Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock
or other conditions which may cause personal injury or
property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the
individual instructions package
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloths for brazing operations and have a fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and appropriate national electrical codes
(in USA, ANSI/NFPA70, National Electrical Code (NEC); in
Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the
safety-alert symbol . When you see this symbol on the unit
and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or
operation.
INSTALLATION GUIDELINE
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury
or death.
Before performing service or maintenance operations on
unit, always turn off main power switch to unit and install
lockout tag. Unit may have more than one power switch.
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
Puron® (R-410A) refrigerant systems operate at higher
pressures than standard R-22 systems. Do not use R-22
service equipment or components on Puron refrigerant
equipment.
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury
or death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing 38AUQ units.
Replacement /Retrofit – R22 to Puron
Split system heat pumps are intended to be installed with
matching indoor sections only. The 38AUQ heat pump outdoor
units are matched only with same-size 40RUQ indoor sections.
Existing R-22 indoor coils cannot be converted to R-410A heat
pump duty. Only the existing refrigerant piping is a candidate
for retrofit use.
Acid test – If the existing system is being replaced because of a
compressor electrical failure, assume acid is in system. If
system is being replaced for any other reason, use an approved
acid test kit to determine acid level. If even low levels of acid
are detected, install a 100 percent activated alumina suction
line filter drier in addition to the replacement liquid-line filter
drier. Operate this system in COOLING ONLY. Remove the
suction line filter drier as soon as possible, with a maximum of
72 hr of operation.
Recommendation: Install a ball valve in the liquid line at the
filter drier location when installing a suction filter in the suction
line.
®
Installation –
1. Remove the existing evaporator coil or fan coil and install
the replacement coil.
2. Drain oil from low points and traps in suction line tubing
if they were not replaced.
3. Remove the existing outdoor unit. Install the new outdoor
unit according to these installation instructions.
4. Install the factory-supplied liquid-line filter drier at the indoor coil just upstream of the TXV.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never install suction-line filter drier in the liquid-line of a
®
Puron
system.
5. If required, install a 100% activated alumina suction line
filter drier at the outdoor unit.
6. Evacuate and charge the system according to the instructions in this installation manual.
7. Operate the system for 10 hr. Monitor the pressure drop
across the suction line filter drier. If pressure drop exceeds 3 psig (21kPa), replace suction-line and liquid-line
filter driers. Be sure to purge system with dry nitrogen
and evacuate when replacing filter driers. Continue to
monitor the pressure drop across suction-line filter drier.
Repeat filter changes is necessary. Never leave suctionline filter drier in system longer than 72 hr (actual time).
2
Fig. 1 — 38AUQ*07-12 Unit Dimensions
UNIT
Standard
Weight
Corner
A
Corner
B
Corner
C
Corner
D
Center of GravityUnit Height
lbs.kg.lbs.kg.lbs.kg.lbs.kg.lbs.kg.XYZH
38AUQ*07
444201134619744904112356
23
[584]
26
[660]
13
[330]
42-3/8
[1076]
38AUQ*08
4832191627411050853912557
20
[508]
24
[610]
13
[330]
42-3/8
[1076]
38AUQ*12
57526118684126571064815771
21
[533]
24
[610]
23
[584]
50-3/8
[1280]
3
Table 1A — Physical Data — 38AUQ*07-12 Units — 60 Hz English
UNIT SIZE 38AUQ*07*08*12
NOMINAL CAPACITY (tons)
OPERATING WEIGHTS (lb)
Aluminum-Fin Coils444483575
REFRIGERANT TYPE
Operating Charge, Typical (lb)
‡
†
Shipping Charge (lb)10.012.015.0
COMPRESSOR
Qty...Type1...Scroll1...Scroll1...Scroll
OUTDOOR FANS
Qty...Rpm2...11002...11002...1100
Motor Hp
Diameter (in)222222
Nominal Airflow (Cfm Total)6,0006,0006,000
Watts (Total)610610610
OUTDOOR COIL (Qty)
Face Area (sq ft total)17.523.028.1
Rows/Fins per inch (FPI)2/172/172/17
CONTROLS
Pressurestat Settings (psig)
High Cutout630 ±10630 ±10630 ±10
Cut-in505 ±20505 ±20505 ±20
Low Cutout27 ±327 ±327 ±3
Cut-in44 ±544 ±544 ±5
PIPING CONNECTIONS (in. ODS)
Qty...Vapor1...1
Qty...Liquid
67.510
R-410A
18.021.027.0
1
/
4
1
/
4
1
/
4
1...Round Tube/Plate Fin (RTPF)
1
/
1...
1...11/
8
3
/
8
1...1/
1...13/
8
2
1...1/
8
2
LEGEND
ODS — Outside Diameter Sweat (socket)
‡ Unit is factory-supplied with partial charge only.
† Typical operating charge with 25 ft of interconnecting piping.
4
Table 1B — Physical Data — 38AUQ*07-12 Units — 60 Hz SI
UNIT SIZE 38AUQ*07*08*12
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Aluminum-Fin Coils201219261
REFRIGERANT TYPE
Operating Charge, Typical (kg)
‡
†
Shipping Charge (kg)4.55.96.8
COMPRESSOR
Qty...Type1...Scroll1...Scroll1...Scroll
CONDENSER FANS
Qty...r/s2...182...182...18
Motor Hp NEMA
Diameter (mm)560560560
Nominal Airflow (L/s)283228322832
Watts (Total)610610610
CONDENSER COIL (Qty)
Face Area (sq m total)1.62.12.6
Rows/Fins per Meter (Fins/m)2/6702/6702/670
CONTROLS
Pressurestat Settings (kPa)
High Cutout4344 ±704344 ±704344 ±70
Cut-in3482 ±1383482 ±1383482 ±138
Low Cutout186 ±21186 ±21186 ±21
Cut-in303 ±35303 ±35303 ±35
PIPING CONNECTIONS (in. ODS)
Qty...Vapor1...1
Qty...Liquid
21.126.435.1
R-410A
8.29.512.2
1
/
4
1
/
4
1
/
4
1...Round Tube/Plate Fin (RTPF)
1
/
1...
1...11/
8
3
/
8
1...1/
1...13/
8
2
1...1/
2
8
LEGEND
NEMA — National Electrical Manufacturers Association
ODS — Outside Diameter Sweat (socket)
‡ Unit is factory-supplied with partial charge only.
† Typical operating charge with 7.62 m of interconnecting piping.
5
123456789 10 11 12 13 14 15 16 17 18
38AUQA12A0C6–0A0A0
Model TypePackaging
38AU= Carrier Condensing Unit
R--- 410A Refrigerant
0=Standard
Type o f Co il
Electrical Options
Q = Heat Pump Scroll Compressor
A=None
C = Non-Fused Disconnect
1=LTL
Service Options
0=None
1=
Not Used
A=PlaceHolder
Base Unit Controls
0 = Electro-Mechanical Controls
Design Revision
Voltage
1 = 575/3/60
5 = 208 / 230/3/60
6 = 460/3/60
2 = Powered Convenience Outlet
Puronr
1 = Un-powered Convenience Outlet
_________________
Nominal Tonnage
07 = 6 Tons
08 = 7.5 Tons
12 = 10 Tons
Refrigerant Options
A = None
B = Low Ambient
A = Initial Rev (Discrete Model Number)
Not Used
A=Not Used
Not Used
0=Not Used
M= Al/Cu with Hail Guard
N = Precoat Al/Cu with Hail Guard
P = E-Coat Al/Cu with Hail Guard
R = Cu/Cu with Hail Guard
Coil Options
A= Al/Cu
B = Precoat Al/Cu
C = E-Coat Al/Cu
E= Cu/Cu
SETANGISEDNOITISOP
)radnelac lacsif( erutcafunam fo keeW1−2
)ASU ,saxeT ,PTE = G( noitacol gnirutcafunaM5
rebmun laitneuqeS6−10
12345678910
4809G12345
POSITION NUMBER
TYPICAL
Year of manufacture (”09” = 2009)3−4
Fig. 2 — Model Number Nomenclature
Fig. 3 — Serial Number Nomenclature
6
REAR:
Min 18” (457 mm)
requried for service
Note: Observe requirements for 39” (914 mm) operating clearance
on either Left or Rear coil opening.
RIGHT:
Min 18” (457 mm)
requried for service
LEFT:
Min 18” (457 mm)
requried for service
FRONT:
42” (1067 mm)
.INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation
requirements.
2. Determine unit location (from project plans) or select unit
location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (pad, rails
or other) that provides for the minimum clearances required for
safety. This includes the clearance to combustible surfaces, unit
performance and service access below, around and above unit
as specified in unit drawings. See Fig. 4.
Select a unit mounting system that provides adequate height to
allow for removal and disposal of frost and ice that will form
during the heating-defrost mode.
NOTE: Consider also the effect of adjacent units on airflow
performance and control box safety clearance.
Do not install the outdoor unit in an area where fresh air supply
to the outdoor coil may be restricted or when recirculation from
the condenser fan discharge is possible. Do not locate the unit
in a well or next to high walls.
Evaluate the path and required line length for interconnecting
refrigeration piping, including suction riser requirements (outdoor unit above indoor unit), liquid line lift (outdoor unit below
indoor unit) and hot gas bypass line. Relocate sections to minimize the length of interconnecting tubing.
DO NOT BURY REFRIGERATION LINES.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto the
unit.
Fig. 4 — Service Clearance Dimensional Drawing
Step 2 — Complete Pre-Installation Checks
CHECK UNIT ELECTRICAL CHARACTERISTIC —
Confirm before installation of unit that voltage, amperage and
circuit protection requirements listed on unit data plate agree
with power supply provided.
UNCRATE UNIT — Remove unit packaging except for the
top skid assembly, which should be left in place until after the
unit is rigged into its final location.
INSPECT SHIPMENT — File a claim with shipping company if the shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and National Electrical
Code (NEC, U.S.A.) for special installation requirements.
• Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and servicing unit. See Fig.1 for unit
dimensions and weight distribution data.
• Locate the unit so that the outdoor coil (condenser) airflow is unrestricted on all sides and above.
• The unit may be mounted on a level pad directly on the
base channels or mounted on raised pads at support
points. See Tables 1A and 1B for unit operating weights.
See Fig. 1 for weight distribution based on recommended
support points.
NOTE: If vibration isolators are required for a particular
installation, use the data in Fig. 1 to make the proper
selection.
Step 3 — Prepare Unit Mounting Support
Slab Mount
Provide a level concrete slab that extends a minimum of 6 in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of
condenser coil air inlet to prevent grass and foliage from
obstructing airflow.
Step 4 — Rig and Mount the Unit
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
.
RIGGING — These units are designed for overhead rigging.
Refer to the rigging label for preferred rigging method. Spreader bars are not required if top crating is left on the unit. All panels must be in place when rigging. As further protection for coil
faces, plywood sheets may be placed against the sides of the
unit, behind cables. Run cables to a central suspension point so
that the angle from the horizontal is not less than 45 degrees.
Raise and set the unit down carefully.
If it is necessary to roll the unit into position, mount the unit on
longitudinal rails, using a minimum of 3 rollers. Apply force to
the rails, not the unit. If the unit is to be skidded into position,
place it on a large pad and drag it by the pad. Do not apply any
force to the unit.
Raise from above to lift the unit from the rails or pad when unit
is in its final position.
After the unit is in position, remove all shipping materials and
top crating.
Step 5 — Complete Refrigerant Piping
Connections
Refrigerant lines must be carefully designed and constructed to
ensure equipment reliability and efficiency. Line length, pressure drop, compressor oil return, and vertical separation are
several of the design criteria that must be evaluated. See
Tab le 2.
IMPORTANT: Do not bury refrigerant piping underground.
IMPORTANT: A refrigerant receiver is not provided with
the unit. Do not install a receiver.
Length EquivEquivalent tubing length, including effects of refrigeration specialties devices
Liquid LineTubing size, inches OD.
Max Lift
Cooling
Heating
Suction LineTube size, inches OD
ChargeCharge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger
NOTE:
Length Linear
Length Equiiv
Max Lift
Cool
Heat
Suction Line
0-25
0-38
3
/
8
25
25
7
/
8
25-50
38-75
3
/
8
50
50
7
/
8
50-75
75-113
3
/
8
48
46
1-1/
8
1
75
60
75-100
113-115
3
/
2
/
39
31
1-1/
8
8
Charge (lbs)17.818.820.322.621.424.5
1
/
2
1
/
2
1
/
2
1
/
2
Max Lift
Cool
Heat
Suction Line
25
25
7
/
8
50
50
1-1/81-1/
75
60
8
1-1/
8
100
60
1-1/
8
Charge (lbs)20.923.024.926.8
Max Lift
Cool
Heat
Suction Line
1
25
25
7
/
2
/
8
1-1/81-1/
1
50
50
/
2
1
/
2
75
60
8
1-1/
8
1
/
2
85
60
1-1/81-3/
Charge (lbs)26.828.830.733.437.2
Maximum liquid lift at maximum permitted liquid line pressure drop
• Indoor unit ABOVE outdoor unit
• Indoor unit BELOW outdoor unit
suction line size (where applicable)
For applications with linear length greater than 100 ft (30.5 m), contact your local Carrier representative.
1
/
2
100
60
5
/
8
100
60
8
CHECK VERTICAL SEPARATION — If there is any vertical
separation between the indoor and outdoor units, check to
ensure that the separation is within allowable limits. Relocate
equipment if necessary.
PROVIDE SAFETY RELIEF — If local codes dictate an
additional safety relief device, purchase locally and install
locally. Installation will require the recovery of the factory
shipping charge before the factory tubing can be cut and the
supplemental relief device is installed.
REFRIGERANT LINE SIZING — Consider the length of
the piping required between the outdoor and indoor units. The
maximum allowable line length is 100 ft (30.5 m). See Table 2.
Refrigerant vapor piping should be insulated.
IMPORTANT: A refrigerant receiver is not provided
with the unit. Do not install a receiver.
Table 3 — Maximum Vertical Separation*
UNIT 38AUQUNIT 40RUQ
070750 (15.2)
080860 (18.3)
121260 (18.3)
*Vertical distance between indoor and outdoor units.
DISTANCE FT (M)
Unit 38AUQ
Above Unit 40RMQ
INSTALL FILTER DRIER(S) AND MOISTURE
INDICATOR(S) — Every unit MUST have a bi-directional
filter drier in the liquid line. Locate the filter drier at the indoor
unit, close to the evaporator coil’s thermal expansion valve
(TXV) inlets.
38AUQ units include one Puron-duty filter drier, shipped in
cartons attached to the unit basepan. Remove the filter drier
and prepare to install in the liquid line at the evaporator coil.
Do not remove connection fitting plugs until ready to connect
and braze the filter drier into the liquid line position.
Table 4 — Puron-duty Filter Drier(s)
Model-SizeQty
38AUQ*071
38AUQ*081
38AUQ*121
Liquid
Line OD
3
/8-in8 cu. in.KH43LG091
1
/2-in16 cu. in.KH43LG085
1
/2-in16 cu. in.KH43LG085
Desiccant
Vol ume
Part
Number Ref
Installation of liquid line moisture indicating sightglass in each
circuit is recommended. Locate the sightglass(es) between the
outlet of the filter drier and the TXV inlet.
Refer to Table 5 for recommendations on refrigeration
specialties.
Select the filter drier for maximum unit capacity and minimum
pressure drop. Complete the refrigerant piping from the indoor
unit to the outdoor unit before opening the liquid and suction
lines at the outdoor unit.
8
Table 5 — Refrigerant Specialties Part Numbers.
LIQUID LINE
SIZE (in.)
3
/
8
1
/
2
5
/
8
†
38AUD units require TWO sets of parts.
LIQUID LINE
SOLENOID VALVE (LLSV)
ALC-066208AMG-24/50-60HMI-1TT3
ALC-066209
†
ALC-066212AMG-24/50-60HMI-1TT5
INSTALL LIQUID LINE SOLENOID VALVE —
It is recommended that a bi-directional solenoid valve be
placed in the main liquid line (see Figs. 5 & 6) between the
outdoor unit and the indoor coil. Locate the solenoid valve at
the end of the liquid line, near the outdoor unit connections,
with flow direction arrow pointed at the outdoor unit. Refer to
Table 5. (A liquid line solenoid valve is required when the
liquid line length exceeds 75 ft [23 m].) This valve prevents
refrigerant migration (which causes oil dilution) to the
compressor during the off cycle, at low outdoor ambient
temperatures. Wire the solenoid according to the unit label
diagram.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Failure to use a solenoid valve relay (SUR) accessory may
cause overload of Comfort Alert Diagnostic Module
(CADM) and compressor alarm lock out.
CAPACITY CONTROL LIQUID LINE SOLENOID VALVE
Evaporator capacity control via liquid solenoid valve is not recommended for use with 38AUQ models.
8 DIAMS
MIN
LEGEND
EQUALIZER LINE
SIGHT GLASS
A LOCATION
TXV
FILTER DRIER
A LOCATION
FLOW
LIQUID
LINE
SOLENOID
VALVE
INDOOR
COIL CKT
AIRFLOW
TXV
SENSING
BULB
15 DIAMS
MIN
10
DIAMS
TXV — Thermostatic Expansion Valve
Fig.5 — Location of Sight Glass(es) and Filter Driers
(typical 38AUQ/40RUQ size 07 & 08 systems)
LLSV
COIL
SIGHT
GLASS
AMG-24/50-60HMI-1TT4
INDOOR
COIL CKT 2
AIRFLOW
INDOOR
COIL CKT 1
AIRFLOW
TXV
SENSING
BULB
15 DIAMS
MIN
TXV
SENSING
BULB
15 DIAMS
MIN
10
DIAMS
10
DIAMS
TXV — Thermostatic Expansion Valve
Fig.6 — Location of Sight Glass(es) and Filter Driers
(typical 38AUQ/40RUQ size 12 system)
Table 6 — Minimum Outdoor Air Operating Temperature
†Wind baffles (field-supplied and field-installed) are recommended
for all units with low ambient head pressure control. Refer to Low
Ambient Control Installation Instructions (shipped with accessory)
for details.
CAPACITY
100
Table 7 — Insulation for Vapor Line Exposed
LENGTH OF EXPOSED
VAP OR L INE*
ftmin.mm
103
258
3511
5015
*Recommended vapor line insulation for piping exposed to outdoor
conditions to prevent loss of heating during heating cycle. When
vapor line goes through interior spaces, insulation should be
selected to prevent condensation on cooling cycle. Heating capacity should be reduced 1000 Btuh (295 W) if over 35 ft (11 m) of
vapor line with
ditions.
†Closed cell foam insulation with a thermal conductivity of: 0.28 Btu
2
• in./ft
• h • °F (0.04 W/m • °C).
3
/4 in. (19 mm) insulation is exposed to outdoor con-
FILTER
DRIER
Provided with unit
See Table 4
EQUALIZER LINE
TXV
CKT 2
8 DIAMS
MIN
TXV
CKT 1
8 DIAMS
MIN
LEGEND
MINIMUM OUTDOOR
TEMP — F (C)*
Standard Unit
35 (1.7)–20 (–28.9)
to Outdoor Conditions
INSULATION THICKNESS†
3
/
8
1
/
2
3
/
4
3
/
4
SIGHT GLASS
LOCATION
FILTER DRIER
LOCATION
Head Pressure
Control†
10
13
19
19
FLOW
LIQUID
LINE
SOLENOID
VALVE
9
MAKE PIPING CONNECTIONS — Piping connections at
Factory
High-Flow
Access Port
Service Valve
with Stem Cap
Field Service
Access Port
(Schrader core)
Sweat
Connection
the 38AUQ unit are ball valves with stub tube extensions. Do
not open the unit service valves until all interconnecting tube
brazing as been completed.
The stub tube connections include ¼-in SAE service fittings
with Schrader valve cores (see Fig. 7). Before making any
brazed connections to the unit service valves, remove both
Schrader valve caps and cores and save for re-installation. Connect a source for nitrogen to one of these service fittings during
tube brazing to prevent the formation of copper oxides inside
the tubes at brazed joints.
Fig. 7 — Typical Piping Connection Assembly
When connecting the field tubing to the 38AUQ service valves,
wrap the valves in wet rags to prevent overheating
Pressure-test all joints from outdoor unit connections over to
the indoor coil, using nitrogen as pressure and with soap-andbubbles.
When pressure-testing is completed, remove the nitrogen
source at the outdoor unit service valves and re-install the two
Schrader valve cores. Torque the cores to 2-3 in-lbs (23-34
N-cm).
Where vapor line is exposed to outdoor air, line must be
insulated. See Table 7 for insulation requirements.
EVACUATION/DEHYDRATION — Evacuate and dehydrate
the connected refrigeration system(s) (excluding the 38AUQ
unit) to 500 microns using a two-stage vacuum pump attached
to the service ports outside the 38AUQ service valves, following description in GTAC II, Module 4, System Dehydration.
Example:
38AUQ*08
60-ft (18.3 m) linear line length
Equivalent line length 90-ft (27.4 m)
Liquid Lift: 20-ft (6.1 m)
Select line sizes from Table 2 (38AUQ):
1
Liquid
Suction 1-
/2 in
1
/8 in.
Charge 23.0 lbs (at 75-ft linear length)
80% of Operating Charge:
0.80 x 23.0 = 17.6 lbs
Factory Shipping Charge: 12 lbs
Field-charge quantity: 17.6 lbs –12.0 lbs = 5.6 lbs
For linear line lengths longer than 100 ft (30.5 m), contact your
local Carrier representative for system charge value.
Step 6 — Install Accessories
Accessories requiring modifications to unit wiring should be
completed now. These accessories may include Winter Start
controls, Low Ambient controls, phase monitor, Compressor
LOCout. Refer to the instructions shipped with the accessory.
Step 7 — Complete Electrical Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit cabinet
must have an uninterrupted, unbroken electrical ground to
minimize the possibility of personal injury if an electrical
fault should occur. This ground may consist of electrical
wire connected to unit ground lug in control compartment,
or conduit approved for electrical ground when installed in
accordance with NEC (National Electrical Code); ANSI/
NFPA 70, latest edition (in Canada, Canadian Electrical
Code CSA [Canadian Standards Association] C22.1), and
local electrical codes.
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
Puron® (R-410A) refrigerant systems operate at higher
pressures than standard R-22 systems. Do not use R-22
service equipment or components on Puron refrigerant
equipment.
IMPORTANT: Charge in Cooling mode only!
PRELIMINARY CHARGE — Before starting the unit, charge
R-410A liquid refrigerant into the high side of each 38AUQ
circuit through the liquid service valve(s). The amount of
refrigerant added must be at least 80% of the operating charge
listed in Table 2 for LINEAR line length LESS the factory
charge quantity (if factory shipping charge has not been
removed). See the following example.
Allow high and low side pressures to equalize. If pressures do
not equalize readily, charge R-410A vapor (using special
service manifold with expansion device) into the suction line
service port for the low side of system to assure charge in the
evaporator. Refer to GTAC II, Module 5, Charging, Recover,
Recycling, and Reclamation for liquid charging procedures.
NOTE: Check all factory and field electrical connections
for tightness. Field-supplied wiring shall conform with the
limitations of 63°F (33°C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet: The
power source leads to the convenience outlet's transformer primary are not factory connected. Installer must connect these
leads according to required operation of the convenience outlet.
If an always-energized convenience outlet operation is desired,
connect the source leads to the line side of the unit-mounted
disconnect. (Check with local codes to ensure this method is
acceptable in your area.) If a de-energize via unit disconnect
switch operation of the convenience outlet is desired, connect
the source leads to the load side of the unit disconnect. On a
unit without a unit-mounted disconnect, connect the source
leads to compressor contactor C and indoor fan contactor IFC
pressure lugs with unit field power leads.
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must
be rewired by moving the black wire with the 1/4-in. female
spade connector from the 230-v connection and moving it to
the 208-v 1/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information.
10
Field power wires are connected to the unit at line-side pres-
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
111 3
L1
L2L3
CTB1
208/230-3-60
460-3-60
575-3-60
Units Without Disconnect Option
Units With Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
Disconnect
per
NEC
sure lugs on compressor contactor C and TB1 (see wiring diagram label for control box component arrangement) or at factory-installed option non-fused disconnect switch. Max wire size
is #4 AWG (copper only).
NOTE: TEST LEADS - Unit may be equipped with short
leads (pigtails) on the field line connection points on contactor C or optional disconnect switch. These leads are for
factory run-test purposes only; remove and discard before
connecting field power wires to unit connection points.
Make field power connections directly to line connection
pressure lugs only.
FIRE HAZARD
Failure to follow this warning could result in intermittent
operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch
and condensing unit. Use only copper wire.
(See Fig. 8.)
Fig. 8 — Disconnect Switch and Unit
Units Without Factory-Installed Disconnect —
When installing units, provide a disconnect switch per NEC
(National Electrical Code) of adequate size. Disconnect sizing
data is provided on the unit informative plate. Locate on unit
cabinet or within sight of the unit per national or local codes.
Do not cover unit informative plate if mounting the disconnect
on the unit cabinet.
Units with Factory-Installed Disconnect —
The factory-installed option disconnect switch is located in a
weatherproof enclosure located under the main control box.
The manual switch handle is accessible through an opening in
the access panel.
All units -
All field wiring must comply with NEC and all local codes.
Size wire based on MCA (Minimum Circuit Amps) on the unit
informative plate. See Fig. 9 for power wiring connections to
the unit power terminal block and equipment ground.
Maximum wire size is #4 ga AWG per pole.
Provide a ground-fault and short-circuit over-current protection
device (fuse or breaker) per NEC Article 440 (or local codes).
Refer to unit informative data plate for MOCP (Maximum
Over-current Protection) device size.
Fig. 9 — Power Wiring Connections
All field wiring must comply with the NEC and local
requirements.
Voltage and Current Balance -
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See Table 10.
On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula shown
in the legend for Table 8, Note 5 (see page 14) to determine the
percent of voltage imbalance. Operation on improper line
voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such operation
would invalidate any applicable Carrier warranty.
Convenience Outlets
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status
before opening unit for service. Locate its disconnect
switch, if appropriate, and open it. Tag-out this switch, if
necessary.
Two types of convenience outlets are offered on 38AUQ
models: Non-powered and unit-powered. Both types provide a
125-volt GFCI (ground-fault circuit-interrupter) duplex
receptacle rated at 15-A behind a hinged waterproof access
cover, located on the end panel of the unit. See Fig. 10.
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.