40QAC / 38HDR
40QAQ / 38QRR
Ceiling---Suspended Duct Free S plit System
Sizes 018 to 060
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
AN INEXPENSIVE AND CREATIVE
SOLUTION TO DESIGN PROBLEMS.
The 38HDR(QRR)/40QAC(QAQ) series duct--free split systems
are a matched combination of an outdoor condensing unit and an
indoor fan coil unit connected only by refrigerant tubing and wires.
The ceiling--suspended fan coils are ideal for retrofit and
modernization projects where it is impractical or prohibitively
expensive to run ductwork and where there are no false ceilings or
wall space available.This selection of fan coils permits
inexpensive and creative solutions to design problems such as:
the environmentally sound refrigerant
The ideal compliment to your ducted system when it is impractical
or prohibitively expensive to use ductwork.
SSpecial space requirements such as garages.
SWhen changes in the load cannot be handled by the
existing system like restaurants.
SWhen adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork like
schools.
SHistorical renovations or any application where
preserving the look of the original structure is essential
like churches.
These compact indoor fan coil units blend nicely with most
ceilings and protrude less than 10 inches (254 mm) from the
ceiling.Advanced system components incorporate innovative
technology to provide reliable cooling performance at low sound
levels.
LOW SOUND LEVELS
R
When noise is a concern, ceiling--suspended duct--free split systems
are the answer. The indoor units are whisper quiet. There are no
compressors indoors, either in the conditioned space or directly
over it, and there is none of the noise usually generated by air
being forced through ductwork.
When sound ordinances and proximity to neighbors demand quiet
operation, the 38HDR/QRR unit is the right choice: The advanced,
blow--through horizontal airflow design distributes air more evenly
over the coil.
BUILT--IN RELIABILITY
Duct--free split system indoor and outdoor units are designed to
provide years of trouble--free operation.
The high wall indoor units include protection against freeze--up.
The condensing units and heat pumps are also protected. There is
a three minute time delay before the compressor will start.
An oversized accumulator on heat pumps, high and low pressure
switches ( loss of pressure switch on heat pumps), and compressor
internal overload protection will ensure a robust system that is ideal
for light commercial applications.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only
by refrigerant piping and wiring to prevent intruders from crawling
through ductwork. In addition, since 38HDR/QRR units can be
installed close to an outside wall, coils are protected from vandals
and severe weather.
FAST INSTALLATION
The small footprint of the outdoor units provide additional
benefits.Because they require minimal service and airflow
clearances, the outdoor units can be located virtually anywhere -on the ground, roof, balcony, under a deck, or even mounted to an
outside wall.
The ceiling--suspended unit has its own mounting bracket for
easier installation. Since there is no need to run ductwork and only
piping and wiring is required between the indoor and outdoor
units, there is minimal disruption to customers in the workplace,
making this system ideal for retrofit applications.
40QAC/38HDR -- 40QAQ/38QR
SIMPLE SERVICING AND
MAINTENANCE
Saving time and money was a big consideration when designing
these systems.
On all indoor units, service and maintenance expense is reduced
due to easy--to--use cleanable filters and the ability to service the
unit from the bottom by removing the filter tracks.
On the outdoor units, a single panel provides immediate access to
the isolated compressor and control compartment, allowing a
service technician easy access to check the unit operation without a
loss of condenser airflow. In addition, the blow--through design of
the outdoor section means that dirt accumulates on the inside
surface of the coil. Coils can be cleaned from the outside using a
pressure hose and mild detergent without removing grilles or using
fin combs.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be
controlledindividuallybasedonusagepattern.The
ceiling--suspended units are equipped with motorized louvers
which permits optimal room air mixing to eliminate hot and cold
spots for occupant comfort. In addition, year--round comfort can be
provided with heat pumps.
ECONOMICAL OPERATION
The duct--free split system design allows individual room heating
or cooling when required. There is no need to run large supply--air
fans or chilled water pumps to handle a few spaces with unique
load patterns. In addition, because air is moved only in the space
required, no energy is wasted moving air through ducts.
EASY--TO--USE CONTROLS
The ceiling--suspended units have electro--mechanical controls and
can be controlled by one of three user friendly thermostats that
mount on the wall.
FLEXIBILITY
A variety of accessories simplify the installation process and help
meet system requirements and weather considerations. Available
accessories are listed in the Standard Features and Accessories
section of this document.
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning &
Refrigeration Institute), and UL.
2
MODEL NUMBER NOMENCLATURE
R
INDOOR UNIT
40QAC3---01
018
---
Fan Coil Unit
Unit Type
QAC --- C o o l i n g O n l y
QAQ --- H e a t P u m p
Nominal Capacity*
024 --- 2 To n
036 --- 3 To n
048 --- 4 To n
060 --- 5 To n s
Volt age
3 --- 208/230 ---1 ---60
OUTDOOR UNIT
38HDR3--- 01
Air--- Cooled Condenser
Unit Type
HDR --- C o o l i n g Only
QRR --- H e a t P u m p
* For nominal size 018 and 030, the indoor unit sizes 024 and 036 are matched with outdoor unit sizes 018 and 030 respectively.
** On sizes 036, 048 and 060
018
Nominal Capacity
018 --- 1 --- 1 / 2 T o n
024 --- 2 To n
030 --- 2 --- 1 / 2 T o n
036 --- 3 To n s
048 --- 4 To n s
060 --- 5 To n s
---
Volt age
3--- 208/230--- 1---60
5--- 208/230--- 3---60**
6--- 4 6 0 --- 3 --- 6 0 * *
40QAC/38HDR -- 40QAQ/38QR
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
®
3
STANDARD FEATURES AND ACCESSORIES
R
Ease Of Installation
Compact SizeS
Hanging Bracket For Indoor UnitS
Stacking KitA
Wall Mounting KitA
Condensate PumpA
Comfort Features
Automatic Air SweepS
Auto Restart FunctionS
Auto Changeover On Heat PumpsS
Energy Saving Features
Stop/Start TimerS
Safety And Reliability
3MinuteTimeDelayForCompressorS
Over Current Protection For CompressorS
High and Low Pressure Switches on Cooling Only U nitsS
High Pressure Switch and Loss Of Charge Switch On HPS
Indoor Coil Freeze ProtectionS
Factory Supplied Filter Dryer For Field InstallationS
Accumulator On Heat Pumps UnitsS
Ease Of Service And Maintenance
Control Box Accessible From Bottom Of UnitS
Cleanable FiltersS
Liquid Line Pressure TabsS
Suction And Discharge Pressure TabsS
Application Flexibility
208/230 and 460 3 Phase on size 036, 048, and 060S
Electric Heat On 40QAQ Un itsS
Long lines up to 200 Ft (accessories required)A
Outside Air Intake KitA
Power Ventilation KitA
Low Ambient Controls ( --- 20° F)A
40QAC/38HDR -- 40QAQ/38QR
Knock Out For Outside Air IntakeS
Wind BafflesA
Wall Mounted ThermostatsA
Warranty
5--- Year Compressor WarrantyS
1--- Year Parts WarrantyS
Compressor Extended Warranty Years 6 Thru 10O
All Parts And Labor Years 2 Thru 5O
All Parts And Labor Years 2 Thru 5, Compressor Years 6 Thru 10O
Legend
SStandard
A Accessory
OOptional
OUTDOOR UNITS
LOW AMBIENT KIT
The kit controls condenser fan cycling using a pressure switch. It is
specifically designed to control fan--motor cycles in response to
saturated condensing pressure. This device maintains a constant
saturated condensing temperature of 100 _F ± 10 _F (37.78_C ±
--12.22 _C) at outdoor--air temperatures between 55 _F and --20 _F
(12.78_C ± --12.22_C), and can be used on all outdoor units
without changing the outdoor fan motor.
WINTER START CONTROL
The Winter Start Control is a SPST delay relay. the control
bypasses the low pressure switch for approximately 3 minutes to
permit start--up for cooling operation under low load conditions at
low ambient temperatures. This relay is recommended on all
systems that have the accessory Low Ambient Kit. Winter Start
Control can also be used to provide low ambient cooling at
outdoor ambient temperatures between 55_F and 40_F (12.8_C
and 4.4_C).
ISOLATION RELAY
To be used when Low Ambient Kit is used with heat pumps. This
will ensure that the pressure switch is bypassed if unit is running in
heat pump mode.
LIQUID LINE SOLENOID VALVE
The Liquid Line Solenoid Valve is an electronically operated
shutoff valve that is installed at the outdoor unit to stop and start
refrigerant flow in response to compressor operation. The valve
maintains a column of refrigerant in the liquid line between
compressor operating cycles and is required for certain long--line
applications and to improve system performance.
CRANKCASE HEATER
The Crankcase Heater is available for units with scroll compressors
and clamps onto the compressor oil sump. It is recommended for
low ambient and long line applications.
WIND BAFFLES
The Wind Baffle is an accessory sheet metal wrapper used to
provide improved unit operation during high winds and is
recommended whenever the Low Ambient Kit is used.
4
STANDARD FEATURES AND ACCESSORIES CONTINUED
R
INDOOR UNITS
CONDENSATE PUMP
(part # 53DS--900------081)
For those applications where the ceiling--suspended unit is not
installed close to an outside wall, and an adequate pitch cannot be
provided, the pump mounts inside the unit with quick plug--in
connections and provide a maximum lift capability of 20 inches
(508 mm).
Fig. 1 – Condensate Pump
A08572
FRESH AIR INTAKE KIT
(Part # 53DS--900------006)
When the ceiling--suspended unit is installed against an outside
wall, the Fresh Air Intake Kit provides variable (up to 30%) fresh
air capability. The kit has a filter that mounts at the fan coil unit
and provides filtering of the outside air before it enters the unit.
POWER VENTILATION KIT
(Part # 53DS--900------066)
The Power Ventilation Kit is used in conjunction with the Fresh
Air Intake Kit and is used when the unit is not installed against an
outside wall and where static pressure needs to be overcome.
REAR OF INDOOR
UNIT
INDOOR UNIT
(TOP)
COVER
ADJUSTABLE
VENTILATION
AIR DAMPER
AIR FILTER
Fig. 2 – Fresh Air Intake Kit
40QAC/38HDR -- 40QAQ/38QR
A08573
5
WIRED CONTROLLER
R
HW Thermostat (Part # 53DFS250--HW)
A specially designed thermostat for ceiling--suspended systems that
incorporate 3--speed fan control. These can be used on both
cooling--only and heat pump systems.
SLarge, Clear DisplaywithBacklighting—current
temperature, set temperature and time are easy--to--read
and all are displayed on the main screen.
SMenu Driven Programming -- Provides guidance
through the scheduling process, showing only necessary
information and choices on each screen.
SAbility to Select Multiple Days -- allows easy
customizing for unique schedules.
SReal--Time Clock -- keeps time during power failure;
automatically updates for daylight saving time.
SPrecise Temperature Control (±1_F)--reliable,
consistent comfort.
SMultiple OVERRIDE options -- can modify schedule for
a specific period of time (up to 365 days).
SSpeedy same--schedule programming -- no need to copy
mulitple days.
SProgrammable or non--programmable modes.
SRemote setback input for occupancy sensors or
timeclocks.
SVersaSpeedt fan ramping algorithm and fan reset
algorithm
40QAC/38HDR -- 40QAQ/38QR
Fig. 3 – 53DFS250--HW Thermostat
6
AHRI* CAPACITY RATINGS
R
System
Ty pe
*Air Conditioning, Heating & Refrigeration Institute
Legend
HSPF --- Heating Seasonal Performance Factor
EER --- Energy Efficiency Rating
SEER --- Seasonal Energy Efficiency Ratio
NOTES:
1. Ratings are net values reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80_F (26.67_C) db, 67_F (19.44_C) wb air
entering indoor unit and 95_F(35_C) db air entering outdoor unit. High Temperature Heating Standard: 70_F (21.11_C) db air entering indoor unit and 47_F
(8.33_C) db, 43_F (6.11_C) wb air entering outdoor unit.
2. Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3. All system ratings are based on fan coil un its operating at high fan speed. Consult Physical Data tables f or airflows at all available fan speeds.
Outdoor SectionIndoor Section
3 8 H D R018 --- --- --- 34 0 QAC 0 2 4 --- --- --- 3172048018,0001311.5N/AN/A
3 8 H D R024 --- --- --- 34 0 QAC 0 2 4 --- --- --- 3172055023,0001311.5N/AN/A
3 8 H D R030 --- --- --- 34 0 QAC 0 3 6 --- --- --- 3390084029,0001312.0N/AN/A
3 8 H D R036 --- --- --- 34 0 QAC 0 3 6 --- --- --- 3390084033,0001311.4N/AN/A
3 8 H D R036 --- --- --- 54 0 QAC 0 3 6 --- --- --- 3390084033,0001311.4N/AN/A
3 8 H D R036 --- --- --- 64 0 QAC 0 3 6 --- --- --- 3390084033,0001311.4N/AN/A
3 8 H D R048 --- --- --- 34 0 QAC 0 4 8 --- --- --- 33900113046,0001311.5N/AN/A
Cooling
3 8 H D R048 --- --- --- 54 0 QAC 0 4 8 --- --- --- 33900113046,0001311.5N/AN/A
3 8 H D R048 --- --- --- 64 0 QAC 0 4 8 --- --- --- 33900113046,0001311.5N/AN/A
3 8 H D R060 --- --- --- 34 0 QAC 0 6 0 --- --- --- 33900160057,0001311.4N/AN/A
3 8 H D R060 --- --- --- 54 0 QAC 0 6 0 --- --- --- 33900160057,0001311.4N/AN/A
3 8 H D R060 --- --- --- 64 0 QAC 0 6 0 --- --- --- 33900160057,0001311.4N/AN/A
Motor HP1/151/6
Blower Quantity…Size (in)2…6x83…6x84…6x8
Indoor Coil
Face Area (sq. f t)2.22.63.34.5
No. Rows4444
Fins per inch15151515
Circuits4488
Filters
Quantity…Size (in)4…12 x 8.755…10.6 x 8.75
Refrigerant Lines
Connection TypeFlare
Liquid Line (in) OD3/8
Vapor L ine (in) OD5/83/4
Condensate Drain
MTP Outside Diameter (in) **3/4
External FinishWhite With Black Trim End Pieces
* When matched with 38HDR018 RPM/CFM will be 862/500 (high), 690/400 (medium), and 552/320 (low)
** 5/8” flexible tubing is required when using condensate pump accessory.
Motor HP1/151/6
Blower Quantity…Size (in)2…6x83…6x84…6x8
Indoor Coil
Face Area (sq. f t)2.22.63.34.5
No. Rows4444
Fins per inch15151515
Circuits4488
Filters
Quantity…Size (in)4…12 x 8.755…10.6 x 8.75
Refrigerant Lines
Connection TypeFlare
Liquid Line (in) OD3/8
Vapor L ine (in) OD5/83/47/8***
Condensate Drain
MTP Outside Diameter (in) **3/4
External FinishWhite With Black Trim End Pieces
*When matched with 38HDR018 RPM/CFM will be 862/500 (high), 690/400 (medium), and 552/320 (low)
**5/8” flexible tubing is required when usin g condensate pump accessory.
*** Connection size is 3/4”. Recommended line size is 7/8’
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
320/0.02400/0.03500/0.03
Air Entering Evaporator --- Ewb ° F (° C)
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
* The 40QAC024 unit must be field configured to an 018 size unit by changing the
motor speed fan tap plug. Refer to Installation Instructions for more details.
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
Rating Co ndition.
Not recommended for long---term operation
400/0.03500/0.03600/0.04
COOLING CAPACITIES
38HDR024 / 40QAC024
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
40QAC/38HDR -- 40QAQ/38QR
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
40QAC/38HDR -- 40QAQ/38QR
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x ( 1 --- BF) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ( ° F )
40QAC/38HDR -- 40QAQ/38QR
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x ( 1 --- BF) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
* The 4 0QAQ024 unit must be field co nfigured to an 018 si ze unit by changing the
motor speed fan tap plug. Refer to Installation Instructions for more details.
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
40QAC/38HDR -- 40QAQ/38QR
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
40QAC/38HDR -- 40QAQ/38QR
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
40QAC/38HDR -- 40QAQ/38QR
BF --- B y p a s s F a c tor
CMP --- C o m p r e s sor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- Tot a l Power
LDB --- L e a v i n g D r y B u l b
LWB --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cool ing Capacity (1000 Btuh)
TCG --- Gross Cooling Capacity (1000 Btuh )
NOTES:
1. Di rect interpolation is permissible. Do not extrapo late.
2. The SHG i s based on 80_F (26.7_C) edb temperature of air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr fa ctor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- B F) x (edb --- 80).
27
PERFORMANCE DATA (CONT.)
R
INSTANTANEOUS AND INTEG. HEATING RATINGS
40QAC/38HDR -- 40QAQ/38QR
Air
Te m p e r a t ure
Entering
Indoor Unit
°F(°C)
55
(12.8)
60
(15.6)
65
(18.3)
70
(21.1)
75
(23.9)
80
(26.7)
Indoor
Airflow
(CFM)
L --- M --- H
320
400
480
320
400
480
320
400
480
320
400
480
320
400
480
320
400
480
Rating Co ndition.
Not recommended for long---term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
28
PERFORMANCE DATA (CONT.)
R
INSTANTANEOUS AND INTEG. HEATING RATINGS
Air
Te m p e r a t ure
Entering
Indoor Unit
°F(°C)
55
(12.8)
60
(15.6)
65
(18.3)
70
(21.1)
75
(23.9)
80
(26.7)
Indoor
Airflow
(CFM)
L --- M --- H
400
480
550
400
480
550
400
480
550
400
480
550
400
480
550
400
480
550
Rating Co ndition.
Not recommended for long---term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
29
PERFORMANCE DATA (CONT.)
R
INSTANTANEOUS AND INTEG. HEATING RATINGS
40QAC/38HDR -- 40QAQ/38QR
Air
Te m p e r a t ure
Entering
Indoor Unit
°F(°C)
55
(12.8)
60
(15.6)
65
(18.3)
70
(21.1)
75
(23.9)
80
(26.7)
Indoor
Airflow
(CFM)
L --- M --- H
630
750
870
400
480
550
400
480
550
400
480
550
400
480
550
400
480
550
Rating Co ndition.
Not recommended for long---term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
30
PERFORMANCE DATA (CONT.)
R
INSTANTANEOUS AND INTEG. HEATING RATINGS
Air
Te m p e r a t ure
Entering
Indoor Unit
°F(°C)
55
(12.8)
60
(15.6)
65
(18.3)
70
(21.1)
75
(23.9)
80
(26.7)
Indoor
Airflow
(CFM)
L --- M --- H
630
750
870
400
480
550
400
480
550
400
480
550
400
480
550
400
480
550
Rating Co ndition.
Not recommended for long---term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
31
PERFORMANCE DATA (CONT.)
R
INSTANTANEOUS AND INTEG. HEATING RATINGS
40QAC/38HDR -- 40QAQ/38QR
Air
Te m p e r a t ure
Entering
Indoor Unit
°F(°C)
55
(12.8)
60
(15.6)
65
(18.3)
70
(21.1)
75
(23.9)
80
(26.7)
Indoor
Airflow
(CFM)
L --- M --- H
820
975
1130
820
975
1130
820
975
1130
820
975
1130
820
975
1130
820
975
1130
Rating Co ndition.
Not recommended for long---term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
32
PERFORMANCE DATA (CONT.)
R
INSTANTANEOUS AND INTEG. HEATING RATINGS
Air
Te m p e r a t ure
Entering
Indoor Unit
°F(°C)
55
(12.8)
60
(15.6)
65
(18.3)
70
(21.1)
75
(23.9)
80
(26.7)
Indoor
Airflow
(CFM)
L --- M --- H
1040
1220
1600
1040
1220
1600
1040
1220
1600
1040
1220
1600
1040
1220
1600
1040
1220
1600
Rating Co ndition.
Not recommended for long---term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
33
APPLICATION DATA
R
UNIT SELECTION
The ceiling--suspended units are available as cooling only or heat
pump with electric heat. For most applications, the cooling load
dictates the size selection of the unit. Select equipment to either
match or be slightly less than anticipated peak load. This provides
better humidity control, fewer unit cycles, and less part--load
operation.
For units used in spaces with high sensible loads, base equipment
selection on unit sensible load, not on total anticipated load. Adjust
for anticipated room wet bulb temperature to avoid under--sizing
equipment.
UNIT MOUNTING (INDOOR)
Unit leveling -- For reliable operation, units should be level in all
planes. The 40QAC/QAQ ceiling--suspended fan coils may have
a slight pitch, but only toward the drain connection.
Clearance -- Refer to Fig. 9 for required CE clearances.
Unit location -- When selecting unit location, select a location that
will provide the best air circulation for the room.
the 40QAC/QAQ ceiling--suspended units should be mounted near
the ceiling and against a wall. The unit should be centered in the
room for best performance. Locating the unit on an outside wall
will make piping easier, but units can also be mounted away from a
wall if desired. If unit is mounted away from a wall, the rear panel
of the unit may need a field--supplied trim strip for improved
appearance. Locate the fan coil return over an area which is not
normally occupied for quietest operation.Do not block air
40QAC/38HDR -- 40QAQ/38QR
discharge for a minimum of 15 ft (4.6 m) to prevent dumping of
cold air and drafts.
Support -- The 40QAC/QAQ units are installed using the
mounting brackets supplied with the unit. The structure should
provide adequate support for the weight of the unit. Refer to the
Physical Data section in this document for fan coil weights.
Installation Template -- The 40QAC/QAQ units are furnished
with cardboard mounting templates to mark the location of the
mounting brackets, wiring, refrigeration line hole locations, and
indicate the location of ventilation air connections.
UNIT MOUNTING (OUTDOOR)
Unit leveling -- For reliable operation, units should be level in all
planes.
Clearance -- Minimum clearance, as shown in Fig. 8, must be
provided for airflow. The condensing units are designed for
free--blow application. Air inlets and outlets should not be
restricted.
Unit location -- A location which is convenient to installation and
not exposed to strong wind. If unit is exposed to strong winds it is
recommended that a wind baffle accessory be used.
A location which can bear the weight of outdoor unit and where
the outdoor unit can be mounted in a level position.
Mounting Pad -- The minimum mounting pad dimensions are
listed in the following table:
Unit Model
38HDR018, 024, 030
38QRR018, 024
38HDR036, 048, 060
38QRR030, 036, 048, 060
Minimum Mounting Pad Dimensions
f t . --- i n . ( m m )
1’--- 11” X 3’ ---6”
(584.2 X 1066.8)
2 ’ --- 0 ” X 4 ’ --- 2 ”
(609.6 X 1270)
SYSTEM OPERATING CONDITIONS
Cooling operating range:
MaximumMinimum
DB
_F(_C)WB_F(_C)DB_F(_C)WB_F(_C)
Outdoor Unit
Indoor Unit
125
(51.7)
95
(35)
---
71
(21.7)
55
(12.8)
67
(19.4)
---
57
(13.9)
Heating operating range:
MaximumMinimum
DB
_F(_C)WB_F(_C)DB_F(_C)WB_F(_C)
Outdoor Unit
Indoor Unit
75
(23.9)
80
(26.7)
67
(19.4)
71
(21.7)
--- 2 0
(--- 28.9)
55
(12.8)
---
---
LOW AMBIENT OPERATION
Both cooling only and heat pumps will operate in cooling down to
55_F (12.8_C).
When equipped with a low ambient controller, the unit will operate
down to --20_F (--28.9_C).
For proper operation, a Winter Start Kit (bypasses the Low
Pressure Switch), a Crankcase Heater (prevents refrigerant
migration during compressor--off cycle), and a Wind Baffle should
also be installed.On heat pumps, a Winter Start Kit is not
required. An Isolation Relay to bypass the Low Ambient
Controller when unit is in heating mode is required.
METERING DEVICES
For cooling only on units, a TXV in the indoor unit controls the
refrigerant flow.
On heat pumps, an Accurator in the outdoor unit controls the
refrigerant flow in heating and another Accurator in the indoor unit
(except size 060, which has a TXV) controls the refrigerant flow in
cooling.
DRAIN CONNECTIONS
The drain connection on the ceiling--suspended unit is located on
the right hand side when facing the unit discharge.
When the unit is installed close to an outside wall, a downward
sloped condensate line can be used to dispose of the water (do not
trap condensate line).If this is not feasible, an accessory
condensate pump that can be installed inside the unit is available
and will provide up to 20 inches (508 mm) of lift. When using a
condensate pump, the drain pipe can be routed through the top of
the unit, if desired.
34
REFRIGERANT LINES
R
General Guides:
1. Refrigerant lines can access the ceiling--suspended unit from
either the top--right or rear--right when facing the unit.
2. Refrigerant lines should not be buried in the ground. If it is
necessary to bury the lines, not more than 36--in (914 mm)
should be buried. Provide a minimum 6--in (152 mm)
vertical rise to the service valves to prevent refrigerant
migration.
3. On cooling only units, the suction line must be insulated.
On heat pumps, insulate both lines. Use a minimum of
1/2--in. (12.7 mm) thick insulation. Closed--cell insulation is
recommended in all long--line applications.
4. Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into
the structure.
NOTE: Since the same outdoor unit can be matched with different
types of indoor units, it may not have enough refrigerant charge.
Refer to the Physical Data tables in this document to determine if
additional charge is required.
Long Line Applications:
The following table indicates the maximum line lengths that can be
used with the high wall systems:
Item
Total Piping200 (61)
Max Lift (fan coil above)65 (20)
Max Drop (fan coil below)200 (61)
For line lengths over 25 ft (7.6 m), .6 oz of charge should be added
for each additional foot up to the maximum allowed.
For line lengths over 80 ft (24.4 m), certain accessories and
adjustments to the piston sizes are also required.
Refer to the Duct Free Split Systems Long Line Guide for
additional information.
Max Length Allowed
ft (m)
CONTROLS
Ceiling--suspended fan coil units have a relay board which controls
system operation in response to the room thermostat.
The 40QAC/QAQ unit has 4 operating modes:
S Fan Only
S Auto (heat pump models only)
S Heating (heat pump models only)
S Cooling
FAN ON LY -- In Fan Only mode, the system filters and circulates
the room air without changing the room air temperature.
AUTO -- In Auto mode, the system will automatically select one of
the following operating modes: cooling, or heating depending on
the selected thermostat set point.
HEATING -- In the Heating mode, the system heats and filters
room air.
COOLING -- In Cooling mode, the system cools, dries and filters
room air.
SEQUENCE OF OPERATION
Increased demand for cooling
(heat pump systems)
1. When the room thermostat senses a demand for cooling, the
fan coil relay board is energized and the indoor fan will start
in the selected speed (if it is not already operating).
2. The reversing valve is energized at all times when in
cooling mode.
3. The internal condensate pump (if so equipped) runs
whenever the reversing valve is energized. The internal
condensate pump (if so equipped) runs whenever there is a
demand for cooling.
4. As long as the condensate float switch and freeze protection
thermostat are closed, the cooling relays in the fan coil unit
will close. This energizes the compressor and outdoor fan in
the outdoor unit. The compressor will continue to operate
until the room thermostat is satisfied.
5. When the cooling demand is satisfied, the compressor and
outdoor fan will stop. If the system is in Auto. mode, the
indoor fan will stop with the compressor. If the unit has the
accessory ventilation kit, the ventilation fan will operate
whenever the indoor fan is set for medium or high speed.
Increased demand for heating
(heat pump systems)
1. When the room thermostat senses a demand for heating, the
fan coil relay board is energized .
2. The indoor fan will start in the selected speed (if it is not
already operating). The reversing valve will not be
energized. The internal condensate pump (if supplied) and
freeze protection thermostat are not operated during heating
operation.
3. The control relay closes, and the compressor and outdoor
fan are energized through the defrost and the defrost timer
runs.
4. Once every 90 minutes (the factory default setting) of the
compressor run time, the DFB (defrost board) logic checks
the defrost thermostat (DFT). If the DFT is open, the unit
continues in heating operation. If the DFT is closed, the
DFB switches the unit to defrost mode. The timing on the
DFB may be set at either 30, 50 or 90 minutes.
Defrost
The DFB energizes the RVS (reversing valve solenoid), and the
reversing valve switches to the cooling position. The relay on the
DFB opens and the outdoor fan stops. The contact on the DFB is
also energized, which in turn energizes the defrost relay on the fan
coil relay board, turns off the electric heater and stops the indoor
fan. The DFB logic checks the 10--minute defrost timer and the
DFT. If the DFT opens in less than 10 minutes, the defrost board
switches the unit back to normal heating operation. If the DFT
remains closed the DFB switches the unit back to heating operation
after 10 minutes. When the DFB changes back to heating mode,
the RVR (reversing valve relay) is deenergized and the reversing
valve switches back to heating operation. Both the outdoor and
indoor fans come back on, and if necessary, the electric heater also
turns on.
40QAC/38HDR -- 40QAQ/38QR
35
Human Interface
R
The 40QAC/QAQ units are controlled by a wired thermostat. For
additional details on thermostat features, refer to the Owner’s
Manual of the individual thermostat model 53DFS250--HW.
Operating Mode Memory
After the system is turned off, or after a power failure, the system
remains in the last operating mode selected. When the system is
turned back on, or when power is automatically restored, operation
continues in the same operating mode as when the system shut
down.
Electric Heat
The 40QAQ units have electric heaters factory installed as shown
in the following table.
ModelKW
40QAQ0242
40QAQ0363
40QAQ0484
40QAQ0605
The electric heater is supplementary. When the heat pump runs for
at least 2 minutes and the temperature spread between the setpoint
is between 3_ to 8_ (depending on dead--band setting), the electric
heater is energized.
40QAC/38HDR -- 40QAQ/38QR
AIR DISTRIBUTION
All ceiling--suspended units are equipped with an automatic air
sweep feature which automatically directs the airflow louvers up
and down to provide optimum room air circulation.If the
automatic sweep feature is not desired, temporarily start the
automatic sweep using the toggle switch on the unit. When the
louvers are in the desired position, turn the automatic sweep off to
hold the louvers in that position.
Outside Air
Up to 30% of outside air can be introduced to the 40QAC/QAQ
units through the pre--punched knockouts. If the unit is installed
next to an outside wall, the Fresh Air Intake Kit can be used. A
Power Ventilation Kit is also available for those applications where
there is a need to overcome static pressure in the fresh air intake
duct.
1. Sound power ratings are per AHRI 270 and AHRI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
Sound Power dBa
HighMediumLow
Sound Pressure
dBa
Sound Power dBa
Sound Pressure
dBa
Sound Power dBa
Sound Pressure
dBa
40QAC/38HDR -- 40QAQ/38QR
WIRING
The indoor and outdoor units have their own power supply (single point connection on unit with electric heat). Low voltage wires run
between the indoor and outdoor units. Two wires are required for cooling only systems and five wires are required for heat pumps.
LEGEND
FLA --- F u l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA --- RatedLoadAmps
NOTES
* Permissible limits of the voltage range at which the unit will operate
satisfactorily
{ Onefanis1.1amps,thesecondfanis0.5amps.
}Two fans each operating at 1.3 amps.
38
TYPICAL WIRING SCHEMATICS
R
ASM— Air Sweep Motor
ASR— Air Sweep Relay
ASW— Air Sweep Switch
C—Contactor
CAP— Capacitor
COMP — Compressor
CR— Control Relay
CT— Current Transformer
DR— Delay Relay
EQUIP
GND
FL— Fuse Link
FPT— Freeze Protection
IFM— Indoor Fan Motor
LPS— Low-Pressure Switch
OFM— Outdoor-Fan Motor
OL— Overload
PDR— Pump Delay Relay
PL— Plug
PM— Pump Motor
PSS— Pump Shut-off Switch
TB— Terminal Block
TRAN— Transformer
LEGEND
— Equipment Ground
Thermostat
Thermostat
Terminal (Marked)
Terminal (unmarked)
Splice
Terminal Block
Fact ory W iring
Field Control Wiring
Field Power Wiring
Printed Circuit Board
Accessory or Optional
Wiring
38HDR
40QAC
40QAC/38HDR -- 40QAQ/38QR
40QAC
38HDR
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90° C
wire or its equivalent.
2. Wire in accordance with National Electrical Code, NEC) and all local codes.
3. Transformer is thermally protected and will reset automatically.
4. IFMs, OFM and COMP have internal thermal protection.
5. Use copper conductors only.
A12211
38HDR and 40QAC Cooling System Wiring Diagram
39
TYPICAL WIRING SCHEMATICS (CONT.)
R
ASM— Air Sweep Motor
ASR— Air Sweep Relay
C—Contactor
CAP— Capacitor
COMP— Compressor
CR— Control Relay
CT— Current Transformer
DFB— Defrost Board (Outdoor Unit)
DFT— Defrost Thermostat
DR— Delay Relay
DTS— Discharge Temp. Sensor
EQUIP. GND — Equipment Ground
FL— Fuse Link
FPT— Freeze Protection Thermostat
FR— Fan R elay
FU— Fuse
HP— Heat Pump
HPS— High-Pressure Switch
HR— Heater Relay
HTR— Heater
HTT— Heater Temp Thermostat
IFM— Indoor Fan Motor
LPS— Low-Pressure Switch
OFM— Outdoor-Fan Motor
OL— Overload
PDR— Pump Delay Relay
PL— Plug
PM— Pump Motor
PSS— Pump Shut-off Switch
RVS— Reversing Valve Solenoid
SSDR— Safety Switch Delay Relay
TB— Te r mi n a l B l oc k
TRAN— Transformer
40QAC/38HDR -- 40QAQ/38QR
NOTES:
1. If any of the original wire furnished must be
replaced, it must be replaced with type
90° C wire or its equivalent.
2. Wire in accordance with National Electrical
Code, NEC) and all lo cal codes.
3. Transformer is thermally protected and will
reset automatically.
4. IFMs, OFM and COMP have internal thermal protection.
5. Jumper wire (O to Y1) required when heat
pump indoor unit is used with cooling only
outdoor unit. Wire must be field supplied.
6. Use copper conductors only.
LEGEND
Terminal (Marked)
Terminal (unmarked)
Splice
Te r m in a l B l o ck
Factory Wiring
Field Control Wiring
Field Power Wiring
Printed Circuit Board
Accessory or Optional Wiring
38QRR
40QAQ
See Note #5
40QAQ
38QRR
38QRR and 40QAQ Heat Pump System Wiring Diagram
A12212
40
GUIDE SPECIFICATIONS
R
HORIZONTAL DISCHARGE OUTDOOR UNITS
Size Range: 1--1/2 to 5 Ton Nominal Cooling Capacity / 1--1/2 to 5 Ton Nominal Heating Capacity
Carrier Model Number: 38HDR/38QRR
PART 1 -- GENERAL
1.01 System Description
A. Outdoor air--cooled split system compressor sections suitable
for on--the--ground, rooftop, wall hung or balcony mounting.
Units shall consist of a scroll compressor, an air--cooled coil,
propeller--type blow--through outdoor fan, reversing valve
(HP), accumulator, Accurator metering device(s), and control
box. Units shall discharge air horizontally as shown on the
contract drawings. Units shall function as the outdoor
component of an air--to--air cooling only, or heat pump system.
B. Units shall be used in a refrigeration circuit matched to
duct--free cooling only or heat pump fan coil units.
1.02 Agency Listings
A. Unit construction shall comply with ANSI/ASHRAE 15, latest
revision, and with the NEC.
B. Units shall be evaluated in accordance with UL standard 1995.
C. Units shall be listed in the CEC directory.
D. Unit cabinet shall be capable of withstanding 500--hour salt
spray test per Federal Test Standard No. 141 (method 6061).
E. Air--cooled condenser coils shall be leak tested at 573 psig.
1.03 Delivery, Storage, And Handling
Units shall be shipped in one piece and shall be stored and handled
per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying
Engineer)
PART 2 -- PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air--cooled outdoor unit.
Contained within the unit enclosure shall be all factory wiring,
piping, controls, and the compressor.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a baked--enamel finish on
inside and outside.
2. Unit access panels shall be removable with minimal screws
and shall provide full access to the compressor, fan, and
control components.
3. Outdoor compartment shall be isolated and have an acoustic
lining to assure quiet operation.
4. Compressor compartment shall be isolated to allow for
diagnostic performance while the system is running.
C. Fans:
1. Outdoor fans shall be direct--drive propeller type, and shall
discharge air horizontally. Fans shall blow air through the
outdoor coil.
2. Outdoor fan motors shall be totally--enclosed, single phase
motors with class B insulation and permanently--lubricated
bearings. Motor shall be protected by internal thermal
overload protection.
3. Shaft shall have inherent corrosion resistance.
4. Fan blades shall be metallic and shall be statically and
dynamically balanced.
5. Outdoor fan openings shall be equipped with PVC coated
metal protection grille over fan.
D. Compressor:
1. Compressor shall be fully hermetic scroll type.
2. Compressor shall be equipped with oil system, operating oil
charge, and motor. Internal overloads shall protect the
compressor from over--temperature and over--current.
3. Motor shall be NEMA rated class F, suitable for operation
in a refrigerant atmosphere.
4. Compressor assembly shall be installed on rubber vibration
isolators.
5. Compressors shall be available in single phase (sizes
018--036) and three phase (sizes 036--060).
E. Outdoor Coil:
Coil shall be constructed of aluminum fins mechanically bonded to
seamless copper tubes, which are cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigerant circuit components shall include brass external liquid
line service valve with service gage port connections, suction line
service valve with service gage connection port, service gage port
connections on compressor suction and discharge lines with
Schrader type fittings with brass caps, accumulator, reversing
valve.
G. Controls and Safeties:
Operating controls and safeties shall be factory selected, assembled,
and tested. The minimum control functions shall include the
following:
1. Controls:
a. A timedelay control sequence isprovided standard through
the fan coil board.
b. Automatic outdoor--fan motor protection.
2. Safeties:
a. Diagnostics provided by matched indoor unit.
b. Compressor motor current and temperature overload
protection.
c. Outdoor fan failure protection (High Pressure Switch).
d. Low Pressure Protection
e. Fusible plug to vent refrigerant safely in case of a fire.
H. Electrical Requirements:
1. All sizes shall operate on single phase, 60 Hz power at
208/230v or on three phase, 60Hz power at either 208/230v
or 460v for size 035/036 units.
2. Unit electrical power shall be a single point connection.
3. Unit control voltage to the indoor--fan coil shall be 24
VDC.
4. All power and control wiring must be installed per NEC
and all local electrical codes.
I. Refrigerant Line Lengths:
Unit shall be capable of 200 ft (61 m) maximum piping run. A
maximum lift (fan coil above) of 65 ft (20 m), and a maximum
drop (fan coil below) of 150 ft (46 m) accessible will be required to
achieve those lengths.
J. Special Features (Field Installed):
1. Low--Ambient Kit: Control shall regulate fan--motor cycles
in response to saturated condensing temperature of the unit.
The control shall be capable of maintaining a condensing
temperature of 100_F ± 10_F (37.78_C ± --12.22_C) with
outdoor temperatures to --20_F (--28.9_C). Installation of kit
shall not require changing the outdoor fan motor.
Indoor, direct expansion, ceiling--suspended fan coil.
1.02 AGENCY LISTING AND CERTIFICATION
1. A. Systems shall be rated and certified in accordance with
AHRI Standards 210/240. Units shall be listed in the AHRI
directory as a matched set.
2. SystemsshallbelistedwithUL(Underwriters’
Laboratories) and UL, Canada.
1.03 DELIVERY, STORAGE, and HANDLING
Units shall be shipped in one piece and shall be stored and handled
per unit manufacturer’s recommendations.
1.04 WARRANTY
The 40QA unit is covered by a 1--year parts limited warranty.
PART 2 -- PRODUCTS
2.01 EQUIPMENT
A. General:
Indoor, direct--expansion, ceiling--suspended fan coil.Fancoil
shall be shipped complete with cooling coil, fan, fan motor,
40QAC/38HDR -- 40QAQ/38QR
piping connectors, and ceiling mounting brackets.
B. Unit Cabinet:
1. Unit cabinet shall be zinc--coated bonderized steel finished
with a baked enamel paint.
2. Inlet grilles shall be attractively styled, high impact
polystyrene.
3. Matching mounting brackets shall be provided.
C. Fans:
1. Indoor fans shall be 3--speed centrifugal blower type with
air intake in the bottom rear of the unit and discharge in the
front.
2. Automatic, motor--driven horizontal air sweep shall be
provided standard.
D. Coils:
1. Indoor coils shall be copper tube with aluminum fins and
galvanized steel tube sheets.
2. Fins shall be bonded to the tubes by mechanical expansion.
3. A drip pan under the coil shall have a drain connection for
the hose attachment to remove condensate.
NOTE: Units use a TXV refrigerant metering device in the indoor
unit for cooling only. Heat pumps use the Accurator piston
refrigerant metering devise in the indoor unit for cooling (except
for size 060 which uses a TXV) and an Accurator in the liquid
service valve for heating.
E. Motors:
Motors shall be a permanently lubricated ball bearing with inherent
overload protection.
F. Co ntrols:
User interface with the unit shall be accomplished via a wired
thermostat that shall have the following functions as a minimum:
1. Automatic restart after power failure at the same operating
conditions as at failure.
2. Thermostat control to enter set points and operating
conditions.
3. Programmable fan speed control shall be user--selectable:
high, medium, low, or automatic operation during all
operating modes.
4. Automatic heating--to--cooling changeover to provide
automatic heating and cooling operation. Control shall
include dead--band to prevent rapid mode cycling.
NOTE:See selectedthermostatinstructionsfor further
information.
G. Filters:
Unit shall have filter track with factory supplied, cleanable filter.
H. Electric Heat
The 40QAQ units shall have a factory installed electric heater with
capacity listed in the schedule. The electric heater, when required,
shall supplement the heating capacity generated by the heat pump
system.
I. Electrical Requirements:
1. Unit shall operate on single--phase, 60 cycle power at
208/230v as specified on the equipment schedule.
2. Unit electrical power shall be a single point connection.
3. Unit control voltage shall be 24--v. All power and control
wiring shall be installed per NEC and all local building
codes.
4. Unit shall have low--voltage terminal block connections.
J. Special Features (Field Installed):
1. Internal Condensate Pump
remove condensate from the drainpan when gravity
drainage cannot be used. The lift capability of the
condensate pump shall be direct vertical 20 inches (508
mm). Float control shall be in the condensate sump to shut
the unit down in case of a pump malfunction.
2. Fresh Air Intake kit
the filter and duct connections to provide for outdoor
ventilation air.
3. Power Ventilation Kit
used with the accessory fresh air kit when fresh air must be
ducted in. The kit will overcome duct static to provide a
constant supply of ventilation air. The kit consists of booster
fan and adjustable speed control to properly balance the fan
to achieve the required airflow rate.
4. 53DFS250--HWThermostat
thermostatshallincorporate3--speedcontrol,
programmability, auto changeover, backlight, locking
keypad and a large LCD display.
: The condensate pump shall
: The fresh air intake kit shall include
: The power ventilation kit shall be
:The53DFS250--HW
Copyright 2012 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Printed in U.S.A.Edition Date: 04/12
C a t a l o g N o . 4 0 Q A C --- Q --- 2 P D
R e p l a ce s : 4 0 QAC --- Q --- 1 P D
42
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.