4'-0" OVERHEAD SPACE REQ'D
FOR SERVICE AND AIR FLOW
3 -0 (BOTH SIDES)
LIQUID LINE VALVE
LIQUID LINE CONN
CONCRETE
MOUNTING
TRANSPORTATION DAMAGE
File claim with shipping company if shipment is
damaged or incomplete.
Unpackaging Unit — Move condensing unit to final
location. Open carton at end marked “compressor
end.” Slide unit from carton taking special care to
not damage service valves or grilles.
PRELIMINARY SURVEY
Consult local building codes and National
Electrical Code (NEC) for special installation
requirements.
When installing unit, allow sufficient space for
air flow clearance, wiring, refrigerant piping and
servicing unit. Position unit so water from roof or
eaves does not flow directly on top of unit.
Install unit on a solid, level mounting pad. Unit
can be attached to pad with a mastic adhesive or
by drilling holes in base pan for 1/4-in. mounting
bolts. Do not block base pan water drainage holes.
38GS,CC,CE Condensing Units Connected to
Carrier Matched Evaporators with Carrier Acces
sory Tubing — Check system refrigerant charge
when tubing lengths are above or below 25 feet.
See Refrigerant Charging (page 10) for details.
Fig. 1 — Dimensions, Connections and Mounting Pad
38GS,CC,CE Unit
Table 1 — Installation Data
38GS
014
COND UNIT 38CC
OPER WT (lb)130 135
UNIT DIM. (ft-in.)
Length A
Width B
Height G
REFRIG CONN.(in.)
Suction (ODF)
Liquid (ODF)
*5/8-in suction connection on 38CE002
t38CE045,005 and 38GS.CC060 are factory supplied with 3/4- to
1 1/8-in suction valve adapter (field installed) for 1 1/8-in
38GS,CC,CE Condensing Units Connected to NonCarrier Evaporators — Check refrigerant charge
when condensing unit is added to a system in
which other than a Carrier approved evaporator is
being used or where the evaporator has been
previously installed. Field-supplied refrigerant pip
ing must be in accordance with Field-Supplied
Piping Data, Table 3.
Where indicated on Table 3 for 38GS,CE units,
install a liquid line filter-drier and accessory crank
case heater on condensing unit. (Filter-drier is
factory supplied on CE045,005 units.) Accessory
start capacitor and relay also required on 38GS
units, but not normally required on 38CE units.
See Compressor Service (page 7). All above items
are standard or not required for 38CC units.
Use an evaporator coil with a bleed-type ex
pansion device. If coil does not have a bleed-type
expansion device it may be necessary to add an
accessory start capacitor and relay to condensing
unit. This would require removing compressor start
tForb/8-in evaporator connection, cut off 3/4-in end
PIPING CONNECTIONS
Condensing units can be connected to evap
orator sections using Carrier accessory tubing
package or field-supplied tubing of refrigerant
grade. (Accessory tubing not available for
38GS060, 38CC060.) See Table 2 for accessory
tubing sizes and Table 3 for recommended fieldsupplied tubing sizes. Where evaporator is 20 ft or
more below condensing unit, reduce liquid line size
one diameter (min 1/4-in. OD).
A capacity reduction will result if accessory
tubing is used in 38CE045,005 systems. For
example, when a 25 ft accessory tubing package is
used, there will be a capacity reduction of 3 3/4%
on 38CE045 and 5% on 38CE005 systems. For
maximum capacity from these systems, use tubing
sizes shown in Table 3.
When other than 25 ft of interconnecting
tubing is used, follow special requirements de
scribed in Refrigerant Charging. Do not use less
than 10 ft of liquid line. Do not cut 5/16-in. or
1/4-in. liquid line. Bend or coil to fit.
Do not use damaged or contaminated tubing. If
accessory tubing package or evaporator section has
been open for more than 15 seconds per connec
tion, evacuate or purge evaporator coil and tubing
system (use field-supplied refrigerant, not unit
refrigerant). Always evacuate or purge if fieldsupplied tubing is used.
Before Connecting Unit Piping, consider the
following:
38CE045,005 AND 38CC UNITS - A filter-drier
package is shipped with these units. Included with
filter-drier are 2 short length tubing assemblies that
are equipped with flare and/or Compatible Fit
tings. Use tubing assemblies to install filter-drier
into system liquid line at evaporator or condensing
unit. See Fig. 2. Connect tubing assembly A (90°
assembly) to evaporator or condensing unit liquid
line Compatible Fitting. Complete the filter-drier
installation as shown.
Page 3
Table 3 — Field-Supplied Piping Data
MAX COND
COND
X-
f 3 UNIT
38GS014,
38GS018
38GS024
38GS030,
38CC030,
38CE002
38GS036,
38CC036,
38CE003
38GS042,
38CC042,
38CE004
38GS048,
38CC048
38CE045
38GS06 0,
38CC060,
38CE005
Cap. Tube
TXV
NOTES
REFRIG
CONTROL
TXV
Cap. Tube
or
AccuRater'*'^
TXV
Cap. Tube
AccuRater
Cap. Tube
or
AccuRater
TXV
Cap. Tube
or
AccuRater
TXV
Cap Tube
or
AccuRater
TXV
Cap Tube
or
AccuRater
TXV
Cap. Tube
or
AccuRater
L^y
Cap. Tube
or
AccuRater
Crankcase heater and liquid line filter-drier required
on 38GS and 38CE units Accessory start capacitor
with relay also required on 38GS unit, but not
normally required on 38CE units See Compressor
Service Reduce liquid line diameter by 1/8-in OD
(min 1/4-in OD) when evaporator is 20 ft or more
below condensing unit
■ Capillary Tube
- Thermal Expansion Valve
1 The following system modifications are required adjust
refrigerant charge on systems with over 25 ft separation
UNIT HT (ft)
Above
Evap
90
150
yo
150
150
90
150
90
150
90 ■
150
90
150
90
150
Be low
Evap
90
50
90
50%
__
50
90
50
90
50
90
50
90
50
90
50
25- 50 51»7S7&~1
SuetLiq
V
'8V»'xiiiiiilili
%
%
%
%
1%
IV»
Vs
V» T
V»
/4
% liM
% Iliiii
V»
REFRIGERANT LINE LENGTH (ft)
Line Diameter (in* OD)
'
IIBI
ilM
iiiiiiiiiii
wmmmmmmm
Ns
T%
k
between condensing unit and evaporator (See Refrigerant
Charging ) Adjust system oil charge as described in Note 2
Oil charge adjustment add 1% of nominal oil charge in
system (Table 7) for each 10 ft of refrigerant line length
above 50 feet Eor example, a system that has a 50-oz oil
charge with 1 50 ft of interconnecting piping requires 5 oz of
additional oil as shown below:
V
iÄiii
MB
ISl
*
150 ft - 50 ft = 100 ft
100 ft -E 10 ft = 10 ft
Litj 1LEíj
iiiiii
IH
■
ilBi%
■
11»
Äiii
10x1% = 10% ( 10)
10 X 50 oz = 5 oz
Do not permit condensing unit to short cycle, particularly on
applications with long vertical line lengths Correct short
cycling condition immediately
m
¡Mil
Í.
..............
Connection Procedure — When making tubing
connections, be sure to provide clearance at unit
for electrical connections.
Connect refrigerant liquid and suction lines to
condensing unit, Fig. 1. Unit Compatible Fittings
permit 2 methods of refrigerant line connection;
mechanical (quick connect) or sweat connection.
Make suction line connection first.
38CE045,005, 38GS060 AND 38CC060 UNITS Remove suction line adapter taped to compressor
suction line. Connect 3/4-in. end of adapter to unit
suction line Compatible Fitting. Sweat connect
refrigerant suction line to 1 1/8-in. end of adapter.
Connect liquid refrigerant line to unit.
MECHANICAL CONNECTION (Mate one set of
connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do
not remove.
Remove plug and be sure 0-ring is in the groove
2.
inside the Compatible Fitting.
Cut tubing to correct length.
3.
Use gage on tag attached to service valve to
4.
mark tube end for correct insertion depth.
Insert tube into Compatible Fitting until it
bottoms. (Tube should be inserted at least as
far as mark on tubing.)
Tighten nut until it bottoms on back coupling
5.
flange.
Page 4
c
Fig. 2 — Filter-Drier Assembly Installation (38CC, 38CE045 and 005)
SWEAT CONNECTION (Use refrigerant grade
tubing.)
1. Remove locking nut, rubber 0-ring and
Schrader core from valve.
2. Cut tubing to correct length.
3. Insert tube into Compatible Fitting. Wrap top
and bottom of service valves in wet cloth to
prevent damage by heat. Solder with low
temperature (450 F) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied
refrigerant.
ELECTRICAL DATA AND WIRING
Field wiring must comply with local and
national fire, safety and electrical codes. Voltage to
unit must be within ± 10% of voltage indicated on
nameplate. Contact local power company for
correction of improper line voltage.
of ifolt ois tmpro|>er Ime
When making electrical connections, provide
clearance at unit for refrigerant piping connections.
See Table 4 for recommended wire and fuse sizes.
Install a Branch Circuit Fused Disconnect of
adequate size to handle unit starting current.
Locate disconnect within sight of and readily
accessible from the unit, per section 440-14 of
National Electrical Code (NEC).
Bring Line Power Leads Into Unit — Extend leads
from fused disconnect thru hole provided in service
embossment (Fig. 1) and thru 7/8-in. hole into
control box.
Connect Ground Lead to a Ground Lug in Control
Box for safety. Connect power wiring. See Fig. 3.
Splice line power leads to red and violet pigtails on
38GS,CE units or to yellow pigtails (3) on 38CC
units. Use wire nuts supplied with unit. Tape each
connection. Wire nuts are suitable for copper or
aluminum wire since they contain joint compound.
Control Power (24 v) wiring is brought thru hole in
service embossment and spliced to yellow pigtails
on all units. See Fig. 4.
Furnace or fan-coil transformer must be used as
24-v supply for system as shown in Fig. 4 (At least
a 40-va transformer is recommended.) Current
38GS048,060 and 38CC048,060 units are equip
ped with a low-voltage transformer used to power
contactor thru unit control circuit. This trans
former must not be used for powering the indoor
thermostat control circuit.
Page 5
I-PHASE
CONN. TO
FUSED
DISCONNECT
3-PHASE
CONN. TO
FUSED
DISCONNECT
SPLICE
------------
FACTORY WIRING
------------
FIELD WIRING
p
—
--I3D GROUND LUG
386S,CEC0NDUNIT
-YEL-
-YEL-
-YEL-
-------I3D GROUND LUG
38CC CONO UNIT
Fig. 3 — Line Power Connections
THERMOSTAT SUBBASE
THERMOSTAT SUBBASE
HH93AZ076
(COOLING ONLY)
THERMOSTAT SUBBASE
HH93AZ042 OR
ONE TRANSFORMER
(COOLING AND ONE-STAGE HEATING)
^CONNECT FS TO LOW-SPEED INDOOR FAN TERMINAL
WHEN 2-SPEED FAN IS USED
IFR, FS and IFM are located in furnace on heating-cooling
applications If accessory IFR is required for cooling only
applications, locate (IFR) in fan coiI
ARRANGEMENT C-
ONE TRANSFORMER
(COOLING AND 2-STAGE HEATING)
^CONNECT FS TO LOW-SPEED INDOOR FAN TERMINAL
WHEN 2-SPEED FAN IS USED
Fig. 4 -- Control Circuit Connections
Control Relay (10 va) or Contactor
Fan Switch
Heating Control
I ndoor Fan Motor
I ndoor Fan Relay
Transformer
Field Splice
---------------
Field Wiring
---------------- Factory Wiring
5
Page 6
Table 4 — Electrical Data
030
036
036
042
042
042
048
048
048
060
060
060
___
___
___
___
___
___
___
___
___
___
___
___
200/230/3253
200/230/3253
460/3506
200/3
230/3253
460/3506
200/3
230/3253
460/3
200/3
230/3
460/3506
22018092
220
506
220
253207
38CE
002
003
___
___
230/1253
230/1
253
004___230/1253
045
005
___
___
230/1253
230/1253
180
18080/70
414
207
41446
18090
20778.5
41439 3
180
414
20765
20782
207
2078823.9
20710027.9
70/60
35
92
13 0/11 5
14 0/12 6
no
100
50
~8819.8
6 5
17 0
15 8
7 8
18 6
16.1
8 3
23 0
20 5
10 3
10.3
16 8
FAN
FLA
2.414
2.1
2 4
2,4
.........
2 1
2.114
2 4
2.410
2 1
2.1
2 48
2.4
2 110
2.11036
2 48
2.4
2 1
2.1
2.18
2.1
2 1
2 0/2 .0
2 0/2 0
1.0
2 0
2 0
1 014
2 0
2.0
1 014
2.08
2 010
1 014
2-.1
2 1
2.1
2.1103155
2 1
___12______
BRANCH CIRCUIT
Wire
Sizef
(AWG)
14
12
123625
10
123130
123130
8
8
10
103350
8
6
12
12
1491
1049
1058
10
10
12
10
1036
8
Max
Ft
Wiref
40
33
28
..37
..........
19
40
35
4550
45
34
44
36
33
41
42
54
49
4530/30
100
46
60
10020
'■ 6750
47
1 74
42
42
4260
Fusei
Amps
20
20
30
20
25
35
40
50
30
45
55
65
50
65
55
75
30/25
15
35
35
15
40
35
45
20
25
35
45
FLA — Full Load Amps LRA — Locked Rotor Amps
______Electrical data shown applicable to all units for
which complete model number is not shown
•Permissible limits of the voltage range at which the units
will operate satisfactorily
START-UP INSTRUCTIONS
If unit is equipped with crankcase heater,
energize heater a minimum of 24 hours before
starting unit To energize heater only, set thermo
stat at “Off” position and close electrical dis
connect to condensing unit.
Units with Time Guard® circuit or solid state
time-delay may not start for approximately 4 to 5
minutes after thermostat closes. See compressor
controls, pages 7 and 8.
Start Procedure
1. Backseat (open) liquid and suction line service
valves.
(■Copper wire sizes Aluminum field wiring may be used when splice-
connected to copper pigtails from unit with factory-supplied wire nuts
Use latest National Electrical Code for aluminum wire sizing
^Maximum dual element fuse size
NOTE Control circuit voltage is 24 volts on all units
ov«rtii^i<?n servkc
4 Do exscod
6 fi-lb lorquc »hen
iighiiiiing.
2. Set thermostat selector switch at "Off.”
3. Set room thermostat at desired temperature.
4. Close electrical disconnects energizing entire
system.
5. Set room thermostat at “Cool” and fan switch
as desired (“Fan”) (“Auto.”).
Check system refrigerant charge. See Refrig
erant Charging.
Motors and controls will operate satisfactorily
in a range from 10% above to 10% below nominal
unit voltage (Table 4).
Page 7
Do not connect charging hoses to capillarycontrolled system during initial start procedure.
(Loss of charge from this procedure may result in
capacity reduction.) If necessary to add manifold
f • gages for servicing, refer to Carrier Standard
Service Techniques Manual, Chapter 1, pages 1—5,
Fig. 8, for bypass method of returning charge to
system. (A charging hose valve must be used to
accomplish bypass of refrigerant on all units.)
"■Factory refrigerant charge adequate for complete system when
connected to Carrier approved evaporators mat are the same
size as condensing unit, with 25 ft of tubing
R-22
CHG*
(lb—oz)
3- 02600
3- 0
3- 0
3- 2
3-M
5- 3
3-14
5- 3
4- 7
4-11
5- 6
5-11
CONDENSER
Rpm
106017/2
1070/870
975/800
Diam
COMPRESSOR SERVICE
Unit Single-Phase Compressors of the Split Capaci
tor (PSC) Type require an equalized system pres
sure to start. When supply voltage is within 10%
limit and compressor does not start, give com
pressor a temporary capacitance boost. See Carrier
Standard Service Techniques Manual, Chapter 2,
for details. Use a 130-mfd start capacitor. Connect
wires with insulated probes to each capacitor
terminal. Touch probes to each side of run
capacitor or to compressor motor terminals R and
S. Start compressor; pull probes away after 3
seconds. Discharge start capacitor. Run compressor
for 10 minutes, then shut off and allow system
pressure to equalize. Try restarting without boost
capacitor. If after 2 attempts (without boost
capacitor) the compressor does not start, add an
accessory start capacitor relay package.
Unit Single-Phase Compressors That are Equipped
With a Compressor Start Thermistor (PTC device);
if compressor will not start, check the thermistor
with an ohmmeter as described below. (If evap
orator coil does not have a bleed-type expansion
device, it may be necessary to remove PTC device
and replace with accessory start capacitor and
relay.)
(in.)
17/2
17/2
FAN
2600/2100
2600/2100
2800/2300
2700/2200
2700/2200
Cfm
2600
2600
2600
2600
2800
2800
2800
2600
2600
2800
2800
2800
CHECKING START THERMISTOR
1. Shut off all power to unit and wait 5 minutes
for thermistor to cool to outdoor temperature.
2. Measure resistance of thermistor with ohmmeter.
Normal resistance readings are 50 to 90 ohms at
75 F outdoor temperature.
3. If ohmmeter resistance reading is 0 or much
higher than 90 ohms the thermistor is defective
and must be replaced.
If start thermistor is good and compressor will
not start, disconnect the thermistor from starting
circuit and give compressor a temporary capaci
tance boost as described above. Run compressor
for 10 minutes, then shut off and allow system
pressure to equalize. Reconnect start thermistor
and try restarting compressor without boost capac
itor. If after 2 attempts the compressor does not
start, remove thermistor and add an accessory start
capacitor relay package.
38CC Units — Compressor start capacitor and relay
or thermistor (PTC) are not required on 3-phase
38CC units.
Safety Devices — Refer to Table 6 for particular
safety controls that each unit is equipped with.
Table 6 — Compressor Safety Controls
SAFETY CONTROLS
INTERNAL CURRENT-
TEMP SENSITIVE
OVERLOAD
INTERNAL THERMO
(Pilot Duty)
LOW-PRESS. SWITCH
HIGH-PRESS. SWITCH
CRANKCASE HEATERAccessory
OUTDOOR FAN
THERMOSTAT
TIME GUARD®
CPCS
SOLID STATE TIMER
CPCS
Compressor Protection Control System
38GS
014,018
024,030
036,042,048
060
-
-
-
060
-
ENSING 1
030,036,
042,048
030, Ò3C
042,048,
030,036,
042,048.
030,036,
042,048.
030,036,
048,060-
38CC ^
060
060
060
060
-
042
-
NITS
38CE
002,003,
004,045,
005
Accessory
-
Accessory
002,003,
004,045,005
-
045,005
COND
UNIT PROTECTION
Internal Current And Temperature Sensitive Over
loads reset automatically when internal motor
temperature drops to a safe level (overloads may
require up to 30 minutes to reset). When an
internal overload is suspected of being open, check
by using an ohmmeter or continuity tester. If
necessary, refer to Carrier Standard Service
Techniques Manual, Chapter 2, for complete
instructions.
Page 8
Low-Pressure Switch is located on unit suction line
High-Pressure Switch is located on unit liquid line
and resets automatically. High pressurestat settings
are; cutout, 425 ± 5 psig; cut-in, 320 ± 20 psig.
Crankcase Heater warms compressor crankcase.
Prevents refrigerant dilution of oil in crankcase.
Outdoor Fan Thermostat maintains proper con
densing temperature at high outdoor temperatures
by switching fan to high speed. Located in control
box (on 38CE).
Filter-Drier is installed in liquid line.
Time Guard® Circuit provides for a 5-minute delay
before restarting compressor after shutdown for
any reason. On normal start-up the Time Guard
timer causes a delay of 15 seconds after thermostat
closes before compressor will start. On compressor
shutdown, the timer recycles for 4 minutes, 45
seconds. During this time the compressor cannot
start.
Solid State Time Delay provides for a 4-minute
delay before restarting compressor after shutdown
for any reason. On normal start-up, timer is
energized after thermostat closes and causes a
4-minute delay before compressor will start.
tection; compressor motor running overload pro
tection; compressor overtemperature protection;
contactor antichatter protection.
The CPCS also provides for a 4- to 6-minute
delay before restarting compressor after shutdown
for any reason. I f compressor loading was light at
the moment compressor was shut off, the delay
will be approximately 4 minutes. If loading was
heavy, the delay will be approximately 6 minutes.
To troubleshoot the CPCS, use unit label diagram
or wiring booklet and the following Control Circuit
Troubleshooting Chart.
CONTROL CIRCUIT TROUBLESHOOTING
CHART NOTES:
2. To disconnect plug from receptacle on CPCS
board — press in tabs located on the receptacle
and pull plug gently while holding tabs. Do not
pull on wiring.
When performing troubleshooting checks, CPCS
3.
receptacle must be plugged into CPCS board.
Receptacle female connections, which do not
4.
grip the male pin tightly, may be repaired with
a small pen knife.
When taking meter readings at CPCS receptacle,
5.
bottom meter probe into terminal hole to
ensure good electrical contact.
Replace CPCS board if electrical short circuit
6.
causes compressor failure. An electrical short in
compressor can short the triac (electronic
switch located on CPCS board). Triac may fail
in a closed (conducting) position and will not
open the control circuit.
Compressor Removal (See Table 7 for compressor
information and Fig. 5 for component location.)
1. Shut off power to unit. Vent refrigerant to
atmosphere or use refrigerant removal methods
shown in Carrier Standard Service Techniques
Manual, Chapter 1.
Remove top access cover and rear access wrap
2.
per (Fig. 5).
Remove power leads from compressor terminal
3.
box. Unsweat suction and hot gas lines.
Remove compressor hold-down bolts. Lift
4.
compressor out thru top or back of unit.
CONTROL
COMPRESSOR
TERMINAL
BOX
CAUTiON: Iks nmt
i>ece|siacle fiHscomsctsd fr«i ebm*
will up CICS
1. Ensure thermostat calls for cooling before
troubleshooting unit.
LIQUID LINE
Fig. 5 — Condensing Unit with Access
Panels Removed
(38CE Unit Shown)
Page 9
■ .
CONTROL CIRCUIT TROUBLESHOOTING CHART (GS,CC048 and 060)
Before attempting any corrective action, wait 8 minutes after power is supplied to permit CPCS time delay period to end. If control circuit
broken and unit has no time delay (or if time delay is over 8 minutes), replace CPCS board
tVoltage reading less than 20 volts may result from feedback circuit
order to make repairs on low side of system
without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve
gage port.
2. Frontseat the liquid line valve.
3. Jumper low-pressure switch (if unit is so
equipped).
4. Start unit and run until suction pressure reaches
5 psig (see Caution).
5. Shut unit off and frontseat suction valve.
6. Vent remaining pressure to atmosphere.
I
REFRIGERANT CHARGING
The 38GS,CC,CE condensing units contain
correct operating charge for complete system when
connected to Carrier approved evaporators that are
the same size as condensing unit, with 25 ft or less
of tubing of recommended size. Charge adjustment
may be required on other systems.
Listed (Table 8) and described below are
recommended methods of checking, adjusting or
recharging Carrier approved systems. When recharg
ing these systems, evacuate system to 5000 mi
crons (29.7-in. vacuum), and weigh in charge
shown in Table 5. When system is not evacuated,
subtract the following amount from total charge.
38CE045,005 - .31 lb (4.8 oz)
(Dial-a-charge charging cylinder is an accurate
device used to recharge systems by weight. These
cylinders are available at refrigeration supply
firms.) After weighing in charge, check or adjust
charge using the Chargemaster® charging device,
charging chart or sight glass method as recom
mended in Table 8. Refer to Carrier Standard
Service Techniques Manual, Chapter 1, for system
evacuation — dehydration instructions.
When 38GS,CC,CE condensing units are con
nected to other than a Carrier evaporator, evacuate
system and weigh in charge shown in Table 5 or
use sight glass method of recharging (38CC thermal
expansion valve systems only).
10
Page 11
Table 8 — Refrigerant Charging Methods
(Carrier Approved Systems)
METHODS OF CHECKING
CONO
UNIT
AccuRater^ ^
38GS
38CC
38CE
TXV — Thermal Expansion Valve
0^ ADJUSTING CHARGE
System Refrigerant Control
Capillary
Tube
Chargemaster ®
or
Charging Chart
Chargemaster
or
Charging Chart
Chargemaster
or
Charging Chart
TXV
Charging Chart
Charging Chart
Sight Glass
Charging Chart
Charging Chart Method — For thermal expansion
valve systems, use Charging Chart, Fig. 6 or 7. See
Carrier Standard Service Techniques Manual,
Chapter 1, for procedure. For capillary tube or
AccuRater"''i'^ systems, use Charging Chart, Fig. 8
or 9 and the following procedure:
1. Operate unit a minimum of 10 minutes before
checking charge.
2. Measure suction pressure by attaching a gage to
suction valve service port.
3. Measure suction line temperature by attaching a
service thermometer to unit suction line near
compressor. (Insulate thermometer for accurate
readings.)
4. Measure outdoor (condenser inlet) air dry-bulb
temperature with second thermometer.
5. Refer to Charging Chart (Fig. 8 or 9). Find
condenser air temperature and project hori
zontally to curve showing suction pressure.
6. From intersect point, project vertically down
ward to chart suction hne temperature.
7. If unit has a higher suction line temperature
than chart, add refrigerant until chart tempera
ture is reached.
8. If unit has a lower suction line temperature
than chart, bleed refrigerant until chart tem
perature is reached.
9. If condenser inlet air temperature or unit
suction pressure changes, change to new suction
line temperature on chart.
Chargemaster® Operation — Operate unit 10 min
utes before using Chargemaster (Carrier Part No.
38GC680004).
RECHARGING METHODS
System Refrigerant Control
AccuRater
Weight Method
Chargemaster or
Charging Chart
Wei ght Method
or
Chargemaster or
Charging Chart
Weight Method
Chargemaster or
Charging Chart
Capillary
Tube
plus
plus
plus
TXV
Wei ght Method
plus
Charging Chart
Weight Method
plus
Charging Chart or
Sight Glass
Wei ght Method
plus
Charging Chart
1. Tape Chargemaster feeler bulb to suction line
close to condensing unit. Insulate bulb. Ensure
suction line is clean for good contact with bulb.
2. Connect refrigerant drum to Chargemaster inlet
port with drum in position for vapor charging.
3. Connect Chargemaster outlet port to unit suc
tion valve service port.
4. Crack valves on refrigerant drum and Chargemaster to purge lines from drum to suction
valve. After purging lines, close valve on Charge-
master only.
5. Measure outdoor air dry-bulb temperature.
6. Crack unit suction valve and read evaporatortemperature at red needle position on Chargemaster temperature gage and suction line tem
perature at black needle position.
CAIHIOI^; Do myi tmé
7. Enter Chargemaster Charging Chart, Table 9 or
10, at outdoor air temperature (step 5) and
evaporator temperature (step 6). Find the
suction line temperature required for correct
system charge. If actual suction line tempera
ture (step 6) is higher than table value, the
system is undercharged. If suction line tempera
ture is lower than table value, the system is
overcharged.
Example (Table 10): At outdoor air tempera
ture of 85 F and evaporator temperature of
44 F, the system will be correctly charged at
71 F ± 2 F suction line temperature.
11
Page 12
8. Add charge by slowly opening Chargemaster®
valve. If necessary, reduce charge by bleeding at
liquid line service valve. Check outdoor air and
evaporator temperature during procedure. If
they change, refer back to Chargemaster
Charging Chart for new value.
Correct use of Chargemaster ensures an opti
mum refrigerant charge will be in system when
conditions and system components are normal.
However, the Chargemaster does not solve or fix
system abnormalities. It indicates correct charge
for condition of system. It will not make correc
tions for dirty filters, slow fans, excessively long or
short suction lines or other abnormal conditions.
This charging device ensures that a correct relation
ship exists between outdoor temperature, evap
orator temperature, and suction line temperature
on a specific system.
Sight Glass Method — A satisfactory operating
charge can be obtained on thermal expansion valve
systems by charging to a clear sight glass. For
optimum charge, elevate high-side pressure to
380 ± 10 psig by blocking condenser fan discharge
or condenser entering air. Charge to a clear sight
glass while holding high-side pressure constant. For
peak efficiency, adjust charge to yield a liquid
refrigerant temperature at the evaporator that is
approximately the same as outdoor dry-bulb
temperature.
A
I
12
Page 13
Table 9 — 38GS,CC Chargemaster® Charging Chart
(Capillary Tube or AccuRaterTM Systems)
30 40 50 60 70
SUCTION LINE TEMPERATURE (»F)
80
Fig. 8 — 38GS,CC Charging Chart
(Capillary Tube or AccuRaterTM Systems)
UU1UUUK
TEMP (F)
60
62
64
66
3240
30- 38
28
27
68
70
72
74
76
78
80
82
90
84
86
88
90
92
94
96
9836
100
102
104
106
108
no
112
114
*Saturated evaporator temperature which is the equivalent tem
perature of pressure taken at the condensing unit suction service
valve
EVAPORATOR TEMP (F)*
28
25 _
“1"
34 37
3ii
Suction L.ine Temperatures
51 ^
49
3747
354557
34
32
31
30
293646
273544
26
43
41
3950
37
33
3240
31
2937
60
67
54
64
52
6172
58
48
56
546375
5261
42
5059
48
38
4655
44536170
35
4251
34
414957
33
39
38
69
66
5766
4755
4553
4451
42
414855
3946
40
43 45 48
72
68
80
76
63
7385
81
59
68 7890
657586
637283
7080
61
6777
59
4957
5361
45515968
43495765
41
475563
4653
75
65
73
63
70
61
59
50
Fig. 9 — 38CE Charging Chart
(Capillary Tube or AccuRaterTM Systems)
13
Table 10 — 38CE Chargemaster® Charging Chart
(Capillary Tube or AccuRaterTM Systems)
EVAPORATOR TEMP (F)
TEMP (F)
60
65
70
75
80
85
32
60
49
41 48 58
35
31
iii
9040
95
100
10544
no
115
Example
36j3Sj40|42
Suction Line
58 65
41 48 58
36 42
......
.1.
— •1
68
50
70
68
59
>, V'
47 53
42
'em
75
69
48 53
43
4^48|50
44
peratore (F]
82
'
6; 69
59
4/ 52
48 53
__
78
67 79
68 88
58
60
49 54 65
50
52
75
62
54
104
80
69
Page 14
COMPATIBLE FITTING REPAIR
Leaking Mechanical Connection — Frontseat con
densing unit service valves and relieve refrigerant
pressure in tubing. Back locknut off Compatible
Fitting onto tube. Cut fitting between threads and
seal ring head as shown in Fig. 10. Remove tubing
section remaining in threaded portion of fitting.
Discard locknut.
Clean, flux, and insert new tube end into
remaining portion of Compatible Fitting. Wrapvalve base in wet rag. Heat and apply low tempera
ture (450 F) solder.
Leaking Sweat Connection — Frontseat service
valves and relieve refrigerant pressure in tubing.
Clean and flux area around leak and apply low
temperature (450 F) solder.
Evacuate or purge evaporator coil and tubing
system. Add refrigerant charge (see charging
instructions).
Off íA&m
Fan Motor Removal
1. Shut off power to unit.
2. Remove unit top access cover and fan grille.
3. Disconnect fan motor wires from fan capacitor
and control relay or contactor. Pull wires out of
control box.
4. Remove fan from motor shaft by pulling
upward on fan hub.
5. Loosen bolt holding fan motor to motor
mounting bracket. Remove motor thru top of
unit. To replace motor, place motor on self
positioning motor mounting flanges and re
tighten bolt.
Fig. 11 — Condenser Fan Position
Fig. 10 — Repair of Mechanical Connection
CONDENSER
Coil Cleaning — Ensure power to unit is shut off
Clean the condensing unit coil at the beginning of
every cooling season or more often if required. Use
ordinary garden hose at a pressure high enough to
clean efficiently. For best results, unscrew and
remove unit top cover (grille). Insert hose nozzle
between fan blades and spray coil fins from
inside-to-outside the unit. If unit has a double-row
coil, loosen screws to separate coils, and flush dirt
toward outside of both coils. Flush dirt from base
pan by spraying water thru top of unit. Avoid
splashing mud on coil or water on the fan motor.
Metal Fan — Required fan position is shown in Fig.
11. Adjust fan by loosening setscrew and moving
fan blades up or down.
Plastic Fan is correctly positioned in unit by
placing fan on motor shaft — align flat mark on top
of fan hub with flat on shaft. Press down evenly on
top of fan hub until shaft bottoms in fan hub.
LUBRICATION
Fan Motor Bearings — Oiling holes are provided at
each end of current condenser fan motor. Remove
fan motor and lubricate motor with 32 drops (16
drops per hole) of SAE-10 nondetergent oil at
intervals described below:
a. Annually, when environment is very dirty,
ambient temperature is higher than 105 F and
average unit operating time exceeds 15 hours a
day.
b. Every 3 years when environment is reasonably
clean, ambient temperature is less than 105 F
and unit operating time averages 8 to 15 hours
a day.
c. Every 5 years when environment is clean,
ambient temperature is less than 105 F and unit
operating time averages less than 8 hours a day.
Compressor contains factory oil charge. When oil is
lost, see Table 7 for oil charge and Carrier Standard
Service Techniques Manual, Chapter 1, page 1—21,
for instructions. Use Carrier PP33-1, Texaco
Capella B or Suniso 3G oil.
14
Page 15
TROUBLESHOOTING CHART*
*To troubleshoot control circuit on 38GS048,060 and 38CC048.060 units, see Control Circuit Troubleshooting Chart, page 9.
15
Page 16
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Tab 4
Form 38GS-13SI Supersedes 38GS-10SI
Printed in U.S.A.2-75 Codes D and MS Catalog No. 533-810
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.