Carrier 35E user guide manual

35E Single-Duct Terminal Units
Variable Volume System
Installation and Start-Up Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
General ..........................................2
Warranty ......................................... 2
INSTALLATION ................................. 4-6
Step 1 — Install Volume Control Box .............4
Step 2 — Make Duct Connections ................4
Step 3 — Install Sensors and Make Field
Wiring Connections — Electronic Analog
or DDC (Direct Digital Controls) ................4
CONTROL SET-UP ............................... 7
General ..........................................7
Set Points ........................................7
Field Adjustments of Minimum and
Maximum Airflow Set Points ................... 7
System Calibration of the Linear Averaging
Flow Probe.....................................7
PNEUMATIC CONTROLS .......................7-11
Preparation for Balancing (Control
Sequences 1102 and 1103)..................... 7
Balancing Procedure
(Control Sequences 1102 and 1103) ............ 9
• DIRECT ACTING THERMOSTAT, NORMALLY OPEN DAMPER (Control Sequence 1102)
• REVERSE ACTING THERMOSTAT, NORMALLY CLOSED DAMPER (Control Sequence 1103)
Balancing Procedure
(Control Sequences 1104-1110) ............... 10
Pneumatic Control Troubleshooting............. 10
Balancing Procedures
(Control Sequences 2100-2105) ............... 11
Analog Control Troubleshooting ................13
Install Sensors and Make Field-Wiring
Connections .................................. 13
• GENERAL
• SUPPLY-AIR TEMPERATURE SENSOR
INSTALLATION
• SPACE TEMPERATURE SENSOR INSTALLATION
AND WIRING
• WIRING THE SPACE TEMPERATURE SENSOR
AND SET POINT ADJUSTMENT SLIDEBAR
• WIRINGTHECCNNETWORKCOMMUNICATION
SERVICE JACK
• PRIMARY AIR TEMPERATURE SENSOR
INSTALLATION
• INDOOR-AIR QUALITY SENSOR INSTALLATION
• INDOOR-AIR QUALITY SENSOR WIRING
• HUMIDITY SENSOR (Wall-Mounted) INSTALLATION
Connect the CCN Communication Bus..........19
• COMMUNICATION BUS WIRE SPECIFICATIONS
• CONNECTION TO THE COMMUNICATION BUS
Water Valve Installation .........................19
ComfortID Start-Up.............................. 19
• GENERAL
• PRIMARY SYSTEM CHECK
• ComfortID CONTROL SYSTEM CHECK
CCN System Start-Up ........................... 20
VVT® CONTROLS ............................ 21-23
General .........................................21
• DIRECT DRIVE HIGH TORQUE ACTUATOR
• RELAY PACKAGE
• ADDITIONAL SENSOR INFORMATION
•THERMOSTATS
Wiring Requirements............................ 21
• CCN COMMUNICATIONS
• THERMOSTAT TO TERMINAL CONTROL BOX
Wiring Connections ............................. 22
Control Start-up................................. 23
• GENERAL
• PRIMARY SYSTEM CHECK
SAFETY CONSIDERATIONS
SAFETY NOTE
Air-handling equipment will provide safe and reliable service when operated within design specifications. The equipment should be operated and serviced only by autho­rized personnel who have a thorough knowledge of sys­tem operation, safety devicesand emergencyprocedures.
Good judgement should be used in applying any manufacturer’s instructions to avoid injury to personnel or damage to equipment and property.
Disconnect all power to the unit before performing mainte­nance or service. Unit may automatically start if power is not disconnected. Electrical shock and personal injury could result.
If it is necessary to remove and dispose of mercury contac­tors in electric heat section, follow all local, state, and fed­eral laws regarding disposal of equipment containing hazardous materials.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3 Ta b 6 a
Catalog No. 533-530 Printed in U.S.A. Form 35E-2SI Pg 1 3-06 Replaces: 35E-1SI
PRE-INSTALLATION
General —
nal available with factory-installed pneumatic, analog electron­ic, Carrier Comfort Network® (CCN) or VVT®(variable vol­ume and temperature) electronic control options that can be used in conjunction with unit-mounted electric or hot water heat options. Figure 1 shows the basic box. Figure 2 is an example of a unit identification label.
STORAGE AND HANDLING — Inspect for damage upon receipt. Shipping damage claims should be filed with shipper at time of delivery. Store in a clean, dry, and covered location. Do not stack cartons. When unpacking units, care should be taken that the inlet collars and externally mounted components do not become damaged. Do not lift units using collars, sensors or externally mounted components as handles. If a unit is sup­plied with electric or hot water heat, care should be taken to prevent damage to these devices. Do not lay uncrated units on end or sides. Do not stack uncrated units over 6 ft high. Do not manhandle. Do not handle control boxes by tubing connections or other external attachments. Table 1 shows component weights.
INITIAL INSPECTION — Once items have been removed from the carton, check carefully for damage to duct connec­tions, coils or controls. File damage claim immediately with transportation agency and notify Carrier.
UNIT IDENTIFICATION — Each unit is supplied with a shipping label and an identification label (Fig. 2).
INSTALLATION PRECAUTION — Check that construction debris does not enter unit or ductwork. Do not operate the central-station air-handling fan without final or construction filters in place. Accumulated dust and construction debris distributed through the ductwork can adversely affect unit operation.
SERVICE ACCESS — Provide service clearance for unit access.
CODES — Install units in compliance with all applicable code requirements.
UNIT SUSPENSION — See Fig. 3 for unit suspension details.
The 35E is a single duct, variable volume termi-
Warranty — All Carrier-furnished items carry the standard
Carrier warranty.
No periodic preventative maintenance required, unless
called for specific control sequence.
Fig. 1 — 35E Single Duct Box (Sizes 4-16)
Fig. 2 — Unit Identification Label
Table 1 — 35E Unit Weights
35E
SIZE
4, 5, 6 14 18 23 32 19/20
7, 8 16 20 25 39 21/23
9, 10 21 25 30 44 28/30
12 26 30 35 56 35/38 14 34 38 43 65 44/49 16 38 42 47 75 50/55 22 65 69 74 91 82/90
DDC — Direct Digital Controls
NOTE: Data is based on the following conditions:
1. Unit casing is 22 gage.
2. Unit insulation is
3. Units rated with standard linear flow sensor.
LEGEND
UNIT ONLY
(lb)
1
/2-in. thick, 1.5-lb Tuf-Skin Rx™, dual density.
WITH PNEUMATIC
CONTROLS
(lb)
WITH DDC OR
ANALOG CONTROLS
(lb)
WITH ELECTRIC HEAT
CONTROLS
(lb)
WITH HOT WATER
(1 ROW/2 ROW) (lb)
2
FIELD SUPPLIED HANDING WIRE
BRACKET
DETAIL
Fig. 3 — Typical Unit Suspension with Brackets
CONTROL ARRANGEMENTS
The 35E single-duct unit is offered with a wide variety of factory-mounted controls that regulate the volume of air deliv­ery from the unit and respond to cooling and heating load re­quirements of the conditioned space. Stand-alone controls will fulfill the thermal requirements of a given control space. These devices are available in both pneumatic and electronic arrange­ments. Carrier VVT® electronic controls and PIC (Product Integrated Control) DDC (Direct Digital Controls) are commu­nicating controls which are integrated with the building system. The PIC controls are compatible with the CCN system. A num­ber of DDC control packages by others are available for con­signment mounting, as indicated.
Control offerings are: 35EA: Analog Electronic
35EC: PIC Direct Digital Electronic 35EP: Pneumatic 35EV: VVT Electronic (Gen. III or 3V™ controls) 35EN: None or DDC by others
Each control approach offers a variety of operating func­tions; a control package number identifies combinations of control functions. The following listings contain the basic func­tion arrangements for each control offering. Because of the variety of functions available, circuit diagrams, operating sequences, and function descriptions are contained in separate Application Data publications. Refer to the specific control publication for details.
CCN Control Arrangements — Carrier Comfort Net-
work® (CCN) controls are factory-installed in a control enclo­sure. Factory-mounted transformers are available as an option. Thermostats are supplied separately as a field-installed acces­sory. Carrier Comfort Network control packages must be used in combination with a thermostat. Thermostats are not included in the CCN package.
4140: Cooling only 4141: Single-stage and 2-stage electric heat 4142: 3-stage electric heat 4143: On-Off hot water 4144: Proportional (floating) hot water heat 4145: Cooling only with supply return tracking 4147: Single-stage, 2-stage and 3-stage electric heat with
supply return tracking
4149: Proportional (floating) hot water with supply return
tracking
4150: Return air damper
CCN Thermostats (Ordered Separately)
Thermostat: 33ZCT56SPT: RT (room temperature) sensor, with set point adjust and override.
Thermostat: 33ZCT55SPT: RT (room temperature) sensor, with override only.
Thermostat: 33ZCT58SPT: Communicating room tempera­ture sensor with LCD (liquid crystal diode), set point adjust, fan control and occupancy override.
Thermostat: 33ZCT56CO2: RT (room temperature) and CO sensor, with set point adjust and override.
Thermostat: 33ZCT55CO2: RT (room temperature) and CO sensor, with override only.
VVT Electronic Control Arrangement — Va r i -
able volume and temperature (VVT) controls are factory­installed in a control enclosure. Factory-mounted transformers are available as an option. Thermostats are supplied separately as a field-installed accessory.
GEN. III CONTROL CODES AND DESCRIPTIONS 8200: Pressure dependent, cooling only 8201: Pressure dependent, cooling with 2-stage electric heat 8202: Pressure dependent cooling with on/off hot water heat 8206: Pressure independent, cooling only 8207: Pressure independent, cooling with 2-stage electric heat 8208: Pressure independent cooling with on/off hot water heat 8209: Variable air volume (VAV) pressure dependent unit
control zone (Monitor)
8210: Bypass controller, 2-in. wg transducer 3V CONTROL CODES AND DESCRIPTIONS 8220: Pressure dependent cooling only
8221: Pressure dependent cooling with 3-stage electric heat 8222: Pressure dependent cooling with on/off hot water heat 8223: Pressure dependent cooling with modulating hot water
heat
8224: Pressure dependent cooling with combination base-
board and 2-stage electric heat 8226: Pressure independent cooling only 8227: Pressure independent cooling with 2-stage electric heat 8228: Pressure independent cooling with on/off hot water heat 8230: Bypass control
Analog Electronic Control Arrangement —
Pressure independent control packages are available without supplemental heat, with on/off hot water or electric heat, pro­portional hot water heat, or with cooling/heating automatic changeover control.
2
2
3
All analog control arrangements include a standard linear inlet flow sensor, 24-v transformer (optional), control enclo­sure and wall thermostat to match the control type.
2100: Heating control 2101: Cooling control 2102: Cooling with on/off electric heat control 2103: Cooling with on/off hot water heat control 2104: Cooling/heating automatic changeover control 2105: Cooling with proportional hot water heat control
Pneumatic Control Arrangement — All control
packages are pressure independent (unless otherwise noted) and available with or without hot water heat, dual maximum airflow, heating and cooling maximum airflow and dual mini­mum airflow. All control arrangements include a standard linear inlet flow sensor.
1100 (Actuator only): DA-NC pressure dependent control 1101 (Actuator only): RA-NO pressure dependent control 1102 (Single function controller): DA-NO with or without hot
water or electric heat 1103 (Single function controller): RA-NC with or without hot
water or electric heat 1104 (Multi-function controller): DA-NO with or without hot
water or electric heat 1105 (Multi-function controller): DA-NC with or without hot
water or electric heat 1106 (Multi-function controller): RA-NO with or without hot
water or electric heat 1107 (Multi-function controller): RA-NC with or without hot
water or electric heat 1108 (Dual Maximum Control): DA-NO with or without hot
water or electric heat 1109 (Heating/Cooling Maximum Control): DA-NO with or
without hot water or electric heat 1110 (Dual Minimum Control): DA-NO with or without hot
water or electric heat PNEUMATIC CONTROL LEGEND DA: Direct-acting thermostat
RA: Reverse-acting thermostat NO: Normally open damper position NC: Normally closed damper position
The single function controller provides single functions, i.e., DA-NO. Multi-function controllers are capable of providing DA-NO, DA-NC, RA-NC or RA-NO functions.
Direct Digital Electronic Control Arrange­ments (Field-Supplied) — Control packages are field-
supplied for factory mounting, unless otherwise noted. All DDC control arrangements include a standard linear inlet flow sensor, transformer to 24 volts and control enclosure.
Contact Carrier for detail about mounting field-supplied controls.
NO CONTROL 0000: 35E box only
D000: 35E box with control box only (For units without electric heat requiring a 24 v control transformer: the control transformer must be ordered from the unit accessories list in Quote Builder.)
D001: 35E box with control box and 24 v transformer P000: 35E box without controls (for DA pneumatic controlled
heat unit) P001: 35E box without controls (for RA pneumatic controlled
electric heat unit)
INSTALLATION
LOCK OUT AND TAG heater electrical disconnect before working on this equipment. Otherwise, one leg of the 3-leg heater remains energized. Electrical shock or personal injury could result.
Step 1 — Install Volume Control Box
1. Move unit to installation area. Remove unit from ship­ping package. Do not handle by controls or damper extension rod.
2. The unit has factory-installed brackets on unit as shown in Fig. 3.
3. Suspend units from building structure with straps, rods, or hanger wires. Secure the unit and level it in each direc­tion. Note that reheat coil is in heavy end of unit.
Step 2 — Make Duct Connections
1. Install supply ductwork on unit inlet collar. Check that air-supply duct connections are airtight and follow all accepted medium-pressure duct installation procedures. (Refer to Table 2 for pressure data.)
NOTE: To ensure proper equipment performance, it is recommended that a length of rigid straight duct equal to 3 times the duct diameter be provided to the inlet.
2. Install the discharge duct. Where a multiple outlet con­nector is used on the box, connect appropriately sized ductwork to the outlets. Use adapter caps to seal unused outlets. Fully open all balancing dampers.
To ensure use of common-diameter air duct, coordinate diameters of box inlet and multiple outlet collars. Insulate duct as required.
Ninety degree elbows or tight radius flexible duct immedi-
ately upstream of inlet collar should be avoided.
Step 3 — Install Sensors and Make Field Wir­ing Connections — Electric Analog or DDC (Direct Digital Controls) —
mensional submittals and control application diagrams for con­trol specifications. All field wiring must comply with National Electrical Code (NEC) and local requirements. Refer to the wiring diagram on the unit for specific wiring connections.
A field-supplied transformer is required if the unit was not equipped with a factory-installed transformer. See Fig. 4.
Single duct terminal units with electric heat are supplied with a single point wiring connection in the heater control box. All unit power is supplied through this connection. Models with electric heat are factory equipped with a control trans­former. See Fig. 5.
Wiring and unit ampacities are referenced in Tables 3A and 3B.
NOTE: Refer to wiring diagram attached to each unit for spe­cific information on that particular unit. Units with 480-3-60 electric heater REQUIRE 4-wire, wye connected power. units with 208/230 v, 3-phase heater can be connected with 3-wire power.
Unit airflow should not be set outside of the range noted in Fig. 6. The minimum recommended airflow for units with elec­tric heat must be at least 75 cfm per kW and not drop below the minimum values listed in the performance data table. The max­imum unit discharge temperature should not exceed 120 F. Prevent air stratification by setting the discharge temperature no more than 15 degrees above the room temperature. Example: 90 F discharge in a 75 F room.
Refer to specific unit di-
4
Table 2 — 35E Basic Pressure Data
INLET
SIZE (in.)
CCN — Carrier Comfort Network® ∆ PS— Thedifferenceinstaticpressure DDC — Direct Digital Controls EAT — Entering Air Temperature UL Underwriters Laboratories ∆ VPS— Change in velocity pressure
*Minimums are for all except CCN controls, which may be lower. Minimum for DDC by
†A minimum 0.03 in. wg discharge static pressure is required to set the flow switch in the
**Maximum discharge temperatures with electric heat are set at 120 F by the National
CFM
(Area)
4 110 2.3 0.10 0.01 0.02 0.03 0.03 0.04 0.01
(0.09) 170 3†† 0.23 0.02 0.04 0.06 0.08 0.10 0.02
(0.14) 265 5†† 0.23 0.04 0.10 0.15 0.20 0.24 0.04
(0.20) 380 7.5†† 0.22 0.09 0.20 0.30 0.40 0.50 0.09
(0.27) 525 9.5†† 0.23 0.09 0.20 0.30 0.40 0.50 0.09
(0.35) 675 13†† 0.21 0.09 0.27 0.44 0.60 0.76 0.09
(0.44) 875 16†† 0.21 0.17 0.31 0.44 0.57 0.69 0.17
(0.55) 1075 21†† 0.20 0.10 0.31 0.50 0.69 0.89 0.10
(0.78) 1550 30†† 0.19 0.09 0.33 0.54 0.75 0.96 0.09
(1.07) 2125 36†† 0.17 0.10 0.31 0.49 0.68 0.86 0.10
(1.40) 2725 36†† 0.14 0.09 0.32 0.53 0.73 0.94 0.09
(2.63) 5200 36†† 0.16 0.09 0.43 0.74 1.05 1.36 0.09
230 3†† 0.43 0.03 0.07 0.11 0.15 0.18 0.03
5 170 3.5 0.09 0.02 0.04 0.06 0.08 0.10 0.02
360 5†† 0.43 0.08 0.18 0.27 0.36 0.45 0.08 100
6 240 4.9 0.09 0.04 0.08 0.12 0.16 0.20 0.04
520 7.5†† 0.42 0.17 0.38 0.57 0.75 0.94 0.17 140
7 330 6.8 0.09 0.04 0.08 0.12 0.16 0.20 0.04
710 9.5†† 0.41 0.17 0.37 0.55 0.73 0.91 0.17 190
8 440 9.1 0.09 0.04 0.12 0.19 0.25 0.32 0.04
925 13†† 0.39 0.17 0.51 0.82 1.13 1.43 0.17 240
9 550 11.3 0.08 0.07 0.12 0.17 0.22 0.27 0.07
1200 16†† 0.40 0.32 0.59 0.83 1.07 1.31 0.32
300
10 675 13.9 0.08 0.04 0.12 0.20 0.27 0.35 0.04
1450 21†† 0.36 0.17 0.56 0.91 1.26 1.62 0.17
425
12 1000 20.6 0.08 0.04 0.14 0.22 0.31 0.40 0.04
2100 30†† 0.34 0.17 0.60 0.99 1.37 1.76 0.17
580
14 1375 28.3 0.07 0.04 0.13 0.21 0.28 0.36 0.04
2900 36†† 0.31 0.19 0.57 0.92 1.26 1.60 0.19
750
16 1775 36†† 0.06 0.04 0.14 0.22 0.31 0.40 0.04
3700 36†† 0.25 0.17 0.59 0.97 1.35 1.73 0.17 1800
22 3300 36†† 0.07 0.04 0.17 0.30 0.42 0.55 0.04
7100 36†† 0.31 0.17 0.81 1.38 1.95 2.53 0.17
others is to be provided by the control’s provider.
electric heater.
Electric Code. Max kW shown assumes 55 F entering air and is limited by unit’s selected
MIN AIRFLOW ( Cfm)*
Cooling Only or
Cooling with Hot Water
55
85
50
or
0
75
or
0
110
or
0
140
or
0
185
or
0
240
or
0
290
or
0
420
or
0
580
or
0
740
or
0
1400
or
0
Electric
LEGEND
ELECTRIC HEAT**
MAX kW
Heat †
1800
AT 5 5 F EAT
1.1 0.02 0.00 0.00 0.01 0.01 0.01 0.00
55
1.7 0.02 0.00 0.01 0.02 0.02 0.03 0.00
85
2.1 0.02 0.01 0.01 0.02 0.03 0.03 0.01
110
2.9 0.02 0.01 0.01 0.02 0.03 0.04 0.01
140
3.9 0.02 0.01 0.02 0.03 0.05 0.06 0.01
190
4.9 0.02 0.01 0.02 0.03 0.04 0.05 0.01
240
6.2 0.02 0.01 0.02 0.04 0.05 0.07 0.01
300
8.7 0.01 0.01 0.02 0.04 0.06 0.07 0.01
425
11.9 0.01 0.01 0.02 0.04 0.05 0.06 0.01
580
15.4 0.01 0.01 0.02 0.04 0.06 0.07 0.01
750
36†† 0.02 0.01 0.05 0.09 0.13 0.16 0.01
from inlet to discharge with damper fully open
Velocity Press
(VPS)
MINIMUM INLET STATIC PRESSURE (Unit and Heat Pressure Drop)
Basic Unit
Basic + 1 Row
(PS)
Coil (PS)
voltage, phase, max capacity and design (see Electrical Data in the Product Data cata­log). Min cfm for electric heat is based on UL/ETL listings. (Diffuser) performance will likely be poor at this low flow rate.) The ASHRAE (American Society of Heating, Refrig­eration and Air Conditioning Engineers) Handbook of Fundamentals does not recom­mend a discharge temperature exceeding 90 F for satisfactory air mixing and comfort.
††Max. kW is limited by design. NOTES:
1. To obtain Total Pressure (Pt), add the Velocity Pressure for a given cfm to the Static Pressure drop (∆ PS) of the desired configuration. Example: Pt for a Size 8 Basic Unit at 925 cfm = 0.39 + 0.17 = 0.56
2. The electric heat max kW is based on 3 phase power. For more details, refer to the air terminal selection program.
Basic + 2 Row
Coil (PS)
Basic + 3 Row
Coil (PS)
Basic + 4 Row
Coil (PS)
Basic +Heater †
(PS)
Table 3A — 35E Heater Power Wiring and
Fuse Sizing (Single Phase, 60 Hz)
HEATER
SIZE (kW)
10.0 34,130 83.3 2 41.7 6 36.1 6
11.0 37,130 91.7 2 45.8 6 39.7 6
12.0 40,956 100.0 1 50.0 6 43.3 6
AWG — American Wire Gage FLA — Full Load Amps
*Values based on 75 C copper wire.
BTUH
0.5 1,707 4.2 14 2.1 14 1.8 14
1.0 3,413 8.3 14 4.2 14 3.6 14
2.0 6,826 16.7 10 8.3 14 7.2 14
3.0 10,239 25.0 8 12.5 12 10.8 14
4.0 13,652 33.3 8 16.7 10 14.4 12
5.0 17,085 41.7 5 20.8 10 18.1 10
6.0 20,478 50.0 5 25.0 8 21.7 10
7.0 23,898 58.3 4 29.2 8 25.3 8
8.0 27,304 66.7 4 33.3 8 28.9 8
9.0 30,717 75.0 3 37.5 6 32.6 8
LEGEND
120 V 208/240 V 277 V
Heater
FLA
AWG *
Heater
FLA
AWG *
Heater
FLA
AWG *
Table 3B — 35E Heater Power Wiring and
HEATER
SIZE (kW)
0.5 1,707 1.4 14 0.6 10
1.0 3,413 2.8 14 1.2 10
2.0 6,826 5.6 14 2.4 10
3.0 10,239 8.3 14 3.6 10
4.0 13,652 11.1 14 4.8 10
5.0 17,085 13.9 12 6.0 10
6.0 20,478 16.7 10 7.2 10
7.0 23,898 19.4 10 8.4 10
8.0 27,304 22.2 10 9.6 10
9.0 30,717 25.0 8 10.8 10
10.0 34,130 27.8 8 12.0 10
12.0 40,956 33.3 8 14.4 12
14.0 47,782 38.8 6 16.8 12
16.0 54,608 44.4 6 19.2 10
18.0 61,434 50.0 6 21.6 10
20.0 68,260 55.5 4 24.0 10
22.0 75,086 61.1 4 26.4 8
24.0 81,912 66.6 4 28.8 8
26.0 88,738 72.3 3 31.3 8
28.0 95,564 77.8 3 33.7 8
30.0 102,390 83.4 2 36.1 6
32.0 109,216 89.0 2 38.6 6
34.0 116,042 94.5 1 41.0 6
36.0 122,868 100.1 1 43.4 6
LEGEND
AWG — American Wire Gage FLA Full Load Amps
*Recommended minimum wire size.
5
Fuse Sizing (3 Phase, 60 Hz)
BTUH
208 V 480 V
Heater FLA AWG* Heater FLA AWG*
L1
120VAC 208VAC 240VAC 277VAC
CLASS II TRANSFORMER (OPTIONAL)
ANALOG OR DDC
CONTROLLER
GROUND
24VAC
BLU
YEL
24 VAC
POWER
LEGEND
DDC — Direct Digital Controls
Field Wiring
Factory Wiring
NOTE: Drawing is typical — refer to actual unit wiring diagram for details.
Fig. 4 — Wiring of Optional Factory-Mounted
Transformer
10000
8000 6000
4000
7250
3709 2840
2000
1000
CFM
800 600
400
200
100
80 60
SIZE 22
SIZE 16 SIZE 14
SIZE 12
SIZE 10
SIZE 9
SIZE 8
SIZE 7
E 6
SIZ
SIZE 5
SIZE 4
2086
1449 1174 927
710
522
362
232
40
20
10
0.01
.05
.03
VOLTS (ANALOG CONTROLS)
0.1
FLOW PROBE IN.WG
0.3 0.5
1
Fig. 6 — Linear Probe CFM vs Pressure Signal Graph
CFM AT ONE INCH SIGNAL
LEGEND
AFS — Airflow Switch DDC — Direct Digital Controls
NOTE: Drawing is typical of 480V, 3-phase, 4-wire heater and control. Refer to actual unit wiring diagram.
Fig. 5 — Typical Power Connections for 35E Units with 3-Stage Electric Heat
ANALOG OR DDC CONTROLLER
SEPARATE CONTROL ENCLOSURE
6
CONTROL SETUP
General —
terminal is designed to supply a varying quantity of cold prima­ry air to a space in response to a thermostat demand. Some units have reheat options to provide heating demand require­ments as well. Most VAV terminals are equipped with pressure compensating controls to regulate the response to the thermo­stat independent of the pressure in the supply ductwork.
To balance the unit, it is necessary to set both the maximum and minimum set points of the controller. The many types of control options available each have specific procedures re­quired for balancing the unit.
The 35E single-duct VAV (variable air volume)
Set Points — Maximum and minimum airflow set points
are normally specified for the job and specific for each unit on the job. Where maximum and minimum airflow levels are not specified on the order, default values are noted on unit ID label.
Field Adjustment of Minimum and Maximum Airflow Set Points — Each 35E unit is equipped with a
flow probe that measures a differential pressure proportional to the airflow. The relationship between flow probe pressures and cfm is shown in the Linear Probe CFM vs Pressure Signal Graph (Fig. 6). This chart is attached to each unit.
System Calibration of the Linear Averaging Flow Probe — To achieve accurate pressure independent
operation, the velocity sensor and linear averaging flow probe must be calibrated to the controller. This will ensure that air­flow measurements will be accurate for all terminals at system start-up.
System calibration is accomplished by calculating a flow coefficient that adjusts the pressure fpm characteristics. The flow coefficient is determined by dividing the flow for a given unit (design air volume in cfm), at a pressure of 1.0 in. wg dif­ferential pressure, by the standard pitot tube coefficient of
4005. This ratio is the same for all sizes if the standard linear averaging probe is used.
Determine the design air velocity by dividing the design air volume (the flow at 1.0 in. wg) by the nominal inlet area (sq ft). This factor is the K factor.
Carrier inlet areas are shown in the table below. The design air volume is also shown in this table. It can be determined from this table that the average design air velocity for 35E units is equal to 2656 fpm at 1.0 in. wg.
UNIT SIZE 35E 04 05 06 07 08 09
INLET
DIAMETER
AIRFLOW (Cfm)
AT 1 i n. w g
INLET AREA
(sq ft)
.
35EUNITSIZE1012141622
INLET DIAMETER 10.0 12.0 14.0 16.0 16 x 24
AIRFLOW (Cfm)
AT 1 i n. w g
INLET AREA
(sq ft)
NOTE: For Carrier ComfortID™ terminals, all flow sizes are normal­ized using a single Probe Multiplier (PMF) for all sizes equal to
2.273.
4.0 5.0 6.0 7.0 8.0 9.0
232 362 502 710 927 1174
0.087 0.136 0.196 0.267 0.349 0.442
1449 2086 2840 3709 7250
0.545 0.785 1.069 1.396 2.640
Record the information on a performance sheet (see Fig. 7). This will provide a permanent record of the balanc­ing information.
installation location information
•boxsize
cooling minimum airflow (cfm) limit
cooling maximum airflow (cfm) limit
reheat (cfm) limit (if applicable)
heating minimum airflow (cfm) limit (if applicable)
heating maximum airflow (cfm) limit (if applicable)
calibration gain (after balancing)
set points
PNEUMATIC CONTROLS
Preparation for Balancing (Control Sequences 1102 and 1103)
1. Inspect all pneumatic connections to assure tight fit and proper location.
2. Verify that the thermostat being used is compatible with the control sequence provided (direct acting or reverse acting).
3. Check main air pressure at the controller(s). The main air pressure must be between 15 psi and 25 psi. (If dual or switched-main air pressure is used, check the pressure at both high and low settings.) The difference between “high” pressure main and “low” pressure main should be at least 4 psi, unless otherwise noted, and the “low” set­ting difference should exceed 15 psi.
4. Check that the unit damper will fail to the proper position when main air pressure is lost. Disconnect the pneumatic actuator line from the velocity controller and observe the VAV damper position. The damper should fail to either a normally open position (indicator mark on shaft end is horizontal) or a normally closed position (indicator mark on shaft end is vertical).
5. Check that there is primary airflow in the inlet duct.
6. Connect a Magnehelic gage, inclined manometer or other differential pressure measuring device to the balancing taps provided in the velocity probe sensor lines. The manometer should have a full scale reading of 0.0 to
1.0 in. wg. The high pressure signal is delivered from the front sensor tap (away from the valve), and the low pres­sure signal is delivered from the back line (near the valve). The pressure differential between high and low represents the amplified velocity pressure in the inlet duct.
7. Read the differential pressure and enter the Linear Aver­aging Probe Chart to determine the airflow in the terminal unit. This chart is shown in Fig. 6 and is also attached to the side of each unit. For example, a differential pressure of 0.10 in. wg for a size 8 unit yields an airflow of 275 cfm.
Volume controllers for 35EP units are shown in Fig. 8-10.
Identification for each controller is shown in Table 4.
7
AIR TERMINAL PERFORMANCE SHEET
JOB NAME ______________________________________________
JOB LOCATION __________________________________________
CUSTOMER _____________________________________________
ENGINEER ______________________________________________
BUILDING LOCATION/FLOOR ______________________________
BUS NUMBER ___________________________________________
CONTROL SET POINTS
Tag
Number
Zone
Address #
Box Size
(in./cfm)
Cooling
(cfm)
min max min max Type Btu min max min max mult.
Reheat
cfm
Heating
(cfm)
Heat kW Occupied Unoccupied
Calibration
Gain
Fig. 7 — Air Terminal Performance Sheet
8
Loading...
+ 16 hidden pages