Carrier 38HDR018, 38HDR024, 38HDR030, 38HDR036, 38HDR048 Product Data

...
40QAC / 38HDR 40QAQ / 38QRR Ceiling---Suspended Duct Free S plit System Sizes 018 to 060
Product Data
AN INEXPENSIVE AND CREATIVE SOLUTION TO DESIGN PROBLEMS.
The 38HDR(QRR)/40QAC(QAQ) series duct--free split systems are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.
The ceiling--suspended fan coils are ideal for retrofit and modernization projects where it is impractical or prohibitively expensive to run ductwork and where there are no false ceilings or wall space available. This selection of fan coils permits inexpensive and creative solutions to design problems such as:
the environmentally sound refrigerant
The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork.
S Special space requirements such as garages.
S When changes in the load cannot be handled by the
existing system like restaurants.
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork like schools.
S Historical renovations or any application where
preserving the look of the original structure is essential like churches.
These compact indoor fan coil units blend nicely with most ceilings and protrude less than 10 inches (254 mm) from the ceiling. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.
LOW SOUND LEVELS
R
When noise is a concern, ceiling--suspended duct--free split systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.
When sound ordinances and proximity to neighbors demand quiet operation, the 38HDR/QRR unit is the right choice: The advanced, blow--through horizontal airflow design distributes air more evenly over the coil.
BUILT--IN RELIABILITY
Duct--free split system indoor and outdoor units are designed to provide years of trouble--free operation.
The high wall indoor units include protection against freeze--up. The condensing units and heat pumps are also protected. There is
a three minute time delay before the compressor will start. An oversized accumulator on heat pumps, high and low pressure
switches ( loss of pressure switch on heat pumps), and compressor internal overload protection will ensure a robust system that is ideal for light commercial applications.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since 38HDR/QRR units can be installed close to an outside wall, coils are protected from vandals and severe weather.
FAST INSTALLATION
The small footprint of the outdoor units provide additional benefits. Because they require minimal service and airflow clearances, the outdoor units can be located virtually anywhere -­on the ground, roof, balcony, under a deck, or even mounted to an outside wall.
The ceiling--suspended unit has its own mounting bracket for easier installation. Since there is no need to run ductwork and only piping and wiring is required between the indoor and outdoor units, there is minimal disruption to customers in the workplace, making this system ideal for retrofit applications.
40QAC/38HDR -- 40QAQ/38QR
SIMPLE SERVICING AND MAINTENANCE
Saving time and money was a big consideration when designing these systems.
On all indoor units, service and maintenance expense is reduced due to easy--to--use cleanable filters and the ability to service the unit from the bottom by removing the filter tracks.
On the outdoor units, a single panel provides immediate access to the isolated compressor and control compartment, allowing a service technician easy access to check the unit operation without a loss of condenser airflow. In addition, the blow--through design of the outdoor section means that dirt accumulates on the inside surface of the coil. Coils can be cleaned from the outside using a pressure hose and mild detergent without removing grilles or using fin combs.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on usage pattern. The ceiling--suspended units are equipped with motorized louvers which permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year--round comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The duct--free split system design allows individual room heating or cooling when required. There is no need to run large supply--air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted moving air through ducts.
EASY--TO--USE CONTROLS
The ceiling--suspended units have electro--mechanical controls and can be controlled by one of three user friendly thermostats that mount on the wall.
FLEXIBILITY
A variety of accessories simplify the installation process and help meet system requirements and weather considerations. Available accessories are listed in the Standard Features and Accessories section of this document.
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning & Refrigeration Institute), and UL.
2
MODEL NUMBER NOMENCLATURE
R
INDOOR UNIT
40 QAC 3---01
018
---
Fan Coil Unit
Unit Type QAC --- C o o l i n g O n l y QAQ --- H e a t P u m p
Nominal Capacity* 024 --- 2 To n 036 --- 3 To n 048 --- 4 To n 060 --- 5 To n s
Volt age 3 --- 208/230 ---1 ---60
OUTDOOR UNIT
38 HDR 3--- 01
Air--- Cooled Condenser
Unit Type HDR --- C o o l i n g Only QRR --- H e a t P u m p
* For nominal size 018 and 030, the indoor unit sizes 024 and 036 are matched with outdoor unit sizes 018 and 030 respectively. ** On sizes 036, 048 and 060
018
Nominal Capacity 018 --- 1 --- 1 / 2 T o n 024 --- 2 To n 030 --- 2 --- 1 / 2 T o n 036 --- 3 To n s 048 --- 4 To n s 060 --- 5 To n s
---
Volt age 3--- 208/230--- 1---60 5--- 208/230--- 3---60** 6--- 4 6 0 --- 3 --- 6 0 * *
40QAC/38HDR -- 40QAQ/38QR
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
®
3
STANDARD FEATURES AND ACCESSORIES
R
Ease Of Installation
Compact Size S Hanging Bracket For Indoor Unit S Stacking Kit A Wall Mounting Kit A Condensate Pump A
Comfort Features
Automatic Air Sweep S Auto Restart Function S Auto Changeover On Heat Pumps S
Energy Saving Features
Stop/Start Timer S
Safety And Reliability
3MinuteTimeDelayForCompressor S Over Current Protection For Compressor S High and Low Pressure Switches on Cooling Only U nits S High Pressure Switch and Loss Of Charge Switch On HP S Indoor Coil Freeze Protection S Factory Supplied Filter Dryer For Field Installation S Accumulator On Heat Pumps Units S
Ease Of Service And Maintenance
Control Box Accessible From Bottom Of Unit S Cleanable Filters S Liquid Line Pressure Tabs S Suction And Discharge Pressure Tabs S
Application Flexibility
208/230 and 460 3 Phase on size 036, 048, and 060 S Electric Heat On 40QAQ Un its S Long lines up to 200 Ft (accessories required) A Outside Air Intake Kit A Power Ventilation Kit A Low Ambient Controls ( --- 20° F) A
40QAC/38HDR -- 40QAQ/38QR
Knock Out For Outside Air Intake S Wind Baffles A Wall Mounted Thermostats A
Warranty
5--- Year Compressor Warranty S 1--- Year Parts Warranty S Compressor Extended Warranty Years 6 Thru 10 O All Parts And Labor Years 2 Thru 5 O All Parts And Labor Years 2 Thru 5, Compressor Years 6 Thru 10 O
Legend
SStandard A Accessory OOptional
OUTDOOR UNITS LOW AMBIENT KIT
The kit controls condenser fan cycling using a pressure switch. It is specifically designed to control fan--motor cycles in response to saturated condensing pressure. This device maintains a constant saturated condensing temperature of 100 _F ± 10 _F (37.78_C ±
--12.22 _C) at outdoor--air temperatures between 55 _F and --20 _F (12.78_C ± --12.22_C), and can be used on all outdoor units without changing the outdoor fan motor.
WINTER START CONTROL
The Winter Start Control is a SPST delay relay. the control bypasses the low pressure switch for approximately 3 minutes to permit start--up for cooling operation under low load conditions at low ambient temperatures. This relay is recommended on all systems that have the accessory Low Ambient Kit. Winter Start Control can also be used to provide low ambient cooling at outdoor ambient temperatures between 55_F and 40_F (12.8_C and 4.4_C).
ISOLATION RELAY
To be used when Low Ambient Kit is used with heat pumps. This will ensure that the pressure switch is bypassed if unit is running in heat pump mode.
LIQUID LINE SOLENOID VALVE
The Liquid Line Solenoid Valve is an electronically operated shutoff valve that is installed at the outdoor unit to stop and start refrigerant flow in response to compressor operation. The valve maintains a column of refrigerant in the liquid line between compressor operating cycles and is required for certain long--line applications and to improve system performance.
CRANKCASE HEATER
The Crankcase Heater is available for units with scroll compressors and clamps onto the compressor oil sump. It is recommended for low ambient and long line applications.
WIND BAFFLES
The Wind Baffle is an accessory sheet metal wrapper used to provide improved unit operation during high winds and is recommended whenever the Low Ambient Kit is used.
4
STANDARD FEATURES AND ACCESSORIES CONTINUED
R
INDOOR UNITS
CONDENSATE PUMP
(part # 53DS--900------081)
For those applications where the ceiling--suspended unit is not installed close to an outside wall, and an adequate pitch cannot be provided, the pump mounts inside the unit with quick plug--in connections and provide a maximum lift capability of 20 inches (508 mm).
Fig. 1 – Condensate Pump
A08572
FRESH AIR INTAKE KIT
(Part # 53DS--900------006)
When the ceiling--suspended unit is installed against an outside wall, the Fresh Air Intake Kit provides variable (up to 30%) fresh air capability. The kit has a filter that mounts at the fan coil unit and provides filtering of the outside air before it enters the unit.
POWER VENTILATION KIT
(Part # 53DS--900------066)
The Power Ventilation Kit is used in conjunction with the Fresh Air Intake Kit and is used when the unit is not installed against an outside wall and where static pressure needs to be overcome.
REAR OF INDOOR UNIT
INDOOR UNIT (TOP)
COVER
ADJUSTABLE VENTILATION AIR DAMPER
AIR FILTER
Fig. 2 – Fresh Air Intake Kit
40QAC/38HDR -- 40QAQ/38QR
A08573
5
WIRED CONTROLLER
R
HW Thermostat (Part # 53DFS250--HW)
A specially designed thermostat for ceiling--suspended systems that incorporate 3--speed fan control. These can be used on both cooling--only and heat pump systems.
S Large, Clear Display with Backlighting—current
temperature, set temperature and time are easy--to--read and all are displayed on the main screen.
S Menu Driven Programming -- Provides guidance
through the scheduling process, showing only necessary information and choices on each screen.
S Ability to Select Multiple Days -- allows easy
customizing for unique schedules.
S Real--Time Clock -- keeps time during power failure;
automatically updates for daylight saving time.
S Precise Temperature Control (±1_F) -- reliable,
consistent comfort.
S Multiple OVERRIDE options -- can modify schedule for
a specific period of time (up to 365 days).
S Speedy same--schedule programming -- no need to copy
mulitple days.
S Programmable or non--programmable modes. S Remote setback input for occupancy sensors or
timeclocks.
S VersaSpeedt fan ramping algorithm and fan reset
algorithm
40QAC/38HDR -- 40QAQ/38QR
Fig. 3 – 53DFS250--HW Thermostat
6
AHRI* CAPACITY RATINGS
R
System
Ty pe
*Air Conditioning, Heating & Refrigeration Institute
Legend HSPF --- Heating Seasonal Performance Factor EER --- Energy Efficiency Rating SEER --- Seasonal Energy Efficiency Ratio NOTES:
1. Ratings are net values reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80_F (26.67_C) db, 67_F (19.44_C) wb air entering indoor unit and 95_F(35_C) db air entering outdoor unit. High Temperature Heating Standard: 70_F (21.11_C) db air entering indoor unit and 47_F (8.33_C) db, 43_F (6.11_C) wb air entering outdoor unit.
2. Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3. All system ratings are based on fan coil un its operating at high fan speed. Consult Physical Data tables f or airflows at all available fan speeds.
Outdoor Section Indoor Section
3 8 H D R018 --- --- --- 3 4 0 QAC 0 2 4 --- --- --- 3 1720 480 18,000 13 11.5 N/A N/A
3 8 H D R024 --- --- --- 3 4 0 QAC 0 2 4 --- --- --- 3 1720 550 23,000 13 11.5 N/A N/A
3 8 H D R030 --- --- --- 3 4 0 QAC 0 3 6 --- --- --- 3 3900 840 29,000 13 12.0 N/A N/A
3 8 H D R036 --- --- --- 3 4 0 QAC 0 3 6 --- --- --- 3 3900 840 33,000 13 11.4 N/A N/A
3 8 H D R036 --- --- --- 5 4 0 QAC 0 3 6 --- --- --- 3 3900 840 33,000 13 11.4 N/A N/A
3 8 H D R036 --- --- --- 6 4 0 QAC 0 3 6 --- --- --- 3 3900 840 33,000 13 11.4 N/A N/A
3 8 H D R048 --- --- --- 3 4 0 QAC 0 4 8 --- --- --- 3 3900 1130 46,000 13 11.5 N/A N/A
Cooling
3 8 H D R048 --- --- --- 5 4 0 QAC 0 4 8 --- --- --- 3 3900 1130 46,000 13 11.5 N/A N/A
3 8 H D R048 --- --- --- 6 4 0 QAC 0 4 8 --- --- --- 3 3900 1130 46,000 13 11.5 N/A N/A
3 8 H D R060 --- --- --- 3 4 0 QAC 0 6 0 --- --- --- 3 3900 1600 57,000 13 11.4 N/A N/A
3 8 H D R060 --- --- --- 5 4 0 QAC 0 6 0 --- --- --- 3 3900 1600 57,000 13 11.4 N/A N/A
3 8 H D R060 --- --- --- 6 4 0 QAC 0 6 0 --- --- --- 3 3900 1600 57,000 13 11.4 N/A N/A
3 8 QRR 0 1 8 --- --- --- 3 4 0 QAQ 0 2 4 --- --- --- 3 1720 480 17,000 13 11.7 17,000 7.7
3 8 QRR 0 2 4 --- --- --- 3 4 0 QAQ 0 2 4 --- --- --- 3 1720 550 23,000 13 11.4 23,800 7.7
3 8 QRR 0 3 0 --- --- --- 3 4 0 QAQ 0 3 6 --- --- --- 3 3900 840 28,000 13 11.2 28,800 7.7
3 8 QRR 0 3 6 --- --- --- 3 4 0 QAQ 0 3 6 --- --- --- 3 3900 840 33,000 13 11.6 32,000 7.7
3 8 QRR 0 3 6 --- --- --- 5 4 0 QAQ 0 3 6 --- --- --- 3 3900 840 33,000 13 11.6 32,000 7.7
3 8 QRR 0 3 6 --- --- --- 6 4 0 QAQ 0 3 6 --- --- --- 3 3900 840 33,000 13 11.6 32,000 7.7
3 8 QRR 0 4 8 --- --- --- 3 4 0 QAQ 0 4 8 --- --- --- 3 3900 1130 45000 13 11.5 45000 7.7
3 8 QRR 0 4 8 --- --- --- 5 4 0 QAQ 0 4 8 --- --- --- 3 3900 1130 45000 13 11.5 45000 7.7
Heat PumpsHeat Pumps
3 8 QRR 0 4 8 --- --- --- 6 4 0 QAQ 0 4 8 --- --- --- 3 3900 1130 45000 13 11.5 45000 7.7
3 8 QRR 0 6 0 --- --- --- 3 4 0 QAQ 0 6 0 --- --- --- 3 3900 1600 56000 13 11.4 56000 7.7
3 8 QRR 0 6 0 --- --- --- 5 4 0 QAQ 0 6 0 --- --- --- 3 3900 1600 56000 13 11.4 56000 7.7
3 8 QRR 0 6 0 --- --- --- 6 4 0 QAQ 0 6 0 --- --- --- 3 3900 1600 56000 13 11.4 56000 7.7
Standard CFM
Outdoor Indoor BTUH HSPF
Net Cool­ing BTUH
SEER EER
High Heat
40QAC/38HDR -- 40QAQ/38QR
CLEARANCES -- OUTDOOR UNIT
D
UNIT Coil Facing Wall --- in. (mm)
A 24 (610) B 36 (914) C 36 (914) D 6 (152)
E 6 (152)
A
B
Fig. 4 – Outdoor Unit Clearance
7
Air-outlet
E
C
Air-inlet
A08436
Fan Facing Wall --- in. (mm)
24 (610) 36 (914)
8 (203) 8 (203) 8 (203)
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(lbs)
WEIGHT(lbs)
OPERATING
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
7/8"-1/2"TRADE
1 3/16"-3/4"TRADE
1 3/8"-1"TRADE
40QAC/38HDR -- 40QAQ/38QRR
F, MAX. 125 F.
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 6" MIN
CLEARANCE ON COIL SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 8" MIN
CLEARANCE ON FAN SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 55
5. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
JUNCTION BOX FOR
POWER SUPLLY AND
2 1/2"
4 3/16"
CONTROL CONNECTIONS
K
P
N
AIR
N
7 1/2"
J
AIR
E
1 7/16"
1 1/2"
FIELD CONTROL SUPPLY
WIRE ENTRY
7/8" HOLE W/GROMMET
H
G
L
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
8"
3/8" LIQUID LINE
4 1/2"
1"
Fig. 5 – 38HDR Dimensions -- English
FEMALE SWEAT CONN.
AB C D E F G H JKLMNP
X = YES
O = NO
460-3-60
208/230-3-60
230-1-60
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
OUTDOOR UNIT DIMENSIONS
38HDR018 1 X O O O 25 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 17 1/8" 22" 13" 6 5/8" 11 1/4" 5/8" 2 15/16" 6" 155 171 42 9/10" X 18" X 28 1/10"
38HDR060 1,2 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 294 319 50 1/2" X 20 1/2" X 46 2/10"
38HDR048 1,2 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 284 309 50 1/2" X 20 1/2" X 46 2/10"
38HDR036 1 X O X X 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 218 240 50 1/2" X 20 1/2" X 40 2/10"
38HDR030 1 X O O O 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 200 223 50 1/2" X 20 1/2" X 40 2/10"
38HDR024 1,2 X O O O 31 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 23 1/8" 28" 14" 6 3/4" 11 5/8" 5/8" 2 15/16" 6" 180 198 42 9/10" X 18" X 34 1/10"
208-230-1-60
C
FD
11/16"
8
B
MINIMUM
DIMENSIONS
MOUNTING PAD
A
18,24 23" X 42"
30,36,48,60 24" X 50"
UNIT SIZE
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(KG)
WEIGHT(KG)
OPERATING
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
22.22 - 12.70 TRADE
30.16 - 19.05 TRADE
34.92 - 25.40 TRADE
C, MAX. 51.7 C.
36.5
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 152.4 MIN
CLEARANCE ON COIL SIDE AND COIL END AND 914.4 MIN CLEARANCE
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 203.2 MIN
CLEARANCE ON FAN SIDE AND COIL END AND 914.4 MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 12.8
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
5. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED.
63.5
106.4 JUNCTION BOX FOR
POWER SUPLLY AND
CONTROL CONNECTIONS
K
AIR
NE
190.5
P
J
AIR
17.5
38.1
FIELD CONTROL SUPPLY
WIRE ENTRY
22.22 HOLE W/GROMMET
H
G
L
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
203.2
114.3
25.4
9.53 LIQUID LINE FEMALE SWEAT CONN.
40QAC/38HDR -- 40QAQ/38QRR
Fig. 6 – 38HDR Dimensions -- SI
AB C D E F G H JKLMNP
X = YES
O = NO
460-3-60
208/230-3-60
230-1-60
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
OUTDOOR UNIT DIMENSIONS CONTINUED
38HDR060 1,2 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5 893.8 1017.6 368.3 215.9 479.4 22.2 87.3 165.1 133.6 145.0 1282.7 X 520.7 X 1173.1
38HDR048 1,2 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5 893.8 1017.6 368.3 215.9 479.4 22.2 87.3 165.1 129.0 140.4 1282.7 X 520.7 X 1173.1
38HDR036 1 X O X X 944.6 1131.9 433.4 468.3 774.7 498.5 741.4 865.2 347.7 206.4 403.2 19.0 87.3 165.1 99.0 109.0 1282.7 X 520.7 X 1020.7
38HDR030 1 X O O O 944.6 1131.9 433.4 468.3 774.7 498.5 741.4 865.2 347.7 206.4 403.2 19.0 87.3 165.1 90.9 101.4 1282.7 X 520.7 X 1020.7
38HDR024 1,2 X O O O 790.6 938.2 369.9 406.4 595.3 436.6 587.4 711.2 355.6 171.5 295.3 15.9 74.6 152.4 81.8 90.0 1090.2 X 457.7 X 866.7
38HDR018 1 X O O O 638.2 938.2 369.9 406.4 595.3 436.6 435.0 558.8 330.2 168.3 285.8 15.9 74.6 152.4 70.4 77.7 1090.2 X 457.7 X 714.3
208-230-1-60
FDC
B
MINIMUM
DIMENSIONS
MOUNTING PAD
A
18,24 584.2 X 1066.8
30,36,48,60 609.6 X 1270.0
UNIT SIZE
9
40QAC/38HDR -- 40QAQ/38QRR
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(lbs)
WEIGHT(lbs)
OPERATING
MINIMUM
DIMENSIONS
MOUNTING PAD
F, MAX. 125 F.
18,24 23" X 42"
30,36,48,60 24" X 50"
UNIT SIZE
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 6" MIN
CLEARANCE ON COIL SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 8" MIN
CLEARANCE ON FAN SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 55
5. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
7/8"-1/2"TRADE
1 3/16"-3/4"TRADE
1 3/8"-1"TRADE
1 7/16"
JUNCTION BOX FOR
POWER SUPLLY AND
CONTROL CONNECTIONS
1 1/2"
H
G
8"
4 1/2"
1"
L
AB C D E F G H J KLMNP
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
OUTDOOR UNIT DIMENSIONS
38QRR060 0 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 306 331 50 1/2" X 20 1/2" X 46 2/10"
38QRR048 0 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 278 303 50 1/2" X 20 1/2" X 46 2/10"
38QRR036 0 X O X X 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 232 255 50 1/2" X 20 1/2" X 40 2/10"
38QRR030 0 X O O O 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 187 210 50 1/2" X 20 1/2" X 40 2/10"
38QRR024 0 X O O O 31 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 23 1/8" 28" 14" 6 3/4" 11 5/8" 5/8" 2 15/16" 6" 176 194 42 9/10" X 18" X 34 1/10"
38QRR018 0 X O O O 25 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 17 1/8" 22" 13" 6 5/8" 11 1/4" 5/8" 2 15/16" 6" 167 183 42 9/10" X 18" X 28 1/10"
X = YES
O = NO
P
AIR
460-3-60
208/230-3-60
230-1-60
208-230-1-60
FIELD CONTROL SUPPLY
WIRE ENTRY
7/8" HOLE W/GROMMET
2 1/2"
N
7 1/2"
4 3/16"
K
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
J
AIR
Fig. 7 – 38QRR Dimensions -- English
3/8" LIQUID LINE
MALE FLARE CONN.
E
B
11/16"
FDC
A
10
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(KG)
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
22.22 - 12.70 TRADE
30.16 - 19.05 TRADE
34.92 - 25.40 TRADE
C.
WEIGHT(KG)
OPERATING
330.2 168.3 285.8 15.9 74.6 152.4 75.9 83.2 1090.2 X 457.7 X 714.3
355.6 171.5 295.3 15.9 74.6 152.4 80.0 88.2 1090.2 X 457.7 X 866.7
558.8
711.2
85.0 95.4 1282.7 X 520.7 X 1020.7
105.4 115.9 1282.7 X 520.7 X 1020.7
126.4 137.7 1282.7 X 520.7 X 1173.1
139.0 150.4 1282.7 X 520.7 X 1173.1
165.1
165.1
165.1
87.3 165.1
347.7 206.4 403.2 19.0
741.4 865.2
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 152.4 MIN
CLEARANCE ON COIL SIDE AND COIL END AND 914.4 MIN CLEARANCE
215.9 479.4 22.2 87.3
215.9 479.4 22.2 87.3
347.7 206.4 403.2 19.0 87.3
741.4 865.2
893.8 1017.6 368.3
893.8 1017.6 368.3
MINIMUM
DIMENSIONS
609.6 X 1270.0
C, MAX. 51.7
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 203.2 MIN
CLEARANCE ON FAN SIDE AND COIL END AND 914.4 MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 12.8
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
5. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED.
63.5
MOUNTING PAD
18,24 584.2 X 1066.8
30,36,48,60
UNIT SIZE
106.4
36.5
JUNCTION BOX FOR
POWER SUPLLY AND
CONTROL CONNECTIONS
38.1
FIELD CONTROL SUPPLY
WIRE ENTRY
22.22 HOLE W/GROMMET
H
G
203.2
114.3
40QAC/38HDR -- 40QAQ/38QRR
25.4
L
Fig. 8 – 38QRR Dimensions -- SI
AB C D E F G H J KLMNP
X = YES
O = NO
460-3-60
208/230-3-60
230-1-60
OUTDOOR UNIT DIMENSIONS CONTINUED
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
38QRR018 0 X O O O 638.2 938.2 369.9 406.4 595.3 436.6 435.0
38QRR024 0 X O O O 790.6 938.2 369.9 406.4 595.3 436.6 587.4
38QRR030 0 X O O O 944.6 1131.9 433.4 468.3 774.7 498.5
38QRR036 0 X O X X 944.6 1131.9 433.4 468.3 774.7 498.5
38QRR048 0 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5
38QRR060 0 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5
208-230-1-60
K
P
N
N
AIR
190.5
J
AIR
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
9.53 LIQUID LINE MALE FLARE CONN.
E
B
17.5
FDC
A
11
DIMENSIONS -- INDOOR UNIT
R
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Standard unit clearances are as follows:
• 0 in. on top and rear
• 3in.onleftside
• 12 in. on right side
• 36 in.on bottom (When facing unit discharge.)
40QAC/38HDR -- 40QAQ/38QR
A08580
UNIT SIZE
024 108 110 4 --- 2 15/16 1294 3 --- 1 0 1169 4 --- 1 5/8 1260 1 --- 9 5/8 549 036 117 119 4 --- 1 0 13/16 1493 4 --- 5 7/8 1368 4 --- 9 1/2 1459 2 --- 1 1/2 648 048 149 151 5 --- 1 1 9/16 1817 5 --- 6 5/8 1692 5 --- 1 0 1/4 1783 1 --- 9 7/8 555 3 --- 3 1/16 992 060 179 181 7 --- 8 2336 7 --- 3 2211 7 --- 6 5/8 2302 1 --- 1 1 5/8 601 4 --- 1 1 9/16 1512
WEIGHT (lb) A B E F G
Cooling
Only
Heat
Pump
f t --- i n . mm f t --- i n . mm f t --- i n . mm f t --- i n . mm f t --- i n . mm
Fig. 9 – 40QA Dimensions
12
PHYSICAL DATA -- OUTDOOR UNIT 38HDR
R
Outdoor Unit 38HDR 018 024 030 036 48 60
System Voltage 208/230--- 1--- 60 208/230 ---1 ---60 208/230 ---1 ---60
Nominal Capacity (Btuh) 18000 24000 30000 36000 48000 60000
Operating Weight lb(kg) 166 (75.3) 176 (79.8) 250 (113.4) 250 (113.4) 278 (126.4) 306 (139)
Refrigerant Type R--- 410A
Metering Device TXV
Unit Factory Charge 6.3 (2.9) 6.5 (3.0) 8.7 (4.0) 8.7 (4.0) 12 (5.5) 12 (5.5)
System Charge (25 ft line) lb (kg) 7.0 (3.2) 7.8 (3.5) 10.1 (4.6) 8.9 (4.0) 12.2 (5.5) 12.5 (5.7)
Additional Charge .7 (.32) 1.3 (.57) 1.4 (.64) .2 (.1) .2 (.1) .5 (.23)
Compressor
Type Scroll
O il Ch a r ge (PO E --- o z ) 25 25 25 25 42 42
Crankcase Heater --- --- 40 40 40 40
Accumulator Ye s
Outdoor Fan
Rpm/CFM 840/1720 840/1720 840/3900 840/3900 840/3900 840/3900 Diameter (in) .. No. of Blades 18…3 18…3 24…3 24…3 24…3 24…3
Motor HP 1/8 1/8 1/4 1/4 1/4 1/4
Outdoor Coil
Face Area (sq. f t) 5.8 7.3 12.1 12.1 14.1 14.1
No. Rows 2 3 2 2 3 3
Fins per inch 20 20 20 20 20 20
Circuits 2 3 3 6 6 6
High Pre ssure Switch
C u t --- I n ( p s i g) 420±25 420±25 420±25 420±25 420±25 420±25
C u t --- O u t ( p s ig) 650±10 650±10 650±10 650±10 650±10 650±10
Low Pressure Switch
C u t --- I n ( p s i g) 45±25 45±25 45±25 45±25 45±25 45±25
C u t --- O u t ( p s ig) 20±5 20±5 20±5 20±5 20±5 20±5
Fusi ble Plug ° F (° C ) 210 (99)
Refrigerant Lines
Connection Type L i qu id/ S u c t i o n --- S w e a t
Suction /Vapor (in) OD 5/8 3/4 7/8 7/8†
Liquid Line (in) OD 3/8
Maximum Length* ft (m) 200 (61)
MaxLift(FanCoilAbove)ft(m) 65 (20)
Max Drop (Fan Coil Below) ft (m) 200 (61)
Controls
Control Voltage 24 vac
External Finish Gray
* Refer to Long Line Application { Valve size connection is 7/8 inch. Recommended line size is 1 --- 1/8 inch.
208/230--- 1--- 60 208/230--- 3--- 60
4 6 0 --- 3 --- 6 0
208/230--- 1--- 60 208/230--- 3--- 60
4 6 0 --- 3 --- 6 0
208/230--- 1--- 60 208/230--- 3--- 60
4 6 0 --- 3 --- 6 0
40QAC/38HDR -- 40QAQ/38QR