Carrier 38BYG048 SERIES300, 38BYG060 SERIES300, 38BYG042 SERIES300, 38BYG036 SERIES300, 38BYG030 SERIES300 Owner’s Manual

...
HEATUNG & COOUNG
%isitx__ _.¢arrier.com
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteratiom service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer_ service agency, or your distributor or branch for infornmdon or assistance. The qualified
installer or agency must use _hctory=authorized kits or accessories when modi_}-ing this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth t:br brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and _\_llow all warnings or cautions included in literature
and attached to the unit. Consnh local building codes and National
Electrical (?ode (NEC) [br special requirements.
Recognize safety informatiom This is the safety-alert symbolz_ .
When you see this symhol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAU=
TION. These words are used with the saf_b_-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which
could result in personal injury or death. (AUTION is used to
identify unsafe practices which would result in minor personal
injuw or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
Be%re installing, modif}'ing, or servicing system, main elec- trical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning tahet. Electrical shock can cause personal injury or death.
iNSTALLATiON RECOMMENDATBONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations fiom improper installation of equipment
h Locate unit away fiom window< patios, decks, and so forth
where unit operation sounds may disturb customer
2. Ensure that vapor- and liquid-robe diameters are appropriate to capacity of unit
3. Rm_ refrigerant tubes as directly as possible by avoiding
unnecessary rams and bends.
38BYC, 38BYG
12 SEER SpMit System
Heat Pump
A98525
Fig. 1--Mode{ 38BYG
4 Leave some slack between structure and unit to absorb
vibration
5 When passing refi'igerant robes through the wall, seal opening
with RTV or other pliable silicon based caulk. (See Fig. 2.)
6. Avoid direct robing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refiigerant tubing fi'om joists and studs with a
rigid wire or strap that comes in direct contact with robing. (See Fig. 20
8. Ensure that robing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
con_bm_ to shape of robing insulation. (See Fig. 20
10. Isolate hanger straps from insulation by using metal sleeves bent to confbrm to shape of insulation.
When outdoor unit is connected to ihctory-approved indoor unit, outdoor unit contains system refrigerant charge fbr operation with
indoor unit of the same size when connected by 15 fi of field-supplied or factoo'-accesso<v robing. For proper unit opera- tion, check refi'igerant charge using charging information located
on control box cover.
IMPORTANT: Maximun_ liquid line size is 3/8-im O.D. fc_r all residential applications including long line.
INPORTANT: Always install a liquid line filter drier on any system using existing field service line sets and or existing indoor coil or fan coil units. Always use a filter direr on burnout unit replacements.
Manufacturer reserves the right to dissontinue, or change at any time, specifications or designs without notise and without insurring obligations,
PC 101 Catalog No. 533-80078 Printed in USA Form 38BYC-3SI Pg 1 11-02 Replaces: 38BYC-2SI
NOTE: Avoid contact between tubing and structure
_-- OUTDOOR WALL--_ INDOOR WALL_"
-_. CAULK
I
1
C
lq/N 7/_ vAPOR TUBE
SULATi
THROUGH THEWALL
HANGERSTRAP*_ l_lr'f--JOIST
(AROUNDVAPOR_
TUBEONLY) _,,\ /_ INSULATION
.............................()
i __.-VAPOR TUBE
r'MtN.--I I_ L LIQUIDTUBE
SUSPENSION
A94028
Fig. 2--Connecting Tubing Installation
_NSTALLATION
Step l--Check Equipment and Job Site
L NPA(K UNIT Move to final location, Remove carton, taking care not to damage
uniL
]:NSPECT EQUIPMENT
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit service
panel. It contains int'ornaation needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Step 2--Bnstall On A Solid, Level Mounting Pad
[f conditions or local codes require the unit be attached to pad,
tiedown bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 3 to detem_ine base pan size and knockout hole location.
On rooftop applications, mount on level platform or _?ame. Place
unit above a load bearing wall and isolate unit and robing set fi'om
strocture. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind baft'les to achieve adequate defrost. Consult Low Ambient
Guideline for wind baffle construction.
NOTE: Unit must be level to within ÷ 2° 3/8 inJft) per compressor manufacturer specifications.
Step 3--Clearance Requirements When installing, allow sufficient space for airflow cleaIance,
wiring, refrigerant piping, and service Allow 30-in clearance to
service end of unit and 48 in above uniL For proper airflow, a 6=in clearance or* 1 side of unit and 12 in on all remaining sides must
be maintained, Maintain a distance of 24 in between units
Position so water, snow, or ice from roof or eaves cannot Pall directly on unit
1
I 3/8"D (953) TIEDOWN
KNOCKOUTS (2) PLACES
B .I
Dimensions On.)
UNIT SRZE
018-024 030°060
On rooftop applications, locate unit at least 6 in. above roof surface.
Step 4-==Operating Ambient
The minimum outdoor operating ambient in cooling mode is 55°F, and the maximum outdoor operating ambient in cooling mode is
125°F The maximum outdoor operating ambient in heating mode
is 66°F,
Step 5--Elevate Unit
Accumulation of water and ice in base pan may cause equipment damage.
In areas where prolonged freezing temperatures are encountered, elevate unit per local climate and code requirements to provide
clearance above estimated snowfidl level and ensure adequate drainage of unit
Step 6--Remove Indoor AccuRater® Piston and Install TXV
For proper unit operation and reliability, units must be installed with field supplied hard shutoff TXV Do not install with evaporator coils having capiltaQ" robe metering devices or pistons.
For TXV kit part number and charging instructions, refer to TXV label in outdoor unit If indoor unit (fire coil) comes f_cto_ equipped with a bi-flow hard shutoff TXV, no TXV change is required,
NINIMUM TIEDOWN KNOCKOUT LOCATIONS
MOUNTING-PAD
DIMENSIONS A B C
22-112 X 22-1/2 3-11116 18-1/8 14-3/8
30 X 30 6-1/2 23-1/2 20
Fig. 3--Mounting Unit to Pad
I
A94199
If TXV installation is required, remove existing AccuRater_ t'rom indoor coil Re_r to Figs 4 and 5 and install TXV kit as _bllows:
1_ Install suction robe adapter_
2. Install liquid flareoto-sweat adapter.
3. Connect external equalizer robe to fitting on suction robe adapter.
4. Position sensing bulb on horizontal portion of suction robe adapter. Secure using supplied hardware.
5. Insulate bulb aRer installation. (See Fig. 5.)
d. Leak check all connections.
feeder tubes, there is a 3/%in. O.D. stub robe approximately 2 in. tong. (See Fig. 60 The defrost thermostat should be located on stub
mbe_ Note that there is only 1 stub robe used with liquid header, and on most units it is the bottom circuit_
f STUB TUBE
DEFROST THERMOSTAT
BULB
UALIZER
TUBE
EXPANSION
VALVE
A88382
Fig. 4--Typical TXV Insta!lation
O'CLOCK
2
SENSING
L-_'S UCTIO N
8 O'CLOCK 4 O'CLOCK
7_ IN. OD & SMALLER LARGER THAN 7_ IN. OD
A81032
Fig. 5--PositioNng of Sensing Bulb
Step 7--Check Outdoor AccuRater® Piston (beck outdoor unit piston Remove retainer on liquid service valve
and check piston size with n_atching nm'uber listed on outdoor unit
rating plate.
Step 8--Check Defrost Thermostat (heck defiost thermostat to ensure it is properly located and
securely attached There is a liquid header with a brass distributor and feeder robe going into outdoor coil At the end of 1 of the
A97517
Fig. 6--Defrost Thermostat Location
Step 9--Make Piping Connections
Relieve pressure and recover all refi'igerant before system repair or final unit disposal to avoid personal ir_.iuI?' or death.
Use all service ports and open all flow control devices,
including solenoid valves.
If ANY refrigerant robing is buried, provide a 6 in. vertical rise at service valve, Ret'rigerant robing lengths up to 36 in, may be buried without further special consideration. For lengths longer than 36 in., refer to Application Guideline and
Service Manual Residential Split System Air ( onditioners
and Heat Pumps,
To prevent damage to unit or service valves obsela'e the fbllowing: *Use a brazing shield *Wrap service valves with wet cloth or use a heatosink
material
Outdoor units may be connected to indoor section using accesso_ robing package or field-supplied refrigerant grade robing of coll'ect
size and condition For robing requirements beyond 50 it, substan- tial capacity and per_brmance losses can occur Following the
recommendations in the Residential Split System Long-Line Application Guideline will redtlce these losses. Ret'cr to Table 1 for field tubing equivalent line length Refer to Table 2 _br accessory requirements
For buried line applications greater than 36 in., refer to Table 2 and Residential Split System Buried Line Application Guideline.
Buried line applications may not exceed 100 t't. If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and moisture in the system
Loading...
+ 5 hidden pages