Carrier 38HDL018-060 User Manual

Light Commercial Condensing Units
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INSTALLATION ..............................1-7
Step 1 — Complete Pre-Installation
Checks ....................................1
• INSPECT SHIPMENT
• CONSIDER SYSTEM REQUIREMENTS
Step 2 — Rig and Mount Unit .................3
• MOUNTING ON GROUND
• MOUNTING ON ROOF
• RIGGING
Step 3 — Complete Refrigerant Piping
Connections ...............................3
• CHECK ACCURATERt CONTROL
• MAKE PIPING SWEAT CONNECTIONS
• PROVIDE SAFETY RELIEF
Step 4 — Make Electrical Connections ........4
• POWER WIRING
• CONTROL CIRCUIT WIRING
• CONNECTIONS TO DUCT-FREE FAN COIL UNITS
Step 5 — Accessory Installation ..............4
START-UP ...................................7
SERVICE ...................................7-9
MAINTENANCE .............................10
TROUBLESHOOTING ........................11
SAFETY CONSIDERATIONS
Install and servicing air-conditioning equipment can be haz­ardous due to system pressure and electrical components. Only trained and qualified service personnel should installor serv­ice air-conditioning equipment
Untrained personnel may perform basic maintenance such as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe safety precautions in literature, and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have a fire extinguisher available. Read these instructions thor­oughly.Consult local building codes and National Electrical Code (NEC, U.S.A. Standard) for special installation requirements.
38HDL018-060
COOLING
Fig. 1 — 38HDL Condensing Unit
Before installing or servicing system, always turn off main power to system. There maybe more than one dis­connect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury.
Step 1 — Complete Pre-Installation Checks
UNPACK UNIT — Move unit to final location. Remove car­ton from unit, being careful not to damage service valves or grilles.
INSPECT SHIPMENT — File claim with shipping com­pany if shipment is damaged or incomplete. Check unit name­plate to ensure unit matches job requirements.
CONSIDER SYSTEM REQUIREMENTS — Consult local building codes and NEC for special installation requirements.
Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit. See Fig. 1 and 2. Unit can be mounted on a level pad directly on base legs or mounted on raised pads at support points. See Fig. 2for cen­ter of gravity.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3a 2a
PC 111 Catalog No. 563-899 Printed in U.S.A. Form 38HDL-1SI Pg 1 9-98 Replaces: New
UNIT SIZE
38HDL
018 2-1 024 2-1 030 2-1 036 2-1 048 3-1 060 3-1
ABCDEFGHJKLM
OPERATING
WEIGHT
ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm lb kg
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-65⁄8168.3 0-111⁄4285.8 0-05⁄815.88 130 58.9
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-63⁄4171.5 0-115⁄8295.3 0-05⁄815.88 136 61.6
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-63⁄4171.5 0-115⁄8295.3 0-03⁄419.05 161 73.0
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-63⁄4171.5 0-115⁄8295.3 0-03⁄419.05 185 83.9
3
⁄16944.6 3-89⁄161131.9 1-51⁄16433.4 1-67⁄16468.3 2- 61⁄2774.7 1-75⁄8498.5 2-55⁄8752.5 2-83⁄16817.6 1-17⁄8352.4 0-81⁄4209.5 0- 4 406.4 0-07⁄822.22 222 100.5
3
⁄16944.6 3-89⁄161131.9 1-51⁄16433.4 1-67⁄16468.3 2- 61⁄2774.7 1-75⁄8498.5 2-55⁄8752.5 2-83⁄16817.6 1-111⁄16347.7 0-81⁄8206.4 0- 37⁄8403.2 0-07⁄822.22 249 112.9
UNIT SIZE
38HDL
018,024,030
and 036
Support Feet Snow Stand Ice Stand
ft-in. mm ft-in. mm ft-in. mm
1-11 x 3-6 584.2 x 1066.8 2-2 x 3-6 660.4 x 1066.8 2-2 x 3-6 660.4 x 1066.8
MINIMUM MOUNTING PAD DIMENSIONS
048 and 060 2- 0 x 4-2 609.6 x 1270.0 2-4 x 4-4 711.2 x 1270.0 2-2 x 4-2 660.4 x 1270.0
NOTES:
1. Required clearances: With coil facing wall, allow 69 (156.4 mm)minimumclearance on coil side and coil end, and 3 ft (914.4 mm) minimum clearance on compressor end and fan side. With fan facing wall, allow 89 (203.2 mm) minimum clearanceonfan side and coilend, and 3 ft (914.4mm) minimum clearance on compressorend and coil side.Withmulti-unit application, arrange unitsso discharge of one does not enter inlet of another.
2. Dimensions in parenthesis are in millimeters.
3. Center of gravity .
2
Fig. 2 — 38HDL018-060 — Dimensional Drawing
Step 2 — Rig and Mount Unit
MOUNTING ON GROUND — Mount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly into unit. Field-fabricated stacking kits can be used when units are to be stacked. If conditions or local codes require unit to be fastened to a pad, 6 field-supplied tiedown bolts should be used and fastened through slots pro­vided in unit mounting feet.
MOUNTING ON ROOF — Mount unit on level platform or frame at least 6 in. (154 mm) above roof surface.Isolate unit and tubing from structure.
RIGGING
Be sure unit panels are securely in place prior to rigging.
Keep unit upright. Lift unit using sling. Use cardboard or padding under sling, and spreader bars to prevent sling dam­age to unit. See Fig. 3. See Fig. 2 for center of gravity ref­erence. Install unit so coil does not face into prevailing winds. If this is not possible and constant winds above 25 mph are expected, use field-fabricated wind baffle.
NOTE: Field-fabricated wind baffles should be used on all units with accessory low-ambient control.
Field-fabricated snow stand may be used to raise unit when operation will be required during the winter. Units may also be wall mounted using the accessory wall mounting kit.
Step 3 — CompleteRefrigerant Piping Connec­tions —
using field-supplied tubing of refrigerant grade and condi­tion. See Tables 1A and 1B for correct line sizes. Do not use less than 10 ft (3 m) of interconnecting tubing.
DO NOT BURY MORE THAN 36 IN. (922 mm) OF REFRIGERANT PIPE IN THE GROUND. If any sec­tion of pipe is buried, there must be a 6 in. (154 m) ver­tical rise to the valve connections on the outdoor unit. If more than the recommended length is buried, refrig­erant may migrate to the cooler, buried section during extended periods of system shutdown. This causes refrigerant slugging and could damage compressor at start-up.
Outdoor units may be connected to indoor units
Fig. 3 — Lifting Unit with Sling
with field-replaceable piston should be supplied with the in­door unit. Refer toAccuRater metering device table in sepa­rate indoor unit installationinstructionstodeterminethecorrect AccuRater piston size required for the condenser/evaporator system being installed.
Note that one of 2 types of the AccuRater devices can be found on the indoor unit. See Fig. 4. Do notinterchangecom­ponents between AccuRater device types. Matching of out­door unit with indoor unit may require field replacement of piston. Replace piston, if required, before connecting refrig­erant lines. Piston replacement instructions are included in the indoor unit installation instructions. After system in­stallation is complete, see Refrigerant charging section on page 8 to check and/or adjust refrigerant charge.
The 38HDL018-060 units may also be installedwith units using a thermostatic expansion valve (TXV). If a TXV is used, be sure to remove the piston from the indoor coil. See installation instructions shipped with the TXV for proper po­sitioning and adjustment.
When more than 50 ft (15.2 m) of interconnecting tubing and more than 30 ft (9.1 m) of vertical lift is used, refer to Part 3 of the Carrier System Design Manual for design de­tails, or contact your local distributor.
If either refrigerant tubing or indoor coil is exposed to at­mospheric conditions for longer than 5 minutes, it must be evacuated to 1000 microns to eliminate contamination and moisture in the system.
Run refrigerant tubes as directly as possible, avoiding un­necessary turns and bends. Suspendrefrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure.Also,whenpassingrefrigeranttubes through the wall, seal opening so that vibration is not trans­mitted to structure. Leave some slack inrefrigerant tubes be­tween structure and outdoor unit to absorb vibration. Refer to separate indoor unit installation instructions for addi­tional information.
CHECK ACCURATERt CONTROL — The correct AccuRater (bypass type) refrigerant control is required for cooling system capacity optimization.AnAccuRater device
TYPE A (BYPASS TYPE)
TYPE B
NOTE: Arrow on AccuRater body points in free-flow direction, away from the indoor coil.
Fig. 4 — AccuRater Metering Device Components
MAKE PIPING SWEAT CONNECTIONS —Remove plas­tic caps from liquid and suction service valves. Use refrig­erant grade tubing. Service valves are closed from the fac­tory and ready for brazing.After wrapping the service valve
3
with a wet cloth, the tubing set can be brazed to the service valve using either silver bearing or non-silver bearing braz­ing material. Consult local code requirements. Refrigerant tubing and indoor coil are ready for leak testing.
NOTE: Unit is shipped with R-22 full factory charge indi­cated on nameplate.
Pass nitrogen or other inert gas throughpiping while braz-
ing to prevent formation of copper oxide.
To avoid damage while brazing, service valves should be wrapped in a heat-sinking material such as a wet cloth.
When brazing tubing sets to the service valves, a braz­ing shield must be used to prevent damagetothe painted unit surface.
PROVIDE SAFETY RELIEF — A fusible plug is located in unit suction line; do not cap this plug. If local code requires additional safety devices, install as directed.
Step 4 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken elec­trical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected totheunitground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA (American National Standards Institute/National Fire Protection Association) 70 (U.S.A. Standards), and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury to others.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation will invalidate any applicable Carrier warranty.
POWER WIRING — Unit is factory-wired for voltage shown on nameplate. Provideadequate,fuseddisconnectswitchwithin sight of unit, readily accessible but out of reach of children. Provision for locking the switch open (off) is advisable to prevent power from being turned on while unit is being ser­viced. Disconnect switch, fuses, and field wiring must be
in compliance with NEC (U.S.A. Standard) and applicable local codes. Use minimum 60 C wire for field power connection.
Route power wires through opening in the unit side panel and connect in unit control box as shown on unit label dia­gram and Fig. 5 and 6. Unit must be grounded.
CONTROL CIRCUIT WIRING — Control voltage is 24 v. See Fig. 5 and unit label diagram for field-supplied wiring details. Route control wire through opening in the unit side panel to connection in unit control box.
NOTE: For wire runs up to 50 ft (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft (15 to 23 m), use no. 16AWG insulated wire. For more than 75 ft (23 m), use no. 14 AWG insulated wire. See Table 2 for conversion to European wire sizes.
NOTE: Operation of unit on improper line voltage consti­tutes abuse and could affect Carrier warranty. See Table 3. Do not install unit in system where voltage may fluctuate above or below permissible limits.
See Table 3 for recommended fuse sizes. When making electrical connections, provide clearance at unit for refrig­erant piping connections.
Use indoor unit transformer as 24-v (40-va minimum) supply for system as shown in Fig. 5 or use accessory transformer.
Before performing service or maintenance, be sure the indoor unit main power switch is off and indoor blower has completely stopped. Failure to do so may result in electrical shock or injury from rotating fan blades.
CONNECTIONS TO DUCT-FREE FAN COIL UNITS — The 38HDL units are designed for easy match-up to 40QAB, 40QKB, and 40QNB018,024 duct-free fan coils. These units provide 24-v power for the outdoor unit from the fan coil. Connect the Y and C terminals of the indoor unit to the blue and brown wires of the outdoor unit with 20 gage (mini­mum) thermostat wire.
Step 5 — Accessory Installation — Install all unit
accessories per accessory installation instructions prior to start-up.
Do not use accessory Time Guardt II device when com­bining a 38HDL unit with 40QNB indoor units.
When ambient temperature will fall below 55 F (13 C), accessory low ambient controller (part no. 53DS900060) is required. When accessory low ambient kit is used, unit should also be equipped with accessory winter start kit and field­fabricated wind baffles.
4
Loading...
+ 8 hidden pages