Carrier 38MHR series Installation Instructions Manual

38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
PAGE
PARTS LIST 3.......................................
SYSTEM REQUIREMENTS 4...........................
DIMENSIONS − OUTDOOR 5..........................
INSTALLATION TIPS 9................................
OUTDOOR UNIT INSTALLATION 9.....................
ELECTRICAL DATA 11...............................
CONNECTION DIAGRAMS 11.........................
SYSTEM VACUUM AND CHARGE 12...................
START−UP 13........................................
OUTDOOR UNIT DIAGNOSTIC GUIDES 13..............
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air−conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start−up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as coil cleaning. All other operations should be performed by trained service personnel only.
When working on the equipment, observe the precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. W ear safety glasses and work gloves. Keep a quenching cloth and a fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information.
!
!
This is the safety−alert symbol the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start−up.
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
CAUTION
2
PARTS LIST
Table 1—Parts List
PART NO. PART NAME QTY.
1 Outdoor unit 1
- Literature package including installation instructions and warranty 1
- Grommet to secure the outdoor unit (helps with vibration prevention during unit operation) 4
- Drain Joint 1
- Drain Hose 1
■ Outdoor
1
Fig. 1 - Parts List
NOTE:
− If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe before it enters the wall to the indoor unit. This ensures that rain drips from the connection pipe before it enters the wall.
− Piping and the interconnecting wiring are field supplied.
− The illustration above is only a sketch. Different models may be slightly different.
The following units are covered in these installation instructions.
Table 2—Unit Sizes
SYSTEM TONS BTUh VOLTAGE - PHASE OUTDOOR MODEL
0.75 9,000 115-1 38MHRC09A--1
1.00 12,000 115-1 38MHRC12A--1
Cooling Only
Heating Pump
0.75 9,000 208/230-1 38MHRC09A--3
1.00 12,000 208/230-1 38MHRC12A--3
1.50 18,000 208/230-1 38MHRC18A--3
2.00 24,000 208/230-1 38MHRC24A--3
0.75 9,000 115-1 38MHRQ09A--1
1.00 12,000 115-1 38MHRQ12A--1
0.75 9,000 208/230-1 38MHRQ09A--3
1.00 12,000 208/230-1 38MHRQ12A--3
1.50 18,000 208/230-1 38MHRQ18A--3
2.00 24,000 208/230-1 38MHRQ24A--3
A150766
3
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and service of the unit. See Fig. 5 for the required minimum distances between the unit, walls or ceilings.
Piping IMPORTANT: Both refrigerant lines must be insulated separately.
S Table 3 contains piping information for the product covered within this document.
T able 3—Piping and Refrigerant Information
System Size 9K (115V) 12V (115V) 9K (208-230V) 12K (208-230V) 18 (208-230V) 24K (208-230V)
Min. Piping Length ft. (m) 10(3) 10(3) 10(3) 10(3) 10(3) 10(3)
Piping
Refrigerant
Standard Piping Length
Max. outdoor-indoor height difference (OU higher than IU)
Max. outdoor-indoor height difference (IU higher than OU)
Max. Piping Length with no additional refrigerant charge per System (Standard Piping length)
Total Max. Piping Length per system
Additional refrigerant charge (between Standard – Max piping length)
Suction Pipe (size - connection type)
Liquid Pipe (size - connection type)
Refrigerant Type Type R410A R410A R410A R410A R410A R410A
Cooling Only Models Charge Amount
Heat Pump Models Charge Amount
ft. (m)
ft. (m)
ft. (m)
ft. (m) 25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5)
ft. (m) 82(25) 82(25) 82(25) 82(25) 98(30) 164(50)
Oz/ft
(g/m)
In (mm) 3/8(9.52) 1/2(12.7) 3/8(9.52) 1/2(12.7) 1/2(12.7) 5/8(15.9)
In (mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.52)
Lbs (kg) 1.06(0.48) 1.30(0.59) 1.06(0.48) 1.30(0.59) 2.09(0.95) 2.65(1.2)
Lbs (kg) 1.76(0.8) 2.12(0.96) 1.76(0.8) 2.12(0.96) 3.30(1.5) 3.968(1.8)
25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5)
33(10) 33(10) 33(10) 33(10) 33(10) 33(10)
33(10) 33(10) 33(10) 33(10) 33(10) 33(10)
0.161(15) 0.161(15) 0.161(15) 0.161(15) 0.161(15) 0.322(30)
All outdoor units have an electronic expansion valve to manage the refrigerant flow of the fan coil connected.
Wiring
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use the Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the
Communication Wiring:
A separate shielded stranded copper conductor only, with a 600 volt rating and double insulated copper wire, must be used as the communication wire from the outdoor unit to the indoor unit. Please use a separate shielded 16GA stranded control wire.
disconnect fuse or breakers respectively. Per the caution note, only stranded copper conductors with a 600
!
CAUTION
volt rating and double insulated copper wire must be used. The use of BX cable is not recommended.
Recommended Connection Method for Power and Communication Wiring − Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3 power/communication wiring from the outdoor unit to the indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are high voltage AC power, one is
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes. S Use copper conductors only with a minimum 600 volt
rating and double insulated copper wire.
communication wiring and the other is a ground wire.
Recommended Connection Method for Power and Communication Wiring (To minimize communication wiring interference) Power Wiring:
The main power is supplied to the outdoor unit. The field supplied power wiring from the outdoor unit to the indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire. To minimize voltage drop, the factory recommended wire size is 14/2 stranded with a ground.
4
DIMENSIONS − OUTDOOR
System Size Height (H) in. (mm) Width (W) in. (mm) Depth (D) in. (mm) Weight-Net lbs. (kg)
9K (115) 21.85(555) 30.31(770) 11.81(300) 57.3(26)
Cooling
Only
Heat
Pump
12K (115V) 21.85(555) 30.31(770) 11.81(300) 57.8(26.2)
9K (208/230V) 21.85(555) 30.31(770) 11.81(300) 54.7(24.8)
12K (208/230V) 21.85(555) 30.31(770) 11.81(300) 53.8(24.4)
18K (208/230V) 21.81(554) 31.50(800) 13.11(333) 70.1(31.8)
24K (208/230V) 27.64(702) 33.27(845) 14.29(363) 88.6(40.2)
System Size Height (H) in. (mm) Width (W) in. (mm) Depth (D) in. (mm) Weight-Net lbs. (kg)
9K (115) 21.85(555) 30.31(770) 11.81(300) 61.5(27.9)
12K (115V) 21.85(555) 30.31(770) 11.81(300) 65.0(29.5)
9K (208/230V) 21.85(555) 30.31(770) 11.81(300) 57.1(25.9)
12K (208/230V) 21.85(555) 30.31(770) 11.81(300) 60.6(27.5)
18K (208/230V) 21.81(554) 31.50(800) 13.11(333) 94.6(42.9
24K (208/230V) 27.64(702) 33.27(845) 14.29(363) 105.2(47.7)
T able 4—Dimensions and Weights
30.66(779) W3
11.81(300) D
H
21.85(555)
0.47(12)
19.17(487) W1
30.31(770) W
2.76(70) W
0.98(25) B1
D3
D2
3.54(90) B2
D1
11.26(286)
13.07(322)
2.36(60)
2.42(61.5) A2
11.73(298)
H1
H2
Unit: inch(mm)
3.66(93)
R
.24(6)
0
0.47(12) A1
Fig. 2 - Sizes 9K and 12K
5
Loading...
+ 9 hidden pages