This publication contains application infor
mation for Carrier 38AD, AE, BA, and GR con
densing units used in split systems with 40RR
direct-expansion air handling units, including
system selection, performance data, combination
ratings, electrical and control data, and refrigerant
piping details.
■ SELECTION PROCEDURE (With Example)
I Given:
COOLING
Grand Total Load (Req’d TC) . . 600,000 Btuh
Sensible Load (Req’d SHC) . . . 430,000 Btuh
Temperature Air Entering
Condenser
...............................................
95 F
Temperature Air Entering
Evaporator — edb...............................77 F db
Temperature Air Entering
Evaporator — ewb
Evaporator Air Quantity
External Static Pressure
Enter the Systems Index at the desired cfm
(20,000). Select the condensing unit(s) and
fan-coil system that meets or exceeds the grand
total load (600,000 Btuh). In this example,
system no. 48 would be selected — two 38AD
024 and one 38AD016 condensing units and a
40RR054 fan-coil, yielding a nominal capacity
of 632,000 Btuh. To determine whether this
system will fully satisfy the cooling require
ments, enter the combination ratings, system
no. 48, page 9, at 20,000 cfm and 95 F condenser
entering air temperature. By interpolation, at
SYSTEMS INDEX
CONDENSING
_UNIT(S)
GR006
ВА008
¡38
ВД009
ВА008
38
ВА009
AD012
AD012
AD014
38
AD016
AD012
AD014
338
AD016
AD024
ADO^g-
AD012 (2)
38
AD024
AD028
AD024
AD012 (2)
AD028
38
AD016 & AD012
AD034
AD016 (2)_
ADÔ28
.............................
AD016 & AD012
AD034
38
AD016 (2)
AD024 & AD016
АЕ044
‘XÿJX'SVK
ш
в
шш
т
ШФ
Шщ
EER — Energy Efficiency Ratio
ТС — Total Capacity (1000 Btuh)
*ARI capacities, Energy Efficiency Ratios rated in accordance with
tFor units operating at 208 v, deduct 1000 Btuh from capacity
the system has a total capacity (TC) of 600,800
Btuh, and a calculated sensible heat capacity
(SHC) of 498,800 Btuh. For close-coupled
systems (15 ft or less of interconnecting pipe),
an additional 2% may be added to both TC and
SHC. As this system is not close-coupled, the
ratings are used directly from the combination
ratings. At this point, the sensible heat capacity
is adjusted for the evaporator entering air db
temperature. For 20,000 cfm, the bypass factor
is 0.18. The adjusted sensible heat capacity is:
Adj SHC = SHC + [1.09 X cfm x (1—bf)
X (edb-80)]
= 498,800 + [1.09 X 20,000
X (1-.18) X (77-80)]
= 498,800- 53,600
= 445,200 Btuh
Therefore, the selected system will meet all
cooling requirements.
Find heating capacity of selected fan-coil unit.
Enter Table 3, page 10, for 40RR054 and
20,000 cfm. A one-row nonfreeze steam coil
will deliver 915,000 Btuh based on 60 F enter
ing air temp, and 2 psig steam. To find the
corrected heating capacity, enter Table 1, page
10, for steam coils at 5 psig steam and 58 F
entering air temperature. By interpolation, the
correction factor is 1.062.
Corrected capacity =
915,000 X 1.062
971,700 Btuh
Leaving air db
edb -t-
58 +
corrected capacity
1.09 X cfm
97\_J00
1.09 X 20,000
= 102.6 F
The heating coil has sufficient capacity and the
leaving air db is less than the maximum
temperature of 140 F.
IV Determine fan rpm and bhp.
Refer to Table 14, page 17, for a 40RR054 at
20,000 cfm and 1.12 in. wg external static
pressure, plus 0.07 in. wg for the heating coil
(Table 4), indicates a fan rpm of 828 and
requires 12.6 bhp. As this rating point is within
the shaded area, the fan drive must be selected
and purchased locally.
V Determine size of liquid and suction lines.
Table 11, page 14, indicates the pipe sizes for
the various condensing units. These sizes are
based on an equivalent length equal to the
maximum length indicated plus 50% for fit
tings. A more accurate estimate may result in
smaller pipe sizes. Enter the table with the
condensing unit (38AD024) and the estimated
length of interconnecting pipe (90 ft). The
suction line will be 2 1/8-in. OD and the liquid
line is 7/8-in. OD. Similarly, for the 38AD016,
the suction line is 2 1/8-in. OD and the liquid
line is 7/8-in. OD. If a 38AD034 — 38AE054
condensing unit is used with more than 25 ft of
piping, a double suction riser may be required.
VI Find size nozzle, TXV and solenoid valve.
To determine the nozzle(s), TXV(s), and sole
noid valve(s), enter Table 6, page 13, with the
system number. Tables 7, 8, 9, and 10 give the
part numbers for the keys indicated in the
previous table. For this example, a C12 nozzle
would be used in each of the 3 distributors.
Also, the TXV’s and solenoid valves used would
be (using Carrier Part No.):
FAN
COIL
40RR054
COND
UNIT
38AD024
38AD024
38AD016
COIL
SECT
u
M
L
TXV
EA03PC503
SOLENOID
VALVE
EF11BS28
EE11BS28
None Requ ired
Part numbers for Alco and Sporlan valves are
obtained in a similar fashion. Also, for several
systems, a single solenoid valve will control
both the middle and lower coil sections as
exemplified by system no. 49. These systems
should be piped in accordance with Fig. 5, page
16. When the condensing unit is below the
fan-coil unit, the maximum liquid lift as pre
sented in Table 13, page 15, should be adhered
to.
COMBINATION RATINGS
Ratings Notes
1. Direct interpolation is permissible. Do not
extrapolate.
2. SHC is based on 80 F db temperature of air
entering evaporator coil.
Below 80 F db, subtract (corr factor x cfm)
from SFIC.
Above 80 F db, add (corr. factor x drn) to SHC.
ENTERING AIR DRY
BYPASS
FACTOR
.1097
.20
.30
...
Interpolation is permissible
Correction Factor = 1 08 x (1
79
81
86
76
78
1.952 92
1 732.59
1 51
77
Correction Factor
2.27
-BULB TEMP (F)
— r
76^
75 1 under 75
85
3 89
4.86
3 464 32
3 03
3 78
BF) X (db - 80)
ovec/85
use formula
shown be low
3. Gross capacities shown do not include a deduc
tion for evaporator fan motor heat.
4. Formulas:
hdb “ tedb
sensible heat capacity (Btuh)
1.08 X cfm
tiwb “ wet-bulb temperature corresponding to
enthalpy of air leaving evaporator coil
(hlwb)
hlwb - hewb
total capacity (Btuh)
4.5 X cfm
where hewb ~ enthalpy of air entering evap coil
5. Combination ratings are based on a 2 F line
loss. For a close-coupled system (less than
15 ft), add 2% to ratings. Piping sizes in Table
13 are based on 2 F line loss. All combination
ratings are based on R-22.
LEGEND
BF — Bypass Factor
TC — Total Capacity (1000 Btuh)
SHC — Sensible Fleating Capacity (1000 Btuh)
KW >- Compressor Motor Power Input
Ewb — Entering Wet-Bulb
U - Upper Coil
M — Middle Coil
L — Lower Coil
U-M-L abbreviations indicate connection of condensing unit to upper.
middle or lower coil of fan-coil unit
i 38GR006 and 40BA009
T emp(F)
Air Ent
TC
85 SHC
KW
TC
95 SHC
KW
TC
100 SHC
KW
TC
105 SHC
KW
TC
SHC
115
KW
2875/. 13
72
67
81
74
4660
8.2
7.7
75
69
44
57
8.7
8.27.9
7266
4358
8.9
8.4
69
6461
42566149
9.28.78.4
59
63
40
5357
9 6
9.1
38BA008 and 40BA009
Temp(F)
Air Ent
TC
85 SHC
KW
TC
SHC
95
KW
TC
SHC
100
KW
TC
SHC
105
KW
TC
SHC
115
KW
2500/. 16
72
67
101
9385105
50
627455
7.7
7.47.0
9689
4860
8.4
8.0
9486
485971
8.7
8.4
91
84
47
5870
9.18.7
8679
45
576850
9.89.4
^^38BA009 and 40BA009
Air
Ci
85
95 SHC
100
105
115
Ent
TC
SHC
KW
TC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
2500/. 16
7267
112
103
54
677959
9.9
10.5
1089990
53
657758
11.2 10.7
105
9689no101
526476
1 1.6
11.1 10.5 12.0
1029486
51
6375
12.0
11.4 10.8 12.5
968981101
49
61
12 8 12 2 1 1 6
38GR006 and 40RR008
2525/. 193375/.2342257.26
r.
85
95
100
105
115
72
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
6762726762
7971658174
55
43
7.77,26.97.9
73676275
4154
8.27.77.48.1
71646073
40536047
8.48.07.68.68.27,9
6258
68
39
52
8.78.2
58556560
63
50
38
9.1
8.6
Evgp Air - Cfm/BF
3825/. 16
Evap Air - Ewb (F)
62
72
67
69
83777484
69
537074
7.4
8.37.9
65
77
65
51
8.9
6374
635065
8.29.1
71
9.4
57
646060
476060
8.99.8
627267
7.78.48.0
7169
6769
8.48.39.08 5
686774
6756
8.68.5
666571
64
8.98.89.59.0
9.3
9.28.8
6555
65
9.39.99.5
ARI - 88,000 Btuh
Evap Air - Cfm/BF
3400/.23
Evap Air - Ewb (F)
6272
81100
72
7.68.58.27.88.6
799889
7.98.9
7795
8.29,38.98.4
7390827591
9.09.99.59.110 1
Evap A
676272
9789
70
7.87.6
928510294
536884
5268
8.58,18.9
87809789
52678055
6575
1089991
865970
7.27.9
8310091
815674
AR
- 100,000 Btuh
ir - Cfm/BF
577587
9.4
53
3400/.23
E vap Air - E
62
72676272
94
11810899
9.510.7
113
10.2
11.6
577287617995
10698
56
7254
13 2 12 5 11 9 13 4 12 7 12 1
wb (F)
75906482101
10.29.711,1 10.59.9
104
738862
11,0 10,5 11.9
1 1.4 10,8
71
11.8
9283103
69
121112102
951 16 107
9311310495
12.3
90
109
60
86
11.0 12.7
8358
E vap Air — Cfm/BF
E vap A ir — Ewb (F)
72
70
83
655064
6248
70
58466062
7.9
8.9
55445758
8.39.38.88.7
7056
7,4
69
626653
7.97.78.58.1
6764746867
616452
6462
8.4
8.0
7.2
66
8.7
9,08.58,4
8.2
58
9 48.9
767169
716665
516565
65
4961
4775/. 19
62
7877
5976
78
57
536262
7.9
72
72
8.5
69
69
8.8
67
67
9.0
62
9.6
4300/.28
67
62
91
7.6
7.3
87
8,27.9
85
84
8.68,2
82
7382
9.0
8.5
8477
7177
9.79.3
4300/.28
6762
98
80
98
11,3 10.6
10,9
11.7
101
92
7892
12.1 1 1.3
9587
7687
6762
7674
74
72
7.67.4
6969
7.9
6767
8.2
8.3
6161
61
8 9
77
72
72
70
70
67
67
62
:^^38BA008 and 40RR008
2200/. 17
72676272
Tc
85
95
100
105
115 SHC
968881100
SHC465767
KW
7.57.26.9
TC
9184
SHC
45556650
KW
8.27.77.4
TC
89
SHC
445465
KW
8.4
TC
87
SHC
435464
KW
8.98.4
TC
82
4152
KW
9 69.18.79 8
¡38BA009 and 40RR008
2200/. 17
72676272
TC
85
95 SHC
100
105 SHC
115
1059789
SHC
50
KW
10.19.69.1
TC
101
4859
KW
10.8 10.49.9
TC
9991
SHC
48
KW
TC
KW
TC
SHC
KW
10.7
11.2
968981101
4757
11.7 11.0 10.5 12.0
92
4555
12.4 11.8 11.1
38AD012 and 40RR008
Temp(F)
Air Ent
2200/. 163000/.203800/.23
7267
TC
85 SHC
95
100 SHC
105
115 SHC
11910798124
54
KW
11.4 10.8 10.3
TC
113103
SHC
52
KW
12.2 1 1.6
TC
1 10
52
KW
TC
SHC
KW
TC
KW
11.9
12.6
10899
51627356
13.1 12.4
103
4960
13 8 13 212 4
38AD012 and 40RR012
Temp(F)
Air Ent I
v.o na f"— -
TC il 33122112
SHC i 64
85
KW hi.4
TC i! 125
95
SHC j 61
3000/. 164000/.20
1 72
10.8
KW il2.411.6 10.9il2.712.0
tc j 122
100
SHC 60
105
115
KW ! 12.8
TC i 118 ^
SHC 58
KW j 13.2
Tc“l n 1
SHCj 56
KW 114 0
12.0
12.4
13 1
E
vap Air - Cfm/BF
3000/.21
Evap Air — Ewb (F)
67
62
92
51
7.6
7796
82
8.17.78.7
80
7679
8.4
76
93
49
7491
48
8.09.0
8679
46
62
Evap A
85104
65
79
7.47.0
88
81
64
77
8.0
7.68.4
8679
77
63
7.9
8.2
8477
6276
8.5
8.29.28.8
72
60
725167
9 48.9 10.0
ir - Cfm/BF
3000/.21
Evap A
if — Ewb (F)
6762
617155
9385107
58
8477
111
10.3
69
54
11.1
104
83
68536780
11.5 1 1.0
10.2
68
5266795774
96
6650
12.9
94
102
69
83
9.9
9.410.6
9890no
68815875
10.7
10.2
9588
10.5 11.8 1 1.3 10.7
861059689
93
11.2
10.8 12.3
8881
77
64
12.1 11.5
Evap Air — Cfm/BF
Evap Air - Ewb (F)
6272
7660
66
647558
10192116
63
94
11.9
94119
10.9 12.7
74
57
13.1
11.2
90
11310496
11.7
13.5 12.8
108
86
70
54698260
14 2
627267
67
114105128
7588658210185
11.2 10.7 ¡12.011.5
101
1 10
87
73
1 1.4
12.0
107981 19
728662
12.3 1 1.7 13.4
7185 j 62
12.2 •il3.7
9991111103
13 6 12 8
Evap Air — Cfm/BF
Evap Air — Ewb (F)
62
67
79
116106 i 1311211 12
76
113103
75
109
7488
10294
71
1 726762
139
94
10.2
9168861057496
90 i 678510473
11.2
100 1123
11.6 113.6
86
12 3
129118143
8910877
jll.811.2 10.5
11.3
109
118
1 127
i 13.1 12.4
j 65
j 115107
] 6281
1143
11.6 13.3
105128
1 14
84
102
12.0 13.8 13.0 12.3
12.8
98
9868
13.6
12 6 14 7 13 8 13 0
COMBINATION RATINGS
ARI - 87,000 Btuh
3800/.24
72
67
62
95
5673
7.77.4
989184
547184
9589
53
8.88.4
93
53
888175
ARI - 98,000 Btuh
3800/. 24
7267
115
6077
11.4
108
58
9991
55
13.0 12.4
123
63
12.9 12.3 11.7
1 7
14 5
5000/. 23
72
12.0
135
12.9
132
7193108
118
88
88
7.2
8.17.7
81
70
82
8.1
86
79
6979
8.4
75
9.69.1
11^ 38AD016 and 40RR012
62
106
98
93
10.0
9.6
10293
92
10.8 10.4
99
91
74
91
89
11.7 11.0
84
71
84115 SHC
11.7
62726762726762
118
109
11.0
114
105
81
98
111
102
79
98100
12.6 12.0KW
1081 10TC
79
96
13.1 12.5
94
77
93115
13 9
13 1
67
62
/-¡22
132
99
121
1 1.4
10.8
125
115
115
11.4
12.2
121112
95112
11.8
12.6
117
108
109101
90101
38AD014 and 40RR012
3000/. 164000/.205000/. 23
7267627267
tc
156143130165152
SHC
85
95
100 SHC
105 SHC
US SHC71
-r.
T ( * 7
8095
KW
15.7 15.0 14.2 16.3
TC
149136123158144
SHC
7792108
KW
16.8 15.8 15.2
TC
146133
76911077694
KW
17.1
TC
KW
TC
KW
16.6 15.6
141129117149136
74
16.7 15.9
17.5
134122Tl 1
18.5 18.0 16.7 19.2 18.2
3000/. 16
7267627267
TC
166153
SHC
85
95
100
105 SHC
7893
KW
14.8 14.0
TC
161
SHC
KW
TC
SHC
KW
TC
KW
TC
KW
148
7590104
15.0 14.4
15.6
157145
74
16.0 15.4 14.8 16.6 15.9
141
153
7287102789711785
16.5 15.8 15.2 17.2
134
146
7085987695
16.7 16.0 18.5 17.6
17.8
38AD012 and 40RR016
T emp(F)
Air Ent
95
105
.
»
TC
SHC
KW
TC
SHC
KW
TC
SHC
SHC
KW
TC
SHC
KW
4500/. 156000/. 19
150139128
79101
12.5 1 1.9
142131
7698
12.7 12.1 13.8 13 0 12 3
13.3
127117142
137
75
13.7 13.1
132122113
7394113
14.2 13.5
123113
6991
14.9 14 2 13 4
38AD014 and 40RR016
Temp(F)
Air Ent
4500/. 156000/. 19
726762
|tc
SSjSHC
95 SHC
I KW
lOOlSHC
i KW
105* SHC
! KW
115 SHC
179166152188
9111313598
KW
17.1
ftc”
171
881 10
18.1
|TC
166
8710813093122148
18.7
!TC
161
85106
19.3
rtc~
153
8 : 102
KW
20 219 2
16.3
158145
17.3
154141174161
17.9 17.C 19.4
149
18.3 17.2
140
E vap Air - Cfm/BF
Evap Air - Ewb (F)
7998
111
120154141
89105
861027190
Evap A
15.4
77
17.3 16.4
17.9 17.1
74
18.3 17.2 16.4
141
129
Ir — Cfm/BF
4000/.20
Low
Suet
133
131
89103
128
122
Evap A
-
ir - Ewb (F)
176
163150
84104
14.6
15.3
170
157144175163
8210112088111
16.0
15.5
166
153141171
80
162149
16.4
154
142
Evap Air -
Evap Air — Ewb (F)
157145
89117
123
12.7 12.2 1 1.5
11.2
120147135125
120
85113125
11784112
96
12.4
12.7 14.6
105
105
130
13.4 12.6
14.2
136126
110
82
13.8
126117108128
79101108
15.2 14 5 13 7
Evap Air — Cfm/BF
Evap Air — Ewb (F)
72
6762
174
127
15.5 17.6
16.7 15.9
180166
13295123
16.4
18.7
17.8 16.9
18.3
137168156
12891121
19.9 18.9 17.7
_
_
-
148134
115134
19 7
128
124
18 2
62
138
118
14.7 16.7
131
96114
15.6
128160146
1 1281104
15.8 18.2
125154
93
1 11
118145
108
17.1 19.9
62
12291
13.9
14.8 16.2
99
119
15.2
137
15.6
130159
1 1382
16.5
133
133
121
121
1 16
1 16
13.0
160191
155
153182
152
148
17.4
143
143
18 7
726762
171158144
85108131
164150137
83106127
17.6 16.7 16.0
80
18.8
77
15.0
15.8
134
126
17.3 16.4
130
142
102124
17.7 16.7
122
134
100121
18.5 17.6
5 000/. 23
7267
181
15.4
87
16.8 16.1
166155
17.4 16.6
18.8 18.1
62
154
168
114136
14.9 14.1
150
134
15.0
15.6
159146
110133
15 4
142
108131
15.9
147136
104127
17 0
7500/.22
7267
160
100133
12.8 12.3
149137
96
13 8 13 2
144133
95128123
14.2 13.5
138
93
14.7
89118
15 4
62
147136
136
11.7
127
127
129
12 4
123
13.0
118
128
126118
13.6
13.9
110
118
no
14 6 13 9
7500/.22
7267
107
17.8
105
18.9
178
104
19.4 18.8
—
_
-
_
_
-
62
165
178
145165
17.0 16.2
170157
157
139
18.0 17.2
164152
152
138
17.7
158146
135146
18.1
19.2
137
148
137
131
19 0
20 0
COMBINATION RATINGS
r38AD016 and 40RR016
P(F)
4500/. 15
E vap
E vap Air — 1
7267627267
TC
199182168206191176
SHC
85
95
100
105
115
0^38ADO24
94117139
KW
TC
SHC
KW 17.2 16.5 15.7
TC
SHC
KW
TC
SHC
KW
TC166* 157144
SHC
KW
15.4
16.1
189174160
114
91
184170
90112
17.8 17.016.2
180166
88110
18.4 17.5 16.7
84106
19 4
18 8
and 40RR016
104133161
14.5
16 4 15.7
196
135101129
17.6
157
192178
13499
18.2
153188
13297
18.8 18.0
174* 160*
12875122
19 9 19.1
17.8
E vap A
A
Pr.*
4500/. 15
E vap A ir - E
72676272
TC
85 SHC
95 SHC
100
105
115
232213195246226
134157
111
KW
19.9 18.8 17.9 20.5
TC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
204
222
107130
20.119.0
21.6
199
218
105
128150115144
22.2 20.8
194177224
213
103126148113
22.8 21.5 20.3 23.5 22.3 21.1
185
203
99122144109
23.0
24.4
121151180131166201
186235216
117
152
22.0 20.9 19.8
18223021 1 193238219200
19.6
22.7 21.6 20.4
168213
25.1
21.7
38AD016 and 40RR024
T emp(F)
Air Ent
uona
TC
SHC
85
KW
TC
95 SHC
KW
TC
SHC
100
KW
TC
SHC
105
KW
TC
SHC
115
KW
6000/. 158000/.18 1 10,000/.2r
726762726762726762
214198183221206
139169121160190
108
17,0
16.2
189
204
105135165118156181
18.1 17.1
185171205191177
199
134
104
17.8
18.7
180
193
1021321621 14 153
18,5 17.4 20.0
19.4
179* 166* 156184* 171* 158* 188*
98128156112
19.4
20.3
Evap Air — Cfm/BF
Evop Air — E\yb (F)
17.4
15.5
210196
175
18,6 17.7 16.8 18.7
16.6
164116155177128172181
17.0
19.3
166199
20 6 20 1
18 7
[38AD012 w/U, 38AD012 w/L. of 40RR024
Temp(F)
6000/. 15
E vap Air — Cfm/BF
vap Air — Ewb (F)
E
726762726762
TC
85 SHC
95 SHC
100 SHC
105 SHC
115 SHC
257237217269
126156186
KW
22.7 21.520.2 23.4 22.2
TC
246226
1221 52 181
KW
TC
KW
TC
KW
TC
KW
23.1
24,4
240
221203
119150179
23.9
25.2
233215198243224
1 16 147177130169205143
26.1 24.7
220
204188228212196 233
1 12
143172
27.8 26. ;
139
257
208
135174212
21.7
25.1 23.8 22.5
250
133172
22.4
26.0 24.6 23.2 26.5 25.2 23.8
23.1 26.9
125
24,5 28,7 26,9 25,3
A
ir — Cfm/BF
6000/. 19
7500/ 22
:wb (F)
627267
211197
1 13 147
15.1 16,8 15.9
181168
16.7
128156108
17.3
174
126154106
200
187
109
158
16.2
164
16.7
159
17.2 19,2 18.3 17.5
149177* 165*
146103
18.3 20.3 19.3
143173
17.9 17,0
196
183
141
18.5 17.6 16.9
192178164
139
137154
ir - Cfm/BF
6000/. 197500/.22
Iwb (F)
6762726762
254
207
18.6
19.5
198243224205
147175127162196
173125159
206188232
171
142
195
178
138166
23.8 22.5 25.6 24,3 23.0
190
15.9
16.5
181
17.4
18.4
185
172203
172126171176
18.0
18.8
149
158
18 8 21 ;
235216
20,0 19.0
21.0
21.4
22.5
23.2 22.1
^213
157
123
24.0
22.8 21,6
220
202185
119
153185
226
21 1
178195
133
16.9
17.5
215200186
129173
17.9 17.0
209195
18.4
19.6
189176
19 1 18 2
20.5
175* 161*
167161
122
20 119 0
8000/. 1810,0007.21
726762
249
178
238
231
25.4
164
277256 ^236
228
216152
21.0 23.7 22,6
218264
213
209
207249
24.G
196138184
199236
244
147193225
25.7 24.4 23.2
257237220
145191
230214
188214
26.0 24.5
27.4
216201
29.2 27,5
38AD024 and 40RR024
P(F)
62
182
178
15.3
173
16.3
169
169100 SHC
Cr
85
95
TC
SHC
KW
TC
SHC
KW 22.7
TC
KW
TC
164
154
18 7
105 SHC
KW
TC
115
SHC
KW
38AD028 and 40RRd'24
1 ciiiH VI
K
G
Slid
TC
SHC
85
KW
TC
95 SHC
20.3
KW
TC
105
115
SHC
KW
TC
SHC
KW
TC
SHC
KW
194100
20.9
195
192
|^"38AD024 and dORRO^d”
Temp (F)
Air Ent
195
16.1
186
TC
85 SHC
KW
TC
SHC
95
KW
181
17.6
TC
100 SHC
KW
TC
105 SHC
KW
TC
115 SHC
KW
BF — Bypass Factor
TC — Total Capacity (1000 Btuh)
21.5
225
SHC — Sensible Heating Capacity (1000 Btuh)
KW — Compressor Motor Power Input
Ewb — Entering Wet-Bulb
U — Upper Coil
M — Middle Coil
220
L — Lower Coil
U-M-L abbreviations indicate connection of condensing unit to
upper, middle or lower coil of fan-coil unit
*Capacities at a minimum 38AD016 charge to prevent high
pressurestat cutout Other capacities are at optimum charge for
201
25.7
maximum capacity.
E
vap /
6000/. 15
72
67
259
238218
128159
21.2 20.1
247227
124
241
121
23.4
235216
1 19
24.2 23.0
223205187
115145175
25 9
189
19.1
208
154
185
21.5 20.4
222203
152
182134174
21.0
22.2
197246
150180
21.7 24.9
24.5 23 2
6000/. 15
62
iir — Cfm/BF
8000/. 18
E
vap /
ur - Ewb(F)
726762
271250
142181
21.8 20.7
258238218265
137176215150
23.3 22.1 21.0 23.7
252
24.5 22.8 21.7
133172207
233214196239
129167196
26 5 25 2 23 8 26.9
E vap
A
229279257237
220
19.7
132213
211147
226207
22.4
23.6
ir — Cfm/BF
8000/. 18
10,0007.21
726762
154
201
22.1
21.1
245225
197
22.5
259
239219
194219
24.5
23.3 22.1
252
232213
145
192213
25,3 24.0
220201
141187201
25.6 24 3
10,0007.21
20,1
2-n4
22.8
Evap Air — Ewb (F)
72
67
299
62726762
274
141
29.8 27,4 25.7
288264
137
31.6
283259
135
32.5 30,6 29.;
275
133162194146
33.4
263242221275
129
34 7
251315291267
172202
166198
29.8
165196
253232
32.2 30,5 34.6 32.7
158189
33 3
31.3
242
302
28.3 32.6 30.9
237296
33.4 31.7 30.2
35 9 34 1
31 3
155195 234
28.9
279
150190
273251304
148188 226160
289
267245
186
254
142182220154 201241
72
6762
325301
166214
26.8 31.8
256
231162212
29.4
224
30.8 35 2
234
32 4 36 6 34 7
29.8 27.5
311288265
33.5
31.7 30.1
282259
208255
34.3 32.5 30,6
297275253
157203252
33.4
284262241
31.6
33 1
Evap Air — Cfm/BF
7500/. 15
10,000/. 1812,500/.21
Evap Air - Ewb (F)
72
6762 I 72
275
253
142180
22.0 20.9
261
137
23.4 22.2
254
134
24.1 22.9 21.7
247
132
24.9
233212193241221201247226206
127164
26 5 25 1
231
218159
19.8 22,5 21.4
239218271249
175212154
21.0
233212
209
173
226
206
170
206149197
23.6
22.3
193
23 7 27 1 25 7
6762726762
287264
24.0
264242221
152200221168225227
24.7 23.5 22.2 25.1
256
25.5
144191
242294271248
208242175233248
202228
22.8 21.6 24.3 23.1
235
24.2
22.9 21.7 20.7
20.3
228278255234
170
227234
270
214
262240220
214
165
22.9 25.9 24.5
160
201
27 5 26 0
24 2
21.9
227
247
22.6
23.8
222
23.3
217206
24 6
LEGEND
237
225
276
261
257
220
COMBINATION RATINGS
[38AD012 w/U, 38AD012 w/L of 40RR02838AD016 w/U, 38AD016 w/L of .