Carrier 38AKS028-044 User Manual

Air-Cooled Condensing Units
Installation, Start-Up and
Service Instructions
CONTENTS
38AKS028-044
50/60 Hz
Page
SAFETY CONSIDERATIONS ...................1
BEFORE INSTALLATION .....................1-3
Rigging ......................................1
Placing Unit .................................3
Mounting Unit ...............................3
INSTALLATION .............................3-12
Refrigerant Piping Connections ...............3
Filter Drier and Moisture Indicator ............3
Power Supply ................................6
Power Wiring ................................6
START-UP ................................13-17
Leak Test and Dehydration ..................13
Preliminary Charge ..........................13
Start Unit ...................................13
Charge System .............................13
Operation ...................................13
Control Module (CM) ........................13
Bypass Relay (BPR) .........................17
Time-Delay Relay (TDR) .....................17
SERVICE ..................................17-20
Access for Servicing ........................17
Fan Adjustment .............................19
Oil Charge ..................................19
Oil Pressure Safety Switch (OPS) ............20
Compressor Protection ......................20
High-Pressure Switch .......................20
Low-Pressure Switch ........................20
Head Pressure Control ......................20
START-UP CHECKLIST .....................CL-1
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.).
Only trained, qualified installers and service mechanics should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep, quenching cloth and fire extinguisher nearby when
brazing.
• Use care in handling, rigging, and setting bulky
equipment.
• See Table 1A or 1B for physical data.
ELECTRIC SHOCK HAZARD Open all remote disconnects before
servicing this equipment.
BEFORE INSTALLATION
Rigging —
above the unit. Use 2-in. (50 mm) OD pipe or hooks in lift­ing holes. Rig with 4 cables and spreader bars. All panels must be in place when rigging. See rigging label on unit for details concerning shipping weights, distance between lift­ing holes, center of gravity, and spreader bar dimensions. See Fig. 2.
If overhead rigging is not possible, place unit on skid or pad for rolling or dragging. When rolling, use minimum of 3 rollers. When dragging, pull the pad. Do not apply force to the unit. When in final position, raise from above to lift unit off pad.
Preferred method is with spreader bars from
All panels must be in place when rigging.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 3a
PC 111 Catalog No. 533-820 Printed in U.S.A. Form 38A-5SI Pg 1 7-94 Replaces: 38AK-3SI
Table 1A — Physical Data — English
UNIT 38AKS 028 034 044
COMPRESSOR Reciprocating Semi-Hermetic
No. ...Type 1...06E9265 1...06E9275 1...06E9299
No. Cyls (ea)...Speed, Rpm (60/50 Hz) 6...1750/1460 Capacity Steps 3 Oil Charge*, Pt 20.0 20.0 19.0
Oil Pressure Switch (psi)
Set Points — Cutout 6 6 2
Differential — Cut-in 14 Max. Crankcase Heater (watts) 180 Protection See Note Capacity Control (Psig) Suction Pressure Unloader(s) No. 1 Unloader Settings
Load 76 76 76
Unload 58 58 58 No. 2 Unloader Settings
Load 78 78 78
Unload 60 60 60 REFRIGERANT CHARGE, R-22
Approximate lb 30.5 43.5 65 COIL STORAGE
(at 125 F liquid temperature
and 80% full), lb CONDENSER FANS, Type Propeller Type, Direct Driven
No. ...Diameter, in. 2...30 3...30
Total Airflow, Cfm 15,700 23,700 Speed, Rpm 60/50 Hz 1140/950
CONDENSER COIL, Type Horizontal Plate Fin Rows...Fins/in. 2...19 3...17 3...17 Total Face Area, sq ft 39.2 39.2 58.4
*See Service, Oil Charge, for Carrier-approved oil. NOTE: Circuit breaker is in main power circuit.
37.7 56.6 84.4
Table 1B — Physical Data — SI
UNIT 38AKS 028 034 044
COMPRESSOR Reciprocating Semi-Hermetic
No. ...Type 1...06E9265 1...06E9275 1...06E9299
No. Cyls (ea)...Speed, R/s (60/50 Hz) 6...29.2/24.3 Capacity Steps 3 Oil Charge*, L 9.4 9.4 9.0
Oil Pressure Switch (kPa)
Set Points — Cutout 41.4 6 13.8
Differential — Cut-in 96.5 Max. Crankcase Heater (watts) 180 Protection See Note Capacity Control (kPa) Suction Pressure Unloader(s) No. 1 Unloader Settings
Load 524 524 524
Unload 400 400 400 No. 2 Unloader Settings
Load 538 538 538
Unload 414 414 414 REFRIGERANT CHARGE, R-22
Approximate, kg 13.8 19.7 29.5 COIL STORAGE
(at 52 C liquid temperature
and 80% full), kg CONDENSER FANS, Type Propeller Type, Direct Driven
No. ...Diameter, mm 2...762 3...762
Total Airflow, L/s 7,400 11,200 Speed, R/s (60/50 Hz) 19.0/15.8 19.0/15.8
CONDENSER COIL, Type Horizontal Plate Fin Rows...Fins/mm 2...1.34 3...1.49 3...1.49 Total Face Area, sq m 3.64 3.64 5.43
*See Service, Oil Charge, for Carrier-approved oil. NOTE: Circuit breaker is in main power circuit.
17.1 25.7 38.3
2
Placing Unit — There must be 4 ft (1220 mm) for ser-
vice on all sides of unit, and a minimum of 8 ft (2440 mm) clear air space above unit. For multiple units, allow 8 ft (2440 mm) separation between units for airflow and service.
Mounting Unit — When unit is in proper location, use
of mounting holes in base rails is recommended for securing unit to supporting structure or for mounting unit on vibra­tion isolators, if required. Fasteners for mounting unit are field supplied. Be sure to mount unit level to ensure proper oil return to compressors.
Compressor Mounting — As shipped, compressor
is held down by 4 bolts. After unit is installed loosen each bolt using nut indicated in Fig. 3 until flatwasher (3⁄8in. [9.5 mm]) can be moved with finger pressure.
Fig. 1 — 38AKS Units
NOTES:
1. Use 2 in. OD (50 mm) pipe or hooks in lifting holes.
2. Rig with 4 cables and spread with 2 ‘‘D’’ long and two ‘‘A’’ long 2 x 4’s in. (50 x 100 mm) or equal.
3. Run the rigging cables to a central suspension point so that the angle from the horizontal is not less than 45 degrees.
All panels must be in place when rigging.
MAX SHIP.
UNIT
38AKS
028 1924 872 81 2057 43.0 1092 28.0 711 73.5 1867 034 2115 960 81 2057 43.0 1092 28.0 711 73.5 1867 044 2797 1207 99 2515 49.0 1245 30.5 775 73.5 1867
WT
Lb Kg in. mm in. mm in. mm in. mm
LIFTING
HOLES
CENTER OF GRAVITY
‘‘A’’
‘‘B’’ ‘‘C’’
‘‘D’’
INSTALLATION
Refrigerant Piping Connections—
pend on length of piping required between condensing unit and evaporator. See Table 2A or 2B. It is important to con­sider liquid lift and compressor oil return. Refer to Part 3 of Carrier System Design Manual for line sizing information, and Fig. 4 for recommended piping details.
Line sizes de-
Liquid Line Solenoid Drop Control — The factory-
supplied solenoid valve must be installed at the indoor unit (fan coil) per Fig. 5, and wired per wiring label found on unit. The solenoid assures that system refrigerant is in the high-pressure side (condenser and liquid line) of the system during the off cycle. Refrigerant migration is minimized.
Factory-supplied liquid line solenoid valve connecting sizes
7
⁄8-in. (22.2 mm) ODF for inlet and7⁄8-in. (22.2 mm)
are ODM for outlet.
Failure to properly install liquid line solenoid at the in­door unit as described, without Carrier authorization, may VOID warranty.
Filter Drier and Moisture Indicator — Every unit
should have a filter drier and a sight glass (moisture indi­cator) field installed. Select the filter drier for maximum unit capacity and minimum pressure drop. Figure 5 shows rec­ommended locations of filter drier(s) and sight glass. Com­plete the refrigerant piping from the evaporator to the con­denser before opening the liquid and suction lines at the condensing unit. One filter drier may be installed at location A in Fig. 5, or 2 filter driers may be installed at locations B.
Fig. 2 — Rigging with Spreader Bars
(Field Supplied)
3
NOTE: All dimensions are in inches (mm).
Fig. 3 — Compressor Mounting
TXV — Thermostatic Expansion Valve
NOTES:
1. Suction line is connected to coil on same side as the entering air.
2. Lower section is first on and last off.
3. For more complete piping information, refer to Carrier System Design Manual, Part 3.
Fig. 4 — Suction Line Piping to Unit
with 2 Section Coil Split
TXV — Thermostatic Expansion Valve
Fig. 5 — Liquid Line Solenoid Valve,
Filter Drier(s) and Sight Glass Locations
Receiver — No receiver is provided with the unit; it is
recommended that one not be used.
Piping Procedure — Do not remove run-around pipe
from suction and liquid line stubs until piping connections are ready to be made. Pass nitrogen or other inert gasthrough piping while brazing, to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve (TXV) in liquid line ahead of each evaporator section. For 2-stage cooling, the field-supplied capacity controlsolenoidusedmust
be wired to be opened by control from a 2-stage thermostat.
SUCTION PIPING AT EVAPORATOR AND TXV BULB LOCATION (See Fig. 5) — The purpose of these recom­mendations is to achieve good mixing of the refrigerant leav­ing the evaporator suction header for proper sensing by the TXV bulb.
1. A minimum of two 90° elbows must be installed up-
stream of the expansion valve bulb location.
2. The TXV sensing bulb should be located on a vertical
riser where possible. If a horizontal location is necessary, secure the bulb at approximately the 4 o’clock position.
3. Size the suction line from the evaporator throughthe riser
for high velocity. Enter the suction pipe sizing charts in the CarrierSystemDesignManual at design tons and equiva­lent length (for 2° F [1.1° C] loss). If reading falls be­tween 2 sizes on chart, choose the smaller pipe size.
Suction piping for the high velocity section should be selected for about 0.5° F (0.3° C) friction loss. If a 2° F (1.1° C) loss is allowed for the entire suction line, 1.5° F (0.8° C) is left for the balance of the suction line, and it should be sized on that basis. Check that the high-velocity sizing
is adequate for oil return up the riser.
If an oil return connection at the bottom of this suction header is supplied with an evaporator, this connection must be teed-in ahead of first mixing elbow. When the compres­sor is below the evaporator, the riser at the evaporator does not have to extend as high as the top level. After a 15-diameter riser has been provided, the suction line may elbow down immediately.
SAFETY RELIEF — Afusible plug is located on unit liquid line before the liquid valve.
4
Table 2A — Refrigerant Piping Sizes — 60 Hz
SINGLE SUCTION RISERS
UNIT
38AKS
028 034 044
L—Liquid Line S—Suction Line
16-25 (4.9-7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2-30.5) 101-200 (30.8-60.9)
LSL S L S L S L S
7
8
7
8
7
8
15⁄ 21⁄ 21⁄
8 8 8
7
8
7
8
7
8
*IMPORTANT — Requires a double suction riser, if evaporator is below condensing unit. See table below. NOTE: Liquid and suction line sizes are OD (in.) Equivalent sizes in mm are listed below.
LENGTH OF INTERCONNECTING PIPING, FT (M)
21⁄8* 21⁄ 21⁄
7
8
11⁄
7
8
8
8 8
21⁄8* 21⁄
8
25⁄8*1
7
8
11⁄
8
1
8
21⁄8* 21⁄
8
5
2
8
*1
DOUBLE SUCTION RISERS — 60 Hz
UNIT
38AKS
028 1
26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2.-30.5) 101-200 (30.8-60.9)
ABCABC A B C A B C
3
8
15⁄
8
21⁄
8
034 —————— — — —1 044 ———1
NOTE: A, B, C dimensions relate to reference diagram.
LENGTH OF INTERCONNECTING PIPING, FT (M)
13⁄
8
15⁄
8
21⁄
5
⁄82
1
⁄82
8
5
⁄81
13⁄
8
5
⁄82
15⁄
8
1
⁄82
21⁄
8
5
⁄81
Table 2B — Refrigerant Piping Sizes — 50 Hz
SINGLE SUCTION RISERS
UNIT
38AKS
028 034 044
L—Liquid Line S—Suction Line
*IMPORTANT — Requires a double suction riser, if evaporator is below condensing unit. See table below.
†For riser, use 1
16-25 (4.9-7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2-30.5) 101-200 (30.8-60.9) LSL S L S L S L S
7
8
7
8
7
8
5
⁄8OD inches.
15⁄
21⁄8†
21⁄
8
8
7
8
7
8
7
8
NOTE: Liquid and suction line sizes are OD (in.) Equivalent sizes in mm are listed below.
LENGTH OF INTERCONNECTING PIPING, FT (M)
21⁄8* 21⁄8* 21⁄
7
8
7
8
8
11⁄
8
21⁄8* 21⁄8*1 25⁄8*1
7
8
1
8
1
8
21⁄8*
5
2
8
*1
5
2
8
*1
7
8
11⁄
8
1
8
13⁄
8
5
⁄82
5
⁄82
15⁄
8
1
⁄82
1
⁄82
7
8
1
8
1
8
21⁄8* 25⁄8*
5
2
8
*
21⁄
8
5
8
5
8
21⁄8*
5
2
8
*
5
2
8
*
DOUBLE SUCTION RISERS — 50 Hz
UNIT
38AKS
028 1 034 15⁄
26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2.-30.5) 101-200 (30.8-60.9)
ABCABC A B C A B C
3
8
15⁄
8
21⁄
8
8
15⁄
8
21⁄
8
044 ———1
NOTE: A, B, C dimensions relate to reference diagram.
Unit Size Dimension — in. (mm)
028 15⁄8(41.3) 034 21⁄8(54.0) 044 21⁄8(54.0)
LENGTH OF INTERCONNECTING PIPING, FT (M)
13⁄
8
15⁄
8
5
⁄82
15⁄
8
21⁄
8
15⁄
8
21⁄
1
⁄82
8
5
⁄81
13⁄
8
15⁄
8
5
⁄82
15⁄
8
15⁄
8
1
⁄82
21⁄
8
21⁄
8
5
⁄81
13⁄
8
15⁄
8
5
⁄82
MAXIMUM LIQUID LIFT
UNIT 38AKS
028 76 23 66 20 034 67 20 60 18 044 76 23 66 20
EQUIVALENT SIZES IN MM
60 Hz 50 Hz
FtMFtM
in. mm
7
⁄ 11⁄ 13⁄ 1 21⁄ 2
8
8 8
5
8 8
5
8
22.2
28.6
34.9
41.3
54.0
66.7
15⁄
8
21⁄
8
1
⁄82
21⁄
8
25⁄
8
5
8
5
Power Supply — Electrical characteristics of available
power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in Table 3.
IMPORTANT:Operatinguniton improper supply volt­age, orwithexcessivephaseimbalance,constitutes abuse and mayaf fectCarrier warranty.SeeUnbalanced3-Phase Supply Voltage, page 7.
Power Wiring — All power wiring must comply with
applicable localandnationalcodes.Install field-supplied branch circuit fused disconnect(s) per NEC (National Electrical Code, U.S.A.) of a type that can be locked OFF or OPEN. Dis­connect(s) must be within sight from and readily accessible from unit in compliance with NEC Article 440-14.
GENERAL WIRING NOTES
1. A crankcase heater is wired in the control circuit so it is always operable as long as power supply disconnect is on, even if any safety device is open or unit stop-start switch is off. It is protected by a 5-amp circuit breaker in control power.
2. The power circuit field supply disconnect should never be
open except when unit is being serviced or is to be down for a prolongedperiod.Whenoperationisresumed, crank­case heater should be energized for 24 hours before start­up. If unit is to be shut down for a prolonged period, it is recommended that the suction and discharge valves be
closed to prevent an excessive accumulation of refriger­ant in the compressor oil.
3. Power entry is one end only.
4. Maximum field wire sizes allowed by lugs on terminal block are:
UNIT
38AKS
028 208/230-3-60 034
044
LEGEND
AWG — American Wire Gage kcmil — Thousand Circular Mils
*All other units use 2/0 AWG (67.4 mm
V-Ph-Hz
208/230-3-60
230-3-50
208/230-3-60
230-3-50
2
).
WIRE SIZE*
350 kcmil
5. Terminals for field power supply are suitable for copper, copper-clad aluminum, or aluminum conductors. Insula­tion must be rated 167 F (75 C) minimum.
CONDENSER FANS— The fans must rotate counterclock­wise when viewed from above. If necessary, correct direc­tion of fan rotation by interchanging any 2 powerinput wires at disconnect switch. Affix crankcase heater decal (located in installer’s packet) to unit disconnect switch.
Table 3 — Electrical Data
60 HZ
UNIT
38AKS
500
028
034
044
028
034
044
CSA Canadian Standards Association FLA Full Load Amps ICF Maximum InstantaneousCurrentFlow duringstarting(the point
LRA Locked Rotor Amps MCA Minimum Circuit Amps (complies with National
MOCP — Maximum Overcurrent Protection RLA Rated Load Amps UL Underwriters’ Laboratories
200 600 100
500 200 600 100
500 200 600 100
UNIT
38AKS
800 300 900
800 300 900
800 300 900
inthestarting sequence wherethesum oftheLRA forthe start­ing compressor,plus the total FLA for allrunningfanmotors is maximum).
Electrical Code [NEC, U.S.A.], Section 430-24)
3 Ph, 60 Hz
208/230
208/230
3 Ph, 50 Hz
LEGEND
Volts
380 460 575
380 460 575
230 380 460 575
Volts
230 346 400
230 346 400
230 346 400
Supplied*
Min. Max.
187 342 414 518
187 342 414 518
187 342 414 518
Supplied*
Min. Max.
198 311 342
198 311 342
198 311 342
UNIT COMPRESSOR FAN MOTORS
MCA
254 418 508 632
254 418 508 632
254 418 508 632
124.6
64.7
60.7
52.5
145.5
72.5
68.7
54.9
203.0
111.1
91.0
81.5
50 HZ
UNIT COMPRESSOR FAN MOTORS
MCA
254 380 400
254 380 400
254 380 400
109.0
64.9
60.5
120.2
76.1
68.5
150.6
112.6
90.8
MOCP (Fuse)
200 110 100
80
250 125 110
90
350 175 150 125
MOCP (Fuse)
175 100 100
200 125 110
250 175 150
*Units are suitable for use on electrical systems where voltage sup-
ICF RLA LRA FLA (ea) Qty
452.2
250.9
226.1
167.4
512.2
283.9
256.1
179.4
702.4
389.8
351.2
282.8
ICF RLA LRA FLA (ea) Qty
348.4
263.4
226.0
372.4
298.4
256.0
557.8
408.8
351.0
pliedtounit terminals isnotbelow orabovelisted minimum andmaxi­mum limits.
89.8
45.5
43.6
36.5
106.5
52.6
50.0
38.5
147.5
79.5
65.4
57.1
76.9
44.9
43.6
85.9
53.9
50.0
105.1
79.5
65.4
446 247 223 164
506 280 253 176
690 382 345 276
342 259 223
366 294 253
545 400 345
6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4
6.4
4.4
3.0
6.4
4.4
3.0
6.4
4.4
3.0
2 2 2 2
2 2 2 2
3 3 3 3
2 2 2
2 2 2
3 3 3
6
FIELD CONNECTIONS
1. Main Power — Bring wires from the fused disconnect switch through hole in bottom rail of unit to control box
12
(Fig. 6 and 7) and connect terminals , , and
line side of terminal block TB1 (see Fig. 8 and 9A
13
11
or 9B). To comply with NECArticle 440-14, the discon­nect must be located within sight from and readily ac­cessible from unit.
2. 24-v ControlPower—Unitshavesinglepointpower con­nections. Control circuit is directly connected internally to unit. Maximum 24-v control circuit is 3 amps.
NOTE: Wire runs use the following insulated wire:
LENGTH
0-50 18 0.82
50-75 16 1.30
Over 75 14 2.08
AWG — American Wire Gage
*35 C minimum.
INSULATED WIRE SIZE*
AWG mm
2
3. Control Circuit Interlock — An airflow switch may be installed in the indoor air handler to prevent unit from running when indoor air is not flowing. This switch (no. HR81JE001) is available from Service Parts Center, or equivalent can be field supplied. This should be electri­cally interlocked in the control circuit, between thermo-
2
stat TC1 (stage 1, cooling) and terminal on TB3.
Y1
See Fig. 8 for typical field wiring. This is in the 24-v cir­cuit. Wires must be run in conduit with ground wire.
4. Transformer Connections — See unit wiring label dia­gram, notes 1 and 2, located behind compressor compart­ment end access door.
IMPORTANT: Ensure power to the crankcase heater is always on (except when servicing the unit). If cir­cuit breakerinsideunitshutsdown the compressor,crank­case heater remains on.
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance:
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 240-3-60.
AB = 243 v BC = 236 v AC = 238 v
Average Voltage =
243 + 236 + 238
3
= 239 volts Determine maximum deviation from average voltage: (AB) 243 − 239=4v
(BC) 239 − 236=3v (AC) 239 − 238=1v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
4
239
= 1.7%
This amount of phase imbalance is satisfactory as it is be-
low the maximum allowable 2%.
IMPORTANT: Contact your local electric utility com­pany immediately if the supply voltage phase imbal­ance is more than 2%.
7
LEGEND
NEC — National Electrical Code VAV — Variable Air Volume
NOTES:
1. There must beminimum(2440mm) 8 ft. clear air spaceabove unit.
2. The approximate operating weight of the unit is:
50 AND 60 HZ
UNIT
38AKS028 1650 748 38AKS028C 1804 818 38AKS034 1803 818 38AKS034C 2009 911
3. A ‘‘C’’in the model number indicates unit has factory-installed copper coil.
WT
(Lb)WT(Kg)
Fig. 6 — Dimensional Drawing, 38AKS028,034
8
Loading...
+ 16 hidden pages