Carrier 38AQS008 User Manual

Page 1
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS .................1
INSTALLATION ............................1-9
Step 1 — Complete Pre-Installation Checks ..1
• UNCRATE UNIT
• CONSIDER SYSTEM REQUIREMENTS
Step 2 — Rig and Mount the Unit ............2
• RIGGING
• MOUNTING
• COMPRESSOR MOUNTING
Step 3 — Complete Refrigerant Piping
Connections .............................2
• SIZE REFRIGERANT LINES
• FILTER DRIER AND MOISTURE INDICATOR
• LIQUID LINE SOLENOID VALVE
• SAFETY RELIEF
• SUCTION PIPING AT INDOOR COIL AND TXV SENSING BULB LOCATION
Step 4 — Make Electrical Connections .......3
• FIELD POWER SUPPLY
• ACCESSORY ELECTRIC HEAT
• FIELD CONTROL WIRING
START-UP ...............................10,11
Preliminary Checks ........................10
Evacuate and Dehydrate ...................10
Refrigerant Charge ........................ 10
Refrigerant Service Ports ..................10
Sequence of Operation ....................10
Checking Cooling and Heating Control
Operation ...............................11
Malfunction ...............................11
SERVICE .................................11-13
Cleaning ..................................11
Lubrication ................................11
Outdoor-Fan Adjustment ...................11
Compressor Removal ......................11
Cooling Mode Operation ...................12
Heating Mode Operation ...................12
TROUBLESHOOTING CHART ..............14,15
START-UP CHECKLIST ................CL-1,CL-2
38AQS008
Air-Cooled Split System Heat Pump
50/60 Hz
Before installing or servicing system, always turn off main power to system. There may be more than one dis­connect switch. Electrical shock can cause personal injury.
INSTALLATION
The 38AQS008 unit uses a semi-hermetic compressor. See
Tables 1A and 1B for physical data.
The 38AQS008 is approved by Carrier for use only with
40RMQ008 fan cooling units. Use only approved far coils.
The 38AQS008 (60 Hz) is Underwriters’Laboratories (UL) and Canadian Underwriters’ Laboratories (CUL) approved for use with the 40RMQ008 fan coil only.
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT (See Fig. 1) — Remove unit packaging except for the top skid assembly and wood bumpers, which should be left in place until after unit is rigged into place.
INSPECT SHIPMENT — File claim with shipping com­pany if shipment is damaged or incomplete.
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install or service air-conditioning equipment.
When working on air-conditioningequipment,observepre­cautions in literature and on tags and labels attached to unit.
Follow all safety codes. Wearsafety glasses and work gloves. Use quenching cloth for brazing operations. Have fire ex­tinguisher available. Read these instructions thoroughly.Con­sult local building codes and National Electrical Code U.S.A. (NEC) for special installation requirements.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5a 5 a
PC 111 Catalog No. 533-887 Printed in U.S.A. Form 38AQS-4SI Pg 1 6-95 Replaces: 38AQS-3SI
Fig. 1 — 38AQS008 Unit
Page 2
Table 1A — Physical Data (English)
Table 1B — Physical Data (SI)
UNIT 38AQS008 60 Hz 50 Hz
OPERATING WEIGHT (lb)
Aluminum Coils (Standard) 540 594 Copper Coils (Optional) 608 662
RIGGING WEIGHT (lb)
Aluminum Coils (Standard) 590 644
Copper Coils (Optional) 658 712 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic
Quantity...Type 1...06DA818 1...06DA824
Quantity Cylinders 46
Speed (rpm) 1750 1460
Oil Charge (oz) (ea) 88 128 OUTDOOR FAN Propeller; Direct Drive
Quantity...rpm 1...1100 1...960
Diameter (in.) 26 26
Motor Hp (NEMA)
Nominal Airflow (cfm) 6500 6100 OUTDOOR COIL Enhanced Copper Tubes,
Face Area (sq ft) 18.0
Storage Capacity (lb)† 16.56
Fins/in. 17.0
Rows (No.) 2 CONNECTIONS (Sweat)
Suction (in.) 1
Liquid (in.) CONTROLS
Pressurestat Settings (psig)
High Cutout 426 7
Cut-in 320 20
Low Cutout 7 3
Cut-in 22 5
Defrost Thermostat
Initiate Defrost (F) 28 Terminates Defrost (F) 65
NEMA — National Electrical Manufacturing Association (U.S.A.)
*Unit is factory supplied with holding charge only.
†Storage capacity of coil with coil 80% full of liquid R-22 at 120 F.
LEGEND
3
4
Aluminum Lanced Fins
1
3
1
8
1
2
UNIT 38AQS008 60 Hz 50 Hz
OPERATING WEIGHT (kg)
Aluminum Coils (Standard) 245 270 Copper Coils (Optional) 276 299
RIGGING WEIGHT (kg)
Aluminum Coils (Standard) 268 292
Copper Coils (Optional) 298 323 REFRIGERANT* R-22 COMPRESSOR Reciprocating. Semi-Hermetic
Quantity...Type 1...06DA818 1...06DA824
Quantity Cylinders 46
Speed (r/s) 29.2 24.2
Oil Charge (L) (ea) 2.60 3.78 OUTDOOR FAN Propeller; Direct Drive
Quantity...r/s 1...18.3 1...16.0
Diameter (mm) 660 660
Motor Hp (NEMA)
Nominal Airflow (L/s) 3070 2900 OUTDOOR COIL Enhanced Copper Tubes,
Face Area (m
Storage Capacity (kg)† 7.5
Fins/m 669
Rows (No.) 2 CONNECTIONS (Sweat)**
Suction (in.) 1
Liquid (in.) CONTROLS
Pressurestat Settings (kPa)
High Cutout 2937 48
Low Cutout 48 20
Defrost Thermostat
Initiate Defrost (C) −2.2 Terminates Defrost (C) 18.3
NEMA — National Electrical Manufacturing Association (U.S.A.)
*Unit is factory supplied with holding charge only.
†Storage capacity of coil with coil 80% full of liquid R-22 at 49 C.
**All pipe sizes are OD inches; equivalent sizes in millimeters follow:
2
) 1.67
Cut-in 2206 138
Cut-in 151 34
LEGEND
in. mm
1
11⁄
2
8
12.7
28.6
3
4
Aluminum Lanced Fins
1
3
1
8
1
2
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and NEC (U.S.A.) for spe­cial installation requirements.
• Allow sufficient space for airflow clearance, wiring, re­frigerant piping, and servicing unit. See Fig. 2.
• Locate unit so that outdoor unit airflow is unrestricted on all sides and above. Refer to Fig. 2.
• Unit may be mounted on a level pad directly on base rails or mounted on raised pads at support points. See Fig. 2 for weight distribution based on recommended support points.
• Provide for condensate drainage and defrost water dis­posal beneath unit.
• Areas with high snowfall may need elevated mounting for adequate airflow.
NOTE: If vibration isolators are required for a particular in­stallation, use corner weight information in Fig. 2 to make proper selection.
Step 2 — Rig and Mount the Unit
Be sure unit panels are securely in place prior to rigging.
RIGGING — These units are designed for overhead rig­ging. Refer to rigging label for preferred rigging method. Spreader bars are not required if top crating is left on unit. All panels must be in place when rigging. (See Fig. 3.) As
further protection for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal plane is not less than 45 degrees. Raise and set unit down carefully.
If it is necessary to roll unit into position, mount unit on rails, using a minimum of 3 rollers. Apply force to rails, not unit. If unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to unit.
Raise from above to lift unit from rails or pad when unit is in final position.
After unit is in position, remove all shipping wrapping and top crating.
MOUNTING — The unit must be elevated to ensure drain­age from basepan during sub-freezing conditions and to pre­vent or limit blockage of outdoor coil during snowfall. Con­sideration should be given to specific geographical areas when determining height of unit elevation.
COMPRESSOR MOUNTING — As shipped, compressors are held down by 4 bolts. After unit is installed, loosen each bolt until the snubber washer can be moved with finger pres­sure. See Fig. 4.
Step 3 — Complete Refrigerant Piping Connec­tions —
uid connection is sweat with plastic cap. Refer to Table2 for the proper line sizes. Follow standard piping practices.
Suction connection is sweat with plastic cap; liq-
2
Page 3
Table 2 — Refrigerant Piping Sizes
LINEAR LENGTH OF PIPING — ft (m)
0-25
UNIT
38AQS
008
L—Liquid Line OD — Outside Diameter S—Suction Line
NOTES:
1. Pipe sizes are based on a 2° F (1° C) loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length shown for each column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation instructions.
4. Line size conversion to mm is:
(0-7.6)
LSLSLSLS
1
⁄211⁄
in. mm
1
2
5
8
3
4
11⁄
8
13⁄
8
8
25-50
(7.6-15.2)
Line Size (in. OD)
5
⁄811⁄
8
LEGEND
12.7
15.9 19
28.6
34.9
50-75
(15.2-22.9)
5
8
11⁄
8
75-100
(22.9-30.5)
5
8
SIZE REFRIGERANT LINES — Consider length of piping required between 38AQS unit and 40RMQ unit, amount of liquid lift, and compressor oil return. See Table 3 and also refer to Part 3 of Carrier System Design Manual for design details and line sizing. Refer to 40RMQ installation instruc­tions for additional information.
Table 3 — Liquid Line Data
MAX
ALLOWABLE
UNIT
38AQS
008 75 22.9 65 19.8 7 48 2 1
1. The liquid lift in cooling mode is based on 80/67 F (22.7/19.4 C) (db/wb [dry bulb/wet bulb]) entering indoor-air temperature and a 95 F (35 C) outdoor-air temperature, with R-22 refrigerant, at an indoor airflow of 3000 cfm (1416 L/s).
2. The liquid lift in heating mode is based on 70/60 F (21.1/15.6 C) (db/wb) entering indoor-air temperature and a 47/43 F (8.3/6.1 C) (db/wb) outdoor-air temperature, with R-22 refrigerant, at an in­door airflow of 3000 cfm (1416 L/s).
LIQUID LIFT
Heating Cooling
ft m ft m psi kPa F C
Max Allowable Pressure Drop
LIQUID LINE
Max Allowable
Temp Loss
FILTER DRIER AND MOISTURE INDICATOR — See Fig. 5. The filter drier is factory supplied and field-installed in the liquid line. Moisture indicator is field-supplied and should be installed just after liquid line shutoff valve. Do not use a receiver; there is none provided with unit and one should not be used.
NOTE: Unit is shipped with R-22 holding charge. System pressure must be relieved before removing caps. Recover re­frigerant prior to brazing.
Pass nitrogen or other inert gas through piping while braz-
ing to prevent formation of copper oxide. LIQUID LINE SOLENOID VALVE —A field supplied liq-
uid line solenoid valve (LLSV) is recommended when pip­ing system length exceeds 75 ft (23 m). The LLSV must be of the biflow type, suited for use in heat pump systems.
11⁄
NOTE: Carrier recommends part number EF23JS214 (Sporlan model CB14S2,
5
⁄8-in. ODF/7⁄8-in. ODM) available from the Replacement Components Division of Carrier Corporation. This solenoid requires field supplied Sporlan MKC-2 coils.
Wire the solenoid in parallel with the compressor con-
tactor coil.
8
Install the LLSV near the outdoor unit. The flow arrow
must be pointed toward the outdoor unit. SAFETY RELIEF — A fusible plug is located on top of the
accumulator. See Fig. 6. Note that all safety relief compo­nents are factory installed. Do not cap fusible plug. If local code requires additional safety device(s), install as directed.
SUCTION PIPING AT INDOOR COIL AND TXV SENS­ING BULB LOCATION — To achieve good mixing of re­frigerant leaving the indoor coil suction header for proper sensing by the thermostatic expansion valve (TXV) bulb (see Fig. 7):
1. A minimum of two 90-degree elbows should be installed
upstream of the TXV bulb location.
2. The TXV bulb should be located on a vertical riser where
possible. If a horizontal location is necessary, secure the bulb at approximately the 4 o’clock position or the 8 o’clock position. See Fig. 7.
3. Enter suction pipe sizing charts in the Carrier System De-
sign Manual at design tons and equivalent length for 2° F (1° C) loss. If the reading falls between 2 sizes on the chart, choose the smaller pipe size.
4. Make sure that the piping system has no inherent oil traps,
and the piping layout will not allow oil to migrate into an idle evaporator coil.
5. Complete refrigerant piping from indoor coil to outdoor
coil before opening liquid and suction lines at the 38AQS unit. See Tables 1A, 1B, and 2 for piping selection data.
Step 4 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken elec­trical ground to minimize the possibility of personal in­jury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for elec­trical ground when installed in accordance with NEC ANSI (American National Standards Institute, U.S.A.)/ NFPA (National Fire Protection Association, U.S.A.) 70 and local electrical codes. Failure to follow this warn­ing could result in the installer being liable for personal injury of others.
FIELD POWER SUPPLY — All units except 208/230-v (60 Hz) units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v orange wire on the trans­former and connecting it to the 208-v red wire from the trans­former. The end of the orange wire must then be insulated.
Refer to unit label diagram for additional information. Short wire leads (pigtails) are provided for field wire connections. Use factory-supplied splices or UL approved copper/ aluminum connector.
When installing units, provide a disconnect per NEC (U.S.A.).
3399
Page 4
UNIT
38AQS008
60 Hz
50 Hz
UNIT
W/ALUMINUM COIL
UNIT
W/COPPER COIL
WEIGHT CHART (WITH ALUMINUM COIL) WEIGHT CHART (WITH COPPER COIL)
Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z
Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
1
⁄2⬙
1-8
[508.0]
1-6
[457.2]
1-5
[431.8]
1-7
[482.6]
1-9 [546.0]
1-7 [495.3]
1-43⁄4⬙
540 245 132 60 100 45 133 60 175 80 608 276 160 73 117 53 142 64 189 86
[425]
1
⁄2⬙
1-63⁄4⬙
594 270 114 52 114 52 183 83 183 83 662 299 142 64 131 59 192 87 197 89
[476.3]
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity. See chart for dimensions.
3. Direction of airflow.
4. Minimum clearance (local codes or jurisdiction may prevail): a. Bottom to combustible surfaces, 0 in. (0 mm) b. Outdoor coil, for proper airflow, 36 in. (914 mm) one side, 12 in.
(305 mm) the other. The side getting the greater clearance is optional. c. Overhead, 60 in. (1524 mm) to assure proper outdoor-fan operation. d. Between units, control box side, 42 in. (1067 mm) per National
Electrical Code (NEC, U.S.A.).
e. Between unit and ungrounded surfaces, control box side, 36 in.
(914 mm) per NEC (U.S.A.).
f. Between unit and block or concrete walls and other grounded surfaces,
control box side, 42 in. (1067 mm) per NEC (U.S.A.).
5. With the exception of the clearance for the outdoor coil as stated in note 4b, a removable fence or barricade requires no clearance.
6. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material.
7. Vertical center of gravity is approximately 40% of total unit height.
Fig. 2 — Dimensions
ELECTRICAL CONNECTIONS
CONNECTION SIZES
3
AA 1
⁄8⬙ Dia. [35] Field Power Supply Hole
BB 2Dia. [51] Power Supply Knock-Out
1
CC 2 DD
⁄2⬙ Dia. [64] Power Supply Knock-Out
7
⁄8⬙ Dia. [22] Field Control Wiring Hole
SERVICE VALVE CONNECTIONS
UNIT SUCTION LIQUID
38AQS008 1
1
⁄8⬙ [28.6]
1
⁄2⬙ [12.7]
4
Page 5
MAX WEIGHT
UNIT
38AQS008
60 Hz 590 268 658 298 50 Hz 644 292 712 323
w/Al Coil
Lb Kg Lb Kg in. mm in. mm in. mm
w/Cu
Fig. 3 — Rigging Label
Coil
ABC
45.0 1143 38.5 989 43.5 1105
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Table 4). Voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 4, Note 2, to determine the percent voltage imbalance.
Operation on improper line voltage or excessive phase im­balance constitutes abuse and may cause damage to elec­trical components. Such operation would invalidate any ap­plicable Carrier warranty.
ACCESSORY ELECTRIC HEAT — If the system is to be equipped with an accessory electric heater, refer to the 40RMQ008 installation instructions and Tables 5A and 5B.
FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation in­structions included with the accessory.Locate thermostat as­sembly on a solid wall in the conditioned space to sense av­erage temperature in accordance with thermostat installation instructions. Carrier-approved thermostat is Part Number HH07AT-171. Subbase is HH93AZ-188.
Route thermostat cable or equivalent single leads of col­ored wire from subbase terminals to low-voltage connec­tions on unit (shown in Fig. 9) as described in Steps 1 through 3 below.
1. Connect thermostat wires to screw terminals of low-
voltage connection board.
2. Pass the control wires through the hole provided in the
corner post. (See Fig. 10.)
3. Feed wire through the raceway built into the corner post
to the 24-v barriers located on the left side of the control box. The raceway provides the required clearance be­tween the high- and low-voltage wiring.
Fig. 4 — Compressor Mounting
All field wiring must comply with NEC (U.S.A.) and lo-
cal requirements. Install field wiring as follows:
1. Install conduit through side panel openings.
2. Install power lines to connections as shown in Fig. 8. Wrap connections with electrical tape.
NOTE: 39 VA is available for field-installed accessories. Control power requirement for heat pump outdoor unit is 36 VA(sealed). The factory-supplied control transformer is 75 VA.
NOTE: For wire runs, use the following insulated wire:
LENGTH
Ft M AWG sq mm
0-50 0-15.2 35 18 0.82
50-75 15.2-22.9 35 16 1.30
Over 75 Over 22.9 35 14 2.08
LEGEND
AWG — American Wire Gage
INSULATION
RATING (C)
SIZE
All wire larger than no. 18 AWG (American Wire Gage) cannot be directly connected to the thermostat and will re­quire a junction box and splice at the thermostat.
5
Page 6
LEGEND
NEC — National Electrical Code TXV — Thermostatic Expansion Valve
*Accessory item. †Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Re­fer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor. A biflow type solenoid valve is required.
5. Filter drier must be of the biflow type, suitable for heat pump duty.
6. Internal factory-supplied TXV and bypass check valve not shown.
Fig.5—Typical Piping Diagram, 38AQS/40RMQ
6
Page 7
Table 4 — Electrical Data
UNIT
38AQS
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps MCA Minimum Circuit Amps NEC National Electrical Code (U.S.A.) OFM Outdoor Fan Motor RLA Rated Load Amps
(60 Hz Only) (60 Hz Only)
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
2. Unbalanced 3-Phase Supply Voltage
= 100 x
NOMINAL VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177
008
nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the percent voltage imbalance.
460-3-60 414 508 15.7 80 1.4 21.0 25 25 89 220-3-50 198 242 39.7 198 3.1 52.7 70 55 205 400-3-50 360 440 19.9 99 1.4 26.3 35 30 106
LEGEND
max voltage deviation from average voltage
average voltage
VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY MINIMUM DISCONNECT
Min Max RLA LRA FLA MCA
Use the following formula to determine
MAX FUSE OR
HACR BRKR AMPS
Example: Supply voltage is 460-3-60.
(AB) 457 452=5v (BC) 464 457=7v (AC) 457 455=2v
Maximum deviation is 7 v. Determine percent voltage imbalance
% Voltage Imbalance = 100
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
457
= 1.53%
FLA LRA
452 + 464 + 455
1371
=
= 457
7
3
3
7
Page 8
Table 5A — Accessory Electric Heater Data (60 Hz)
UNIT
40RMQ
008
MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps)
*Sizes shown are for single-point connection of electric heat acces-
sory and air handler.
HEATER RATING
VOLTAGE
240 .694 .751 .918 1 ———— — 480 .694 .840 .918 1 575 .915 1 1.089
NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.412 = Btuh.
HEATER
PART NO.
CAELHEAT001A00 240-3-60 CAELHEAT002A00 480-3-60 6.0 12.3 15 CAELHEAT003A00 575-3-60 5.0 11.9 15 CAELHEAT004A00 240-3-60 CAELHEAT005A00 480-3-60 12.0 19.8 25 CAELHEAT006A00 575-3-60 10.0 18.1 25 CAELHEAT007A00 240-3-60 CAELHEAT008A00 480-3-60 18.0 27.4 40 CAELHEAT009A00 575-3-60 15.1 24.4 35 CAELHEAT010A00 240-3-60 CAELHEAT011A00 480-3-60 30.1 42.4 60 CAELHEAT012A00 575-3-60 25.1 67.0 50 CAELHEAT013A00 240-3-60 CAELHEAT014A00 480-3-60 42.1 57.4 80 CAELHEAT015A00 575-3-60 35.1 49.5 70
LEGEND
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
V-PH-Hz NOMINAL kW
HEATER
AMPS
12.0 25.6 30
5
24.1 40.7 50
10
36.0 55.7 80
15
60.1 85.8 125
25
84.0 115.8 175
35
NOTES:
1. MCA and MOCP values apply to both standard andalternate factory­supplied motors.
2. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine heater capacity (kW) at unit nameplate voltage, multi­ply 240-v, 480-v, or 575-v capacity by multipliers found in table below.
MCA* MOCP*
UNIT
40RMQ
008
MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps)
*Sizes shown are for single-point connection of electric heat acces-
sory and air handler.
HEATER RATING
VOLTAGE
230 .915 1.0 1.084 400 0.903 1.0 1.076
HEATER
PART NO.
CAELHEAT002A00 400-3-50 3.47 5.0 11.1 15 CAELHEAT001A00 230-3-50 4.59 11.5 25.0 30 CAELHEAT005A00 400-3-50 6.94 10.0 17.3 25 CAELHEAT004A00 230-3-50 9.18 23.1 39.5 50 CAELHEAT008A00 400-3-50 10.42 15.0 23.6 30 CAELHEAT007A00 230-3-50 13.78 34.6 53.9 80 CAELHEAT011A00 400-3-50 17.36 25.1 36.2 50 CAELHEAT010A00 230-3-50 22.96 57.6 82.6 110 CAELHEAT014A00 400-3-50 24.31 35.1 48.7 70 CAELHEAT013A00 230-3-50 32.14 80.7 111.5 175 CAELHEAT017A00 400-3-50 6.94 10.0 23.0 30 CAELHEAT016A00 230-3-50 9.18 23.1 39.5 50 CAELHEAT020A00 400-3-50 13.89 20.0 35.5 50 CAELHEAT019A00 230-3-50 18.37 46.1 79.9 110 CAELHEAT023A00 400-3-50 20.83 30.1 48.1 70 CAELHEAT022A00 230-3-50 27.55 69.2 108.7 150
LEGEND
220 230 240 380 400 415
Table 5B — Accessory Electric Heater Data (50 Hz)
V-PH-Hz NOMINAL kW
ACTUAL HEATER VOLTAGE
HEATER
AMPS
NOTES:
1. MCA and MOCP values apply to both standard andalternate factory­supplied motors.
2. Electrical resistance heaters are rated at 230 v or 400 v. To de­termine heater capacity (kW) at unit nameplate voltage, multiply 230-v or 400-v capacity by multipliers found in table below.
MCA* MOCP*
898 8
Page 9
CORNER POST
RACEWAY THERMOSTAT
FIELD CONNECTION
POWER WIRING CONNECTIONS
Fig. 6 — Fusible Plug Locations
LEGEND
TXV —
NOTE: The 8 o’clock position is shown above.
Thermostatic Expansion Valve
Fig. 7 — TXV Sensing Bulb Location
LEGEND
Cooling
C—
Heating
H—
Heater Relay
HR —
Indoor Fan Contactor
IFC —
Fig. 9 — Control Wiring Connections
LLSV —
SUPL — TB
Fig. 10 — Field Control Wiring Raceway
Liquid Line Solenoid Val ve Supplemental Terminal Block
LEGEND
C— NEC —
Contactor National Electrical Code (U.S.A.) Field Wiring Factory Wiring
Splice Connection (Factory Supplied)
Fig. 8 — 38AQS008 Power Wiring Connections
9
2
801
Page 10
START-UP
Preliminary Checks
1. Check that all internal wiring connections are tight and that all barriers, covers, and panels are in place.
2. Field electrical power source must agree with unit name­plate rating.
3. Ensure all service valves are open. Ensure all compressor service valves are backseated.
4. Verify that compressor holddown bolts have been loos­ened and that flat/snubber washers can be rotated by fin­ger pressure (snug, but not tight).
5. Verify compressor crankcase heater is securely in place. Crankcase heater must operate for at least 24 hours be­fore start-up.
6. Note that compressor oil level is visible in the sight glass.
7. Check for leaks in refrigerant system by using soap bubbles and/or electronic leak detector.
8. Check voltage imbalance as shown in Table 4, Note 2.
9. Check that both outdoor and indoor units are properly mounted in accordance with installation instructions and applicable codes.
Evacuate and Dehydrate — Evacuate and dehydrate
entire refrigerant system by use of the methods described in Carrier GTAC II, Module 4, System Dehydration.
Refrigerant Charge — Refer to Carrier GTACII, Mod-
ule 5, Charging Recovery, Recycling, and Reclamation. NOTE: Use of a Carrier Totalclaimrefrigeration recovery
unit is highly recommended when recovering refrigerant.
Unit panels must be in place when unit is operating dur-
ing charging procedure.
Unit is shipped with holding charge only. Weigh in 15 lb
(7 kg) of R-22 to start unit.
Fig. 11 — Cooling Charging Chart — 38AQS008
Do not reuse drained oil or use any oil that has been ex-
posed to atmosphere. Procedures for adding or removing oil
are given in Carrier’s Refrigerant Service Techniquesmanual.
If oil is added, run unit for additional 10 minutes. Stop unit and check oil level. If level is still low, add oil only after determining that piping system is designed for proper oil re­turn and that system is not leaking oil.
Refrigerant Service Ports — Each unit system has 3
service ports: one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure caps on the ports are tight.
CHARGE COOLING — Use Cooling Charging Chart (see Fig. 11). Varyrefrigerant until the conditions of the chart are met. Note that charging chart is different from the type nor­mally used. Chart is based on charging the units to the cor­rect subcooling for the various operating conditions. Accu­rate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the liquid line service valve. Mount the temperature sensing device on the liquid line, close to the liquid line service valve, and in­sulate it so that outdoor ambient temperature does not affect the reading. Indoor airflow must be within the normal op­erating range of the unit.
Operate unit a minimum of 15 minutes. Ensure pressure and temperature readings have stabilized. Plot liquid pres­sure and temperature on chart and add or reduce charge to meet curve. Adjust charge to conform with charging chart, using liquid pressure and temperature to read chart.
OIL CHARGE (Tables 1A and 1B) — Allow unit to run for about 20 minutes. Stop unit and check compressor oil level. Add oil only if necessary to bring oil into view in sight glass.
Use only Carrier-approved compressor oil.
Approved oils are:
Suniso 3GS and WF32-150
Sequence of Operation — When power is supplied
to unit, the transformer (TRAN) is energized. The crankcase heater is also energized.
COOLING — With the thermostat subbase in the cooling position, and when the space temperature comes within 2° F (1° C) of the cooling set point, the thermostat makes circuit R-O. This energizes the reversing valve solenoid (RVS) and places the unit in standby condition for cooling.
As the space temperature continues to rise, the second stage of the thermostat makes, closing circuit R-Y. When com­pressor time delay (5 ± 2 minutes) is completed, a circuit is made to contactor (C ), starting the compressor (COMP) and outdoor-fan motor (OFM). Circuit R-G is made at the same time, energizing the indoor-fan contactor (IFC) and starting the indoor-fan motor (IFM) after one-second delay.
When the thermostat is satisfied, contacts open, deener­gizing C. The COMP, IFM, and OFM stop.
HEATING — On a call for heat, thermostat makes circuits R-Y and R-G. When compressor time delay (5 ± 2 minutes) is completed, a circuit is made to C, starting COMPand OFM. Circuit R-G also energizes IFC and starts IFM after a 1-second delay.
10
Page 11
Should room temperature continue to fall, circuit R-W is made through second-stage thermostat bulb. If optional elec­tric heat package is used, a relay is energized, bringing on supplemental electric heat. When thermostat is satisfied, con­tacts open, deenergizing contactor and relay; motors and heat­ers deenergize.
DEFROST — Defrost board (DB) is a time and temperature control, which includes a field-selectable time period be­tween checks for frost (30, 50, and 90 minutes). Electronic timer and defrost cycle start only when contactor is ener­gized and defrost thermostat (DFT) is closed (below 28 F [−2.2 C]).
Defrost mode is identical to Cooling mode, except outdoor­fan motor (OFM) stops and a bank of supplemental electric heat turns on to warm air supplying the conditioned space. Defrost mode is terminated when the DFT reaches 65 F (18.3 C).
Checking Cooling and Heating Control Opera­tion —
tion as follows:
1. Place room thermostat SYSTEM switch in an OFF po-
2. Place SYSTEM switch in COOLposition and FANswitch
3. Place system switch in HEAT position. Set control above
4. When using an automatic changeover room thermostat,
Start and check the unit for proper control opera-
sition. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when F ANswitch is placed in AUTO. position.
in AUTO. position. Set control below room temperature. Observe that compressor,outdoor fan, and indoor fan mo­tors start. Observe that cooling cycle shuts down when control setting is satisfied.
room temperature. Observe that compressor, outdoor fan, indoor fan motor, and electric heaters (if equipped) start. Observe that heating cycle shuts down when control set­ting is satisfied.
place both SYSTEM and FAN switches in AUTO posi­tions. Observe that unit operates in Cooling mode when temperature control is set to ‘‘call for Cooling’’ (below room temperature), and unit operates in Heating mode when temperature control is set to ‘ ‘callfor heating’ ’(above room temperature).
Cleaning — Inspect unit interior at the beginning of each
cooling season and as operating conditions require. OUTDOOR COIL — Inspect coil monthly. Clean outdoor
coil annually and as required by location or outdoor-air conditions.
Clean coil as follows:
1. Turn off unit power.
2. Remove and save top panel screws on outdoor unit.
3. Remove outdoor coil corner post. See Fig. 12. To hold top panel open, place coil corner post between top panel and side panel. See Fig. 13.
4. Remove bracket holding coil sections together at return end of outdoor coil. Carefully separate the outer coil sec­tion 3 to 4 in. from the inner coil section. See Fig. 14.
5. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiffbrush in the normal manner.
6. Reposition the outer coil section and secure the sections together. Remove the coil corner post from between the top panel and side panel. Install the coil corner post and replace all screws removed in Step 2.
Lubrication
COMPRESSORS — Compressor has its own oil supply.Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. See Start-Up, Oil Charge section.
FAN MOTOR BEARINGS — Fan motor bearings are of the permanently lubricated type. No further lubrication is required.
Outdoor-Fan Adjustment (Fig. 15)
1. Shut off unit power supply.
2. Remove outdoor-fan assembly (grille, motor, motor cover, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 15.
5. Tighten setscrews.
6. Replace outdoor-fan assembly.
Malfunction — The high-pressure switch, loss-of-
charge switch, and compressor overtemperature safety are located in a Cycle-LOC™ circuit that prevents heat pump operation if these safety devices are activated.
The lockout system can be reset by adjusting the thermo­stat to open the contacts (down for heating mode, up for cool­ing mode) deenergizing the Cycle-LOC circuitry. Compres­sor overcurrent protection is achieved with overload breakers which are temperature sensitive and will automatically reset.
Unit is equipped with a no-dump reversing valve circuit. When unit is in cooling mode, reversing valve remains in cooling position until a call for heating is requested by ther­mostat. When unit is in heating mode, reversing valve re­mains in heating position until there is a call for cooling.
SERVICE
When servicing unit, shut off all electrical power to unit to avoid shock hazard or injury from rotating parts.
Compressor Removal — See Tables 1A and 1B for
compressor information. Follow safety codes and wear safety glasses and work gloves.
1. Shut off power to unit. Remove unit access panel (front of unit).
2. Remove refrigerant from system using refrigerant re­moval methods described in Carrier’s Refrigrant Serv­ice Techniques manual.
3. Disconnect compressor wiring at compressor terminal box. Disconnect high-pressure switch.
4. Remove bolts from discharge service valve and suction flange.
Excessive movement of copper lines at compressor may cause higher levels of vibration when unit is restored to service.
11
Page 12
5. Remove crankcase heater from compressor base.
6. Remove compressor holddown bolts and lift compres­sor off basepan.
7. Remove compressor from unit.
8. Clean system. Add new liquid line filter drier (biflow type).
9. Install new compressor and position in unit. Connect suc­tion and discharge lines to compressor. Connect high pres­sure switch. Ensure that compressor holddown bolts are in place. Connect wiring. Install crankcase heater.
10. Evacuate and recharge unit.
11. Restore unit power.
Cooling Mode Operation — See Fig. 16.
1. Hot refrigerant gas from compressor flows through the reversing valve and is directed to the outdoor coil vapor header.
2. Once at the outdoor coil vapor header, hot refrigerant gas flows up to check valve A,which is closed. All refrig­erant is then directed to complete a path through the lower 6 coil circuits (6 passes in each circuit).
3. Refrigerant flows through from the liquid header side out­lets into the transfer header, where it flows upward.
4. Refrigerant leaves the transfer header through side con­nections in 4 locations and enters the middle coil circuits (4 coil circuits above check valve A).
5. Refrigerant leaves the 4 middle coil circuit and enters the top portion of vapor header. The refrigerant moves up to the top 2 remaining coil circuits, where it enters the sub­cooler section.
Fig. 14 — Separating Coil Sections
Fig. 12 — Cleaning Outdoor Coil
Fig. 13 — Propping Up Top Panel
Fig. 15 — Outdoor-Fan Adjustment
6. Subcooled refrigerant leaves the coil circuits through the side outlets. It passes through check valve Binto the system liquid line and then into the indoor coil.
7. Liquid refrigerant is expanded and evaporated to a low­pressure vapor in the indoor coil. Refrigerant vapor then returns to the outdoor unit through the system vapor line, where it is drawn through the reversing valve and accu­mulator and back to the compressor suction connection.
Heating Mode Operation — See Fig. 17.
1. Hot gas from compressor flows through the reversing valve and is directed to the system vapor line and indoor coil vapor header (not shown). Refrigerant is condensed and subcooled in the indoor coil and returns to the outdoor unit through the system liquid line.
2. Check valve Bis closed and all liquid refrigerant enters the liquid header.
3. Refrigerant leaves the liquid header through 12 loca­tions. It is then expanded in fixed orifice metering de­vices contained within the outlet tubes.
4. Refrigerant evaporates to low pressure vapor as it com­pletes its passage through the 12 parallel coil circuits (6 passes each).
5. Refrigerant moves from the coil circuits into the vapor header, where it is drawn through the reversing valve and accumulator and back to compressor suction connection.
12
Page 13
Fig. 16 — Cooling Mode Operation
Fig. 17 — Heating Mode Operation
13
Page 14
LEGEND
TXV — Thermostatic Expansion Valve
TROUBLESHOOTING CHART, COOLING CYCLE
14
Page 15
LEGEND
N.C. — Normally Closed
TROUBLESHOOTING CHART, HEATING CYCLE
15
Page 16
Page 17
Page 18
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
PC 111 Catalog No. 533-887 Printed in U.S.A. Form 38AQS-4SI Pg 18 801 6-95 Replaces: 38AQS-3SI
Page 19
START-UP CHECKLIST
A. Preliminary Information
OUTDOOR: MODEL NO. SERIAL NO.
INDOOR: AIR HANDLER MANUFACTURER
MODEL NO. SERIAL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE?
IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?
(Y/N)
(Y/N)
CONTROLS
ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)
ARE PROPER AIR FILTERS IN PLACE? (Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)
PIPING
IS LIQUID LINE SOLENOID VALVE LOCATED AT THE OUTDOOR UNIT AS RECOMMENDED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR COIL, INDOOR COIL, TXV (Thermostatic Expansion
Valve), SOLENOID VALVES, FILTER DRIER, REVERSING VALVE, CHECK VALVE, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)
HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED? (Y/N)
IS THE OIL LEVEL IN COMPRESSOR CRANKCASE INTO VIEW IN THE COMPRESSOR SIGHT GLASS?
(Y/N)
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB
(AB + AC + BC)/3 = AVERAGE VOLTAGE =
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
VAC VBC V
V
V
CL-1
%
Page 20
C. Start-Up
CHECK INDOOR-FAN SPEED AND RECORD.
CHECK OUTDOOR-FAN SPEED AND RECORD.
AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING OUTDOOR-AIR TEMP LEAVING OUTDOOR-AIR TEMP INDOOR ENTERING-AIR DB (dry bulb) TEMP INDOOR ENTERING-AIR WB (wet bulb) TEMP INDOOR LEAVING-AIR DB TEMP INDOOR LEAVING-AIR WB TEMP
COMPRESSOR AMPS (L1/L2/L3)
NOTES:
COOLING
HEATING
/ /
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
PC 111 Catalog No. 533-887 Printed in U.S.A. Form 38AQS-4SI Pg CL-2 801 6-95 Replaces: 38AQS-3SI
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...