Installing, starting up, and servicing air--conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by
trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep
quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult
local building codes and current editions of the National Electrical
Code ( NEC ) NFPA 70. In Canada, refer to current editions of the
Canadian electrical code CSA 22.1.
!
Recognize safety information. This is the safety--alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words: DANGER, WARNING, and CAUTION.
These words are used with the safety--alert symbol. DANGER
identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which could
result in personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
!
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 mm) vertical rise to the valve connections on
.
the outdoor units. If more than the recommended length is
buried, refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start--up.
WARNING
CAUTION
GENERAL
These instruc t ions cove r the install ation, start--up and servicing of the
multi--zone outdoor unit connect ed to up to five indoor fan coi l units.
For approved combinations , please refer to t he Product Data .
2
PIPING REQUIREMENTS
IMPORTANT: Both refrigerant lines must be insulated separately .
The minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m). The following lengths are allowed.
Table 1—Piping Lengths
Min. Piping Length per each indoor unitft (m)10 (3)10 (3)10 (3)10 (3)
Standard Piping Length per each indoor unitft (m)25 (7.5)25 (7.5)25 (7.5)25 (7.5)
Max. outdoor---indoor height difference
(OU higher than IU)
Max. outdoor---indoor height difference
(IU higher than OU)
Max. height different between indoor unitsft (m)32(10)32(10)32(10)32(10)
Piping
Refrigerant
Max. Length per each indoor unitft (m)66(20)82(25)98(30)98(30)
Max. Piping Length with no additional
refrigerant charge per System (Standard Piping
length x No. of Zones)
Total Maximum Piping Length per systemFt. (m)98(30)147(45)196(60)245(75)
Additional refrigerant charge
(between Standard – Max piping length)
NOTE: The refrigerant charge included is adequate for the number of zones multiplied by the maximum piping length per zone with no additional
refrigerant.
Indoor High Wall
Indoor Cassette
Indoor Ducted
Indoor Floor Console
Refrigerant Piping:
Line sets to be sized based on the connection size of the indoor unit. Each pipe should be insulated individually.
Conversion Joints:
The outdoor unit may include a package of conversion joints to facilitate installation of various sizes of fan coils. These joints are to be
connected to the outdoor unit as needed to match the line set size.
Sum Total Liquid Pipe ft. (m) --- Additional Charge Required After ft. (m.) x Additional Charge oz./ft. (g/m) 0.16 (15)
NOTES:
If the calculation results in a negative number no additional refrigerant is required.
ELECTRONIC EXPANSION VALVES IN THE OUTDOOR UNIT ARE USED AS METERING DEVICES.
SYSTEM VOLTAGEOPERATING VOLTAGECOMPRESSOROUTDOOR FANMCA
VOLT/PHASE/HZMAX / MINRLAFLAHPW
208---230/1/60253 / 187
9.7
MAX
FUSE/CB
AMP
30.16501520
30.161201925
30.161202740
30.11852950
4
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a minimum 600 volt .
rating and 2/64--inch thick insulation.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
S Be sure to comply with local codes while running wire from
indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Therefore, be sure all wiring is
tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through hole
in the conduit panel.
CAUTION
CAUTION
All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use the
Electrical Data table MCA (minimum circuit amps) and MOCP
(maximum over current protection) to correctly size the wires and
the disconnect fuse or breakers respectively.
Per the caution note, use only copper conductors with a minimum
600 volt rating and 2/64 --inch thick insulation. The use of BX
cable is not recommended.
Recomme nde d Connection Method for Power and
Communication --W i ring -- Power and Communication Wi r ing:
The main power is supplied to the outdoor unit. The field supplied
14/3 power/communication wiring from the outdoor unit to indoor
unit consists of four (4) wires and provides the power for the
indoor unit. Two wires are high voltage AC power; one is
communication wiring and the other is a ground wire.
Recomme nde d Connection Method for Power and
Communication Wiring (To minimize communicati on wiring
interference)
Power Wiring:
The main power is supplied to the outdoor unit. The field suppl i ed
power wiring from the outdoor unit to the indoor unit consist s of three
(3) wires and pr ovides the power for the indoor unit. Two wires are
high voltage AC power and one is a ground wire. T o minimize a
voltage drop, t he factory recomm ended wire size is 14/2 stranded with
a ground.
Communication Wiring:
A separate shielded copper conductor only, with a minimum 600
volt rating and 2/64--inch thick insulation, must be used as the
communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.