistors use a snap-mount to attach through the unit sheet metal panels. The snap-mount tabs must be flattened on the tip end of the sensor to release for removal from the panel. (See Fig. 10.) To reinstall, make sure the snap-mount tabs extend out.
C07015
Fig. 10 -- SAT, RAT and OAT Thermistor Mounting
Refrigerant Temperatures
Condenser coil temperatures are measured with 5 kilo-ohm thermistors. These measurements provide an approximate saturated condensing temperature for each circuit (SCT.A). Fig. 11 shows the factory locations for the SCT thermistors on 48/50PD units. Ensure that thermistors are placed at the correct location and are snapped securely over the return bend so that contact is made between the thermistor and the tube.
C07016
Fig. 11 -- Saturated Condensing Temperature Thermistor
Location
Thermistor/Temperature Sensor Check
A high quality digital volt-ohmmeter is required to perform this check.
Connect the digital voltmeter across the appropriate thermistor terminals at the J8 terminal strip on the Main Base Board (see Major System Components section).
Using the voltage reading obtained, read the sensor temperature from Table 15-- 17.
To check thermistor accuracy, measure temperature at probe location with an accurate thermocouple-type temperature-measuring instrument. Insulate thermocouple to avoid ambient temperatures from influencing reading. Temperature measured by thermocouple and temperature determined from thermistor voltage reading should be close, within 5°F, if care was taken in applying thermocouple and taking readings.
If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) using either voltage drop measured across thermistor at the J8 terminal, or by determining the resistance with unit shut down and thermistor disconnected from J8. Compare the values determined with the value read by the control in the Temperatures mode using the Scrolling Marquee display.
48/50PD
37
Page 38
Sensor Trim
Corrective offsets can be applied to the space temperature and the supply air temperature sensor readings. These corrections are set in the ConfigurationTRIM menu for the display, or in the MaintenanceTRIM table for CCN. See the Indoor Air Quality section for available adjustments to IAQ and OAQ sensor readings. The space temperature may be corrected by entering either a calibration temperature value in SPT.C, or an offset temperature value in SPT.T. The supply-air temperature may be corrected by entering either a calibration temperature value in SAT.C,oran offset temperature value in SAT.T. The return--air temperature may be corrected by entering either a calibration temperature value in RAT.C or an offset temperature value in RAT.T. Temperature corrections should only be made if sensor readings are compared to an accurate reference temperature measurement device.
Transducer Troubleshooting
The electronic control uses suction pressure transducers to measure the suction pressure of the refrigerant circuits. The pressure/voltage characteristics of these transducers are in shown in Table 18, the 5vdc power is applied to legs A and B of the transducer and legs B
48/50PD
to C represent the voltage drop shown in the table. The accuracy of these transducers can be verified by connecting an accurate pressure gauge to the second refrigerant port in the suction line.
Forcing Inputs and Outputs
Many variables may have their value forced through CCN or directly at the local display. This can be useful during diagnostic testing and also during operation, typically as part of an advanced third party control scheme. Input and output points that may be forced are indicated as ‘forcible’ in the write status column of the display and CCN tables.
If the user needs to force a variable, follow the same process as when editing a configuration parameter. A forced variable will be displayed on the Scrolling Marquee with a blinking period “.” following its value. A forced value on Navigatoraccessory is indicated with a blinking “f”. A forced value on CCN devices is indicated with “Control” if forced at the unit display, or “Supervisor” if forced via CCN. To remove a local force with the Scrolling Marquee, select the point with the ENTER key and then press the up -- arrow and down-arrow keys simultaneously.
IMPORTANT: In the case of a control power reset, any force in effect at the time of power reset will be cleared.
38
Page 39
Table 1 5 — Tempera t u re (_F) vs Resistance/Voltage Drop Values for
RAT, OAT, SAT, and SPT Thermistors (10K at 25_C Resistors)
TEMP VOLTAGE RESISTANCE TEMP VOLTAGE RESISTANCE TEMP VOLTAGE RESISTANCE
(F) DROP (V) (Ohms) (F) DROP (V) (Ohms) (F) DROP (V) (Ohms)
--- 2 5 4.758 196,453 61 2.994 14,925 147 0.890 2,166
--- 2 4 4.750 189,692 62 2.963 14,549 148 0.876 2,124
--- 2 3 4.741 183,300 63 2.932 14,180 149 0.862 2,083
--- 2 2 4.733 177,000 64 2.901 13,824 150 0.848 2,043
--- 2 1 4.724 171,079 65 2.870 13,478 151 0.835 2,003
--- 2 0 4.715 165,238 66 2.839 13,139 152 0.821 1,966
--- 1 9 4.705 159,717 67 2.808 12,814 153 0.808 1,928
--- 1 8 4.696 154,344 68 2.777 12,493 154 0.795 1,891
--- 1 7 4.686 149,194 69 2.746 12,187 155 0.782 1,855
--- 1 6 4.676 144,250 70 2.715 11,884 156 0.770 1,820
--- 1 5 4.665 139,443 71 2.684 11,593 157 0.758 1,786
--- 1 4 4.655 134,891 72 2.653 11,308 158 0.745 1,752
--- 1 3 4.644 130,402 73 2.622 11,031 159 0.733 1,719
--- 1 2 4.633 126,183 74 2.592 10,764 160 0.722 1,687
--- 1 1 4.621 122,018 75 2.561 10,501 161 0.710 1,656
--- 1 0 4.609 118,076 76 2.530 10,249 162 0.699 1,625
--- 9 4.597 114,236 77 2.500 10,000 163 0.687 1,594
--- 8 4.585 110,549 78 2.470 9,762 164 0.676 1,565
--- 7 4.572 107,006 79 2.439 9,526 165 0.666 1,536
--- 6 4.560 103,558 80 2.409 9,300 166 0.655 1,508
--- 5 4.546 100,287 81 2.379 9,078 167 0.645 1,480
--- 4 4.533 97,060 82 2.349 8,862 168 0.634 1,453
--- 3 4.519 94,020 83 2.319 8,653 169 0.624 1,426
--- 2 4.505 91,019 84 2.290 8,448 170 0.614 1,400
--- 1 4.490 88,171 85 2.260 8,251 171 0.604 1,375 0 4.476 85,396 86 2.231 8,056 172 0.595 1,350 1 4.461 82,729 87 2.202 7,869 173 0.585 1,326 2 4.445 80,162 88 2.173 7,685 174 0.576 1,302 3 4.429 77,662 89 2.144 7,507 175 0.567 1,278 4 4.413 75,286 90 2.115 7,333 176 0.558 1,255 5 4.397 72,940 91 2.087 7,165 177 0.549 1,233 6 4.380 70,727 92 2.059 6,999 178 0.540 1,211 7 4.363 68,542 93 2.030 6,838 179 0.532 1,190 8 4.346 66,465 94 2.003 6,683 180 0.523 1,169 9 4.328 64,439 95 1.975 6,530 181 0.515 1,148
10 4.310 62,491 96 1.948 6,383 182 0.507 1,128 11 4.292 60,612 97 1.921 6,238 183 0.499 1,108 12 4.273 58,781 98 1.894 6,098 184 0.491 1,089 13 4.254 57,039 99 1.867 5,961 185 0.483 1,070 14 4.235 55,319 100 1.841 5,827 186 0.476 1,052 15 4.215 53,693 101 1.815 5,698 187 0.468 1,033 16 4.195 52,086 102 1.789 5,571 188 0.461 1,016 17 4.174 50,557 103 1.763 5,449 189 0.454 998 18 4.153 49,065 104 1.738 5,327 190 0.447 981 19 4.132 47,627 105 1.713 5,210 191 0.440 964 20 4.111 46,240 106 1.688 5,095 192 0.433 947 21 4.089 44,888 107 1.663 4,984 193 0.426 931 22 4.067 43,598 108 1.639 4,876 194 0.419 915 23 4.044 42,324 109 1.615 4,769 195 0.413 900 24 4.021 41,118 110 1.591 4,666 196 0.407 885 25 3.998 39,926 111 1.567 4,564 197 0.400 870 26 3.975 38,790 112 1.544 4,467 198 0.394 855 27 3.951 37,681 113 1.521 4,370 199 0.388 841 28 3.927 36,610 114 1.498 4,277 200 0.382 827 29 3.903 35,577 115 1.475 4.185 201 0.376 814 30 3.878 34,569 116 1.453 4,096 202 0.370 800 31 3.853 33,606 117 1.431 4,008 203 0.365 787 32 3.828 32,654 118 1.409 3,923 204 0.359 774 33 3.802 31,752 119 1.387 3,840 205 0.354 762 34 3.776 30,860 120 1.366 3,759 206 0.349 749 35 3.750 30,009 121 1.345 3,681 207 0.343 737 36 3.723 29,177 122 1.324 3,603 208 0.338 725 37 3.697 28,373 123 1.304 3,529 209 0.333 714 38 3.670 27,597 124 1.284 3,455 210 0.328 702 39 3.654 26,838 125 1.264 3,383 211 0.323 691 40 3.615 26,113 126 1.244 3,313 212 0.318 680 41 3.587 25,396 127 1.225 3,244 213 0.314 670 42 3.559 24,715 128 1.206 3,178 214 0.309 659 43 3.531 24,042 129 1.187 3,112 215 0.305 649 44 3.503 23,399 130 1.168 3,049 216 0.300 639 45 3.474 22,770 131 1.150 2,986 217 0.296 629 46 3.445 22,161 132 1.132 2,926 218 0.292 620 47 3.416 21,573 133 1.114 2,866 219 0.288 610 48 3.387 20,998 134 1.096 2,809 220 0.284 601 49 3.357 20,447 135 1.079 2,752 221 0.279 592 50 3.328 19,903 136 1.062 2,697 222 0.275 583 51 3.298 19,386 137 1.045 2,643 223 0.272 574 52 3.268 18,874 138 1.028 2,590 224 0.268 566 53 3.238 18,384 139 1.012 2,539 225 0.264 557
54 3.208 17,904 140 0.996 2,488 55 3.178 17,441 141 0.980 2,439 56 3.147 16,991 142 0.965 2,391 57 3.117 16,552 143 0.949 2,343 58 3.086 16,131 144 0.934 2,297 59 3.056 15,714 145 0.919 2,253 60 3.025 15,317 146 0.905 2,209
48/50PD
39
Page 40
Table 1 6 — Tempera t u re (_F) vs. Resistance/Voltage Drop Values for SCT Sensors (5K at 25_C Resistors)
TEMP
(F)
--- 2 5 3.699 98,010 59 1.982 7,866 143 0.511 1,190
--- 2 4 3.689 94,707 60 1.956 7,665 144 0.502 1,165
--- 2 3 3.679 91,522 61 1.930 7,468 145 0.494 1,141
--- 2 2 3.668 88,449 62 1.905 7,277 146 0.485 1,118
--- 2 1 3.658 85,486 63 1.879 7,091 147 0.477 1,095
--- 2 0 3.647 82,627 64 1.854 6,911 148 0.469 1,072
--- 1 9 3.636 79,871 65 1.829 6,735 149 0.461 1,050
--- 1 8 3.624 77,212 66 1.804 6,564 150 0.453 1,029
--- 1 7 3.613 74,648 67 1.779 6,399 151 0.445 1,007
--- 1 6 3.601 72,175 68 1.754 6,238 152 0.438 986
--- 1 5 3.588 69,790 69 1.729 6,081 153 0.430 965
--- 1 4 3.576 67,490 70 1.705 5,929 154 0.423 945
--- 1 3 3.563 65,272 71 1.681 5,781 155 0.416 925
--- 1 2 3.550 63,133 72 1.656 5,637 156 0.408 906
--- 1 1 3.536 61,070 73 1.632 5,497 157 0.402 887
--- 1 0 3.523 59,081 74 1.609 5,361 158 0.395 868
--- 9 3.509 57,162 75 1.585 5,229 159 0.388 850
--- 8 3.494 55,311 76 1.562 5,101 160 0.381 832
--- 7 3.480 53,526 77 1.538 4,976 161 0.375 815
--- 6 3.465 51,804 78 1.516 4,855 162 0.369 798
--- 5 3.450 50,143 79 1.493 4,737 163 0.362 782
--- 4 3.434 48,541 80 1.470 4,622 164 0.356 765
--- 3 3.418 46,996 81 1.448 4,511 165 0.350 750
--- 2 3.402 45,505 82 1.426 4,403 166 0.344 734
--- 1 3.386 44,066 83 1.404 4,298 167 0.339 719
48/50PD
10 3.185 31,202 94 1.179 3,318 178 0.282 581 11 3.165 30,260 95 1.160 3,243 179 0.277 570 12 3.145 29,351 96 1.141 3,170 180 0.272 561 13 3.124 28,473 97 1.122 3,099 181 0.268 551 14 3.103 27,624 98 1.104 3,031 182 0.264 542 15 3.082 26,804 99 1.086 2,964 183 0.259 533 16 3.060 26,011 100 1.068 2,898 184 0.255 524 17 3.038 25,245 101 1.051 2,835 185 0.251 516 18 3.016 24,505 102 1.033 2,773 186 0.247 508 19 2.994 23,789 103 1.016 2,713 187 0.243 501 20 2.972 23,096 104 0.999 2,655 188 0.239 494 21 2.949 22,427 105 0.983 2,597 189 0.235 487 22 2.926 21,779 106 0.966 2,542 190 0.231 480 23 2.903 21,153 107 0.950 2,488 191 0.228 473 24 2.879 20,547 108 0.934 2,436 192 0.224 467 25 2.856 19,960 109 0.918 2,385 193 0.220 461 26 2.832 19,393 110 0.903 2,335 194 0.217 456 27 2.808 18,843 111 0.888 2,286 195 0.213 450 28 2.784 18,311 112 0.873 2,239 196 0.210 445 29 2.759 17,796 113 0.858 2,192 197 0.206 439 30 2.735 17,297 114 0.843 2,147 198 0.203 434 31 2.710 16,814 115 0.829 2,103 199 0.200 429 32 2.685 16,346 116 0.815 2,060 200 0.197 424 33 2.660 15,892 117 0.801 2,018 201 0.194 419 34 2.634 15,453 118 0.787 1,977 202 0.191 415 35 2.609 15,027 119 0.774 1,937 203 0.188 410 36 2.583 14,614 120 0.761 1,898 204 0.185 405 37 2.558 14,214 121 0.748 1,860 205 0.182 401 38 2.532 13,826 122 0.735 1,822 206 0.179 396 39 2.506 13,449 123 0.723 1,786 207 0.176 391 40 2.480 13,084 124 0.710 1,750 208 0.173 386 41 2.454 12,730 125 0.698 1,715 209 0.171 382 42 2.428 12,387 126 0.686 1,680 210 0.168 377 43 2.402 12,053 127 0.674 1,647 211 0.165 372 44 2.376 11,730 128 0.663 1,614 212 0.163 367 45 2.349 11,416 129 0.651 1,582 213 0.160 361 46 2.323 11,112 130 0.640 1,550 214 0.158 356 47 2.296 10,816 131 0.629 1,519 215 0.155 350 48 2.270 10,529 132 0.618 1,489 216 0.153 344 49 2.244 10,250 133 0.608 1,459 217 0.151 338 50 2.217 9,979 134 0.597 1,430 218 0.148 332 51 2.191 9,717 135 0.587 1,401 219 0.146 325 52 2.165 9,461 136 0.577 1,373 220 0.144 318 53 2.138 9,213 137 0.567 1,345 221 0.142 311 54 2.112 8,973 138 0.557 1,318 222 0.140 304 55 2.086 8,739 139 0.548 1,291 223 0.138 297 56 2.060 8,511 140 0.538 1,265 224 0.135 289 57 2.034 8,291 141 0.529 1,240 225 0.133 282
58 2.008 8,076 142 0.520 1,214
VOLTAGE DROP (V)
0 3.369 42,679 84 1.382 4,196 168 0.333 705 1 3.352 41,339 85 1.361 4,096 169 0.327 690 2 3.335 40,047 86 1.340 4,000 170 0.322 677 3 3.317 38,800 87 1.319 3,906 171 0.317 663 4 3.299 37,596 88 1.298 3,814 172 0.311 650 5 3.281 36,435 89 1.278 3,726 173 0.306 638 6 3.262 35,313 90 1.257 3,640 174 0.301 626 7 3.243 34,231 91 1.237 3,556 175 0.296 614 8 3.224 33,185 92 1.217 3,474 176 0.291 602 9 3.205 32,176 93 1.198 3,395 177 0.286 591
RESISTANCE
(Ohms)
TEMP (F)
VOLTAGE DROP (V)
RESISTANCE
(Ohms)
TEMP (F)
VOLTAGE DROP (V)
RESISTANCE
(Ohms)
40
Page 41
Table 17 — Temperature vs Resistance Values for the DTT Thermistor
(86K at 25_C Resistors)
Degree C Degree F Resistance (k Ohms)
--- 4 0 --- 4 0 2889.60
--- 3 5 --- 3 1 2087.22
--- 3 0 --- 2 2 1522.20
--- 2 5 --- 1 3 1121.44
--- 2 0 --- 4 834.72
--- 1 5 5 627.28
--- 1 0 14 475.74
--- 5 23 363.99
0 32 280.82
5 41 218.41
10 50 171.17
15 59 135.14
20 68 107.44
25 77 86.00
30 86 69.28
35 95 56.16
40 104 45.81
45 113 37.58
50 122 30.99
55 131 25.68
60 140 21.40
65 149 17.91
Degree C Degree F Resistance (k Ohms)
70 158 15.07
75 167 12.73
80 176 10.79
85 185 9.20
90 194 7.87
95 203 6.77
100 212 5.85
105 221 5.09
110 230 4.45
115 239 3.87
120 248 3.35
125 257 2.92
130 266 2.58
135 275 2.28
140 284 2.02
145 293 1.80
150 302 1.59
155 311 1.39
160 320 1.25
165 329 1.12
170 338 1.01
175 347 0.92
180 356 0.83
48/50PD
41
Page 42
Table 18 — Pressure (psig) vs. Voltage Drop Values for Suction Pressure Transducers
PRESSURE
(psig)
0 2 4 6
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
48/50PD
40 42 44 46 48 50 52 54 56 58 60 62 64 66
VOLTAGE DROP (V)
0.465
0.485
0.505
0.524
0.544
0.564
0.583
0.603
0.623
0.642
0.662
0.682
0.702
0.721
0.741
0.761
0.780
0.800
0.820
0.839
0.859
0.879
0.898
0.918
0.938
0.958
0.977
0.997
1.017
1.036
1.056
1.076
1.095
1.115
PRESSURE
(psig)
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134
VOLTAGE DROP (V)
1.135
1.154
1.174
1.194
1.214
1.233
1.253
1.273
1.292
1.312
1.332
1.351
1.371
1.391
1.410
1.430
1.450
1.470
1.489
1.509
1.529
1.548
1.568
1.588
1.607
1.627
1.647
1.666
1.686
1.706
1.726
1.745
1.765
1.785
PRESSURE
(psig)
136 138 140 142 144 146 148 150 152 154 156 158 160 162 164 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202
VOLTAGE DROP (V)
1.804
1.824
1.844
1.863
1.883
1.903
1.922
1.942
1.962
1.982
2.001
2.021
2.041
2.060
2.080
2.100
2.119
2.139
2.159
2.178
2.198
2.218
2.237
2.257
2.277
2.297
2.316
2.336
2.356
2.375
2.395
2.415
2.434
2.454
PRESSURE
(psig)
204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248 250 252 254 256 258 260 262 264 266 268 270
VOLTAGE DROP (V)
2.474
2.493
2.513
2.533
2.553
2.572
2.592
2.612
2.631
2.651
2.671
2.690
2.710
2.730
2.749
2.769
2.789
2.809
2.828
2.848
2.868
2.887
2.907
2.927
2.946
2.966
2.986
3.005
3.025
3.045
3.065
3.084
3.104
3.124
MAJOR SYSTEM COMPONENTS
General
The 48/50PD single package rooftop units contain the ComfortLinkelectronic control system that monitors all operations of the rooftop. The control system is composed of several main control components and available factory-installed options or field-installed accessories as listed in sections below. See Fig. 12--14 for the control and power schematics for 48/50PD. Fig. 15 shows the layout of the control box, unit, and thermistor and transducer locations for the 48/50PD.
42
Page 43
48/50PD
Fig. 12 -- 48PD Control Wiring Schematic
43
C08582
Page 44
48/50PD
Fig. 13 -- 50PD Control Wiring Schematic
44
C08583
Page 45
48/50PD
Fig. 14 -- 48/50PD Power Wiring Schematic and Legend
45
C08584
Page 46
48/50PD
Fig. 15 -- Typical Unit Component Arrangement
46
C08657
Page 47
Main Base Board (MBB)
See Fig. 16 and Table 19. The MBB is the center of the ComfortLink control system. It contains the major portion of the operating software and controls the operation of the unit. The MBB continuously monitors input/output channel information received from its inputs and from the Economizer Control Board (ECB). The MBB receives inputs from thermistors and transducers.
The MBB also receives the Current Sensor inputs for compressors and other discrete or digital inputs. The MBB reads space
RED LED - STATUS GREEN LED -
CEPL130346-01
LEN (LOCAL EQUIPMENT NETWORK)
temperature (SPT) from either a T--55, T-- 56 or T-- 58 device and space temperature offset (SPTO) from a T--56 device. See Field-Installed Accessories section. The MBB controls 9 relays.
IMPORTANT: The Main Base Board (MBB) has a 3-position instance jumper that is factory set to ‘1.’ Do not change this
setting.
YELLOW LED ­CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER (SET TO 1)
J1
J6
J4
J5
J2
J3
J7
LEN
CCN
STATUS
J8
Fig. 16 -- Main Base Board (MBB)
48/50PD
J10
J9
C07026
47
Page 48
Table 19 — MBB Connections
DISPLAY
NAME
Input power from TRAN1 control box 24 VAC J 1 , 1 --- 3 IGC Fan Request gas section switch input J6, 4
FDWN Fire shutdown switch supply/return/space switch input J6, 6
HUM Space Humidity switch space switch input J7, 4
DigitalScrollUnloader switch input J7, 6
C.ALM Scroll Compressor Alarm switch input J7, 8
CMP.A Compressor A Feedback switch input J7, 10
FIL.S Filter status switch indoor fan section switch input J 9 , 2 --- 3
CS.A1 Compressor A1 Current Sensor control box 0--- 5vdc digital input J 9 , 1 0 --- 1 2
SPT Space temperature (T55/56) space 10k thermistor J 8 , 1 --- 2
SPTO Space temperature offset (T56) space 10k thermistor J 8 , 2 --- 3
OAT Outdoor air temperature outdoor coil support 10k thermistor J 8 , 5 --- 6
SAT Supply air temperature
SCT.A Saturated condenser temperature, circuit A outdoor coil, circuit A 5k thermistor J 8 , 9 --- 1 0
RAT Return air temperature Return air Section 10k thermistor J 8 , 1 3 --- 1 4
48/50PD
FAN.S Fan status switch indoor fan section switch input J 8 , 1 5 --- 1 6
SSP.A Suction pressure, circuit A compressor A suction
CTLR DigitalScrollCtrlPwr relay J10, 11
CCH Crankcase heat relay relay J10, 13
OFC.1 Outdoor fan 1 relay relay J10, 19
IDF Indoor fan VFD pwr relay relay J10, 21
ALRM Alarm relay relay J10, 23
HT.1 Heat Stage 2 relay relay J10, 25 HT.2 Heat Stage 1 relay relay J10, 27
Local Equipment Network (LEN) communication J 5 , 1 --- 3 Carrier Comfort Network (CCN) communication J 5 , 5 --- 7 Network device power 24 VAC J5 , 9 --- 1 0 Scrolling Marquee Display (LEN) communication J 4 , 1 --- 3 Scrolling Marquee Display power 24 VAC J 4 , 5 --- 6 Modulation Board (AUX1) LEN communication J 3 , 1 --- 3 Optional ECB power 24 VAC J 2 , 1 --- 2
POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
INPUTS
indoor fan housing, or
supply duct
OUTPUTS
COMMUNICATION
10k thermistor J 8 , 7 --- 8
0 --- 5 V D C p r e s s u r e
transducer
CONNECTION
PIN NUMBER
J 8 , 1 8 --- 2 0
48
Page 49
Economizer Control Board (ECB)
The ECB controls the economizer actuator. (See Fig. 17 and Table
20.) The control signal from the ECB uses either the MFT (Multi-Function Technology) digital communication protocol or a 4 to 20 mA output signal as defined by the configuration ConfigurationECONE.CTL. The ECB has inputs for Indoor Air Quality (IAQ), Outdoor Air Quality (OAQ), enthalpy and RH sensor. It also controls two power exhaust outputs.
By digitally communicating with the ECB, the economizer actuator is able to provide the damper position and diagnostic information to the ComfortLink controller. The damper position is displayed at OutputsECONEC.AP. Diagnostic information is displayed via Alert T414. More information about these alarms is contained in the Alarms and Alerts section.
IMPORTANT: The Economizer Control Board (ECB) has a
4-position DIP switch that is factory set to ‘0’ (ON, towards
the center of the board). Do not change this setting.
48/50PD
Fig. 17 -- Economizer Control Board (ECB)
49
C07027
Page 50
Table 2 0 — ECB Connections
DISPLAY
NAME
Input power from MBB control box 24 VAC J 1 , 1 --- 2 RM.OC Remote occupancy switch field installed switch input J4, 2 ENTH or
IAQ.S IAQ Indoor air quality sensor return/space 0 --- 2 0 m A J5, 2 OAQ or
SP.RH
PE.1 Power exhaust 1 relay relay J8, 3 PE.2 Power exhaust 2 relay relay J8, 6 EC.CP Commanded Economizer position 0 --- 2 0 m A J9, 1
48/50PD
EC.CP & EC.AP
Outdoor enthalpy switch, or
Indoor air quality switch
Outdoor air quality sensor, or
Relative humidity sensor
Sensor Common Ground J5, 3
Actuator Common Ground J7, 3
Output power to enthalpy switch 24 VAC J4, 3
Output power for loop power sensors 24 VDC J5, 1
Output power to economizer actuator 24 VAC J7, 2
Local Equipment Network (LEN) communication J 2 , 1 --- 3
Carrier Comfort Network (CCN) communication J3
Economizer actuator position
(digital control)
POINT DESCRIPTION SENSOR
LOCATION
INPUTS
economizer, or
return/space
field installed 0 --- 2 0 m A J5, 5
OUTPUTS
COMMUNICATION
TYPE OF I/O CONNECTION
switch input J4, 4
MFT
communication
PIN NUMBER
J7, 1
50
Page 51
Modulation Board (AUX1)
The AUX1 board controls the compressor capacity and the indoor fan speed (See Fig. 18 and Table 21.) It outputs a 1 -- 5vdc and a 2--10vdc signal to the DSC and VFD for capacity and fan speed, respectively. This board is also used as the LEN connection buss
for the ECB, therefore must be operational for the ECB to communicate.
IMPORTANT: The AUX1 board has an 8--position DIP switch (S1) that is factory set for its LEN address. All the switches must be in the off position except 4, 5 and 7 which are on (off is towards the center of the board). Do not change this setting.
48/50PD
Fig. 18 -- Modulation Board (AUX1)
Table 21 — AUX1 Connections
DISPLAY
NAME
Input power from TRAN1 24 VAC J 1 , 1 1 --- 1 2 CAPC Compressor Capacity 1 --- 5 v d c CH9 F. S P D Commanded Fan Speed 2 --- 1 0 v d c CH10
Local Equipment Network (LEN) communication J9 , 1 --- 3
Local Equipment Network (LEN) communication J9 , 1 --- 3
POINT DESCRIPTION TYPE OF I/O
OUTPUTS
COMMUNICATION
CONNECTION
PIN NUMBER
C08658
51
Page 52
Digital Scroll Control Board (DSC)
The DSC board controls the compressor’s capacity. (See Fig. 19 and Table 22.) It receives a 1--5vdc signal from the AUX1 board determined by the cooling algorithm.
The DSC has direct control of the compressor and pulses a solenoid unloader on and off to provide a specific capacity. The discharge temperature thermistor (DTT) is monitored by the DSC for compressor safety. The DSC is equipped with an LED (light--emitting diode) for diagnostics. See the troubleshooting section for more details.
48/50PD
Fig. 19 -- Digital Scroll Controller (DSC)
Table 22 — DSC Connections
DISPLAY
NAME
CTLR DigitalScrollCtrlPwr 24 VAC 24VAC/24COM
Compressor Discharge Temperature (DTT) Discharge line 86k thermistor T1/T2
CAPC Compressor Capacity 1 --- 5 v d c C1/C2
Load Control Power* 19--- 250VAC L1/L2
C.ALM Scroll Compressor Alarm Relay A1/A2 CMP.A Compressor A Feedback Relay M1/M2
DigitalScrollUnloader
* Voltage used for contacts M1 & M2, U1 & U2, and V1 & V2 (24 VAC used).
POINT DESCRIPTION
INPUTS
OUTPUTS
SENSOR
LOCATION
Compressor
section
TYPE OF I/O
Relay U1/U2
CONNECTION
PIN NUMBER
C08659
52
Page 53
Variable Frequency Drive (VFD)
The VFD varies the frequency of the AC voltage supplied to the indoor fan. (See Fig. 20 and Table 23.) This causes the variance in the speed of the fan. The commanded fan speed is received by the VFD from the AUX1 board as a 2--10vdc signal.
The AI1 DIP switch must be in the off (or towards “U”) position to properly read the analog signal. There are three jumper wires that must remain installed for proper operation. The VFD is mounted behind the fan housing on the fan sled and the remote keypad is mounted on the front of the fan housing for easy access. The VFD is factory set to the auto mode for unit operation.
48/50PD
C09146
Fig. 20 -- Variable Frequency Drive (VFD)
Table 23 — VFD Connections
DISPLAY NAME POINT DESCRIPTION TYPE OF I/O
LOW VOLTAGE INPUTS
Shielded Cable Ground Shield 1 SCR
F. S P D Commanded Fan Speed 2 --- 1 0 v d c 2 AI1*
Analog Input 1 Common Ground 3 AGND Low Voltage Power (jumped to DI1 & DI4) 24v 10 24v Low Voltage Common (jumped to DCOM) Ground 11 GND Discrete Inputs Common (jumped from GND) Ground 12 DCOM Discrete Input 1 (jumped from 24v) Switch Input 13 DI1 Discrete Input 4 (jumped from 24v) Switch Input 16 DI4
HIGH VOLTAGE
V o l t a g e L e g f r o m I F C --- 2 1 Voltage Input U1 MAINS V o l t a g e L e g f r o m I F C --- 2 2 Voltage Input V1 MAINS V o l t a g e L e g f r o m I F C --- 2 3 Voltage Input W1 MAINS V o l t a g e L e g t o I F M --- 3 Voltage Output U2 MOTOR V o l t a g e L e g t o I F M --- 2 Voltage Output V2 MOTOR V o l t a g e L e g t o I F M --- 1 Voltage Output W2 MOTOR
* Requires the Al1 dip switch to be in in the Off (or towards “U”) position.
TERMINAL
NUMBER
TERMINAL
NAME
53
Page 54
Integrated Gas Control (IGC) Board
The IGC is provided on gas heat units. (See Fig. 21 and Table 24.)
The IGC is equipped with an LED (light-emitting diode) for diagnostics. See the Troubleshooting section for more information.
The IGC controls the direct spark ignition system and monitors the rollout switch, limit switch, and induced-draft motor Hall Effect switch.
RED LED-STATUS
48/50PD
Fig. 21 -- Integrated Gas Control (IGC) Board
Table 24 — IGC Connections
TERMINAL
LABEL
RT, C Input power from TRAN 1 control box 24 VAC SS Speed sensor gas section analog input J 1 , 1 --- 3 FS, T1 Flame sensor gas section switch input W Heat stage 1 MBB 24 VAC J2, 2 RS Rollout switch gas section switch input J 2 , 5 --- 6 LS Limit switch gas section switch input J 2 , 7 --- 8 CS Centrifugal switch (not used) switch input J 2 , 9 --- 1 0
L1, CM Induced draft combustion motor gas section line VAC IFO Indoor fan request control box relay J2, 1 GV (W1) Gas valve (heat stage 1) gas section relay J2, 12 GV (W2) Gas Valve (heat stage 2, from MBB) gas section Not on IGC
POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
INPUTS
OUTPUTS
CONNECTION
PIN NUMBER
C07028
54
Page 55
Low Voltage Terminal S trip
(TB1)
This circuit board provides a connection point between the major control boards and a majority of the field-installed accessories. (See
Fig. 22 -- Low--Voltage Terminal Board (LVTB)
Table 25 — Field Connection Terminal Strip
Fig. 22 and Table 25.) The circuit breakers for the low voltage control transformers, interface connection for the Carrier Comfort Network® (CCN) communication, and interface connection for the Local Equipment Network (LEN) communications are also located on the low voltage terminal strip.
C08660
48/50PD
TERMINAL
LABEL
1 24 VDC Sensor Loop power 24 VDC output J10, 17 2 IAQ Indoor air quality sensor return/space 4 --- 2 0 m A i n p u t J10, 16 3 Air quality & humidity sensor common Ground J10, 15
4
5 RM.OC Remote occupancy switch field installed 24 VAC input J10, 13 6 Switchpower(ENTH,RM.OC,IAQ.S) 24 VAC output J10, 11 --- 12
7
8* EC.CP
9 Economizer signal common Ground J10, 3 --- 5
10* EC.AP
R 24 VAC power 24 VAC output J11, 11---14 Y1 NOT USED J11,10 Y2 NOT USED J11, 9
W1 NOT USED J11, 7--- 8 W2 HUM Space Humidity Switch space 24 VAC input J11, 6
G NOT USED J11, 5 C 24 VAC common 24 VAC output J11, 2 ---4
X ALRM Alarm output (normally open) 24 VAC output J11, 1
FIRE
SHUTDOWN
1
FIRE
SHUTDOWN
2
T55
1 --- 2
T55
2 --- 3
FAN STATUS
1 --- 2 LEN Local Equipment Network (LEN) communication J 1 3 , 1 --- 3 , 4 --- 5
CCN Carrier Comfort Network (CCN) communication J 1 3 , 6 --- 8 , 4 --- 5
* Refer to Third Party Control section for more information
DISPLAY
NAME
OAQ or SP.RH
ENTH or IAQ.S
FDWN Fire shutdown switch 24 VAC output supply/return switch input J12, 7
FDWN Fire shutdown switch input supply/return switch input J12, 6
SPT Space temperature (T55/56) space 10k thermistor J12, 4---5
SPTO Space temperature offset (T56) space 10k thermistor J12, 3--- 4
POINT DESCRIPTION
Outdoor air quality sensor or Relative humidity sensor
Outdoor enthalpy switch, or Indoor air quality switch
Economizer commanded position actuator (when in digital control)
Economizer position feedback (when in analog control)
NOT USED J12, 1---2
SENSOR
LOCATION
field installed 4 --- 2 0 m A i n p u t J10, 14
economizer, or
return/space
economizer 2 --- 1 0 V D C o u t p u t J10, 6---8
economizer
TYPE OF I/O
24 VAC input J10, 9---10
communication
2 --- 1 0 V D C o u t p u t
CONNECTION
PIN NUMBER
J10, 1--- 2
55
Page 56
Scrolling Marquee Display
This device is the keypad interface used to access rooftop information, read sensor values, and test the unit. (See Fig. 23.) The Scrolling Marquee display is a 4-key, 4-character, 16-segment LED (light-emitting diode) display. Eleven mode LEDs are located on the display as well as an Alarm Status LED. See Basic Control Usage section for further details.
IMPORTANT: Conductors and drain wire must be 20 AWG (American Wire Gauge) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of -- 20_Cto 60_C is required. See Table below for acceptable wiring.
MANUFACTURER PART NO.
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
48/50PD
Accessory Navigatort Display
The accessory hand-held Navigator display can be used with 48/50PD units. (See Fig. 24.) The Navigator display operates the same way as the Scrolling Marquee device. The Navigator display plugs into the LEN port on either TB or the ECB board.
Alarm Status
ESCAPE
ENTER
Fig. 23 -- Scrolling Marquee
C06320
It is important when connecting to a CCN communication bus that a color-coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative and white for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. The shield screw on TB1 can be used to tie the cables together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. The shield screw on TB1 is not acceptable for grounding. If the communication bus cable exits from one building and enters another, the shields must be
Alpha
Belden
Carol
West Penn
2413 or 5463
8772
C2528
302
connected to grounds at the lightning suppressor in each building
C
o
m
f
o
r
t
L
N
in
A
V
I
k
G
A
T
O
T
IM
E
W
L
W
T
S
E
T
R
E
1
2
T
.
5
8
5
4
.
6
°
F
4
4
P
.1
°
F
4
4
.
0
°
F
where the cable enters or exits the building (one point per building only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (--) conductors. (Substitute appropriate
M
O
D
E
Ala
rm
Ru
Sta
n Sta
tus
tu
s
S
e
rv
ice
Te
s
t
T
em
p
era
ture
s
P
res
s
ure
s
S
e
tpo
in
ts
In
pu
ts
O
utp
uts
C
on
fig
u
ra
tion
T
im
e C
lo
ck
E
O
S
p
er
C
ating
M
od
es
A
la
rm
s
E
N
T
E
R
colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB1, the white wire to COM terminal, and the black wire to the (--) terminal.
4. The RJ14 CCN connector on TB1 can also be used, but is only intended for temporary connection (for example, a laptop computer running Carrier network software).
5. Restore power to unit.
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector. If conditions return to normal, check the CCN connector and cable. Run new
C06321
Fig. 24 -- Accessory Navigatort Display
Carrier Comfort Network (CCN)R Interface
The units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is field supplied and installed. The system elements are connected to the communication bus in a daisy chain arrangement. (See Fig. 25.) The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made at TB. (See Fig. 25.) Consult the CCN Contractor’s Manual for further information.
cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
Field-Installed Accessories
Space Temperature Sensor (T--55)
The T--55 space temperature sensor (part no. 33ZCT55SPT) is a field-installed accessory. The sensor is installed on a building interior wall to measure room air temperature. The T--55 sensor also includes an override button on the front cover to permit occupants to override the Unoccupied Schedule (if programmed).
TB1--T55--1 Sensor Input........
TB1--T55 -- 2 Sensor Common........
Space Temperature Sensor (T--56)
The T--56 space temperature sensor (part no. 33ZCT56SPT) is a field-installed accessory. This sensor includes a sliding scale on the front cover that permits an occupant to adjust the space temperature set point remotely. The T-- 56 sensor also includes an override button on the front cover to allow occupants to override the unoccupied schedule (if programmed).
TB1--T55--1 Sensor Input........
TB1--T55 -- 2 Sensor Common........
TB1--T55--3 Setpoint Offset Input........
56
Page 57
Space Temperature Sensor (T--58)
The T--58 space temperature sensor (part no. 33ZCT58SPT) is a field-installed accessory. The T-- 58 sensor communicates with the ComfortLinkcontroller, providing space temperature, heating and cooling set points, and mode operation information.
Refer to the T--58 installation instructions for information on installing and configuring the T-- 58 sensor.
CCN BUS
Each T--58 sensor must have a unique address on the CCN. Each T--58 sensor must also be configured with the address of the unit control it is communicating to.
Space Temperature Sensor Averaging
See Fig. 26 for space temperature averaging with T -- 55 sensors only. If the use of one T--56 sensor is required, refer to Fig. 27.
REMOTE CCN SITE
BUILDING SUPERVISOR
NETWORK OPTIONS
AUTODIAL GATEWAY
TERMINAL SYSTEM MANAGER
CL
CL
ROOFTOP UNIT
ROOFTOP UNIT
CL
ROOFTOP UNIT
HEATING/COOLING UNITS
TCU
DAV AIR TERMINAL
TCU
DAV AIR TERMINAL
CL
CL
ROOFTOP UNIT
ROOFTOP UNIT
TCU
LEGEND CCN -- Carrier Comfort Networkr CL -- ComfortLinkt Controls DAV -- Digital Air Volume HVAC -- Heating, Ventilation, and Air Conditoning TCU -- Terminal Control Unit
TO ADDITIONAL TERMINALS
DAV FAN POWERED MIXING BOX
48/50PD
NON CARRIER HVAC EQUIPMENT
COMFORT
CONTROLLER
AIR DISTRIBUTION-DIGITAL AIR VOLUME CONTROL (DAV)
C07030
Fig. 25 -- CCN System Architecture
57
Page 58
RED
T
BLK
RED
BLK
TB1-T55
1
2
TO MAIN BASE BOARD
RED
BLK
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4
RED
BLK
RED
BLK
SPACE TEMPERATURE AVERAGING --4 T-55 SENSOR APPLICATION
TB1-T55
1
48/50PD
2
TO MAIN BASE BOARD
RED
BLK
BLK
SENSOR 1
RED
RED
BLK
SENSOR 2
RED
BLK
SENSOR 3
LEGEND
B -- Terminal Block ______ -- Factory Wiring _ _ _ _ -- Field Wiring
RED
BLK
RED
BLK
SENSOR 6SENSOR 5
BLK
SENSOR 4
RED
RED
BLK
RED
BLK
SENSOR 8SENSOR 7 SENSOR 9
SPACE TEMPERATURE AVERAGING --9 T-55 SENSOR APPLICATION
C07032
Fig. 26 -- Space Temperature Sensor Averaging
RED
BLK
TB1-T55
1
2
TO MAIN
BASE
BOARD
RED
BLK
RED
BLK
RED
BLK
RED
BLK
TB1-T55
3
TO MAIN
BASE
BOARD
T-55 SENSOR 1 T-55 SENSOR 2 T-55 SENSOR 3 T-56 SENSOR 4
WHT
C07033
Fig. 27 -- Space Temperature Sensor Averaging with 3 T--55 Sensors and One T--56 Sensor
58
Page 59
Carrier Accessory Kits
There are specific accessory kits sold for various field installed accessories. These kits vary based on model, size, voltage, manufacture date, and duct orientation. Some of these kits include Economizer, Power Exhaust, and Electric Heat. Refer to the Controls Quick Set--Up section for configuration and more information on these accessories.
Two--Position Damper
The two-position outdoor air damper accessory usage depends on model size and return duct orientation. This accessory wires directly into the low voltage circuit for the indoor fan control. No other control configuration is needed.
Indoor Air Quality
The indoor air quality (IAQ) sensor (part no. 33ZCSENCO2) is a field-installed accessory which measures CO When installing this sensor, an ECB board must be installed and the unit must be configured for IAQ use by setting ConfigurationAIR.QIA.CF to a value of 1, 2, or 3. See the Indoor Air Quality section for more information.
TB1--2 4--20 mA Input.......
TB1--3 Sensor Common.......
TB1--R 24 VAC Output......
TB1--C Common (GND)......
levels in the air.
2
Outdoor Air Quality
The outdoor air quality (OAQ) sensor is a field-installed accessory that measures CO ECB board must be installed and the unit must be configured for OAQ use by setting ConfigurationAIR.QOA.CF to a value of 1 or 2. See the Indoor Air Quality section for more information.
TB1--4 4--20 mA Input.......
TB1--3 Sensor Common.......
TB1--R 24 VAC Output......
TB1--C Common (GND)......
levels in the air. When installing this sensor, an
2
Smoke Detectors
The smoke detectors are field-installed accessories. These detectors can detect smoke in either the return air (part no. CRSMKDET003A00) or supply and return air (part no. CRSMKSUP002A00). When installing either detector, the unit must be configured for fire shutdown by setting ConfigurationUNITFS.SW to normally open (1) or normally closed (2).
TB1--Fire Shutdown--1 Dry Contact Source....
TB1--Fire Shutdown--2 Discrete Input to Board....
TB1--R 24 VAC Output................
TB1--C Common (GND)................
Filter Status
The filter status accessory (part no. CRSTATUS002B00) is a field-installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting ConfigurationUNITFL.SW to normally open (1) or normally closed (2). Normally open (1) is the preferred configuration. Filter status wires are pre-run in the unit harness and located near the switch installation location. Refer to the Filter Accessory Installation Instructions for more information.
Fan Status
The fan status accessory (part no. CRSTATUS003B00) is a field-installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting ConfigurationUNITFN.SW to normally open (1) or normally closed (2). Normally open (1) is the preferred configuration. Fan status wires are pre-run in the unit harness and located near the switch installation location. Refer to the Fan Accessory Installation Instructions for more information.
IMPORTANT: The Fan Status terminals on TB1 are NOT to be used.
Enthalpy Sensors
The enthalpy accessories (part no. CRENTSNG002A00 and CRENTDIF002A00) are field-installed accessories. The first accessory (outdoor air only) determines when the enthalpy is low relative to a fixed reference. Adding the second accessory (return air) compares the enthalpy between the outdoor and return airstreams. In each case, the enthalpy 4 to 20 mA signals are converted to a switch output which is read by the ECB. When installing this accessory, the unit must be configured for enthalpy-based control by setting ConfigurationECONEN.SW to normally open (1). Normal status is an active switch which tells the control that enthalpy is LOW. The actual switch terminal LOW is normally closed. Refer to the Enthalpy Kit Installation Instructions for more information on its installation.
Return/Supply Air Temperature Sensor
The temperature sensor (part no. 33ZCSENSAT) is a field-installed accessory which may be installed on the common return air duct and/or the common supply air duct near the unit. The duct supply air temperature (SAT) may be used to replace the SAT sensor that is internal to the unit. A supply duct SAT measurement is valid for heating mode display while the factory-standard internal SAT is not valid for heating due to its location upstream of the heating section. When installing the supply duct SAT, the unit must be configured by setting ConfigurationUNITSAT.H to ENBL. A SAT sensor in the supply duct is the preferred configuration for systems with Carrier variable volume and temperature (VVT®) accessory controls.
Space Humidistat
The Space Humidistat (part no. -- --HL ----38MG--029) is a wall mounted device with an adjustable setpoint to control humidity levels. The humidistat input is provided on the field connection terminal board. The Space Humidity Switch configuration,
Configuration
normally closed status of this input at LOW humidity.
TB1--R 24 VAC Dry Contact Source......
TB1--W2 Discrete Input to Board.....
UNIT→RH.SW, identifies the normally open or
Space Humidity Sensor
The space relative humidity sensor (part no. 33ZCSENDRH--01 duct mount or 33ZCSENSRH--01 wall mount) is a field--installed accessory. The space relative humidity (RHS) may be selected for use if the outdoor air quality sensor (OAQ) is not used and an economizer board is installed. When installing the relative humidity sensor, the unit must be configured by setting
Configuration
TB1--1 24 VDC Loop Power.......
TB1--4 4--20 mA Input Signal.......
UNIT→RH.S to YES.
SERVICE
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
59
48/50PD
Page 60
Remove Surface Loaded Fibers
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R-- 410A) refrigerant systems operate at higher pressures than standard R-- 22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal
48/50PD
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in your building.
3. IMMEDIATELY call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
4. If you cannot reach your gas supplier, call the fire
department.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
Surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the fins.
IMPORTANT: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse.
Periodic Clean Water Rinse
A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments. However, it is very important that the water rinse is made with very low velocity water stream to avoid damaging the fin edges. Monthly cleaning as described below is recommended.
Routine Cleaning of Round--Tube Coil Surfaces
Monthly cleaning with Totaline® environmentally sound coil cleaner is essential to extend the life of coils. This cleaner is available from Carrier Replacement parts division as part number P902--0301 for a one gallon container, and part number P902--0305 for a 5 gallon container. It is recommended that all round--tube coils, including standard aluminum, pre-coated, copper/copper or E-coated coils be cleaned with the Totaline environmentally sound coil cleaner as described below. Coil cleaning should be part of the unit’s regularly scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment.
Avoid the use of:
S coil brighteners S acid cleaning prior to painting S high pressure washers S poor quality water for cleaning
Totaline environmentally sound coil cleaner is non-flammable, hypoallergenic, non--bacterial, and a USDA accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces, or insulation. Use of non-recommended coil cleaners is strongly discouraged since coil and unit durability could be affected.
Totaline Environmentally Sound Coil Cleaner Application Equipment
1
/2gallon garden sprayer
S 2 S water rinse with low velocity spray nozzle
!
CAUTION
Cleaning
Inspect unit interior at beginning of each heating and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior.
Coil Maintenance and Cleaning Recommendation
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in corrosion and damage to the unit.
Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environmentally sound coil cleaner as described above.
60
Page 61
!
CAUTION
UNIT RELIABILITY HAZARD
Failure to follow this caution may result in reduced unit performance.
High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop.
Totaline Environmentally Sound Coil Cleaner Application Instructions
1. Proper eye protection such as safety glasses is recommended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.
4. Mix Totaline environmentally sound coil cleaner in a
1
/2gallon garden sprayer according to the instructions
2 included with the cleaner. The optimum solution temperature is 100_F.
IMPORTANT: Do NOT USE water in excess of 130_F, as th e enzymatic activity will be destroyed.
5. Thoroughly apply Totaline® environmentally sound coil cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned areas.
8. Interior and exterior finned areas must be thoroughly cleaned.
9. Finned surfaces should remain wet with cleaning solution for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing. Reapplying cleaner as needed to ensure 10-minute saturation is achieved.
11. Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Protect fins from damage from the spray nozzle.
Condensate Drain Pan
Check and clean each year at the start of the cooling season. In winter, keep drains and traps dry.
To clean the condensate pan:
1. Disconnect condensate drain system from side or bottom drain connection.
2. Remove and clean trap.
3. Remove 4 screws securing condensate pan access cover to unit. Save screws and panel.
4. Slide condensate pan out from unit and clean. Pan is made of non-corrosive plastic. Use a mild cleaner to remove heavy deposits of dirt and grime.
5. Replace pan in unit.
6. Replace condensate pan access cover with 4 screws saved from Step 3.
7. Re-attach and prime condensate trap.
8. Connect condensate drainage system.
ROLLOUT SWITCH
HEAT EXCHANGER SECTION
MAIN BURNER SECTION
INDUCED DRAFT MOTOR
COMBUSTION FAN HOUSING
MAIN GAS VALVE
C07037
Fig. 28 -- Typical Gas Heating Section
Filters
Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to unit Installation Instructions for type and size.
Outdoor--Air Inlet Screens
Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens. See unit installation instructions for quantity and size.
Main Burner (48PD)
At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames. Refer to Main Burners section.
Flue Gas Passageways (48PD)
The flue collector box and heat exchanger cells may be inspected by opening heat section access door, flue box cover, and main burner assembly. (See Fig. 28.) Refer to Main Burners section for burner removal sequence. If cleaning is required, clean tubes with a wire brush. Use Caution with ceramic heat exchanger baffles. When installing retaining clip, be sure the center leg of the clip extends inward toward baffle. (See Fig. 29.)
CERAMIC BAFFLE
CLIP
NOTE: One baffle and clip will be in each upper tube of the heat exchanger.
C07260
Fig. 29 -- Removing Heat Exchanger Ceramic
Baffles and Clips
Combustion--Air Blower (48PD)
Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency.
61
48/50PD
Page 62
To inspect blower wheel, open heat section door. Using a flashlight, look into the flue exhaust duct to inspect. If cleaning is required, remove motor and wheel assembly by removing the screws holding the flue box cover to the flue box. Remove the screws holding the inducer housing to the inlet plate. The wheel can then be removed from the motor shaft and cleaned with a detergent or solvent. Replace the wheel onto the motor shaft in the correct position and reassemble the flue cover onto the flue box.
Lubrication
Compressors
Each compressor is charged with the correct amount of oil at the factory.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components.
The compressor is in a Puron refrigerant system and uses a
48/50PD
polyolester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Avoid exposure of the oil to the atmosphere.
Polyolester (POE) compressor lubricants are known to cause long term damage to some synthetic roofing materials. Exposure, even if immediately cleaned up, may cause roofing materials to become brittle (leading to cracking) within a year. When performing any service which may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include compressor replacement, repairing refrigerant leaks, and replacing refrigerant components. To prepare rooftop:
1. Cover extended roof work area with an impermeable plastic dropcloth or tarp. Make sure a 10 x 10 ft area around the work area is covered.
2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent run-offs. Towel will also protect dropcloth from tears caused by tools or components.
3. Place terry cloth shop towel inside the unit directly under components to be serviced to prevent spills through the bottom of the unit.
4. Perform the required service.
5. Remove an dispose of any oil contaminated material per local codes.
Indoor Fan Shaft Bearings
The indoor fan has permanently sealed bearings. No field lubrication is necessary.
Condenser and Evaporator--Fan Motor Beari ngs
The condenser-fan and evaporator-fan motors have permanently sealed bearings, so no field lubrication is necessary.
Economizer or Manual Outside Air Damper
If blade adjustment is required, refer to unit or accessory installation instructions.
Evaporator Fan Service and Replacement
The units feature a slide-out fan deck for easy servicing of the indoor-fan motor, pulleys, belt, bearings and VFD. To service components in this section, perform the following procedure:
1. Turn off unit power.
2. Open the fan section access door.
3. Remove two no. 10 screws at front of slide-out fan deck. Save screws. (See Fig. 30.)
4. Disconnect the electrical wires connected to the slide--out fan deck (supply air thermistor and fan status switch if installed). Wires may be damaged if not disconnected.
5. Fan deck can now be slid out to access serviceable components.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit.
DO NOT SLIDE FAN DECK OUT PAST THE FAN DECK STOP. If further access is required, the fan deck must be supported. Make sure plugs and wiring are not pinched between fan housing and unit sheet metal post.
6. To replace fan deck to operating position, slide fan deck back into the unit. Secure with the two no. 10 screws removedinStep3.
7. Re-attach electrical wires.
8. Close fan section access door.
9. Restore power to unit.
C08661
Fig. 30 -- Evaporator--Fan Motor Adjustment
Evaporator Fan Performance Adjustment
Fan motor pulleys are factory set for speed shown in Appendix D. To change fan speeds:
1. Shut off unit power supply.
2. Loosen nuts on the 4 carriage bolts in the mounting base. Using adjusting bolts and plate, slide motor and remove belt.
3. Loosen movable-pulley flange setscrew. (See Fig. 31.)
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Appendix D. See Appendix D for air quantity limits.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Appendix D for speed change for each full turn of pulley flange.)
6. Replace belts.
62
Page 63
7. Realign fan and motor pulleys:
a. Loosen fan pulley setscrews.
b. Slide fan pulley along fan shaft.
c. Make angular alignment by loosening motor from
mounting plate.
8. Tighten belts.
9. Restore power to unit.
C06041
Fig. 31 -- Evaporator--Fan Alignment and Adjustment
Evaporator Fan B elt Tension Adjustment
To adjust belt tension:
1. Turn off unit power.
2. Slide out fan deck to service position as shown in Evaporator Fan Service and Replacement section above.
3. Loosen motor mounting plate bolts.
4. Move motor mounting plate to adjust to proper belt tension. Motor adjuster bolts may be used to tighten belts. (See Fig.
30.) Do not overtighten belt.
5. Check for proper belt alignment. Adjust if necessary.
6. Tighten motor mounting plate bolts to lock motor in proper position.
7. Return fan deck back into operating position.
8. Restore power to unit.
Variable Frequency Drive (VFD) Replacement
The 48/50PD units are equipped with a VFD that is mounted behind the blower housing on the fan sled. The VFD’s remote display is mounted on the front of the fan housing for easier access. The VFD is mounted to a plate which is mounted to the fan sled. When accessing the VFD or to remove the VFD, follow the Evaporator fan service and replacement Steps 1--5 and the following steps:
IMPORTANT: If fan deck stop screws are removed for further access, the front of the fan deck MUST BE SUPPORTED.
1. Remove the 2 screws holding the VFD’s mount bracket to the fan sled. The horizontal cross section of the bottom half of the mount bracket is shown on Fig. 32.
2. Cut the wire ties holding the VFD power wires to the fan housing and the two wire ties holding the control wires to the VFD display/keypad at the top of the fan scroll.
3. With the VFD still attached, remove the mount bracket from the fan sled. To do this requires a slight lift on the screw side then a push towards the pulley side of the fan sled.
(See Fig. 32.) Lift out the bracket when the pulley side is clear from the fan sled.
4. With all the wires stilled attached to the VFD, turn the VFD assembly so it is parallel with the fan sled.
5. Pull the VFD assembly to the front of the fan sled and place in a secure flat surface.
6. Disconnect the power, ground, RJ45, and control wiring to the VFD making sure to note their connections.
IMPORTANT: Wires are marked with VFD terminal labels and wiring diagram shows the wiring connections.
7. Remove the 4 screws holding the VFD to the mount bracket and remove the VFD.
8. Remove the replacement VFD cover and install jumper wires provided with it as shown on the unit wiring diagram. If jumpers are not provided with the replacement VFD, remove them from the defective one or field supply the jumpers.
9. Set AI1 and AI2 DIP switches to the U (off) direction as indicated on the plastic housing near the DIP switch.
10. Replace the VFD with the new one.
11. Install the 4 screws in the VFD to secure it to the mounting bracket.
12. Connect the wiring as it was on the previous VFD, refer to the wiring diagram.
13. Move the VFD assembly to the back of the fan sled.
14. Turn the VFD assembly lengthwise with the fan housing, making sure the screw side of the bracket lines up with the screw holes on the fan sled.
15. Make sure the bracket s pulley side U bend is clear of the fan sled and pull the assembly towards the screw side.
16. Install the 2 screws in the bracket to secure it to the fan sled.
17. Secure power and control wires with new wire ties.
18. Follow the Evaporator fan service and replacement Steps 6--9.
19. Power up VFD and set up its parameters per Table 40 in Appendix B.
IMPORTANT: If fan deck stops were removed, they must be reinstalled.
For VFD service and maintenance, refer to Appendix B.
C08662
Fig. 32 -- VFD Mount Bracket Cross Section
Condenser-Fan Adjustment
1. Shut off unit power supply.
2. Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 33.
4. Tighten setscrews and replace condenser-fan assembly.
5. Turn on power to unit.
48/50PD
63
Page 64
T
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system, absorbing moisture.
C08570
Fig. 33 -- Condenser--Fan Adjustment
5. Repeat this procedure. System will then contain minimal amounts of contaminants and water vapor.
Refrigerant Charge
Verify Sensor Performance
Verify that thermistor, transducer, and switch inputs are reading correctly. These values can be accessed through the Scrolling Marquee display in the Temperatures, Pressures, and Inputs menus. Some values will depend on configuration choices. Refer to the Control Set Up Checklist completed for the specific unit installation and to the configuration tables in Appendix A.
Economizer Operation During Power Failure
Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Do not
manually operate damper motor.
48/50PD
Evacuation
Proper evacuation of the system will remove noncondensables and ensure a tight, dry system before charging. Evacuate from both high and low side ports. Never use the system compressor as a vacuum pump. Refrigerant tubes and indoor coil should be evacuated to 500 microns. Always break a vacuum with dry nitrogen. The two possible methods are the deep vacuum method and the triple evacuation method.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a minimum vacuum of 500 microns and a vacuum gauge capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 34.)
5000
4500
4000
3500
3000
2500
MICRONS
2000
1500
1000
500
4
3
0
2
1
MINUTES
Fig. 34 -- Deep Vacuum Graph
Triple Evacuation Method
The triple evacuation method should only be used when vacuum pump is capable of pumping down to 28--in. of mercury and system does not contain any liquid water. Proceed as follows:
1. Pump system down to 28--in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
LEAK IN SYSTEM
VACUUM TIGH TOO WET
TIGHT DRY SYSTEM
56
7
C06264
Amount of refrigerant charge is listed on unit nameplate. Refer to Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during charging procedure.
Puron® (R-410A) refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puron (R--410A) refrigerant systems operate at higher pressures than standard R-- 22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment. Gauge set, hoses, and recovery system must be designed to handle Puron refrigerant. If unsure about equipment, consult the equipment manufacturer.
IMPORTANT: Do not use recycled refrigerant as it may contain
contaminants.
No Charge in the System
Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to unit nameplate). Verify charge using the charging chart via “Charge in the System.”
Charge in the System
IMPORTANT: The circuit must be running in normal cooling
mode with the compressor capacity at 100%. The VFD must be running at max fan speed and indoor airflow must be within specified air quantity limits for cooling (See Appendix D). All outdoor fans must be on and running at high speed. Use the Cooling Service Test Outdoor Fan Override function to start all outdoor fans.
An accurate pressure gauge and temperature--sensing device is required. Charging is accomplished by ensuring the proper amount of liquid subcooling. Connect pressure gauge to the compressor discharge service valve. Connect temperature sensing device to the liquid line between the condenser and the TXV (thermostatic expansion valve), and insulate it so that ambient temperature does not affect reading. Use the cooling charging chart (Fig. 35 -- 36) to determine if additional charge is needed or if some charge needs to be removed from the system.
To Use the Cooling Charging Chart
Use the temperature and pressure readings, and find the intersection point on the cooling charging chart. If intersection point on chart is above line, add refrigerant. If intersection point on chart is below line, carefully recover some of the charge. Recheck suction pressure as charge is adjusted.
64
Page 65
The TXV is set to maintain between 10 and 15 degrees of
R410AREREFRIRIGE
RANT
OUTDOORFR FANMN M UST BEO PERATING ONHN HIGHSH SPEED
20
40
60
80
100
120
140
160
150
20025250 30000
350
400
450
500
550
600
Co mpresssso r D
isc ha rge P ressssu re, [ p
sig]
Adddd Chaharge if A
bove
the Cururve
RemoveveChCharargeifif Belolow th eCuCurveve
Outdoor
Coil L
eaving
Temp
eratu
re,
[Deg
rees
F]
R410AREREFRIRIGE
RANT
OUTDOORFR FANMN M UST BEO PERATING ONHN HIGHSH SPEED
20
40
60
80
100
120
140
160
150
20025250 30000
350
400
450
500
550
600
Co mpresssso r D
isc ha rge P ressssu re, [ p
sig]
Adddd Chaharge if A
bove
the Cururve
RemoveveChCharargeifif Belolow th eCuCurveve
Outdoor
Coil L
eaving
Temp
eratu
re,
[Deg
rees
F]
superheat at the compressors. The valves are factory set and cannot be adjusted. Do not use A TXV designed for use with R-- 22.
16
14
F]
12
rees
[Deg re,
eratu
10
Te m p
eavin
80
Coil
Outdoor
60
40
20
R4
bov
the
150
200
RANT
350
400
450
500
550
isc
sig
600
C07040
Fig. 35 -- Charging Chart 48/50PD05
16
14
F]
12
rees
[Deg re,
eratu
10
Te m p
eavin
80
Coil
Outdoor
60
40
20
R4
bov
the
150
200
RANT
350
400
450
500
550
isc
sig
600
Table 2 6 — Altitude Compensation*
48PG03--07
ELEVATION
(ft)
0-1,999
2,000 3,000 4,000 5,000 6,000 7,000 8,000
9,000 10,000 11,000 12,000 13,000 14,000
*As the height above sea level increases, there is less oxygen per cubic foot of air.
Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
Orifices available through your Carrier dealer.
NATURAL GAS
ORIFICE†
45 52 47 52 47 53 47 53 48 53 48 53 48 53 49 54 49 54 50 54 51 54 51 55 52 55 52 56
PROPANE
ORIFICE†
Gas V alve Adjustment
The gas valve opens and closes in response to the thermostat or limit control.
When power is supplied to valve terminals W2 (High Fire) and C1, the main valve opens to its preset position.
The regular factory setting is stamped on the valve body. To adjust regulator:
1. Set unit at setting for no call for heat.
2. Turn main gas valve to OFF position.
3. Remove connection. Install a suitable pressure-measuring device.
4. Set main gas valve to ON position.
5. Set thermostat at setting to call for heat.
6. Remove screw cap covering regulator adjustment screw. (See Fig. 37.)
7. Turn adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. The setting is 3.50 in.wgonsizes03-14and3.00onsize16--28.
8. Once desired pressure is established, set unit setting for no call for heat, turn off main gas valve, remove pressure-measuring device, and replace screw cap.
1
/8-in. pipe plug from manifold pressure tap
1
/8-in. pipe plug and
48/50PD
Fig. 36 -- Charging Chart 48/50PD06
PuronR Refrigerant
Puron refrigerant operates at 50 to 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron refrigerant. Do not mix with components that have been used with other refrigerants. Puron refrigerant, as with other HFCs, is only compatible with POE oils.
Recovery cylinder service pressure rating must be 400 psig. Puron systems should be charged with liquid refrigerant. Use a commercial-type metering device in the manifold hose. Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard. Use hoses with 750 psig service pressure rating. Leak detectors should be designed to detect HFC refrigerant.
C07041
C08663
Fig. 37 -- 48PD Gas Valve
65
Page 66
High Altitude
For high altitude applications greater than 2,000 ft the heat input rate should be reduced. The higher the altitude is above sea level, the less oxygen is in the air. See Table 8 for orifice sizing. A high altitude kit is available to convert unit for altitudes up to 7,000 ft.
Main Burners
For all applications, main burners are factory set and should require no adjustment.
Main Burner Removal
1. Shut off (field-supplied) manual main gas valve.
2. Shut off power to unit.
3. Open gas section access door.
4. Disconnect gas piping from gas valve inlet.
5. Remove wires from gas valve.
6. Remove wires from rollout switch.
7. Remove sensor wire and ignitor cable from IGC board.
9. Rotate the burner/manifold assembly to the right, away from the flue extension and lift burner/manifold assembly out of unit.
Cleaning and Adjustment
1. Remove burner rack from unit as described in Main Burner Removal section above.
2. Inspect burners, and if dirty, remove burners from rack. The two outer burners have the flame crossover closed off in order to prevent gas flow from exiting the sides of the burner assembly. To prevent ignition problems, make sure the outer burners are returned to their original position when done servicing.
3. Using a soft brush, clean burners and crossover port as required.
4. Adjust spark gap. (See Fig. 38.)
5. Reinstall burners on rack.
6. Reinstall burner rack as described above.
8. Remove 2 screws that hold the burner assembly to vestibule plate.
48/50PD
E
E
SPARK GAP
0.181” [4.6]
SECTION
C-C
AA
C
C
SECTION
A-A
SCALE 1:1
B
Fig. 38 -- Spark Gap Adjustment
Filter Drier
Replace filter drier whenever refrigerant system is exposed to atmosphere. Only use factory specified liquid-line filter driers with working pressures no less than 650 psig. Do not install a suction-line filter drier in liquid line. A liquid-line filter drier designed for use with Puron® refrigerant is required on every unit.
Protective Devices
Compressor Rotation
Overcurrent
Each compressor has internal line break motor protection.
Overtemperature
Each compressor has an internal protector to protect it against excessively high discharge gas temperatures.
25.4
MAX. TYP.
B
SECTION
E-E
SCALE 2:1
SECTION
SCALE 1:1
D
D
B-B
SPARK GAP
0.120 TO 0.140” [3.05 TO 3.56]
SECTION
D-D
C06269
High--Pressure Switch
If the high-pressure switch trips, the compressor will shut down and the current sensor (3-phase units only) will not detect current. See the Current Sensor section below for more information.
Current Sensor (CS) (3--Phase Units Only)
The purpose of the CS is to detect losses in compressor power. After detecting a loss in compressor power, unit control locks out the compressor for 15 minutes. After 15 minutes, the alarm will automatically reset. If this alarm occurs 3 times consecutively, the compressor will remain locked out until an alarm reset is initiated via CCN or manually via the Scrolling Marquee display (see Alarms and Alerts section for more details).
IMPORTANT: The current sensor is not currently used in the 48/50PD, but reserved for future implementation.
66
Page 67
Evaporator Fan Motor Protection
Indoor-fan motors less than 5 hp are equipped with internal overcurrent and overtemperature protection. Protection devices reset automatically. Disconnect and lock out power when servicing motor. Indoor-fan motors 5 hp and larger are equipped with a manual reset, calibrated trip, magnetic circuit breaker and overcurrent protection. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker.
Condenser--Fan Motor Protection
Each condenser-fan motor is internally protected against overtemperature.
Fuses are located in the control box and feed power to the condenser fan motors. Always replace blown fuses with the correct size fuse as indicated on the unit fuse label.
Saturated Suction P ressure (SSP)
If the SSP for a particular circuit is reading below the alarm set point for an extended period of time, that circuit will be shut down. After 15 minutes, the alarm will automatically reset. If this alarm occurs 3 times consecutively, the circuit will remain locked out until an alarm reset is initiated via CCN or manually via the Scrolling Marquee display (see Alarms and Alerts section for more details).
Relief Devices
All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices protect the high and low side and are located at the suction line service port. Protect joint during brazing operations near joint.
Compressor Sound Shield
The 48/50PD units are equipped with a compressor sound shield. The sound shield has two parts, the compressor jacket encloses the shell of the compressor and the base shield is installed between the bottom of the compressor and the unit base pan. The sound shield reduces the difference in noise levels as the compressor loads and unloads in the frequency ranges of 200 to 2000 Hz. Since the human speech occurs in the 200 to 2000 Hz frequency ranges the sound shield reduces the speech annoyance caused by the loading and unloading of the compressor.
The compressor jacket is held closed around the compressor by Velcro tape. To remove the compressor jacket, separate the Velcro along the side and top of the compressor. Slide the jacket toward the back of the compressor to remove the jacket. Make sure the jacket is reinstalled after servicing or replacing the compressor.
The compressor base shield is accessible when the compressor is removed. To remove the base shield without removing the compressor, remove one front compressor mounting bolt and grommet. At the three remaining compressor mounting grommets, cut the sound shield so that the base shield can be slid in the direction of the compressor mounting bolt and grommet that was removed. (See Fig. 39.) Cut replacement base shield along dotted lines as shown in Fig. 39 and reinstall in reverse direction. When installing the base shield, place the soft side facing upward. Reinstall compressor mounting grommet and bolt.
Cut Compressor Base Sound
COMPRESSOR BASE
SHIELD
Remove this compressor mounting bolt and grommet at this location.
Slide Compressor Base Sound Shield in this direction.
C08664
Fig. 39 -- Base Sound Shield
Control Circuit, 24-- V
Each control circuit is protected against overcurrent by a 3.2 amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting.
Replacement Parts
A complete list of replacement parts may be obtained from any Carrier distributor upon request.
Diagnostic L EDs
The MBB, ECB, AUX1, IGC and DSC control boards have LED lights for diagnostic purposes. The meanings and error codes can be found in the the troubleshooting section of this manual.
48/50PD
67
Page 68
APPENDIX A - LOCAL DISPLAY AND CCN TABLES
Table 2 7 — MODE - RUN STATUS
ITEM EXPANSION RANGE UNITS
RUN STATUS STATUS DISPLAY
VIEW Auto View of Run Status (VIEW = Display only)
HVAC HVAC Mode Status 1=Disabled
OCC Currently Occupied Ye s/ No OCCUPIED SAT Supply Air Temperature xxx..x dF SAT_DISP ALRM Current Alarms & Alerts xx ALRMALRT TIME Time of Day xx.xx hh.mm TIMECOPY
VERS Software Version Numbers VERSIONS
MBB CESR131459--- xx --- xx ( x x --- x x in
ECB CESR131249---xx--- xx MODEL_NUMBER_02 AUX CESR131333--- xx --- xx MODEL_NUMBER_ 03 MARQ CESR131171---xx--- xx MODEL_NUMBER_04
MODE Control Modes MODEDISP
SYS Unit operation disabled
48/50PD
HVAC HVAC Operation Disabled
HV.DN Remote HVAC Mode Disable Ye s/N o HVACDOWN forcible EFF.C Cool Setpoint in Effect xxx.x CSP_EFF EFF.H Heat Setpoint in Effect xxx.x HSP_EFF OCC Currently Occupied Ye s/ No OCCUPIED forcible T. O V R Timed Override in Effect Yes /No MODETOVR LINK Linkage Active Yes/N o MODELINK D.LMT Demand Limit In Effect Yes / No MODEDMDL C.LOC Compressor OAT Locko ut Yes/ N o COMPLOCK H.LOC Heat OAT Lockout Ye s/ No HEATLOCK E.LOC Econo Cool OAT Lockout Ye s/N o ECONLOCK
COOL Cooling Status COOLDISP
DMD.C Cooling Demand xxx.x ^F COOL_DMD SA.CP Supply Air Cont rol Point xxx.x dF SA_CTLPT SASP Cool Supply Air Setpoint xxx.x dF SASP SR.CD Cool Demand SASP Reset xxx.x ^F CD_RESET SR.RH De humidifying SASP Reset xxx.x ^F RH_RESET F.SPD Commanded Fan Speed xxx % FANSPEED CMP.A Compre ssor A Feedback On/Off COMP_A TG.A Compressor A Timeguard xxx sec TIMGD_A CAPC Compressor Capacity xxx % CAPACITY MAX.C Max Compressor Capacity xxx % MAX_CAPC forcible MIN.C Min Compressor Capacity xxx % MIN_CAPC LMT.C Max Capacity In Effect xxx % CAPLIMIT SST.A Sat . Suctio n Temp A xxx.x dF SST_A SSP.A Suction Pressure A xxx.x psig SSP_A SCT.A Sat. Condenser Temp A xxx.x dF SCT_A SCP.A Condenser Pressure A xxx.x psig SCP_A OFC.1 Outdoor Fan 1 Relay On/Off OFC_1
HEAT Heating Status HEATDISP
DMD.H Heating Demand xxx.x ^F HEAT_DMD AVL.H Available Heating Stages x AVLHSTGS REQ.H Requested Heating Stages x REQHSTGS MAX.H Max Allowed Heat Stages x MAXHSTGS forcible LMT.H Max Heat Stage In Effect x HSTGLIMT F.SPD Commanded Fan Speed xxx % FANSPEED HT.1 Heat Stage 1 Relay On/Off HEAT_1 TG.H1 Heat Stage 1 Timequard xxx sec TIMGD_H1 HT.2 Heat Stage 2 Relay On/Off HEAT_2 TG.H2 Heat Stage 2 Timequard xxx sec TIMGD_H2
ECON Economizer Status ECONDISP
EC.CP Econo Commanded Position xxx % ECONOCMD EC.AP Econo Actual Position xxx % ECONOPOS EC.MP MinPositioninEffect xxx % MIN_ POS IAQ.S IAQ Level (switch) High/Low IAQIN IAQ IAQ Level (sensor) xxxx ppm IAQ OAT Outdoor Air Temperature xxx.x dF OA_TEMP ENTH Outdoor Enthalpy Switch High/Low ENTHALPY OAQ OAQ Level (sensor) xxxx ppm OAQ PE.1 Power Exhaust 1 Relay On/Off PE_1 PE.2 Power Exhaust 2 Relay On/Off PE_2
HRS Component Run Hours STRTH OUR
A1 Compressor A1 Run Hours xxxxx.xx hours HR_A1 forcible CCH Crankcase Htr Run Hours xxxxx.xx hours HR_CCH forcible IDF Indoor Fan Run Hours xxxxx.xx hours HR_IDF forcible OFC.1 Outdoor Fan 1 Run Hours xxxxx.xx hours HR_OFC_1 forcible HT.1 Heat Stage 1 Run Hours xxxxx.xx hours HR_HTR_1 forcible HT.2 Heat Stage 2 Run Hours xxxxx.xx hours HR_HTR_2 forcible PE.1 Power Exhaust1 Run Hours xxxxx.xx ho urs HR_PE_1 forcible PE.2 Power Exhaust2 Run Hours xxxxx.xx ho urs HR_PE_2 forcible ALRM Alarm Relay Run Hours xxxxx.xx hours HR_ALM forcible
Unit operation enabled Service test enabled
Ventilation (fan--- only) Cooling Unoccupied Free Cooling Heating
2=Fan Only 3=Cool 4=Heat
table)
CCN
TABL E/ SUB ---TABLE
CCN POINT
HVACMODE
MODEL_NUMBER_01
SYS_MODE_TEXT1 SYS_MODE_TEXT2 (table only) SYS_MODE_TEXT3 (table only) HVACMODE_TEXT_1 HVACMODE_TEXT_2 (table only) HVACMODE_TEXT_3 (table only)
CCN WRITE
STATUS
68
Page 69
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 27 — MODE - RUN STATUS (cont)
ITEM EXPANSION RANGE UNITS
STRT Component Starts
A1 Compressor A1 Starts xxxxxx ST_A1 forcible CCH Crankcase Heater Starts xxxxxx ST_CCH forcible IDF Indoor Fan Starts xxxxxx ST_IDF forcible OFC.1 Outdoor Fan 1 Starts xxxxxx ST_OFC_1 forcible HT.1 Heat Stage 1 Starts xxxxxx ST_HTR_1 forcible HT.2 Heat Stage 2 Starts xxxxxx ST_HTR_2 forcible PE.1 Power Exhaust 1 Start s xxxxxx ST_ PE_1 forcible PE.2 Power Exhaust 2 Start s xxxxxx ST_ PE_2 forcible ALRM Alarm Relay Starts xxxxxx ST_ALM forcible
(ALRMDISP) = CCN
only)
(GENERIC = CCN
only)
(LON_DATA = CCN
only)
Active Alarm 1 Code xxx ALMCODE1 Active Alarm 2 Code xxx ALMCODE2 Active Alarm 3 Code xxx ALMCODE3 Active Alarm 4 Code xxx ALMCODE4 Active Alarm 5 Code xxx ALMCODE5 Reset All Current Alarms Ye s /No ALRESET forcible Reset Alarm H istory Yes/ No ALHISCLR forcible
nviSpaceTemp xxx.x dF NVI_SPT forcible nviSetPoint xxx.x dF NVI_SP forcible nvoSpaceTemp xxx.x dF NVO_ SPT nvoUnitStatus.mode xxxx NVO_MODE nvoUnitStatus.heat_out_p xxx.x % NVO_HPRI nvoUnitStatus.heat_out_s xxx.x % NVO_HSEC nvoUnitStatus.cool_out xxx.x % NVO_COOL nvoUnitStatus.econ_out xxx.x % NVO_ECON nvoUnitStatus.fan_out xxx % NVO_ FAN nvoUnitStatus.in_alarm xxx NVO_ALRM nviSetPtOffset xxx.x ^F NVI_SPTO forcible nviOutside Temp xxx.x dF NVI_OAT forcible nviOutside RH xxxx.x % NVI_OARH forcible nvoEffectSetPt xxx.x dF NVO_EFSP nvoOutsideTemp xxxx.x dF NVO_OAT nvoOutsideRH xxx.x % NVO_OARH nviSpaceRH xxx.x % NVI_SPRH forcible nviCO2 xxxxx NVI_CO2 forcible nvoCO2 xxxxx NVO_ CO2 nvoTEMP1 xxx.x dF NVO_SAT nvoTEMP2 xxx.x dF NVO_RAT nviPCT1 xxx.x % NVI_ RHSP forcible nvoPCT1 xxx.x % NVO_SPRH nviDISCRETE1 Off/On NVI_FSD forcible nviDISCRETE2 No/Yes NVI_OCC forcible nviDISCRETE3 Off/On NVI_IAQD forcible nvoDISCRETE1 Off/On NVO_ FSD nvoDISCRETE2 No /Yes NVO_OCC nvoDISCRETE3 Off/On NVO_IAQD nciCO2Limit xxxxx NCI_CO2 forcible nciSetPnts.occupied_cool xxx.x dF NCI_OC SP forcible nciSetPnts.standby_cool xxx.x dF NCI_SCSP forcible nciSetPnts.unoccupd_co ol xxx.x dF NCI_UCSP forcible nciSetPnts.occupied_heat xxx.x dF NCI_OHSP forcible nciSetPnts.standby_heat xxx.x dF NCI_SHSP forcible nciSetPnts.unoccupd_heat xxx.x dF NCI_UHSP forcible
CCN
TABL E/ SUB ---TABLE
ALRMDISP
GENERIC
LON_ DATA
CCN POINT
up to 20 points
CCN WRITE
STATUS
48/50PD
69
Page 70
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 28 — MODE - SERVICE TEST
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/SUB--- TA BL E CCN POINT
SERVICE TEST MAINTENANCE DISPLAY
TEST Field Service Test Mode On/Off Off (TEST = display only) MAN_CTRL forcible forcible INDP Test Independent Outputs TESTINDP
ECON Economizer Position Test 0 to 100 % 0 S_ ECONO forcible forcible E.CAL Calibrate Economizer On/Off Off S_ ECOCAL forcible forcible PE.1 Power Ex haust 1 Test On/Off Off S_PE_1 forcible forcible PE.2 Power Ex haust 2 Test On/Off Off S_PE_2 forcible forcible ALRM Alarm Relay Test On/Off Off S_ ALMOUT forcible forcible CCH Crankcase Heat Test On/Off Off S_CCH forcible forcible
FANS Tes t Fa n s TESTFANS
IDF Supply VFD Power Test On/Off Off S_IDF forcible forcible F.SPD Indoor Fan Speed Test 0 to 100 % 0 S_VSPEED forcible forcible OFC.1 Outdoor Fan Relay Test On/Off Off S_OFC_1 forcible forcible
COOL Test Cooling TESTCOOL
CTLR DigScrollCtrlPwrTest On/Off Off S_CMPCTL forcible forcible CAPC Compressor Capacity Test 0 to 100 % 0 S_VCAP forcible forcible F.SPD Cool Test Fan Speed 0 to 100 % 0 S_ VSPDCL forcible forcible
48/50PD
HEAT Te st H e a t i n g TESTHEAT
HT.1 Heat Stage 1 Test On/Off Off S_HEAT_1 forcible forcible HT.2 Heat Stage 2 Test On/Off Off S_HEAT_2 forcible forcible
CCN
WRITE
STATUS
Table 29 — MODE - TEMPERATURES
ITEM EXPANSION RANGE UNITS CCN TABLE /S UB --- TA BL E CCN POINT
STATUS DISPLAY
TEMPERATURES UINPUT
AIR.T Air Temperatures
SAT Supply Air Temperature xxx.x dF SAT_DISP OAT Outdoor Air Temperature xxx.x dF OA_TEMP forcible forcible SPT Space Temperature xxx.x dF SPACE_T forcible forcible SPTO Space Temperature Offset xxx.x dF SPTO forcible forcible RAT Return Air Temperature xxx.x dF RETURN_T forcible forcible
REF.T Refrigerant Temperatures xxx.x dF
SST.A Sat. Suction Temp A xxx.x dF SST_A SCT.A Sat. Condenser Temp A xxx.x dF SCT_A
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
DISPLAY
WRITE
STATUS
Table 30 — MODE - PRESSURES
ITEM EXPANSION RANGE UNITS CC N TABLE/ SUB--- TA BLE CCN POINT
STATUS DISPLAY
PRESSURES UINPUT
SSP.A Suction Pressure A xxx.x psig SSP_A SCP.A Condenser Pressure A xxx.x psig SCP_A
CCN
WRITE
STATUS
70
Page 71
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 31 — MODE - SET POINTS
ITEM EXPANSION RANGE UNITS DEFAULT CCN TAB LE /SUB ---TABLE CCN POINT
SETPOINTS SET_PNT
OCSP Occupied Cool Setpoint 55 to 80F dF 78 OCSP UCSP Unoccupied Cool Setpoint 75 to 95F dF 85 UCSP OHSP Occupied Heat Setpoint 55 to 80F dF 68 OHSP UHSP Unoccupied Heat Setpoint 40 to 80F dF 60 UHSP GAP Heat --- Cool Setpoint Gap 2 to 10F ^F 5 HCSP_GAP STO.R SPT Offset Range (+/ --- ) 0to5F ^F 5 SPTO_RNG SASP Cool Supply Air Setpoint 45 to 75 dF 65 SASP RH.SP Space RH Setpoint 30 to 95 % 50 SPRH_SP RH.DB Space RH Deadband 2to20 % 5 SPRH_DB C.LO Compressor Lockout Temp 0 to 100F dF 0 OATLCOMP HT.LO Heating Lockout Temp 40 to 125F dF 75 OATLHEAT EH.LO Econo Cool Hi Temp Limit 40 to 100F dF 65 OATLECLH EL.LO Econo Cool Lo Temp Limit --- 30 to 50F dF 0 OATLECLL FC.LO Free Cool Low Temp Limit 0 to 70F dF 50 OATLUEFC
Table 3 2 — MODE - - I N P U T S
ITEM EXPANSION RANGE UNITS CCN TA BL E/ SUB --- TABLE
STATUS DISPLAY
INPUTS UINPUTS
GEN.I General Inputs
FIL.S Filt er Status Switch Dirty/Clean FILTSTAT forcible FAN. S Fan Status Switch On/Off FAN_STAT forcible FDWN Fire Shutdow n Switch On/Off FIREDOWN forcible ENTH Outdoor Enthalpy Switch High/Low ENTHALPY forcible RM.OC Remote Occupancy Switch On/Off REM_OCC forcible HUM Space Humidity Switch High/Low HUM_STAT forcible CMP.A Compressor A Feedback On/Off COMP_A C.ALM Scroll Compressor Alarm On/Off COMP_ALM
CS.IN Current Sensor Inputs
CS.A1 Compressor A1 Feedback On/Off CS_A1
AIR.Q Air Quality Inputs
IAQ.S IAQ Level (switch) High/Low IAQIN forcible forcible IAQ IAQ Level (sensor) xxxx ppm IAQ forcible forcible OAQ OAQ Level (sensor) xxxx ppm OAQ forcible forcible SP.RH Space Humidity Sensor xxx.x % SPRH forcible forcible
SETPOINT CONFIGURATION
CCN
POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
48/50PD
71
Page 72
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 33 — MODE - OUTPUTS
ITEM EXPANSION RANGE UNITS CCN TABLE /S UB --- TA BL E CCN POINT
OUTPUTS UOUTPUT
FANS Fan Outp uts
IDF Indoor Fan VFD Pwr Relay On/Off IDF F.SPD Commanded Fan Speed xxx % FANSPEED OFC.1 Outdoor Fan 1 Relay On/Off OFC_1
COOL Cool Outputs
CTLR DigitalScrollCtrlPwr On/Off COMPCTLR CAPC Compressor Capacity xxx % CAPACITY CCH Crankcase Heat Relay On/Off CCH
HEAT Heat Outputs
HT.1 Heat Stage 1 Relay On/Off HEAT_1 HT.2 Heat Stage 2 Relay On/Off HEAT_2
ECON Economizer Outputs
EC.CP Econo Commanded Position 0 to 100 % ECONOCMD forcible forcible EC.AP Econo Actual Position 0 to 100 % ECONOPOS PE.1 Power Exhaust 1 Relay On/Off PE_1 forcible forcible
48/50PD
PE.2 Power Exhaust 2 Relay On/Off PE_2 forcible forcible
ALRM Alarm Relay On/Off ALMOUT forcible forcible
STATUS DISPLAY
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
72
Page 73
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 34 — MODE - CONFIGURATION
ITEM EXPANSION RA NGE UNITS DEFAULT
CONFIGURATION SERVICE
DISP Display Configuration DISPLAY
METR Met ric Display On/Off Off DISPUNIT 11 LANG Language Select ion 0=English
PROT Password Enable Enable/Disable Disable PA SS_ EBL 12 PSWD Service Password 0000 to 9999 1111 PA SSW OR D 12 TEST Test Display LEDs On/Off Off (display only, not in
UNIT Unit Configuration UNIT
S.DLY Startup Delay 0 to 600 sec 30 STARTDLY 12 OC.FN FanOnWhenOccupied Ye s/N o Ye s OCC_FAN 12 IDF.F Shut Down on IDF Failure Ye s /No Ye s FATALFAN 12 FS.MX Supply Fan Maximum
FS.MN Supply Fan Minimum
FS.VM Vent Mode Fan Speed 40 to 100 ^F 50 SPEEDVNT 12 FN.SW Fan Status Switch 0=No Switch
FL.SW Filter St atus Switch 0=No Switch
FS.SW Fire Shutdown Sw itch 0=No Switch
RM.SW Remote Occupancy
RH.S RH Sensor on OAQ Input Ye s /No No RH_OAQ 13 RH.SW Space Humidity Switch 0=No Switch
TCS.C Temp Cmp Strt Cool Factr 0to60 mins 0 TCSTCOOL 13 TCS.H TempCmpStrtHeatFactr 0to60 mins 0 TCSTHEAT 13
COOL Cooling Configuration COOL_CFG
MIN.C Min Compressor Capacity 15 to 80 % 70 MIN_CAPC 14 FS.CD Fan Speed Control
MRT.C Compressor Min On Time 120 to 999 sec 180 MIN_ON MOT.C Compressor Min Off Time 300 to 999 sec 300 MIN_OF F RST.C Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S 24 FOD.C Fan-off Delay, Mech Cool 0 to 600 sec 60 COOL_FOD CS.A1 Current Sensing A1 Enable/Disable Disable: reserved for
C.LO Compressor Lockout
ALM.N Alert Each Strike Yes//No Yes ALM_NOW 24 SAT Supply Air Temperature
SASP Cool Supply Air Setpoint 45 to 75 dF 65 SASP 17 SA.MU SASP Maximum Reset Up 0to20 ^F 10 SASPMAXU 18 SA.MD SASP Maximum Reset
SAT.U Minimum SAT Upper Level 35.0 to 65.0 dF 60 SATMIN_H SAT.L Minimum SAT Lower Level 35.0 to 65.0 dF 45 SATMIN_L
SST Low Suction Control
SST.O Suction OK Temperature 10 to 50 dF 18 SSTOK 26 SST.1 Low Suct ion --- Level 1 10 to 50 dF 20 SSTLEV1 26 SST.2 Low Suct ion --- Level 2 5to50 dF 15 SSTLEV2 26 SST.3 Low Suct ion --- Level 3 0to50 dF 10 SSTLEV3 26 PSI.D Ckt A Minimum Pressure 0 to 500 psig 20 DELTAP_A 26
OFC Outdoor Fan Control
1.MXP Fan Lev1 Max Pressure 100 to 500 psig 450 LEV1MAXP 15
2.MNP Fan Lev2 Min Pressure 100 to 500 psig 200 LEV2MINP 15
2.ON FanLev2OnTemperature 0 to 100 F 55 LEV2ON 15
2.OFF Fan Lev2 Off Temperature 0 to 100 F 45 LEV2OFF 15
Speed
Speed
Switch
Demand
Te m p
Down
1=Spanish 2=French 3=Portuguese
80 to 100 % 100 SPEEDMAX 12
10 to 40 % 20 SPEEDMIN 12
1=Normal Open 2=Normal Closed
1=Normal Open 2=Normal Closed
1=Normal Open 2=Normal Closed 0=No Switch 1=Normal Open 2=Normal Closed
1=Normal Open 2=Normal Closed
1to9.9 ^F 3 SPEEDDMD 17
0 to 100F dF 0 OATLCOMP
--- 2 0 t o 0 ^F --- 1 0 SASPMAXD 18
0 LANGUAGE 11
0: no FIOP 1: FIOP
0: no FIOP 1: FIOP
0: no FIOP 1: FIOP
0 REMOCCFG 12
0 HUMSTCFG 13
future use DO NOT ENABLE
CCN
TABL E/ SUB ---TABLE
CONFIGURATION
table)
CCN POINT
DISPTEST 12
FANSTCFG 12
FILSTCFG 12
SHTDNCFG 12
A1_SENSE 25
PAG E
NO.
48/50PD
73
Page 74
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 34 — MODE - CONFIGURATION (cont)
ITEM EXPANSION RA NGE UNITS DEFAULT
HEAT Heating Configuration HEAT_CFG
HT.TY Type of Heat Installed 0=No Heat
N.HTR Number of Heat Stages 1to2 1 (50 series <15kW)
MRT.H Heat Minimum On Time 60 to 999 sec 120 HMIN_ON 22 MOT.H Heat Minimum Off Time 60 to 999 sec 120 HMIN_OFF 22 H.DEC Heat Stage Decrease
H.INC Heat Stage Increase Time 120 to 999 sec 450 HSTAGINC 21 FOD.E Fan--- off Delay, Elect Heat 10 to 600 sec 30 ELEC_FOD 22 FOD.G Fan--- off Delay, Gas Heat 45 to 600 sec 45 GAS_FOD 20 HT.LO Heating Lockout Temp 40 to 125F dF 75 OATLHEAT 20 SAT SUPPLY AIR
SAT.H SAT Heat Mode Sensing Enable/Disable Disable SAT_HEAT 21
48/50PD
ECON Economizer Configuration ECON_CFG
SAM.L Maximum SAT Lower
SAM.U Maximum SAT Upper
SPT SPACE TEMPERATURE
HT.PD SPT Heat Demand (+)
HT.ND SPT Heat Demand (--- )
H.LAG Heat Thermal Lag Factor 0to5 min 1 HEAT_LAG 21
EC.EN Economizer Installed Ye s /No No: no FIOP
E.CTL Economizer Control Type 1=Dig/Position
MP.25 Econ Min at 25%
MP.50 Econ Min at 50%
MP.75 Econ Min at 75%
MP.MX Econ Min at Max
EC.MX Econo Cool Max Position 0 to 100 % 100 ECONOMAX M.ANG Min Actuator Ctrl Angle 75 to 90 88 MINANGLE 27 EH.LO Econo Cool Hi Temp Limit 40 to 100F dF 65 OATLECLH 15 EL.LO Econo Cool Lo Temp Limit --- 30 to 50F dF 0 OATLECLL 15 DF.DB Diff Dry Bulb Control Disable/Enable Enable DIFFBULB UEFC Unoccupied Free Cooling 0=Disabled
FC.TM Free Cool PreOcc Time 1 to 9999 min 120 UEFCTIME 16 FC.LO Free Cool Low Temp Limit --- 30 to 70F dF 50 OATLUEFC 16 PE.EN Power Exha ust Installed Ye s /No No: no FIOP
PE1.C Power Exhaust Stage1
PE2.C Power Exhaust Stage2
IDF.C Indoor Fan Max Speed
EN.SW Enthalpy Switch 0=No Switch
Time
TEMPERATURE
Level
Level
Level
Level
Fanspeed
Fanspeed
Fanspeed
Fanspeed
CFM
CFM
CFM
1=Gas 2=Electric
120 to 999 sec 300 HSTAGDEC 22
85 to 200 dF 140 SATMAX_L 21
85 to 200 dF 160 SATMAX_H 21
0.5 to 5 ^F 1 HDEM_POS 21
--- 5 t o --- 0 . 5 ^F --- 1 HDEM_NEG 21
2=Dig/Command 3=Analog Ctrl 0 to 100 % 0 MINP_25 19
0 to 100 % 0 MINP_50 19
0 to 100 % 0 MINP_75 19
0 to 100 % 30 MINP_MAX 19
1=Unoccupied 2=Preoccupancy
100 to 15000 cfm 600 PE1_CFM 16
100 to 15000 cfm 0 PE2_CFM 16
500 to 15000 cfm 1600 (05)
1=Normal Open 2=Normal Closed
0(50serieswithno electric heat) 1(48series) 2(50serieswith electric heat)
2(48series,50 series >=15kW)
Yes : F IOP 1 ECON_CTL 10
2 UEFC_CFG 15
Yes : F IOP
2000 (06) 0: no FIOP
1: FIOP
CCN
TABL E/ SUB ---TABLE
CCN POINT
HEATTYPE 20
NUM_HEAT 22
ECONO 8
PE_ENABL 16
IDF_CFM 16
ENTHLCFG 59
PAG E
NO.
74
Page 75
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 34 — MODE - CONFIGURATION (cont)
ITEM EXPANSION RA NGE UNITS DEFAULT
AIR.Q Air Quality Config. IAQ_CFG
IA.CF IAQ Analog Input Config 0=No IAQ
IA.FN IAQ Analog Fan Config 0=Never
II.CF IAQ Sw itch Input Config 0=No IAQ
II.FN IAQ Switch Fan Config 0=Never
AQ.MN Econo Min IAQ Position 0 to 100 % 10 IAQMINP 17 OVR.P IAQ Override Position 0 to 100 % 100 IAQOVPOS 17 OA.CF OAQ Analog Input Config 0=No OAQ
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQLOCK 17 AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW 19 AQD.H AQ Differential High 0 to 5000 700 DAQ_HIGH 19 DF.ON FanOnAQDifferential 0 to 5000 600 DAQFNON 17 DF.OF Fan Off AQ Differential 0 to 5000 200 DAQFNOFF 17 I.4M IAQ Sensor Value at 4mA 0 to 5000 0 IAQ_4MA 16 I.20M IAQ Sensor Value at 20mA 0 to 5000 2000 IAQ_20MA 16 O.4M OAQ Sensor Value at 4mA 0 to 5000 0 OAQ_4MA 17 O.20M OAQ Sensor Value at
H.4M RH Sensor Value at 4mA 0to50 % 0 RH_4MA H.20M RH Sensor Value at 20mA 60 to 100 % 100 RH_20MA
ALM.O Alarm Relay Config. ALM_CFG
A.SPC SPT/SPRH Sensor Failure Ye s/N o Yes SPACE_AL A.SRT SAT/RAT Sensor Failure Yes/ No Ye s SATRATAL A.OAT OAT Thermistor Failure Ye s /N o Ye s OAT_AL A.CS Current Sensor Failure Ye s /No No CS_AL A.CMP Compressor Failure Ye s/N o Ye s COMP_AL A.CKT Refrig Circuit Failure Ye s /N o Ye s CKT_AL A.SSP SSP Transducer Failure Yes/N o Ye s SSP_AL A.SCT SCT Thermistor Failure Ye s /No Ye s SCT_AL A.FAN Indoor Fan Failure Ye s/N o Yes FAN_AL A.FIL Dirty Filter Yes / No Ye s FILT_AL A.ECO Economizer Failure Ye s /No Ye s ECON_AL
PID PID Configurations PID_CFG
EC.P Economizer PID --- kP 0.0 to 99.9 2.5 ECONO_P EC.I Economizer PID --- kI 0.0 to 99.9 0.1 ECONO_I EC.D Economizer PID --- kD 0.0 to 99.9 1 ECONO_D EC.DT Economizer PID --- rate 10.0 to 180.0 sec 15 ECONO_DT E.DBD Economizer PID
CP.P C a p a c i t y P I D --- k P 0 to 99.9 1.5 VCAP_P CP.I C a p a c i t y P I D --- k I 0 to 99.9 0.1 VCAP_I CP.D C a p a c i t y P I D --- k D 0 to 99.9 1 VCAP_D CP.DT Capacity PID --- rate 1to30 secs 5 VCAP_ DT LK.P Linkage Staging PID --- kP 0.0 to 99.9 10 LINK_P LK.I Linka ge Sta ging PID --- kI 0.0 to 99.9 5 LINK_I LK.D Linkage Staging PID --- kD 0.0 to 99.9 5 LINK_D LK.DT Linkage Staging PID ---
20mA
Deadband
rate
1=DCV 2=Override IAQ 3=Ctrl Min Pos
1=Occupied 2=Always
1=DCV N/O 2=DCV N/C 3=Override N/O 4=Override N/C
1=Occupied 2=Always
1=DCV 2=Lockout OAQ
0 to 5000 2000 OAQ_20MA 17
0to25 % 3 ECONBAND
10.0 to 180.0 secs 30 LINK_DT
0: no FIOP 1: FIOP
0 IAQANFAN 14
0 IAQINCFG 17
0 IAQINFAN 17
0 OAQANCFG 17
CCN
TABL E/ SUB ---TABLE
CCN POINT
IAQANCFG 59
PAG E
NO.
48/50PD
75
Page 76
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 34 — MODE - CONFIGURATION (cont)
ITEM EXPANSION RA NGE UNITS DEFAULT
(GENERIC = CCN only) GENERICS 5
48/50PD
TRIM Sensor Calibration (CCN TRIM --- see
SPT.C Space Temp Calibration --- 30 to 130 dF 38 SPT.T Space Temp Trim --- 30 to 30 ^F 0 38 SAT.C Supply Air Temp Calib. --- 30 to 130 dF 38 SAT.T Supply Air Temp Trim --- 30 to 30 ^F 0 38 RAT.C Return Air Temp Calib. ---30 to 130 dF 38 RAT.T Return Air Temp Trim --- 30 to 30 ^F 0 37
CCN CCN Configuration 48_50_PD
CCN.A CCN Element Number 1 to 239 1 CCNADD 8 CCN.B CCN Bus Number 0 to 239 0 CCNBUS 8 BAUD CCN Baud Rate 2400, 4800, 9600,
BROD CCN Broadcast Config. BRODEFS
B.TIM CCN Time/Date Broadcast Ye s /N o No CCNBC 23 B.OAT CCN OAT Broadcast Yes / No No OATBC 23 B.GS Global Schedule Broadcst Yes/ N o No GSBC 23 B.ACK CCN Broadcast Ack’er Ye s /No No CCNBCACK 23
SCH.O CCN Schedule Overrides SCHEDOVR
SCH.N Schedule Number 0=Always
HOL.G Accept Global Holidays Yes/N o No HOLIDAYT 23 OV.TL Override Time Limit 0to4 ho urs 4 OTL 23 OV.EX Timed Override Hours 0to4 hours 0 OVR_EXT 23 OV.SP SPT Override Enabled Ye s/ N o Yes TIMEOVER 23
LDSH CCN Schedule Overrides LO AD SHED
S.GRP Loadshed Group Number 0to16 0 SHED_NUM 24 R.MXC Redline Max Capacity 0 to 100 % 100 MAXCREDL 24 S.MXC Loadshed Max Capacity 0 to 100 % 100 MAXCSHED R.MXH Redline Max Heat Stages 0to2 2 MAXHREDL 24 S.MXH Loadshed Max Heat
POINT 01 Definition 8 --- c h a r A S C I I Poi nt_ 01
POINT 02 Definition 8 --- c h a r A S C I I Poi nt_ 02
POINT 03 Definition 8 --- c h a r A S C I I Poi nt_ 03
POINT 04 Definition 8 --- c h a r A S C I I Poi nt_ 04
POINT 05 Definition 8 --- c h a r A S C I I Poi nt_ 05
POINT 06 Definition 8 --- c h a r A S C I I Poi nt_ 06
POINT 07 Definition 8 --- c h a r A S C I I Poi nt_ 07
POINT 08 Definition 8 --- c h a r A S C I I Poi nt_ 08
POINT 09 Definition 8 --- c h a r A S C I I Poi nt_ 09
POINT 10 Definition 8 --- c h a r A S C I I Poi nt_ 10
POINT 11 Definition 8 --- c h a r A S C I I Poi nt_ 11
POINT 12 Definition 8 --- c h a r A S C I I Poi nt_ 12
POINT 13 Definition 8 --- c h a r A S C I I Poi nt_ 13
POINT 14 Definition 8 --- c h a r A S C I I Poi nt_ 14
POINT 15 Definition 8 --- c h a r A S C I I Poi nt_ 15
POINT 16 Definition 8 --- c h a r A S C I I Poi nt_ 16
POINT 17 Definition 8 --- c h a r A S C I I Poi nt_ 17
POINT 18 Definition 8 --- c h a r A S C I I Poi nt_ 18
POINT 19 Definition 8 --- c h a r A S C I I Poi nt_ 19
POINT 20 Definition 8 --- c h a r A S C I I Poi nt_ 20
3 CCNBAUDD 8
0 SCHEDNUM 23
Stages
19200, 38400
Occupied
1 --- 6 4 =
Local Schedule
=GlobalSchedule
0to2 2 MAXHSHED
65--- 99
CCN
TABL E/ SUB ---TABLE
Maintenance Display)
CONFIGURATION
CCN POINT
PAG E
NO.
76
Page 77
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 35 — MODE - TIME CLOCK
ITEM EXPANSION RANGE UNITS DEFAULT
TIME CLOCK CONFIGURATION
TIME Time of Day TIME
TIME Hour and Minute xx.xx hh.mm TIME
DATE Current Date
MNTH Month of Year January, February,  &,
DOM Day of Month 1to31 DOM YEAR Ye a r xxxx YOCDISP DAY Day of Week Monda y, Tuesday,  &,
DST Daylight Savings Config. BRODEFS
December
Sunday
CCN
TABL E/ SUB ---TABLE
(continued)
CCN POINT
MOY
DOWDISP
STR.M Start Month January, February,  &,
STR.W Start Week 1to5 2 STARTW STR.D Start Day 1to7 7 STARTD M.ADD Minute s to Add 0to90 60 MINADD
STP.M Stop Month January, February,  &,
STP.W Stop Week 1to5 1 STOPW STP.D Sto p Day 1to7 7 STOPD M.SUB Minutes to Subtract 0to90 60 MINSUB
SCH.L Occupancy Schedule (SCH.L = Display only)
PER.x Occupancy Period x OCC.x Occupied From 00.00 to 23.59 hh.mm 00.00 PERxOCC UNC.x Occupied To 00.00 to 23.60 hh.mm 00.00 PERxUNC MON.x Monday in Period Ye s/ N o No PERxMON TUE.x Tuesday in Period Ye s /No No PERxTUE WED.x Wednesday in Period Yes / No No PERxWED THU.x Thursday in Period Ye s /No No PERxTHU FRI.x Friday in Period Yes/ No No PERxFRI SAT.x Saturday in Period Yes /No No PERxSAT SUN.x Sunday in Period Ye s /No No PERxSUN HOL.x Holiday in Period Yes/ N o No PERxHOL (repeat up to x=8
Periods)
(OCCFECS = CCN only) OCCDEFCS
HOL.L Holiday Schedule HOLIDAY
HOL.x Holiday x 0 HOLDYxxS MON.x Holiday Start Month 1to12=Januaryto
DAY.x Holiday Start Day 1to31 0 HOLDAYxx LEN.x Holiday Duration (days) 1to99 0 HOLLENxx (repeat up to x=9
Holidays)
Timed Override Hours x hours O V R --- E X T Peri od x DOW
(MTWTFSSH) Occupied From 00.00 to 24.00 hh.mm 00.00 OCCTODx Occupied To 00.00 to 24.00 hh.mm 00.00 UNOCTODx
December
December
xxxxxxxx 00000000 DOWx
December
3 STARTM
11 STOPM
0 HOLMONxx
(repeat up to x=8 Periods)
(repeat up to xx=30 Holidays)
48/50PD
Table 36 — CCN ONLY TABLES
ITEM EXPANSION RANGE UNITS DEFAULT
(ALARMDEF = CCN only) ALARMDEF
Alarm Routing Control 00000000 to 11111111 11000000 ALRM_CNT Equipment Priority 0to7 4 EQP_TYPE Comm Failure Retry Time 1 to 240 min 10 RETRY_TM R e --- A l a r m T i m e 1 to 255 min 180 RE--- ALARM AlarmSystemName up to 8 alphanum 48_50_PD ALRM_NAM
(CTLRID = CCN only) C T L R --- I D
Device Name: 48_50_PD Description: text string Location: text string Software Part Number: CESR131459---XX--- XX Model Number: Serial Number: Reference Number:
CCN
TABL E/ SUB ---TABLE
77
CCN POINT
Page 78
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 37 — MODE - OPERATING MODES
ITEM EXPANSION RA NGE UNITS
OPERATING MODES MAINTENANCE
MODE Cont rol Modes MODES
SYS Unit operation disabled
HVAC HVAC Operation Disabled
HV.DN Remote HVAC Mode
EFF.C Cool Setpoint in Effect xxx.x CSP_EFF EFF.H Heat Setpoint in Effect xxx.x HSP_EFF OCC Currently Occupied Yes / No OCCUPIED forcible forcible
48/50PD
T. O V R Timed Override in Effect Yes/ No MODETOVR LINK Linkage Active Yes /N o MODELINK D.LMT Demand Limit In Effect Ye s/ N o MODEDMDL C.LOC Compresso r OAT Lockout Ye s /N o COMPLOCK H.LOC Heat OAT Lockout Ye s/ N o HEATLOCK E.LOC Econo Cool OAT Lockout Yes/ No ECONLOCK
COOL Cool Mode Diagnostic COOLDIAG
COOL In Cooling Mode? Yes/ No IN_COOL OK.CL OK to Select Cool Mode? Ye s/ N o OKTOCOOL MS.TG Mode Select Timeguard xxx secs COOLMSTG OK.EC OK to Use Economizer? Yes /No ECONCOOL OK.MC OK to Use Compressor? Ye s/N o MECHCOOL C.LOC Compresso r OAT Lockout Ye s /N o COMPLOCK C.LO Compressor Lockout Temp xxx dF OATLCOMP IDF Indoor Fan State On/Off IDFSTATE F.SPD Commanded Fan Speed xxx FANSPEED REQ.C Requested Cooling
MIN.C Min Compressor Capacity xxx % MIN_CAPC MAX.C Max Compressor Capacity xxx % MAX_CAPC LMT.C Max Capacity In Effect xxx % CAPLIMIT CAPC Compressor Capacity xxx % CAPACITY CTLR DigitalScrollCtrlPwr On/Off COMPCTLR CMP.A Compressor A Feedback On/Off COMP_A ST.A Circuit A Strikes x ASTRIKES F. L E V Outdoor Fan Level x FANLEV SAT Supply Air Temperature
SAT Supply Air Temperature xxx.x dF SAT_DISP SA.DM Supply Air Temp Demand xxx.x ^F SAT_DMD SAT.U Minimum SAT Upper Level xx.x dF SATMIN_H SAT.L Minimum SAT Lower Level xx.x dF SATMIN_L
SPT Space Temperature
SPT Space Temperature xxx.x dF SPACE_T forcible TRND Spacetemp Trend (F/min) xxx.x SPTTREND DMD.C Cooling Demand xxx.x ^F COOL_DMD
Unit operation enabled Service test enabled
Ventilation (fan--- only) Cooling Unoccupied Free Cooling Heating
Disable
Capacity
Yes / No HVACDOWN forcible
xxx % REQ_CAPC
CCN
TABL E/ SUB ---TABLE
DISPLAY
CCN POINT
SYS_MODE_TEXT1 SYS_MODE_TEXT2 (table only) SYS_MODE_TEXT3 (table only)
HVACMODE_TEXT _1 HVACMODE_TEXT _2 (table only) HVACMODE_TEXT _3 (table only)
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
78
Page 79
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 37 — MODE - OPERATING MODES (cont)
ITEM EXPANSION RA NGE UNITS
HEAT Heat Mode Diagnostic HEATDIAG
HEAT In Heating Mode? Yes / No IN_HEAT OK.HT OK to Select Heat Mode? Ye s /No OKTOHEAT MS.TG Mode Select Timeguard xxx secs HEATMSTG H.LOC Heat OAT Lockout Ye s/ N o HEATLOCK HT.LO Heating Lockout Temp xxx dF OATLHEAT IDF Indoor Fan State On/Off IDFSTATE F.SPD Commanded Fan Speed xxx FANSPEED AVL.H Available Heating Stages x AVLHSTGS REQ.H Requested Heating Stages x REQHSTGS LMT.H Max Heat Stage In Effect x HSTGLIMT ACT.H Actual Heating Stages x ACTHSTGS HT.1 Heat Stage 1 Relay On/Off HEAT_1 HT.2 Heat Stage 2 Relay On/Off HEAT_2 SAT Supply Air Temperature
SAT.H SAT Heat Mode Sensing Enable/Disable SAT_HEAT SAT Supply Air Temperature xxx.x dF SAT_DISP SAM.L Maximum SAT Lower Level xxx dF SATMAX_L SAM.U Maximum SAT Upper Level xxx dF SATMAX_H
SPT Space Temperature
SPT Space Temperature xxx.x dF SPACE_T forcible DMD.H Heating Demand xxx.x dF HEAT_DMD TRND Spacetemp Trend (F/min) xxx.x SPTTREND HT.PD SPT Heat Demand (+)
HT.ND SPT Heat Demand (--- )
ECON Economizer Diagnostic ECONDIAG
DMD.L Demand Limiting DMDL
( D i s p l a y T R I M --- s e e
Configuration)
H.LAG Heat Thermal Lag Factor x.x min HEAT_LAG
EC.EN Economizer Installed Ye s /No ECONO OCC Currently Occupied Yes / No OCCUPIED forcible forcible IDF Indoor Fan State On/Off IDFSTATE F.SPD Commanded Fan Speed NNN FANSPEED COOL In Cooling Mode? Yes/ No IN_COOL E.LOC Econo Cool OAT Lockout Yes/ No ECONLOCK EH.LO Econo Cool Hi Temp Limit xxx dF OATLECLH EL.LO Econo Cool Lo Temp Limit xx dF OATLECLL FC.LO Free Cool Low Temp Limit xx dF OATLUEFC EN.LO Econo Cool Enth Lockout Ye s /No ENTHLOCK EC.MX Econo Cool Max Position xxx % ECONOMAX AQ.DV IAQ DCV Mode Yes /N o IN_IAQDV AQ.MN Econo Min IAQ Position xxx % IAQMINP AQ.OV IAQ Override Mode Yes /N o IN_IAQOV OVR.P IAQ Override Position xxx % IAQOVPOS AQ.LO OAQ Lockout Mode Ye s /N o IN_OAQLO OAQ.L OAQ Lockout Limit xxxx OAQLOCK LP.OV Lo Refrig Press Override Ye s/N o IN_LPOV EC.CP Econo Commanded
EC.AP Econo Actual Position xxx % ECONOPOS EC.MP MinPositioninEffect xxx % MIN_POS forcible C.ANG Actuato r Control Angle CTLANGLE E.CAL Economizer Calibrating Yes/ No ECOINCAL
D.LMT Demand Limit In Effect Ye s/ N o MODEDMDL LMT.C Max Capacity In Effect xxx CAPLIMIT LMT.H Max Heat Stage In Effect x HSTGLIMT REDL Redline Activated Ye s/N o MODEREDL SHED Loadshed Activated Yes /No MODESHED MAX.C Max Compressor Capacity x MAX_CAPC forcible MAX.H Max Allowed Heat Stages x MAXHSTGS forcible
Level
Level
Positio n
Sensor Ca librat ion TRIM
Space Temp Calibration ---30 to 130 dF SPT_CAL forcible Space Temp Trim --- 30 to 30 ^F SPT_OFF forcible Supply Air Temp Calib. --- 30 to 130 dF SAT_CAL forcible Supply Air Temp Trim --- 30 to 30 ^F SAT_OFF forcible Return Air Temp Calib. --- 30 to 130 dF RAT_CAL forcible Return Air Temp Trim --- 30 to 30 ^F RAT_OFF forcible
xx.x ^F HDEM_POS
xx.x ^F HDEM_NEG
xxx % ECONOCMD forcible
CCN
TABL E/ SUB ---TABLE
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
48/50PD
79
Page 80
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 37 — MODE - OPERATING MODES (cont)
ITEM EXPANSION RA NGE UNITS
(OCCDEFM = CCN only) Occupancy Supervisory OCCDEFM
(LINKDATA = CCN only) CCN --- Linkage LINKDATA
48/50PD
Current Mode (1=Occup) 0,1 MODE CurrentOccupPeriod# 0to8 PER_NO T i m e --- O v e r r i d e i n E f f e c t Ye s /No OVERLAST Time--- Override Duration 0to4 hours OVR_HRS Current Occupied Time xx.xx hh:mm STRTTIME Current Unoccupied Time xx.xx hh:mm ENDTIME Next Occupied Day NXTOCDAY Next Occupied Time xx.xx hh:mm NXTOCTIM Next Unoccupied Day NXTUNDAY Next Unoccupied Time xx.xx hh:mm NXTUNTIM Previous Unoccupied Day PRVUNDAY Previous Unoccupied Time xx.xx hh.mm PRVUNTIM
Supervisory Element # xxx S U P E --- A D R Supervisory Bus xxx S U P E --- B U S Supervisory Blo ck Number xxx BLOCKNUM Average Occup. Heat Stp. xxxx.x dF AOH S Average Occup. Cool Stp. xxxx.x dF AOCS Average Unocc. Heat Stp. xxxx.x dF AUHS Average Unocc. Cool Stp. xxxx.x dF AUCS AverageZoneTemperature xxxx.x dF AZT Average Occup. Zone Temp xxxx.x dF AOZT Linkage System Occupied? Yes/ No LO CC Next Occupied Day ”Mon”, ”Tue”,
Next Occupied Time xx:xx hh:mm LNEXTOCC forcible Next Unoccupied Day ”Mon”, ”Tue”,
Next Unoccupied Time xx:xx hh:mm LNEXTUNC forcible Last Unoccupied Day ”Mon”, ”Tue”,
Last Unoccupied Time xx:xx hh:mm LLASTUNC forcible
& , ”Sun”
& , ”Sun”
& , ”Sun”
3 --- c h a rtext
3 --- c h a rtext
3 --- c h a rtext
CCN
TABL E/ SUB ---TABLE
CCN POINT
LNEXTOCD
LNEXTUOD
LLASTUOD
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
Table 38 — MODE - ALARMS
ITEM EXPANSION RANGE DEFAULT
ALARMS ALARMS
R.CUR Reset All Current Alarms Yes/ N o No ALRESET forcible forcible R.HIS Reset Alarm History Ye s/ N o No ALHISCLR forcible forcible CURR Currently Active Alarms
alarm# text string ALARM01C ---
(repeat up to 25
alarms)
HIST Alarm History ALARM HISTORY
alarm# alarm#--- mm/dd/yy --- hh.mm
(repeat up to 20
Alarms)
--- t e x t s t r i n g
CCN
TABL E/ SUB ---TABLE
MAINTENANCE DISPLAY
CCN POINT
ALARM25C
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
80
Page 81
APPENDIX B - VFD INFORMATION
On 48/50PD units, the supply fan speed is controlled by a 3 -- phase VFD. The VFD is located in the supply fan section behind an indoor fan scroll. The VFD speed is controlled directly by the ComfortLinkt controls through a 0--10Vdc signal based on a space temperature sensor. The VFD has a display, which can be used for service diagnostics, but setup of the control is to be done through the scrolling marquee display.
Table 39 — VFD TERMINAL DESIGNATIONS
TERMINAL FUNCTION
U1
V1
W1 Three --- Phase main circuit input power supply
U2
V2 Three --- Phase AC output to motor, 0V to maximum input
W2 voltage level
X 1 --- 1 1 ( G N D )
X 1 --- 1 2 ( C O M M O N ) Factory---supplied jumper
X1--- 10 (24VDC)
X 1 --- 1 3 ( D I --- 1 ) Run (factory---supplied jumper)
X1--- 10 (24VDC) Start Enable 1 (factory--- supplied jumper). When opened,
X 1 --- 1 6 ( D I --- 4 ) the drive goes to emergency stop
X 1 --- 2 ( A I --- 1 )
X 1 --- 3 ( A G N D ) Factory wired for 0---10Vdc remote input
The VFD is powered during normal operation to prevent condensation from forming on the boards during the off mode and is stopped by driving the speed to 0 (by sending a 0Vdc signal to the VFD). The units use ABB VFDs. The interface wiring for the VFDs is shown in the figure below. The VFD connects to ComfortLink through a 0-- 10Vdc output on the AUX1 board. Terminal designations are shown in the Terminal Designation table. Configurations are shown in the VFD Configurations table.
48/50PD
0-10Vdc
A48-7712
C08674
Fig. 40 -- VFD Wiring
81
Page 82
APPENDIX B - VFD INFORMATION (CONT)
Table 40 — VFD CONFIGURATIONS
APPLICATION CRITICAL DRIVE PARAMETERS FOR ABB ACH550 DRIVES
Parameter Group
S T A R T --- U P
DATA
48/50PD
START/STOP/DIR
ANALOG INPUTS
RELAY OUTPUTS
SYSTEM
CONTROL
OVER RIDE
LIMITS
START/STOP
ACCEL/DECEL
MOTOR
FAULT
FUNCTIONS
All Other Parameter Settings are ABB Drive Default Settings
Parameter
Number
9901 Language (0) English --- ABB Drive default
9902 Application Macro (1) HVAC Default ---
9904 Motor Control Mode (3) Scalar : Freq --- ABB Drive default
9905 Motor Nominal Voltage 230 460 Volts
9906 Motor Nominal Current 7.0 3.5 Amps
9907 Motor Nominal Frequency 60 Hz ABB Drive default
9908 Motor Nominal Speed 1725 RPM
9909 Motor Nominal Power 2.4 HP
1001 EXT1 Commands (1) DI --- 1 Start/Stop --- ABB Drive default
1002 EXT2 Commands (1) DI --- 1 Start/Stop --- ABB Drive default
1003 Direction (1) Forward ---
1301 M i n i m u m A l --- 1 20 % ABB Drive defau lt
1302 M a x i m u m A l --- 1 100 % ABB Dr ive default
1401 Relay Output 1 (7) Started ---
1402 Relay Output 2 (2) Run --- ABB Drive default
1403 Relay Output 3 ( 3 ) F a u l t ( --- 1 ) --- ABB Drive default
1601 Run Enable (0) Not Set --- ABB Drive default
1608 Start Enable 1 ( 4 ) D I --- 4 --- ABB Drive defau lt
1701 Override Set (3 ) D I --- 3 ---
1702 Override Freq 60 Hz
1703 Override Speed 1750 RPM
1704 Over Pass Code 0 ---
1705 Override On ---
2003 Maximum Current 8.0 4.0 Amps
2007 Minimum Frequency 0 Hz ABB Drive default
2008 Maximum Frequency 60 Hz ABB Drive defau lt
2101 Start Function (8) Ramp ---
2102 Stop Function (2) Ramp ---
2202 Accelerate Time 30 Seconds ABB Drive default
2203 Decelerate Time 30 Seconds ABB D rive default
2601 Flux Optimization (1) On ---
2605 Volt/Freq Ratio (2) Squared ---
2606 Switching Frequency 8 kHz
3006 Motor Thermal Time 1050 Seconds
Description
HK30WA001 ---208/230V HK30WA008 --- 460V
Value
UNITS NOTE
PD Product specific setting
PD Product specific setting
PD Product specific setting
PD Product specific setting
PD Product specific setting
PD Product specific setting
Carrier default settings from PPS
Carrier default settings from PPS
Carrier default settings from PPS
Carrier default settings from PPS
Carrier default settings from PPS
Carrier default settings from PPS
PD Product specific setting
PD Product specific setting
PD Product specific setting
PD Product specific setting
Carrier default settings from PPS
Carrier default settings from PPS
Carrier default settings from PPS
82
Page 83
APPENDIX B - VFD INFORMATION (CONT)
VFD Operation
The VFD keypad is shown in Fig. 41. The function of SOFT KEYS 1 and 2 change depending on what is displayed on the screen. The function of SOFT KEY 1 matches the word in the lower left--hand box on the display screen. The function of SOFT KEY 2 matches the word in the lower right--hand box on the display screen. If the box is empty, then the SOFT KEY does not have a function on that specific screen. The UP and DOWN keys are used to navigate through the menus. The OFF key is used to turn off the VFD. The AUTO key is used to change control of the drive to automatic control. The HAND key is used to change control of the drive to local (hand held) control. The HELP button is used to access the help screens.
For the VFD to operate on the 48/50PD units, the drive must be set in AUTO mode. The word “AUTO” will appear in the upper left hand corner of the VFD display. Press the AUTO button to set the drive in AUTO mode.
C08675
Fig. 41 -- VFD Keypad
Start Up with Assistant
Initial start--up has been performed at the factory. Use of the start up assistant will override factory VFD configurations. See below to check that all parameters listed in VFD Configurations table are correctly configured on the VFD.
Start Up by Changing Parameters Individually
Initial start--up is performed at the factory. To start up the VFD with by changing individual parameters, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2).
5. Use the UP or DOWN keys to change the value of the parameter.
6. Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed.
7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the parameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu.
IMPORTANT: The current parameter value appears above the highlight parameter. To view the default parameter value, press the UP and DOWN keys simultaneously. To restore the default factory settings, select the application macro “HVAC Default.”
VFD Modes
The VFD has several different modes for configuring, operating, and d iagnosing the VFD. The modes are:
S Standard Display mode ⎯ shows drive status information and
operates the drive
S Parameters mode edits parameter values individually S Start--up Assistant mode guides the start up and
configuration
S Changed Parameters mode shows all changed parameters S Drive Parameter Backup mode stores or uploads the
parameters
S Clock Set mode sets the time and date for the drive S I/O Settings mode checks and edits the I/O settings
Standard Display Mode
Use the standard display mode to read information on the drive status and operate the drive. To reach the standard display mode, press EXIT until the LCD display shows status information as described below. See Fig. 42.
The top line of the LCD display shows the basic status information of the drive. The HAND icon indicates that the drive control is local from the control panel. The AUTO icon indicates that the drive is in remote control mode, such as the basic I/O (X1) or field bus.
The arrow icon indicates the drive and motor rotation status. A rotating arrow (clockwise or counterclockwise) indicates that the drive is running and at set point and the shaft direction is forward or reverse. A rotating blinking arrow indicates that the drive is running but not at set point. A stationary arrow indicates that the drive is stopped. For Carrier rooftop units, the correct rotation is counterclockwise.
The upper right corner shows the frequency set point that the drive will maintain.
Using parameter group 34, the middle of the LCD display can be configured to display 3 parameter values. The default display shows parameters 0103 (OUTPUT FREQ) in percentages, 0104 (CURRENT) in amperes, and 0120 (AI1) in milliamperes.
The bottom corners of the LCD display show the functions currently assigned to the two soft keys. The lower middle displays the current time (if configured to show the time).
The first time the drive is powered up, it is in the OFF mode. To switch to local hand--held control and control the drive using the control p anel, press and ho ld the HAND bu tton. Pressing the HAND button switches the drive to hand control while keeping the drive running. Press the AUTO button to switch to remote input control. To start the drive press the HAND or AUTO buttons, to stop the drive press the OFF button.
C08676
Fig. 42 -- Standard Display Example
48/50PD
83
Page 84
APPENDIX B -- VFD INFORMATION (CONT)
To adjust the speed in HAND mode, press the UP or DOWN buttons (the reference changes immediately). The reference can be modified in the local control (HAND) mode, and can be parameterized (using Group 11 reference select) to also allow modification in the remote control mode.
Parameters Mode
The Parameters mode is used to change the parameters on the drive. To change parameters, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2).
5. Use the UP or DOWN keys to change the value of the parameter.
48/50PD
6. Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed.
7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the parameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu.
IMPORTANT: The current parameter value appears above the highlight parameter. To view the default parameter value, press the UP and DOWN keys simultaneously. To restore the default factory settings, select the Carrier application macro.
Start--Up Assistant Mode
To use the Start--Up Assistant, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight ASSISTANTS on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight Commission Drive and press SEL (SOFT KEY 2).
4. The Start--Up Assistant will display the parameters that need to be configured. Select the desired values and press SA VE (SOFT KEY 2) after every change. The process will continue until all the parameters are set. The assistant checks to make sure that entered values are in range.
The assistant is divided into separate tasks. The user can activate the tasks one after the other or independently. The tasks are typically done in this order: Application, References 1 and 2, Start/Stop Control, Protections, Constant Speeds, PID Control, Low Noise Setup, Panel Display, Timed Functions, and Outputs.
Changed Parameters Mode
The Changed Parameters mode is used to view and edit recently changed parameters on the drive. To view the changed parameters, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight CHANGED PAR on the display screen and press ENTER (SOFT KEY 2). A list of the recently changed parameters will be displayed.
3. Use the UP or DOWN keys to highlight the desired parameter group and press EDIT (SOFT KEY 2) to change the parameter if desired.
4. Press EXIT (SOFT KEY 1) to exit the Changed Parameters mode.
Drive Parameter Backup Mode
The drive parameter back up mode is used to export the parameters from one drive to another. The parameters can be uploaded from a VFD to the removable control panel. The control panel can then be transferred to another drive and the parameters downloaded into memory.
Depending on the motor and application, there are two options available. The first option is to download all parameters. This copies both application and motor parameters to the drive from the control panel. This is recommended when using the same application for drives of the same size. This can also be used to create a backup of the parameters group for the drive.
The second option downloads only the application parameters to the drive. This is recommended when using the same application for drives of different sizes. Parameters 9905, 9906, 9907, 9908, 9909, 1605, 1607, 5201, and group 51 parameters and internal motor parameters are not copied.
Upload All Parameters
To upload and store parameters in the control panel from the VFD, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP o r DOWN keys to highlight UPLOAD TO PANEL and press SEL (SOFT KEY 2).
4. The text “Copying Parameters” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1).
5. When the upload is complete, the text “Parameter upload successful” will be displayed.
6. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu.
7. The control panel can now be disconnected from the drive.
Download All Parameters
To download all parameters from the control panel to the VFD, perform the following procedure:
1. Install the control panel with the correct parameters onto the VFD.
2. Select MENU (SOFT KEY 2). The Main menu will be displayed.
3. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight DOWNLOAD TO DRIVE ALL and press SEL (SOFT KEY 2 ).
5. The text “Restoring Parameters” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1).
6. When the download is complete, the text “Parameter download successful” will be displayed.
7. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu.
8. The control panel can now be disconnected from the drive.
84
Page 85
Download Application Parameters
To download application parameters only to the control panel from the VFD, perform the following procedure:
1. Install the control panel with the correct parameters onto the VFD.
2. Select MENU (SOFT KEY 2). The Main menu will be displayed.
3. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2).
4. Use the UP o r DOWN keys to highlight DOWNLOAD APPLICA TION and press SEL (SOFT KEY 2).
5. The text “Downloading Parameters (partial)” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1).
6. When the download is complete, the text “Parameter download successful” will be displayed.
7. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu.
8. The control panel can now be disconnected from the drive.
Clock Set Mode
The clock set mode is used for setting the date and time for the internal clock of the VFD. In order to use the timer functions of the VFD control, the internal clock must be set. The date is used to determine weekdays and is visible in the fault logs.
To set the clock, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight CLOCK SET on the display screen and press ENTER (SOFT KEY 2). The clock set parameter list will be displayed.
3. Use the UP or DOWN keys to highlight CLOCK VISIBILITY and press SEL (SOFT KEY 2). This parameter is used to display or hide the clock on the screen. Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
4. Use the UP or DOWN keys to highlight SET TIME and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the hours and minutes. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
5. Use the UP or DOWN keys to highlight TIME FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
6. Use the UP or DOWN keys to highlight SET DATE and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the day, month, and year. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
7. Use the UP or DOWN keys to highlight DATE FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
8. Press EXIT (SOFT KEY 1) twice to return to the main menu.
I/O Settings Mode
The I/O Settings mode is used for viewing and editing the I/O settings.
To configure the I/O settings, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight I/O SETTINGS on the display screen and press ENTER (SOFT KEY 2). The I/O Settings parameter list will be displayed.
3. Use the UP or DOWN keys to highlight the desired I/O setting and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to select the parameter to view. Press OK (SOFT KEY 2).
5. Use the UP or DOWN keys to change the parameter setting. Press SAVE (SOFT KEY 2) to save the configuration. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed.
6. Press EXIT (SOFT KEY 1) twice to return to the main menu.
VFD Diagnostics
The drive detects error situations and reports them using:
S Green and red LEDs on the body of the drive (located under the
keypad)
S Status LED on the control panel S Control panel display S The Fault Word and Alarm Word parameter bits (parameters
0305 to 0309)
The form of the display depends on the severity of the error. The user can specify the severity for many errors by directing the drive to ignore the error situation, report the situation as an alarm, or report the situation as a fault.
Faults (Red LED Lit)
The VFD signals that it has detected a severe error, or fault, by:
S Enabling the red LED on the drive (LED is either steady or
flashing)
S Setting an appropriate bit in a Fault Word parameter (0305 to
0307)
S Overriding the control panel display with the display of a fault
code
S Stopping the motor (if it was on) S Sets an appropriate bit in Fault Word parameter 0305 -- 0307.
The fault code on the control panel display is temporary. Pressing the MENU, ENTER, UP button or DOWN buttons removes the fault message. The message reappears after a few seconds if the control panel is not touched and the fault is still active.
Alarms (Green LED Flashing)
For less severe errors, called alarms, the diagnostic display is advisory. For these situations, the drive is simply reporting that it had detected something unusual. In these situations, the drive:
S Flashes the green LED on the drive (does not apply to alarms
that arise from control panel operation errors)
S Sets an appropriate bit in an Alarm Word parameter (0308 or
0309)
S Overrides the control panel display with the display of an alarm
code and/or name
Alarm messages disappear from the control panel display after a few seconds. The message returns periodically as long as the alarm condition exists.
Correcting Faults
The recommended corrective action for faults is shown in the Fault Listing Table 41. The VFD can also be reset to remove the fault. If an external source for a start command is selected and is active, the VFD may start immediately after fault reset.
To reset a fault indicated by a flashing red LED, turn off the power for 5 minutes. To reset a fault indicated by a red LED (not flashing), p ress RESET from the control panel or turn off the power for 5 minutes. Depending on the value of parameter 1604 (FAULT RESET SELECT), digital input or serial communication could also be used to reset the drive. When the fault has been corrected, the motor can be started.
48/50PD
85
Page 86
History
For reference, the last three fault codes are stored into parameters 0401, 0412, 0413. For the most recent fault (identified by parameter 0401), the drive stores additional data (in parameters 0402 through 0411) to aid in troubleshooting a problem. For example, a parameter 0404 stores the motor speed at the time of the fault. To clear the fault history (all of Group 04, Fault History parameters), follow these steps:
1. In the control panel, Parameters mode, select parameter
0401.
2. Press EDIT.
3. Press the UP and DOWN buttons simultaneously.
4. Press SAVE.
Correcting Alarms
To correct alarms, first determine if the Alarm requires any corrective action (action is not always required). Use Table 42 to find and address the root cause of the problem.
If diagnostics troubleshooting has determined that the drive is defective during the warranty period, contact ABB Automation
48/50PD
Inc., at 1--800-- 435--7365, option 4, option 3. A qualified technician will review the problem with the caller and make a determination regarding how to proceed. This may involve dispatching a designated service station (DSS) representative from an authorized station, dispatching a replacement unit, or advising return for repair.
VFD Maintenance
If installed in an appropriate environment, the VFD requires very little maintenance.
Table 43 lists the routine maintenance intervals recommended by Carrier.
Heat Sink
The heat sink fins accumulate dust from the cooling air. Since a dusty sink is less efficient at cooling the drive, overtemperature faults become more likely. In a normal environment check the heat sink annually, in a dusty environment check more often.
Check the heat sink as follows (when necessary):
1. Remove power from drive.
2. Remove the cooling fan.
3. Blow clean compressed air (not humid) from bottom to top and simultaneously use a vacuum cleaner at the air outlet to trap the dust. If there a risk of the dust entering adjoining equipment, perform the cleaning in another room.
4. Replace the cooling fan.
5. Restore power.
86
Page 87
APPENDIX B - VFD INFORMATION (CONT)
Table 41 — FAULT CODES
FAULT CODE
10
11 ID RUN FAIL The motor ID run was not completed successfully. Check motor connections.
12
13 RESERVED Not used.
14 EXT FAULT 1 Digital input defined to report first external fault is active. See parameter 3003 EXTERNAL FAULT 1.
15 EXT FAULT 2 Digital input defined to report second external fault is active. See parameter 3004 EXTERNAL FAULT 2.
16
17
18 THERM FAIL Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted. Contact Carrier.
19
20 OPEX PWR Internal fault. Low voltage condition detected on the OINT board. Contact Carrier.
21 CURR MEAS Internal fault. Current measurement is out of range. Contact Carrier.
22 SUPPLY PHASE Ripple voltage in the DC link is too high. Check for missing main phase or blown fuse.
23 RESERVED Not used.
24
25 RESERVED Not used.
26 DRIVE ID Internal fault. Configuration block drive ID is not valid.
27 CONFIG FILE Internal configuration file has an error. Contact Carrier.
28
29 EFB CON FILE Error in reading the configuration file for the field bus adapter.
30 FORCE TRIP Faulttripforcedbythefieldbus.Seethefieldbusreferenceliterature.
31 EFB 1 Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
32 EFB 2 Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
33 EFB 3 Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
34
35 OUTP WIRING Error in power wiring suspected. Check that input power wired to drive output. Check for ground faults.
101--- 105 SYSTEM ERROR Error internal to the drive. Contact Carrier and report the error number.
201--- 206 SYSTEM ERROR Error internal to the drive. Contact Carrier and report the error number.
FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
1
2
3
4 SHORT CIRC Fault current. Check for short---circuit in the motor cable(s) or motor or supply disturbances.
5 OVERLOAD Inverter overload condition. The drive output current exceeds the ratings.
6
7
8
9
OVERCURRENT
DC OVERVOLT
DEV OVERTEMP
DC OVERVOLT
Al1 LOSS
Al2 LOSS
MOT OVERTEMP
PAN E L L OSS
MOTOR STALL
EARTH FAULT
UNDERLOAD
OPEX LINK
OVERSPEED
SERIAL 1 ERR
MOTOR PHASE
Output current is excessive. Check for excessive motor load, insufficient acceleration time (parameters 2202 ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections.
Intermediate circuit DC voltage is excessive. Check for static or transient over voltages in the input power supply, insufficient deceleration time (parameters 2203 DECELER TIME 1, default 30 seconds), or undersized brake chopper (if present).
Drive heat sink is overheated. Temperature is at or above 115_C (239_F). Check for fan failure, obstructions in the air flow,dirtordustcoatingontheheatsink,excessiveambienttemperature,orexcessivemotorload.
Intermediate circuit DC voltage is not sufficient. Check for missing phase in the input power supply, blown fuse, or under voltage on main circuit.
Analog input 1 loss. Analog input value is less than AI1 FLT LIMIT (3021). Check source and connection for analog input and parameter settings for AI1 FLT LIMIT (3021) and 3001 AI<MIN FUNCTION.
Analog input 2 loss. Analog input value is less than AI2 FLT LIMIT (3022). Check source and connection for analog input and parameter settings for AI2 FLT LIMIT (3022) and 3001 AI<MIN FUNCTION.
Motor is too hot, as estimated by the drive. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
Panel communication is lost and either drive is in local control mode (the control panel displays LOC), or drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or reference from the control panel. To correct check the communication lines and connections. Check parameter 3002 PANEL COMM ERROR, parameters in Group 10: Command Inputs and Group 11:Reference Select (if drive operation is REM).
Motor or process stall. Motor is operating in the stall region. Check for excessive load or insufficient motor power. Check parameters 3010 through 3012.
The load on the input power system is out of balance. Check for faults in the motor or motor cable. Verify that motor cable does not exceed maximum specified length.
Motor load is lower than expected. Check for disconnected load. Check parameters 3013 UNDERLOAD FUNCTION through 3015 UNDERLOAD CURVE.
Internal fault. A communication --- related problem has been detected between the OMIO and OINT boards. Contact Carrier.
Motor speed is greater than 120% of the larger (in magnitude) of 2001 MINIMUM SPEED or 2002 MAXIMUM SPEED parameters. Check parameter settings for 2001 and 2002. Check adequacy of motor braking torque. Check applicability of torque control. Check brake chopper and resistor.
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line.
Fault in the motor circuit. One of the motor phases is lost. Check for motor fault, motor cable fault, thermal relay fault , or internal fault.
48/50PD
87
Page 88
APPENDIX B - VFD INFORMATION (CONT)
Table 41 — FAUL T CODES (cont)
FAULT CODE
1000
1001 PAR PFA R E FNG Parameter values are inconsistent. Check that 2007 MINIMUM FREQ is negative, when 8123 PFA ENABLE is active.
1002
1003
1004
1005
48/50PD
1006
1007
1008
1009
1010 OVERRIDE/PFA
FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
Parameter values are inconsistent. Check for any of the following: 2001 MINIMUM SPEED > 2002 MAXIMUM SPEED 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ
PAR H Z RP M
PAR P FA IO C NF
PAR A I S C AL E
PAR A O S C AL E
PAR P C U 2
PAR E X T RO
PAR F B U S
PAR P FA MO D E
PAR P C U 1
CONFLICT
2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: --- 128/+128 2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: --- 128/+128 2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: --- 128/+128 2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: --- 128/+128
Parameter values are inconsistent. The number of programmed PFA relays does not match with Interlock configuration, when 8123 PFA ENABLE is active. Check consistency of RELAY OUTPUT parameters 1401 through 1403, and 1410 through 1412. Check 8117 NR OF AUX MOTORS, 8118 AUTOCHANGE INTERV, and 8120 INTERLOCKS.
Parameter values are inconsistent. Check that parameter 1301 AI 1 MIN > 1302 AI 1 MAX and that parameter 1304 AI 2 MIN > 1305 AI 2 MAX.
Parameter values are inconsistent. Check that parameter 1504 AO 1 MIN > 1505 AO 1 MAX and that parameter 1510 AO 2 MIN > 1511 AO 2 MAX.
Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check the following parameters:
1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 2.6 Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW) or PN = 746 * 9909 MOTOR NOM POWER (if units are HP, e.g., in US)
Parameter values are inconsistent. Check the extension relay module for connection and 1410 through 1412 RELAY OUTPUTS 4 through 6 have non---zero values.
Parameter values are inconsistent. Check that a parameter is set for field bus control (e.g., 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL = 0.
Parameter values are inconsistent. The 9904 MOTOR CTRL MODE must = 3 (SCALAR SPEED) when 8123 PFA ENABLE activated.
Parameter values for power control are inconsistent or improper motor nominal frequency or speed. Check for both of the following: 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16
0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor poles) < 0.992
Override mode is enabled and PFA is activated at the same time. This cannot be done because PFA interlocks cannot be observed in the override mode.
88
Page 89
APPENDIX B - VFD INFORMATION (CONT)
Table 42 — ALARM CODES
ALARM
CODE
2001 --- Reserved
2002 --- Reserved
2003 --- Reserved
2004 DIR LOCK
2005 I/O COMM
2006 Al 1 LOSS
2007 Al 2 LOSS
2008 PAN E L L OS S
2009 --- Reserved
2010 MOT OVERTEMP
2011 UNDERLOAD
2012 MOTOR STALL Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near.
2013* AU TORESET
2014 AU TOCHAN GE
2015 PFA INTERLOCK
2016 --- Reserved
2017* OFF BUTTON This alarm indicates that the OFF button has been pressed.
2018 PID SLEEP
2019 ID RUN The VFD is performing an ID run.
2020 OVERRIDE Override mode is activated.
2021
2022
2023 EMERGENCY STOP Emergency stop is activated.
* This alarm is not indicated by a relay output, even when the relay output is configured to indicate alarm conditions, parameter 1401 RELAY OUTPUT = 5 (ALARM)or16 (FLT/ALARM).
ALARM NAME
IN PANEL
START ENABLE 1
MISSING
START ENABLE 2
MISSING
DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
The change in direction being attempted is not allowed. Do not attempt to change the direction of motor rotation, or Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe).
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line.
Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections. Check the parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault operation (3001).
Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections. Check parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation (3001).
Panel communication is lost and either the VFD is in local control mode (the control panel displays HAND), or the VFD is in remote control mode (AUTO) and is parameterized to accept start/stop, direction or reference from the control panel. To correct, check the communication lines and connections, Parameter 3002 PANEL LOSS, and parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM).
Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a Motor Overload fault trip may be near. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near. Check that the motor and drive ratings match (motor is NOT undersized for the drive). Check the settings on parameters 3013 to
3015.
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To control automatic reset, use parameter group 31 (AUTOMATIC RESET).
This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81 (PFA) and the Pump Alternation macro.
This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when Autochange is used), or a speed regulated motor (when Autochange is not used).
This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122 through 4126.
This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use parameter 1608. To correct, check the digital input configuration and the communication settings.
This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use parameter1609. To correct, check the digital input configuration and the communication settings.
48/50PD
Table 43 — MAINTENANCE INTERVALS
MAINTENANCE INTERVAL
Heat sink temperature check and cleaning
Main cooling fan replacement Every five years
HVAC Control panel battery change Every ten years
Every 6 to 12 months (depending on the dustiness of the environment)
89
Page 90
APPENDIX B - VFD INFORMATION (CONT)
Main Fan Replacement
The main cooling fan of the VFD has a life span of about 60,000 operating hours at maximum rated operating temperature and drive load. The expected life span doubles for each 18 F drop in the fan temperature (fan temperature is a function of ambient temperatures and drive loads).
Fan failure can be predicted by the increasing noise from fan bearings and the gradual rise in the heat sink temperature in spite of heat sink cleaning. If the drive is operated in a critical part of a process, fan replacement is recommended once these symptoms start appearing. Replacement fans are available from Carrier.
To replace the main fan for frame sizes R1 through R2, perform the following (see Main Fan Replacement figure):
1. Remove power from drive.
2. Remove drive cover.
3. For frame sizes R1 and R2, press together the retaining clips on the fan cover and lift.
4. Disconnect the fan cable.
48/50PD
5. Install the new fan by reversing Steps 2 to 4.
6. Restore power.
Control Panel Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the display window.
Battery Replacement
A battery is only used in assistant control panels that have the clock function available and enabled. The battery keeps the clock operating in memory during power interruptions. The expected life for the battery is greater than ten years. To remove the battery, use a coin to rotate the battery holder on the back of the control panel. Replace the battery with type CR2032.
3
3
4
2
C08681
Fig. 43 -- Main Fan Replacement
(Frame Sizes R1--R2)
90
Page 91
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
APPENDIX C -- START--UP DATA
Table 44 — Fan Performance - 48PDD05 Vertical Units
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
504 0.16 613 0.23 710 0.31 798 0.40 881 0.49 527 0.19 632 0.27 725 0.35 810 0.44 890 0.54 551 0.22 652 0.31 741 0.40 823 0.49 900 0.59 576 0.26 673 0.35 759 0.44 838 0.54 912 0.65 600 0.30 694 0.40 777 0.50 854 0.60 926 0.71 626 0.35 716 0.45 797 0.55 871 0.66 941 0.78 651 0.40 739 0.51 817 0.62 889 0.73 957 0.85 677 0.46 762 0.57 838 0.69 908 0.80 974 0.93 703 0.52 785 0.64 859 0.76 927 0.88 992 1.01
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
LEGEND Bhp -- Brake Horsepower
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
957 0.59 1030 0.70 1098 0.80 1163 0.91 1225 1.03 964 0.64 1035 0.75 1102 0.86 1166 0.98 1227 1.10 973 0.70 1042 0.81 1107 0.92 1170 1.04 1231 1.17 983 0.76 1050 0.87 1114 0.99 1176 1.12 1235 1.24
994 0.82 1060 0.94 1122 1.06 1183 1.19 1241 1.32 1007 0.89 1071 1.02 1132 1.14 1191 1.27 1248 1.41 1021 0.97 1083 1.10 1143 1.23 1200 1.36 1256 1.50 1037 1.05 1097 1.18 1155 1.32 1211 1.45 1266 1.60 1053 1.14 1111 1.27 1168 1.41 1223 1.55 1276 1.70
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
Table 45 — Fan Performance - 48PDE05 Vertical Units
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
509 0.16 618 0.24 714 0.32 802 0.41 884 0.50
533 0.19 637 0.27 730 0.36 814 0.45 894 0.55
557 0.23 658 0.31 746 0.40 828 0.50 905 0.60
582 0.27 679 0.36 764 0.45 843 0.55 917 0.66
608 0.31 701 0.40 783 0.50 860 0.61 931 0.72
634 0.36 723 0.46 803 0.56 877 0.67 947 0.79
660 0.41 747 0.52 824 0.63 896 0.74 963 0.86
686 0.47 770 0.58 846 0.70 915 0.82 981 0.94
713 0.54 795 0.66 868 0.78 935 0.90 999 1.02
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
961 0.60 1033 0.70 1101 0.81 1166 0.92 1228 1.03
968 0.65 1039 0.76 1106 0.87 1169 0.98 1230 1.10
977 0.70 1046 0.82 1111 0.93 1174 1.05 1234 1.17
987 0.77 1054 0.88 1118 1.00 1180 1.12 1239 1.25
999 0.83 1065 0.95 1127 1.07 1187 1.20 1245 1.33 1013 0.90 1076 1.03 1137 1.15 1196 1.28 1253 1.42 1027 0.98 1089 1.11 1148 1.24 1206 1.37 1261 1.51 1043 1.06 1103 1.20 1161 1.33 1217 1.47 1271 1.61 1060 1.16 1118 1.29 1175 1.43 1229 1.57 1282 1.72
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
48/50PD
91
Page 92
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
Table 46 — Fan Performance - 48PDF05 Vertical Units
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
520 0.17 628 0.24 723 0.33 811 0.41 892 0.51
545 0.20 648 0.28 739 0.37 823 0.46 902 0.56
570 0.24 668 0.32 756 0.41 837 0.51 913 0.61
596 0.28 691 0.37 775 0.46 853 0.56 927 0.67
623 0.32 714 0.42 795 0.52 870 0.62 942 0.73
650 0.37 737 0.48 816 0.58 889 0.69 958 0.80
677 0.43 762 0.54 838 0.65 909 0.76 976 0.88
705 0.50 787 0.61 861 0.72 929 0.84 994 0.97
734 0.57 813 0.68 884 0.80 951 0.93 1014 1.06
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900
48/50PD
2000
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
968 0.61 1040 0.71 1108 0.82 1172 0.93 1233 1.04
976 0.66 1046 0.77 1112 0.88 1176 1.00 1237 1.11
985 0.72 1054 0.83 1119 0.95 1181 1.07 1241 1.19
996 0.78 1063 0.90 1127 1.02 1188 1.14 1247 1.27 1009 0.85 1074 0.97 1136 1.09 1196 1.22 1254 1.35 1024 0.92 1087 1.05 1147 1.17 1205 1.31 1262 1.44 1039 1.00 1100 1.13 1159 1.26 1216 1.40 1272 1.54 1056 1.09 1116 1.22 1173 1.36 1229 1.50 1283 1.64 1074 1.19 1132 1.32 1188 1.46 1242 1.61 1295 1.75
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
Table 47 — Fan Performance - 48PDD06 Vertical Units
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
593 0.27 688 0.37 773 0.46 851 0.56 925 0.67
620 0.32 711 0.42 793 0.52 868 0.62 939 0.73
646 0.37 734 0.47 813 0.58 886 0.69 955 0.80
673 0.43 758 0.53 835 0.64 905 0.76 972 0.88
700 0.49 783 0.60 857 0.72 925 0.84 990 0.96
728 0.56 807 0.68 879 0.80 946 0.92 1009 1.05
755 0.63 833 0.76 903 0.88 968 1.01 1029 1.14
783 0.71 858 0.84 926 0.97 990 1.11 1050 1.24
811 0.80 884 0.94 950 1.07 1012 1.21 1071 1.35
840 0.90 910 1.04 975 1.18 1035 1.33 1092 1.47
868 1.00 937 1.15 1000 1.30 1059 1.45 1115 1.60
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
995 0.78 1061 0.89 1125 1.01 1186 1.14 1245 1.26 1007 0.85 1072 0.96 1134 1.09 1194 1.22 1252 1.35 1021 0.92 1084 1.04 1145 1.17 1203 1.30 1260 1.44 1036 1.00 1098 1.13 1157 1.26 1214 1.39 1269 1.53 1053 1.08 1112 1.22 1170 1.35 1226 1.49 1280 1.63 1070 1.18 1128 1.31 1184 1.45 1238 1.60 1291 1.74 1088 1.28 1145 1.42 1199 1.56 1253 1.71 1304 1.86 1107 1.38 1162 1.53 1216 1.68 1268 1.83 1318 1.98 1127 1.50 1181 1.65 1233 1.80 1284 1.95 1333 2.11 1147 1.62 1200 1.77 1251 1.93 1300 2.09 1349 2.25 1168 1.75 1220 1.91 1270 2.07 1318 2.23 1365 2.40
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
92
Page 93
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
Table 48 — Fan Performance - 48PDE06 Vertical Units
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
607 0.29 700 0.38 784 0.47 861 0.57 934 0.68
634 0.33 724 0.43 804 0.53 879 0.64 950 0.75
662 0.39 748 0.49 826 0.60 898 0.71 967 0.82
690 0.45 773 0.55 848 0.67 918 0.78 985 0.90
719 0.51 799 0.63 872 0.74 940 0.86 1004 0.98
748 0.59 825 0.70 896 0.83 962 0.95 1024 1.08
777 0.67 852 0.79 920 0.92 985 1.05 1045 1.18
807 0.75 879 0.88 946 1.01 1008 1.15 1067 1.29
837 0.85 907 0.98 971 1.12 1032 1.26 1090 1.40
867 0.95 935 1.09 998 1.24 1057 1.38 1113 1.53
897 1.06 963 1.21 1024 1.36 1082 1.51 1137 1.66
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1004 0.79 1070 0.91 1133 1.03 1194 1.15 1253 1.28 1017 0.86 1081 0.98 1143 1.11 1203 1.24 1260 1.37 1032 0.94 1094 1.06 1155 1.19 1213 1.32 1269 1.46 1048 1.02 1109 1.15 1168 1.28 1224 1.42 1279 1.56 1066 1.11 1125 1.24 1182 1.38 1237 1.52 1291 1.66 1084 1.21 1142 1.35 1197 1.49 1251 1.63 1304 1.78 1104 1.31 1160 1.45 1214 1.60 1267 1.75 1318 1.90 1124 1.43 1179 1.57 1231 1.72 1283 1.87 1333 2.03 1145 1.55 1198 1.70 1250 1.85 1300 2.01 1349 2.17 1167 1.68 1219 1.83 1269 1.99 1318 2.15 1366 2.31 1189 1.82 1240 1.97 1290 2.14 1337 2.30
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
Table 49 — Fan Performance - 48PDF06 Vertical Units
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
620 0.30 711 0.39 794 0.49 871 0.59 944 0.70
648 0.35 736 0.45 816 0.55 890 0.65 960 0.76
677 0.40 762 0.51 838 0.61 910 0.72 978 0.84
707 0.47 788 0.58 862 0.69 931 0.80 997 0.92
737 0.54 815 0.65 887 0.77 954 0.89 1017 1.01
767 0.61 843 0.73 912 0.85 977 0.98 1039 1.11
798 0.70 871 0.82 938 0.95 1001 1.08 1061 1.21
829 0.79 900 0.92 965 1.05 1026 1.19 1084 1.33
861 0.89 929 1.03 992 1.17 1052 1.31 1108 1.45
893 1.00 959 1.15 1020 1.29 1078 1.43 1133 1.58
925 1.12 989 1.27 1048 1.42 1105 1.57 1158 1.72
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
48/50PD
AIRFLOW
(CFM)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1013 0.81 1078 0.92 1141 1.05 1202 1.17 1260 1.30 1027 0.88 1091 1.00 1152 1.13 1211 1.25 1269 1.39 1043 0.96 1105 1.08 1165 1.21 1222 1.35 1278 1.48 1060 1.05 1120 1.18 1179 1.31 1235 1.44 1290 1.59 1078 1.14 1137 1.27 1194 1.41 1249 1.55 1302 1.70 1098 1.24 1155 1.38 1210 1.52 1264 1.67 1316 1.81 1119 1.35 1174 1.49 1228 1.64 1280 1.79 1331 1.94 1140 1.47 1195 1.62 1247 1.77 1298 1.92 1348 2.08 1163 1.60 1216 1.75 1267 1.90 1317 2.06 1365 2.22 1186 1.73 1238 1.89 1288 2.05 1336 2.21 1384 2.37 1210 1.88 1261 2.04 1309 2.20 1357 2.37
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
93
Page 94
Table 50 — Fan Performance - 48PDD05 Horizontal Units
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900
48/50PD
2000
LEGEND Bhp -- Brake Horsepower
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
436 0.12 559 0.19 661 0.27 753 0.35 839 0.45
456 0.14 574 0.22 673 0.30 762 0.39 845 0.49
477 0.17 592 0.25 687 0.34 774 0.43 853 0.53
500 0.20 611 0.29 703 0.38 787 0.48 864 0.58
523 0.24 631 0.33 721 0.43 801 0.53 877 0.63
548 0.28 652 0.38 739 0.48 818 0.58 891 0.69
573 0.32 674 0.43 759 0.54 835 0.64 906 0.76
600 0.37 697 0.48 779 0.60 854 0.71 923 0.83
627 0.43 720 0.55 801 0.67 873 0.79
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
918 0.54 993 0.64 1063 0.75 1130 0.86 1193 0.97
922 0.58 995 0.69 1064 0.80 1130 0.91 1193 1.03
929 0.63 1000 0.74 1067 0.85 1132 0.97 1194 1.09
937 0.69 1006 0.80
947 0.74 1015 0.86 1079 0.98 1141 1.10 1201 1.23
959 0.81 1025 0.93 1088 1.05 1148 1.18 1207 1.31
973 0.88 1037 1.00 1098 1.13 1157 1.26 1214 1.39
988 0.95 1050 1.08 1110 1.21 1168 1.35 1223 1.48 1004 1.04 1065 1.17 1123 1.30 1179 1.44 1234 1.58
__ High--Range Motor/Drive Required
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1072 0.91 1136 1.03 1196 1.16
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
941 0.91
Table 51 — Fan Performance -- 48PDE05 Horizontal Units
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
LEGEND Bhp -- Brake Horsepower
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
443 0.12 564 0.20 666 0.27 758 0.36 842 0.45
463 0.15 580 0.22 678 0.31 767 0.40 849 0.49
485 0.17 598 0.26 693 0.34 778 0.44 858 0.54
508 0.21 617 0.30 709 0.39 792 0.48 869 0.59
532 0.24 638 0.34 727 0.43 807 0.54 882 0.64
558 0.28 660 0.39 746 0.49 824 0.59 896 0.70
584 0.33 682 0.44 766 0.55 842 0.66 912 0.77
611 0.38 706 0.50 788 0.61 861 0.72 930 0.84
639 0.44 731 0.56 810 0.68 882 0.80
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
922 0.55 996 0.65 1066 0.75 1133 0.86 1196 0.97
926 0.59 999 0.69 1068 0.80 1133 0.92 1196 1.03
933 0.64 1004 0.75
942 0.69 1011 0.80 1077 0.92 1140 1.04 1200 1.17
952 0.75 1020 0.87 1084 0.99 1146 1.11 1205 1.24
965 0.82 1030 0.94 1093 1.06 1153 1.19 1211 1.32
979 0.89 1043 1.01 1104 1.14 1163 1.27 1220 1.41
995 0.97 1057 1.09 1116 1.22 1174 1.36 1229 1.50 1012 1.05 1072 1.18 1130 1.32 1186 1.46 1240 1.60
__ High--Range Motor/Drive Required
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1071 0.86 1136 0.98 1197 1.10
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
948 0.92
94
Page 95
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
Table 52 — Fan Performance - 48PDF05 Horizontal Units
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
456 0.13 574 0.20 675 0.28 766 0.37 850 0.46
477 0.16 591 0.23 688 0.32 776 0.41 857 0.50
500 0.18 610 0.27 703 0.36 788 0.45 867 0.55
524 0.22 630 0.31 720 0.40 802 0.50 879 0.60
550 0.26 652 0.35 739 0.45 819 0.55 893 0.66
576 0.30 675 0.40 759 0.50 836 0.61 908 0.72
604 0.35 699 0.46 781 0.57 856 0.68 925 0.79
633 0.41 724 0.52 804 0.63 876 0.75
662 0.47 750 0.59 828 0.71 898 0.83 964 0.95
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
944 0.87
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
LEGEND Bhp -- Brake Horsepower
High Range Motor/Drive Required
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
929 0.56 1003 0.66 1073 0.76 1139 0.87 1202 0.98
934 0.60 1006 0.71 1075 0.82 1140 0.93 1202 1.05
941 0.65 1012 0.76
1079 0.87 1143 0.99 1204 1.11
951 0.71 1020 0.82 1085 0.94 1148 1.06 1208 1.18
963 0.77 1029 0.89 1093 1.01 1155 1.13 1214 1.26
976 0.84 1041 0.96 1103 1.08 1163 1.21 1221 1.34
991 0.91 1054 1.04 1115 1.16 1174 1.30 1230 1.43 1008 0.99 1070 1.12 1129 1.25 1186 1.39 1241 1.53 1026 1.08 1086 1.21 1144 1.35 1199 1.49
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
1253 1.63
Table 53 — Fan Performance - 48PDD06 Horizontal Units
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
521 0.22 628 0.31 718 0.40  800 0.49 877 0.60
546 0.25 649 0.35 737 0.45  816 0.55 890 0.65
572 0.30 671 0.40 757 0.50  834 0.61 906 0.72
599 0.35 695 0.45 777 0.56  852 0.67 922 0.79
627 0.40 719 0.51 799 0.63  872 0.74 940 0.86
655 0.46 745 0.58 822 0.70  893 0.82 959 0.94
684 0.53 771 0.66 846 0.78  915 0.91 979 1.03
714 0.61 797 0.74 871 0.87  938 1.00 1001 1.13
744 0.69 824 0.83 896 0.96  961 1.10 1022 1.24
775 0.78 852 0.92 922 1.06  985 1.21 1045 1.35
806 0.88 880 1.03 948 1.18 1010 1.32 1069 1.47
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
48/50PD
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
949 0.70 1018 0.82 1083 0.93 1146 1.05 1207 1.18
961 0.77 1027 0.88 1091 1.00 1153 1.13 1212 1.26
974 0.83 1039 0.95 1101 1.08 1161 1.21 1219 1.34
988 0.91 1052 1.03 1112 1.16 1171 1.29 1227 1.43
1004 0.99 1066 1.11 1125 1.25 1182 1.38 1238 1.52 1022 1.07 1082 1.20 1139 1.34 1195 1.48 1249 1.62 1040 1.17 1099 1.30 1155 1.44 1209 1.59 1262 1.73 1060 1.27 1117 1.41 1172 1.55 1225 1.70 1277 1.85 1081 1.38 1136 1.52 1190 1.67 1242 1.82 1292 1.98 1102 1.50 1156 1.65 1209 1.80 1259 1.96 1309 2.12 1124 1.62 1177 1.78 1228 1.94 1278 2.10 1326 2.26
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
95
Page 96
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
Table 54 — Fan Performance - 48PDE06 Horizontal Units
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
536 0.23 640 0.32 729 0.41 811 0.51 887 0.61 563 0.27 663 0.36 749 0.46 828 0.56 901 0.67 590 0.31 686 0.42 770 0.52 846 0.62 917 0.74 619 0.37 711 0.47 792 0.58 866 0.69 935 0.81 648 0.43 737 0.54 816 0.65 887 0.77 954 0.89 678 0.49 764 0.61 840 0.73 909 0.85 975 0.98 709 0.56 792 0.69 865 0.81 933 0.94 996 1.07 740 0.65 820 0.78 891 0.91 957 1.04 1019 1.17 772 0.73 849 0.87 918 1.01 982 1.14 1042 1.28 804 0.83 879 0.97 946 1.12 1008 1.26 1066 1.40 837 0.94 909 1.09 974 1.24 1034 1.38 1092 1.53
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000
48/50PD
2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
958 0.72 1027 0.83 1092 0.95 1154 1.07 1214 1.20 971 0.78 1037 0.90 1101 1.02 1162 1.15 1221 1.28
985 0.85 1049 0.97 1111 1.10 1171 1.23 1228 1.36 1001 0.93 1063 1.05 1124 1.18 1182 1.32 1238 1.45 1018 1.01 1079 1.14 1138 1.27 1194 1.41 1249 1.55 1036 1.10 1096 1.24 1153 1.37 1208 1.51 1262 1.66 1056 1.20 1114 1.34 1170 1.48 1224 1.63 1276 1.78 1077 1.31 1134 1.45 1188 1.60 1241 1.75 1292 1.90 1099 1.43 1154 1.57 1207 1.72 1259 1.88 1309 2.03 1122 1.55 1176 1.70 1228 1.86 1278 2.02 1327 2.18 1146 1.69 1198 1.84 1249 2.00 1298 2.16 1346 2.33
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
Table 55 — Fan Performance - 48PDF06 Horizontal Units
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
551 0.24 653 0.33 741 0.42 821 0.52 896 0.62
579 0.28 676 0.38 761 0.48 839 0.58 912 0.69
608 0.33 701 0.43 783 0.54 858 0.64 929 0.76
638 0.39 727 0.49 807 0.60 879 0.71 948 0.83
668 0.45 755 0.56 831 0.68 902 0.79 968 0.91
700 0.52 783 0.64 857 0.76 925 0.88 990 1.01
732 0.60 812 0.72 884 0.85 950 0.97 1013 1.11
765 0.68 842 0.81 912 0.95 976 1.08 1037 1.21
799 0.78 873 0.92 940 1.05 1002 1.19 1062 1.33
833 0.88 904 1.03 969 1.17 1030 1.31 1087 1.46
867 1.00 936 1.15 999 1.30 1058 1.44 1114 1.60
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
968 0.73 1035 0.85 1100 0.97 1162 1.09 1222 1.21
981 0.80 1047 0.92 1110 1.04 1171 1.16 1229 1.29
996 0.87 1060 0.99 1121 1.12 1181 1.25 1238 1.38 1013 0.95 1075 1.08 1135 1.21 1193 1.34 1248 1.48 1031 1.04 1092 1.17 1150 1.30 1206 1.44 1261 1.58 1051 1.14 1110 1.27 1166 1.41 1221 1.55 1275 1.69 1072 1.24 1129 1.38 1185 1.52 1238 1.67 1290 1.82 1094 1.35 1150 1.50 1204 1.64 1256 1.79 1307 1.95 1118 1.48 1172 1.62 1225 1.77 1275 1.93 1325 2.09 1142 1.61 1195 1.76 1246 1.92 1296 2.07 1344 2.24 1168 1.75 1219 1.91 1269 2.07 1317 2.23 1365 2.40
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
96
Page 97
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
Table 56 — Fan Performance - 50PD05 Vertical Units
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
492 0.15 604 0.22 701 0.31 790 0.39 873 0.49 513 0.18 620 0.26 714 0.34 800 0.43 880 0.53 534 0.21 638 0.29 729 0.38 812 0.48 889 0.58 557 0.24 657 0.33 745 0.43 825 0.53 900 0.63 580 0.28 677 0.38 762 0.48 839 0.58 912 0.69 603 0.33 697 0.43 779 0.53 855 0.64 926 0.75 627 0.38 718 0.48 798 0.59 871 0.70 940 0.82 651 0.43 739 0.54 817 0.65 889 0.77 956 0.89 675 0.49 761 0.61 837 0.72 907 0.85 972 0.97
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
LEGEND Bhp -- Brake Horsepower
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
950 0.58 1023 0.69 1092 0.79 1157 0.90 1219 1.02 955 0.63 1027 0.74 1094 0.85 1158 0.96 1220 1.08 962 0.68 1032 0.79 1098 0.91 1161 1.03 1222 1.15 971 0.74 1039 0.85 1103 0.97 1165 1.09 1225 1.22 981 0.80 1047 0.92 1110 1.04 1171 1.17 1229 1.30
993 0.87 1057 0.99 1118 1.11 1178 1.24 1235 1.38 1005 0.94 1068 1.06 1128 1.19 1186 1.33 1242 1.46 1019 1.02 1080 1.14 1139 1.28 1196 1.41 1251 1.56 1034 1.10 1094 1.23 1151 1.37 1206 1.51 1260 1.65
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
Table 57 — Fan Performance -- 50PD06 Vertical Units
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
568 0.25 667 0.34 753 0.44 833 0.54 908 0.64 592 0.29 687 0.39 771 0.49 848 0.59 920 0.70 616 0.34 708 0.44 789 0.54 864 0.65 934 0.76 641 0.39 730 0.50 809 0.61 881 0.72 950 0.83 665 0.45 752 0.56 829 0.67 900 0.79 966 0.91 690 0.51 775 0.63 850 0.75 918 0.87 983 0.99 716 0.57 798 0.70 871 0.82 938 0.95 1001 1.08 742 0.65 821 0.78 892 0.91 958 1.04 1020 1.18 768 0.73 845 0.86 915 1.00 979 1.14 1039 1.28 794 0.81 869 0.96 937 1.10 1000 1.24 1059 1.38 820 0.91 894 1.05 960 1.20 1021 1.35 1079 1.50
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
48/50PD
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
1.2 1.4 1.6 1.8 2.0
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
978 0.75 1046 0.87 1110 0.98 1172 1.11 1231 1.23
989 0.81 1055 0.93 1117 1.05 1178 1.18 1236 1.31 1001 0.88 1065 1.00 1126 1.13 1185 1.26 1242 1.39 1015 0.96 1077 1.08 1136 1.21 1194 1.35 1250 1.48 1029 1.04 1090 1.16 1148 1.30 1204 1.44 1259 1.58 1045 1.12 1104 1.26 1161 1.39 1216 1.53 1269 1.68 1061 1.21 1119 1.35 1174 1.49 1228 1.64 1280 1.79 1078 1.31 1135 1.45 1189 1.60 1241 1.75 1293 1.90 1096 1.42 1151 1.57 1204 1.71 1256 1.87 1306 2.02 1115 1.53 1169 1.68 1221 1.84 1271 1.99 1320 2.15 1134 1.65 1187 1.81 1238 1.97 1287 2.13 1335 2.29
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
97
Page 98
Table 58 — Fan Performance - 50PD05 Horizontal Units
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900 2000
AIRFLOW
(Cfm)
1200 1300 1400 1500 1600 1700 1800 1900
48/50PD
2000
LEGEND Bhp -- Brake Horsepower
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
422 0.11 548 0.19 652 0.26 745 0.35 831 0.44 439 0.13 561 0.21 662 0.29 752 0.38 835 0.47 457 0.16 577 0.24 674 0.33 761 0.42 842 0.51 477 0.19 593 0.27 688 0.37 773 0.46 851 0.56 498 0.22 611 0.31 704 0.41 786 0.51 862 0.61 521 0.25 630 0.35 720 0.46 801 0.56 875 0.67 545 0.29 650 0.40 738 0.51 817 0.62 889 0.73 569 0.34 672 0.45 757 0.57 834 0.68 904 0.80 595 0.39 694 0.51 777 0.63 852 0.75
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
911 0.53  986 0.63 1056 0.74 1123 0.85 1187 0.96 913 0.57  986 0.68 1056 0.78 1122 0.90 1185 1.01 918 0.62  989 0.72 1058 0.84 1123 0.95 1185 1.07 925 0.67  995 0.78 1061 0.89 1125 1.01 1186 1.14 934 0.72 1002 0.84 1067 0.95 1129 1.08 1189 1.21 944 0.78 1010 0.90 1074 1.02 1135 1.15 1194 1.28 956 0.85 1021 0.97 1083 1.09 1143 1.23 1200 1.36 970 0.92 1033 1.04 1094 1.17 1152 1.31 1208 1.45 985 1.00 1047 1.13 1106 1.26 1162 1.40 1217 1.54
__High Range Motor/Drive Required
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
921 0.87
Table 59 — Fan Performance -- 50PD06 Horizontal Units
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
491 0.19 604 0.28 697 0.37 781 0.47 859 0.57 513 0.23 623 0.32 714 0.42 795 0.52 871 0.62 537 0.27 643 0.37 731 0.47 810 0.57 884 0.68 561 0.31 664 0.42 750 0.52 827 0.63 899 0.75 586 0.36 686 0.47 770 0.58 845 0.70 915 0.82 613 0.41 709 0.53 790 0.65 864 0.77 640 0.47 732 0.60 812 0.72 884 0.85 950 0.97 667 0.54 757 0.67 834 0.80 695 0.61 782 0.75 857 0.89 926 1.02 989 1.16 724 0.69 807 0.84 881 0.98 948 1.12 1010 1.26 753 0.78 833 0.93 905 1.08 971 1.23 1032 1.38
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
932 0.89
904 0.93 969 1.06
AIRFLOW
(Cfm)
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
LEGEND Bhp -- Brake Horsepower
Low Range Motor/Drive Required
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
932 0.68 1002 0.79 1068 0.91 1132 1.03 1192 1.15 942 0.73 1009 0.85 1074 0.97 1136 1.09 1196 1.22 953 0.80 966 0.86 1030 0.99 1092 1.11 1151 1.24 1208 1.38 980 0.94 1043 1.06 1103 1.19 1161 1.33 1217 1.47
996 1.02 1057 1.15 1115 1.28 1172 1.42 1227 1.56 1012 1.11 1072 1.24 1129 1.38 1184 1.52 1238 1.67 1030 1.20 1088 1.34 1144 1.48 1198 1.63 1251 1.78 1049 1.30 1106 1.44 1160 1.59 1213 1.74 1265 1.89 1068 1.41 1124 1.56 1178 1.71 1229 1.86 1279 2.02 1089 1.53 1143 1.68 1196 1.84 1246 1.99 1295 2.16
1019 0.91 1082 1.04 1143 1.17 1201 1.30
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
98
Page 99
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Static pressure losses from accessories and options (economizer, etc.) must be added to external static pressure before entering Fan Performance table. Refer to Accessory/FIOP Static Pressure information.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance tables are based on wet coils, clean filters, and casing losses. Gas heat losses are included for 48 series units.
4. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using the fan motors up to the bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
5. Use of a field-supplied motor may affect wire size. Recalculate the unit power supply MCA and MOCP if required. Contact your Carrier representative for details.
6. Use the following formula to calculate input watts: Input Watts = Bhp x (746/Motor Eff)
48/50PD
99
Page 100
APPENDIX D -- ADDITIONAL START--UP DATA
Table 60 — Air Quantity Limits (50PD Units)
UNIT
50PD
05 06
COOLING (cfm)
1200 2000 1200 2000 1500 2500 1500 2500
HEATING (cfm)
OPTIONAL ELECTRIC HEAT
Table 61 — Air Quantity Limits (48PD Units)
UNIT
48PD
05 (Low Heat)
05 (Med Heat)
05 (High Heat)
06 (Low Heat)
06 (Med Heat)
06 (High Heat)
COOLING (cfm) HEATING (cfm)
Min Max Min Max
1200 2000 600 1680 1200 2000 940 2810 1200 2000 1130 2820 1500 2500 940 2810 1500 2500 1130 2820 1500 2500 1510 2520
Table 62 — Evaporator Fan Motor Specifications - 48/50PD
48/50PD DRIVE VOLTAGE/PHASE EFFICIENCY MAX BHP MAX AMPS
05 & 06 Low & High
NOTES:
1. Extensive motor and electrical testing ensures that the motors can be utilized with confidence up to the maximum applied bhp, watts, and amps. Using the fan motor up to the maximum ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2. Convert bhp to watts using the following formula:
48/50PD
watts =
bhp (746)
motor efficiency
208/230--- 3ph 0.80 2.0 6.4
460--- 3ph 0.80 2.0 3.2
3. The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor-fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT-compliant energy- efficient motor. Variable-speed mo tors are exempt from EPACT compliance requirements. Therefore, the indoor-fan motors for Carrier 48/50PG03--14 units are exempt from these requirements.
Table 63 — Fan Rpm at Motor Pulley Settings* - 48/50PD
UNIT
48/50PD
05
06
*Approximate fan rpm shown, based on 1725 rpm motor.
NOTE: Factory speed setting is at 5 turns open.
DRIVE
0
1
/
Low 910 878 847 815 784 753 721 690 659 627 596
High 1173 1139 1104 1070 1035 1001 966 932 897 863 828
Low 978 949 920 891 863 834 805 776 748 719 690
High 1261 1227 1194 1161 1128 1095 1062 1028 995 962 929
2
1 11/
MOTOR PULLEY TURNS OPEN
2
2 21/
2
3 31/
2
4 41/
2
5
AIRFLOW
(CFM)
600
800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
Table 64 — Accessory/FIOP Pressure Drop (in. wg) - 48/50PD
ELECTRIC
HEAT
0.01 0.01 0.03
0.01 0.01 0.05
0.02 0.02 0.07
0.02 0.03 0.10
0.03 0.04 0.14
0.04 0.06 0.17
0.05 0.07 0.22
0.07 0.09 0.26
0.08 0.11 0.31
0.10 0.13 0.37
0.11 0.15 0.43
0.13 0.18 0.49
0.15 0.21 0.56
ECONOMIZER
(Vertical)
ECONOMIZER
(Horizontal)
100
Loading...