Carrier 38AKS028-044 User Manual

Page 1
Air-Cooled Condensing Units
Installation, Start-Up and
Service Instructions
CONTENTS
38AKS028-044
50/60 Hz
Page
SAFETY CONSIDERATIONS ...................1
BEFORE INSTALLATION .....................1-3
Rigging ......................................1
Placing Unit .................................3
Mounting Unit ...............................3
INSTALLATION .............................3-12
Refrigerant Piping Connections ...............3
Filter Drier and Moisture Indicator ............3
Power Supply ................................6
Power Wiring ................................6
START-UP ................................13-17
Leak Test and Dehydration ..................13
Preliminary Charge ..........................13
Start Unit ...................................13
Charge System .............................13
Operation ...................................13
Control Module (CM) ........................13
Bypass Relay (BPR) .........................17
Time-Delay Relay (TDR) .....................17
SERVICE ..................................17-20
Access for Servicing ........................17
Fan Adjustment .............................19
Oil Charge ..................................19
Oil Pressure Safety Switch (OPS) ............20
Compressor Protection ......................20
High-Pressure Switch .......................20
Low-Pressure Switch ........................20
Head Pressure Control ......................20
START-UP CHECKLIST .....................CL-1
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.).
Only trained, qualified installers and service mechanics should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep, quenching cloth and fire extinguisher nearby when
brazing.
• Use care in handling, rigging, and setting bulky
equipment.
• See Table 1A or 1B for physical data.
ELECTRIC SHOCK HAZARD Open all remote disconnects before
servicing this equipment.
BEFORE INSTALLATION
Rigging —
above the unit. Use 2-in. (50 mm) OD pipe or hooks in lift­ing holes. Rig with 4 cables and spreader bars. All panels must be in place when rigging. See rigging label on unit for details concerning shipping weights, distance between lift­ing holes, center of gravity, and spreader bar dimensions. See Fig. 2.
If overhead rigging is not possible, place unit on skid or pad for rolling or dragging. When rolling, use minimum of 3 rollers. When dragging, pull the pad. Do not apply force to the unit. When in final position, raise from above to lift unit off pad.
Preferred method is with spreader bars from
All panels must be in place when rigging.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 3a
PC 111 Catalog No. 533-820 Printed in U.S.A. Form 38A-5SI Pg 1 7-94 Replaces: 38AK-3SI
Page 2
Table 1A — Physical Data — English
UNIT 38AKS 028 034 044
COMPRESSOR Reciprocating Semi-Hermetic
No. ...Type 1...06E9265 1...06E9275 1...06E9299
No. Cyls (ea)...Speed, Rpm (60/50 Hz) 6...1750/1460 Capacity Steps 3 Oil Charge*, Pt 20.0 20.0 19.0
Oil Pressure Switch (psi)
Set Points — Cutout 6 6 2
Differential — Cut-in 14 Max. Crankcase Heater (watts) 180 Protection See Note Capacity Control (Psig) Suction Pressure Unloader(s) No. 1 Unloader Settings
Load 76 76 76
Unload 58 58 58 No. 2 Unloader Settings
Load 78 78 78
Unload 60 60 60 REFRIGERANT CHARGE, R-22
Approximate lb 30.5 43.5 65 COIL STORAGE
(at 125 F liquid temperature
and 80% full), lb CONDENSER FANS, Type Propeller Type, Direct Driven
No. ...Diameter, in. 2...30 3...30
Total Airflow, Cfm 15,700 23,700 Speed, Rpm 60/50 Hz 1140/950
CONDENSER COIL, Type Horizontal Plate Fin Rows...Fins/in. 2...19 3...17 3...17 Total Face Area, sq ft 39.2 39.2 58.4
*See Service, Oil Charge, for Carrier-approved oil. NOTE: Circuit breaker is in main power circuit.
37.7 56.6 84.4
Table 1B — Physical Data — SI
UNIT 38AKS 028 034 044
COMPRESSOR Reciprocating Semi-Hermetic
No. ...Type 1...06E9265 1...06E9275 1...06E9299
No. Cyls (ea)...Speed, R/s (60/50 Hz) 6...29.2/24.3 Capacity Steps 3 Oil Charge*, L 9.4 9.4 9.0
Oil Pressure Switch (kPa)
Set Points — Cutout 41.4 6 13.8
Differential — Cut-in 96.5 Max. Crankcase Heater (watts) 180 Protection See Note Capacity Control (kPa) Suction Pressure Unloader(s) No. 1 Unloader Settings
Load 524 524 524
Unload 400 400 400 No. 2 Unloader Settings
Load 538 538 538
Unload 414 414 414 REFRIGERANT CHARGE, R-22
Approximate, kg 13.8 19.7 29.5 COIL STORAGE
(at 52 C liquid temperature
and 80% full), kg CONDENSER FANS, Type Propeller Type, Direct Driven
No. ...Diameter, mm 2...762 3...762
Total Airflow, L/s 7,400 11,200 Speed, R/s (60/50 Hz) 19.0/15.8 19.0/15.8
CONDENSER COIL, Type Horizontal Plate Fin Rows...Fins/mm 2...1.34 3...1.49 3...1.49 Total Face Area, sq m 3.64 3.64 5.43
*See Service, Oil Charge, for Carrier-approved oil. NOTE: Circuit breaker is in main power circuit.
17.1 25.7 38.3
2
Page 3
Placing Unit — There must be 4 ft (1220 mm) for ser-
vice on all sides of unit, and a minimum of 8 ft (2440 mm) clear air space above unit. For multiple units, allow 8 ft (2440 mm) separation between units for airflow and service.
Mounting Unit — When unit is in proper location, use
of mounting holes in base rails is recommended for securing unit to supporting structure or for mounting unit on vibra­tion isolators, if required. Fasteners for mounting unit are field supplied. Be sure to mount unit level to ensure proper oil return to compressors.
Compressor Mounting — As shipped, compressor
is held down by 4 bolts. After unit is installed loosen each bolt using nut indicated in Fig. 3 until flatwasher (3⁄8in. [9.5 mm]) can be moved with finger pressure.
Fig. 1 — 38AKS Units
NOTES:
1. Use 2 in. OD (50 mm) pipe or hooks in lifting holes.
2. Rig with 4 cables and spread with 2 ‘‘D’’ long and two ‘‘A’’ long 2 x 4’s in. (50 x 100 mm) or equal.
3. Run the rigging cables to a central suspension point so that the angle from the horizontal is not less than 45 degrees.
All panels must be in place when rigging.
MAX SHIP.
UNIT
38AKS
028 1924 872 81 2057 43.0 1092 28.0 711 73.5 1867 034 2115 960 81 2057 43.0 1092 28.0 711 73.5 1867 044 2797 1207 99 2515 49.0 1245 30.5 775 73.5 1867
WT
Lb Kg in. mm in. mm in. mm in. mm
LIFTING
HOLES
CENTER OF GRAVITY
‘‘A’’
‘‘B’’ ‘‘C’’
‘‘D’’
INSTALLATION
Refrigerant Piping Connections—
pend on length of piping required between condensing unit and evaporator. See Table 2A or 2B. It is important to con­sider liquid lift and compressor oil return. Refer to Part 3 of Carrier System Design Manual for line sizing information, and Fig. 4 for recommended piping details.
Line sizes de-
Liquid Line Solenoid Drop Control — The factory-
supplied solenoid valve must be installed at the indoor unit (fan coil) per Fig. 5, and wired per wiring label found on unit. The solenoid assures that system refrigerant is in the high-pressure side (condenser and liquid line) of the system during the off cycle. Refrigerant migration is minimized.
Factory-supplied liquid line solenoid valve connecting sizes
7
⁄8-in. (22.2 mm) ODF for inlet and7⁄8-in. (22.2 mm)
are ODM for outlet.
Failure to properly install liquid line solenoid at the in­door unit as described, without Carrier authorization, may VOID warranty.
Filter Drier and Moisture Indicator — Every unit
should have a filter drier and a sight glass (moisture indi­cator) field installed. Select the filter drier for maximum unit capacity and minimum pressure drop. Figure 5 shows rec­ommended locations of filter drier(s) and sight glass. Com­plete the refrigerant piping from the evaporator to the con­denser before opening the liquid and suction lines at the condensing unit. One filter drier may be installed at location A in Fig. 5, or 2 filter driers may be installed at locations B.
Fig. 2 — Rigging with Spreader Bars
(Field Supplied)
3
Page 4
NOTE: All dimensions are in inches (mm).
Fig. 3 — Compressor Mounting
TXV — Thermostatic Expansion Valve
NOTES:
1. Suction line is connected to coil on same side as the entering air.
2. Lower section is first on and last off.
3. For more complete piping information, refer to Carrier System Design Manual, Part 3.
Fig. 4 — Suction Line Piping to Unit
with 2 Section Coil Split
TXV — Thermostatic Expansion Valve
Fig. 5 — Liquid Line Solenoid Valve,
Filter Drier(s) and Sight Glass Locations
Receiver — No receiver is provided with the unit; it is
recommended that one not be used.
Piping Procedure — Do not remove run-around pipe
from suction and liquid line stubs until piping connections are ready to be made. Pass nitrogen or other inert gasthrough piping while brazing, to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve (TXV) in liquid line ahead of each evaporator section. For 2-stage cooling, the field-supplied capacity controlsolenoidusedmust
be wired to be opened by control from a 2-stage thermostat.
SUCTION PIPING AT EVAPORATOR AND TXV BULB LOCATION (See Fig. 5) — The purpose of these recom­mendations is to achieve good mixing of the refrigerant leav­ing the evaporator suction header for proper sensing by the TXV bulb.
1. A minimum of two 90° elbows must be installed up-
stream of the expansion valve bulb location.
2. The TXV sensing bulb should be located on a vertical
riser where possible. If a horizontal location is necessary, secure the bulb at approximately the 4 o’clock position.
3. Size the suction line from the evaporator throughthe riser
for high velocity. Enter the suction pipe sizing charts in the CarrierSystemDesignManual at design tons and equiva­lent length (for 2° F [1.1° C] loss). If reading falls be­tween 2 sizes on chart, choose the smaller pipe size.
Suction piping for the high velocity section should be selected for about 0.5° F (0.3° C) friction loss. If a 2° F (1.1° C) loss is allowed for the entire suction line, 1.5° F (0.8° C) is left for the balance of the suction line, and it should be sized on that basis. Check that the high-velocity sizing
is adequate for oil return up the riser.
If an oil return connection at the bottom of this suction header is supplied with an evaporator, this connection must be teed-in ahead of first mixing elbow. When the compres­sor is below the evaporator, the riser at the evaporator does not have to extend as high as the top level. After a 15-diameter riser has been provided, the suction line may elbow down immediately.
SAFETY RELIEF — Afusible plug is located on unit liquid line before the liquid valve.
4
Page 5
Table 2A — Refrigerant Piping Sizes — 60 Hz
SINGLE SUCTION RISERS
UNIT
38AKS
028 034 044
L—Liquid Line S—Suction Line
16-25 (4.9-7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2-30.5) 101-200 (30.8-60.9)
LSL S L S L S L S
7
8
7
8
7
8
15⁄ 21⁄ 21⁄
8 8 8
7
8
7
8
7
8
*IMPORTANT — Requires a double suction riser, if evaporator is below condensing unit. See table below. NOTE: Liquid and suction line sizes are OD (in.) Equivalent sizes in mm are listed below.
LENGTH OF INTERCONNECTING PIPING, FT (M)
21⁄8* 21⁄ 21⁄
7
8
11⁄
7
8
8
8 8
21⁄8* 21⁄
8
25⁄8*1
7
8
11⁄
8
1
8
21⁄8* 21⁄
8
5
2
8
*1
DOUBLE SUCTION RISERS — 60 Hz
UNIT
38AKS
028 1
26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2.-30.5) 101-200 (30.8-60.9)
ABCABC A B C A B C
3
8
15⁄
8
21⁄
8
034 —————— — — —1 044 ———1
NOTE: A, B, C dimensions relate to reference diagram.
LENGTH OF INTERCONNECTING PIPING, FT (M)
13⁄
8
15⁄
8
21⁄
5
⁄82
1
⁄82
8
5
⁄81
13⁄
8
5
⁄82
15⁄
8
1
⁄82
21⁄
8
5
⁄81
Table 2B — Refrigerant Piping Sizes — 50 Hz
SINGLE SUCTION RISERS
UNIT
38AKS
028 034 044
L—Liquid Line S—Suction Line
*IMPORTANT — Requires a double suction riser, if evaporator is below condensing unit. See table below.
†For riser, use 1
16-25 (4.9-7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2-30.5) 101-200 (30.8-60.9) LSL S L S L S L S
7
8
7
8
7
8
5
⁄8OD inches.
15⁄
21⁄8†
21⁄
8
8
7
8
7
8
7
8
NOTE: Liquid and suction line sizes are OD (in.) Equivalent sizes in mm are listed below.
LENGTH OF INTERCONNECTING PIPING, FT (M)
21⁄8* 21⁄8* 21⁄
7
8
7
8
8
11⁄
8
21⁄8* 21⁄8*1 25⁄8*1
7
8
1
8
1
8
21⁄8*
5
2
8
*1
5
2
8
*1
7
8
11⁄
8
1
8
13⁄
8
5
⁄82
5
⁄82
15⁄
8
1
⁄82
1
⁄82
7
8
1
8
1
8
21⁄8* 25⁄8*
5
2
8
*
21⁄
8
5
8
5
8
21⁄8*
5
2
8
*
5
2
8
*
DOUBLE SUCTION RISERS — 50 Hz
UNIT
38AKS
028 1 034 15⁄
26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2.-30.5) 101-200 (30.8-60.9)
ABCABC A B C A B C
3
8
15⁄
8
21⁄
8
8
15⁄
8
21⁄
8
044 ———1
NOTE: A, B, C dimensions relate to reference diagram.
Unit Size Dimension — in. (mm)
028 15⁄8(41.3) 034 21⁄8(54.0) 044 21⁄8(54.0)
LENGTH OF INTERCONNECTING PIPING, FT (M)
13⁄
8
15⁄
8
5
⁄82
15⁄
8
21⁄
8
15⁄
8
21⁄
1
⁄82
8
5
⁄81
13⁄
8
15⁄
8
5
⁄82
15⁄
8
15⁄
8
1
⁄82
21⁄
8
21⁄
8
5
⁄81
13⁄
8
15⁄
8
5
⁄82
MAXIMUM LIQUID LIFT
UNIT 38AKS
028 76 23 66 20 034 67 20 60 18 044 76 23 66 20
EQUIVALENT SIZES IN MM
60 Hz 50 Hz
FtMFtM
in. mm
7
⁄ 11⁄ 13⁄ 1 21⁄ 2
8
8 8
5
8 8
5
8
22.2
28.6
34.9
41.3
54.0
66.7
15⁄
8
21⁄
8
1
⁄82
21⁄
8
25⁄
8
5
8
5
Page 6
Power Supply — Electrical characteristics of available
power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in Table 3.
IMPORTANT:Operatinguniton improper supply volt­age, orwithexcessivephaseimbalance,constitutes abuse and mayaf fectCarrier warranty.SeeUnbalanced3-Phase Supply Voltage, page 7.
Power Wiring — All power wiring must comply with
applicable localandnationalcodes.Install field-supplied branch circuit fused disconnect(s) per NEC (National Electrical Code, U.S.A.) of a type that can be locked OFF or OPEN. Dis­connect(s) must be within sight from and readily accessible from unit in compliance with NEC Article 440-14.
GENERAL WIRING NOTES
1. A crankcase heater is wired in the control circuit so it is always operable as long as power supply disconnect is on, even if any safety device is open or unit stop-start switch is off. It is protected by a 5-amp circuit breaker in control power.
2. The power circuit field supply disconnect should never be
open except when unit is being serviced or is to be down for a prolongedperiod.Whenoperationisresumed, crank­case heater should be energized for 24 hours before start­up. If unit is to be shut down for a prolonged period, it is recommended that the suction and discharge valves be
closed to prevent an excessive accumulation of refriger­ant in the compressor oil.
3. Power entry is one end only.
4. Maximum field wire sizes allowed by lugs on terminal block are:
UNIT
38AKS
028 208/230-3-60 034
044
LEGEND
AWG — American Wire Gage kcmil — Thousand Circular Mils
*All other units use 2/0 AWG (67.4 mm
V-Ph-Hz
208/230-3-60
230-3-50
208/230-3-60
230-3-50
2
).
WIRE SIZE*
350 kcmil
5. Terminals for field power supply are suitable for copper, copper-clad aluminum, or aluminum conductors. Insula­tion must be rated 167 F (75 C) minimum.
CONDENSER FANS— The fans must rotate counterclock­wise when viewed from above. If necessary, correct direc­tion of fan rotation by interchanging any 2 powerinput wires at disconnect switch. Affix crankcase heater decal (located in installer’s packet) to unit disconnect switch.
Table 3 — Electrical Data
60 HZ
UNIT
38AKS
500
028
034
044
028
034
044
CSA Canadian Standards Association FLA Full Load Amps ICF Maximum InstantaneousCurrentFlow duringstarting(the point
LRA Locked Rotor Amps MCA Minimum Circuit Amps (complies with National
MOCP — Maximum Overcurrent Protection RLA Rated Load Amps UL Underwriters’ Laboratories
200 600 100
500 200 600 100
500 200 600 100
UNIT
38AKS
800 300 900
800 300 900
800 300 900
inthestarting sequence wherethesum oftheLRA forthe start­ing compressor,plus the total FLA for allrunningfanmotors is maximum).
Electrical Code [NEC, U.S.A.], Section 430-24)
3 Ph, 60 Hz
208/230
208/230
3 Ph, 50 Hz
LEGEND
Volts
380 460 575
380 460 575
230 380 460 575
Volts
230 346 400
230 346 400
230 346 400
Supplied*
Min. Max.
187 342 414 518
187 342 414 518
187 342 414 518
Supplied*
Min. Max.
198 311 342
198 311 342
198 311 342
UNIT COMPRESSOR FAN MOTORS
MCA
254 418 508 632
254 418 508 632
254 418 508 632
124.6
64.7
60.7
52.5
145.5
72.5
68.7
54.9
203.0
111.1
91.0
81.5
50 HZ
UNIT COMPRESSOR FAN MOTORS
MCA
254 380 400
254 380 400
254 380 400
109.0
64.9
60.5
120.2
76.1
68.5
150.6
112.6
90.8
MOCP (Fuse)
200 110 100
80
250 125 110
90
350 175 150 125
MOCP (Fuse)
175 100 100
200 125 110
250 175 150
*Units are suitable for use on electrical systems where voltage sup-
ICF RLA LRA FLA (ea) Qty
452.2
250.9
226.1
167.4
512.2
283.9
256.1
179.4
702.4
389.8
351.2
282.8
ICF RLA LRA FLA (ea) Qty
348.4
263.4
226.0
372.4
298.4
256.0
557.8
408.8
351.0
pliedtounit terminals isnotbelow orabovelisted minimum andmaxi­mum limits.
89.8
45.5
43.6
36.5
106.5
52.6
50.0
38.5
147.5
79.5
65.4
57.1
76.9
44.9
43.6
85.9
53.9
50.0
105.1
79.5
65.4
446 247 223 164
506 280 253 176
690 382 345 276
342 259 223
366 294 253
545 400 345
6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4
6.4
4.4
3.0
6.4
4.4
3.0
6.4
4.4
3.0
2 2 2 2
2 2 2 2
3 3 3 3
2 2 2
2 2 2
3 3 3
6
Page 7
FIELD CONNECTIONS
1. Main Power — Bring wires from the fused disconnect switch through hole in bottom rail of unit to control box
12
(Fig. 6 and 7) and connect terminals , , and
line side of terminal block TB1 (see Fig. 8 and 9A
13
11
or 9B). To comply with NECArticle 440-14, the discon­nect must be located within sight from and readily ac­cessible from unit.
2. 24-v ControlPower—Unitshavesinglepointpower con­nections. Control circuit is directly connected internally to unit. Maximum 24-v control circuit is 3 amps.
NOTE: Wire runs use the following insulated wire:
LENGTH
0-50 18 0.82
50-75 16 1.30
Over 75 14 2.08
AWG — American Wire Gage
*35 C minimum.
INSULATED WIRE SIZE*
AWG mm
2
3. Control Circuit Interlock — An airflow switch may be installed in the indoor air handler to prevent unit from running when indoor air is not flowing. This switch (no. HR81JE001) is available from Service Parts Center, or equivalent can be field supplied. This should be electri­cally interlocked in the control circuit, between thermo-
2
stat TC1 (stage 1, cooling) and terminal on TB3.
Y1
See Fig. 8 for typical field wiring. This is in the 24-v cir­cuit. Wires must be run in conduit with ground wire.
4. Transformer Connections — See unit wiring label dia­gram, notes 1 and 2, located behind compressor compart­ment end access door.
IMPORTANT: Ensure power to the crankcase heater is always on (except when servicing the unit). If cir­cuit breakerinsideunitshutsdown the compressor,crank­case heater remains on.
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance:
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 240-3-60.
AB = 243 v BC = 236 v AC = 238 v
Average Voltage =
243 + 236 + 238
3
= 239 volts Determine maximum deviation from average voltage: (AB) 243 − 239=4v
(BC) 239 − 236=3v (AC) 239 − 238=1v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
4
239
= 1.7%
This amount of phase imbalance is satisfactory as it is be-
low the maximum allowable 2%.
IMPORTANT: Contact your local electric utility com­pany immediately if the supply voltage phase imbal­ance is more than 2%.
7
Page 8
LEGEND
NEC — National Electrical Code VAV — Variable Air Volume
NOTES:
1. There must beminimum(2440mm) 8 ft. clear air spaceabove unit.
2. The approximate operating weight of the unit is:
50 AND 60 HZ
UNIT
38AKS028 1650 748 38AKS028C 1804 818 38AKS034 1803 818 38AKS034C 2009 911
3. A ‘‘C’’in the model number indicates unit has factory-installed copper coil.
WT
(Lb)WT(Kg)
Fig. 6 — Dimensional Drawing, 38AKS028,034
8
Page 9
LEGEND
NEC — National Electrical Code NOTES:
1. There must beminimum(2440mm) 8 ft. clear air spaceabove unit.
2. The approximate operating weight of the unit is:
50 HZ AND 60 HZ
UNIT
38AKS044 2437 1106 38AKS044C 2745 1246
3. A ‘‘C’’in the model number indicates unit has factory-installed copper coil.
WT
(Lb)WT(Kg)
Fig. 7 — Dimensional Drawing, 38AKS044
9
Page 10
modifications or additions must be in compliance
NOTES:
1.Factorywiring in accordancewith the NEC.Any field
with all applicable codes.
ing of 180 va pilot duty plus capacity required for
2. All field interlock contacts must have minimum rat-
field-installed equipment. All field interlock con-
tacts inthe24-vcontrol circuit must have minimum
rating of 70 va pilot duty plus capacity required for
field-installed equipment.
3.Forinternal unit wiring,referencewiring bookorunit
wiring label diagram. TB2 is 115-1-60, TB3 is
24-1-60.
38AKS unit control box: LLS1, LLS2, field control
4. The following components are not located in the
thermostat, AFS, alarm shut-off switch, and alarm
or light.
Fig.8—Typical Wiring Schematic
LEGEND
AFS Airflow Switch
CB Circuit Breaker
EQUIP — Equipment
FU Fuse
GND Ground
LLS1 Liquid Line Solenoid for
Solenoid Drop Control
Capacity Control
LLS2 Liquid Line Solenoid for
NEC National Electrical Code, U.S.A.
TB Terminal Block
Field Power Wiring
TC Thermostat Cooling
Field Control Wiring
Factory Installed Wiring
10
Page 11
FM Fan Motor
FU Fuse
LEGEND
BPR Bypass Relay
C—Contactor, Compressor
GND Ground
LLSV — Liquid Line Solenoid Valve
NEC National Electrical Code (U.S.A.)
DB Circuit Breaker
CR Control Relay
CM Control Module
TB Terminal Block
TRAN — Transformer
EQUIP — Equipment
FC Fan Contactor
Fig. 9A — Component Arrangement — 60 Hz
11
Page 12
12
LEGEND
BPR Bypass Relay
C—Contactor, Compressor
CB Circuit Breaker
CR Control Relay
CM Control Module
EQUIP — Equipment
FC Fan Contactor
FM Fan Motor
FU Fuse
GND Ground
LLSV Liquid Line Solenoid Valve
NEC National Electrical Code (U.S.A.)
TB Terminal Block
TDR Time Delay Relay
Fig. 9B — Component Arrangement — 50 Hz
TRAN — Transformer
Page 13
Initial Check
START-UP
The start-up of the compressor can occur between 3 seconds and approximately 5 minutes from the time the control cir­cuit is energized due to the anti-short cycle feature of the control module (CM).
Do not attempt to start the condensing unit, even mo­mentarily, until the following steps have been com­pleted. Compressor damage may result.
1. Check all auxiliary components, suchasair-handlingequip­ment, and other equipment. Consult the manufacturer’s instructions regarding any other equipment connected to the condensing unit. If used, airflow switch must be properly installed. See Fig. 8.
2. Backseat (open) compressor suction and discharge valves. Close valves one turntoallowpressuretoreachtest gages.
3. Open liquid line service valve.
4. Set thermostat.
5. Check tightness of all electrical connections.
6. Compressor oil level should be visible in sight glass. See Service, Oil Charge section on page 19.
7. Be sure unit isproperlyleaktested, dehydrated, and charged. See below.
8. Electrical power source must agree with nameplate rating.
9. Crankcase heater must be firmly locked into compres­sor crankcase. Be sure crankcase is warm(heater should be on for 24 hours before starting compressor).
10. Be sure compressor floats freely on the mounting springs. See Compressor Mounting section on page 2 and Fig. 3 for loosening compressor bolts.
Leak Test and Dehydration — Leak test the entire
refrigerant system by the pressure method described in the Carrier Training Booklet; GTAC II, Module 4 - System Dehydration.
PreliminaryCharge— Refer to Carrier TrainingBook-
let; GTAC II, Module 5 for charging methods and proce­dures. Charge system with approximately 25 lbs (11.3 kg) of R-22 by the liquid charging method (charging through liq­uid service valve), on the high side, and charging by weight. Charge per Fig. 10-12.
StartUnit — Close field disconnect. Set thermostat above
ambient temperature so that there is no demand for cooling. Now,onlythe crankcase heater is energized.After the heater has been on for 24 hours, the unit can be started. If no time has elapsed since the preliminary charge step has been com­pleted, it is unnecessary to wait the 24-hour period.
Close the compressor circuit breaker, then reset the in­door thermostat below ambient temperature, so that a call for cooling is ensured.
NOTE: Do not use the compressor circuit breaker to start and stop compressor, except in an emergency.
Charge System — Actual start-up should be done only
under supervision of a qualified refrigeration mechanic. Re­fer to charging charts.
See Fig. 10-12 for the particular unit being charged. Mea­sure pressure at the liquid line service valve, being sure a Schrader depressor is used if required. Also, measure liquid line temperature as close to the liquid service valve as pos­sible. Add or reduce charge until the pressure and tempera­ture conditions of the charging charge curve are met. If liq­uid pressureandtemperaturepointfallabove curve, add charge. If liquid pressure and temperature point fall below curve, reduce the charge until the conditions match the curve.
Never charge liquid into the low-pressure side of sys­tem. Do not overcharge. During charging or removal of refrigerant, be sure indoor fan system is operating.
Operation— Refer to control circuit diagram on the unit,
or in the unit wiring book.
Control Module (CM) — The unit control module is
located in the control section of the control box. See Fig. 9A or 9B. It performs several functions. The CM has a built-in compressor anti-short-cycle timer which will not al­low the compressor to restart until 5 minutes (190 seconds/ –75 seconds) have elapsed since the previous shutdown.
The compressor oil pressure is monitored through the CM. The unit is allowed to remain operational as long as the oil pressure safety switch (OPS) has not been open for more than 2 minutes after the compressor hasstarted. If after start­up, the OPS is open for more than 2 minutes, the CM shuts down the compressor and places the unit in a lockout con­dition. The CM activates the fault indication circuit, and the field-supplied unit service lamp isilluminated(ifsoequipped). The unit cannot be restarted until power is interrupted at the unit, resetting the CM. The 5-minute recycle time relay is initiated.
The CM also monitors the high-pressure switch (HPS) and compressor thermal protection. If at any time the HPS opens, the CM shuts down the compressor and places the unit in a lockout condition. The CM activates the fault indication cir­cuit, and the field-supplied unit service lamp is illuminated (if so equipped). The unit cannot be restarted until the HPS is reset and until power is interrupted at the unit, resetting the CM. The 5-minute recycle time relay is initiated.
If the unit shuts down on an automatic reset switch, such as the low-pressure switch (LPS), the compressor will be al­lowed to restart when the switch recloses and the CM anti­short-cycle time has elapsed.
13
Page 14
14
Fig. 10 — 38AKS028 Charging Chart, 50/60 Hz
Page 15
15
Fig. 11 — 38AKS034 Charging Chart, 50/60 Hz
Page 16
16
Fig. 12 — 38AKS044 Charging Chart, 50/60 Hz
Page 17
FOR SERVICING ONLY — To speed up the 5-minute anti­short cycle, a temporary jumper may be placed between ter­minals T1 and T6 of the control module.
This jumper must be removed after servicing is com­plete. Failure to remove this jumper is considered abu­sive treatment and will void the Carrier warranty.
Bypass Relay (BPR) — All units are equipped with a
BPR located in the control section of the control box. See Fig. 9Aor 9B. The function of the BPR istoprovidea2-minute bypass of the LPS at start-up, and to energize the unload­er(s) at start-up to provide unloaded compressor starting. Two minutes after the compressor starts, the BPR completes its function and is no longer active in the control circuit until the next restart of the unit.
Time-DelayRelay(TDR)(50 Hz Only) — This solid-
state delay-on-make relay is factoryset for a 1-second delay. The number 1 dip switch is set to the ON position, and all the other dip switches are set to the OFF position. Once the control relay (CR) is energized, the compressor contactor C1 is powered, and the first set of compressor windings is en­ergized.After the 1-second timedelay, contactor C1Ais pow­ered and the second set of compressor windings is energized (part-wind start).
Sequence of Operation — When space thermostat
calls for cooling, the no. 1 condenser fan and compressor start after CM initial time delay of 3 (12/–1) seconds. If an optional airflow switch is used, compressor and no. 1 con­denser fan will not start until sufficient indoor airflow has closed the switch.After 3 seconds the compressor starts and the liquid line solenoid valve for solenoid drop control opens. The crankcaseheaterisdeenergized. If the head pressurereaches 260 psig (1792 kPa) the second condenser fan starts. Fan no. 3 (38AKS044 only) starts if outdoor ambient air rises above 80 F (26.7 C).
If cooling demand is low, suction pressure at the com­pressor drops. As the pressure drops, the compressor un­loads 2 banks of cylinders as required. If cooling demand is high and 2-stage operation is used, the second stage of the thermostat activates the capacity control liquid line solenoid which activates the second stage evaporator coil. The com­pressor cylinders load or unload in response to compressor suction pressure to meet evaporator load.
T wominutes after compressor starts, the BPR timer is deen­ergized and the LPS bypass is deactivated. If the LPS trips during the first 2 minutes of operation, the compressor will remain operational. If the LPS trips after 2 minutes,the com­pressor operation is interrupted, and the compressor cannot restart until the 5-minute CM anti-short cycle timer expires.
As the space cooling load is satisfied, the second stage of the thermostat opens, and closes the field-supplied capacity control liquid line solenoid valve to deactivate the second stage coil. The compressor adjusts the number of active cyl­inders to meet the new load. When the space temperature is satisfied, the first stage of the thermostat opens and the con­trol relay and the BPR open. This closes the solenoid drop control valve. The compressor stops and the crankcase heater is energized,preventingrefrigerantfrommigratingtothecom­pressor during the off cycle (solenoid drop refrigerant con­trol). The CM anti-short cycling timer is energized and runs for approximately 5 minutes. During this time, the compres­sor is not able to restart.
Complete Unit Stoppage
CAUSES — Interruption of supplied power,compressor over­temperature protection, or open HPS causes compressor stoppage.
RESTART — The unit recycles and restarts automatically under the CM when power is restored. Stoppage by HPS, or compressor circuit breaker requires manual resetting of the control circuit. Torestartthe CM timer when HPS is tripped, it is necessary to interrupt power to the unit, restarting the CM logic. It is necessary to manually reset the compressor circuit breaker at the unit.
If LPS is not closed within 2 minutes after compressor starts, the compressor locks out and the outdoor fans con­tinue to run. It stays locked out for 5 minutes until the CM anti-short cycle timer expires. After 5 minutes, the LPS is bypassed by the BPR (winter start control). It remains jum­pered for 2 minutes. Because the LPS is jumpered, the com­pressor restarts and runs for the 2-minute time period. At the end of this 2 minutes, if the LPS has still not closed, the compressor is again locked out. The outdoor fans continue to run as long as there is a call for cooling. Automatic reset of the LPS causes the CM to recycle so that the compressor can start.
If sufficientcompressoroilpressurehasnot been built within 2 minutes after the compressor starts, the unit is completely deenergized until the oil pressure switch is manually reset at the unit.
If unit or circuit stoppage occurs more than once due to any safety device, the trouble should be corrected be­fore any attempt to restart.
SERVICE
Turn off all power to unit before proceeding.
Access for Servicing (See Fig. 13)
COMPRESSOR SECTION — The compressor compart­ment has 2 side access panels and one front door for ser­vicing, providing access to compressor, all components of the refrigerant system, electrical controls, and control box. After opening front door there is an inner cover that must be removed for access to control box (except 208/230-v and 460-v units).
OIL PRESSURE SAFETY SWITCH — Switch is manually reset, and accessed by removing the side access panel on the left side of the unit (as viewed from the compressor end). See Fig. 13. The OPS is found in the compressor junction box. Open the compressor circuit breaker prior to removing the compressor junction box cover in order to access the OPS. The liquid line service valve can be found behind the side access door on the right side of the unit (as viewed from the compressor end).
CONDENSER SECTION — Condenser fan motors and fans can be serviced by removal of outlet grilles or side panels. If a fan motor is serviced, be sure the wire fan guard is in place over each fan before starting unit. See Fig. 14 for proper fan adjustment. Tightenfanhub securely on motor shaft with setscrew which bears against the key. Be sure to replacePer­magum and rubber cap over end of motor shaft to protect against moisture causing fan to rust on shaft.
17
Page 18
TRAN1
CM
CR1
FC
FC3
FC2
COMPRESSOR END AND RIGHT-SIDE VIEW
TRAN2
C1
TB2
CB2
CB1
TB3
COMPRESSOR END, CONTROL PANEL REMOVED
LIQUID LINE SERVICE VALVE
OIL PRESSURE SAFETY SWITCH
COMPRESSOR END, LEFT-SIDE ACCESS DOOR
(JUNCTION BOX COVER REMOVED)
Fig. 13 — 38AKS Unit with Access Panels Removed
COMPRESSOR END, RIGHT-SIDE ACCESS DOOR
18
Page 19
Fan Adjustment — Adjust fan as shown in Fig. 14.
NOTE: Dimension in ( ) is in millimeters.
Capacity Control — Capacity control is by 2 suction
pressure actuated unloaders. Each controls 2 cylinders. Un­loaders are factory set (see Table 1Aor 1B) but may be field adjusted. Number 1 unloader is on cylinder bank on same side of compressor as terminal box.
CONTROL SET POINT — The control set point (cylinder load point) is adjustable from 0 to 85 psig (0 to 586 kPag). T oadjust, turn control set point adjustment nut (Fig. 15) clock­wise to its bottom stop. In this position, set point is 85 psig (586 kPag). Then, turn adjustment counterclockwise to desired control set point. Every full turn counterclock­wise decreases set point by 7.5 psig (52 kPag).
Fig. 14 — Location of Prop on Motor Shaft from
Outside of Orifice Ring
Oil Charge — Compressors are factory charged with oil
as follows:
COMPRESSOR
06E9265 20.0 (9.4) 06E9275 20.0 (9.4) 06E9299 19.0 (9.0)
AMOUNT
pints (liters)
When additional oil or a complete charge is required, use
only Carrier-approved compressor oil:
Petroleum Specialities Inc. ..................Cryol 150
Texaco, Inc. .........................Capella WF-32
Witco Chemical Corp. ...................Suniso 3 GS
IMPORTANT: Do not use drained oil or use oil that has been exposed to atmosphere. Refer to Carrier Train­ing Booklet, GTAC II, Module 5, for procedures to add oil. To remove oil, isolate the compressor, reclaim internal compressorcharge,anduse the compressor drain plug.
Liquid Shutoff/Charging Valve — Valve is located
inside the compressor compartment and is provided with
1
⁄4-in. flare connection for field charging.
Fig. 15 — Capacity Control Valve
PRESSURE DIFFERENTIAL — The pressure differential (difference between cylinder load and unload points) is ad­justable from 6 to 22 psig (41 to 152 kPag). To adjust, turn pressure differential adjustment screw (Fig. 15) counter­clockwise to its backstop position. In this position, differ­ential is 6 psig (41 kPag). Then, turn adjustment clockwise to desired pressure differential. Every full turn clockwise in­creases differential by 1.5 psig (10 kPag).
19
Page 20
Oil Pressure Safety Switch (OPS) — The OPS in
the control circuit stops the compressor and unit, if proper oil pressure differentialis not established at start-up or main­tained during operation. If OPS stops the unit, determine the cause and correct before restarting unit. Failure to do so will constitute abuse. Equipment failure due to abuse may void
the warranty.
Compressor Protection
CIRCUIT BREAKER — Calibrated trip manual reset, am­bient compensated, magnetic breaker protects against motor overload and locked rotor conditions.
CONTROLMODULETIMER—This controlprotectscom­pressor against short cycling. See Sequence of Operation on page 17.
CRANKCASE HEATER — This minimizes absorption of liquid refrigerant by oil in crankcase during brief or ex­tended shutdown periods.
IMPORTANT: Never open any switch or disconnect that deenergizes the crankcase heater unless unit is be­ing serviced or is to be shut down for a prolonged pe­riod. After a prolonged shutdown on a service job, en­ergize the crankcase heater for 24 hours before starting the compressor.
High-Pressure Switch — This switch has fixed, non-
adjustable settings. Switch is mounted on the compressor (See Table 4).
Low-Pressure Switch — This switch has fixed, non-
adjustable settings. Switch is mounted on the compressor. (See Table 4.)
Head Pressure Control — Control maintains ad-
equate dischargepressureunderlowambienttemperaturecon­ditions. See Table 5.
FAN CYCLING — These 38AKS units have standard pro­vision for fully automatic intermediate-season head pressure control through condenser fan cycling. Fan no. 2 is cycled by a fan cycling pressure switch (FCPS) which responds to variation in discharge pressure. The pressure sensor is lo­cated in the liquid line of the refrigerant circuit. Fan no. 3 cycling is controlled by outdoor-air temperature through an air temperature switch (ATS) (38AKS044 units only).
Table 5 — Minimum Outdoor-Air
Operating Temperature
UNIT
38AKS
028
034
044
COMPR
CAP. (%)
100 90 (32) 31 (–1) –20 (–29)
67 80 (27) 35 (2) –20(–29) 33 70 (21) 43 (6) –20(–29)
100 90 (32) 30 (–1) –20 (–29)
67 80 (27) 34 (1) –20(–29) 33 70 (21) 42 (6) –20(–29)
100 90 (32) 25 (–4) –20 (–29)
67 80 (27) 30 (–1) –20 (–29) 33 70 (21) 35 (2) –20(–29)
COND TEMP,
F (C)
TheATS is located in the lower divider panel between the compressor compartment and condenser section. Through a hole in the panel, the sensing element is exposed to air en­tering the no. 1 fan compartment. Fan no. 1 is noncycling. Table 6 shows the operating settings of the FCPS and the ATS.
MIN OUTDOOR TEMP, F (C) Standard
Unit
Low Ambient
Control
(MotormasterT)
Table 4 — Pressure Switch Settings, psig (kPa)
HIGH PRESSURE LOW PRESSURE
Cutout Cut-in Cutout Cut-in
426±7
(2937 ± 48)
320±20
(2206 ± 138)
27±3
(186 ± 21)
44±5
(303 ± 34)
Winter Start Control — Bypass relay timer bypasses
low-pressure switch for 2 minutes on unit start-up.
Table 6 — Fan Cycling Controls
CONTROL BY SWITCH OPENS SWITCH CLOSES
Temp, F (C) 70 ± 3 (21 ± 1.7) 80 ± 3 (27 ± 1.7)
Pressure,
psig (kPa)
NOTE: See Fig. 6 and 7 for fan arrangement.
160 ± 10 (1103 ± 69) 260 ± 15 (1793 ± 103)
20
Page 21
TROUBLESHOOTING
SYMPTOM AND PROBABLE CAUSE PROBABLE REMEDY COMPRESSOR DOES NOT RUN
1. Control circuit breaker tripped 1. Reset control circuit breaker
2. Power line open 2. Reset circuit breaker
3. Oil pressure switch tripped 3. Reset oil pressure switch at unit
4. Safety device tripped 4. Reset control circuit with thermostat
5. Contactor stuck open 5. Replace contactor
6. Loose terminal connection 6. Check connections
7. Improperly wired controls 7. Check and rewire
8. Seized compressor 8. Check motor winding for open or short.
9. Low line voltage 9. Check line voltage — determine location of
10. Compressor motor defective 10. Check motor winding for open or short.
COMPRESSOR STOPS ON LOW-PRESSURE CONTROL
1.Compressorsuctionshutoffvalvepartiallyclosed 1. Open valve
2. Low refrigerant charge 2. Add refrigerant
3. Liquid line solenoid valve(s) fails to open 3. Check liquid line solenoid valve for proper
4. Liquid line shutoff valve closed 4. Open valve
COMPRESSOR STOPS ON HIGH-PRESSURE CONTROL
1. Compressor discharge valve partially closed 1. Open valve or replace if defective
2. Air in system 2. Purge and evacuate system
3. Condenser fan(s) not operating 3. Check motor wiring and repair or replace if
4. System is overcharged. 4. Reclaim charge as needed
UNIT OPERATES TOO LONG OR CONTINUOUSLY
1. Low refrigerant charge 1. Add refrigerant
2. Control contacts fused 2. Replace control
3. Air in system 3. Purge and evacuate system
4. Partially plugged expansion valve or filter drier 4. Clean or replace
SYSTEM IS NOISY
1. Piping vibration 1. Support piping as required
2. Compressor noisy 2. Check valve plates for valve noise. Replace
COMPRESSOR LOSES OIL
1. Leak in system 1. Repair leak
2. Crankcase heaters not energized during 2. Check wiring and relays. Check heater and shutdown replace if defective
3. Improper interconnecting piping design 3. Check piping for oil return. Replace if
FROSTED SUCTION LINE
1. Expansion valve admitting excess refrigerant 1. Adjust expansion valve
HOT LIQUID LINE
1. Shortage of refrigerant due to leak. 1. Repair leak and recharge
2. Expansion valve opens too wide 2. Adjust expansion valve
FROSTED LIQUID LINE
1. Restricted filter drier 1. Remove restriction or replace
COMPRESSOR WILL NOT UNLOAD
1. Defective unloader 1. Replace
2. Defective capacity control solenoid valve 2. Replace valve
3. Miswired liquid line solenoid 3. Rewire correctly
4. Weak, broken, or wrong valve body spring 4. Replace spring
COMPRESSOR WILL NOT LOAD
1. Miswired capacity control liquid solenoid 1. Rewire correctly
2. Defective capacity control solenoid valve 2. Replace valve
3. Plugged strainer (high side) 3. Clean or replace strainer
4. Stuck or damaged unloader piston or piston 4. Clean or replace the necessary parts ring(s)
Replace compressor, if necessary voltage drop and remedy deficiency Replace compressor, if necessary
operation. Replace if necessary
defective
compressor if bearings are worn
necessary
21
Page 22
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover:
• Unit Familiarization
• Installation Overview
A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included.
• Maintenance
• Operating Sequence
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 3a
PC 111 Catalog No. 533-820 Printed in U.S.A. Form 38A-5SI Pg 22 7-94 Replaces: 38AK-3SI
Page 23
START-UP CHECKLIST
(Remove and store in job file)
A. Preliminary Information
OUTDOOR:MODELNO. SERIALNO. INDOOR: AIR HANDLER MANUFACTURER
MODEL NO. SERIAL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)
CUT ALONG DOTTED LINE
CONTROLS
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N) ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N) ARE PROPER AIR FILTERS IN PLACE? (Y/N) HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
PIPING
ARE LIQUID LINE SOLENOID VALVE(S) LOCATED AT THE EVAPORATOR COIL AS REQUIRED? (Y/N) HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR,
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS. HAVEALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N) ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING ABOUT1⁄2FULL? (Y/N)
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB V AC V BC V (AB + AC + BC)/3 = AVERAGE VOLTAGE = V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = % IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
CL-1
----------------------------------------------------------------------------------------
Page 24
C. Start-Up
CHECK EVAPORATOR FAN SPEED AND RECORD. CHECK CONDENSER FAN SPEED AND RECORD. AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEAVING CONDENSER AIR TEMP EVAP ENTERING AIR DB TEMP EVAP ENTERING AIR WB TEMP EVAP LEAVING AIR DB TEMP EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS (L1) COMPRESSOR AMPS (L2) COMPRESSOR AMPS (L3)
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING OIL LEVEL AT1⁄8TO1⁄3FULL? (Y/N)
NOTES:
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 3a
PC 111 Catalog No. 533-820 Printed in U.S.A. Form 38A-5SI Pg CL-2 7-94 Replaces: 38AK-3SI
Loading...