Carrier 38GS User Manual

Page 1
Number One Airconditioning Mater
Syracuse New York

Air-Cooled Condensing Units

g DIAM KOS FOR CONTROL WIRING
SUCTION LINE CONN
SUCTION LINE VALVE
4'-0" OVERHEAD SPACE REQ'D FOR SERVICE AND AIR FLOW
3 -0 (BOTH SIDES)
LIQUID LINE VALVE
LIQUID LINE CONN
CONCRETE
MOUNTING

TRANSPORTATION DAMAGE

File claim with shipping company if shipment is
damaged or incomplete.
Unpackaging Unit — Move condensing unit to final
location. Open carton at end marked “compressor end.” Slide unit from carton taking special care to not damage service valves or grilles.

PRELIMINARY SURVEY

Consult local building codes and National Electrical Code (NEC) for special installation requirements.
When installing unit, allow sufficient space for air flow clearance, wiring, refrigerant piping and servicing unit. Position unit so water from roof or eaves does not flow directly on top of unit.
Install unit on a solid, level mounting pad. Unit can be attached to pad with a mastic adhesive or
by drilling holes in base pan for 1/4-in. mounting bolts. Do not block base pan water drainage holes.
38GS,CC,CE Condensing Units Connected to Carrier Matched Evaporators with Carrier Acces
sory Tubing — Check system refrigerant charge
when tubing lengths are above or below 25 feet. See Refrigerant Charging (page 10) for details.
Fig. 1 — Dimensions, Connections and Mounting Pad
38GS,CC,CE Unit
Table 1 — Installation Data
38GS
014
COND UNIT 38CC
OPER WT (lb) 130 135 UNIT DIM. (ft-in.)
Length A
Width B
Height G
REFRIG CONN.(in.)
Suction (ODF)
Liquid (ODF)
*5/8-in suction connection on 38CE002
t38CE045,005 and 38GS.CC060 are factory supplied with 3/4- to
1 1/8-in suction valve adapter (field installed) for 1 1/8-in
suction line
© Carrier Corporation 1975
38CB
- - -
- - -
'l-4
% lYsT '/b I
018
1-4
024
142|149
N4
Com
036 042
030 030 036 002* 003 004 045 005
158 191
2-10V4
1-10
1-4 1 1-4 (2-0
DOtible Fittings
%
'8
048 060t
042 048 060t
193 200
----
2-0 2-0
-----
'/4t
38GS,CC,CE Condensing Units Connected to Non­Carrier Evaporators — Check refrigerant charge
when condensing unit is added to a system in which other than a Carrier approved evaporator is being used or where the evaporator has been previously installed. Field-supplied refrigerant pip ing must be in accordance with Field-Supplied Piping Data, Table 3.
Where indicated on Table 3 for 38GS,CE units,
install a liquid line filter-drier and accessory crank case heater on condensing unit. (Filter-drier is factory supplied on CE045,005 units.) Accessory start capacitor and relay also required on 38GS
units, but not normally required on 38CE units.
See Compressor Service (page 7). All above items are standard or not required for 38CC units.
Use an evaporator coil with a bleed-type ex pansion device. If coil does not have a bleed-type expansion device it may be necessary to add an accessory start capacitor and relay to condensing unit. This would require removing compressor start
thermistor (PTC device) on units so equipped.
Form 38GS-13SI
Page 2
Table 2 — Accessories
PART
NUMBER
HH01AD040 HH93AZ040
JHH51AR00J[^
HH07AT070, HH07AT074 H N93^076
HH0iAD042”
HH93AZ042 HH01YA092
HH_93_YZ094 32LT900301
(200-3 Ph) 32LT900601 (460-3 Ph)
38GS900102 38GS900212
38GS900112 38GS900292
38GS900172 38GS900182
38GC900031 10 38GC900071 10 38GC900041 38GC900081 38GS900221 38GC900091 38GC900061 35
38GC900101 38GC900191 50 % 38GC900ni
Low-Voltage Control Honeywell Deluxe Thermostat Thermostat Subbase
Comfort Control Center (Use with HH01AD040)
Low-Voltage Control — Honeywell Thermostat Thermostat Subbase (with Automatic Changeover)
Low-Voltage Control ~ Honeywell Thermostat Thermostat Subbase
Low-Voltage Control Grayson Thermostat Thermostat Subbase
Solid State Head Pressure Control
Indoor Fan Relays (^¡x HN61KJ210)
40VA Low-Voltage Control Transformers (24 V - Six 38GS900Q9])
Crankcase Heaters (Six 38GS900131)
Crankcase Heaters (Six 38GS900281) Start Capacitor and Relay Package (Six 38GS900041) Start Capacitor
Tubing Pa
Liqui d
Lgth
(ft)
18 18 25 25
35
50
(in.)
r 5/^
OD
%
% % % : %
V
D6
V
V
4
Tube End
OD (in.)
DESCRIPTION
and Relay F^ackage (Six 38GS900051
ckages
Suction*
OD
(in.)
^8 ^8
y« , % %
%
%
%
T ubeODFnd
in.)
Evap
%
^8 % 1 % % ^8 %
%
V
/4
I V4t
%
%
Cond
^41 I
%
%t
%t % % ^/4 %t
%
y —
/4 k4
38CC — (Fan motor suitable for 32LT)
38GS
V
014,018,024
4
3/ H
030,036,042,048
/4
V
014,018,024
/8
030,036,042,048 014,018,024 030,036,042,048 014,018,024
=/8
V
030,036,042,048
/4
014,018,024 -
%
030,036,042,048
USAGE
38GS,CC,CE
38GS,CC,CE 38GS,CC,CE
38GS (except 38G5014), 38CE
38GS0Ì4
38GS (except 38GSÒ42), 38CE
38GS042
UNIT
38CC
-
030,036,042,048
-
030,036,042,048
-
030,036,042,048
-
030,036,042,048
030,036,042,048
38CE
002
003,004,045,005
002
003,004,045,005
002
“0Ü3%O470457O0r^
002 003,004,045,005 002 003,004,045,005
*AII suction lines have a 90° bend at one end
tForb/8-in evaporator connection, cut off 3/4-in end

PIPING CONNECTIONS

Condensing units can be connected to evap orator sections using Carrier accessory tubing package or field-supplied tubing of refrigerant grade. (Accessory tubing not available for 38GS060, 38CC060.) See Table 2 for accessory tubing sizes and Table 3 for recommended field­supplied tubing sizes. Where evaporator is 20 ft or more below condensing unit, reduce liquid line size one diameter (min 1/4-in. OD).
A capacity reduction will result if accessory tubing is used in 38CE045,005 systems. For example, when a 25 ft accessory tubing package is used, there will be a capacity reduction of 3 3/4% on 38CE045 and 5% on 38CE005 systems. For maximum capacity from these systems, use tubing sizes shown in Table 3.
When other than 25 ft of interconnecting tubing is used, follow special requirements de scribed in Refrigerant Charging. Do not use less
than 10 ft of liquid line. Do not cut 5/16-in. or
1/4-in. liquid line. Bend or coil to fit.
Do not use damaged or contaminated tubing. If accessory tubing package or evaporator section has been open for more than 15 seconds per connec tion, evacuate or purge evaporator coil and tubing system (use field-supplied refrigerant, not unit refrigerant). Always evacuate or purge if field­supplied tubing is used.
Before Connecting Unit Piping, consider the
following: 38CE045,005 AND 38CC UNITS - A filter-drier package is shipped with these units. Included with
filter-drier are 2 short length tubing assemblies that are equipped with flare and/or Compatible Fit
tings. Use tubing assemblies to install filter-drier into system liquid line at evaporator or condensing unit. See Fig. 2. Connect tubing assembly A (90°
assembly) to evaporator or condensing unit liquid line Compatible Fitting. Complete the filter-drier installation as shown.
Page 3
Table 3 — Field-Supplied Piping Data
MAX COND
COND
X-
f 3 UNIT
38GS014, 38GS018
38GS024
38GS030, 38CC030, 38CE002
38GS036, 38CC036, 38CE003
38GS042, 38CC042, 38CE004
38GS048,
38CC048
38CE045
38GS06 0, 38CC060, 38CE005
Cap. Tube TXV
NOTES
REFRIG
CONTROL
TXV
Cap. Tube
or
AccuRater'*'^
TXV
Cap. Tube
AccuRater
Cap. Tube
or
AccuRater
TXV
Cap. Tube
or
AccuRater
TXV
Cap Tube
or
AccuRater
TXV
Cap Tube
or
AccuRater
TXV
Cap. Tube
or
AccuRater
L^y
Cap. Tube
or
AccuRater
Crankcase heater and liquid line filter-drier required on 38GS and 38CE units Accessory start capacitor
with relay also required on 38GS unit, but not
normally required on 38CE units See Compressor Service Reduce liquid line diameter by 1/8-in OD
(min 1/4-in OD) when evaporator is 20 ft or more
below condensing unit
■ Capillary Tube
- Thermal Expansion Valve
1 The following system modifications are required adjust
refrigerant charge on systems with over 25 ft separation
UNIT HT (ft)
Above
Evap
90
150
yo
150
150
90
150
90
150
90 ■
150
90
150
90
150
Be low
Evap
90
50
90 50 %
__
50
90
50
90
50
90
50
90
50
90
50
25- 50 51» 7S 7&~ 1
Suet Liq
V
'8 'x iiiiii lili
%
%
%
%
1%
IV»
Vs
V» T
/4
% liM
% Iliiii
REFRIGERANT LINE LENGTH (ft)
Line Diameter (in* OD)
'
IIBI
ilM
iiiiiiiiiii
wmmmmmmm
N s
T %
k
between condensing unit and evaporator (See Refrigerant Charging ) Adjust system oil charge as described in Note 2 Oil charge adjustment add 1% of nominal oil charge in system (Table 7) for each 10 ft of refrigerant line length above 50 feet Eor example, a system that has a 50-oz oil charge with 1 50 ft of interconnecting piping requires 5 oz of additional oil as shown below:
V
iÄiii
MB
ISl
*
150 ft - 50 ft = 100 ft 100 ft -E 10 ft = 10 ft
Litj 1 LEíj
iiiiii
IH
ilBi %
11»
Äiii
10x1% = 10% ( 10)
10 X 50 oz = 5 oz
Do not permit condensing unit to short cycle, particularly on applications with long vertical line lengths Correct short cycling condition immediately
m
¡Mil
Í.
..............
Connection Procedure — When making tubing
connections, be sure to provide clearance at unit for electrical connections.
Connect refrigerant liquid and suction lines to condensing unit, Fig. 1. Unit Compatible Fittings permit 2 methods of refrigerant line connection; mechanical (quick connect) or sweat connection. Make suction line connection first.
38CE045,005, 38GS060 AND 38CC060 UNITS ­Remove suction line adapter taped to compressor suction line. Connect 3/4-in. end of adapter to unit suction line Compatible Fitting. Sweat connect refrigerant suction line to 1 1/8-in. end of adapter. Connect liquid refrigerant line to unit.
MECHANICAL CONNECTION (Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove. Remove plug and be sure 0-ring is in the groove
2.
inside the Compatible Fitting. Cut tubing to correct length.
3. Use gage on tag attached to service valve to
4. mark tube end for correct insertion depth. Insert tube into Compatible Fitting until it
bottoms. (Tube should be inserted at least as far as mark on tubing.)
Tighten nut until it bottoms on back coupling
5. flange.
Page 4
c
Fig. 2 — Filter-Drier Assembly Installation (38CC, 38CE045 and 005)
SWEAT CONNECTION (Use refrigerant grade
tubing.)
1. Remove locking nut, rubber 0-ring and Schrader core from valve.
2. Cut tubing to correct length.
3. Insert tube into Compatible Fitting. Wrap top and bottom of service valves in wet cloth to prevent damage by heat. Solder with low temperature (450 F) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied refrigerant.

ELECTRICAL DATA AND WIRING

Field wiring must comply with local and
national fire, safety and electrical codes. Voltage to unit must be within ± 10% of voltage indicated on
nameplate. Contact local power company for correction of improper line voltage.

of ifolt ois tmpro|>er Ime

When making electrical connections, provide clearance at unit for refrigerant piping connections. See Table 4 for recommended wire and fuse sizes.

Install a Branch Circuit Fused Disconnect of

adequate size to handle unit starting current. Locate disconnect within sight of and readily accessible from the unit, per section 440-14 of
National Electrical Code (NEC).
Bring Line Power Leads Into Unit — Extend leads
from fused disconnect thru hole provided in service embossment (Fig. 1) and thru 7/8-in. hole into control box.
Connect Ground Lead to a Ground Lug in Control
Box for safety. Connect power wiring. See Fig. 3.
Splice line power leads to red and violet pigtails on 38GS,CE units or to yellow pigtails (3) on 38CC
units. Use wire nuts supplied with unit. Tape each
connection. Wire nuts are suitable for copper or aluminum wire since they contain joint compound.
Control Power (24 v) wiring is brought thru hole in
service embossment and spliced to yellow pigtails on all units. See Fig. 4.
Furnace or fan-coil transformer must be used as
24-v supply for system as shown in Fig. 4 (At least
a 40-va transformer is recommended.) Current 38GS048,060 and 38CC048,060 units are equip ped with a low-voltage transformer used to power contactor thru unit control circuit. This trans former must not be used for powering the indoor thermostat control circuit.
Page 5
I-PHASE CONN. TO FUSED DISCONNECT
3-PHASE
CONN. TO
FUSED
DISCONNECT
SPLICE
------------
FACTORY WIRING
------------
FIELD WIRING
p
--I3D GROUND LUG 386S,CEC0NDUNIT
-YEL-
-YEL-
-YEL-
-------I3D GROUND LUG
38CC CONO UNIT
Fig. 3 — Line Power Connections
THERMOSTAT SUBBASE
THERMOSTAT SUBBASE HH93AZ076
(COOLING ONLY)
THERMOSTAT SUBBASE HH93AZ042 OR
ONE TRANSFORMER
(COOLING AND ONE-STAGE HEATING)
^CONNECT FS TO LOW-SPEED INDOOR FAN TERMINAL
WHEN 2-SPEED FAN IS USED
IFR, FS and IFM are located in furnace on heating-cooling applications If accessory IFR is required for cooling only applications, locate (IFR) in fan coiI
ARRANGEMENT C-
ONE TRANSFORMER
(COOLING AND 2-STAGE HEATING)
^CONNECT FS TO LOW-SPEED INDOOR FAN TERMINAL
WHEN 2-SPEED FAN IS USED

Fig. 4 -- Control Circuit Connections

Control Relay (10 va) or Contactor Fan Switch Heating Control I ndoor Fan Motor I ndoor Fan Relay Transformer
Field Splice
---------------
Field Wiring
---------------- Factory Wiring
5
Page 6
Table 4 — Electrical Data
030 036 036 042 042 042 048 048 048 060 060 060
___ ___ ___ ___ ___
___ ___ ___ ___ ___ ___ ___
200/230/3 253
200/230/3 253
460/3 506 200/3
230/3 253 460/3 506 200/3 230/3 253 460/3 200/3
230/3
460/3 506
220 180 92
220
506 220 253 207
38CE 002 003
___ ___
230/1 253 230/1
253
004___ 230/1 253 045 005
___ ___
230/1 253 230/1 253
180 180 80/70 414
207 414 46
180 90 207 78.5 414 39 3
180
414
207 65 207 82 207 207 88 23.9 207 100 27.9
70/60
35
92
13 0/11 5 14 0/12 6
no
100
50
~88 19.8
6 5 17 0 15 8
7 8 18 6
16.1
8 3 23 0 20 5 10 3
10.3 16 8
FAN
FLA
2.4 14
2.1 2 4
2,4
.........
2 1
2.1 14 2 4
2.4 10 2 1
2.1 2 4 8
2.4 2 1 10
2.1 10 36 2 4 8
2.4 2 1
2.1
2.1 8
2.1 2 1
2 0/2 .0
2 0/2 0
1.0 2 0 2 0
1 0 14
2 0
2.0
1 0 14
2.0 8
2 0 10 1 0 14
2-.1
2 1
2.1
2.1 10 31 55 2 1
___12______
BRANCH CIRCUIT
Wire Sizef
(AWG)
14 12
12 36 25
10
12 31 30 12 31 30
8
8
10 10 33 50
8 6
12
12 14 91 10 49 10 58
10 10
12 10 10 36
8
Max
Ft
Wiref
40 33
28
..37
..........
19
40 35
45 50 45
34
44 36
33
41 42
54
49 45 30/30
100
46 60
100 20
'■ 67 50
47
1 74
42 42
42 60
Fusei Amps
20 20 30
20
25 35
40
50
30 45
55 65
50
65 55 75
30/25
15 35 35
15 40 35
45
20
25 35 45
FLA — Full Load Amps LRA — Locked Rotor Amps
______Electrical data shown applicable to all units for
which complete model number is not shown
•Permissible limits of the voltage range at which the units will operate satisfactorily

START-UP INSTRUCTIONS

If unit is equipped with crankcase heater, energize heater a minimum of 24 hours before starting unit To energize heater only, set thermo
stat at “Off” position and close electrical dis
connect to condensing unit.
Units with Time Guard® circuit or solid state time-delay may not start for approximately 4 to 5 minutes after thermostat closes. See compressor controls, pages 7 and 8.

Start Procedure

1. Backseat (open) liquid and suction line service valves.
(■Copper wire sizes Aluminum field wiring may be used when splice-
connected to copper pigtails from unit with factory-supplied wire nuts
Use latest National Electrical Code for aluminum wire sizing
^Maximum dual element fuse size
NOTE Control circuit voltage is 24 volts on all units
ov«rtii^i<?n servkc
4 Do exscod
6 fi-lb lorquc »hen
iighiiiiing.
2. Set thermostat selector switch at "Off.”
3. Set room thermostat at desired temperature.
4. Close electrical disconnects energizing entire system.
5. Set room thermostat at “Cool” and fan switch
as desired (“Fan”) (“Auto.”).
Check system refrigerant charge. See Refrig
erant Charging.
Motors and controls will operate satisfactorily
in a range from 10% above to 10% below nominal unit voltage (Table 4).
Page 7
Do not connect charging hoses to capillary­controlled system during initial start procedure. (Loss of charge from this procedure may result in capacity reduction.) If necessary to add manifold
f • gages for servicing, refer to Carrier Standard
Service Techniques Manual, Chapter 1, pages 1—5, Fig. 8, for bypass method of returning charge to
system. (A charging hose valve must be used to accomplish bypass of refrigerant on all units.)
Table 5 — Service Data
CONO
UNIT
38GS014 38GS018 38GS024 38GS030 38GS036 38GS042 4-12 38GS048 5- 3 38GS060
38CC030 3- 2 38CC036 38CC042 3-12 38CC048
38CC060 5- 3
38CE002
38CE003 38CE004 5- 2
38CE045 38CE005
"■Factory refrigerant charge adequate for complete system when
connected to Carrier approved evaporators mat are the same size as condensing unit, with 25 ft of tubing
R-22
CHG*
(lb—oz)
3- 0 2600 3- 0 3- 0 3- 2 3-M
5- 3
3-14
5- 3
4- 7
4-11
5- 6
5-11
CONDENSER
Rpm
1060 17/2
1070/870
975/800
Diam

COMPRESSOR SERVICE

Unit Single-Phase Compressors of the Split Capaci
tor (PSC) Type require an equalized system pres
sure to start. When supply voltage is within 10% limit and compressor does not start, give com pressor a temporary capacitance boost. See Carrier Standard Service Techniques Manual, Chapter 2, for details. Use a 130-mfd start capacitor. Connect wires with insulated probes to each capacitor terminal. Touch probes to each side of run capacitor or to compressor motor terminals R and S. Start compressor; pull probes away after 3
seconds. Discharge start capacitor. Run compressor
for 10 minutes, then shut off and allow system pressure to equalize. Try restarting without boost capacitor. If after 2 attempts (without boost capacitor) the compressor does not start, add an accessory start capacitor relay package.
Unit Single-Phase Compressors That are Equipped
With a Compressor Start Thermistor (PTC device);
if compressor will not start, check the thermistor
with an ohmmeter as described below. (If evap orator coil does not have a bleed-type expansion device, it may be necessary to remove PTC device and replace with accessory start capacitor and relay.)
(in.)
17/2
17/2
FAN
2600/2100
2600/2100 2800/2300
2700/2200 2700/2200
Cfm
2600 2600 2600 2600
2800 2800
2800
2600 2600 2800 2800 2800
CHECKING START THERMISTOR
1. Shut off all power to unit and wait 5 minutes for thermistor to cool to outdoor temperature.
2. Measure resistance of thermistor with ohmmeter. Normal resistance readings are 50 to 90 ohms at 75 F outdoor temperature.
3. If ohmmeter resistance reading is 0 or much higher than 90 ohms the thermistor is defective
and must be replaced.
If start thermistor is good and compressor will
not start, disconnect the thermistor from starting circuit and give compressor a temporary capaci tance boost as described above. Run compressor for 10 minutes, then shut off and allow system pressure to equalize. Reconnect start thermistor and try restarting compressor without boost capac itor. If after 2 attempts the compressor does not start, remove thermistor and add an accessory start
capacitor relay package.
38CC Units — Compressor start capacitor and relay
or thermistor (PTC) are not required on 3-phase 38CC units.
Safety Devices — Refer to Table 6 for particular
safety controls that each unit is equipped with.
Table 6 — Compressor Safety Controls
SAFETY CONTROLS
INTERNAL CURRENT-
TEMP SENSITIVE OVERLOAD
INTERNAL THERMO
(Pilot Duty)
LOW-PRESS. SWITCH
HIGH-PRESS. SWITCH
CRANKCASE HEATER Accessory
OUTDOOR FAN
THERMOSTAT TIME GUARD® CPCS
SOLID STATE TIMER
CPCS
Compressor Protection Control System
38GS
014,018 024,030
036,042,048
060
-
-
-
060
-
ENSING 1
030,036, 042,048
030, Ò3C
042,048,
030,036, 042,048.
030,036, 042,048.
030,036,
048,060 -
38CC ^
060
060
060
060
-
042
-
NITS
38CE
002,003, 004,045,
005
Accessory
-
Accessory
002,003, 004,045,005
-
045,005
COND

UNIT PROTECTION

Internal Current And Temperature Sensitive Over
loads reset automatically when internal motor
temperature drops to a safe level (overloads may require up to 30 minutes to reset). When an internal overload is suspected of being open, check by using an ohmmeter or continuity tester. If necessary, refer to Carrier Standard Service Techniques Manual, Chapter 2, for complete instructions.
Page 8
Low-Pressure Switch is located on unit suction line
and resets automatically. Low-pressure switch set tings are: cutout, 31+4 psig; cut-in, 60 (+ 15, - 0)
psig.
High-Pressure Switch is located on unit liquid line
and resets automatically. High pressurestat settings are; cutout, 425 ± 5 psig; cut-in, 320 ± 20 psig.
Crankcase Heater warms compressor crankcase.
Prevents refrigerant dilution of oil in crankcase.
Outdoor Fan Thermostat maintains proper con
densing temperature at high outdoor temperatures by switching fan to high speed. Located in control box (on 38CE).
Filter-Drier is installed in liquid line.
Time Guard® Circuit provides for a 5-minute delay
before restarting compressor after shutdown for
any reason. On normal start-up the Time Guard timer causes a delay of 15 seconds after thermostat closes before compressor will start. On compressor shutdown, the timer recycles for 4 minutes, 45 seconds. During this time the compressor cannot start.
Solid State Time Delay provides for a 4-minute
delay before restarting compressor after shutdown for any reason. On normal start-up, timer is energized after thermostat closes and causes a 4-minute delay before compressor will start.
Compressor Protectibn Control System (CPCS —
Solid State) provides; compressor motor locked rotor protection; compressor start winding pro
tection; compressor motor running overload pro tection; compressor overtemperature protection;
contactor antichatter protection.
The CPCS also provides for a 4- to 6-minute delay before restarting compressor after shutdown for any reason. I f compressor loading was light at the moment compressor was shut off, the delay will be approximately 4 minutes. If loading was
heavy, the delay will be approximately 6 minutes. To troubleshoot the CPCS, use unit label diagram
or wiring booklet and the following Control Circuit Troubleshooting Chart.
CONTROL CIRCUIT TROUBLESHOOTING CHART NOTES:
2. To disconnect plug from receptacle on CPCS board — press in tabs located on the receptacle and pull plug gently while holding tabs. Do not pull on wiring.
When performing troubleshooting checks, CPCS
3. receptacle must be plugged into CPCS board.
Receptacle female connections, which do not
4. grip the male pin tightly, may be repaired with a small pen knife.
When taking meter readings at CPCS receptacle,
5. bottom meter probe into terminal hole to
ensure good electrical contact. Replace CPCS board if electrical short circuit
6.
causes compressor failure. An electrical short in compressor can short the triac (electronic switch located on CPCS board). Triac may fail in a closed (conducting) position and will not open the control circuit.
Compressor Removal (See Table 7 for compressor
information and Fig. 5 for component location.)
1. Shut off power to unit. Vent refrigerant to atmosphere or use refrigerant removal methods shown in Carrier Standard Service Techniques Manual, Chapter 1.
Remove top access cover and rear access wrap
2.
per (Fig. 5).
Remove power leads from compressor terminal
3. box. Unsweat suction and hot gas lines.
Remove compressor hold-down bolts. Lift
4.
compressor out thru top or back of unit.
CONTROL
COMPRESSOR TERMINAL BOX
CAUTiON: Iks nmt
i>ece|siacle fiHscomsctsd fr«i ebm* will up CICS
1. Ensure thermostat calls for cooling before troubleshooting unit.
LIQUID LINE
Fig. 5 — Condensing Unit with Access
Panels Removed
(38CE Unit Shown)
Page 9
■ .

CONTROL CIRCUIT TROUBLESHOOTING CHART (GS,CC048 and 060)

Before attempting any corrective action, wait 8 minutes after power is supplied to permit CPCS time delay period to end. If control circuit
broken and unit has no time delay (or if time delay is over 8 minutes), replace CPCS board
tVoltage reading less than 20 volts may result from feedback circuit
I—mnrnnrtWfsrr—I r* Olif *—
26VA
O CPCS Receptacle ^Component Connections
TYPICAL CONTROL CIRCUIT
INDOOR UNIT TRANSFORMER
THERMOSTAT " ^Q—-—(CR
--0-^-0-
TRIAC
(COOLING), ,
Page 10
Table 7 — Compressor Data
COND
UNIT
38GS014__. 38GS014-.. 38GS018200
38GS0182iO
38GS018300 38GS0183IO 38GS024200
38GS0242i0 38GS024300 38GS024370 38GS030200
38GS0302I0 38GS030300 230/1 38GS0303i0
38GS036200
38GS0362fO
38GS036300
38GS0363i0
38GS042___
38GS048___
38GS060
38CC030.__ 200/230/3
38CC036___ 38CC036___ 38CC042___ 38CC042 38CC042__. 38CC048___
38CC048
38CC048-__ 460/3
38CC060
38CC060___ 230/3
38CC060
38CE002
38CE003
38CE004 38CE045
38CE005
---------
* Refer to Service Parts Catalog for replacement compressor
model numbers Single-phase units may include compressor start assist device
___
___
___
___
___
___ ___ ___
___
___
Tabular data shown applicable to all models except
those shown italicized 000
V/PH
208/1 230/1 208/1 208/1 230/1 230/1 208/1 208/1 230/1 230/1 208/1 208/1
230/1 208/1 208/1 230/1 230/1 230/1 230/1 230/1
200/230/3
460/3 200/3 230/3 460/3 200/3 230/3
200/3
400/3
230/1 230/1
230/1 230/1
230/1
PRODUCTION
COMPR*
38GS400804 38GS400804
38GC401994
MD2023CB
38GC400224 21
MD2023CB 44
38GL400314
MB2723CB 44
38GL400324
MD2723CB
38GC401984 42
MB3423CB
38GC401404
MC3423CB 44
38GC402004
MB4023CB
38GC401564
MC4023CB 44
38GS400424
PC5329AD PC6728AB
MF3423BC MF4023CB
MH4023CB 44
38GR403364 46
38GR403364 46 38GR403374 46 PF5326AD 76 PG5326AD 76 PH5326AD 76
PF6725AA PG6725AA 76 PH6725AA
MD2023CB 44 MD3023CB 44 MC3423CB
PC4629AD 76 PC5329AD 76
OIL
RECHG
(Oz)
21 21 21
44
42
42 44
44 42
46 44 46
46 76 76
44 44
• 76
76
44

PUMPDOWN PROCEDURE

The 38GS,CC,CE units may be pumped down in
order to make repairs on low side of system without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
2. Frontseat the liquid line valve.
3. Jumper low-pressure switch (if unit is so equipped).
4. Start unit and run until suction pressure reaches 5 psig (see Caution).
5. Shut unit off and frontseat suction valve.
6. Vent remaining pressure to atmosphere.
I

REFRIGERANT CHARGING

The 38GS,CC,CE condensing units contain
correct operating charge for complete system when connected to Carrier approved evaporators that are the same size as condensing unit, with 25 ft or less of tubing of recommended size. Charge adjustment may be required on other systems.
Listed (Table 8) and described below are
recommended methods of checking, adjusting or recharging Carrier approved systems. When recharg ing these systems, evacuate system to 5000 mi crons (29.7-in. vacuum), and weigh in charge shown in Table 5. When system is not evacuated, subtract the following amount from total charge.
38GS014,018,024; 38CE002 - .11 lb (1.6 oz) 38GS030,036; 38CE003,004; 38CC030,036 - .21
lb (3.2 oz) 38GS042,048,060; 3 8CC042,048,060;
38CE045,005 - .31 lb (4.8 oz) (Dial-a-charge charging cylinder is an accurate
device used to recharge systems by weight. These cylinders are available at refrigeration supply firms.) After weighing in charge, check or adjust charge using the Chargemaster® charging device, charging chart or sight glass method as recom mended in Table 8. Refer to Carrier Standard Service Techniques Manual, Chapter 1, for system evacuation — dehydration instructions.
When 38GS,CC,CE condensing units are con nected to other than a Carrier evaporator, evacuate system and weigh in charge shown in Table 5 or use sight glass method of recharging (38CC thermal expansion valve systems only).
10
Page 11
Table 8 — Refrigerant Charging Methods
(Carrier Approved Systems)
METHODS OF CHECKING
CONO
UNIT
AccuRater^ ^
38GS
38CC
38CE
TXV — Thermal Expansion Valve
0^ ADJUSTING CHARGE
System Refrigerant Control
Capillary
Tube
Chargemaster ®
or
Charging Chart
Chargemaster
or
Charging Chart
Chargemaster
or
Charging Chart
TXV
Charging Chart
Charging Chart
Sight Glass
Charging Chart
Charging Chart Method — For thermal expansion
valve systems, use Charging Chart, Fig. 6 or 7. See Carrier Standard Service Techniques Manual, Chapter 1, for procedure. For capillary tube or
AccuRater"''i'^ systems, use Charging Chart, Fig. 8 or 9 and the following procedure:
1. Operate unit a minimum of 10 minutes before checking charge.
2. Measure suction pressure by attaching a gage to suction valve service port.
3. Measure suction line temperature by attaching a
service thermometer to unit suction line near
compressor. (Insulate thermometer for accurate
readings.)
4. Measure outdoor (condenser inlet) air dry-bulb temperature with second thermometer.
5. Refer to Charging Chart (Fig. 8 or 9). Find condenser air temperature and project hori zontally to curve showing suction pressure.
6. From intersect point, project vertically down ward to chart suction hne temperature.
7. If unit has a higher suction line temperature than chart, add refrigerant until chart tempera
ture is reached.
8. If unit has a lower suction line temperature than chart, bleed refrigerant until chart tem perature is reached.
9. If condenser inlet air temperature or unit suction pressure changes, change to new suction line temperature on chart.
Chargemaster® Operation — Operate unit 10 min
utes before using Chargemaster (Carrier Part No. 38GC680004).
RECHARGING METHODS
System Refrigerant Control
AccuRater
Weight Method
Chargemaster or
Charging Chart Wei ght Method
or
Chargemaster or
Charging Chart
Weight Method
Chargemaster or
Charging Chart
Capillary
Tube
plus
plus
plus
TXV
Wei ght Method
plus
Charging Chart
Weight Method
plus
Charging Chart or
Sight Glass
Wei ght Method
plus
Charging Chart
1. Tape Chargemaster feeler bulb to suction line close to condensing unit. Insulate bulb. Ensure
suction line is clean for good contact with bulb.
2. Connect refrigerant drum to Chargemaster inlet port with drum in position for vapor charging.
3. Connect Chargemaster outlet port to unit suc tion valve service port.
4. Crack valves on refrigerant drum and Charge­master to purge lines from drum to suction
valve. After purging lines, close valve on Charge-
master only.
5. Measure outdoor air dry-bulb temperature.
6. Crack unit suction valve and read evaporator temperature at red needle position on Charge­master temperature gage and suction line tem
perature at black needle position.

CAIHIOI^; Do myi tmé

7. Enter Chargemaster Charging Chart, Table 9 or
10, at outdoor air temperature (step 5) and evaporator temperature (step 6). Find the suction line temperature required for correct system charge. If actual suction line tempera ture (step 6) is higher than table value, the
system is undercharged. If suction line tempera ture is lower than table value, the system is overcharged.
Example (Table 10): At outdoor air tempera ture of 85 F and evaporator temperature of 44 F, the system will be correctly charged at 71 F ± 2 F suction line temperature.
11
Page 12
8. Add charge by slowly opening Chargemaster® valve. If necessary, reduce charge by bleeding at liquid line service valve. Check outdoor air and evaporator temperature during procedure. If
they change, refer back to Chargemaster
Charging Chart for new value.
Correct use of Chargemaster ensures an opti mum refrigerant charge will be in system when conditions and system components are normal. However, the Chargemaster does not solve or fix system abnormalities. It indicates correct charge for condition of system. It will not make correc tions for dirty filters, slow fans, excessively long or short suction lines or other abnormal conditions.
This charging device ensures that a correct relation ship exists between outdoor temperature, evap
orator temperature, and suction line temperature
on a specific system.
Sight Glass Method — A satisfactory operating
charge can be obtained on thermal expansion valve
systems by charging to a clear sight glass. For optimum charge, elevate high-side pressure to 380 ± 10 psig by blocking condenser fan discharge or condenser entering air. Charge to a clear sight glass while holding high-side pressure constant. For peak efficiency, adjust charge to yield a liquid refrigerant temperature at the evaporator that is approximately the same as outdoor dry-bulb
temperature.
A
I
12
Page 13
Table 9 — 38GS,CC Chargemaster® Charging Chart
(Capillary Tube or AccuRaterTM Systems)
30 40 50 60 70
SUCTION LINE TEMPERATURE (»F)
80
Fig. 8 — 38GS,CC Charging Chart
(Capillary Tube or AccuRaterTM Systems)
UU1UUUK
TEMP (F)
60 62 64 66
32 40 30- 38 28 27
68 70 72 74 76 78 80 82
90
84 86 88 90 92 94 96
98 36 100 102
104 106 108
no
112 114
*Saturated evaporator temperature which is the equivalent tem
perature of pressure taken at the condensing unit suction service valve
EVAPORATOR TEMP (F)*
28
25 _
“1"
34 37
3ii
Suction L.ine Temperatures
51 ^
49 37 47 35 45 57 34 32 31 30 29 36 46 27 35 44 26
43
41
39 50
37
33
32 40
31
29 37
60
67
54
64
52
61 72 58
48
56 54 63 75 52 61
42
50 59 48
38
46 55 44 53 61 70
35
42 51
34
41 49 57
33
39
38
69
66
57 66
47 55 45 53 44 51 42 41 48 55
39 46
40
43 45 48
72
68
80 76
63
73 85
81
59
68 78 90
65 75 86
63 72 83
70 80
61
67 77
59
49 57
53 61
45 51 59 68
43 49 57 65 41
47 55 63 46 53
75
65
73
63
70
61 59
50
Fig. 9 — 38CE Charging Chart
(Capillary Tube or AccuRaterTM Systems)
13
Table 10 — 38CE Chargemaster® Charging Chart
(Capillary Tube or AccuRaterTM Systems)
EVAPORATOR TEMP (F)
TEMP (F)
60 65 70 75 80
85
32
60 49 41 48 58 35 31
iii
90 40
95 100 105 44
no
115
Example
36j3Sj40|42
Suction Line
58 65
41 48 58
36 42
......
.1.
— •1
68
50
70
68
59
>, V'
47 53 42
'em
75 69
48 53 43
4^48|50
44
peratore (F]
82
'
6; 69
59
4/ 52
48 53
__
78 67 79
68 88
58
60
49 54 65
50
52
75
62
54
104
80 69
Page 14
COMPATIBLE FITTING REPAIR
Leaking Mechanical Connection — Frontseat con
densing unit service valves and relieve refrigerant pressure in tubing. Back locknut off Compatible Fitting onto tube. Cut fitting between threads and seal ring head as shown in Fig. 10. Remove tubing section remaining in threaded portion of fitting. Discard locknut.
Clean, flux, and insert new tube end into remaining portion of Compatible Fitting. Wrap valve base in wet rag. Heat and apply low tempera ture (450 F) solder.
Leaking Sweat Connection — Frontseat service
valves and relieve refrigerant pressure in tubing. Clean and flux area around leak and apply low temperature (450 F) solder.
Evacuate or purge evaporator coil and tubing system. Add refrigerant charge (see charging instructions).
Off íA&m

Fan Motor Removal

1. Shut off power to unit.
2. Remove unit top access cover and fan grille.
3. Disconnect fan motor wires from fan capacitor and control relay or contactor. Pull wires out of control box.
4. Remove fan from motor shaft by pulling upward on fan hub.
5. Loosen bolt holding fan motor to motor mounting bracket. Remove motor thru top of unit. To replace motor, place motor on self positioning motor mounting flanges and re tighten bolt.
Fig. 11 — Condenser Fan Position
Fig. 10 — Repair of Mechanical Connection

CONDENSER

Coil Cleaning Ensure power to unit is shut off
Clean the condensing unit coil at the beginning of every cooling season or more often if required. Use ordinary garden hose at a pressure high enough to clean efficiently. For best results, unscrew and remove unit top cover (grille). Insert hose nozzle between fan blades and spray coil fins from inside-to-outside the unit. If unit has a double-row coil, loosen screws to separate coils, and flush dirt
toward outside of both coils. Flush dirt from base
pan by spraying water thru top of unit. Avoid
splashing mud on coil or water on the fan motor.
Metal Fan — Required fan position is shown in Fig.
11. Adjust fan by loosening setscrew and moving
fan blades up or down.
Plastic Fan is correctly positioned in unit by
placing fan on motor shaft — align flat mark on top of fan hub with flat on shaft. Press down evenly on top of fan hub until shaft bottoms in fan hub.

LUBRICATION

Fan Motor Bearings — Oiling holes are provided at
each end of current condenser fan motor. Remove fan motor and lubricate motor with 32 drops (16 drops per hole) of SAE-10 nondetergent oil at intervals described below:
a. Annually, when environment is very dirty,
ambient temperature is higher than 105 F and average unit operating time exceeds 15 hours a day.
b. Every 3 years when environment is reasonably
clean, ambient temperature is less than 105 F and unit operating time averages 8 to 15 hours a day.
c. Every 5 years when environment is clean,
ambient temperature is less than 105 F and unit operating time averages less than 8 hours a day.
Compressor contains factory oil charge. When oil is
lost, see Table 7 for oil charge and Carrier Standard Service Techniques Manual, Chapter 1, page 1—21, for instructions. Use Carrier PP33-1, Texaco Capella B or Suniso 3G oil.
14
Page 15
TROUBLESHOOTING CHART*
*To troubleshoot control circuit on 38GS048,060 and 38CC048.060 units, see Control Circuit Troubleshooting Chart, page 9.
15
Page 16
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Tab 4
Form 38GS-13SI Supersedes 38GS-10SI
Printed in U.S.A. 2-75 Codes D and MS Catalog No. 533-810
Loading...