Carrier 35L user guide manual

35L,N Dual Duct Terminal Units
Variable Volume System
Installation and Start-Up Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
General ..........................................2
Warranty ......................................... 2
CONTROL ARRANGEMENTS................... 2-7
Analog Electric Control Arrangement ............ 3
Direct Digital Electronic Control
Arrangement (Field Supplied)................... 3
Pneumatic Control Arrangement .................3
No Control ....................................... 3
INSTALLATION ................................. 3-6
Step 1 — Install Volume Control Box .............3
Step 2 — Make Duct Connections ................3
Step 3 — Install Sensors and Make Field
Wiring Connections — Electronic Analog
or DDC (Direct Digital Controls) ................3
CONTROL SET UP ..............................6,7
General ..........................................6
Set Points ........................................6
Field Adjustments of Minimum and
Maximum Airflow Set Points ................... 6
System Calibration of the Linear Averaging
Flow Probe.....................................6
PNEUMATIC CONTROLS ........................7,8
Balancing Procedure
(Control Sequences 1500-1523) ................ 7
Pneumatic Control Troubleshooting..............8
Balancing Procedures
(Control Sequences 2400, 2440 and 2470) ......9
Applications for Dual Duct (Minimum Air
from Cold Duct) .................................. 9
Analog Control Troubleshooting ................ 10
Install Sensors and Make
Field-Wiring Connections .....................10
• GENERAL
• SUPPLY-AIR TEMPERATURE SENSOR
INSTALLATION
• SPACE TEMPERATURE SENSOR INSTALLATION
AND WIRING
• WIRING THE SPACE TEMPERATURE SENSOR
AND SET POINT ADJUSTMENT SLIDEBAR
• WIRINGTHECCNNETWORKCOMMUNICATION
SERVICE JACK
• PRIMARY AIR TEMPERATURE SENSOR
INSTALLATION
• INDOOR-AIR QUALITY SENSOR INSTALLATION
• INDOOR-AIR QUALITY SENSOR WIRING
• HUMIDITY SENSOR (Wall-Mounted) INSTALLATION
Connect the CCN Communication Bus..........15
• COMMUNICATION BUS WIRE SPECIFICATIONS
• CONNECTION TO THE COMMUNICATION BUS
• GENERAL
• PRIMARY SYSTEM CHECK
• COMFORTID CONTROL SYSTEM CHECK
CCN System Start-Up ........................... 17
• COMFORTID TEST AND BALANCE TOOL SOFTWARE
• COMFORTID CONSTANT VOLUME DUAL DUCT CONTROL PACKAGE NO. 4160
• COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH CONSTANT MINIMUM COLD DECK AIRFLOW CONTROL PACKAGE NO. 4170
• COMFORTID VARIABLE AIR VOLUME DUAL DUCTWITHCOLDDECKCLOSE-OFFCONTROL PACKAGE NO. 4175
• COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH CONSTANT VENTILATION CONTROL PACKAGE NO. 4180
• COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH DEMAND CONTROL VENTILATION CONTROL PACKAGE NO. 4190
SAFETY CONSIDERATIONS
SAFETY NOTE
Air-handling equipment will provide safe and reliable service when operated within design specifications. The equipment should be operated and serviced only by autho­rized personnel who have a thorough knowledge of system operation, safety devicesand emergency procedures.
Good judgement should be used in applying any manu­facturer’s instructions to avoid injury to personnel or dam­age to equipment and property.
Disconnect all power to the unit before performing mainte­nance or service. Unit may automatically start if power is not disconnected. Electrical shock and personal injury could result.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3 Ta b 6 a
Catalog No. 04-53350001-01 Printed in U.S.A. Form 35L,N-1SI Pg 1 3-06 Replaces: 35L,M,N-1SI
PRE-INSTALLATION
General —
The 35L,N units are dual duct terminals avail­able with factory-installed pneumatic, analog, and Carrier ComfortNetwork®(CCN)DirectDigitalControl(DDC) control options. See Table 1. Figure 1 shows the basic box. Figure 2 is an example of a unit identification label.
Table 1 — 35L,N Units
UNIT DESCRIPTION
35L Basic unit, no mixing 35N Premium unit, high mixing, constant volume flow sensing
STORAGE AND HANDLING — Inspect for damage upon receipt. Shipping damage claims should be filed with shipper at time of delivery. Store in a clean, dry, and covered location. Do not stack cartons. When unpacking units, care should be taken that the inlet collars and externally mounted components do not become damaged. Do not lift units using collars, sensors or externally mounted components as handles. Do not lay uncrated units on end or sides. Do not stack uncrated units over 6 ft high. Do not manhandle. Do not handle control boxes by tubing connections or other external attachments. Table 2 shows component weights.
INITIAL INSPECTION — Once items have been removed from the carton, check carefully for damage to duct connec­tions, coils or controls. File damage claim immediately with transportation agency and notify Carrier.
UNIT IDENTIFICATION — Each unit is supplied with a shipping label and an identification label (Fig. 2).
INSTALLATION PRECAUTION — Check that construction debris does not enter unit or ductwork. Do not operate the central-station air-handling fan without final or construction filters in place. Accumulated dust and construction debris distributed through the ductwork can adversely affect unit operation.
SERVICE ACCESS — Provide service clearance for unit access.
CODES — Install units in compliance with all applicable code requirements.
ODS: 2181487
TAG:
FACTORY NO: 832889 ITEM: 003
MODEL NO: 35LN 06
MIN
COLD INLET CFM:
MAX
HOT INLET CFM: HAND (COLD INLET LOC):
CFGCD: 1A*0*0*0R*0606*D000*00*000*0000
0
RC
D000 CTRL BOX E
SIZE: C=06 H=06
VP: VP:
Fig. 2 — Unit Identification Label
Table 2 — 35L,N Unit Weights
UNIT SIZE
35L
35N
DDC — Direct Digital Controls
NOTE: Data is based on the following conditions:
1. Unit casing is 22 gage.
2. Unit insulation is fiberglass.
3. Units rated with standard linear flow sensor.
BASE
UNIT
(lb)
4, 5, 6 29 37 47
7, 8 33 41 51
9, 10 41 49 59
12 51 59 69 14 67 75 85 16 75 83 93 22 129 137 147
6 31 39 49
8 42 50 60 10 61 69 79 12 80 88 98 14 98 106 116 16 111 119 129
LEGEND
1
WITH
PNEUMATIC
CONTROLS
(lb)
/2-in. thick, 1.5-lb Tuf-Skin Rx™ dual density
ANALOG CONTROLS
UP
MAX
MIN
.000
.000
.000
.000
WITH DDC OR
(lb)
Fig. 1 — 35L Dual Duct Box
Warranty — All Carrier-furnished items carry the standard
Carrier warranty.
CONTROL ARRANGEMENTS
The 35L,N dual duct units are offered with a wide variety of factory-mounted controls that regulate the volume of air deliv­ery from the unit and respond to cooling and heating load requirements of the conditioned space. Stand-alone controls will fulfill the thermal requirements of a given control space. These devices are available in both pneumatic and electronic arrangements. Carrier PIC (Product Integrated Controls) is a communicating control that is integrated with the building sys­tem. The PIC controls are compatible with the CCN system. A number of DDC (Direct Digital Controls) control packages by others are available for consignment mounting, as indicated.
Control offerings are:
35(L,N)A: Analog Electronic 35(L,N)C: CCN Direct Digital Electronic 35(L,N)P: Pneumatic 35(L,N)N: None or DDC by others
Each control approach offers a variety of operating func­tions; a control package number identifies combinations of control functions. The following listings contain the basic function arrangements for each control offering. Because of the
2
variety of functions available, circuit diagrams, operating se­quences, and function descriptions are contained in separate Application Data publications. Refer to the specific control publication for details.
CCN Control Arrangement — The CCN control
packages must be used in combination with a thermostat. Ther­mostats are not included in the CCN package.
4160: Constant volume dual duct 4170: 35N only, variable volume dual duct, constant minimum
cooling (requires cold deck inlet and total flow probe) 4175: 35N only, variable volume dual duct, cooling close-off
during heating (requires hot deck inlet and total flow probe) 4180: 35N only, constant ventilation dual duct, Cooling only
(requires cold deck inlet and total flow probe) 4190: Variable air volume (VAV) with Demand Control Venti-
lation (DCV) requires separate CO
sensor
2
Analog Electronic Control Arrangement — Con-
trol package is pressure independent and includes a standard linear airflow sensor in both the hot and cold inlets for variable air volume control, 24-volt transformer, control enclosures, and a wall thermostat to match the control type.
Variable volume control: 2400 — Heating and cooling control, hot and cold inlet sensor
location (35L,N) 2440 — Heating and cooling control, hot inlet and discharge
airflow sensing (35N only) 2470 — Heating and cooling control, cold inlet and discharge
airflow sensing (35N only)
Direct Digital Electronic Control Arrangement (Field Supplied) — Control packages are field supplied
for factory mounting, unless otherwise noted. All DDC control arrangements include a standard linear inlet flow sensor, 24-volt transformer and control enclosure.
Contact Carrier for details about mounting field-supplied
controls.
Pneumatic Control Arrangement — All control pack-
ages are pressure independent and include standard linear airflow sensors in both the hot and cold inlets for variable air volume control or an airflow sensor in one inlet and the unit discharge for constant volume control arrangements. Thermo­stats will either be direct acting (DA) or reverse acting (RA), and damper position will be identified as normally open (NO) or normally closed (NC).
Variable air volume control with inlet air sensing (all units): 1500 — Multi-function controller, DA-NC cold inlet, NC
hot inlet 1501 — Multi-function controller, DA-NC cold inlet, NO
hot inlet 1502 — Multi-function controller, DA-NO cold inlet, NO
hot inlet 1503 — Multi-function controller, DA-NO cold inlet, NC
hot inlet 1504 — Multi-function controller, RA-NC cold inlet, NC
hot inlet 1505 — Multi-function controller, RA-NC cold inlet, NO
hot inlet 1506 — Multi-function controller, RA-NO cold inlet, NO
hot inlet 1507 — Multi-function controller, RA-NO cold inlet, NC
hot inlet Constant volume control with hot inlet and discharge air
sensing (35N Units): 1508 — Multi-function controller, DA-NC cold inlet, NC
hot inlet
1509 — Multi-function controller, DA-NC cold inlet, NO hot inlet 1510 — Multi-function controller, DA-NO cold inlet, NO hot inlet 1511 — Multi-function controller, DA-NO cold inlet, NC hot inlet 1512 — Multi-function controller, RA-NC cold inlet, NC hot inlet 1513 — Multi-function controller, RA-NC cold inlet, NO hot inlet 1514 — Multi-function controller, RA-NO cold inlet, NO hot inlet 1515 — Multi-function controller, RA-NO cold inlet, NC hot inlet
Constant volume control with cold inlet and discharge air sensing (35N units):
1516 — Multi-function controller, DA-NC cold inlet, NC hot inlet
1517 — Multi-function controller, DA-NC cold inlet, NO hot inlet
1518 — Multi-function controller, DA-NO cold inlet, NO hot inlet
1519 — Multi-function controller, DA-NO cold inlet, NC hot inlet
1520 — Multi-function controller, RA-NC cold inlet, NC hot inlet
1521 — Multi-function controller, RA-NC cold inlet, NO hot inlet
1522 — Multi-function controller, RA-NO cold inlet, NO hot inlet
1523 — Multi-function controller, RA-NO cold inlet, NC hot inlet
A multi-function controller is capable of providing DA-NO, DA-NC, RA-NC or RA-NO functions (all units).
No Control
0000: 35L,N box only D000: 35L,N box with control box only D001: 35L,N box with control box and transformer
INSTALLATION
Step 1 — Install Volume Control Box
1. Move unit to installation area. Remove unit from ship­ping package. Do not handle by controls or damper extension rod.
2. The unit has factory-installed brackets.
3. Suspend units from building structure with straps, rods, or hanger wires. Secure the unit and level it in each direc­tion.
Step 2 — Make Duct Connections
1. Install supply ductwork on each of the unit inlet collar. Check that air-supply duct connections are airtight and follow all accepted medium-pressure duct installation procedures. (Refer to Tables 3-5 for pressure data.)
2. Install the discharge ducts. Fully open all balancing dampers.
A straight length of inlet duct is not required before the unit inlet. Ninety-degree elbows or tight radius flexible duct imme­diately upstream of inlet collar should be avoided.
3
Step 3 — Install Sensors and Make Field Wiring Connections — Electric Analog or DDC (Direct Digital Controls) —
submittals and control application diagrams for control specifi­cations. All field wiring must comply with National Electrical Code (NEC) and local requirements. Refer to the wiring diagram on the unit for specific wiring connections.
INLET
SIZE
(0.09)
(0.14)
(0.20)
(0.27)
(0.35)
(0.44)
(0.55)
(0.78)
(1.07)
(1.40)
(2.63)
*CCN (Carrier Comfort Network®) controls permit a lower minimum flow.
NOTES:
1. P
2. To obtain Total Pressure, add the Velocity Pressure for a
CFM
(in.)
4
5
6
7
8
9
1200 0.40 0.32
10
1075 0.20 0.10 1450 0.36 0.17
12
1000 0.08 0.04 1550 0.19 0.09 2100 0.34 0.17
14
1375 0.07 0.04 2125 0.17 0.10 2900 0.31 0.19
16
1775 0.06 0.04 2725 0.14 0.10 3700 0.25 0.17
1200
22
3300 0.07 0.04 5200 0.16 0.09 7000 0.31 0.17
is the difference in static pressure across the assembly,
s
with the damper fully open.
givenCFMtotheStaticPressuredrop(∆ P configuration.
MINIMUM AIRFLOW
50 110 0.10 0.01 170 0.23 0.02 230 0.43 0.03
75 170 0.09 0.02 265 0.23 0.04 360 0.43 0.08
100 240 0.09 0.04 380 0.22 0.09 520 0.42 0.17
150 330 0.09 0.04 525 0.23 0.09 710 0.41 0.17
200 440 0.09 0.04 675 0.21 0.09 925 0.39 0.17
250 550 0.08 0.07 875 0.21 0.17
300 675 0.08 0.04
450
600
800
Refer to specific unit dimensional
Table 3 — 35L Non-Mixing Dual Duct Basic Pressure Data
(CFM)*
40
or
0
63
or
0
90
or
0
123
or
0
160
or
0
203
or
0
251
or
0
361
or
0
491
or
0
642
or
0
1211
or
0
MINIMUM CCN
AIRFLOW (CFM)
23
or
0
36
or
0
52
or
0
71
or
0
93
or
0
117
or
0
145
or
0
208
or
0
284
or
0
371
or
0
699
or
0
) of the desired
s
A field-supplied transformer is required if the unit was not
equipped with a factory-installed transformer. See Fig. 3. NOTE: Refer to wiring diagram attached to each unit for
specific information on that particular unit.
Unit airflow should not be set outside of the range noted in
Fig. 4A-4C and the performance data section of this document.
MINIMUM INLET STATIC PRESSURE
(Unit Pressure Drop) (in. wg)
Veloc it y
Pressure
V
PS
0.02 0.00
0.02 0.00
0.02 0.01
0.02 0.01
0.02 0.01
0.02 0.01
0.02 0.01
0.02 0.01
0.01 0.01
0.01 0.01
0.02 0.01
Basic
Unit P
S
MINIMUM SYSTEM OPERATING
PRESSURE (in. wg) AT
MAXIMUM LISTED FLOW RATE
0.03
0.08
0.17
0.17
0.18
0.31
0.17
0.17
0.18
0.18
0.17
4
Table 4 — 35N Dual Duct, Full Blending Basic Pressure Data — Inlet Sensor Pickup
MINIMUM INLET STATIC PRESSURE
INLET
SIZE
(Area)
6
(0.20)
8
(0.35)
10
(0.55)
12
(0.78)
14
(1.07)
16
(1.40)
*Assumes inlet flow sensor. For discharge flow sensor, use data for
next even size. CCN (Carrier Comfort Network®) controls permit a lower minimum flow. Size 16 discharge is same as inlet.
NOTES:
is the difference in static pressure across the assembly,
1. ∆P
s
with the damper fully open.
2. Minimum recommended airflow (cfm) is based on 0.03 in. wg differential pressure on the inlet sensor or 0 airflow. 0.03 in. wg is equal to 15-20% of the nominal flow rating of the terminal
MINIMUM AIRFLOW
CFM
100 240 0.06 0.16 380 0.15 0.40 520 0.28 0.72
200 440 0.06 0.15 675 0.14 0.36 925 0.26 0.68
300
675 0.05 0.20 1075 0.14 0.52 1450 0.25 0.94
450 1000 0.04 0.18 1550 0.09 0.44 2100 0.16 0.80
600 1375 0.04 0.23 2125 0.09 0.54 2900 0.17 1.01
800 1775 0.02 0.19 2725 0.04 0.44 3700 0.08 0.81
(CFM)
90
or
0
160
or
0
251
or
0
361
or
0
491
or
0
642
or
0
MINIMUM CCN
AIRFLOW (CFM)
52
or
0
93
or
0
145
or
0
208
or
0
284
or
0
371
or
0
(Unit Pressure Drop) (in. wg)
Velocity
Pressure
V
PS
Basic
Unit
P
0.01 0.03
0.01 0.03
0.01 0.04
0.01 0.04
0.01 0.04
0.00 0.04
unit. Less than 15-20% may result in greater than ±5% control of the unit airflow. Some DDC controls, supplied by others, may have different limitations.
3. Minimum airflow may be 0.
4.Maximumairflow(cfm)isbasedona1in.wgdifferential pressure from the airflow sensor.
5. To obtain Total Pressure, add the Velocity Pressure for a givenCFMtotheStaticPressuredrop(∆P configuration.
MINIMUM SYSTEM OPERATING
PRESSURE (in. wg) AT
MAXIMUM LISTED FLOW RATE
S
0.42
0.44
0.43
0.43
0.48
0.48
) of the desired
s
Table 5 — 35N Dual Duct, Full Blending — Discharge Sensor Pickup
INLET
SIZE
MAX. PRIMARY AIRFLOW (cfm)
6 927 185 or 0 93 or 0
8 1448 290 or 0 145 or 0 10 2085 417 or 0 208 or 0 12 2838 568 or 0 284 or 0 14 16
3706 741 or 0 371 or 0
CCN — Carrier Comfort Network
MINIMUM AIRFLOW
Standard CCN
5
L1
120VAC 208VAC 240VAC 277VAC
CLASS II TRANSFORMER (OPTIONAL)
ANALOG OR DDC
CONTROLLER
GROUND
24VAC
BLU YEL
24 VAC
POWER
LEGEND
DDC — Direct Digital Controls
Field Wiring
Fac to ry Wiring
NOTE: Drawing is typical — refer to actual unit wiring diagram for details.
Fig. 3 — Wiring of Optional Factory-Mounted
Transformer
10000
1000
16 inch
14 inch
CFM
100
10
12 inch
10 inch
8 inch
6 inch
0.01
FLOW PROBE PRESSURE DIFFERENTIAL IN.WG
VOLTS (ANALOG CONTROLS)
0.1
NOTE: Size 16 discharge is same as inlet.
Fig. 4B — Dual Duct Inlet Flow Probe Chart
(35N only)
3665
2840
2086
1449
927
522
CFM AT ONE INCH SIGNAL
1
10000
1000
CFM
100
10
0.01
Largest
Inlet Size
14-16"
12 "
10 "
8 "
6 "
0.1
FLOW PROBE PRESSURE DIFFERENTIAL IN.WG
VOLTS (ANALOG CONTROLS)
NOTE: Size 16 discharge is same as inlet.
Fig. 4A — Dual Duct Outlet Flow Probe Chart
(35N only)
Flow
Constant
37093709
2840
2086
1449
927
CFM AT ONE INCH SIGNAL
1
CONTROL SET UP
General —
maintain optimum temperatures in the conditioned zone by varying the air volume supplied by the hot and cold ducts while providing the proper discharge air temperature.
To balance the unit it is necessary to set both the maximum and minimum set points of the controllers. Many types of con­trol options are available, each have specific procedures re­quired for balancing the unit.
The 35L,N dual duct terminals are designed to
Set Points — Maximum and minimum airflow set points
are normally specified for the job and specific for each unit on the job. Where maximum and minimum airflow levels are not specified on the order, default values are noted on unit ID label.
Field Adjustment of Minimum and Maximum Airflow Set Points —
probe which measures a differential pressure proportional to the airflow. The relationship between flow probe pressures and cfm is shown in the Flow Probe Chart (Fig. 4A-4C). This chart is attached to each unit.
Each unit is equipped with a flow
System Calibration of the Linear Averaging Flow Probe —
operation, the velocity sensor and linear averaging flow probe must be calibrated to the controller. This will ensure that air­flow measurements will be accurate for all terminals at system start-up.
System calibration is accomplished by calculating a flow coefficient that adjusts the pressure fpm characteristics. The flow coefficient is determined by dividing the flow for a given unit (design air volume in cfm), at a pressure of 1.0 in. wg differential pressure, by the standard pitot tube coefficient of
4005. This ratio is the same for all sizes if the standard linear averaging probe is used.
Determine the design air velocity by dividing the design air volume (the flow at 1.0 in. wg) by the nominal inlet area (sq ft). This factor is the K factor.
To achieve accurate pressure independent
6
10000
8000
6000
4000
2000
1000
800
600
400
CFM
200
100
80
60
40
20
10
0.01 .03
22
SIZE
16
SIZE
14
SIZE
12
SIZE
10
SIZE
9
SIZE
8
SIZE
7
SIZE
SIZE 6
5
SIZE
4
SIZE
.05
FLOW PROBE PRESSURE DIFFERENTIAL IN. WG
0.1
0.3 0.5
7250
3709
2840
2086
1449 1174 927
710
522
362
232
1
NOTE: Size 22 available on 35L units only.
Fig. 4C — Dual Duct Inlet Flow Probe Chart
(35L only)
Carrier inlet areas are shown in Table 6. The design air volume is shown in this table. It can be determined from this table that the average design air velocity for those units is equal to 2656 fpm at 1.0-in. wg.
Table 6 — Inlet Areas
35L,N UNIT SIZE 04* 05* 06 07* 08 09*
INLET
DIAMETER
4.0 5.0 6.0 7.0 8.0 9.0
CFM AT 1 IN. WG 232 362 502 710 927 1174
INLET AREA
(sq ft)
.
0.087 0.136 0.196 0.267 0.349 0.442
35L,NUNITSIZE1012141622*
INLET DIAMETER 10.0 12.0 14.0 16.0 16 x 24
CFM AT 1 IN. WG 1449 2086 2840 3709 7250
INLET AREA
(sq ft)
0.545 0.785 1.069 1.396 2.640
*35L units only. NOTE: For Carrier ComfortID™ terminals, all flow sizes are normal-
ized using a single Probe Multiplier (PMF) for all sizes equal to
2.273.
PNEUMATIC CONTROLS
All control packages are pressure independent and include standard linear airflow sensors in both the hot and cold inlets for variable air volume control (control sequence 1500 to 1507) or an airflow sensor in one inlet and unit discharge for constant volume control arrangements (control sequence 1508 to 1523).
Preparation for Balancing
1. Inspect all pneumatic connections to assure tight fit and proper location.
2. Verify that the thermostat being used is compatible with the control sequence provided (direct acting or reverse acting).
3. Check main air pressure at the controller(s). The main air pressure must be between 15 psi and 25 psi. (If dual or
CFM AT ONE INCH SIGNAL
switched-main air pressure is used, check the pressure at both high and low settings.) The difference between “high” pressure main and “low” pressure main should be at least 4 psi, unless otherwise noted, and the “low” set­ting difference should exceed 15 psi.
4. Check that the unit damper will fail to the proper position when main air pressure is lost. Disconnect the pneumatic actuator line from the velocity controller and observe the VAV damper position. The damper should fail to either a normally open position (indicator mark on shaft end is horizontal) or a normally closed position (indicator mark on shaft end is vertical).
5. Check that there is primary airflow in the inlet duct.
6. Connect a Magnehelic gage, inclined manometer or other differential pressure measuring device to the balancing taps provided in the velocity probe sensor lines. The manometer should have a full scale reading of 0.0 to
1.0 in. wg. The high pressure signal is delivered from the front sensor tap (away from the valve), and the low pres­sure signal is delivered from the back line (near the valve). The pressure differential between high and low represents the amplified velocity pressure in the inlet duct.
7. Read the differential pressure and enter the Flow Probe Chart to determine the airflow in the terminal unit. This chartisshowninFig.4A-4Candisalsoattachedtothe side of each unit. For example, a differential pressure of
0.10 in. wg for a size 8 unit yields an airflow of 275 cfm.
Volume controller for units is shown in Fig. 5.
Balancing Procedure (Control Sequences 1500-1523)
1. Damper action is factory set at NO (normally open), or NC (normally closed). To reselect loosen damper selec­tion switch screw and align pointer with damper pointer and tighten screw. The spring range of the actuator is not critical since the controller will output the necessary pres­sure to the actuator to position the damper according to set point. (See Fig. 5.)
2. Pipe the controller: Connect port “B” to the damper actu­ator. Connect port “M” to the clean, dry main air. Connect port “T” to the thermostat output. Connect port “H” to the total pressure tap on the airflow sensor. Connect port “L” to the static pressure tap on the airflow sensor.
The controller can be set up for cooling or heating applications using either a direct acting (DA) or reverse acting (RA) ther­mostat signal. The two flow adjustments are labeled “LO STAT P” and “HI STAT P. ”
TO THERMOSTAT BRANCH SIGNAL (RESET SIGNAL)
RESET START POINTADJUSTMENT (FACTORY SETAT 8 PSI)
* TO STATIC PRESSURE
TO TOTALPRESSURE *(DIFFERENCE IS: DIFFERENTIAL PRESSURE, OR DEVICE VELOCITY PRESSURE)
PUSH ON NIPPLES FOR 3/16” (5) I.D. FR TUBING (5)
TO DAMPER ACTUATOR
TO MAIN AIR SUPPLY
LOOSEN SCREW TO CHANGE DAMPER ACTION (SUPPLIED IN N.O. POSITION)
GAGE TAP. LEAVE CAP ON UNLESS CONNECTING GAGE FOR RESET START OR RESET SPAN ADJUSTMENT
DAMPER ACTION SELECTION (FACTORY SETAT NORMALLY OPEN) NOTE: SCREW MUST BE TIGHT ANDARROWS IN PERFECT ALIGNMENT FOR DEVICE TO FUNCTION PROPERLY.
H
B
M
DAMPER
Fig. 5 — CSC-3011 Controller
L
NC
NO
G
T
DIFFERENTIAL PRESSURE (FLOW)
RESETSTART
LO STAT ∆P
I
I
R
N
R
N
C
C
RESETSPAN
LIMIT ADJUSTMENT WHEN TSTAT PRESSURE IS HIGH (HI STAT) (FACTORY SETAT 0.65 IN. WG.)
HISTAT ∆P
- FIELD ADJUSTMENT REQUIRED
DIFFERENTIAL PRESSURE (FLOW) LIMIT ADJUSTMENT WHEN TSTAT PRESSURE IS LOW (LO STAT) (FACTORY SETAT 0 IN. WG.)
ALL ADJUSTMENTS CCW TO INCREASE (1/8-5/32FLATBLADE SCREWDRIVER)
RESET SPANADJUSTMENT (FACTORY SETAT 5 PSI)
7
LO STAT P setting is the desired airflow limit when the thermostat pressure is less than, or equal to, the reset start point.
• For DA Cooling or RA Heating: Adjust LO STAT P to the desired minimum airflow with 0 psig (or a pressure less than the reset start point) at port “T.” The LO STAT P must be set first. The LO STAT P will affect the HI STAT P setting.
• For RA Cooling or DA Heating: Adjust LO STAT P to the desired maximum airflow with 0 psig (or a pressure less than the reset start point) at port “T.” The LO STAT P must be set first. The LO STAT P will affect the HI STAT P setting.
HI STAT P setting is the desired airflow limit when the ther- mostat pressure is greater than, or equal to, the reset stop-point. The reset stop-point is the reset span pressure added to the reset start-point pressure.
• For DA Cooling or RA Heating (see Fig. 6): Adjust HI STAT P to the desired maximum airflow with 20 psig (or a pressure greater than the reset stop point) at port “T.” The HI STAT Pmustbesetlast.TheHISTAT P setting will be affected by the LO STAT P setting.
• For RA Cooling or DA Heating (see Fig. 6): Adjust HI STAT P to the desired minimum airflow with 20 psig (or a pressure greater than the reset stop point) at port “T.” The HI STAT Pmustbesetlast.TheHISTAT P setting will be affected by the LO STAT P setting.
NOTE: After the “LO STAT P” and “HI STAT P” initial adjustments are made, cycle the thermostat pressure a few times to settle the internal reset mechanisms and verify set­tings. Fine tune the settings if necessary. The thermostat pres­sure may be left at a high pressure and the “G” port cap may be removed and replaced to cycle the reset mechanism.
RESET START setting is factory set at 8.0 psig. This is the lowest thermostat pressure that the LO STAT P airflow will begin to reset towards the HI STAT P airflow. To change the RESET START setting; regulate thermostat pressure to the “T” port to the desired reset start point pressure, adjust RESET START adjustment until pressure at the “G” port is slightly higher than 0 psig, i.e., 0.1 psig.
NOTE: The “G” port taps into the controller’s internal reset chamber, which always starts at 0 psig. The RESET START
adjustment is a positive bias adjustment that sets the desired thermostat start point to the controller’s internal reset start point of 0 psig.
RESET SPAN setting is factory set at 5.0 psig. This is the required change in thermostat pressure that the controller will reset between the LO STAT P setting and the HI STAT ∆P setting. To change the RESET SPAN setting; adjust RESET SPAN adjustment until pressure at the “G” port equals the desired reset span pressure.
NOTE: The “G” port taps into the controller’s internal reset chamber, which will always be at a pressure between 0 psig and the RESET SPAN pressure.
Preventative Maintenance
1. Inspect pneumatic tubing for loose connections or leaks.
2. Clean out pneumatic line filters regularly according to manufacturer’s recommendations.
Pneumatic Control Troubleshooting — See Table 7.
DA HEATING
MAX
F
L O W
MIN
03813 psig
ROOM TEMPERATURE
MAX
F
L O W
MIN
ROOM TEMPERATURE
*May require changing the RESET START from 8.0 to 3.0 psig if
sequencing is involved.
Reset Span
Reset Start*
RA HEATING
Reset Span
13 8
Reset Start
3
LO STAT ∆P
HI STAT ∆P
HI STAT ∆P
LO STAT ∆P
0 psig
Fig. 6 — Reset Cycle for CSC-3011 Control
DA COOLING
MAX
F
L O W
MIN
03813 psig
ROOM TEMPERATURE
MAX
F
L O W
MIN
ROOM TEMPERATURE
Reset Span
Reset Start
RA COOLING
Reset Span
8
13
Reset Start*
3
HI STAT ∆P
LO STAT ∆P
LO STAT ∆P
HI STAT ∆P
0 psig
Table 7 — Troubleshooting
PROBLEM PROBABLE CAUSE
Controller does not reset to maximum or minimum set point during bal­ance procedure.
Controller does not reset to maximum or minimum set point during operation.
Pneumatic actuator does not stroke fully. Leak in pneumatic line between the controller and the actuator. Main air
Air valve stays in wide open position. Velocity probe is blocked by an obstruction (sandwich bag, etc.). Insuffi-
NOTE: Always check:
• Main air pressure (15 psi to 25 psi) at the controller.
• Disconnected or kinked pneumatic lines to the controller.
Quality of compressed air (oil or water in lines).
Balancer is using the thermostat for control signal. An artificial signal must be provided in place of the thermostat.
Thermostat is not demanding maximum or minimum air volume. Main air pressure at the controller is less than 15 psi.
pressure at the controller is less than 15 psi. Leak in the diaphragm.
cient supply air in the inlet duct.
• Proper thermostat signal and logic (Direct/Reverse Acting).
• Blocked velocity probe or insufficient primary supply air.
• Leaks in the actuator diaphragm.
• Mechanical linkage of the actuator/air valve.
8
ANALOG CONTROLS
Balancing Procedures (Control Sequences 2400, 2440, 2470) —
system is a pressure independent volume reset control that uses KMC Controls CSP-5001 controller-actuator. See Fig. 7.
The system provides for independently adjustable set points
for minimum, maximum, and auxiliary airflow limits.
Room temperature control is provided by the associated room thermostat which is selected according to the application. The room thermostat provides a fixed 2 degrees F reset span re­gardless of the minimum and maximum velocity limit set points.
Adjustments for the minimum and maximum airflows are made at the thermostat.
The thermostat (CTE-5100 Series) operates on a 16 vdc power supply from the CSP controller and outputs a 0 to 10 vdc signal on the T terminals; T [direct acting]) and T acting]). See the reference sequence diagram on unit for details on which ‘T’ terminals are used on each model thermostat, but in general T for heating. Terminals T1and T2are adjustable to limit mini­mum and maximum flow. Terminals T 0 to 10 vdc output signal.
1. Required tools: a. b. Smallflatblade(
c. Digital voltmeter capable of displaying a 0 to
d. HSO-5001 Test Leads (optional for meter taps)
2. Remove thermostat cover.
Thermostat cover is removed by loosening the setscrews on each side of the thermostat. Using a wrench turn the setscrews clockwise until cover is loose.
3. Check voltages.
Verify 16 vdc between (+) and (–) terminals.
and T3are used for the cooling mode, T2and T
1
1
/16in. hex/key wrench
10 vdc range which will display in hundredths of vdc
The analog electronic control
in the cooling mode (DA
in the heating mode (RA [reverse
2
1
1
and T4have a fixed
3
/8in.) screwdriver
1
/6in. hex/key
Applications for Dual Duct (Minimum Air From Cold Duct) —
plished by connecting two CSP-5001 Series controllers with a dual set point (RA/DA) thermostat, as shown in Fig. 8. In this application the CSP controllers are mounted separately on the cold and hot deck dampers with each utilizing its own flow sensor. The cold deck utilizes the T while the hot deck controller receives its requested flow signal from T maximum flow settings. In addition, by using the “R” override terminal on the thermostat cold deck, minimum flow can be overrided to zero upon a call for heating (or vice-versa). See Fig. 9 and 10.
4
. Both units can be set independently for minimum and
2
Fig. 8 — Dual Control Connections
Dual duct applications are easily accom-
signal from the thermostat
1
PPORTS
GEAR DISENGAGEMENT BUTTON
0-10V VELOCITY OUTPUT 0-10V INPUT SIGNAL 16V DC OUTPUT
(THERMOSTAT POWER)
Fig. 7 — CSP-5001 Controller
90
45
ADJUSTABLE END STOPS
0
L
H
N O M
MIN
MAX
NOR
METER
M
16
O
I
24V
U
V
N
DC
AC
I
A X
˜
+
%
RED-CLS
M
GRN-OPN
I
N
C
LED
ccw cw
E
HEATING MAX
T2
HEATING MIN
*Connect jumper from T2 to R1 to override cooling minimum to zero, upon
call for heating. Leave R2 connected to ground.
HTG. S.P.
RISE IN ROOM TEMPERATURE
T1
CLG. S.P.
COOLING MAX
COOLING MIN
Fig. 9 — Minimum Air From Cooling
Minimum Air From Heating*
Minimum Air From Cooling*
COOLING MAX
16
DC
V
WIRING
INO
U
T
COMMON (16V DC, INPUT, OUTPUT)
POWER
SUPPLY
˜
24 V
AC
HEATING MAX
HEATING MIN
*Connect jumperfromT1toR2tooverrideheatingminimumtozero,upon
call for heating. Leave R1 connected to ground.
T2
HTG. S.P.
RISE IN ROOM TEMPERATURE
CLG. S.P.
T1
COOLING MIN
Fig. 10 — Minimum Air From Heating
9
Analog Control Troubleshooting — The follow-
ing troubleshooting guide is directed towards single duct cool­ing applications, the same concepts can be applied to other configurations.
Never jumper terminal 16 VDC to “-” as this would cause a short, and possibly damage the power supply.
CONTROLLER
1. Verify 24 vac at terminals “~” (phase) and “-” (ground). Tolerance can be –15% to +20% (20.4 to 28.8 vac).
2. Verify 16 vdc at terminals “16 VDC” and “-”.
a. Tolerance is 15.0 to 17.0 vdc power supply to
thermostat.
b. If not correct, disconnect thermostat and recheck.
If still incorrect, replace CSP controller.
3. Check requested flow voltage on terminal “IN” and “-”.
a. Use charts on pages 6 and 7, Fig. 4A-4C to corre-
late into cubic feet per minute (cfm).
b. If reading is not what is desired, see the System
Calibration of the Linear Averaging Flow Probe section to adjust thermostat.
4. Check actual flow voltage on terminal “OUT” and “-” (for 0 to 10 vdc).
Use charts on pages 6 and 7, Fig. 4A-4C to correlate into cfm.
5. Check box movement, damper rotation, etc.
a. Review requested flow and actual flow parameters
above to determine if unit should be satisfied (within 50 fpm) or driving open or closed.
b. If damper is not moving, verify damper is not stuck
or at end of travel. Check rotation jumpers for proper position.
c. Change requested flow to make unit drive opposite
direction. This can be accomplished by moving the set point sliders or 1) and 2) below.
1.) To manually open the box, remove wiring from terminal “IN” and jumper terminal “IN” to ter­minal “16VDC”. This will tell unit to control at 3300 fpm/full airflow, and the green LED should turn on (and the box should drive open).
2.) To manually close the box, remove wiring from terminal “IN”, jumper and “IN” terminal to “-” terminal.Thiswilltellunittocontrolatzero fpm/no airflow, and the red LED should be on (and the box should drive closed).
NOTE: When using the same transformer for more than one control, the phase and ground must be consistent with each device.
Wire the control as shown on the control package diagram for the specific installation. Control wiring diagrams can be found inside the control box.
SUPPLY-AIR TEMPERATURE (SAT) SENSOR INSTAL­LATION — On terminals with heat, the SAT sensor is provid­ed. The sensor is factory wired to the controlled and shipped in the control box. The SAT must be field-installed in the duct downstream from the air terminal. The SAT sensor part num­ber is 33ZCSENSAT. See Table 8 for resistance information.
To install the sensor, proceed as follows:
1. Remove the plug from one of the
7
/8-in. openings in the
control box and pass the sensor probe through the hole.
2. Drill or punch a1/2-in. hole in the duct downstream of the unit, at a location meeting the requirements shown in Fig. 11.
3. Using 2 self-drilling screws (supplied), secure the sensor probe to the duct.
The SAT sensor probe is 6 inches in length. The tip of the probe must not touch the inside of the duct. Use field-supplied bushings as spacers when mounting the probe in a duct that is 6 in. or less in diameter.
If the unit is a cooling only unit, the SAT sensor is not pro­vided and is not required.
For units with hot and cold airstreams, locate SAT sensor probe at least 2 ft downstream (see Fig. 11).
DO NOT run sensor or relay wires in the same conduit or raceway with Class 1 service wiring.
DO NOT abrade or nick the outer jacket of cable. DO NOT pull or draw cable with a force that may harm the
physical or electrical properties. DO NOT bend a cable through a radius sharper than that
recommended by its manufacturer. AVOID splices in any control wiring.
Perform the following steps if state or local code requires the use of conduit, or if your installation requires a cable length of more than 8 ft:
1. Disconnect the sensor cable from the ComfortID zone controller, at the terminals labeled SAT and GND.
2. Mount the sensor to the duct (see steps 2 and 3 above).
3. Mount a field-supplied 4-in. x 4-in. x 20-in. extension box over the duct sensor.
1
4. Connect a conduit (
/2-in. nominal) to the zone controller
enclosure and extension box.
5. Pass the sensor probe through the extension box opening and into the conduit.
6. Reconnect the sensor leads to the zone controller labeled SAT and GND.
ComfortID™ CONTROLS
Install Sensors and Make Field Wiring Connections
GENERAL — All field wiring must comply with National Electrical Code (NEC) and local requirements. Refer to Tables 8-11 for electrical and wiring specifications.
For information on how to test and balance CCN controls,
refer to the 33ZC Installation and Operation Instructions.
Disconnect electrical power before wiring inside the con­troller. Electrical shock, personal injury, or damage to the zone controller can result.
HEATED
AIR
COOL
AIR
LEGEND
SAT — Supply Air Temperature Sensor ZC — Zone Controller
ZC
Fig. 11 — Supply Air Temperature Probe
(Part No. 33ZCSENSAT) Locations
10
2 FT. MIN.
SAT
LEAVING
AIR
Table 8 — Thermistor Resistance vs Temperature Values for
Supply-Air Temperature Sensor, Primary Air Temperature Sensor and Space Temperature Sensor
RESISTANCE
(Ohms)
29481 32 17050 54 10227 76 6340 98 4051 120 28732 33 16646 55 10000 77 6209 99 3972 121 28005 34 16253 56 9779 78 6080 100 3895 122 27298 35 15870 57 9563 79 5954 101 3819 123 26611 36 15497 58 9353 80 5832 102 3745 124 25943 37 15134 59 9148 81 5712 103 3673 125 25295 38 14780 60 8948 82 5595 104 3603 126 24664 39 14436 61 8754 83 5481 105 3533 127 24051 40 14101 62 8563 84 5369 106 3466 128 23456 41 13775 63 8378 85 5260 107 3400 129 22877 42 13457 64 8197 86 5154 108 3335 130 22313 43 13148 65 8021 87 5050 109 3272 131 21766 44 12846 66 7849 88 4948 110 3210 132 21234 45 12553 67 7681 89 4849 111 3150 133 20716 46 12267 68 7517 90 4752 112 3090 134 20212 47 11988 69 7357 91 4657 113 3033 135 19722 48 11717 70 7201 92 4564 114 2976 136 19246 49 11452 71 7049 93 4474 115 2920 137 18782 50 11194 72 6900 94 4385 116 2866 138 18332 51 10943 73 6755 95 4299 117 2813 139 17893 52 10698 74 6613 96 4214 118 2761 140 17466 53 10459 75 6475 97 4132 119
SPACE TEMPERATURE SENSOR INSTALLATION AND WIRING — The SPT sensor accessory is ordered separately for field installation. It is installed on interior walls to measure room space air temperature. See Fig. 12-16 and Table 8.
The wall plate accommodates both the NEMA (National
Electrical Manufacturing Association) standard and the Euro-
1
/4DIN standard. The use of a junction box to accommo-
pean date the wiring is recommended for installation. The sensor may be mounted directly on the wall, if acceptable by local codes.
DO NOT mount the sensor in drafty areas such as near heat­ing or air-conditioning ducts, open windows, fans, or over heat sources such as baseboard heaters or radiators. Sensors mount­ed in those areas will produce inaccurate readings.
Avoid corner locations. Allow at least 3 ft between the sen­sor and any corner. Air in corners tends to be stagnant resulting in inaccurate sensor readings.
Sensor should be mounted approximately 5 ft up from the floor, in an area that best represents the average temperature found in the space (zone).
The space temperature sensor cover includes a service jack connector. If wiring connection is made to the service jack, the connector can then be used to connect a network service tool with the Carrier Comfort Network® system.
Before installing the space temperature sensor, decide whether or not the service jack wiring connection will be made. If connection is desired, the CCN communication cable should be available at time of sensor installation, for convenient wir­ing connections. The cable selected must meet the require­ments for the entire network. See page 15 for CCN communi­cation cable specifications.
Install and wire the space temperature sensor as follows: NOTE: Space temperature sensor will be identified as T55 or
T56. Refer to Control Sequence drawings to determine which SPT is part of the particular control package being installed. (The difference between T55 and T56 is that T56 includes set point adjustment capability.)
1. Locate the two Allen type screws at the bottom of the sensor.
2. Turn the two screws clockwise to release the cover from the sensor wall mounting plate.
3. Lift the cover from the bottom and then release it from the top fasteners.
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
5. Usingtwono.6-32x1mounting screws (provided with the sensor), secure the sensor to the electrical box.
6. Use 20 gage wire to connect the sensor to the controller. This size is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and set point adjustment connections. The standard CCN com­munication cable may be used. If the set point adjustment (slide-bar) is not required, then an unshielded, 18 or 20 gage, two-conductor, twisted pair cable may be used. Re­fer to Table 9.
The CCN network service jack requires a separate, shielded CCN communication cable. Always use sepa­rate cables for CCN communication and sensor wiring. (Refer to Fig. 15 and 16 for wire terminations.)
7. Replace the cover by inserting the cover at the top of the mounting plate first, then swing the cover down over the lower portion. Rotate the two Allen head screws counter­clockwise until the cover is secured to the mounting plate and locked in position.
8. For more sensor information, see Table 8 for thermistor resistance vs temperature values.
NOTE: Clean sensor with damp cloth only. Do not use solvents.
Table 9 — Recommended Sensor and Device
Wiring
MANUFACTURER
Belden 8205 88442 Columbia D6451 American A21501 A48301 Quabik 6130 Alpha 1895 Manhattan M13402 M64430
NOTE: Wiring is 20 gage, 2 conductor twisted cable.
PART NUMBER
Regular Plenum
WIRING THE SPACE TEMPERATURE SENSOR AND SET POINT ADJUSTMENT SLIDEBAR — To wire the sen­sor and slidebar, perform the following (see Fig. 15 and 16):
1. Identify which cable is for the sensor wiring.
2. Strip back the jacket from the cables for at least 3 inches.
1
Strip
/4-in. of insulation from each conductor. Cut the
shield and drain wire from the sensor end of the cable.
4. Feed the wires from the electrical box through the open­ing in the center of the sensor mounting plate.
TEMP
(F)
11
3(MIN)
OR
2/3 OF WALL HEIGHT
D
5
2
3
45
61
RED(+)
WHT(GND)
BLK(-)
CCN COM
Fig. 12 — Typical Space Temperature Sensor
Room Location
Cool
Warm
Fig. 13 — Space Temperature Sensor
(P/N 33ZCT56SPT Shown)
SEN
SW1
BLK (GND)
RED (SPT)
SENSOR WIRING
Fig. 15 — Space Temperature Sensor Wiring
(33ZCT55SPT)
2
3
45
61
RED(+)
WHT(GND)
BLK(-)
CCN COM
NOTE: Dimensions are in inches.
Fig. 14 — Space Temperature Sensor and Wall
Mounted Humidity Sensor Mounting
12
SET
SEN
SW1
WHT
(T56) BLK (GND) RED (SPT)
SENSOR WIRING
JUMPER TERMINALS AS SHOWN
Cool Warm
Fig. 16 — Space Temperature Sensor Wiring
(33ZCT56SPT)
3. Connect the sensor cable as follows: a. Connect one wire from the cable (RED) to the SPT
terminal on the controller. Connect the other end of the wire to the left terminal on the SEN terminal block of the sensor.
b. Connect another wire from the cable (BLACK) to
the ground terminal on the controller. Connect the other end of the wire to the remaining open termi­nal on the SEN terminal block.
c. For T56 sensors, connect the remaining wire
(WHITE/CLR) to the T56 terminal on the control­ler. Connect the other end of the wire to the right most terminal on the SET terminal block.
d. In the control box, connect the cable shield to
J1-3, equipment ground.
e. Install a jumper between the two center T56 termi-
nals (right SEN and left SET).
WIRING THE CCN NETWORK COMMUNICATION SERVICE JACK — To wire the service jack, perform the following:
1. Strip back the jacket from the CCN communication ca-
ble(s) for at least 3 inches. Strip
1
/4in. of insulation from each conductor. Remove the shield and separate the drain wire from the cable. Twist together all the shield drain wires and fasten them together using an closed end crimp lug or a wire nut. Tape off any exposed bare wire to pre­vent shorting.
2. Connect the CCN + signal wire(s) (RED) to Terminal 5.
3. Connect the CCN– signal wire(s) (BLACK) to Terminal 2.
4. Connect the CCN GND signal wire(s) (WHITE/CLR) to Terminal 4 .
PRIMARY AIR TEMPERATURE SENSOR INSTALLA­TION — A primary air temperature (PAT) sensor is used on a zone controller which is functioning as a Linkage Coordinator for a non-CCN (Carrier Comfort Network®)/Linkage compati­ble air source. The part number is 33ZCSENPAT. See Fig. 17. The sensor is also available as field-supplied accessory.
When used on a zone controller, try to select a zone control­ler which will allow installation of the PAT sensor in the main trunk, as close to the air source as possible. See Fig. 18.
To mount the PAT sensor, remove sensor cover.
1. Drill a
1
/2-in. hole in supply duct.
2. Using field-supplied drill tap screw, secure sensor to duct.
3. Connect sensor to zone controller using field-supplied 2-conductor cable. Refer to Table 9.
4. Use field-supplied wire nuts to connect cable to sensor.
5. At zone controller, connect sensor wires to PAT and GND terminals.
INDOOR-AIR QUALITY SENSOR INSTALLATION — The indoor-air quality (IAQ) sensor accessory monitors carbon dioxide levels. This information is used to increase the airflow to the zone and may also modify the position of the outdoor-air dampers to admit more outdoor air as required to provide the desired ventilation rate. The wall sensor is used to monitor the conditioned space. The sensor uses infrared technology to measure the levels of CO available with or without an LCD readout to display the CO
present in the air. The wall sensor is
2
level in ppm and is also available in a combination model whichsensesbothtemperatureandCO
The CO
sensors are factory set for a range of 0 to
2
level.
2
2000 ppm and a linear voltage output of 0 to 10 vdc. Refer to the instructions supplied with the CO quirements and terminal locations. The sensor requires a sepa-
sensor for electrical re-
2
rate field-supplied 24 vac 25 va transformer to provide power to the sensor. The transformer may be mounted in the control box if space is provided (except electric heat units).
Fig. 17 — Primary Air Temperature Sensor
(Part Number 33ZCSENPAT)
Fig. 18 — Primary Air Temperature
Sensor Installation
(Air-Handling Unit Discharge Locations)
For factory configuration changes to some models of the sensor, the User Interface Program (UIP) or Sensor Calibration Service Kit is required.
To accurately monitor the quality of the air in the condi­tioned air space, locate the sensor near the return air grille so it senses the concentration of CO
leaving the space. The sensor
2
should be mounted in a location to avoid direct breath contact.
Do not mount the space sensor in drafty areas such as near supply diffusers, open window, fans, or over heat sources. Al-
2
low at least 3 ft between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor.
To mount the sensor, refer to the installation instructions shipped with the accessory kit.
INDOOR AIR QUALITY SENSOR WIRING — To wire the sensor after it is mounted in the conditioned air space, see Fig. 19-21 and the instructions shipped with the sensor. Use
13
two 2-conductor 20 AWG twisted-pair cables (see Table 9) to connect the field-supplied separate isolated 24 vac power source to the sensor and to connect the sensor to the control terminals. To connect the sensor to the control, identify the positive (+) and ground (GND) terminals on the sensor and connect the positive terminal to the RH/IAQ terminal on the control and connect the ground terminal to terminal GND.
HUMIDITY SENSOR (Wall-Mounted) INSTALLA­TION — The accessory space humidity sensor is field sup­plied and installed on an interior wall to measure the relative humidity of the air within the occupied space. See Fig. 22.
Theuseofastandard2x4-in.electricalboxtoaccommo­date the wiring is recommended for installation. The sensor can be mounted directly on the wall, if acceptable by local codes.
If the sensor is installed directly on a wall surface, install the humidity sensor using 2 screws and 2 hollow wall anchors (field-supplied); do not overtighten screws.
Fig. 19 — Indoor Air Quality Sensor
(Wall-Mounted Version Shown) 33ZCSENCO2
Fig. 20 — Ventilation Rates Based on
CO2Set Point
0
HF23BJ042
Made in Switzerland
by Belimo Automation
LR 92800
NEMA2
LISTED 94D5
U
TEMP.IND. &
L
REG.EQUIP.
Class 2 Supply
WIP
yel
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60Hz 3VA 2W
5K
COM
2
1
ora
blu
red
blk
1
3
wht
Do NOT clean or touch the sensing element with chemical solvents; they can permanently damage the sensor.
The sensor must be mounted vertically on the wall. The Carrier logo should be oriented correctly when the sensor is properly mounted.
DO NOT mount the sensor in drafty areas such as near heat­ing or air-conditioning ducts, open windows, fans, or over heat sources such as baseboard heaters, radiators, or wall-mounted light dimmers. Sensors mounted in those areas will produce inaccurate readings.
Avoid corner locations. Allow at least 4 ft between the sen­sor and any corner. Airflow near corners tends to be reduced, resulting in erratic sensor readings.
Sensor should be vertically mounted approximately 5 ft up from the floor, beside the space temperature sensor.
For distances up to 500 feet, use a 3-conductor, 18 or 20 AWG cable. A CCN communication cable can be used, although the shield is not required. The shield must be removed from both ends of the cable if this cable is used.
IAQ
GND
21
87
24VAC
LINE VOLTAGE
SEPARATE
POWER
SUPPLY
REQUIRED*
*Do not connect to the same transformer that supplies power to the zone controller.
Fig. 21 — Indoor Air Quality Sensor Wiring
14
Fig. 22 — Wall Mounted Relative Humidity Sensor
(P/N 33AMSENRHS000)
The power for the sensor is provided by the control board. The board provides 24 vdc for the sensor. No additional power source is required.
To wire the sensor, perform the following:
1. At the sensor, remove 4-in. of jacket from the cable. Strip
1
/4-in. of insulation from each conductor. Route the cable through the wire clearance opening in the center of the sensor. See Fig. 23.
2. Connect the RED wire to the sensor screw terminal marked (+).
3. Install one lead from the resistor (supplied with the sen­sor) and the WHITE wire, into the sensor screw terminal marked (–). After tightening the screw terminal, test the connection by pulling gently on the resistor lead.
4. Connect the remaining lead from the resistor to the BLACK wire and secure using a field-supplied closed end type crimp connector or wire nut.
5. Using electrical tape, insulate any exposed resistor lead to prevent shorting.
6. At the control box, remove the jacket from the cable.
7. Strip
1
/4-in. of insulation from each conductor.
8. Connect the RED wire to terminal +24v on the control board.
9. Connect the BLACK wire to terminal GND on the con­trol board.
10. Connect the WHITE/CLEAR wire to terminal RH/IAQ on the control board.
Connect the CCN Communication Bus — The
zone controllers connect to the bus in a daisy chain arrange­ment. The zone controller may be installed on a primary CCN bus or on a secondary bus from the primary CCN bus. Connecting to a secondary bus is recommended.
At 9,600 baud, the number of controllers is limited to 128 zones maximum, with a limit of 8 systems (Linkage Coordinator configured for at least 2 zones.) Bus length may not exceed 4000 ft, with no more than 60 devices on any
1000-ft section. Optically isolated RS-485 repeaters are required every 1000 ft.
At 19,200 and 38,400 baud, the number of controllers is limited to 128 maximum, with no limit on the number of Linkage Coordinators. Bus length may not exceed 1000 ft.
The first zone controller in a network connects directly to the bridge and the others are wired sequentially in a daisy chain fashion.
The CCN communication bus also connects to the zone controller space temperature sensor. Refer to Step 3 of the in­stallation section for sensor wiring instructions.
COMMUNICATION BUS WIRE SPECIFICATIONS — The Carrier Comfort Network (CCN) Communication Bus wiring is field-supplied and field-installed. It consists of shielded three-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN communication bus wire used for the entire network. See Table 10 for recom­mended cable.
Table 10 — Recommended Cables
MANUFACTURER CABLE PART NO.
Alpha 2413 or 5463 American A22503 Belden 8772 Columbia 02525
NOTE: Conductors and drain wire must be at least 20 AWG (American Wire Gage), stranded, and tinned copper. Individual con­ductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 Cto60 C is required.
CONNECTION TO THE COMMUNICATION BUS
1. Strip the ends of the red, white, and black conductors of the communication bus cable.
2. Connect one end of the communication bus cable to the bridge communication port labeled COMM2 (if connecting on a secondary bus).
When connecting the communication bus cable, a color code system for the entire network is recom­mended to simplify installation and checkout. See Table 11 for the recommended color code.
3. Refer to Fig. 23. Connect the other end of the communi­cation bus cable to the terminal block labeled CCN in the zone controller of the first air terminal. Following the col­or code in Table 11, connect the Red (+) wire to Terminal
1. Connect the White (ground) wire to Terminal 2. Con­nect the Black (–) wire to Terminal 3.
4. Connect additional zone controllers in a daisy chain fashion, following the color coded wiring scheme in Table 11.
Table 11 — Color Code Recommendations
SIGNAL TYPE
+ Red 1 Ground White 2 Black 3
CCN BUS WIRE
COLOR
PLUG PIN
NUMBER
NOTE: The communication bus drain wires (shield) must be tied together at each zone controller. If the communica­tion bus is entirely within one building, the resulting contin­uous shield must be connected to ground at only one single point. If the communication bus cable exits from one build­ing and enters another building, connect the shields to ground at a lightning suppressor in each building where the cable enters or exits (one point only).
15
HUMIDITY SENSOR
0
HF23BJ042
Made in Switzerland by Belimo Automation
LR 92800
NEMA 2
LISTED 94D5 TENP IND & REG. EQUIP.
Class 2 Supply
WIP
yel
RED
WHITE
BLACK
Shield
(If Used)
FAN A C
SEC DMP
HEAT2
FAN
24VAC
N/A
HEAT3
CW COM CCW
6
15
RH/IAQ
SECFLOW
J4
DMPPOS
1
1
CCN
J2A
3
1
LOW
1
ZONE Controller
Part Number: 33ZCFANTRM
S/N:
Bus#:
Element#:
Unit#:
HIGH
2
red wht
®
3
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60 Hz 3VA 2W
5K
COM
1
ora
blk
blu
US
C
1
J6
2 1
J7
3
®
1
J8
3
J6
1
CCW
COMCWHEAT1
24VAC
GND
+10V
GND
TEST
GND
3
16
+24V SPT GND
SAT
T56
GND
PAT
N/A
2
1
+
LEN
+
G
G
-
J2B
-
3
J3
SRVC
+
-
J1
24VAC
G
499
CCN COMMUNICATION CONNECTOR
BLACK (–)
+
-
RED (+)
WHITE (GND)
CCN
Fig. 23 — Zone Controller Connections
ComfortID™ Controls Start-Up
GENERAL — Air volume delivery to the conditioned space is controlled by the modulating of the primary air damper and the sequencing of the air source supply fan. The controller po­sitions the damper by way of an actuator and turns the fan on and off through linkage for the CCN compatible air source equipment control.
PRIMARY SYSTEM CHECK
1. Check that all controls, control box, and ductwork have been properly installed and set according to installation instructions and job requirements.
2. Check that final filters have been installed in the air­handling apparatus. Dust and debris can adversely affect system operation.
3. Check fan and system controls for proper operation.
4. Check electrical system connections.
5. Check that all air duct connections are tight.
6. See that all balancing dampers at box outlets are in full­open position.
ComfortID CONTROL SYSTEM CHECK
1. Check interconnections between thermostats and unit controls.
2. Force all dampers to control to the maximum cooling cfm using the Building Supervisor, ComfortWORKS Network Service Tool or ComfortID Test and Balance Tool software.
3. Set supply-duct balancing dampers, if used, in maximum cool position.
4. Check that the static pressure available at each box is above the minimum required, force all dampers to control to the minimum cooling cfm and verify that the static pressure is below the maximum safe operating limits when the damper is providing minimum cooling airflow.
5. Set air source supply fan speed and duct static pressure regulator to obtain satisfactory static pressure at design airflow.
6. While at peak system load, check system operation and pressures.
7. Check duct pressure at various points in the system. If sys­tem static pressure probe has been properly located, pres­sure atlast units of all branchheaders should remain essen­tially the same. If pressure has changed considerably, re­check the supply air static pressure controller or relocate the probe to better sense system pressure changes.
8. Remove all forces and balance each control box zone using through the balancing procedure described on page 9.
®
,
16
CCN System Start-Up — The Building Supervisor,
ComfortWORKS®, and the Network Service Tool can aid in system start-up and troubleshooting.
All set-up and set point configurations are factory set and field adjustable. Changes are made by using either Building Supervisor, ComfortWORKS or the Network Service Tool. TheNetworkServiceToolcanbeusedasaportabledeviceto change system set-up and set points from a zone sensor or ter­minal control module. During start-up, the Building Supervisor ortheNetworkServiceToolcanalsobeusedtoverifycommu­nication with each controller.
For specific operating instructions, refer to the appropriate user manual.
COMFORTID TEST AND BALANCE TOOL SOFT­WARE — The ComfortID Test and Balance Tool software is used for testing each controller if the Network Service Tool or CCN are not available. The ComfortID Test and Balance Tool is compatible with Windows95 and higher and Windows NT4 (with Service Pack Level 3 or better) operating systems.
This software is used for control calibration. It allows for various functions that expedite system checks and testing.
Carrier requires the use of the B&B485CARLP9A Port Powered RS232 to RS485 Converter for proper operation.
NOTE: The B&B485CARLP9A Port Powered RS232 to RS485 Converter is available through:
B&B Electronics 1500 Boyce Memorial Drive P.O. Box 1040 Ottawa, IL 61350
Refer to the ComfortID Test and Balance Tool Software Instal­lation and Operation Instructions for additional information.
COMFORTID CONSTANT VOLUME DUAL DUCT CONTROL PACKAGE NO. 4160 — Dual duct units are designed to provide accurate temperature control while main­taining a constant airflow to the space. A typical application is shown in Fig. 24. Use package no. 4160 with 35L,N units.
COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH CONSTANT MINIMUM COLD DECK AIRFLOW CONTROL PACKAGE NO. 4170 — Dual duct units are designed to provide accurate variable air volume (VAV) tem­perature control in both heating and cooling modes with a min­imum amount of energy consumption. Typically system used with this control package provide all the ventilation air though the cold deck only. This control package provides VAV cooling operation and VAV heating with variable air temperature. The control will maintain the minimum cooling airflow set point during heating to provide the required ventilation to the space. A typical application is shown in Fig. 25. Use package no. 4170 with 35N units.
COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH COLD DECK CLOSE-OFF CONTROL PACKAGE NO. 4175 — Dual duct units are designed to provide accurate variable air volume (VAV) temperature control in both heating and cooling modes with a minimum amount of energy consumption. A typical system used with this control package provides ventilation air though both the hot and cold decks. This control package provides VAV cooling operation and variable air temperature heating. It will reduce the cold deck (cooling) airflow to zero during maximum heating to eliminate energy waste. A typical application is shown in Fig. 26. Use package No. 4175 with 35N units.
HEAT
ACTUATOR
DAMPER
ACTUATOR
HEATED AIR
LEAVING
AIR
COOL AIR
DAMPER
ACTUATOR
24 VAC
SUPPLY
AIR SENSOR
SLAVE
CONTROLLER
DAMPER
ACTUATOR
HEATED AIR
LEAVING
COOL AIR
DAMPER
ACTUATOR
ZONE
CONTROLLER
24 VAC
CCN BUS
OPTIONAL
SUPPLY
AIR SENSOR
SPACE
TEMPERATURE
SENSOR
Fig. 24 — Constant Volume Dual Duct Control
AIR
ZONE
CONTROLLER
SPACE
CCN BUS
TEMPERATURE
SENSOR
Fig. 25 — VAV Dual Duct with Constant Minimum
Cold Deck Airflow Control
17
HEAT
ACTUATOR
DAMPER
ACTUATOR
HEATED AIR
Leaving
SPACE
SENSOR
Air
Supply
Air Sensor
COOL AIR
DAMPER
ACTUATOR
ZONE
CONTROLLER
CCN BUS
24 VAC
TEMPERATURE
Fig. 26 — VAV Dual Duct with Cold Deck Close-Off
Control
COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH CONSTANT VENTILATION CONTROL PACK­AGE NO. 4180 — Dual duct units are designed to provide accurate variable air volume (VAV) temperature control with a minimum amount of energy consumption. A typical system used with this control package provides all the ventilation air though a separate outside air system. The ventilation air is con­ditioned (heated/cooled/dehumidified) as required to provide a neutral temperature. The ventilation air is connected to the hot deck inlet of the terminal. The control package provides VAV cooling operation and constant volume ventilation. It will maintain the ventilation airflow set point at all times to provide the required ventilation to the space. Field supplied and installed perimeter or ducted heating may additionally be con­trolled. A typical application is shown in Fig. 27. Use package no. 4180 with 35N units.
COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH DEMAND CONTROLLED VENTILATION CON­TROL PACKAGE NO. 4190 — Dual duct units are designed to provide accurate variable air volume (VAV) temperature control with a minimum amount of energy consumption. A typical system used with this control package provides all the ventilation air though a separate outside air system. The venti­lation air is conditioned (heated/cooled/dehumidified) as required to provide a neutral temperature. The ventilation air is connected to the hot deck inlet of the terminal. The control package provides VAV cooling operation and demand con­trolled ventilation. It will adjust the ventilation to maintain the required ventilation rate when occupied and maintain at least the minimum base ventilation rate at all times. Field supplied and installed perimeter or ducted heating may additionally be controlled. A typical application is shown in Fig. 28. Use pack­age no. 4190 with 35L,N units.
CCN BUS
SECONDARY
VENTILATION
AIR
CONDITIONED
AIR
CONTROLLER
DAMPER
ACTUATOR
DAMPER
ACTUATOR
ZONE
CONTROLLER
24 VAC
CCN BUS
SPACE
CARBON DIOXIDE
SENSOR
Leaving
SPACE
TEMPERATURE
SENSOR
Optional space or
ducted heat source
Air
Optional supply air
sensor for ducted
heat source
Fig. 28 — VAV Dual Duct with Demand Controlled
Ventilation
SECONDARY CONTROLLER
DAMPER
VENTILATION
AIR
CONDITIONED
AIR
ACTUATOR
DAMPER
ACTUATOR
ZONE
CONTROLLER
CCN BUS
24 VAC
SPACE
TEMPERATURE
SENSOR
Leaving
Optional space or
ducted heat source
Air
Optional supply air
sensor for ducted
heat source
Fig. 27 — VAV Dual Duct with Constant Ventilation
Control
18
Copyright 2006 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3 Ta b 6 a
Catalog No. 04-53350001-01 Printed in U.S.A. Form 35L,N-1SI Pg 20 3-06 Replaces: 35L,M,N-1SI
Loading...