Carrier 38MVC009-1, 40MVC009-1, 38MVC012-1, 40MVC012-1, 38MVC012-3 Product Data

...
40MVC / 38MVC 40MVQ / 38MVQ High---Wall D uct Free Split System Sizes 009 to 024
Product Data
AN INEXPENSIVE AND CREATIVE SOLUTION TO DESIGN PROBLEMS.
The 38/40MVC(Q) series duct--free split systems are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the wall, near the ceiling. This selection of fan coils permits inexpensive and creative solutions to design problems such as:
the environmentally sound refrigerant
The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork.
S Add--ons to current space (an office or family room
addition)
S Special space requirements
S When changes in the load cannot be handled by the
existing system.
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.
These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.
LOW SOUND LEVELS
When noise is a concern, the duct--free split systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.
When sound ordinances and proximity to neighbors demand quiet operation, the 38MVC,MVQ unit is the right choice: The advanced, horizontal airflow design distributes air more evenly over the coil.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since 38MVC,MVQ units can be installed close to an outside wall, coils are protected from vandals and severe weather.
FAST INSTALLATION
This compact duct--free split system is simple to install. A mounting bracket is standard with the indoor units and only wire and piping need to be run between indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in the home or workplace. This makes the
38/40MVC, MVQ
38/40MVC,MVQ duct--free split systems the equipment of choice, especially in retrofit situations.
SIMPLE SERVICING AND MAINTENANCE
Removing the top panel on outdoor units provides immediate access to the control compartment, providing a service technician access to check unit operation. In addition, the draw--thru design of the outdoor section means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced due to easy--to--use cleanable filters. In addition, these high wall systems have extensive self--diagnostics to assist in troubleshooting.
BUILT--IN RELIABILITY
Duct--free split system indoor and outdoor units are designed to provide years of trouble--free operation.
The high wall indoor units include protection against freeze--up and high evaporator temperatures on heat pumps.
The condensing units and heat pumps are also protected. There is a three minute time delay before the compressor will start. The compressor is also protected by the over--current protection. On size 18k and 24k heat pumps, there is high temperature protection.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on usage pattern. The air sweep feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year--round comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The duct--free split system design allows individual room heating or cooling when required. There is no need to run large supply--air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted moving air through ducts.
EASY--TO--USE CONTROLS
The high--wall units have microprocessor--based controls to provided the ultimate in comfort and efficiency. The user friendly wireless remote control provides the interface between user and the unit.
ACCESSORIES
Customizing these duct--free split systems to your application is easily accomplished. Low--ambient temperature capability (permitting cooling operation down to --20_F (--28.89_C)outdoor ambient) is easily added on all units.
Adding a condensate pump accessory to the high wall fan coil provides installation flexibility.
AGENCY LISTINGS
All systems are listed with ARI (Air Conditioning & Refrigeration Institute), and ETL.
2
MODEL NUMBER NOMENCLATURE
INDOOR UNIT
40 MVC 3---01
Fan C oil U nit
Unit Type MVC --- C o o l i n g O n l y MVQ --- H e a t P u m p
018
Nominal Capacity 009 --- 3 / 4 To n 012 --- 1 To n 018 --- 1 --- 1 / 2 Ton 024 --- 2 To n s
---
Volt age
--- --- 3 0 V D C 1 --- 1 1 5 --- 1 --- 6 0 3 --- 208/230--- 1 --- 60
Air---Cooled Condenser
OUTDOOR UNIT
38 MVC 3---01
Unit Type MVC --- C o o l i n g O n l y MVQ --- H e a t P u m p
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
018
Nominal Capacity 009 --- 3 / 4 To n 012 --- 1 To n 018 --- 1 --- 1 / 2 Ton 024 --- 2 To n s
---
Volt age 1--- 1 1 5 --- 1 --- 6 0 3--- 208/230--- 1--- 60
38/40MVC, MVQ
3
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting Brackets S Low Voltage Controls S
Comfort Features
Microprocessor Controls S Wireless Remote Control S Automatic Air Sweep S Air Direction Control S Auto Restart Function S Cold Blow Protection On Heat Pumps S Turb o Mo d e On Size s 9K a n d 12 K S Auto Changeover On Heat Pumps S
Energy Saving Features
Sleep Mode S Stop/Start Timer S
Safety And Reliability
3MinuteTimeDelayForCompressor S Over Current Protection For Compressor S Indoor Coil Freeze Protection S Indoor Coil High Temperature Protection On Heat Pumps S Condenser High Temperature Protection On heat Pumps{ S Accumulator On Heat Pumps S
Ease Of Service And Maintenance
38/40MVC, MVQ
Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Suction And Discharge Pressure Taps (Sizes 18 and 24K) S
Application Flexibility
Low Ambient Controls (--- 20° F) A Condensate Pumps A Crankcase Heater A Wind Baffles F
Warranty
5 ---Year Compressor Warranty S 1 --- Parts Warranty S Compressor Extended Warranty Years 6 Thru 10 O All Parts And Labor Years 2 Thru 5 O All Parts And Labor Years 2 Thru 5, Compressor Years 6
Thru 10
{ Sizes 18k & 24k
Legend
SStandard A Accessory OOptional F Field Fabricated
O
INDOOR UNITS
A07892
Fig. 1 – Condensate Pump Accessory
On high wall fan coils, the condensate pump has a lift capability of 12 ft (3.6 m) on the discharge side with the pump mounted in the fan coil or 6 ft (1.8 m) on the suction side if the pump is remote mounted. The pump is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
NOTE: An external 115v power source will be required to run the pump on unit sizes 9k and 12k.
OUTDOOR UNITS LOW AMBIENT KIT
The kit controls condenser fan cycling using a pressure switch. It is specifically designed to control fan--motor cycles in response to saturated condensing pressure. This device maintains a constant saturated condensing temperature of 100 _F ± 10 _F (37.78_C ±
--12.22 _C) at outdoor--air temperatures between 55 _F and --20 _F (12.78_C ± --12.22_C), and can be used on all outdoor units without changing the outdoor fan motor.
CRANKCASE HEATER
Available for units with rotary compressors. Heater clamps around compressor oil sump. Recommended for low--ambient applications on sizes 9, 12 , 18, 24 and long line applications.
AHRI* CAPACITY RATINGS
OUTDOOR
SECTION
3 8 M V C 0 0 9 --- --- --- 1 4 0 M V C 0 0 9 --- --- --- 1 1000 325 9,200 13 N/A N/A 3 8 M V C 0 1 2 --- --- --- 1 4 0 M V C 0 1 2 --- --- --- 1 1000 425 11,400 13 N/A N/A 3 8 M V C 0 1 2 --- --- --- 3 4 0 M V C 0 1 2 --- --- --- 3 1000 425 11,800 13 N/A N/A 3 8 M V C 0 1 8 --- --- --- 3 4 0 M V C 0 1 8 --- --- --- 3 1600 630 17,500 13 N/A N/A 3 8 M V C 0 2 4 --- --- --- 3 4 0 M V C 0 2 4 --- --- --- 3 1600 750 22,000 13 N/A N/A 3 8 M V Q009 --- --- --- 1 4 0 M V Q 0 0 9 --- --- --- 1 1000 325 9,600 13 9,400 7.7 3 8 M V Q012 --- --- --- 1 4 0 M V Q 0 1 2 --- --- --- 1 1000 425 11,500 13 11,500 7.7 3 8 M V Q012 --- --- --- 3 4 0 M V Q 0 1 2 --- --- --- 3 1000 425 12,000 13 11,500 7.7 3 8 M V Q018 --- --- --- 3 4 0 M V Q 0 1 8 --- --- --- 3 1600 560 17,500 13 17,000 7.7 3 8 M V Q024 --- --- --- 3 4 0 M V Q 0 2 4 --- --- --- 3 1600 750 22,500 13 21,500 7.7
*Air Conditioning, Heating & Refrigeration Institute
Legend HSPF --- Heating Seasonal Performance Factor SEER --- Seasonal E n ergy Efficiency Ratio NOTES:
1. Ratings are net values reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80_F (26.67_C) db, 67_F (19.44_C) wb air entering indoor unit and 95_F(35_C) db air entering outdoor unit. High Temperature Heating Standard: 70_F (21.11_C) db air entering indoor unit and 47_F (8.33_C) db, 43_F (6.11_C) wb air entering outdoor unit.
2. Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3. All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data tables for airflows at all available fan speeds.
INDOOR
SECTION
STANDARD CFM
Outdoor Indoor BTUH HSPF
COOLING BTUH SEER
HIGH HEAT
4
DIMENSIONS -- INDOOR
Model Size
9K 32.09 (815) 11.02 (280) 7.68 (195) 12K 35.67 (906) 11.26 (286) 9.25 (235) 18K 49.21 (1250) 12.80 (325) 9.06 (230) 24K 49.21 (1250) 12.80 (325) 9.06 (230)
in. (mm)
DIMENSIONS -- OUTDOOR
A07336
W
H
in. (mm)
D
in. (mm)
Operating Weight lb (kg)
17.6 (8)
25.3 (11.5)
39.6 (18)
39.6 (18)
Air Flow
H
L1
L2
L3
35
Model Size
9K 30.71 (780) 21.26 (540) 21.61 (549) 11.81 (300) 10.87 (276) 12K 29.92 (760) 23.23 (590) 20.87 (530) 12.40 (315) 11.42 (290) 18K 33.07 (840) 27.36 (695) 22.05 (560) 14.17 (360) 13.19 (335) 24K 35.00 (889) 33.50 (851) 23.11 (588) 13.98 (355) 13.11 (333)
W
in. (mm)
H
in. (mm)
L1
in. (mm)
L2
in. (mm)
SERVICE VALVE LOCATIONS
9K
12K
18K
W
L3
in. (mm)
24K
Operating Weight
lb (kg)
Cooling Only
70.4 (32) 72.6 (33)
79.2 (36) 83.6 (38)
116.6 (53) 117.7 (53.5)
149.6 (68) 151 (68.5)
Operating Weight
Heat Pumps
38/40MVC, MVQ
A07337
lb (kg)
J
Service Valve Locations
J 3.46 (88) 3.19 (81) 3.46 (88) 4.02 (102) K 3.46 (88) 5.63 (143) 3.62 (92) 6.57 (167)
in. (mm)
9K
K
12K
in. (mm)
J
K
18K
in. (mm)
K
J
A07376a
24K
in. (mm)
J
K
5
CLEARANCES -- INDOOR
38/40MVC, MVQ
CLEARANCES -- OUTDOOR
5
"
(0.13m)
min.
6" (0.15m) min.
(1.8m)
6'
Fig. 2 – Indoor unit clearance
5
"
(0.13m)
min.
A07891
A
D
UNIT 9k and 12k in. (mm)
A 24 (610)
B 24 (610) C 24 (610)
D 6 (152) E 12 (305)
B
Fig. 3 – Outdoor Unit Clearance
Air-inlet
E
C
Air-outlet
A07894
18k and 24k in. (mm)
24 (610) 36 (914) 24 (610)
6 (152)
12 (305)
6
PHYSICAL DATA
Outdoor Unit 38MVC 009 012 012 018 24
System Voltage 115 V 115 V 208/230 208/230 208/230 Nominal Capacity (Btuh) 9000 12000 12000 18000 24000 Operating Weight lb(kg) 70.4(32) 79.2(36) 79.2(36) 116.6(53) 149.6(68) Refrigerant Type R--- 410A Metering Device Capillary Tube at Outdoor Charge lb (kg) 2.3 (1.0) 2.9 (1.3) 3.0 (1.4) 4.4 (2.0) 5.3 (2.4) Compressor
Type Rotary Model EA82X1C--- 1FZDU1 EA108X1C--- 1FZDU1 PA108X1C---3FZDU PA150X2CS--- 3KUU PA200X2CS ---3MUU O il C h a r g e ( POE --- o z ) 11.8 11.8 11.8 25.4 25.4
Outdoor Fan
Rpm 900 900 900 840 740 Diameter (in) .. No. of Blades 15.8 … 3 15.8 … 3 15.8 … 3 18.1 … 3 18.1 … 3 Motor (watts / hp) 23 / 0.102 23 / 0.102 23 / 0.102 53 / 0.224 100 / 0.218
Outdoor Coil
Face Area ( sq. ft) 4.05 3.94 3.94 5.51 6.67 No. Rows 2 2 2 4 3 Fins per inch 17 17 17 18 18 Circuits 4 4 4 4 6
Refrigerant Lines
Connection Type Flare Liquid (Mix Phase) (in) OD 1/4” 1/4” 1/4” 1/4” 3/8” Vapor Line (in) OD 3/8” 1/2” 1/2” 1/2” 5/8” Maximum Length* ft (m) 65 (20.0) 65 (20.0) 65 (20.0) 100 (30.4) 100 (30.4) MaxLift(FanCoilAbove)ft(m) 35 (10.7) 35 (10.7) 35 (10.7) 50 (12.2) 60 (18.3) Max Drop (Fan Coil Below)ft (m) 35 (10.7) 35 (10.7) 35 (10.7) 50 ( 12.2) 60 (18.3)
Controls
Control Voltage 13 VDC 13 VDC 13 VDC Pulse DC Pulse D C
External Finish White White White White White
38/40MVC, MVQ
Outdoor Unit
38MVQ
System Voltage 115 V 115 V 208/230 208/230 208/230 Nominal Capacity (Btuh) 9000 12000 12000 18000 24000 Operating Weight lb(kg) 72.6 (33) 83.6 (38) 83.6 (38) 117.7 (53.5) 151.0 (68.5) Refrigerant Type R--- 410A Metering Device Capillary Tube at Outdoor Charge lb (kg) 2.4 (1.1) 3.0 (1.4) 3.0 (1.4) 4.5 (2.0) 5.3 (2.4) Compressor
Type Rotary Model EA82X1C---1FZDU1 EA108X1C---1FZDU1 PA108X1C --- 3FZDU PA150X2CS --- 3KUU PA200X2CS--- 3MUU O il C h a r g e ( POE --- o z ) 11.8 11.8 11.8 25.4 25.4
Outdoor Fan
Rpm 900 900 900 840 740 Diameter (in) .. No. of Blades 15.8 … 3 15.8 … 3 15.8 … 3 18.1 … 3 18.1 … 3 Motor (watts / hp) 23 / 0.102 23 / 0.102 23 / 0.102 53 / 0.224 100 / 0.218
Outdoor Coil
Face Area ( sq. ft) 4.05 3.94 3.94 5.51 6.67 No. Rows 2 2 2 2 3 Fins per inch 17 18 18 18 18 Circuits 4 4 4 4 6
Refrigerant Lines
Connection Type Flare Liquid Line (in) OD 1/4” 1/4” 1/4” 1/4” 3/8” Vapor Line (in) OD 3/8” 1/2” 1/2” 1/2” 5/8” Maximum Length* ft (m) 65 (20.0) 65 (20.0) 65 (20.0) 100 (30.4) 100 (30.4) MaxLift(FanCoilAbove)ft(m) 35 (10.7) 35 (10.7) 35 (10.7) 50 (12.2) 60 ( 18.3) Max Drop (Fan Coil Below)ft (m) 35 (10.7) 35 (10.7) 35 (10.7) 50 (12.2) 60 (18.3)
Controls
Control Voltage 13 VDC 13 VDC 13 VDC Pulse D C Pulse DC
Finish White White White White White
* Refer to Long Line Application section on page 21
009 012 012 018 024
7
PHYSICAL DATA (CONT.)
Indoor Unit 40MVC 009 012 018 024
System Voltage 115 115 or 208/230 208/230 208/230 Nominal Capacity (Btuh) 9000 12000 18000 24,000 Operating Weight lb(kg) 17.6(8) 25.3(11.5) 39.6(18) 39.6(18) Refrigerant Type R--- 410A Metering Device Capillary Tube at Outdoor Charge (lb) 2.3(1.0) 2.9(1.3) 4.4(2.0) 5.3(2.4) Indoor Fan
Rpm/Cfm (High) 1250/325 1270/425 1070/630 1070/750 Rpm/Cfm (Medium) 1000/260 1100/365 1000/570 1000/660 Rpm/Cfm (Low) 800/190 1000/340 960/500 960/ 585 Motor (Watts / hp) 20 / .034 25 / .044 31 / .075 50 / .112 Blower Diameter Length (in) 3.84 25.87 4.17 25.2 4.21 37.6 4.21 37.6
Indoor Coil
Face Area ( sq. ft) 2.15 2.54 4.36 4.36 No. Rows 2 2 2 2 Fins per inch 19.5 19.5 19.5 19.5 Circuits 2 3 6 6
Controls Integrated Microprocessor
Remote Controller Wireless Fan Mode High/Medium/Low/Auto Turb o M o de Ye s Yes No No Dehumidification Mode Ye s Sleep Mode Ye s Diagnostics Ye s
38/40MVC, MVQ
Timer Mode Ye s Freeze Protection Ye s Tes t Mo de Ye s Auto Restart Yes Auto Sweep Ye s Control Voltage 13 VDC 13 VDC Pulse DC Pulse D C
Refrigerant Lines
Connection Type Flare Liquid Line (in) OD 1/4” 1/4” 1/4” 3/8” Vapor Line (in) OD 3/8” 1/2” 1/ 2” 5/8” Maximum Length ft(m)* 65(19.8) 65(19.8) 100(30.5) 100(30.5) Max Lift (Fan Coil Above) ft(m) 35(10.7) 35(10.7) 50(15.2) 60(18.3) Max Drop (Fan Coil Below) ft(m) 35(10.7) 35(10.7) 50(15.2) 60(18.3)
Condensate Drain
Size (in) .65 (OD) .53 (ID) .65 (OD) .53 (ID) .65 (OD) .53 (ID) .65 (OD) .53 ( ID)
External Finish White White White White
* Refer to Long Line Application section on page 21
8
PHYSICAL DATA (CONT.)
Indoor Unit 40MVQ 009 012 018 024 System Voltage 115 115 or 208/230 208/230 208/230 Nominal Capacity (Btuh) 9000 12000 18000 24000 Operating Weight lb (kg) 17.6 (8) 25.3 (11.5) 39.6 (18) 39.6 (18) Refrigerant Type R--- 410A Metering Device Capillary Tube at Outdoor Charge lb (kg) 2.35 (1.1) 3.0 (1.4) 4.5 (2.0) 5.3 (2.4) Indoor Fan
Rpm/Cfm (High) 1250/325 1270/425 1070/630 1070/750 Rpm/Cfm (Medium) 1000/260 1100/365 1000/570 1000/660 Rpm/Cfm (Low) 800/190 1000/340 960/500 960/585 Motor (Watts / hp) 20 / .034 25 / .044 31 / .075 50 / .112 Blower Diameter Length (in) 3.84 25.87 4.17 25.2 4.21 37.6 4.21 37.6
Indoor Coil
Face Area ( sq. ft) 2.15 2.54 4.36 4.36 No. Rows 2 2 2 2 Fins per inch 19.5 19.5 19.5 19.5 Circuits 2 3 6 6
Controls Integrated Microprocessor
Remote Controller Wireless Fan M ode High/Medium/Low/Auto Auto Changeover Ye s Dehumidification Mode Ye s Demand Defrost Ye s Sleep Mode Ye s Diagnostics Yes Timer Mode Ye s Freeze Protection Yes Tes t Mo de Ye s Auto Restart Yes Auto Sweep Ye s Control Voltage 13 VDC 13 VDC Pulse DC Pulse DC
Refrigerant Lines
Connection Type Flare Liquid Line (in) OD 1/4” 1/4” 1/4” 3/8” Vapor Line (in) OD 3/8” 1/2” 1/2” 5/8” Maximum Length* ft (m) 65 (19.8) 65 (19.8) 100 ( 30.5) 100 (30.5) MaxLift(FanCoilAbove)ft(m) 35 (10.7) 35 (10.7) 50 (15.2) 60 (18.3) Max Drop (Fan Coil Below) ft (m) 35 (10.7) 35 (10.7) 50 (15.2) 60 (18.3)
Condensate Drain
Size (in) .65 (OD) .53 (ID) .65 (OD) .53 ( ID) .65 (OD) .53 (ID) .65 (OD) .53 (ID)
External Finish White White White White
* Refer to Long Line Application section on page 21
38/40MVC, MVQ
9
PERFORMANCE DATA
Te m p _F(_C)
Air Entering
38/40MVC, MVQ
Condenser
55
(12.78)
65
(18.33)
75
(23.89)
85
(29.44)
95
(35)
105
(40.56)
115
(46.11)
125
(51.67)
(Edb)
TCG 7.70 8.60 9.37 10.14 9.08 9.34 10.07 10.66 9.75 9.74 10.44 10.93 SHG 7.44 6.61 5.80 4.95 9.08 7.59 6.45 5.29 9.75 8.30 6.95 5.50
TC 7.69 8.58 9.36 10.12 9.07 9.32 10.06 10.65 9.74 9.72 10.42 10.92
kW 0.48 0.48 0.48 0.47 0.48 0.48 0.47 0.47 0.48 0.48 0.47 0.47 CMP 0.39 0.39 0.39 0.38 0.39 0.39 0.38 0.38 0.39 0.39 0.38 0.38 LDB 45.0 48.9 52.8 56.9 48.4 53.5 57.6 61.7 52.9 56.9 60.7 64.8 LWB 40.9 45.6 50.8 56.2 43.3 49.2 54.5 60.2 45.4 51.6 56.9 62.6 TCG 7.40 8.31 9.14 9.95 8.88 9.08 9.87 10.51 9.53 9.50 10.27 10.81 SHG 7.40 6.57 5.71 4.88 8.88 7.55 6.41 5.25 9.53 8.34 6.98 5.51
TC 7.38 8.29 9.13 9.93 8.86 9.07 9.85 10.50 9.52 9.48 10.26 10.80
kW 0.54 0.55 0.55 0.54 0.55 0.55 0.54 0.54 0.55 0.55 0.54 0.54 CMP 0.45 0.45 0.46 0.45 0.46 0.46 0.45 0.45 0.45 0.45 0.45 0.45 LDB 45.1 49.1 53.2 57.2 49.1 53.6 57.7 61.9 53.5 56.7 60.6 64.8 LWB 41.6 46.2 51.2 56.5 43.6 49.6 54.8 60.3 45.7 51.9 57.1 62.7 TCG 7.50 7.94 8.88 9.73 8.56 8.72 9.57 10.33 9.28 9.12 10.00 10.61 SHG 7.50 6.52 5.62 4.80 8.56 7.49 6.33 5.21 9.28 8.24 6.93 5.50
TC 7.49 7.93 8.87 9.71 8.54 8.70 9.55 10.31 9.26 9.10 9.98 10.60
kW 0.61 0.61 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 CMP 0.52 0.52 0.53 0.52 0.52 0.53 0.53 0.52 0.53 0.53 0.52 0.52 LDB 44.7 49.2 53.6 57.6 50.1 53.8 57.9 62.0 54.2 57.0 60.7 64.8 LWB 41.4 47.0 51.7 56.9 44.1 50.1 55.2 60.6 46.0 52.3 57.4 62.8 TCG 7.20 7.55 8.50 9.42 8.20 8.09 9.25 10.04 8.99 8.72 9.62 10.34 SHG 7.20 6.49 5.52 4.67 8.20 7.34 6.28 5.12 8.99 8.23 6.86 5.44
TC 7.18 7.53 8.48 9.41 8.19 8.07 9.23 10.03 8.97 8.71 9.61 10.33
kW 0.68 0.69 0.69 0.70 0.69 0.69 0.70 0.70 0.70 0.70 0.70 0.70 CMP 0.59 0.59 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 LDB 46.0 49.3 54.0 58.2 51.3 54.3 58.1 62.3 54.9 57.0 60.9 65.0 LWB 42.1 47.8 52.5 57.5 44.7 51.1 55.6 60.9 46.4 52.7 57.8 63.1 TCG 6.86 7.02 8.06 9.06 7.82 7.63 8.86 9.66 8.57 8.22 9.22 9.98 SHG 6.86 6.37 5.42 4.53 7.82 7.28 6.20 5.00 8.57 8.22 6.83 5.35
TC 6.85 7.00 8.05 9.05 7.80 7.61 8.85 9.64 8.55 8.20 9.21 9.97
kW 0.76 0.76 0.77 0.78 0.77 0.77 0.78 0.78 0.78 0.78 0.78 0.78 CMP 0.66 0.67 0.68 0.69 0.67 0.67 0.68 0.69 0.68 0.68 0.69 0.69 LDB 47.5 49.8 54.4 58.8 52.6 54.4 58.3 62.7 56.0 57.0 60.9 65.2 LWB 42.8 48.9 53.3 58.1 45.3 51.7 56.2 61.4 46.9 53.3 58.2 63.4 TCG 6.40 6.54 7.59 8.70 7.39 7.09 8.26 9.20 8.10 8.10 8.73 9.56 SHG 6.40 6.19 5.28 4.40 7.39 7.09 6.11 4.86 8.10 8.10 6.74 5.26
TC 6.39 6.53 7.58 8.69 7.38 7.07 8.25 9.19 8.08 8.09 8.72 9.54
kW 0.84 0.85 0.86 0.87 0.86 0.85 0.87 0.87 0.86 0.86 0.87 0.87 CMP 0.75 0.75 0.76 0.77 0.76 0.76 0.77 0.77 0.77 0.77 0.77 0.78 LDB 49.6 50.6 55.0 59.4 54.0 55.0 58.6 63.1 57.3 57.3 61.2 65.4 LWB 43.9 49.9 54.2 58.7 46.0 52.5 57.0 61.9 47.5 53.4 58.7 63.8 TCG 5.87 5.81 7.03 8.09 6.91 6.91 7.64 8.67 7.59 7.59 8.01 8.99 SHG 5.87 5.79 5.08 4.18 6.91 6.91 5.97 4.70 7.59 7.59 6.61 5.10
TC 5.85 5.80 7.01 8.08 6.89 6.90 7.63 8.65 7.57 7.57 7.99 8.97
kW 0.93 0.93 0.95 0.96 0.95 0.95 0.96 0.97 0.96 0.96 0.96 0.97 CMP 0.83 0.83 0.85 0.86 0.85 0.85 0.86 0.87 0.86 0.86 0.86 0.87 LDB 52.0 52.4 55.9 60.3 55.6 55.6 59.0 63.6 58.7 58.7 61.5 65.8 LWB 45.0 51.3 55.2 59.7 46.7 52.8 57.8 62.5 48.1 54.0 59.4 64.3 TCG 5.33 5.33 6.22 7.44 6.37 6.37 6.80 8.09 7.03 7.03 7.00 8.35 SHG 5.33 5.33 4.75 3.96 6.37 6.37 5.71 4.54 7.03 7.03 6.31 4.96
TC 5.31 5.31 6.21 7.42 6.35 6.35 6.78 8.07 7.02 7.02 6.99 8.33
kW 1.03 1.03 1.04 1.06 1.04 1.04 1.05 1.07 1.05 1.05 1.05 1.07 CMP 0.93 0.93 0.94 0.96 0.94 0.94 0.95 0.97 0.95 0.95 0.95 0.97 LDB 54.4 54.5 57.3 61.3 57.5 57.5 59.8 64.1 60.2 60.2 62.2 66.2 LWB 46.2 52.3 56.7 60.8 47.6 53.5 58.8 63.2 48.8 54.6 60.4 64.9
57
(13.89)62(16.67)67(19.44)72(22.22)57(13.89)62(16.67)67(19.44)72(22.22)57(13.89)62(16.67)67(19.44)72(22.22)
COOLING CAPACITIES
38MVC(Q)009--1 / 40MVC(Q)009--1
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
190/0.04 259/0.04 327/0.05
Air Entering Evaporator --- Ewb _F(_C)
LEGEND
BF --- Bypass Factor CMP --- Compressor Edb --- Entering Dry Bulb Ewb --- Entering Wet Bulb k W --- Tota l Po w e r LDB --- Leaving Dry Bulb L WB --- L e a v i n g Wet Bu l b SHG --- Gross Sensible Capacity (1000 Btu/hour) TC --- Total Net Cooling Capacity (1000 Btu/hour)
---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil. Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG. Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
10
PERFORMANCE DATA (CONT.)
38MVC(Q)012--1 / 40MVC(Q)012--1
Te m p _F(_C)
Air Entering
Condenser
(Edb)
55
(12.78)
65
(18.33)
75
(23.89)
85
(29.44)
95
(35)
105
(40.56)
115
(46.11)
125
(51.67)
57 (13.89)
TCG 11.97 12.10 12.93 13.50 12.26 12.28 13.10 13.60 12.71 12.61 13.33 13.76
SHG 11.97 9.93 8.34 6.68 12.26 10.27 8.58 6.77 12.71 10.96 8.95 6.97
TC 11.94 12.07 12.90 13.47 12.23 12.25 13.07 13.57 12.68 12.58 13.30 13.74
kW 0.63 0.63 0.62 0.62 0.63 0.63 0.62 0.62 0.62 0.62 0.62 0.62
CMP 0.53 0.53 0.53 0.53 0.53 0.53 0.53 0.53 0.53 0.53 0.53 0.53
LDB 48.2 53.5 57.8 62.4 49.8 54.6 58.9 63.5 53.0 56.6 61.0 65.3
LWB 43.2 49.4 54.8 60.6 44.0 50.2 55.7 61.4 45.5 51.7 57.2 62.9
TCG 11.64 11.71 12.64 13.30 11.94 11.91 12.79 13.37 12.44 12.25 13.07 13.52
SHG 11.64 9.78 8.27 6.66 11.94 10.15 8.49 6.73 12.44 10.95 9.02 6.90
TC 11.61 11.68 12.61 13.27 11.91 11.88 12.76 13.34 12.41 12.22 13.04 13.49
kW 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72
CMP 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62
LDB 49.0 53.9 58.0 62.4 50.6 54.9 59.1 63.5 53.5 56.6 60.8 65.4
LWB 43.6 49.8 55.1 60.8 44.3 50.6 55.9 61.6 45.7 52.1 57.4 63.1
TCG 11.28 11.27 12.27 13.00 11.56 11.45 12.43 13.12 12.07 11.48 12.70 13.25
SHG 11.28 9.63 8.15 6.61 11.56 9.92 8.47 6.75 12.07 10.16 8.94 6.89
TC 11.25 11.24 12.24 12.97 11.53 11.43 12.40 13.09 12.04 11.46 12.67 13.23
kW 0.81 0.81 0.82 0.82 0.81 0.81 0.82 0.82 0.82 0.82 0.82 0.82
CMP 0.71 0.71 0.71 0.72 0.71 0.71 0.71 0.72 0.71 0.71 0.71 0.72
LDB 49.9 54.3 58.3 62.5 51.5 55.5 59.1 63.5 54.3 58.3 60.9 65.4
LWB 44.0 50.3 55.5 61.1 44.8 51.2 56.3 61.9 46.1 52.7 57.7 63.3
TCG 10.79 10.76 11.78 12.63 11.12 10.68 11.96 12.76 11.63 11.29 12.24 12.93
SHG 10.79 9.24 7.98 6.49 11.12 9.50 8.25 6.64 11.63 10.62 8.81 6.89
TC 10.76 10.73 11.76 12.60 11.09 10.65 11.93 12.73 11.60 11.27 12.21 12.91
kW 0.91 0.91 0.92 0.92 0.92 0.91 0.92 0.93 0.92 0.92 0.92 0.93
CMP 0.81 0.81 0.82 0.82 0.81 0.81 0.82 0.82 0.82 0.82 0.82 0.82
LDB 51.2 55.3 58.7 62.8 52.5 56.4 59.6 63.7 55.2 57.3 61.2 65.4
LWB 44.6 51.5 56.0 61.4 45.3 52.0 56.7 62.2 46.5 52.8 58.0 63.5
TCG 10.17 9.76 11.21 12.15 10.55 10.05 11.37 12.27 11.12 11.12 11.66 12.49
SHG 10.17 9.14 7.81 6.32 10.55 9.50 8.08 6.47 11.12 11.12 8.64 6.79
TC 10.14 9.73 11.18 12.12 10.53 10.02 11.34 12.24 11.09 11.09 11.63 12.46
kW 1.02 1.01 1.03 1.04 1.02 1.02 1.03 1.04 1.03 1.03 1.03 1.04
CMP 0.91 0.91 0.92 0.93 0.92 0.91 0.92 0.93 0.92 0.92 0.93 0.93
LDB 52.7 55.4 59.1 63.2 53.8 56.4 60.0 64.1 56.2 56.2 61.5 65.6
LWB 45.4 52.0 56.6 61.8 45.9 52.5 57.3 62.6 47.0 53.0 58.5 63.8
TCG 9.51 8.95 10.54 11.55 9.87 9.86 10.70 11.68 10.54 10.55 10.96 11.88
SHG 9.51 8.73 7.59 6.12 9.87 9.86 7.88 6.28 10.54 10.55 8.44 6.60
TC 9.48 8.92 10.51 11.52 9.84 9.84 10.68 11.65 10.52 10.52 10.93 11.85
kW 1.13 1.12 1.14 1.15 1.13 1.13 1.14 1.15 1.14 1.14 1.15 1.16
CMP 1.02 1.01 1.04 1.05 1.03 1.03 1.04 1.05 1.04 1.04 1.04 1.05
LDB 54.4 56.5 59.7 63.7 55.5 55.5 60.4 64.6 57.4 57.4 61.9 66.0
LWB 46.2 52.9 57.2 62.4 46.7 52.7 57.9 63.1 47.5 53.5 59.0 64.2
TCG 8.82 8.82 9.56 10.82 9.16 9.16 9.82 10.96 9.81 9.81 10.17 11.16
SHG 8.82 8.82 7.29 5.87 9.16 9.16 7.61 6.04 9.81 9.81 8.21 6.37
TC 8.79 8.79 9.53 10.79 9.13 9.13 9.80 10.93 9.78 9.78 10.14 11.13
kW 1.25 1.25 1.26 1.28 1.25 1.25 1.26 1.28 1.26 1.26 1.27 1.28
CMP 1.14 1.14 1.15 1.17 1.14 1.14 1.15 1.17 1.15 1.15 1.16 1.17
LDB 56.2 56.2 60.4 64.4 57.2 57.1 61.0 65.1 58.9 58.9 62.4 66.4
LWB 47.0 53.0 58.2 63.0 47.4 53.4 58.7 63.6 48.2 54.1 59.6 64.7
TCG 8.11 8.14 8.49 9.97 8.42 8.41 8.65 10.10 9.01 9.01 8.81 10.30
SHG 8.11 8.14 6.97 5.59 8.42 8.41 7.18 5.77 9.01 9.01 7.63 6.11
TC 8.08 8.11 8.46 9.94 8.39 8.38 8.63 10.07 8.99 8.98 8.78 10.27
kW 1.37 1.37 1.37 1.40 1.37 1.37 1.38 1.40 1.39 1.39 1.38 1.41
CMP 1.26 1.26 1.26 1.29 1.26 1.26 1.27 1.29 1.27 1.27 1.27 1.29
LDB 58.1 58.0 61.2 65.1 58.9 58.9 62.1 65.7 60.5 60.6 63.5 66.9
LWB 47.9 53.7 59.2 63.8 48.2 54.1 59.7 64.3 49.0 54.8 60.7 65.3
339/0.04 367/0.04 427/0.05
62
(16.67)67(19.44)72(22.22)57(13.89)62(16.67)67(19.44)72(22.22)57(13.89)62(16.67)67(19.44)72(22.22)
COOLING CAPACITIES
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
Air Entering Evaporator --- Ewb _F(_C)
38/40MVC, MVQ
LEGEND
BF --- Bypass Factor CMP --- Compressor Edb --- Entering Dry Bulb Ewb --- Entering Wet Bulb k W --- Tota l Po w e r LDB --- Leaving Dry Bulb L WB --- L e a v i n g Wet Bu l b SHG --- Gross Sensible Capacity (1000 Btu/hour) TC --- Total Net Cooling Capacity (1000 Btu/hour)
---
11
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil. Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG. Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Loading...