Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep, quenching cloth and fire extinguisher nearby when
brazing.
• Use care in handling, rigging, and setting bulky
equipment.
• See Table 1A or 1B for physical data.
ELECTRIC SHOCK HAZARD
Open all remote disconnects before
servicing this equipment.
BEFORE INSTALLATION
Rigging —
above the unit. Use 2-in. (50 mm) OD pipe or hooks in lifting holes. Rig with 4 cables and spreader bars. All panels
must be in place when rigging. See rigging label on unit for
details concerning shipping weights, distance between lifting holes, center of gravity, and spreader bar dimensions.
See Fig. 2.
If overhead rigging is not possible, place unit on skid or
pad for rolling or dragging. When rolling, use minimum of
3 rollers. When dragging, pull the pad. Do not apply forceto the unit. When in final position, raise from above to lift
unit off pad.
Preferred method is with spreader bars from
All panels must be in place when rigging.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 3a
PC 111Catalog No. 533-820Printed in U.S.A.Form 38A-5SIPg 17-94Replaces: 38AK-3SI
and 80% full), kg
CONDENSER FANS, TypePropeller Type, Direct Driven
No. ...Diameter, mm2...7623...762
Total Airflow, L/s7,40011,200
Speed, R/s (60/50 Hz)19.0/15.819.0/15.8
CONDENSER COIL, TypeHorizontal Plate Fin
Rows...Fins/mm2...1.343...1.493...1.49
Total Face Area, sq m3.643.645.43
*See Service, Oil Charge, for Carrier-approved oil.
NOTE: Circuit breaker is in main power circuit.
17.125.738.3
2
Page 3
Placing Unit — There must be 4 ft (1220 mm) for ser-
vice on all sides of unit, and a minimum of 8 ft (2440 mm)
clear air space above unit. For multiple units, allow 8 ft
(2440 mm) separation between units for airflow and service.
Mounting Unit — When unit is in proper location, use
of mounting holes in base rails is recommended for securing
unit to supporting structure or for mounting unit on vibration isolators, if required. Fasteners for mounting unit are
field supplied. Be sure to mount unit level to ensure proper
oil return to compressors.
Compressor Mounting — As shipped, compressor
is held down by 4 bolts. After unit is installed loosen each
bolt using nut indicated in Fig. 3 until flatwasher (3⁄8in.
[9.5 mm]) can be moved with finger pressure.
Fig. 1 — 38AKS Units
NOTES:
1. Use 2 in. OD (50 mm) pipe or hooks in lifting holes.
2. Rig with 4 cables and spread with 2 ‘‘D’’ long and two ‘‘A’’ long
2 x 4’s in. (50 x 100 mm) or equal.
3. Run the rigging cables to a central suspension point so that the
angle from the horizontal is not less than 45 degrees.
pend on length of piping required between condensing unit
and evaporator. See Table 2A or 2B. It is important to consider liquid lift and compressor oil return. Refer to Part 3 of
Carrier System Design Manual for line sizing information,
and Fig. 4 for recommended piping details.
Line sizes de-
Liquid Line Solenoid Drop Control — The factory-
supplied solenoid valve must be installed at the indoor unit
(fan coil) per Fig. 5, and wired per wiring label found on
unit. The solenoid assures that system refrigerant is in the
high-pressure side (condenser and liquid line) of the system
during the off cycle. Refrigerant migration is minimized.
Factory-supplied liquid line solenoid valve connecting sizes
7
⁄8-in. (22.2 mm) ODF for inlet and7⁄8-in. (22.2 mm)
are
ODM for outlet.
Failure to properly install liquid line solenoid at the indoor unit as described, without Carrier authorization, may
VOID warranty.
Filter Drier and Moisture Indicator — Every unit
should have a filter drier and a sight glass (moisture indicator) field installed. Select the filter drier for maximum unit
capacity and minimum pressure drop. Figure 5 shows recommended locations of filter drier(s) and sight glass. Complete the refrigerant piping from the evaporator to the condenser before opening the liquid and suction lines at the
condensing unit. One filter drier may be installed at location
A in Fig. 5, or 2 filter driers may be installed at locations B.
Fig. 2 — Rigging with Spreader Bars
(Field Supplied)
3
Page 4
NOTE: All dimensions are in inches (mm).
Fig. 3 — Compressor Mounting
TXV — Thermostatic Expansion Valve
NOTES:
1. Suction line is connected to coil on same side as the entering air.
2. Lower section is first on and last off.
3. For more complete piping information, refer to Carrier System
Design Manual, Part 3.
Fig. 4 — Suction Line Piping to Unit
with 2 Section Coil Split
TXV — Thermostatic Expansion Valve
Fig. 5 — Liquid Line Solenoid Valve,
Filter Drier(s) and Sight Glass Locations
Receiver — No receiver is provided with the unit; it is
recommended that one not be used.
Piping Procedure — Do not remove run-around pipe
from suction and liquid line stubs until piping connections
are ready to be made. Pass nitrogen or other inert gasthrough
piping while brazing, to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve (TXV)
in liquid line ahead of each evaporator section. For 2-stage
cooling, the field-supplied capacity controlsolenoidusedmust
be wired to be opened by control from a 2-stage thermostat.
SUCTION PIPING AT EVAPORATOR AND TXV BULB
LOCATION (See Fig. 5) — The purpose of these recommendations is to achieve good mixing of the refrigerant leaving the evaporator suction header for proper sensing by the
TXV bulb.
1. A minimum of two 90° elbows must be installed up-
stream of the expansion valve bulb location.
2. The TXV sensing bulb should be located on a vertical
riser where possible. If a horizontal location is necessary,
secure the bulb at approximately the 4 o’clock position.
3. Size the suction line from the evaporator throughthe riser
for high velocity. Enter the suction pipe sizing charts in
the CarrierSystemDesignManual at design tons and equivalent length (for 2° F [1.1° C] loss). If reading falls between 2 sizes on chart, choose the smaller pipe size.
Suction piping for the high velocity section should be
selected for about 0.5° F (0.3° C) friction loss. If a 2° F
(1.1° C) loss is allowed for the entire suction line, 1.5° F
(0.8° C) is left for the balance of the suction line, and it should
be sized on that basis. Check that the high-velocity sizing
is adequate for oil return up the riser.
If an oil return connection at the bottom of this suction
header is supplied with an evaporator, this connection must
be teed-in ahead of first mixing elbow. When the compressor is below the evaporator, the riser at the evaporator does
not have to extend as high as the top level. After a
15-diameter riser has been provided, the suction line may
elbow down immediately.
SAFETY RELIEF — Afusible plug is located on unit liquid
line before the liquid valve.
*IMPORTANT — Requires a double suction riser, if evaporator is below condensing unit. See table below.
NOTE: Liquid and suction line sizes are OD (in.) Equivalent sizes in mm are listed below.
applicable localandnationalcodes.Install field-supplied branch
circuit fused disconnect(s) per NEC (National Electrical Code,
U.S.A.) of a type that can be locked OFF or OPEN. Disconnect(s) must be within sight from and readily accessible
from unit in compliance with NEC Article 440-14.
GENERAL WIRING NOTES
1. A crankcase heater is wired in the control circuit so it is
always operable as long as power supply disconnect is
on, even if any safety device is open or unit stop-start
switch is off. It is protected by a 5-amp circuit breaker in
control power.
2. The power circuit field supply disconnect should never be
open except when unit is being serviced or is to be down
for a prolongedperiod.Whenoperationisresumed, crankcase heater should be energized for 24 hours before startup. If unit is to be shut down for a prolonged period, it
is recommended that the suction and discharge valves be
closed to prevent an excessive accumulation of refrigerant in the compressor oil.
3. Power entry is one end only.
4. Maximum field wire sizes allowed by lugs on terminal
block are:
UNIT
38AKS
028208/230-3-60
034
044
LEGEND
AWG — American Wire Gage
kcmil — Thousand Circular Mils
*All other units use 2/0 AWG (67.4 mm
V-Ph-Hz
208/230-3-60
230-3-50
208/230-3-60
230-3-50
2
).
WIRE
SIZE*
350 kcmil
5. Terminals for field power supply are suitable for copper,
copper-clad aluminum, or aluminum conductors. Insulation must be rated 167 F (75 C) minimum.
CONDENSER FANS— The fans must rotate counterclockwise when viewed from above. If necessary, correct direction of fan rotation by interchanging any 2 powerinput wires
at disconnect switch. Affix crankcase heater decal (located
in installer’s packet) to unit disconnect switch.
Table 3 — Electrical Data
60 HZ
UNIT
38AKS
500
028
034
044
028
034
044
CSA— Canadian Standards Association
FLA— Full Load Amps
ICF— Maximum InstantaneousCurrentFlow duringstarting(the point
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps (complies with National
1. Main Power — Bring wires from the fused disconnect
switch through hole in bottom rail of unit to control box
12
(Fig. 6 and 7) and connect terminals,, and
line side of terminal block TB1 (see Fig. 8 and 9A
13
11
or 9B). To comply with NECArticle 440-14, the disconnect must be located within sight from and readily accessible from unit.
2. 24-v ControlPower—Unitshavesinglepointpower connections. Control circuit is directly connected internally
to unit. Maximum 24-v control circuit is 3 amps.
NOTE: Wire runs use the following insulated wire:
LENGTH
0-50180.82
50-75161.30
Over 75142.08
AWG — American Wire Gage
*35 C minimum.
INSULATED WIRE SIZE*
AWGmm
2
3. Control Circuit Interlock — An airflow switch may be
installed in the indoor air handler to prevent unit from
running when indoor air is not flowing. This switch (no.
HR81JE001) is available from Service Parts Center, or
equivalent can be field supplied. This should be electrically interlocked in the control circuit, between thermo-
2
stat TC1 (stage 1, cooling) and terminalon TB3.
Y1
See Fig. 8 for typical field wiring. This is in the 24-v circuit. Wires must be run in conduit with ground wire.
4. Transformer Connections — See unit wiring label diagram, notes 1 and 2, located behind compressor compartment end access door.
IMPORTANT: Ensure power to the crankcase heater
is always on (except when servicing the unit). If circuit breakerinsideunitshutsdown the compressor,crankcase heater remains on.
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never
operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine
the percent voltage imbalance:
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v
AC = 238 v
Average Voltage =
243 + 236 + 238
3
= 239 volts
Determine maximum deviation from average voltage:
(AB) 243 − 239=4v
(BC) 239 − 236=3v
(AC) 239 − 238=1v
Maximum deviation is 4 v. Determine percent voltage
imbalance:
% Voltage Imbalance = 100 x
4
239
= 1.7%
This amount of phase imbalance is satisfactory as it is be-
low the maximum allowable 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply voltage phase imbalance is more than 2%.
7
Page 8
LEGEND
NEC — National Electrical Code
VAV — Variable Air Volume
NOTES:
1. There must beminimum(2440mm) 8 ft. clear air spaceabove
unit.
2. The approximate operating weight of the unit is:
3. A ‘‘C’’in the model number indicates unit has factory-installed
copper coil.
WT
(Lb)WT(Kg)
Fig. 6 — Dimensional Drawing, 38AKS028,034
8
Page 9
LEGEND
NEC — National Electrical Code
NOTES:
1. There must beminimum(2440mm) 8 ft. clear air spaceabove
unit.
2. The approximate operating weight of the unit is:
50 HZ AND 60 HZ
UNIT
38AKS04424371106
38AKS044C27451246
3. A ‘‘C’’in the model number indicates unit has factory-installed
copper coil.
WT
(Lb)WT(Kg)
Fig. 7 — Dimensional Drawing, 38AKS044
9
Page 10
modifications or additions must be in compliance
NOTES:
1.Factorywiring in accordancewith the NEC.Any field
with all applicable codes.
ing of 180 va pilot duty plus capacity required for
2. All field interlock contacts must have minimum rat-
field-installed equipment. All field interlock con-
tacts inthe24-vcontrol circuit must have minimum
rating of 70 va pilot duty plus capacity required for
field-installed equipment.
3.Forinternal unit wiring,referencewiring bookorunit
wiring label diagram. TB2 is 115-1-60, TB3 is
24-1-60.
38AKS unit control box: LLS1, LLS2, field control
4. The following components are not located in the
thermostat, AFS, alarm shut-off switch, and alarm
or light.
Fig.8—Typical Wiring Schematic
LEGEND
AFS— Airflow Switch
CB— Circuit Breaker
EQUIP — Equipment
FU— Fuse
GND— Ground
LLS1— Liquid Line Solenoid for
Solenoid Drop Control
Capacity Control
LLS2— Liquid Line Solenoid for
NEC— National Electrical Code, U.S.A.
TB— Terminal Block
Field Power Wiring
TC— Thermostat Cooling
Field Control Wiring
Factory Installed Wiring
10
Page 11
FM— Fan Motor
FU— Fuse
LEGEND
BPR— Bypass Relay
C—Contactor, Compressor
GND— Ground
LLSV — Liquid Line Solenoid Valve
NEC— National Electrical Code (U.S.A.)
DB— Circuit Breaker
CR— Control Relay
CM— Control Module
TB— Terminal Block
TRAN — Transformer
EQUIP — Equipment
FC— Fan Contactor
Fig. 9A — Component Arrangement — 60 Hz
11
Page 12
12
LEGEND
BPR— Bypass Relay
C—Contactor, Compressor
CB— Circuit Breaker
CR— Control Relay
CM— Control Module
EQUIP — Equipment
FC— Fan Contactor
FM— Fan Motor
FU— Fuse
GND— Ground
LLSV— Liquid Line Solenoid Valve
NEC— National Electrical Code (U.S.A.)
TB— Terminal Block
TDR— Time Delay Relay
Fig. 9B — Component Arrangement — 50 Hz
TRAN — Transformer
Page 13
Initial Check
START-UP
The start-up of the compressor can occur between 3 seconds
and approximately 5 minutes from the time the control circuit is energized due to the anti-short cycle feature of the
control module (CM).
Do not attempt to start the condensing unit, even momentarily, until the following steps have been completed. Compressor damage may result.
1. Check all auxiliary components, suchasair-handlingequipment, and other equipment. Consult the manufacturer’s
instructions regarding any other equipment connected
to the condensing unit. If used, airflow switch must be
properly installed. See Fig. 8.
2. Backseat (open) compressor suction and discharge valves.
Close valves one turntoallowpressuretoreachtest gages.
3. Open liquid line service valve.
4. Set thermostat.
5. Check tightness of all electrical connections.
6. Compressor oil level should be visible in sight glass.
See Service, Oil Charge section on page 19.
7. Be sure unit isproperlyleaktested, dehydrated, and charged.
See below.
8. Electrical power source must agree with nameplate
rating.
9. Crankcase heater must be firmly locked into compressor crankcase. Be sure crankcase is warm(heater should
be on for 24 hours before starting compressor).
10. Be sure compressor floats freely on the mounting springs.
See Compressor Mounting section on page 2 and Fig. 3
for loosening compressor bolts.
Leak Test and Dehydration — Leak test the entire
refrigerant system by the pressure method described in the
Carrier Training Booklet; GTAC II, Module 4 - System
Dehydration.
PreliminaryCharge— Refer to Carrier TrainingBook-
let; GTAC II, Module 5 for charging methods and procedures. Charge system with approximately 25 lbs (11.3 kg) of
R-22 by the liquid charging method (charging through liquid service valve), on the high side, and charging by weight.
Charge per Fig. 10-12.
StartUnit — Close field disconnect. Set thermostat above
ambient temperature so that there is no demand for cooling.
Now,onlythe crankcase heater is energized.After the heater
has been on for 24 hours, the unit can be started. If no time
has elapsed since the preliminary charge step has been completed, it is unnecessary to wait the 24-hour period.
Close the compressor circuit breaker, then reset the indoor thermostat below ambient temperature, so that a call
for cooling is ensured.
NOTE: Do not use the compressor circuit breaker to start
and stop compressor, except in an emergency.
Charge System — Actual start-up should be done only
under supervision of a qualified refrigeration mechanic. Refer to charging charts.
See Fig. 10-12 for the particular unit being charged. Measure pressure at the liquid line service valve, being sure a
Schrader depressor is used if required. Also, measure liquid
line temperature as close to the liquid service valve as possible. Add or reduce charge until the pressure and temperature conditions of the charging charge curve are met. If liquid pressureandtemperaturepointfallabove curve, add charge.
If liquid pressure and temperature point fall below curve,
reduce the charge until the conditions match the curve.
Never charge liquid into the low-pressure side of system. Do not overcharge. During charging or removal of
refrigerant, be sure indoor fan system is operating.
Operation— Refer to control circuit diagram on the unit,
or in the unit wiring book.
Control Module (CM) — The unit control module is
located in the control section of the control box. See
Fig. 9A or 9B. It performs several functions. The CM has a
built-in compressor anti-short-cycle timer which will not allow the compressor to restart until 5 minutes (190 seconds/
–75 seconds) have elapsed since the previous shutdown.
The compressor oil pressure is monitored through the CM.
The unit is allowed to remain operational as long as the oil
pressure safety switch (OPS) has not been open for more
than 2 minutes after the compressor hasstarted. If after startup, the OPS is open for more than 2 minutes, the CM shuts
down the compressor and places the unit in a lockout condition. The CM activates the fault indication circuit, and the
field-supplied unit service lamp isilluminated(ifsoequipped).
The unit cannot be restarted until power is interrupted at the
unit, resetting the CM. The 5-minute recycle time relay is
initiated.
The CM also monitors the high-pressure switch (HPS) and
compressor thermal protection. If at any time the HPS opens,
the CM shuts down the compressor and places the unit in a
lockout condition. The CM activates the fault indication circuit, and the field-supplied unit service lamp is illuminated
(if so equipped). The unit cannot be restarted until the HPS
is reset and until power is interrupted at the unit, resetting
the CM. The 5-minute recycle time relay is initiated.
If the unit shuts down on an automatic reset switch, such
as the low-pressure switch (LPS), the compressor will be allowed to restart when the switch recloses and the CM antishort-cycle time has elapsed.
13
Page 14
14
Fig. 10 — 38AKS028 Charging Chart, 50/60 Hz
Page 15
15
Fig. 11 — 38AKS034 Charging Chart, 50/60 Hz
Page 16
16
Fig. 12 — 38AKS044 Charging Chart, 50/60 Hz
Page 17
FOR SERVICING ONLY — To speed up the 5-minute antishort cycle, a temporary jumper may be placed between terminals T1 and T6 of the control module.
This jumper must be removed after servicing is complete. Failure to remove this jumper is considered abusive treatment and will void the Carrier warranty.
Bypass Relay (BPR) — All units are equipped with a
BPR located in the control section of the control box. See
Fig. 9Aor 9B. The function of the BPR istoprovidea2-minute
bypass of the LPS at start-up, and to energize the unloader(s) at start-up to provide unloaded compressor starting. Two
minutes after the compressor starts, the BPR completes its
function and is no longer active in the control circuit until
the next restart of the unit.
Time-DelayRelay(TDR)(50 Hz Only) — This solid-
state delay-on-make relay is factoryset for a 1-second delay.
The number 1 dip switch is set to the ON position, and all
the other dip switches are set to the OFF position. Once the
control relay (CR) is energized, the compressor contactor C1
is powered, and the first set of compressor windings is energized.After the 1-second timedelay, contactor C1Ais powered and the second set of compressor windings is energized
(part-wind start).
Sequence of Operation — When space thermostat
calls for cooling, the no. 1 condenser fan and compressor
start after CM initial time delay of 3 (12/–1) seconds. If an
optional airflow switch is used, compressor and no. 1 condenser fan will not start until sufficient indoor airflow has
closed the switch.After 3 seconds the compressor starts and
the liquid line solenoid valve for solenoid drop control opens.
The crankcaseheaterisdeenergized. If the head pressurereaches
260 psig (1792 kPa) the second condenser fan starts. Fan
no. 3 (38AKS044 only) starts if outdoor ambient air rises
above 80 F (26.7 C).
If cooling demand is low, suction pressure at the compressor drops. As the pressure drops, the compressor unloads 2 banks of cylinders as required. If cooling demand is
high and 2-stage operation is used, the second stage of the
thermostat activates the capacity control liquid line solenoid
which activates the second stage evaporator coil. The compressor cylinders load or unload in response to compressor
suction pressure to meet evaporator load.
T wominutes after compressor starts, the BPR timer is deenergized and the LPS bypass is deactivated. If the LPS trips
during the first 2 minutes of operation, the compressor will
remain operational. If the LPS trips after 2 minutes,the compressor operation is interrupted, and the compressor cannot
restart until the 5-minute CM anti-short cycle timer expires.
As the space cooling load is satisfied, the second stage of
the thermostat opens, and closes the field-supplied capacity
control liquid line solenoid valve to deactivate the second
stage coil. The compressor adjusts the number of active cylinders to meet the new load. When the space temperature is
satisfied, the first stage of the thermostat opens and the control relay and the BPR open. This closes the solenoid drop
control valve. The compressor stops and the crankcase heater
is energized,preventingrefrigerantfrommigratingtothecompressor during the off cycle (solenoid drop refrigerant control). The CM anti-short cycling timer is energized and runs
for approximately 5 minutes. During this time, the compressor is not able to restart.
Complete Unit Stoppage
CAUSES — Interruption of supplied power,compressor overtemperature protection, or open HPS causes compressor
stoppage.
RESTART — The unit recycles and restarts automatically
under the CM when power is restored. Stoppage by HPS, or
compressor circuit breaker requires manual resetting of the
control circuit. Torestartthe CM timer when HPS is tripped,
it is necessary to interrupt power to the unit, restarting the
CM logic. It is necessary to manually reset the compressor
circuit breaker at the unit.
If LPS is not closed within 2 minutes after compressor
starts, the compressor locks out and the outdoor fans continue to run. It stays locked out for 5 minutes until the CM
anti-short cycle timer expires. After 5 minutes, the LPS is
bypassed by the BPR (winter start control). It remains jumpered for 2 minutes. Because the LPS is jumpered, the compressor restarts and runs for the 2-minute time period. At
the end of this 2 minutes, if the LPS has still not closed, the
compressor is again locked out. The outdoor fans continue
to run as long as there is a call for cooling. Automatic reset
of the LPS causes the CM to recycle so that the compressor
can start.
If sufficientcompressoroilpressurehasnot been built within
2 minutes after the compressor starts, the unit is completely
deenergized until the oil pressure switch is manually reset at
the unit.
If unit or circuit stoppage occurs more than once due to
any safety device, the trouble should be corrected before any attempt to restart.
SERVICE
Turn off all power to unit before proceeding.
Access for Servicing (See Fig. 13)
COMPRESSOR SECTION — The compressor compartment has 2 side access panels and one front door for servicing, providing access to compressor, all components of
the refrigerant system, electrical controls, and control box.
After opening front door there is an inner cover that must be
removed for access to control box (except 208/230-v and
460-v units).
OIL PRESSURE SAFETY SWITCH — Switch is manually
reset, and accessed by removing the side access panel on the
left side of the unit (as viewed from the compressor end).
See Fig. 13. The OPS is found in the compressor junction
box. Open the compressor circuit breaker prior to removing
the compressor junction box cover in order to access the OPS.
The liquid line service valve can be found behind the side
access door on the right side of the unit (as viewed from the
compressor end).
CONDENSER SECTION — Condenser fan motors and fans
can be serviced by removal of outlet grilles or side panels.
If a fan motor is serviced, be sure the wire fan guard is in
place over each fan before starting unit. See Fig. 14 for proper
fan adjustment. Tightenfanhub securely on motor shaft with
setscrew which bears against the key. Be sure to replacePermagum and rubber cap over end of motor shaft to protect
against moisture causing fan to rust on shaft.
17
Page 18
TRAN1
CM
CR1
FC
FC3
FC2
COMPRESSOR END AND RIGHT-SIDE VIEW
TRAN2
C1
TB2
CB2
CB1
TB3
COMPRESSOR END, CONTROL PANEL REMOVED
LIQUID LINE
SERVICE
VALVE
OIL PRESSURE SAFETY SWITCH
COMPRESSOR END, LEFT-SIDE ACCESS DOOR
(JUNCTION BOX COVER REMOVED)
Fig. 13 — 38AKS Unit with Access Panels Removed
COMPRESSOR END, RIGHT-SIDE ACCESS DOOR
18
Page 19
Fan Adjustment — Adjust fan as shown in Fig. 14.
NOTE: Dimension in ( ) is in millimeters.
Capacity Control — Capacity control is by 2 suction
pressure actuated unloaders. Each controls 2 cylinders. Unloaders are factory set (see Table 1Aor 1B) but may be field
adjusted. Number 1 unloader is on cylinder bank on same
side of compressor as terminal box.
CONTROL SET POINT — The control set point (cylinder
load point) is adjustable from 0 to 85 psig (0 to 586 kPag).
T oadjust, turn control set point adjustment nut (Fig. 15) clockwise to its bottom stop. In this position, set point is
85 psig (586 kPag). Then, turn adjustment counterclockwise
to desired control set point. Every full turn counterclockwise decreases set point by 7.5 psig (52 kPag).
Fig. 14 — Location of Prop on Motor Shaft from
Outside of Orifice Ring
Oil Charge — Compressors are factory charged with oil
When additional oil or a complete charge is required, use
only Carrier-approved compressor oil:
Petroleum Specialities Inc. ..................Cryol 150
Texaco, Inc. .........................Capella WF-32
Witco Chemical Corp. ...................Suniso 3 GS
IMPORTANT: Do not use drained oil or use oil that
has been exposed to atmosphere. Refer to Carrier Training Booklet, GTAC II, Module 5, for procedures to
add oil. To remove oil, isolate the compressor, reclaim
internal compressorcharge,anduse the compressor drain
plug.
Liquid Shutoff/Charging Valve — Valve is located
inside the compressor compartment and is provided with
1
⁄4-in. flare connection for field charging.
Fig. 15 — Capacity Control Valve
PRESSURE DIFFERENTIAL — The pressure differential
(difference between cylinder load and unload points) is adjustable from 6 to 22 psig (41 to 152 kPag). To adjust, turn
pressure differential adjustment screw (Fig. 15) counterclockwise to its backstop position. In this position, differential is 6 psig (41 kPag). Then, turn adjustment clockwise
to desired pressure differential. Every full turn clockwise increases differential by 1.5 psig (10 kPag).
19
Page 20
Oil Pressure Safety Switch (OPS) — The OPS in
the control circuit stops the compressor and unit, if proper
oil pressure differentialis not established at start-up or maintained during operation. If OPS stops the unit, determine the
cause and correct before restarting unit. Failure to do so will
constitute abuse. Equipment failure due to abuse may void
the warranty.
Compressor Protection
CIRCUIT BREAKER — Calibrated trip manual reset, ambient compensated, magnetic breaker protects against motor
overload and locked rotor conditions.
CONTROLMODULETIMER—This controlprotectscompressor against short cycling. See Sequence of Operation on
page 17.
CRANKCASE HEATER — This minimizes absorption of
liquid refrigerant by oil in crankcase during brief or extended shutdown periods.
IMPORTANT: Never open any switch or disconnect
that deenergizes the crankcase heater unless unit is being serviced or is to be shut down for a prolonged period. After a prolonged shutdown on a service job, energize the crankcase heater for 24 hours before starting
the compressor.
High-Pressure Switch — This switch has fixed, non-
adjustable settings. Switch is mounted on the compressor (See
Table 4).
Low-Pressure Switch — This switch has fixed, non-
adjustable settings. Switch is mounted on the compressor.
(See Table 4.)
Head Pressure Control — Control maintains ad-
equate dischargepressureunderlowambienttemperatureconditions. See Table 5.
FAN CYCLING — These 38AKS units have standard provision for fully automatic intermediate-season head pressure
control through condenser fan cycling. Fan no. 2 is cycled
by a fan cycling pressure switch (FCPS) which responds to
variation in discharge pressure. The pressure sensor is located in the liquid line of the refrigerant circuit. Fan no. 3
cycling is controlled by outdoor-air temperature through an
air temperature switch (ATS) (38AKS044 units only).
Table 5 — Minimum Outdoor-Air
Operating Temperature
UNIT
38AKS
028
034
044
COMPR
CAP. (%)
10090 (32)31 (–1)–20 (–29)
6780 (27)35 (2)–20(–29)
3370 (21)43 (6)–20(–29)
10090 (32)30 (–1)–20 (–29)
6780 (27)34 (1)–20(–29)
3370 (21)42 (6)–20(–29)
10090 (32)25 (–4)–20 (–29)
6780 (27)30 (–1)–20 (–29)
3370 (21)35 (2)–20(–29)
COND
TEMP,
F (C)
TheATS is located in the lower divider panel between the
compressor compartment and condenser section. Through a
hole in the panel, the sensing element is exposed to air entering the no. 1 fan compartment. Fan no. 1 is noncycling.
Table 6 shows the operating settings of the FCPS and the
ATS.
MIN OUTDOOR TEMP, F (C)
Standard
Unit
Low Ambient
Control
(MotormasterT)
Table 4 — Pressure Switch Settings, psig (kPa)
HIGH PRESSURELOW PRESSURE
CutoutCut-inCutoutCut-in
426±7
(2937 ± 48)
320±20
(2206 ± 138)
27±3
(186 ± 21)
44±5
(303 ± 34)
Winter Start Control — Bypass relay timer bypasses
low-pressure switch for 2 minutes on unit start-up.
Table 6 — Fan Cycling Controls
CONTROL BYSWITCH OPENSSWITCH CLOSES
Temp, F (C)70 ± 3 (21 ± 1.7)80 ± 3 (27 ± 1.7)
Pressure,
psig (kPa)
NOTE: See Fig. 6 and 7 for fan arrangement.
160 ± 10 (1103 ± 69) 260 ± 15 (1793 ± 103)
20
Page 21
TROUBLESHOOTING
SYMPTOM AND PROBABLE CAUSEPROBABLE REMEDY
COMPRESSOR DOES NOT RUN
1. Control circuit breaker tripped1. Reset control circuit breaker
2. Power line open2. Reset circuit breaker
3. Oil pressure switch tripped3. Reset oil pressure switch at unit
4. Safety device tripped4. Reset control circuit with thermostat
5. Contactor stuck open5. Replace contactor
6. Loose terminal connection6. Check connections
7. Improperly wired controls7. Check and rewire
8. Seized compressor8. Check motor winding for open or short.
9. Low line voltage9. Check line voltage — determine location of
10. Compressor motor defective10. Check motor winding for open or short.
COMPRESSOR STOPS ON LOW-PRESSURE
CONTROL
1.Compressorsuctionshutoffvalvepartiallyclosed1. Open valve
2. Low refrigerant charge2. Add refrigerant
3. Liquid line solenoid valve(s) fails to open3. Check liquid line solenoid valve for proper
4. Liquid line shutoff valve closed4. Open valve
COMPRESSOR STOPS ON HIGH-PRESSURE
CONTROL
1. Compressor discharge valve partially closed1. Open valve or replace if defective
2. Air in system2. Purge and evacuate system
3. Condenser fan(s) not operating3. Check motor wiring and repair or replace if
4. System is overcharged.4. Reclaim charge as needed
UNIT OPERATES TOO LONG OR
CONTINUOUSLY
1. Low refrigerant charge1. Add refrigerant
2. Control contacts fused2. Replace control
3. Air in system3. Purge and evacuate system
4. Partially plugged expansion valve or filter drier4. Clean or replace
SYSTEM IS NOISY
1. Piping vibration1. Support piping as required
2. Compressor noisy2. Check valve plates for valve noise. Replace
COMPRESSOR LOSES OIL
1. Leak in system1. Repair leak
2. Crankcase heaters not energized during2. Check wiring and relays. Check heater and
shutdownreplace if defective
3. Improper interconnecting piping design3. Check piping for oil return. Replace if
1. Shortage of refrigerant due to leak.1. Repair leak and recharge
2. Expansion valve opens too wide2. Adjust expansion valve
FROSTED LIQUID LINE
1. Restricted filter drier1. Remove restriction or replace
COMPRESSOR WILL NOT UNLOAD
1. Defective unloader1. Replace
2. Defective capacity control solenoid valve2. Replace valve
3. Miswired liquid line solenoid3. Rewire correctly
4. Weak, broken, or wrong valve body spring4. Replace spring
COMPRESSOR WILL NOT LOAD
1. Miswired capacity control liquid solenoid1. Rewire correctly
2. Defective capacity control solenoid valve2. Replace valve
3. Plugged strainer (high side)3. Clean or replace strainer
4. Stuck or damaged unloader piston or piston4. Clean or replace the necessary parts
ring(s)
Replace compressor, if necessary
voltage drop and remedy deficiency
Replace compressor, if necessary
operation. Replace if necessary
defective
compressor if bearings are worn
necessary
21
Page 22
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the
equipment discussed in this manual. Product programs cover:
• Unit Familiarization
• Installation Overview
A large selection of product, theory, and skills programs is available. All programs include a video
cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training
sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are
included.
• Maintenance
• Operating Sequence
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 3a
PC 111Catalog No. 533-820Printed in U.S.A.Form 38A-5SIPg 227-94Replaces: 38AK-3SI
Page 23
START-UP CHECKLIST
(Remove and store in job file)
A. Preliminary Information
OUTDOOR:MODELNO.SERIALNO.
INDOOR: AIR HANDLER MANUFACTURER
MODEL NO.SERIAL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE?(Y/N)
IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP?(Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?(Y/N)
HAS THE GROUND WIRE BEEN CONNECTED?(Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?(Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?(Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED?(Y/N)
CUT ALONG DOTTED LINE
CONTROLS
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED?(Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?(Y/N)
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS?(Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?(Y/N)
ARE PROPER AIR FILTERS IN PLACE?(Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?(Y/N)
DO THE FAN BELTS HAVE PROPER TENSION?(Y/N)
PIPING
ARE LIQUID LINE SOLENOID VALVE(S) LOCATED AT THE EVAPORATOR COIL AS REQUIRED?(Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR,
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR?(Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVEALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)?(Y/N)
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING ABOUT1⁄2FULL?(Y/N)
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:ABVACVBCV
(AB + AC + BC)/3 = AVERAGE VOLTAGE =V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CHECK EVAPORATOR FAN SPEED AND RECORD.
CHECK CONDENSER FAN SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING CONDENSER AIR TEMP
LEAVING CONDENSER AIR TEMP
EVAP ENTERING AIR DB TEMP
EVAP ENTERING AIR WB TEMP
EVAP LEAVING AIR DB TEMP
EVAP LEAVING AIR WB TEMP
COMPRESSOR AMPS (L1)
COMPRESSOR AMPS (L2)
COMPRESSOR AMPS (L3)
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT1⁄8TO1⁄3FULL?(Y/N)
NOTES:
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 3a
PC 111Catalog No. 533-820Printed in U.S.A.Form 38A-5SIPg CL-27-94Replaces: 38AK-3SI
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.