Carrier 38HDF018-036, 38HDR018-060 User Manual

Installation, Start-Up and
Service Instructions
CONTENTS
Page
INSTALLATION ................................ 1-10
Step 1 — Complete Pre-Installation Checks ......1
• UNPACK UNIT
• INSPECT SHIPMENT
• CONSIDER SYSTEM REQUIREMENTS
• MATCHING THE CONDENSING UNIT TO AN INDOOR UNIT
• MOUNTING ON GROUND
• MOUNTING ON ROOF
• RIGGING
Step 3 — Complete Refrigerant Piping
Connections ................................... 3
• CHECK ACCURATER CONTROL
• FILTER DRIER
• MAKE PIPING SWEAT CONNECTORS
• PROVIDE SAFETY RELIEF
Step 4 — Make Electrical Connections ...........6
• CONTROL CIRCUIT WIRING
• POWER WIRING
• CONNECTIONS TO DUCT-FREE FAN COIL UNITS
START-UP ....................................... 11
SERVICE ..................................... 11-14
MAINTENANCE ................................. 14
TROUBLESHOOTING..........................14,15
38HDF018-036
Duct Free Condensing Units
38HDR018-060
Ducted Condensing Units
Puron® (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 ser­vice equipment or components on Puron refrigerant equip­ment. If service equipment is not rated for Puron refrigerant, equipment damage or personal injury may result.
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNPACK UNIT (See Fig. 1) — Move the unit to final loca­tion. Remove unit from carton, being careful not to damage service valves and grilles.
SAFETY CONSIDERATIONS
Installing and servicing air conditioning equipment can be
hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install or service air conditioning equipment.
Untrained personnel can perform basic maintenance, such
as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe safety precautions in litera­ture, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Elec­trical shock can cause serious personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 3 e 2 f
Catalog No. 02-38HD0001-SI Printed in U.S.A. Form 38HD-4SI Pg 1 1-06 Replaces: 38HDC-3SI
INSPECT SHIPMENT — File a claim with the shipping company if shipment is damaged or incomplete. Check unit nameplate to ensure unit matches job requirements.
CONSIDER SYSTEM REQUIREMENTS — Consult local building codes and NEC for special installation requirements.
Allow sufficient space for airflow clearance, wiring, refrig-
erant piping, and servicing unit. See Fig. 2.
Locate unit so that condenser airflow is unrestricted on both
sides. Refer to Fig. 2.
Unit may be mounted on a level pad directly on base legs or mounted on raised pads at support points. See Fig. 2 for center of gravity.
MATCHING THE CONDENSING UNIT TO AN INDOOR UNIT — The 38HDF,HDR units can be matched to a corresponding indoor unit. The 38HDF018-036 units can be matched with an in-ceiling cassette or high wall indoor unit. The 38HDR unit can be matched with under-ceiling and resi­dential fan coils. Refer to separate indoor unit literature for more information.
Fig. 1 — 38HDF,HDR Unit
Support Feet
15.88 166 75.3
15.88 176 79.8
19.05 187 84.8
19.05 250 113.4
15.88 166 75.8
15.88 176 79.8
19.05 187 84.8
19.05 250 113.4
22.22 278 126.1
4
/
030
3
4
/
036
7
8
/
048
22.22 306 138.8
8
/
7
060
M OPERATING WT
8
8
4
4
8
/
030
3
/
036
5
/
018
5
8
/
024
3
/
/
5
5
3
in. mm lb kg
018
024
DIMENSIONS
MINIMUM MOUNTING PAD
ft-in. mm
UNIT SIZE
38HDF
38HDR
UNIT SIZE
CHASSIS SIZES 0 & .6 1-11x3-6 584.2 x 1066.8
CHASSIS SIZES 1 & 1.6 2-0x4-2 609.6 x 1270
on coil side and coil end, and 3 feet minimum clearance on compressor
end and fan side. With fan facing wall, allow 8 in. minimum clearance on
fan side and coil end, and 3 feet minimum clearance on compressor end
and coil side. With multi-unit application, arrange units so discharge of one
2
2
/
/
1
1
0-6
0-6
0-6
16
/
/
15
15
0-2
0-2
4
/
/
1
5
0-11
0-11
8
/
/
5
3
0-6
16
16
16
/
/
7
7
0-3
0-3
8
8
8
/
/
7
7
1-3
1-6
4
8
2
/
/
1
1
0-8
0-8
16
2
/
/
1
11
NOTES:
1. Required clearances: with coil facing wall, allow 6 in. minimum clearance
does not enter inlet of another.
2. Dimensions in parenthesis are in millimeters.
3. Center of Gravity .
ABCD E FG H J KL NP
SIZE
CHASSIS
(Reference)
1-1
1-2
16
/
16
/
1
1
2-4 1-2 0-6
1-10 1-1 0-6
8
/
/
1
1
1-5
1-11
16
/
/
3
3
1-5
1-5
16
/
/
7
7
1-4 1-11
1-4 1-11
16
/
/
9
9
1-2
1-2
16
/
/
15
15
3-0
3-0
8
/
/
1
1
2-1
2-7
(638.2) (938.2) (369.9) (406.4) (595.3) (436.6) (435) (559.1) (330.2) (168.3) (285.8) (75) (152.4)
3-4
2-10
8
16
16
16
16
8
16
16
/
/
3
13
2-5
2-1
8
8
/
/
5
5
1-7
1-7
2
2
/
/
1
1
2-6
2-6
16
16
/
/
7
7
1-6
1-6
16
16
/
/
1
1
1-5
1-5
16
16
/
/
9
9
3-8
3-8
16
16
/
/
3
3
(790.6) (938.2) (369.9) (406.4) (595.3) (436.6) (587.4) (711.5) (355.6) (171.5) (295.3) (75) (152.4)
(1097) (1131.9) (433.4) (468.3) (774.7) (498.5) (893.4) (1017.9) (354.2) (215.9) (479.4) (88) (165.4)
(944.6) (1131.9) (433.4) (468.3) (774.7) (498.5) (741) (865.5) (347.7) (206.4) (403.2) (88) (165.4)
3-1
3-7
(FIELD PROVIDED AND INSTALLED)
Fig. 2 — 38HDF,HDR Unit Dimensions
38HDR
Unit Size
UNIT MODELS
018 018 0
38HDF
Unit Size
024,030 024 0.6
048,060 1.6
036 030,036 1.0
NOTE: Dimensions shown in feet-inches. Dimensions in ( ) are millimeters.
2
Step 2 — Rig and Mount Unit
MOUNTING ON GROUND — Mount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly onto unit. Accessory stacking kits can be used when units are to be stacked. See installation instructions provided with the accessory kit. Use field-provided snow stand or ice rack where prolonged subfreezing temperatures or heavy snow occurs.
If conditions or local codes require unit be fastened to a pad, 6 field-supplied tiedown bolts should be used and fastened through slots provided in unit mounting feet.
MOUNTING ON ROOF — Mount unit on a level platform or frame at least 6 in. above roof surface. Isolate unit and tub­ing from structure.
RIGGING
Be sure unit panels are securely in place prior to rigging. Loose unit panels could result in equipment damage or per­sonal injury.
Keep the unit upright and lift unit using a sling. Use card­board or padding under the sling, and spreader bars to prevent sling damage to the unit. See Fig. 3. See Fig. 2 for center of gravity reference. Install the unit so that the coil does not face into prevailing winds. If this is not possible and constant winds above 25 mph are expected, use accessory wind baffle. See installation instructions provided with the accessory kit.
NOTE: Accessory wind baffles should be used on all units with accessory low ambient temperature control.
Field-fabricated snow or ice stands may be used to raise unit when operation will be required during winter months. Units may also be wall mounted using the accessory wall-mounting kit.
When more than 50 ft of interconnecting tubing and more than 30 ft of vertical lift is used, consult the residential long line application instruction guide. For long-line applications, inter­connecting lines over 100 ft must be installed with a liquid line solenoid. A liquid line solenoid may also be installed on some units to improve part-load efficiency. Refer to the ARI (Air Conditioning & Refrigeration Institute) Directory.
If either refrigerant tubing or indoor coil is exposed to the atmosphere, the system must be evacuated following good refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding unnecessary turns and bends. Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to structure. Also, when passing refrigerant tubes through a wall, seal the opening so that vibration is not transmit­ted to structure. Leave some slack in refrigerant tubes between structure and outdoor unit to absorb vibration. Refer to separate indoor unit installation instructions for additional information.
CHECK ACCURATER CONTROL — The correct Accu­Rater (bypass type) refrigerant control is required for system capacity optimization. An AccuRater device with field­replaceable piston (see Fig. 4) is supplied with the outdoor unit. Refer to the AccuRater metering device table in separate indoor unit installation instructions to determine the correct AccuRater piston size required for the condenser/evaporator system being installed.
Piston style as shown in Fig. 4 is shipped with the unit. Do not interchange components between the AccuRater device types. Matching of outdoor unit with indoor unit may require field replacement of piston. Replace piston, if required, before connecting refrigerant lines. See Fig. 4. Piston replacement instructions are included in the indoor unit installation instruc­tions. After system installation is complete, see the Refrigerant Charging section on page 12 to check and/or adjust refrigerant charge.
FILTER DRIER — The filter drier must be replaced whenev­er the refrigeration system is exposed to the atmosphere. See Fig. 4 for filter drier installation.
Fig. 3 — Lifting Unit with Sling
Step 3 — Complete Refrigerant Piping Con­nections —
units using field-supplied tubing of refrigerant grade and condi­tion. See Tables 1A and 1B for correct line sizes. Do not use less than 10 ft of interconnecting tubing.
DO NOT BURY MORE THAN 36 IN. OF REFRIGER­ANT PIPE IN THE GROUND. If any section of pipe is buried, there must be a 6-in. vertical rise to the valve connections on the outdoor unit. If more than the recommended length is buried refrigerant may migrate to cooler, buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start-up.
Outdoor units may be connected to indoor
NOTE: Arrow on AccuRater body points in free flow direction, away from the indoor coil.
38HDF018-036
38HDR018-060
Fig. 4 — AccuRater (Bypass Type) Metering
Device Components
3
Only use factory specified liquid-line filter driers with rated
working pressures less than 600 psig. NOTE: Do not install a suction-line filter drier in liquid line. MAKE PIPING SWEAT CONNECTIONS — Remove plastic
To avoid damage while brazing, service valves should be wrapped with a heat-sinking material such as a wet cloth.
caps from liquid and suction service valves. Use refrigerant grade tubing. Service valves are closed from the factory and are ready for brazing. After wrapping the service valve with a wet cloth, the tubing set can be brazed to the service valve using ei­ther silver bearing or non-silver bearing brazing material. Con­sult local code requirements. Refrigerant tubing and the indoor coil are now ready for leak testing.
When brazing tubing sets to the service valves, a brazing shield MUST be used to prevent damage to the painted unit surface.
NOTE: Unit is shipped with R-410A factory charge indicated on nameplate.
Pass nitrogen or other inert gas through piping while braz-
ing to prevent formation of copper oxide.
PROVIDE SAFETY RELIEF — A fusible plug is located in unit suction line; do not cap this plug. If local code requires additional safety devices, install as directed.
Table 1A — 38HDF018-036 Physical Data
UNIT 38HDF 018 024 030 036 NOMINAL CAPACITY (Tons) 1.5 2.0 2.50 3.0 OPERATING WEIGHT (lb) 166 176 187 250 REFRIGERANT TYPE R-410A METERING DEVICE AccuRater (Located at Fan Coil) CHARGE (lb)* 4.8 5.3 5.0 7.1 OUTDOOR FAN
Rpm/Cfm 840/1720 840/1720 840/1720 850/1720 Diameter (in.) 18 18 18 24 No. Blades 333 3 Motor (hp)
1
/
8
OUTDOOR COIL
Face Area (sq ft) 5.82 7.27 7.27 12.1 No. Rows 233 2 FPI 20 20 20 20
HIGH PRESSURE SWITCH
Cut-In (psig) 420 ± 25 420 ± 25 420 ± 25 420 ± 25 Cutout (psig) 650 ± 10 650 ± 10 650 ± 10 650 ± 10
LOW PRESSURE SWITCH
Cut-In (psig) 45 ± 25 45 ± 25 45 ± 25 45 ± 25 Cutout (psig) 20 ± 5 20 ± 5 20 ± 5 20 ± 5
REFRIGERANT LINES
Connection Type Sweat Liquid Line (in.) OD Vapor Line (in.) OD Max Length (ft) 200 200 200 200 Max Lift (ft) 65 65 65 65
3
/
8
5
/
8
Max Drop (ft) 150 150 150 150
COMPRESSOR
Type Scroll Model ZP16K5E-PFV ZP21K5E-PFV ZP25K5E-PFV ZP34K5P-PFV Oil Charge (POE - oz) 25.0 25.0 25.0 42.0 Accumulator Ye s
CONTROLS
Fusible Plug (F) 210 Control Voltage† 24 vac
System Voltage 208/230 v 208/230 v 208/230 v
FINISH Gray
LEGEND *Unit shipped with full factory charge. See ARI (Air Conditioning and
FPI Fins Per Inch POE — Polyol E st er
1
/
8
3
/
8
5
/
8
1
/
8
3
/
8
3
/
4
1
/
4
3
/
8
3
/
4
208/230 v, Single and 3 Phase,
460 v, 3 Phase
Refrigeration Institute) capacity table for proper charge and piston for each fan coil type.
†24 v and a minimum of 40 va is provided in the fan coil unit.
4
Table 1B — 38HDR018-060 Physical Data
UNIT 38HDR 018 024 030 036 048 060 NOMINAL CAPACITY (Tons) 1.5 2.0 2.50 3.0 4.0 5.0 OPERATING WEIGHT (lb) 166 176 250 250 278 306 REFRIGERANT TYPE R-410A METERING DEVICE AccuRater (Located at Fan Coil) CHARGE (lb)* 6.3 6.5 10.0 8.9 12.0 12.2 OUTDOOR FAN
Rpm/Cfm 840/1720 840/1720 850/3900 850/3900 850/3900 850/3900 Diameter (in.) 18 18 24 18 24 24 No. Blades 333333 Motor (hp)
1
/
8
OUTDOOR COIL
Face Area (sq ft) 5.8 7.3 12.1 12.1 14.1 14.1 No. Rows 232233 FPI 20 20 20 20 20 20
HIGH PRESSURE SWITCH
Cut-In (psig) 420 ± 25 420 ± 25 420 ± 25 420 ± 25 420 ± 25 420 ± 25 Cutout (psig) 650 ± 10 650 ± 10 650 ± 10 650 ± 10 650 ± 10 650 ± 10
LOW PRESSURE SWITCH
Cut-In (psig) 45 ± 25 45 ± 25 45 ± 25 45 ± 25 45 ± 25 45 ± 25 Cutout (psig) 20 ± 5 20 ± 5 20 ± 5 20 ± 5 20 ± 5 20 ± 5
REFRIGERANT LINES
Connection Type Sweat Liquid Line (in.) OD Vapor Line (in.) OD Max Length (ft) 200 200 200 200 200 200
3
/
8
5
/
8
Max Lift (ft) 65 65 65 65 65 65 Max Drop (ft) 150 150 150 150 150 150
COMPRESSOR
Type Scroll Model ZP16K5E-PFV ZP21K5E-PFV ZP25K5E-PFV ZPZ9K5E-PFV ZP42K5E-PFV ZP51K5E-PFV Oil Charge (POE - oz) 25.0 25.0 25.0 25.0 42.0 42.0
Crankcase Heater (watts) 40 40 40 40
Accumulator Ye s
CONTROLS
Fusible Plug (F) 210 Control Voltage** 24 vac System Voltage 208/230 v 208/230 v 208/230 v 208/230 v, Single and 3 Phase, 460 v, 3 Phase
FINISH Gray
LEGEND *Unit shipped with full factory charge. See ARI (Air Conditioning
FPI Fins Per Inch POE — Polyol E st er
1
/
8
3
/
8
5
/
8
1
/
4
3
/
8
3
/
4
1
/
4
3
/
8
3
/
4
1
/
4
3
/
8
7
/
8
1
/
4
3
/
8
7
/8†
and Refrigeration Institute) capacity table for proper charge and piston for each fan coil type.
†Valve connection size is
11/8inches.
7
/8inch. Recommended line size is
**24 v and a minimum of 40 va is provided in the fan coil unit.
5
Loading...
+ 11 hidden pages