Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual
instructions package
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
nationalelectricalcodes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
38AU
It is important to recognize safety information. This is the
safety--alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause in personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause in personal
injury,death and/or equipment damage.
R
Puron
higher pressures than standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
(R--410A) refrigerant systems operate at
. When you see this symbol on the
WARNING
WARNING
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
38AU units.
INSTALLATION GUIDELINE
Replacement/Retrofit — R--22 to Puron
Replacement/retrofit installations require change-out of
outdoorunit,meteringdevice,andfilterdriers.
Change-outofindoorcoil(evaporator)and
interconnecting tubing is recommended.
Existing evaporator coil – If the existing evaporator coil
may be re-used, check with the coil manufacturer to verify
the coil construction is suitable for operation with the
higher pressures of Puron
the existing TXV valve is compatible with R-410A,
replace if necessary. The minimum factory test pressure
rating must be 250 psig (1725 kPa). Existing coil will
need to be purged with Nitrogen to remove as much
mineral oil as possible to eliminate cross contamination of
oils.
Acid test – If the existing system is being replaced
because of a compressor electrical failure, assume acid is
in system. If system is being replaced for any other
reason, use an approved acid test kit to determine acid
level. If even low levels of acid are detected, install a 100
percent activated alumina suction-line filter drier in
addition to the replacement liquid-line filter drier.
Remove the suction line filter drier as soon as possible,
with a maximum of 72 hr of operation. Recommendation:
Install a ball valve in the liquid line at the filter drier
location when installing a suction filter in the suction line.
Existing refrigeration piping – Reuse of existing refrigerant
piping involves three issues: quality (strength) of existing
tubing, cleanliness and tube size. Inspect all tube segments
and joints for signs of damage, corrosion or poor brazing.
Flush the interconnecting piping system with dry Nitrogen to
eliminate as much trace of mineral oil as possible.
R
(R-410A). Also determine if
R
2
Same tube sizes are capable of handling higher flowrates
(expressed as tons of cooling capacity) with Puron
refrigerant compared to R--22 at constant pressure drops.
For example, a
higher tons with Puron
drop). A 1
tons with Puron than with R--22 (at 2_F pressure drop).
Refrigeration lines selected for R--22 use are typically
oversized for Puron applications. Carefully check the
existing suction line size against the table for maximum size
(see Table 7); replace vertical riser segments if necessary.
Check existing liquid line size against sizing data in Table 5
or 6; replace with smaller lines when feasible.
Installation –
1. Remove the existing evaporator coil or fan coil and
install the replacement coil when appropriate.
2. Drain oil from low points and traps in suction line
tubing (and hot gas bypass tubing if appropriate) and
evaporator if they were not replaced. Removing oil
from evaporator coil may require purging of the
tubing with dry nitrogen.
3. Unless indoor unit is equipped with a Puron® approved metering device, change the metering device
to a thermal expansion valve (TXV) designed for
Puron
4. Remove the existing outdoor unit. Install the new outdoor unit according to these installation instructions.
1
/2--inch OD liquid line is rated at 33%
R
1
/8--inch OD suction line is rated at 53% higher
R
(R-410A).
than with R--22 (at 5_F pressure
5. Install a new field-supplied liquid-line filter drier at
the indoor coil just upstream of the TXV or fix orifice
metering device.
6. If a suction line filter drier is also to be installed, install suction line drier downstream of suction line service valve at condensing unit.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never install suction--line filter drier in the liquid--line
of a Puron
7. If required, install a 100% activated alumina suction
line filter drier at the outdoor unit.
8. Evacuate and charge the system according to the instructions in this installation manual.
9. Operate the system for 10 hr. Monitor the pressure
drop across the suction line filter drier. If pressure
drop exceeds 3 psig (21kPa), replace suction-line and
liquid-line filter driers. Be sure to purge system with
dry nitrogen and evacuate when replacing filter
driers. Continue to monitor the pressure drop across
suction-line filter drier. Repeat filter changes is necessary. Never leave suction-line filter drier in system
longer than 72 hr (actual time).
R
system.
38AU
3
38AU
C10942
UNIT
Standard
Weight
Corner
A
Corner
B
Corner
C
Corner
D
Center of Gravity
Unit
Height
lbs.kg.lbs.kg.lbs.kg.lbs.kg.lbs.kg.XYZH
38AUZ*16
(MCHX)
38AUD*16
(MCHX)
38AUZ*16
(RTPF)
38AUD*16
(RTPF)
LEGEND: MCXH = Novation™ coil
633288220100134611356114465.5
633288220100134611356114465.5
731332237107172781356118684
731332237107172781356118684
RTPF = Round Tube/Plate Fin coil
38
[965.2]
38
[965.2]
38
[965.2]
38
[965.2]
19
[482.6]
19
[482.6]
19
[482.6]
19
[482.6]
15
[381]
15
[381]
17
[431.8]
17
[431.8]
503/
8
[1279.2]
503/
8
[1279.2]
503/
8
[1279.2]
503/
8
[1279.2]
Fig. 1 -- 38AU**16 Unit Dimensions
4
UNIT
Standard
Weight
Corner
A
lbs.kg.lbs.kg.lbs.kg.lbs.kg.lbs.kg.XYZH
38AUZ*25
(RTPF)
38AUD*25
(RTPF)
LEGEND: RTPF = Round Tube/Plate Fin coil
9784443601631888514767283128
9784443601631888514767283128
Corner
B
Corner
C
Corner
D
Fig. 2 -- 38AU**25 Unit Dimensions
Center of Gravity
38
[965.2]
38
[965.2]
23
[584.2]
23
[584.2]
17
[431.8]
17
[431.8]
Unit
Height
503/
[1279.2]
503/
[1279.2]
38AU
C10943
8
8
5
Table 1A — Physical Data — 38AUZ*16-25 Units — 60 Hz English
NOVATION™ (Size 16 only)
G= Al/Al
K = E-Coat Al/Al
T = Al/Al with Hail Guard
W= E-Coat Al/Al with Hail Guard
RTPF (Sizes 16 & 25)
A= Cu/Al
B = Precoat (Cu/Al)
C = E-Coat (Cu/Al)
M= Cu/Al with Hail Guard
N = Precoat (Cu/Al) with Hail Guard
P = E-Coat (Cu/Al) with Hail Guard
Fig. 3 -- Model Number Nomenclature
12345678910
0510U12345
POSITION
1 – 2
3 – 4
5
6 – 10
Week of manufacture (fiscal calendar)
Year of manufacture ("10" = 2010)
Manufacturing location (U = Monterrey, Mexico)
DESIGNATES
Sequence number
Fig. 4 -- Serial Number Nomenclature
C10944
C101041
10
Matching 38AU Model To Evaporator Coil
The Model 38AUZ is a single-circuit unit design,
requiring one set of refrigeration piping. This model can
be connected to an evaporator coil with one circuit or with
two circuits (by manifolding the evaporator connections
into a single piping system).
The Model 38AUD is a dual-circuit unit design that
requires two sets of refrigeration piping between the
outdoor unit and the evaporator coil (or coils). This model
can only be connected to an evaporator coil that has two
refrigeration circuits (or to two separate evaporator coils).
The Model 38AUD CANNOT be connected to a
single-circuitevaporatorcoil.TheModel38AUD
CANNOT be field-converted to a single-circuit design.
Table 3 – Evaporator Coil Connections
Evaluatethepathandrequiredlinelengthfor
interconnecting refrigeration piping, including suction
riser requirements (outdoor unit above indoor unit), liquid
line lift (outdoor unit below indoor unit) and hot gas
bypass line. Relocate sections to minimize the length of
interconnecting tubing.
DO NOT BURY REFRIGERATION LINES.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
REAR:
Min 18” (457 mm)
requried for service
RIGHT:
Min 18” (457 mm)
requried for service
Evaporator Coil has Connect to Model Notes
Single Circuit38AUZ ONLY
Two Circuits
38AUZ
Or
38AUDUse two separate
Manifold evaporator
circuits into single
piping system
piping systems
Before unpacking this new 38AU model, compare the
evaporator coil design to the 38AU model.
.INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (pad,
rails or other) that provides for the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit as specified in unit
drawings. See Fig. 5.
NOTE:Consider also the effect of adjacent units on
airflow performance and control box safety clearance.
Do not install the outdoor unit in an area where fresh air
supply to the outdoor coil may be restricted or when
recirculation from the condenser fan discharge is possible.
Do not locate the unit in a well or next to high walls.
LEFT:
Min 18” (457 mm)
requried for service
Note: Observe requirements for 39” (914 mm) operating clearance
on either Left or Rear coil opening.
FRONT:
42” (1067 mm)
C10201
Fig. 5 -- Service Clearance Dimensional Drawing
Step 2 — Complete Pre-Installation Checks
Check Unit ElectricalCharacteristics: Confirm before
installation of unit that voltage, amperage and circuit
protection requirements listed on unit data plate agree with
power supply provided.
Un--crate Unit: Remove unit packaging except for the top
skid assembly, which should be left in place until after the
unit is rigged into its final location.
Inspect Shipment: File a claim with shipping company if
the shipment is damaged or incomplete.
Consider System Requirements:
S Consult local building codes and National Electrical
Code (NEC, U.S.A.) for special installation
requirements.
S Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and servicing unit. See Fig.1 and
Fig. 2 for unit dimensions and weight distribution data.
S Locate the unit so that the outdoor coil (condenser)
airflow is unrestricted on all sides and above.
S The unit may be mounted on a level pad directly on the
base channels or mounted on raised pads at support
points. See Tables 1A through 2B for unit operating
weights. See Fig. 1 and Fig. 2 for weight distribution
based on recommended support points.
NOTE: If vibration isolators are required for a particular
installation, use the data in Fig. 1 and Fig. 2 to make the
proper selection.
38AU
11
Step 3 — Prepare Unit Mounting Support
Slab Mount —
Provide a level concrete slab that extends a minimum of 6
in. (150 mm) beyond unit cabinet. Install a gravel apron in
front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow.
Step 4 — Rig and Mount the Unit
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Rigging: These units are designed for overhead rigging.
38AU
Refer to the rigging label for preferred rigging method.
Spreader bars are not required if top crating is left on the
unit. All panels must be in place when rigging. As further
protection for coil faces, plywood sheets may be placed
against the sides of the unit, behind cables. Run cables to
a central suspension point so that the angle from the
horizontal is not less than 45 degrees. Raise and set the
unit down carefully.
If it is necessary to roll the unit into position, mount the
unit on longitudinal rails, using a minimum of 3 rollers.
Apply force to the rails, not the unit. If the unit is to be
skidded into position, place it on a large pad and drag it
by the pad. Do not apply any force to the unit.
Raise from above to lift the unit from the rails or pad
when unit is in its final position.
After the unit is in position, remove all shipping materials
and top crating.
CAUTION
Step 5 — Complete Refrigerant Piping
Connections
IMPORTANT: Do not bury refrigerant piping
underground.
IMPORTANT: A refrigerant receiver is not provided
with the unit. Do not install a receiver.
Provide Safety Relief —
If local codes dictate an additional safety relief device,
purchase locally and install locally. Installation will
require the recovery of the factory shipping charge before
the factory tubing can be cut and the supplemental relief
device is installed.
Model 38AUD has two separate refrigeration systems. If
required, each circuit will require a field-supplied/installed
supplemental relief device.
Table 4 – Equivalent Lengths for Common Fittings (ft)
Nominal
Tube OD
3
/
8
1
/
2
5
/
8
3
/
4
7/
8
11/
8
13/
8
15/
8
21/
8
Nominal
Tube OD
3
/
8
1
/
2
5
/
8
3
/
4
7/
8
11/
8
13/
8
15/
8
21/
8
90° Std90° Lrad 90° Street 45° Std45° Street
1.30.82.20.61
1.40.92.30.71.1
1.612.50.81.3
1.81.22.90.91.5
21.43.20.91.6
2.61.74.11.32.1
3.32.35.61.73
42.66.32.13.4
53.38.22.64.5
Branch
Flow
2.60.81.11.3
2.70.91.21.4
3.51.21.71.8
103.34.75
No ReductReduce 25% Reduce 50%
311.41.6
41.41.92
51.72.32.6
72.33.13.3
82.63.74
Elbows
Tees
Straight-Thru
Check 38AU Model with Evaporator Coil Connections —
Confirm before installation of unit that the evaporator coil
connections are consistent with this 38AU model. See
Table 3 on page 11.
Determine Refrigerant Line Sizes —
Select the recommended line sizes for 38AUZ and
38AUD unit from the appropriate tables.
Determine the linear length of interconnecting piping
required between the outdoor unit and indoor unit
(evaporator). Consider and identify also the arrangement
of the tubing path (quantity and type of elbows in both
lines), liquid line solenoid size, filter drier and any other
refrigeration specialties located in the liquid line. Refer to
the indoor unit installation instructions for additional
details on refrigeration specialties devices.
Determine equivalent line length adjustments for path and
components and add to linear line lengths. See Table 4,
Equivalent Lengths for Common Fittings, for usual fitting
types.Alsoidentifyadjustmentsforrefrigeration
specialties. Refer to Part 3 of the Carrier System Design
Manual for additional data and information on equivalent
lengths.
NOTE: Equivalent line lengths will vary based on tube
diameter. Calculate equivalent line length for each pipe by
adding equivalent length adjustments to linear lengths for
each pipe.
12
Enter the appropriate table to select the recommended line
sizes.
Model:Line Sizes Table Quantity of Line Sets
38AUZ51
38AUD62
Liquid Lift —
A liquid lift condition exists when the outdoor unit is
located below the indoor (evaporator) unit and liquid
flows vertically up in a portion of the liquid line. The
vertical column of liquid reduces the available state point
subcooling at the evaporator coil’s thermal expansion
valve. This effect reduces the length of liquid lift (feet of
elevation) that a liquid line size can accommodate.
Longer linear tube lengths will also reduce the amount of
liquid lift possible.
Check Tables 5 (38AUZ) and 6 (38AUD) for maximum
liquid lift capabilities for line sizes. Reselect the liquid
Linear LengthTypical linear tubing length, (50% added to l inear to define E quivalent Length for this table)
Liquid LineTubing size, inches OD.
Max LiftMaximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —
Suction LineTube size, inches OD
ChargeCharge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size
NOTE:For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m),
m0-88-1515-2323-3030-38
5
/
8
Max Lift255075100125
Suction Line1-1/
Charge (lbs)
Novation24.327.530.633.737.8
RTPF42.745.949.052.156.2
Max Lift2550717763
Suction Line1-1/81-3/81-3/
Charge (lbs)37.840.844.647.851.1
Equivalent tubing length, including effects of refrigeration specialties devices
S Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV
S Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV
(where applicable)
contact your local Carrier representative.
8
5
/
8
5
/
1-3/
5
/
8
8
8
8
line tube size if necessary. If maximum available tube size
cannot provide the required lift distance on this
installation, relocate the outdoor unit to reduce the
equivalent line length or the lift requirement.
Suction Riser —
A suction riser condition exists when the outdoor unit is
located above the indoor (evaporator) unit and suction
vapor must flow vertically up to return to the compressor.
Oil return is a concern when the suction tube size is too
large to produce the minimum refrigerant velocity to
ensure oil return at minimum load conditions.
Check Table 7 for maximum suction tube size for 38AU
units at minimum load conditions. Consider suction speed
riser (reduced tube size for vertical segment only) or
double suction riser arrangement if the recommended
suction tube size does not provide necessary minimum
flowrates for this riser.
NOTE: 38AUD requires TWO sets of refrigeration piping
R-410AEquivalent Length
Ft0-3838-7575-113113-150150-188
m0-1212-2323-3434-4646-57
Linear Length
Ft0-2525-5050-7575-100100-125
Model
38AUD*16Liquid Line
38AUD*25Liquid Line
38AU
Legend:
Equivalent
Length
Linear LengthTypical linear tubing length (50% added to linear to define Equivalent L ength for this table)
Liquid LineTubing size, inches OD.
Max LiftMaximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —
Suction LineTube size, inches OD
ChargeCharge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size
NOTE:For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m),
m0-88-1515-2323-3030-38
1
/
2
Max Lift255075100125
Suction Line
Charge ea. (lbs)
Novation11.713.815.717.619.6
RTPF21.723.825.727.629.6
Max Lift2550547560994695
Suction Line11/
Charge (lbs) 1219.3
Equivalent tubing length, including effects of refrigeration specialties devices
S Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV
S Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV
(where applicable)
contact your local Bryant representative.
7
/
8
1
/
2
18.3
8
1
/
2
11/
1
/
2
11/
21.0
20.3
1
/
2
8
8
11/
1
/
2
11/
23.0
22.0
8
5
8
26.0
25.0
1
/
2
11/
8
1
/
8
11/
25.9
24.9
/
2
8
5
13/813/
29.7
28.7
1
/
2
11/
8
1
/
8
28.0
27.0
5
/
2
8
32.7
31.7
/
8
Ta bl e 7 – 38AU Maximum Suction Pipe Size
Model:Unit SizeMaximum Tube Size
38AUZ
38AUD
1615/
2515/
1615/
2515/
8
8
8
8
Vertical Separation (outdoor unit above indoor unit) –
Vertical elevation difference of 200 ft (60 m) is permitted
when the outdoor unit (38AUZ or 38AUD) is located
above the indoor unit.
Insulate Suction Lines —
Apply closed-cell tubular insulation to all suction lines
between evaporator coil connection and 38AU unit’s
suction service valve.
Hot Gas Bypass —
Hot gas bypass, if used, should be introduced before the
evaporator. (A bypass route that also bypasses the evaporator
circuit may lead to oil trapping in the evaporator circuit
during low load conditions and then to oil slugging as
evaporator load increases.) Model 38AU units do not include
a hot gas stub connection; a tee must be field-supplied and
1
installed in the compressor discharge line. Run a
/2-in OD
line between outdoor unit and evaporator coil inlet. Install an
Auxiliary Side Connector at the evaporator between TXV
and distributor (follow instructions for the side connector
part). Insulate the hot gas line.
38AUD: Generally only one hot gas bypass system will be
applied on a two-circuit unit. Connect the hot gas bypass
system to Circuit 1 (first-on/last-off, connected to the
evaporator coil’s bottom circuit).
38AUD Piping Connections —
The 38AUD’s two circuits are designated Circuit 1 and
Circuit 2. Circuit 1 is controlled by the thermostat’s Y1 (or
TC1) contact and will be the first circuit on and last circuit
off. Circuit 2 is controlled by the thermostat’s Y2 (or TC2)
contact and this circuit is always the “lag” circuit.
See Fig. 6 for location of Circuit 1 and Circuit 2 service
valves and field piping connections. Circuit 1 is on the
left-hand side of the service valve compartment; Circuit 2
is on the right.
When a single piece evaporator coil with two separate
circuits is connected to a 38AUD, the lower coil circuit
should be connected to the 38AUD’s Circuit 1 so that the
evaporator’s lower coil segment is first-on/last-off (to avoid
re-evaporation of condensate on dry lower coil segments).
14
CKT
1
CKT
1
CKT
2
CKT
2
Circuit 1
Connections
38AU units include one (38AUZ) or two (38AUD)
Puron-duty filter drier(s), shipped in cartons attached to
the unit basepan. Remove the filter drier(s) and prepare to
install in the liquid line(s) at the evaporator coil. Do not
remove connection fitting plugs until ready to connect and
braze the filter drier into the liquid line position.
Circuit 2
Connections
1
C10355
Fig. 6 -- 38AUD Service Valve Locations
Plan the Circuit 1 and Circuit 2 tubing segments carefully,
mark each segment and check constantly as piping
systems are assembled to avoid piping errors.
Connecting 40RU to 38AUD: The 40RU fan coil in sizes
16, 25 and 28 is a face-split coil design that also has its
circuits designated as 1 and 2. See Fig. 7. Note that the
lower coil segment changes as the arrangement of the
40RU changes. In a vertical arrangement, the 40RU’s
lower coil segment is segment 2; this segment should be
connected to the 38AUD’s Circuit 1. In a horizontal
arrangement, the 40RU’s lower segment is now segment
1; this segment should be connected to the 38AUD’s
Circuit 1.
Note that refrigerant suction piping should be insulated.
40RU
Arrangement
Vertical
Horizontal
Cooling
Stage
Y1
Y2
Y1
Y2
40RU Coil
Segment
2
1
1
2
Connect to
38AUD
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Install Filter Drier(s) and Moisture Indicator(s) —
Every unit MUST have a filter drier in the liquid line.
38AUD models require two filter driers (one in each
liquid line). Locate the filter drier(s) at the indoor unit,
close to the evaporator coil’s thermal expansion valve
(TXV) inlets.
Table 9 – Refrigerant Specialties Part Numbers.
LIQUID LINE
SIZE (in.)
1
/
2
5
/
8
38AUD units require TWO sets of parts.
LIQUID LINE
SOLENOID VALVE (LLSV)
EF680035EF680037KM680004
EF680036EF680037KM680005
Installation of liquid line moisture indicating sightglass in
each circuit is recommended. Locate the sightglass(es)
between the outlet of the filter drier and the TXV inlet.
Refer to Table 9 for recommendations on refrigeration
specialties.
LLSV
COIL
15
SIGHT
GLASS
FILTER
DRIER
provided with unit
see Table 8
8 DIAMS
MIN
8 DIAMS
MIN
8 DIAMS
EQUALIZER LINE
TXV
EQUALIZER LINE
TXV
CKT 2
SIGHT
GLASSES
B LOCATION
TXV
CKT 1
MIN
SIGHT GLASS
A LOCATION
FILTER
DRIERS
B LOCATION
FILTER DRIER
A LOCATION
LIQUID LINE
SOLENOID
VALVE
SIGHT GLASS
A LOCATION
INDOOR
COIL CKT
AIRFLOW
INDOOR
COIL CKT 2
AIRFLOW
INDOOR
COIL CKT 1
38AU
AIRFLOW
TXV
SENSING
BULB
15 DIAMS
10
MIN
DIAMS
Single Circuit Coil Piping Configuration
For single compressor condensing units
TXV
SENSING
BULB
15 DIAMS
10
MIN
DIAMS
TXV
SENSING
BULB
15 DIAMS
10
MIN
DIAMS
Dual Circuit Coil Piping Configuration
For single compressor condensing units
Fig. 8 -- Location of Sight Glass(es) and Filter Driers
Typical 38AUZ Systems
8 DIAMS
MIN
8 DIAMS
EQUALIZER LINE
TXV
CKT 2
TXV
CKT 1
MIN
SIGHT
GLASSES
FILTER
DRIERS
AIRFLOW
AIRFLOW
SUCTION
CIRCUIT 2
TXV
SENSING
BULB
15 DIAMS
15 DIAMS
SUCTION
CIRCUIT 1
10
MIN
DIAMS
TXV
SENSING
BULB
10
MIN
DIAMS
Dual Circuit Coil Piping Configuration
For two circuit condensing units
Fig. 9 -- Location of Sight Glasses and Filter Driers
Typical 38AUD Systems
In some applications, depending on space and convenience
requirements, it may be desirable to install 2 filter driers and
sight glasses in a single circuit application. One filter drier
and sight glass may be installed at A locations (see Fig. 8) or
2 filter driers and sight glasses may be installed at B
locations (see Figs. 8 and 9).
Select the filter drier for maximum unit capacity and
minimum pressure drop. Complete the refrigerant piping
FLOW
FILTER DRIER
A LOCATION
LIQUID LINE
SOLENOID
VALVE
LIQUID LINE
SOLENOID VALVE
CIRCUIT 2
LIQUID LINE
SOLENOID VALVE
CIRCUIT 1
FLOW
C10202
FLOW
FLOW
C10072
from the indoor unit to the outdoor unit before opening
the liquid and suction lines at the outdoor unit.
Install Liquid Line Solenoid Valve —
It is recommended that a solenoid valve be placed in the
main liquid line (see Figs. 8 & 9) between the condensing
unit and the evaporator coil. Locate the solenoid valve at the
outlet end of the liquid line, near the evaporator coil
connections, with flow direction arrow pointed at the
evaporator coil. Refer to Table 9. (A liquid line solenoid
valve is required when the liquid line length exceeds 75 ft
[23 m].) This valve prevents refrigerant migration (which
causes oil dilution) to the compressor during the off cycle, at
low outdoor ambient temperatures. Wire the solenoid in
parallel with the compressor contactor coil (see Figs. 8 & 9).
This means of electrical control is referred to as solenoid
drop control.
Solenoid drop control wiring: Control the power to the
liquid line solenoid through a Solenoid Valve Relay (SVR)
in all units. Use part number HN61PC005 (field--supplied,
installed). 38AUZ unit requires one SVR; 38AUD unit
requires two relays.
38AUD unitalsorequiresaseparatecontrolpower
transformer for the liquid solenoid valve loads. Select
transformer part number according to unit power supply.
Unit PowerTransformer Part #
208/230HT01BD202
460HT01BD702
575HT01BD902
Mount the SVR (and transformer TRAN3 when used) in
unit control box. Connect per wiring schematic label on
unit or per Fig. 29 (38AUZ) or Fig. 30 (38AUD).
CapacityControlLiquidLineSolenoidValve:
Evaporator capacity staging control via direct thermostat
control of a liquid solenoid valve on the evaporator’s
second stage circuit is not possible with 38AU models. If
this installation is a retrofit for a unit that included
automatic pressure--operated unloading, check the existing
thermostat and liquid solenoid valve wiring for possible
direct thermostat control of a solenoid valve; re--wire per
Figs. 17 or 18 and 29 or 30.
Selecting an Accumulator –
Because all 38AU models use scroll compressors, an
accumulator is not required. If an accumulator is to be
added, check the accumulator manufacturer’s literature
carefully for indication of its suitability for use with
R--410A; look for minimum working pressure of 200 psig
(1380 kPa). Select the accumulator first on the basis of its
cataloged minimum capacity (tons) to ensure oil return from
the accumulator, then on tube size or holding capacity.
Make Piping Connections —
Piping connections at the 38AU unit are ball valves with
stub tube extensions. Do not open the unit service valves
until all interconnecting tube brazing has been completed.
16
The stub tube connections include1/4-in SAE service
A
fittings with Schrader valve cores (see Fig. 10). Before
making any brazed connections to the unit service valves,
remove both Schrader valve caps and cores and save for
re-installation. Connect a source for nitrogen to one of
these service fittings during tube brazing to prevent the
formation of copper oxides inside the tubes at brazed
joints.
charging. For a cylinder without a dip tube, invert the
cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R--410A) refrigerant is a blend, it is
strongly recommended that refrigerant always be removed
from the cylinder as a liquid. Admit liquid refrigerant into
the system in the discharge line. If adding refrigerant into
the suction line, use a commercial metering/expansion
device at the gauge manifold; remove liquid from the
cylinder, pass it through the metering device at the gauge
set and then pass it into the suction line as a vapor. Do not
remove Puron (R–410A) refrigerant from the cylinder as a
vapor.
Preliminary Charge —
Factory
High-Flow
ccess Port
Field Service
Access Port
(Schrader core)
Before starting the unit, charge R-410A liquid refrigerant
Service Valve
with Stem Cap
Sweat
Connection
Fig. 10 -- Typical Piping Connection Assembly
C10203
into the high side of each 38AU circuit through the liquid
service valve(s). The amount of refrigerant added must be
at least 80% of the operating charge listed in Tables 5 or 6
for LINEAR line length LESS the factory charge quantity
(if factory shipping charge has not been removed). See
38AU
example below.
When connecting the field tubing to the 38AU service
valves, wrap the valves in wet rags to prevent overheating
Pressure-test all joints from outdoor unit connections over
to the evaporator coil, using nitrogen as pressure and with
soap-and-bubbles.
Allow high and low side pressures to equalize. If pressures
do not equalize readily, charge R-410A vapor (using special service manifold with expansion device) into the suction line service port for the low side of system to assure
charge in the evaporator. Refer to GTAC II, Module 5,
Charging, Recover, Recycling, and Reclamation for liquid
When pressure-testing is completed, remove the nitrogen
charging procedures.
source at the outdoor unit service valves and re-install the
two Schrader valve cores. Torque the cores to 2-3 in-lbs
(23-34 N-cm).
Evacuation/Dehydration —
Evacuate and dehydrate the connected refrigeration
system(s) (excluding the 38AU unit) to 500 microns using
a two-stage vacuum pump attached to the service ports
outside the 38AU service valves, following description in
GTAC II, Module 4, System Dehydration.
!
WARNING
Example:
38AUD*25 (RTPF)
60-ft (18.3 m) linear line length
Equivalent line length 90-ft (27.4 m)
Liquid Lift: 20-ft (6.1 m)
Select line sizes from Table 6 (38AUD):
1
Liquid
Suction 1-
/2in
1
/8in.
Charge
Circuit 1: 23.0 lbs (at 75-ft linear length)
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
R
Puron
(R--410A) refrigerant systems operate at
higher pressure than standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
This unit is designed for use with Puron (R--410A)
refrigerant. Do not use any other refrigerant in this
system.
Puron (R--410A) refrigerant is provided in pink (rose)
colored cylinders. These cylinders are available with and
without dip tubes; cylinders with dip tubes will have a
label indicating this feature. For a cylinder with a dip
tube, place the cylinder in the upright position (access
valve at the top) when removing liquid refrigerant for
Circuit 2: 17.6 -- 15 = 2.6 lbs
For linear line lengths longer than 125 ft (38 m), contact
your local Carrier representative for system charge value.
Step 6 — Install Accessories
Accessories requiring modifications to unit wiring should
be completed now. These accessories may include Winter
Start controls and Low Ambient controls. Refer to the
instructions shipped with the accessory.
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.