Carrier 33ZCSECTRM, 33ZCFANTRM, 33ZCVAVTRM User Manual

Page 1
Single Duct Air Terminal Zone Controller
VAV Fan Terminal Zone Controller
Secondary Terminal Zone Controller
Installation, Start-Up and
Configuration Instructions
Part Numbers 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM
CONTENTS
SAFETY CONSIDERATIONS GENERAL INSTALLATION
General Zone Controller Hardware Field-Supplied Hardware
• SPACE TEMPERATURE SENSOR
• PRIMARY AIR TEMPERATURE SENSOR
• SUPPLY AIR TEMPERATURE (SAT) SENSOR
• RELATIVE HUMIDITY SENSOR
• INDOOR AIR QUALITY (CO
Mount Zone Controller
• LOCATION
• MOUNTING
Connect the Power Transformer Connect Airflow Pickups Install Sensors
• SPACE TEMPERATURE SENSOR INSTALLATION
• PRIMARY AIR TEMPERATURE SENSOR INSTALLATION
• SUPPLY AIR TEMPERATURE (SAT) SENSOR INSTALLATION
• INDOOR AIR QUALITY SENSOR INSTALLATION
• HUMIDITY SENSOR (WALL-MOUNTED) INSTALLATION
Remote Occupancy Contact Connect the Outputs Modulating Baseboard Hydronic Heating Connect the CCN Communication Bus
• COMMUNICATION BUS WIRE SPECIFICATIONS
• CONNECTION TO THE COMMUNICATION BUS
START-UP Perform System Check-Out Network Addressing Initial Operation and Test Airflow Check Fan and Heat Configuration and Test
CONFIGURATION Points Display Screen Modify Controller Configuration
• ALARM LIMIT CONFIGURATION SCREEN
• CONTROLLER IDENTIFICATION SCREEN
• HOLIDAY CONFIGURATION SCREENS
• LINKAGE COORDINATOR CONFIGURATION SCREEN
• OCCUPANCY CONFIGURATION SCREEN
• SET POINT SCREEN
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-50
. . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . 2
) SENSOR
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . 31
. . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . 26
. . . . . . . . 26
. . . . . . . . . . 26
. . . . . . . . . . . . . . . . . . . . . 29
. . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . 32
Service Configuration Selection Screen
• AIRFLOW SERVICE CONFIGURATION SCREEN
• TERMINAL SERVICE CONFIGURATION SCREEN
• OPTIONS SERVICE CONFIGURATION SCREEN
• SECONDARY DAMPER SERVICE CONFIGURATION SCREEN
Maintenance Table Menu Screen
• LINKAGE MAINTENANCE TABLE
• OCCUPANCY MAINTENANCE TABLE
• ZONE AIR BALANCE/COMMISSIONING TABLE
• ZONE MAINTENANCE TABLE
. . . . . . . . . . . . . . . . 43
. . . . . . . . . 37
SAFETY CONSIDERATIONS
SAFETY NOTE
Air-handling equipment will provide safe and reliable service when operated within design specifications. The equipment should be operated and serviced only by authorized personnel who have a thorough knowledge of system operation, safety devices and emergency procedures.
Good judgement should be used in applying any manu­facturer’s instructions to avoid injury to personnel or dam­age to equipment and property.
Disconnect all power to the unit before performing mainte­nance or servic e. Unit may automati cally start if pow er is not disconnected. Electrical shock and personal injury could result.
If it is necessary to remove and dispose of mercury contac­tors in electric heat secti on, follow al l local, sta te, and fed­eral laws regarding disposal of equipment containing hazardous materials.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 1 a 1 3 a
PC 111 Catalog No. 533-355 Printed in U.S.A. Form 33ZC-1SI Pg 1 303 11-99 Replaces: New
Page 2
GENERAL
The zone controller is a single duct, fan powered, Variable Air Volume (VAV) terminal control with a factory-integrated controller and actuator. The zone controller maintains precise temperature control in the sp ace by operating the terminal f an and regulating the flow of conditioned air into the space. Build­ings with diverse loading conditions can be supported by con­trolling reheat or supplemental heat.
The VAV Fan Terminal Zone Controller (33ZCFANTRM) provides dedicated control functions for series fan or parallel fan powered terminals, single duct terminals with 3 stages of heat, or as a primary controller for dual duct or zone pressure control applications.
The Single Duct Air Terminal Zone Controller (33ZCVAVTRM) provides dedicated control functions for sin­gle duct terminals with modulating heat or up to 2 stages of heat.
When the VAV Fan Terminal Zone Controller is used in conjunction with a secondary terminal and the 33ZCSECTRM secondary terminal zone controller, either dual duct or zone pressurization applications can be supported.
Carrier’s Linkage system is an integrated combination of Carrier Comfort Network (CCN) controllers for use with Sin­gle Duct air terminals and VAV Fan Powered terminals. The Single Duct air terminal and VAV Fan terminal zone control­lers are part of the Carrier ComfortID system.
Devices manufactured by Carrier which have Product Inte­grated Controls on the same communication bus as the zone controller, air handlers (such as the 39L,T), or large rooftop units do not require an external controller to function as part of a Carrier linkage system. These air handlers or large rooftop units feature factory-installed Product Integrated Control (PIC) controllers that are directly compatible wi th the system. Con­sult your local Carrier representative for the complete list of compatible air handlers. The Comfort System AirManager (CSAM) or the CC6400 supports linkage for non-Carrier de­vices or air handlers. Figure 1 shows an example of a Carrier linkage system.
INSTALLATION
General —
direct digital control (DDC) controller for variable air volum e (VAV) air terminals. It can be retrofitted on units manufactured by Carrier or other manufacturers to provide pressure­independent VAV control.
Each zone controller has the ability to function as a linkage coordinator for systems with up to 128 zones. As a linkage co­ordinator, a zone controller will retrieve and provide system in­formation to the air handling equipment and other zone con­trollers. A zone controller can function as a stand alone device by installing a primary supply air sensor.
The zone controller monitors differential pressure from an airflow pickup (or a pair of pickups) mounted on the terminal box. It compares the resulting signal to an airflow set point in order to provide pressure-independent control of the air passing through the terminal.
The zone controller is connected to a wall-mounted, field­supplied, space temperature sensor (SPT) in order to monitor zone temperature changes and satisfy zone demand.
On stand-alone applications or applications with heat, the zone controller must be connected to a field-supplied supply air temperature (SAT) sensor to monitor the temperature of the air delivered by the air terminal.
Carrier’s Network Service T ool can be connected to the sys­tem at the SPT sensor if CCN communication wiring is run to
The zone controller is a microprocessor-based
the SPT sensor. The Network Service Tool can be used to ad­just set points, set operating parameters, and fully configure the zone controller or any device on the system.
Zone Controller Hardware —
The zone controller
consists of the following hardware:
terminal control module
torque-limiting damper actuator
airflow transducer (velocity sensor)
plastic enclosure
one no. 8 x
1
/2-in. sheet metal screw (to prevent zone
controller rotation)
NOTE: A filter is not provided for the airflow transducer. For installations on systems with a high degree of impuri­ties, an air filter can be purchased and installed on the trans­ducer high pressure pickup.
Figure 2 shows the zone controller physical details.
Figures 3-5 show the 3 different types of zone controllers.
Field-Supplied Hardware —
Each zone controller re­quires the following field-supplied components to complete its installation :
air terminal unit
space temperature sensor
transformer — 24 vac, 40 va
two no. 10 x
sensor to duct, if required)
two no. 6-32 x
1
/2-in. sheet metal screws (to secure SAT
5
/8-in. screws (to mount SPT sensor base
to electrical box)
contactors (if required for fan or electric heat)
supply air temperature sensor (required for terminal with
ducted heat)
indoor air quality sensor (if required)
relative humidity sensor (if required)
one SPST (for each stage of electric heat, not required
for Carrier fan terminals)
valve and actuator for hot water heat (if required)
delta pressure airflow pickup NOTE: When selecting an airflow pickup, it is the
designer's responsibility to select a sensor that provides the desired ou tput at the design airflow.
•wire
polyethylene tubing (for pressure pickup)
bushings ( re qu ire d wh en m o un tin g SAT sensor in a duct
6-in. or less in diameter)
primary air temperature sensor (if required) SPACE TEMPERATURE SE NSOR — Each zone control-
ler requires a field-supplied Carrier space temperature sensor. There are two sensors available for this application:
33ZCT55SPT, Space Temperature Sensor with Override
Button
33ZCT56SPT, Space Temperature Sensor with Override
Button and Set Point Adjustment
PRIMARY AIR TEMPERATURE SENSOR — A field­supplied, primary air temperature (PAT) sensor (part number 33ZCSENPAT) is used on a zone controller which is function­ing as a Linkage Coordinator for a non CCN/Linkage compati­ble air source.
SUPPLY AIR TEMPERATURE (SAT) SENSOR — On stand-alone applications or applications with ducted heat, the zone controller must be connected to a field-supplied supply air temperature (SAT) sensor (part number 33ZCSENSAT) to monitor the temperature of the air delivered by the air terminal. The zone controller will maintain the air temperature below the maximum air temperature in ducted heating applications.
2
Page 3
CCN PRIMARY BUS (BUS 0)
CCN
SYSTEM
MONITORING
SOFTWARE
FULLY
COMPATIBLE
AIR HANDLER
SECONDARY BUS
CC6400 OR CSAM
EQUIPPED
NON-CCN
AIR HANDLER
BRIDGE
(RECOMMENDED)
COMFORTID
EQUIPPED
AIR TERMINAL
(1 OF UP TO 128)
ADDRESSED
SEQUENTIALLY
LEGEND
CCN — CSAM —
Carrier Comfort Network
Comfort System
Air
Manager
COLLECTION
DATA
OPTION
Fig. 1 — Typical Carrier Linkage System
3
Page 4
DAMPER SHAFT
ACTUATOR CLAMP ASSEMBLY
LOW PRESSURE TUBING ROUTING
LOW
MECHANICAL STOP
1
®
3
ZONE Controller
3art Number: 33ZCFANTRM
S/N:
Bus#:
Element#:
Unit#:
HIGH
ACTUATOR RELEASE BUTTON
0
HF23BJ042
Made in Switzerland by Belimo Automation
LR 92800
NEMA 2
LISTED 94D5 TENP IND & REG. EQUIP.
Class 2 Supply
yel
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60 Hz 3VA 2W
5K
COM
WIP
1
2
red wht
ora
blk
blu
Fig. 2 Zone Controller Physical Details (33ZCFANTRM Shown)
RELATIVE HUMIDITY SENSOR — The 33AMSENRHS000 relative humidity sensor is required for zone humidity control (dehumidification).
NOTE: The relative humidity sensor and CO
sensor cannot
2
be used on the same zone controller. INDOOR AIR QUALITY (CO
) SENSOR — An indoor air
2
quality sensor is required for optional demand control ventila­tion. The CGCDXSEN002A00 CO2 Sensor is an indoor, wall mounted sensor with an LED display. The CGCDXSEN003A00 CO
Sensor is an indoor, wall mounted
2
sensor without display . NOTE: The relative humidity sensor and CO
sensor cannot
2
be used on the same zone controller.
Mount Zone Controller
LOCA TIO N — The zone controller must be mounted on the air terminal’s damper actuator shaft. For service access, there should be at least 12 in. of clearance between the front of the zone controller and adjacent surfaces. Refer to Fig. 6.
MOUNTING — Perform the following steps to mount the zone controller:
1. Visually inspect the damper and determine the direc­tion in which the damper shaft moves to open the damper — clockwise (CW) or counterclockwise (CCW). Refer to Fig. 7.
If the damper rotates CCW to open, it does not require any configuration changes.
If the damper rotates CW to open, then the damper actuator logic must be reversed. This is done in the software when performing system start-up and damper calibration test. Do not attempt to change damper rota­tion by changing wiring. This will upset the damper position feedback potentiometer readings.
2. Rotate the damper shaft to the fully closed position. Note direction of rotation.
15
US
C
1
J6
2 1
J7
3
®
1
J8
3
J6
1
CCW
COMCWHEAT1
24VAC
FAN AC
FAN
24VAC
N/A
HEAT3
CW COM COW
SEC DMP
6
HEAT2
RH/IAQ
SECFLOW
J4
DMPPOS
1
1
3
GND
+10V
GND
TEST
GND
CCN
J2A
1
3
+
J1
G
-
J3
+24V
SPT
GND
SAT
T56
GND
PAT
REMOTE
1
LEN
J2B
3
SRVC
+
24VAC
16
GROMMET
2
+
G
-
ANTI­ROTATION TAB
-
G
NOTE: Actuator clamp accepts dampers
HIGH PRESSURE TUBING ROUTING
shafts with the following characteristics: Round —
Square —
1
/4-in. to 5/8-in.
(6 to 16 mm)
1
/4-in. to 7/16-in.
(6 to 11 mm) Damper shaft must be a minimum of 1.5-in. (38 mm) long.
3. Press the release button on the actuator and rotate the clamp in the same direction that was required to close the damper in Step 2.
4. Press the release button on the actuator and rotate the actuator back one position grad uat i on. Releas e t he b ut­ton and lock the actuator in this position.
5. Mount the zone controller to the terminal by sliding the damper shaft through the actuator clamp assembly. Secure the zone controller to the duct by installing the screw provided through the gromm et in the anti­rotation tab. Be sure the floating grommet is in the center of the slot. Failure to center the grommet may cause the actuator to stick or bind.
6. Tighten the actuator clamp assembly to the damper shaft. Secure by tightening the two 10-mm nuts.
7. If the damper has less than 90 degrees of travel between the fully open and fully closed positions, then a mechanical stop must be set on the actuator. The mechanical stop prevents the damper from opening past the maximum damper position. To set the mechanical stop, perform the following procedure:
a. Press the actuator release button and rotate the
damper to the fully open position.
b. Using a Phillips screwdriver, loosen the appropri-
ate stop clamp screw.
c. Move the stop clamp screw so that it contacts the
edge of the cam on the actuator. Secure the stop clamp screw in this position by tightening the screw.
8. Verify that the damper opens and closes. Press the actuator release button and rotate the damper. Verify that the damper does not rotate past the fully open position. Release the button and lock the damper in the fully open position.
801
4
Page 5
0
HF23BJ042
Made in Switzerland by Belimo Automation
LR 92800
NEMA 2
LISTED 94D5 TENP IND & REG. EQUIP.
Class 2 Supply
5K
WIP
yel
blu
ora
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60 Hz 3VA 2W
COM
1
2
red wht
blk
15
LOW
1
®
ZONE Controller
Part Number: 33ZCFANTRM
S/N:
Bus#:
Element#:
Unit#:
US
C
1
J6
2 1
J7
3
®
1
J8
3
SEC DMP
J6
3
HIGH
1
CCW
COMCWHEAT1
24VAC
HEAT2
FAN AC
FAN
24VAC
N/A
HEAT3
CW COM COW
6
RH/IAQ
GND
SECFLOW
+10V
J4
DMPPOS
GND
TEST
GND
1
1
CCN
J2A
3
1
3
+
G
-
J1
+24V
SPT
GND
SAT
T56
GND
PAT
REMOTE
1
3
J3
24VAC
LEN
J2B
16
2
+
G
-
SRVC
+
-
G
0
HF23BJ042
Made in Switzerland by Belimo Automation
LR 92800
NEMA 2
LISTED 94D5 TENP IND & REG. EQUIP.
Class 2 Supply
5K
WIP
yel
blu
ora
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60 Hz 3VA 2W
COM
1
2
red wht
blk
Fig. 3 VAV Fan Terminal Zone Controller
LOW
US
C
1
®
®
3
ZONE Controller
Part Number: 33ZCVAVTRM
S/N:
Bus#:
Element#:
Unit#:
HIGH
1
CCW
J6
COMCWHEAT1
24VAC
HEAT2
6
15
RH/IAQ
GND
SECFLOW
+10V
J4
DMPPOS
GND
TEST
GND
1
1
CCN
J2A
3
1
3
+
G
-
J1
+24V
SPT
GND
SAT
T56
GND
PAT
REMOTE
1
3
J3
24VAC
LEN
J2B
16
2
+
G
-
SRVC
+
-
G
Fig. 4 Single Duct Air Terminal Zone Controller
5
801
Page 6
0
HF23BJ042
Made in Switzerland
by Belimo Automation
LR 92800
NEMA 2
LISTED 94D5
U
TEMP. IND. &
L
REG. EQUIP.
Class 2 Supply
5K
WIP
blu
yel
ora
LOW
1
®
C
US
®
ZONE Controller
35 in-lb (4 Nm)
80...110s
Part Number: 33ZCSECTRM
S/N:
24VAC/DC 50/60Hz 3VA 2W
COM
3
2
1
wht
red
blk
Fig. 5 Secondary Terminal Zone Controller
Unit#:
HIGH
J2
CCW
COMCWN/A
1
N/A
N/A
6
GND
D
FLOW
OUT
TPUT
+10V
OV
J1
CW
COM
MMON
CCW
1
CW
J1
6
ALLOW 12 CLEARANCE FOR SERVICE ACCESS TO CONTROL BOX
3 REF.
ZONE
CONTROLLER
END VIEW INLET
Fig. 6 Service Clearance for Zone Controller Mounting
6
Page 7
AIR FLOW
CW TO OPEN, CCW TO CLOSE
AIR FLOW
CCW TO OPEN, CW TO CLOSE
Fig. 7 Damper Configuration
Connect the Power Transformer
An individual, field-supplied, 24 vac power transformer is recommended for each zone controller. If multiple zone controllers are powered from one power transformer (100 va maximum for UL [Under­writers Laboratories] Class 2 conformance), maintain polarity on the power input terminals. All transformer secondaries are required to be grounded. Use only stranded copper conductors for all wiring to the zone controller. Wiring connections must be made in accordance with NEC (Nati onal Electrical Code) and local codes. Ground the transformer at the transformer lo­cation. Provide an 18-gage, green, chassis ground wire at the terminal.
The power supply is 24 vac ± 10% at 40 va (50/60 Hz).
For 33ZCVAVTRM zone controllers, the power require­ment sizing allows for accessory water valves and for electric heat contactor(s). Water valves are limited to 15 va on both two-position and modulating hot water. The electric heat con­tactor(s) are limited to 10 va (holding) each.
For 33ZCFANTRM zone controllers, the power require­ment sizing allows for accessory water valves and for the fan contactor. Water valves are limited to 8 va on both two-position and modulating hot water. The fan contactor is limited to 11 va (holding).
NOTE: If a water valve or electric heat contactor exceeds these limits, or external contactors are required for electric heat, then it is recommended a 60 va transformer be used. The maximum rating for any output is 20 va.
NOTE: Do not run sensor or communication wiring in the same conduit with line-voltage wiring.
NOTE: An accessory conduit box (part no. 33ZCCONBOX) is available for conduit wiring connections to the zone controller.
Perform the following steps to connect the power
transformer:
1. Install the field-supplied transformer in an electrical enclosure that conforms to NEC and local codes.
2. Connect 24 vac from the transformer as shown in the applicable wiring diagram (Fig. 8A-J).
Connect Airflow Pickups
The zone controller de­termines velocity pressure by obtaining the difference between high and low duct pressure from two airflow pickups. The pickups are connected to barb fittings on the zone controller
1
with
/4-in. polyethylene tubing. All piping for this purpose
must conform to local codes.
Figure 9 indicates the positions of the two barb fittings. Perform the following steps to install and connect the air-
flow pickups:
1. Select a location on the air handlers supply air duct where the airflow pickups will be installed. The loca­tion should be one where there are at least three duct diameters of straight duct upstream of the pickups. If this requirement is not met, stable airflow measure­ments may not be possible.
2. Mount the field-supplied airflow pickup(s) in the duct, following the manufacturer' s directions. Two individ­ual pickups may be used, one for high pressure airflow and one for low pressure airflow . A dual pickup, which combines the two functions, may also be used. When using individual pickups, make sure that the one for high pressure airflow faces upstream, in the direction the air is coming from, and the one for low pressure airflow faces downstream, in the direction the air is going to.
3. Use field-supplied
1
/4-in. tubing (rated for the applica­tion) to connect the high pressure airflow pickup to barb fitting P1 on the pressure transd ucer. At the zone controller, the P1 fitting is on the side with the filter installed. Be careful to avoid sharp bends in the tubing, because malfunctions may occur if the tubing is bent too sharply. Use at least 2 ft of tubing for reading stability.
1
4. Use field-supplied
/4-in. tubing (rated for the applica­tion) to connect the low pressure airflow pickup to barb fitting P2 on the pressure transducer. Be careful to avoid sharp bends in the tubing, because malfunctions may occur if the tubing is bent too sharply. Use at least 2 feet of tubing for stability.
7
Page 8
Voltage
Line
+24V
SPT
SPT
RH/IAQ
GND
SAT
GND
SECFLOW
TRAN
comunications
comunications
Not used
CCN
PAT
T56
GND
SAT
+10V
Y
Bl
DMPPOS
GND
REMOTE
N/A
GND
Or
R
(+)
W
(GND)
B
(-)
24 VAC
CCN
HEAT2HEAT1 24VAC
GROUND
TRANSFORMER
TERMINAL
GROUND
Low
10
80...110s
35 in-lb(4Nm)
Automation
Switzerland
Made in
By Belimo
HF23BJ042
50/60Hz
24VAC/DC
Hi
2W
3VA
com
RBW
Wht
Fig. 8A Zone Controller Wiring Single Duct Air Terminal, Cooling Only
RedBlk
Ora
BluYel
Carrier Comfort Network
CCN
LEGEND
Supply-Air Temperature Sensor
Space Temperature Sensor
SAT
SPT
Transformer
Field Wiring
Factory Wiring
TRAN
303
8
Page 9
SPT
Voltage
Line
SAT
comunications
comunications
CCN
CCN
Not used
24 VAC
TRAN
GROUND
TRANSFORMER
TERMINAL
GROUND
HWV
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
SAT
+10V
Low
T56
Y
GND
GND
Bl
DMPPOS
PAT
REMOTE
N/A
GND
Or
R
(+)
W
(GND)
B
(-)
HEAT2HEAT1 24VAC
RBW
Hi
LEGEND
WhtRedBlk
80...110s
10
35 in-lb(4Nm)
50/60Hz
24VAC/DC
2W
3VA
com
Fig. 8B Zone Controller Wiring Single Duct Air Terminal, Two-Position Hot Water Heat
Ora
Carrier Comfort Network
Hot Water Valve
Supply-Air Temperature Sensor
Space Temperature Sensor
Transformer
Field Wiring
Factory Wiring
CCN
HWV
SAT
SPT
TRAN
be used.
*Normally open or normally closed valve may
Automation
Switzerland
Made in
By Belimo
HF23BJ042
9
BluYel
303
Page 10
SPT
Voltage
Line
SAT
comunications
comunications
CCN
CCN
Not used
TRAN
24 VAC
GROUND
TRANSFORMER
GROUND
TERMINAL
CL
OP
COM
HWV
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
SAT
+10V
Low
T56
Y
GND
GND
Bl
DMPPOS
PAT
REMOTE
N/A
GND
Or
R
(+)
W
(GND)
B
(-)
HEAT2HEAT1 24VAC
RBW
Hi
303
WhtRedBlk
80...110s
10
35 in-lb(4Nm)
50/60Hz
24VAC/DC
2W
3VA
com
Fig. 8C Zone Controller Wiring Single Duct Air Terminal, Modulating Hot Water Heat
Ora
Transformer
Field Wiring
Fac tory W irin g
Space Temperature Sensor
Supply-Air Temperature Sensor
Hot Water Valve
Carrier Comfort Network
Automation
Switzerland
*Required for some spring return modulating
valves.
TRAN
SPT
SAT
HWV
CCN
LEGEND
Made in
By Belimo
HF23BJ042
BluYe l
10
Page 11
SPT
SAT
Line
Voltage
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
comunications
CCN
comunications
Not Used
CCN
PAT
T56
SAT
+10V
Y
GND
GND
Bl
DMPPOS
REMOTE
N/A
GND
Or
R
(+)
W
(GND)
B
(–)
TRAN
GROUND
24 VAC
HEAT2HEAT1 24VAC
RBW
TRANSFORMER
GROUND
TERMINAL
Low
H2 H1
Hi
WhtRedBlk
2W
80...110s
10
35 in-lb(4Nm)
50/60Hz
24VAC/DC
3VA
com
OraBluYel
Fig. 8D Zone Controller Wiring Single Duct Air Terminal, Staged Electric Heat (2 Stages)
Made in
By Belimo
Automation
Switzerland
HF23BJ042
Carrier Comfort Network
Heater Relay
Hot Water Valve
Supply-Air Temperature Sensor
Space Temperature Sensor
Transformer
Field Wiring
Factory Wiring
CCN
H
HWV
SAT
SPT
LEGEND
TRAN
11
801
Page 12
Voltage
Line
SAT
SPT
comunications
comunications
CCN
CCN
Not used
T56
SAT
SPT
GND
+24V
GND
RH/IAQ
Carrier Comfort Network
Heater Relay
Supply-Air Temperature Sensor
Space Temperature Sensor
Transformer
Field Wiring
Fac tory W irin g
CCN
H
SAT
SPT
LEGEND
TRAN
NOTE: The VAV fan terminal zone controller is used on single duct air
terminals with 3 stages of electric heat.
+10V
Y
SECFLOW
Bl
DMPPOS
FAN AC
GND
GND
FAN
PAT
REMOTE
N/A
GND
Or
Used
24 VAC
Not
R
R
Heat3
CW
B
W
B
W
COM
CCW
Second
Damper
TRAN
24 VAC
HEAT2HEAT1 24VAC
GROUND
TRANSFORMER
GROUND
TERMINAL
RBW
Low
Hi
WhtRedBlk
80...110s
10
H3 H2 H1
35 in-lb(4Nm)
50/60Hz
24VAC/DC
2W
3VA
com
Fig. 8E Zone Controller Wiring Single Duct Air Terminals, Staged Electric Heat (3-Stage)
Ora
Automation
Switzerland
Made in
By Belimo
HF23BJ042
BluYel
303
12
Page 13
Line
Voltage
SPT
Line
Voltage
Fan
Contactor
M
Fan Motor
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
comunications
Not Used
T56
SAT
+10V
Y
GND
Bl
DMPPOS
FAN
AC
GND
FAN
PAT
REMOTE
N/A
GND
Or
24 VAC
Not
Used
R
(+)
Heat3
CW
W
B
(GND)
COM
Second
(–)
CCW
Damper
CCN
comunications
CCN
TRAN
GROUND
TRANSFORMER
24 VAC
GROUND
TERMINAL
HEAT2HEAT1 24VAC
RBW
Carrier Comfort Network
CCN
LEGEND
Space Temperature Sensor
Transformer
Field Wiring
Factory Wiring
SPT
TRAN
Low
10
80...110s
35 in-lb(4Nm)
Automation
Switzerland
Made in
By Belimo
HF23BJ042
50/60Hz
24VAC/DC
Hi
2W
3VA
com
WhtRedBlk
Fig. 8F Zone Controller Wiring Fan Powered Terminals, Cooling Only
OraBluYel
13
801
Page 14
M
Fan Motor
Line
Voltage
+24V
SPT
SPT
GND
SAT
Not Used
comunications
CCN
SAT
T56
GND
PAT
REMOTE
B
W
R
Line
comunications
CCN
24 VAC
Voltage
TRAN
GROUND
TRANSFORMER
GROUND
TERMINAL
Fan Contactor
HWV
RH/IAQ
GND
+10V
SECFLOW
Y
DMPPOS
FAN AC
Low
N/A
GND
GND
Bl
Or
FAN
24 VAC
Not Used
(+)
Heat3
CW
(GND)
(-)
COM
Second
CCW
Damper
HEAT2HEAT1 24VAC
RBW
Hi
WhtRedBlk
LEGEND
801
80...110s
10
Carrier Comfort Network
Hot Water Valve
Supply-Air Temperature Sensor
Space Temperature Sensor
Transformer
Field Wiring
Factory Wiring
CCN
HWV
SAT
SPT
TRAN
35 in-lb(4Nm)
Automation
Switzerland
Made in
By Belimo
HF23BJ042
50/60Hz
24VAC/DC
3VA
com
OraBluYe l
Fig. 8G Zone Controller Wiring Fan Powered Terminals, Two-Position Hot Water Heat
14
2W
Page 15
Line
Voltage
SPT
SAT
PAT*
Line
Voltage
M
Fan Motor
Fan Contactor
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
comunications
comunications
CCN
CCW
CCN
Not Used
T56
FAN A C
GND
Bl
DMPPOS
GND
FAN
PAT
REMOTE
N/A
GND
Or
24 VAC
Not
Used
R
(+)
Heat3
CW
W
(GND)
B
(-)
COM
Second
Damper
SAT
+10V
Y
TRAN
GROUND
TRANSFORMER
24 VAC
GROUND
TERMINAL
HEAT2HEAT1 24VAC
RBW
LEGEND
Hi
24V*
COM
Low
OP
CL
HWV
WhtRedBlk
2W
80...110s
10
Transformer
Field Wiring
Factory Wiring
Space Temperature Sensor
Supply-Air Temperature Sensor
Primary Air Temperature Sensor
Hot Water Valve
Carrier Comfort Network
TRAN
SPT
SAT
PAT
HWV
CCN
*Required only on Linkage master if on a non-compatible air source.
35 in-lb(4Nm)
Automation
Switzerland
Made in
By Belimo
HF23BJ042
50/60Hz
24VAC/DC
3VA
com
OraBluYe l
Fig. 8H Zone Controller Wiring Fan Powered Terminals, Modulating Hot Water Heat
15
801
Page 16
M
Fan Motor
Line
Voltage
SPT
Field Wiring
SAT
PAT*
Line
Voltage
Factory Wiring
TRAN
comunications
Not Used
CCN
CCN
comunications
24 VAC
CCN Carrier Comfort Network
H Heater Relay
LEGEND
GROUND
TRANSFORMER
GROUND
TERMINAL
PAT Primary Air Temperature Sensor
SAT Supply-Air Temperature Sensor
SPT Space Temperature Sensor
TRAN Transformer
Fan Contactor
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
SAT
Low
+10V
Y
T56
DMPPOS
FAN AC
GND
Bl
GND
FAN
Or
PAT
REMOTE
N/A
24 VAC
GND
Not Used
Heat3
B
W
R
CW
(GND)
(-)
COM
Second
CCW
Damper
HEAT2HEAT1 24VAC
RBW
(+)
Hi
801
WhtRedBlk
Fig. 8I Zone Controller Wiring Fan Powered Terminals, Staged Electric Heat
80...110s
10
35 in-lb(4Nm)
50/60Hz
24VAC/DC
3VA
com
2W
H3 H2 H1
OraBluYel
Automation
Switzerland
Made in
HF23BJ042
By Belimo
*Required only on Linkage master if on a non-compatible air source.
16
Page 17
SPT
Not Used
CCN
comunications
CCN
comunications
LINE
VOLTAGE
24 VAC
TRAN
TRANSFORMER
GROUND
TERMINAL
GROUND
PRIMARY DAMPER 33ZCFANTRM
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
SAT
+10V
Low
T56
Y
DMPPOS
FAN AC
GND
Bl
GND
FAN
PAT
Or
REMOTE
N/A
24 VAC
GND
Not Used
Heat3
R
(+)
Second
Damper
CW
W
(GND)
B
(-)
COM
CCW
Hi
SHIELD
HEAT2HEAT1 24VAC
RBW
SHIELDED (CCN-TYPE) CABLE
10
80...110s
35 in-lb(4Nm)
Automation
Switzerland
Made in
By Belimo
HF23BJ042
17
50/60Hz
24VAC/DC
2W
3VA
com
WhtRedBlk
OraBluYe l
LEGEND
Carrier Comfort Network
CCN
Space Temperature Sensor
Transformer
SPT
TRAN
Field Wiring
Fig. 8J Zone Controller Wiring Dual Duct Applications
Factory Wiring
303
Page 18
GND
+10V
SECFLOW
CW
GND
CCW
Transformer
Field Wiring
Factory Wiring
Space Temperature Sensor
Carrier Comfort Network
TRAN
SPT
CCN
LEGEND
Or
Bl
Y
RBW
SECONDARY DAMPER — 33ZCSECTRM
Low
10
80...110s
35 in-lb(4Nm)
Automation
Switzerland
Made in
By Belimo
HF23BJ042
50/60Hz
24VAC/DC
Hi
2W
3VA
com
WhtRedBlk
OraBluYe l
Fig. 8J Zone Controller Wiring Dual Duct Applications (cont)
18
Page 19
Install Sensors
SPACE TEMPERATURE SENSOR INSTALLATION A space temperature sensor must be installed for each zone controller. There are three types of SPT sensors available from Carrier: the 33ZCT55SPT space temperature sensor with timed override button, the 33ZCT56SPT space temperature sensor with timed override button and set point adjustment and t he 33ZCT58SP T with liquid crystal display. See Fig. 10.
The space temperature sensor is used to meas ure the build­ing interior temperature and should be located on an interior building wall. The sensor wall plate accommodates the NEMA standard 2 x 4 junction box. The sensor can be mounted direct­ly on the wall surface if accpectable by local codes.
Do not mount the sensor in drafty locations such as near air conditioining or heating ducts, over heat sources such as base­board heaters, radiators, or directly above wall mounted l ight­ing dimmers. Do not mount the sensor near a window which may be opened, near a wall corner, or a door. Sensors mounted in these areas will have inaccurate and erratic sensor readings.
The sensor should be mounted approximately 5 ft from the floor, in an area representing the average temperature in the space. Allow at least 4 ft between the sensor and any corner and mount the sensor at least 2 ft from an open doorway.
Install the sensor as follows (see Fig. 11):
1. Locate the two Allen type screws at the bottom of the sensor.
2. Turn the two screws clockwise to release the cover from the sensor wall mounting plate.
3. Lift the cover from the bottom and then release it from the top fasteners.
4. Feed the wires from the electrical box through the opening in the center of the sensor mounting plate.
5. Using two no. 6-32 x 1 mounting screws (provided with the sensor), secure the sensor to the electrical box.
6. Use 20 gage wire to connect the sensor to the control­ler. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and set point adjustment connections. The standard CCN communication cable may be used. If the set point adjustment (slidebar) is not required, then an unshielded, 18 or 20 gage, two-conductor, twisted pair cable may be used.
The CCN network service jack requires a separate, shielded CCN communication cable. Always use sepa­rate cables for CCN communication and sensor wir­ing. (Refer to Fig. 12 for wire terminations.)
7. Replace the cover by inserting the cover at the top of the mounting plate first, then swing the cover down over the lower portion. Rotate the two Allen head screws counterclockwise until the cover is secured to the mounting plate and locked in position.
8. For more sensor information, see Table 1 for ther­mistor resistance vs temperature values.
NOTE: Clean sensor with damp cloth only. Do not use solvents.
Wiring the Space Temperature Sensor
(33ZCT55SPT and 33ZCT56SP T) To wire the sensor, perform the following (see Fig. 12 and 13):
1. Identify which cable is for the sensor wiring.
2. Strip back the jacket from the cables for at least 3-inches. Strip
1
/4-in. of insulation from each conduc­tor. Cut the shield and drain wire from the sensor end of the cable.
3. Connect the sensor cable as follows: a. Connect one wire from the cable (RED) to the
SPT terminal on the controller. Connect the other end of the wire to the left terminal on the SEN ter­minal block of the sensor.
b. Connect another wire from the cable (BLACK) to
the GND terminal on the controller. Connect the other end of t h e w i re to the rem ain i ng op e n t erm i ­nal on the SEN terminal block.
c. On 33ZCT56SPT thermostats, connect the re-
maining wire (WHITE/CLR) to the T56 terminal on the controller. Connect the other end of the wire to the right most terminal on the SET termi­nal block.
d. In the control box, install a No. 6 ring type crimp
lug on the shield drain wire. Install this lug under the mounting screw in the upper right corner of the controller (just above terminal T1).
e. On 33ZCT56SPT thermostats install a jumper
between the two center terminals (right SEN and left SET).
Wiring the Space T emperature Sensor (33ZCT58SPT) T58 space temperature sensor is wired differently than other conventional sensors. The T58 sends all its sensor information through the CCN bus to the zone controller that is is associated with. The SPT sensor wiring connections are not used. The T58 sensor does not need to be directly wired to the zone controller.
The T58 sensor may be powered by a separate 24-V AC pow­er supply or may be connected to the J1 24 VAC power termi­nals on the zone controller. Be sure that the polarity of the power supply connections are consistent. For multiple devices wired to the same power supply, all positive (+) and negative (–) termi­nals should be wired in the same polarity.
Wire the T58 sensor to the CCN. Connect the CCN + termi­nal to the RED signal wire (CCN+). Connect the CCN – termi­nal to the BLACK signal wire (CCN–). Connect the GND terminal to the WHITE/CLEAR signal wire (Ground). Refer to the T58 sensor Installation Instructions for more information on installing and wiring the sensor.
IMPORTANT: The T58 sensor must be configured with
the bus address and device type of the zone controller
before it will broadcast temperature to the zone control-
ler. Refer to the T58 sensor Installation Instructions for
more information on configuring the sensor.
Wiring the CCN Network Communication Service Jack See Fig. 12, 13, and 14. To wire the service jack, perform the following:
1. Strip back the jacket from the CCN communication cable(s) for at least 3 inches. Strip
1
/4-in. of insulation from each conductor. R emove the shield and separate the drain wire from the cable. Twist together all the shield drain wires and fasten them together us ing an closed end crimp lug or a wire nut. Tape off any exposed bare wire to prevent shorting.
2. Connect the CCN + signal wire(s) (RED) to Ter minal 5.
3. Connect the CCN – signal wire(s) (BLACK) to Ter minal 2.
4. Connect the CCN GND signal wire(s) (WHITE/CLR) to Terminal 4.
The
19
801
Page 20
LOW PRESSURE TUBING
L
H
NOTE: Minimum length of tubing is 2 ft.
0
HF23BJ042
Made in Switzerland
by Belimo Automation
LR 92800
NEMA 2
LISTED
94D5 TEMP. IND. & REG. EQUIP.
Class 2 Supply
yel
U
L
5K
WIP
ora
blu
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60Hz 3VA 2W
COM
2
1
red
blk
1
3
wht
HIGH PRESSURE TUBING
Fig. 9 Airflow Pickup Installation
Cool
Warm
Fig. 10 Space Temperature Sensor
(P/N 33ZCT56SPT Shown)
NOTE: Dimensions are in inches.
Fig. 11 Space Temperature Sensor and Wall
Mounted Humidity Sensor Mounting
20
Page 21
SW1
2
3
45
61
SW1
SEN
SET
Cool Warm
WHT
(T56) BLK (GND) RED (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
JUMPER TERMINALS AS SHOWN
2
3
SEN
45
61
RED(+)
WHT(GND)
BLK(-)
CCN COM
BLK (GND)
RED (SPT)
Fig. 12 Space Temperature Sensor Wiring
(33ZCT55SPT)
Table 1 Thermistor Resistance vs Temperature Values for Space Temperature Sensor, Return-Air
Temperature Sensor, and Supply-Air Temperature Sensor
TEMP
(C)
40 40 335,65135 31 242,19530 22 176,68325 13 130,24320 4 96,97415 5 72,89510 14 55,298
5 23 42,315
0 32 32,651
5 41 25,395 10 50 19,903 15 59 15,714 20 68 12,494 25 77 10,000 30 86 8,056 35 95 6,530 40 104 5,325 45 113 4,367 50 122 3,601 55 131 2,985 60 140 2,487 65 149 2,082 70 158 1,752
SENSOR WIRING
TEMP
(F)
Fig. 13 Space Temperature Sensor Wiring
(33ZCT56SPT)
RESISTANCE
(Ohms)
21
Page 22
Wiring when distance between zone controller and space temperature sensor is 100 feet or less
CCN COMM BUS
3 COND COMM CABLE (TYP)
2 COND TWISTED CABLE OR 3 COND CABLE (TEMP SENSOR WIRING) (TYP)
100 FT. MAXIMUM
AIR TERMINAL
UNIT (TYP)
ZONE CONTROLLER (TYP)
Warm
Cool
SPACE
TEMPERATURE
SENSOR
Wiring when distance between zone controller and space temperature sensor is greater than 100 feet
CCN COMM BUS
2 COND TWISTED CABLE OR 3 COND CABLE (TEMP SENSOR WIRING) (TYP)
AIR TERMINAL
UNIT (TYP)
ZONE CONTROLLER (TYP)
Warm
Cool
SPACE
TEMPERATURE
SENSOR
Fig. 14 Communication Bus Wiring to Zone Controller
DISTANCE GREATER
THAN 100 FT.
Warm
Cool
Warm
Cool
Before wiring the CCN connection, refer to the Connect to the CCN Communication Bus section on page 26, for commu­nication bus wiring and cable selection. The cable selected must be identical to the CCN communication bus wire used for the entire network.
The other end of the communication bus cable must be con­nected to the remainder of the CCN communication bus. If the cable is installed as a T-tap into the bus, the cable length cannot exceed 100 ft. Wire the CCN service jack of the sensor in a daisy chain arrangement with other equipment. Refer to the Connect to the CCN Communication Bus section, page 26, for more details.
22
Page 23
PRIMARY AIR TEMPERATURE SENSOR INSTALLA­TION A primary air temperature (PAT) sensor is used on a zone controller which is functioning as a Linkage Coordinator for a non CCN/Linkage compatible air source. The part num­ber is 33ZCSENP AT. See Fig. 15.
When used on a zone controller, try to select a zone control­ler which will al low in stalla tion of the PAT sensor in the mai n trunk, as close to the air source as possible. See Fig. 16.
SUPPLY AIR TEMPERATURE (SAT) SENSOR INSTAL­LATION On terminals with heat, the SAT sensor is re­quired. The SAT must be installed in the duct downstream from the air terminal. The SAT sensor is also sometimes called a duct temperature (DT) sensor. The part number is 33ZCSENSAT.
The SAT sensor probe is 6 inches in length. The tip of the probe must not touch the inside of the duct. Use field-supplied bushings as spacers when mounting the probe in a duct that is 6 in. or less in diameter.
If the unit is a cooling only unit, the SAT is not required.
Fig. 15 Primary Air Temperature Sensor
(Part Number 33ZCSENPAT)
Fig. 16 Primary Air Temperature Sensor
Installation (Unit Discharge Location)
If the unit is equipped with electric reheat, e nsure that the sensor is installed at least 2 ft downstream of the electric heater. See Fig. 17 for the sensor location in this application.
If the unit has an octopus connected directly at the dis­charge, install the sensor in the octopus. If the unit has an elec­tric heater, the two foot minimum distance between the sensor and the heater must be maintained. See Fig. 17 for the sensor location in this application.
Disconnect electrical power before wiring the zone control­ler. Electrical shock, personal injury, or damage to the zone controller can result.
Do not run sensor or relay wires in the same conduit or race­way with Class 1 AC or DC service wiring. Do not abrade, cut, or nick the outer jacket of the cable. Do not pull or draw cable with a force that may harm the physical or electrical properties. A void splices in any control wiring.
Perform the following steps to connect the SAT sensor to the zone controller:
1. Locate the opening in the control box. Pass the sensor probe through the hole.
2. Drill or punch a
1
/4-in. hole in the duct downstream of the unit, at a location that conforms to the require­ments shown i n Fig. 17.
3. Use two field-supplied, self-drilling screws to secure the sensor probe to the duct. Use field-supplied bush­ings as spacers when installing the sensor probe in a duct 6 in. or less in diameter.
Perform the following steps if state or local code requires the use of conduit, or if your installation requires a cable length of more than 8 ft:
1. Remove the center knockout from a field-supplied 4 x 2-in. junction box and secure the junction box to the duct at the location selected for the sensor probe.
2. Drill a the junction box.
3. Connect a
1
/2-in. hole in the duct through the opening in
1
/2-in. nominal field-supplied conduit between the zone controller enclosure and the junction box.
4. Pass the sensor probe wires through the conduit and insert the probe in the duct. Use field-supplied bush­ings as spacers when installing the sensor probe in a duct 6 in. or less in diameter.
5. Secure the probe to the duct with two field-supplied self-drilling screws.
6. If you are extending cable length beyond 8 ft, use ple­num rated, 20 AWG, twisted pair wire.
7. Connect the sensor leads to the zone controllers wir­ing harness terminal board at the terminals labeled SAT and GND.
8. Neatly bundle and secure excess wire.
INDOOR AIR QUALITY SENSOR INSTALLATION
The indoor air quality (IAQ) sensor accessory monitors carbon dioxide levels. This information is used to modify the position of the outdoor air dampers to admit more outdoor air as required to provide the desired ventilation rate. Two types of sensors are supplied. The wall sensor can be used to monitor the conditioned air space; the duct sensor monitors the return air duct. Both wall and duct sensors use infrared technology to measure the levels of CO
present in the air. The wall sensor is
2
available with or without an LCD readout to display the CO level in ppm. See Fig. 18.
The sensor part number is 33ZCSENCO2. To mount the sensor, refer to the installation instructions shipped with the ac­cessory kit.
2
23
800
Page 24
2 FT. MIN.
UNIT WITH ELECTRIC REHEAT
PRIMARY AIR INLET
AIR
TERMINAL
UNIT
ZC
UNIT WITH OCTOPUS
AIR
TERMINAL
UNIT
ZC
The CO
PRIMARY AIR INLET
Zone Controller
ZC
Fig. 17 Supply Air Temperature Probe (Part No. 33ZCSENSAT) Locations
sensors (33ZCSENCO2) factory set for a range of
2
0 to 2000 ppm and a linear voltage output of 0 to 10 vdc. Figure 19 shows ventilation rates for various CO
set points
2
when outside air with a typical CO2 level of 350 ppm is used. Refer to the instructions supplied with the CO
sensor for elec-
2
trical requirements and terminal locations. The zone controller requires 24 vac 25 va transformer to provide power to the sensor.
5.625 (14.3)
5
(12.7)
HEAT
HEAT
SAT
2 FT. MIN.
OCTOPUS
SAT
T o convert the CO
sensor into a duct-mounted CO2 sensor,
2
the duct-mounted aspirator (33ZCASPCO2) will need to be purchased.
To accurately monitor the quality of the air in the condi­tioned air space, locate the sensor near the return air grille so it senses the concentration of CO
leaving the space. T he sensor
2
should be mounted in a location to avoid direct breath contact.
Do not mount the space sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft between the sensor and any corner. A void mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return air stream.
To accurately monitor the quality of the air in the return air duct, locate the sensor at least 6 in. upstream or 15 in. down­stream of a 90 degree turn in the duct. The downstream loca­tion is preferred. Mount the sensor in the center of the duct.
3.25 (8.3)
1.125 (2.9)
Fig. 18 Indoor Air Quality (CO2) Sensor
(33ZCSENCO2)
303
0.25
(0.8)
IMPORTANT: If the sensor is mounted in the return air duct, readjust the mixed-air dampers to allow a small amount of air to flow past the return air damper when­ever the mixing box is fully open to the outside air. If the damper is not properly adjusted to provide this mini­mum airflow, the sensor may not detect the indoor-air quality during the economizer cycle.
24
Page 25
Fig. 19 Ventilation Rated Based on
*
CO2 Set Point
Indoor Air Quality Sensor Wiring
To wire the sensors after they are mounted in the conditioned air space and return air duct, see Fig. 20 and the instructions shipped with the se n­sors. For each sensor, use two 2-conductor 18 AWG twisted­pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the con­trol board terminals. To connect the sensor to the control board, identify the positive (+) PIN-8 and ground (GND) PIN-7 termi­nals on the sensor and connect the positive terminal to terminal RH/IAQ and connect the ground terminal to terminal GND.
HUMIDITY SENSOR (WALL-MOUNTED) INSTALLA­TION The accessory space humidity sensor is installed on an interior wall t o measu re th e rela tive humidi ty of the air with­in the occupied space. See Fig. 21.
The use of a standard 2- x 4-in. electrical box to accommo­date the wiring is recommended for installation. The sensor can be mounted directly on the wall, if acceptable by local codes.
If the sensor is installed directly on a wall surface, install the humidity sensor using 2 screws and 2 hollow wall anchors (field-supplied); do not overtighten screws. See Fig. 11.
Do NOT clean or touch the sensing element with chemical solvents; they can permanently damage the sensor.
The sensor must be mounted vertically on the wall. The Carrier logo should be oriented correctly when the sensor is properly mounted.
DO NOT mount the sensor in drafty areas such as near heat­ing or air-conditioning ducts, open windows, fans, or over heat sources such as baseboard heaters, radiators, or wall-mounted light dimmers. Sensors mounted in those areas will produce in­accurate readings.
Avoid corner locations. Allow at least 4 ft between the sen­sor and any corner. Airflow near corners tends to be reduced, resulting in erratic sensor readings.
Sensor should be vertically mounted approximately 5 ft up from the floor, beside the space temperature sensor.
For distances up to 500 feet, use a 3-conductor, 18 or 20 AWG cable. A CCN communication cable can be used, although the shield is not required. The shield must be removed from the sensor end of the cable if this cable is used. See Fig. 22 for wiring details.
The power for the sensor is provided by the control board. The board provides 24 vdc for the sensor. No additional power source is required.
T o wire the sensor , perform the following:
1. At the sensor, remove 4-in. of jacket from the cable.
1
Strip
/4-in. of insulation from each conductor. Route the cable through the wire clearance opening in the center of the sensor. See Fig. 22.
2. Connect the RED wire to the sensor screw terminal marked (+).
3. Install one lead from the resistor (supplied with the sensor) and the WHITE wire, into the sensor screw ter­minal marked (–). After tightening the screw terminal, test the connection by pulling gently on the resistor lead.
4. Connect the remaining lead from the resistor to the BLACK wire and secure using a closed end type crimp connector or wire nut.
5. Using electrical tape, insulate any exposed resistor lead to prevent shorting.
6. At the control box, remove the jacket from the cable and route the RED conductor over to the left side of the control board. Route the remaining conductors to the right side of the control board.
RH/IAQ
GND
21
24 VAC
87
SEPARATE ISOLATED
POWER SUPPLY
REQUIRED
(24 VAC, 25 VA
MINIMUM)
LINE VOLTAGE
0
HF23BJ042
Made in Switzerland
by Belimo Automation
LR 92800
NEMA 2
LISTED 94D5
U
TEMP. IND. &
L
REG. EQUIP.
Class 2 Supply
5K
WIP
blu
yel
ora
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60Hz 3VA 2W
COM
2
1
red
blk
1
3
wht
Do not connect to the same transformer that supplies power to the zone controller.
Fig. 20 Indoor Air Quality Sensor Wiring
25
303
Page 26
Fig. 21 Wall Mounted Relative Humidity Sensor
(P/N 33AMSENRHS000)
7. Strip
1
/4-in. of insulation from each conductor
and equip each with a
1
/4-in. female quick connect
terminal.
8. Connect the RED wire to terminal +24v on the control board.
9. Connect the BLACK wire to terminal GND on the control board.
10. Connect the WHITE/CLEAR wire to terminal RH/IAQ on the control board.
11. Connect shield to ground (if shielded wire is used).
Remote Occupancy Contact
The remote occu­pancy input (J4 pin 2) has the capability to be connected to a normally open or normally closed occupancy dry contact. Wire the dry contact as show in Fig. 23 between J4 Pin 2 and 24 VAC J1 Pin 1. The 24 VAC necessary to supply the ComfortID Controller remote occupancy contact input shall be supplied using the existing ComfortID Controller.
Connect the Outputs
Wire the zone controller’s outputs (fan, staged heat, valves) as shown in the applicable wiring diagrams in Fig. 8A-J.
Modulating Baseboard Hydronic Heating
stall the water valve on the leaving water end of the baseboad heater. See Fig. 24. Observe the fluid flow direction when mounting the valve. Be sure to properly heat sink the valve and direct the flame away from th e actuator and val ve body when sweating the va lve connect ions. Insta ll the leav ing water te m­perature sensor (33ZCSENCHG) on the hydronic heating coil as shown. The sensor accommodates nominal copper pipe
1
from
/2 to 1-in. (OD sizes from 5/8 to 1.125 in.). It should be secured to the pipe with the clamp supplied. If piping is larger than 1-in. nominal size, a field-supplied clamp must be used. Use fiberglass pipe insulation to insulate the sensor assembly.
Refer to Fig. 8C and 8H to wire the modulating water valve and the sensor to the zone controller. Connect the leaving water temperature sensor to the controller using the wiring connec­tions shown for the SAT sensor. (NOTE: The leaving water temperature sensor replaces the SA T sensor in this application.) Use 18 or 20 AWG wire for all connections. The water valve actuator housing may be used as a junction box if the leaving water temperature sensor cable is not long enough and the sen­sor cable must be extended to reach the controller.
For modulating hydronic heating applications, the default configuration must be changed to properly control the valve.
In-
Refer to the service configuration table and set the Heating Loop parameters as follows:
Proportional Gain = 20.0 Integral Gain = 0.5 Derivative Gain = 0.0 Start Value = 102.0
Also, set the Ducted Heat decision to YES and set the Max­imum Duct Temperature decision equal to the design (maxi­mum) boiler water temperature minus 20 degrees, but not greater than 200 degrees F.
Connect the CCN Communication Bus
The zone controllers connect to the bus in a daisy chain arrange­ment. The zone controller may be installe d on a pri mary CCN bus or on a secondary bus from the primary CCN bus. Con­necting to a secondary bus is recommended.
At 9,600 baud, the number of controllers is limited to 128 zones maximum, with a limit of 8 systems (Linkage Coordina­tor configured for at least 2 zones). Bus length may not exceed 4000-ft, with no more than 60 devices on any 1000-f t section. Optically isolated RS-485 repeaters are required every 1000 ft.
At 19,200 and 38,400 baud, the number of controllers is limited to 128 maximum, with no limit on the number of Linkage Coordinators. Bus length may not exceed 1000 ft.
The first zone controller in a network connects directly to the bridge and the others are wired sequentially in a daisy chain fashion. Refer to Fig. 25 for an illustration of CCN Communi­cation Bus wiring.
The CCN Communication Bus also connects to the zone controller space temperature sensor. Refer to the Install the Sensors section for sensor wiring instructions.
COMMUNICATION BUS WIRE SPECIFICATIONS The Carrier Comfort Network (CCN) Communication Bus wiring is field-supplied and field-installed. It consists of shielded three-conductor cable with drain (ground) wire. T he cable selected must be identical to the CCN Com munication Bus wire used for the entire network. See Table 2 for recom­mended cable.
Table 2 Recommended Cables
MANUFACTURER CABLE PART NO. Alpha American Belden Columbia
NOTE: Conductors and drain wire must be at least 20 AWG (American Wire Gage), stranded, and tinned copper. Individual con­ductors must be insulated with PVC, PVC/nylon, vinyl, teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20° C to 60° C is required.
2413 or 5463
A22503
8772
02525
CONNECTION TO THE COMMUNICATION BUS
1. Strip the ends of the red, white, and black conductors of the communication bus cable.
2. Connect one end of the communication bus cable to the bridge communication port labeled COMM2 (if connecting on a secondary bus).
When connecting the communication bus cable, a color code system for the entire network is recom­mended to simplify installation and checkout. See Table 3 for the recommended color code.
Table 3 Color Code Recommendations
SIGNAL TYPE
+ Ground
CCN BUS WIRE
COLOR
Red 1 White 2 Black 3
PLUG PIN
NUMBER
801
26
Page 27
3. Connect the other end of the communication bus cable to the terminal block labeled CCN in the zone control­ler of the first air terminal. Following the co lor code in Table 3, connect the Red (+) wire to Terminal 1. Connect the White (ground) wire to Terminal 2. Con­nect the Black (–) wire to Terminal 3.
4. Connect additional zone controllers in a daisy chain fashion, following the color coded wiring scheme in Table 3. Refer to Fig. 25.
NOTE: The communication bus drain wires (shield) must be tied together at each zone controller. If the communica­tion bus is entirely within one building, the resulting contin­uous shield must be connected to ground at only one single point. If the communication bus cable exits from one build­ing and enters another building, connect the shields to ground at a lightning suppressor in each building where the cable enters or exits (one point only).
3 CONDUCTOR 20 AWG CABLE
RED
+
-
RH/IAQ
WHITE
BLACK
SHIELD (IF USED)
499
RESISTOR
(SUPPLIED
W/SENSOR)
HUMIDITY SENSOR
0
HF23BJ042
Made in Switzerland
by Belimo Automation
LR 92800
NEMA 2
LISTED 94D5
U
TEMP. IND. &
L
REG. EQUIP.
Class 2 Supply
WIP
blu
yel
GND
+24V
1
35 in-lb (4 Nm)
80...110s
24VAC/DC 50/60Hz 3VA 2W
5K
COM
3
2
1
ora
wht
red
blk
Fig. 22 Humidity Sensor Wiring
27
Page 28
FIELD-SUPPLIED
DRY CONTACT SWITCH
comunications
Not used
CCN
Voltage
Line
comunications
24 VAC
CCN
TRAN
TRANSFORMER
GROUND
TERMINAL
GROUND
+24V
SPT
RH/IAQ
GND
GND
SECFLOW
SAT
T56
+10V
Y
Low
GND
GND
Bl
DMPPOS
PAT
N/A
GND
Or
R
(+)
W
(GND)
B
(-)
HEAT2HEAT1 24VAC
RBW
Fig. 23 Remote Occupancy Wiring
Hi
303
10
80...110s
35 in-lb(4Nm)
Automation
Switzerland
Made in
By Belimo
HF23BJ042
50/60Hz
24VAC/DC
2W
3VA
28
com
Wht
RedBlk
Ora
BluYel
LEGEND
Carrier Comfort Network
Supply-Air Temperature Sensor
Space Temperature Sensor
Transformer
Field Wiring
Factory Wiring
CCN
SAT
SPT
TRAN
Page 29
33ZCSENCHG (SENSOR)
1
2
CCN
DRAIN WIRE (TYP)
BLK (TYP)
WHT (TYP)
RED (TYP)
3
ZC (TYP)
FLOW
Fig. 24 Typical Water Valve and Sensor Installation
2
3
1
CCN
1/2 TUBE 3/4 TUBE 1 TUBE
1000 FT. MAXIMUM
2
1
CCN
3
1
2
CCN
GND
2
3
3
1
4
COMM 2
AIR TERMINAL
UNIT (TYP)
LEGEND
CCN ZC
Carrier Comfort Network Zone Controller
Fig. 25 Communication Bus Wiring
START-UP
Use the Carrier network communication software to start up
and configure the zone controller.
All set-up and set point configurations are factory-set and
field-adjustable.
®
Changes can be made using the ComfortWORKS
soft­ware, ComfortVIEW software, or Network Service Tool. The Network Service Tool is a portable interface device that al­lows the user to change system set-up and set points from a zone sensor or terminal control module. During start-up, the Carrier software can also be used to verify communication with each zone controller.
For specific operating instructions, refer to the literature
provided with the software.
Perform System Check-Out
1. Check correctness and tightness of all power and com­munication connections.
2. Check that all air terminals, ductwork, and zone con­trollers are properly installed and set according to installation instructions and job requirements.
BRIDGE (RECOMMENDED)
3. Check that all air duct connections are tight.
4. At the air terminals, check fan and system controls for proper operation. Verify that actuator screws are prop­erly tightened.
5. At the air terminals, check electrical system and con­nections of any optional electric reheat coil. If hot water reheat is used, check piping and valves against job drawings.
6. At the air terminals, make sure that all balancing dampers at box outlets are in the fully open position.
7. If using an air handler with field-installed controls, make sure controls and sensors h ave been installed and wired per manufacturer installati on inst ru ct ions .
8. At air handlers, verify that the motor starter and, if applicable, the Hand/Off/Auto (HOA) switch are installed and wired.
NOTE: The HOA switch must be in the Off position.
29
800
Page 30
9. Check to be sure the area around the air handler(s) is clear of construction dirt and debris.
10. Check that final filters are installed in the air han­dler(s). Dust and debris can adversely affect system operation.
11. Verify that the zone controller and the air handler con­trols are properly connected to the CCN bus.
Before starting the air source fan, make sure that dampe rs at the systems air terminals are not fully closed. Starting the fan with dampers closed will result in da mage to the system ductwork.
12. Remember to utilize good duct design and to provide sufficient straight duct at the inlet of the box. A mini­mum of three times the inlet size is recommended.
Network Addressing
when all the zone controllers are installed and powered, and the SPT sensors are wired and functioning properly. This method can be used if no addresses have been set previously. The ad­dress of an individual zone controller may be set by using the address search function on the Service Tool software when it is directly connected to the service port of the zone controller and the CCN bus is disconnected. This is the standard method of setting the address.
Addresses may also be set using the Service Tool Address Search Function if the zone controller is isolated from the CCN bus.
Each zone controller will default to an address of 0, 140 when its application software is initially loaded. Since multiple controllers will be on the same bus, a unique address must be assigned to each controller before the system can operate prop­erly. The assignment of controller addresses will be performed through software by using the Address Search function of the Network Service Tool, as follows:
1. The software recognizes that the Zone Controller's ad­dress, stored in the zone controller memory, has not been written yet (this will be true when the unit is first powered up on the job, or after a jumper-initiated reset).
2. Press the override button on the SPT (terminals J4-14 and J4-12 are shorted) for 1 to 10 seconds.
3. The zone controller address changes from 0, 140 to 239,
239 for a period of 15 minutes.
4. Use Network Service Tool to change the address from 239, 239 to a valid system address within 15 minutes.
NOTE: If the address is not changed from 239, 239 to a valid system address within 15 m inutes, the control­ler will revert to address 0, 140 and use of the override button will cause the address function to repeat. The operator MUST actively set the address even if the final desired address is 0, 140.
Initial Operation and Test
procedure:
1. Apply 24 vac power to the control.
2. Connect the service tool to the phone jack service port of the controller.
3. Using the service tool, upload the controller from address assigned in Network Addressing section above.
4. From the Terminal Service Configuration screen, properly configure the damper type and inlet size. If a round inlet is used, then enter the size directly in the Inlet Diameter decision. If a square, rectangular, or
Use the following method
Perform the following
elliptical damper inlet is supplied, then enter th e inlet size in square inches in the Inlet Area decision.
5. If the terminal damper closes in the CW direction, then no adjustment is required. Otherwise, locate the damper direction configuration decision (CW Rota­tion) and toggle the value to OP EN by usin g th e space bar. This configuration decision is also located on the Terminal Service Configuration screen.
6. After entering the area and rotation direction, verify operation of the damper. From the service tool Diag­nostic, Maintenance Screen, select the Zone Air Balance/Commissioning Table and force the Commis­sioning Mode point to Enable. Then select the Damper/Transducer Cal point and force this point to Enable. The controller automatically tests the actuator by fully closing the damper.
It checks the fully closed position to determine if the control was properly mounted. It then opens the damper. The control scales the actual actuator travel range used to a 0 to 100% open value. Finally the con­trol will close the damper, test, and zero the pressure transducer. When completed, the control automatically removes the force from the Damper/Transducer Cal point. If a failure occurs at any point during the testing, the Auto-Calibration point at the bottom of the s creen will indicate ALARM and the test will be aborted.
7. The actuator stroke has now been calibrated for the proper rotation.
Airflow Check
has been performed, the terminal is ready for an airflow check. To perform airflow check, make sure Terminal Type, Prim ary Inlet Size, and Pro be Multiplier settings on the Terminal Ser­vice Configuration screen are configured. If all of the terminals were installed with the dampers open, it is acceptable to start the fan at this time. If it becomes difficult for the air source to provide the necessary static pressure for airflow testing, it may be necessary to calibrate the damper transducer for a majority of terminals and check temperatures and set points to be sure most will be contro ll ing to le ss th an ma xi mum CFM wh e n the air source is started.
When the system fan is running and the static pressure is fairly stable access the Zone Air Balance/Commissioning table and force the Commissioning Mode Point to Enable. The sys­tem is now ready to enable maximum CFM a nd check if the airflow controls correctly with the maximum CFM set point. Read the Zone Air Balance/Commissioning table section on page 47 which describes the Zone Air Balance/Commissioning table and what adjustments can be made from this screen. If the maximum airflow function is working properly, the user can stop here and leave the rest of the airflow calibration for the air balance contractor.
If working with the air balance contractor, proceed with the minimum airflow calibration at this time. If this terminal is fan powered or the terminal was instal led with heat, and the heat configuration was already performed, continue with the fan and heat test while the Zone Air Balance/Commissioning table is still being displayed.
Fan and Heat Configuration and Test
form the following procedure to configure and test the fan and heat:
1. Display the Terminal Service Configuration screen to make sure the proper T ermin al Type and Heat Type are configured. See the Configuration section to answer questions about the individual configurations.
2. From the Diagnostics Maintenance Screen select the Zone Air Balance/Commissioning table.
3. Force the Commissioning Mode to Enable.
After the damper transducer calibration
Per-
501
30
Page 31
4. If the terminal is a parallel or series powered fan box, force the Fan Override to Enable. If the damper is open it may have to be repositioned to the proper position depending on the box type. Damper percent change will be displayed. After the damper is positioned cor­rectly, the fan relay should energize and the fan should run for a few seconds.
5. Make sure the fan runs and the Fan Override decision returns to disabled to ensure the fan is wired correctly for proper operation.
6. Force the Heating Override to Enable. If the unit is a single duct unit, this must be done with the primary terminal at reheat set point. The damper will modulate to maintain the terminal reheat CFM. The heat outputs will be commanded to provide maximum heat. If the unit is a fan powered terminal, the fan must be on.
NOTE: The CFM settings can be found under service con­figuration in the table AIRFLOW.
CONFIGURATION
The following sections describe the computer configuration screens which are used to configure the zone controller. The screens shown may be displayed differently when using differ­ent Carrier software.
Points Display Screen
allows the user to view the stat us of the air termi nal controlle r points. See Tabl e 4.
TERMINAL MODE The terminal mode is determine d by the equipment mode as reported by linkage and spac e require­ments determined by space temperature and set points. The ZEROCAL and COMMISS modes are the result of the activat­ing the commissioning maintenance table to perform terminal testing and commissioning.
T erminal Mode: Display Units ASCII
Default V alue COOL Display Range HEAT, COOL, VENT, FAN AND VENT, DEHUMID, WARM­UP, REHEAT, PRESSURE, EVAC, OFF, ZEROCAL, C OM MISS Network Access Read only
The Points Display screen
TERMINAL TYPE Terminal type is the confirmation of the terminal type configuration in the SERVCONF Service Config table.
T erminal Type: Display Units ASCII
Default value SINGLDUCT Display Range SINGLDUCT, PAR F AN , S ER FAN, DUALDUCT Network Access Read only
CONTROLLING SETPOINT Controlling Setpoint will display either the heating master reference or the cooling mas­ter reference depending upon what mode the terminal is in. The display will default to the heating master reference and display the last controlling master reference when in ne ither heating nor cooling.
Controlling Setpoint Display Units F (C)
Default V alue: –40 Display Range: –40 to 245 Network Access: Read only
SPACE TEMPERATURE Space temperature from 10 k thermistor (Type III) located in the space.
Space T emperature: Display Units F (C)
Default Value -40.0 Display Range -40.0 to 245.0 Network Access Read/W rite
PRIMARY AIRFLOW Volume of primary air calculated for pressure reading from the velocity pressure pickup probe located in the input collar of the air terminal.
Primary Airflow: Display Units cfm
Default V alue 0 Display Range 0 to 9999 Network Access Read/Write
PRIMARY DAMPER POSITION Damper position per­cent range of rotation determined by the transducer calibration procedure. The zone controller is designed be used on dampers with any range of rotation.
Primary Damper Position: Display Units % open
Default V alue 0 Display Range 0 to 100 Network Access Read only
DESCRIPTION DEFAULT POINT NAME Terminal Mode Ter min a l Type Controlling Setpoint Space Temperature Primary Airflow Primary Damper Position Supply Air Temperature Local Heating Capacity Terminal Fan Relative Humidity Air Quality (ppm) Secondary Airflow Primary Air Temperature Heat
Tabl e 4 Points Display Screen
COOL MODE
SINGLDUCT TYPE
-40.0 F CNTSP
-40.0 F SPT 0 cfm PRIFLO
100 % DMPPOS
0.0 F SAT
0 % HCAP
Off FAN
0 % RH RH
0 ppm AQ
0 cfm SECFLO
0.0 F PATEMP
Dsable HEAT
31
801
Page 32
SUPPLY AIR TEMPERATURE Temperature of the air leaving the zone controller downstream of any ducted heat source. Measured by a 10 k thermistor (Type III). This tem­perature is used to control the maximum discharge air to the space when local heat is active. The sensor is not required or recommended for cooling only terminals. If supply air temper­ature display is required by specification, on a cooling only box, a heat type other than zero must be configured. This will have no adverse affect on the operation of a cooling only terminal.
Supply Air Temperature: Display Units F (C)
Default V alue 0.0 Display Range -40.0 to 245.0 Network Access Read/Write
LOCAL HEATING CAPACITY When local heat at the terminal is enabled the percent of heat being delivered is deter­mined by the following formula for modulating (floating point) type heat:
% Capacity = [(SA T - SPT)/(Maximum Duct Temp – SPT )] The percent of heat delivered is deter mined by the follow-
ing for two-position hot water or staged electric heat:
% Output Capacity = (# of active stages/Total stages) * 100
Local Heating Capacity: Display Units % output capacity
Default V alue 0 Display range 0 to 100 Network Access Read only
TERMINAL FAN The commanded output for the terminal fan on a fan powered terminal.
T erminal Fan: Display Units Discrete ASCII
Default V alue Off Display Range Off/On Network Access Read/Write
RELATIVE HUMIDITY Space Relative Humidity read­ing from the optional relative humidity sensor. Used by Hu­midity control function if configured.
Relative Humidity: Display Units % RH
Default V alue 0 Display Range 0 to 100 Network Access Read/Write
AIR QUALITY Indoor air quality reading from a CO
sen-
2
sor installed in the space. Used by Air Quality control function if configured.
Air Quality (ppm):Display units None shown (parts per
million implied) Default V alue 0 Display range 0 to 5000 Network Access Read/Write
SECONDARY AIRFLOW Airflow reading from the sec­ondary pressure transducer, supplied with the secondary actua­tor, intended for dual duct and pressure control applications.
Secondary Airflow: Display Units cfm
Default V alue 0 Display Range 0 to 9999 Network Access Read/Write
PRIMARY AIR TEMPERATURE Primary air tempera­ture from sensor (10 kΩ, Type III), located in main trunk of ductwork for supply air provided by the air-handling equip­ment. Used for linkage coordination.
Primary Air T emperature: Display Units F (C)
Default V alue 0.0 Display Range -40.0 to 245.0 Network Access Read/W rite
HEAT ENABLE/DISABLE Provides enable/disable function for local heat at the terminal. When enabled the Local heat capacity function will run to operate the terminal heat.
Heat Display: Display Units Discrete ASCII
Default Value Dsable Display Range Dsabe/Enable Network Access Read/Write
Modify Controller Configuration
In Service T ool software, select the desired zone controller and access the Modify Controller Configuration Menu screen. This configura­tion screen is also displayed under CONFIGURE when using ComfortWORKS
®
and ComfortVIEW software.
The Modify Controller Configuration Menu screen is used to access the Alarm Limit Configuration screen, Controller Identification screen, Holiday Configuration screen, Linkage Coordinator Configuration screen, Occupancy Configuration screen, and Set Point scre en.
ALARM LIMIT CONFIGURATION SCREEN The Alarm Limit Configuration screen is used to configure the alarm settings for the zone controller. See T able 5.
DESCRIPTION DEFAULT POINT NAME Alarm Routing Control Re-Alarm Time SPT Occupied Hysteresis Unoccupied SPT
Low Limit High Limit
Occupied RH Low Limit High Limit
Unoccupied RH Low Limit High Limit
Air Quality Low Limit High limit
High Velocity Pressure
801
Table 5 Alarm Limit Configuration Screen
00000000 ROUTING
0RETIME
5.0 F SPTHYS
40 F 99 F
10 % 99 %
0 %
100 %
250 ppm
1200 ppm
1.2 in. wg HIGHVP
32
LOWLIM
HIGHLIM
LOWLIM
HIGHLIM
LOWLIM
HIGHLIM
LOWLIM
HIGHLIM
Page 33
Alarm Routing Control
This decision indicates which CCN system software or devices will receive and process alarms sent by the zone controller. This decision consists of eight digits each can be set to zero or one. A setting of 1 indi­cates alarms should be sent to this device. A setting of zero dis­ables alarm processing for that device. Currently the corre­sponding digits are configured for the following devices: first digit - user interface software; second digit - autodial gateway or Tel ink; fourth digit - alarm printer interface module; digits 3, and 5 through 8 - unused.
Alarm Routing Control: Range 00000000 to 11111111
Default Value 00000000
Re-Alarm Time
This decision is used to configure the num­ber of minutes the zone controller will wait before an alarm condition which has not been corrected will be re-transmitted on the communications network. Re-alarming of an alarm con­dition will continue until the condition no longer exists.
Alarm Re-Alarm Time: Units Minutes
Range 0 to 1440 Default Value 0 (Disabled)
Space Temperature Occupied Hysteresis
This configura­tion defines the range above the occupied high set point and be­low the occupied low set point that the space temperature must exceed for an alarm condition to exist during occupied hours.
Space Temperature Occupied Hysteresis: Units delta F (delta C)
Range 0.0 to 99.9 Default V alue 5.0
Unoccupied Space Temperature Low Limit
This configu­ration defines the lowest temperature that the unoccupied space can be before an alarm is generated.
Unoccupied Space T emperature Low Limit: Units F (C)
Range 0 to 255 F Default V alue 40
Unoccupied Space Temperature High Limit
This configu­ration defines the highest temperature that the unoccupied space can be before an alarm is generated.
Unoccupied Space T emperature High Limit: Units F (C)
Range 0 to 255 F Default V alue 99
Occupied Humidity Low Limit
This configuration defines the lowest humidity that the occupied space c an be before an alarm is generated.
Occupied Humidity Low Limit: Units % humidity
Range 0 to 100% Default V alue 10
Occupied Humidity High Limit
This configuration de­fines the highest humidity that the occupied space can be be­fore an alarm is generated.
Occupied Humidity High Limit: Units % humidity
Range 0 to 100% Default V alue 99
Unoccupied Humidity Low Limit
This configuration de­fines the lowest humidity that the unoccupied space can be before an alarm is generated.
Unoccupied Humidity Low Limit: Units % humidity
Range 0 to 100% Default V alue 0
Unoccupied Humidity High Limit
This configuration de­fines the highest humidity that the unoccupied space can be before an alarm is genenerated.
Unoccupied Humidity High Limit: Units % humidity
Range 0 to 100% Default Value 100
Indoor Air Quality Low Limit
This configuration defines the lowest CO2 level that the occupied space can have before an alarm is generated.
Indoor Air Quality Low Limit: Units PPM (implied)
Range 0 to 5000 Default Value 250
Indoor Air Quality High Limit the highest CO
level that the occupied space can have before
2
This configuration defines
an alarm is generated. Indoor Air Quality
High Limit: Units PPM
Range 0 to 5000 PPM Default Value 1200
High Velocity Pressure
This configuration defines the maximum velocity pressure the zone controller should see at the pickup mounted in the inlet of the terminal. This is also used by the zone controller to calculate the maximum CFM the terminal will b e able to c ontrol to using the t erminal inlet siz e configured in the service configuration table.
High Velocity Pressure: Units in. wg
Range 0.0 to 2.0 in. wg Default V alue 1.2
CONTROLLER IDENTIFICATION SCREEN The con­troller identification screen displays the device information for the zone controller.
HOLIDAY CONFIGURATION SCREENS The zone controller has configuration screens for up to 12 different holi­day schedules. Highlight the holiday name on the screen and press enter to configure the holiday schedule. A separate screen is used to ENTER the Holiday schedule.
Start Month
The start month is the month in which the hol­iday starts. Months are represented by numbers with 1 repre­senting January, 2 February, up to 12.
Start Month: Range 1 to 12
Default V alue 1
Start Day
The start day is the day on which the holiday will
start. Start Day: Range 1 to 31
Default V alue 1
Duration
Length of time, in days, that the holiday will last.
Duration: Range 0 to 365
Default V alue 0
33
801
Page 34
LINKAGE COORDINATOR CONFIGURATION SCREEN The Linkage Coordinator Configuration screen allows the user to set the linkage coordinator configuration set­tings. See Tabl e 6.
Linkage Master Zone
This decision defines if the zone controller will function as a Linkage Coordinator (Linkage Master) for itself and other zones.
If the zone controller is to use a supply air sensor for stand­alone operation, this configuration must be configured to No and the number of Zones to 1.
If the zone controller will use its primary air sensor to deter­mine the air handler mode for a number of zone controllers, configure this configuration to Yes, input the number of zones, and leave the air source decisions at the default values of zero.
If this zone controller will communicate linkage informa­tion with an air source, configure this configuration to Y es. The number of zones must be configured and the address of the air source entered.
Linkage Master Zone: Range Yes/No
Default V alue No
Number of Zones
This decision defines the number of zone controllers (including itself) for the Linkage Coordinator to scan and include as part of the average temperature, set point s, and occupancy information to the air source. The address of the zone controller functioning as a Linkage Coordinator must be larger than the number of zones configured. The z one control­ler will scan addresses less than its own, including information for as many zones as are configured. Other zone controller con­figured as linkage coordinators will also be included, so it is possible to have zones scanned by more than one linkage coor­dinator. Therefore care must be taken in addressing to prevent overlapping systems, unless overlapping systems is necessary. In large buildings the use of bridges and multiple busses is rec­ommended to improve communication and provide system differentiation.
Number of Zones: Range 1 to 128
Default V alue 1
Air Source Bus and Element Number
The Air Source Bus and Element Number configurations define the address of t he air source providing conditioned air to the zones c ontrolled by the linkage coordinator. If the address is left at zero, the Link­age coordinator will look for a primary air sensor to determine the equipment mode. If no primary air sensor is installed, or the sensor fails, the Linkage Coordinator will default the air source mode to Cooling.
Air Source Bus Number: Range 0 to 240
Default V alue 0
Air Source Element Number: 0 to 240
Default V alue 0
Static Pressure Reset
Air systems designed with diversity (airflow required with all zones at maxi mum cfm exceeds de­sign capacity of air handler) are capable of providing enough CFM to all zones on days when conditions meet the demand at design static. At other times, the air system does not require the design static to meet the load requirements.
Static pressure reset allows the static pressure set point on the air source to be reset w henever t he system l oad is reduc ed from the design maximum. The zone controller will then moni­tor damper positions. When the system dampers are modulat­ing at lower damper positions due to the higher static, the static pressure will the n b e re se t to a lower value a llowing the damp ­ers to open more. This allows the system to automati cally make adjustments to the static pressure and optimize performance of the fan which will reduce energy consumption.
The linkage coordinator monitors the position of all damp­ers in its system. When any zone’s maximum damper position reaches the Reset Maximum Damper Position, the linkage co­ordinator will reduce the value of the reset variable.
The Maximum Damper Position and Static Pressure Reset values can be viewed on the Linkage maintenance screen.
NOTE: The static pressure set point configured in the air source should be the desired maximum (zero reset) static pressure.
DESCRIPTION DEFAULT POINT NAME Zone Linkage Linkage Master Zone Number of Zones Air Source Bus Number Air Source Element Number Static Pressure Reset Reset Minimum Damper Position Reset Maximum Damper Position Maximum Reset SP Reset Variable Name CCN Linkage Data CCN Variable Name CCN Function Configuration Data Transfer Rate CCN Output Point Destination Bus Number Destination Element Number Temperature Sensor Grouping Temperature Sensor Mode Temperature Sensor Configuration Broadcast Device ID
Table 6 Linkage Coordinator Configuration Screen
No MZENA
1 NSYSTZ 0 ASBUSN 0 ASELEMN
50 % MINDP 80 % MAXDP
0.0 in. wg SPMAX (blank) SPRVAR
(blank) CCNVAR
3 CCNFUNC
1 0 m i nu te s DATA R ATE
(blank) CCNOUTP
0DESTBUSN 0DESTELEN
1 BRD_RECV 1SENSCFG 1 BRDDEVID
801
34
Page 35
Reset Minimum Damper Position: Units %
Reset Maximum Damper Position: Units %
Maximum Reset: Units in. wg
Static Pressure Reset Variable Name: Units ASCII (8 characters)
*To use Static Pressure Reset with a Comfort System AirManager, configure the variable name to SPRESET .
Currently, to make use of the static reset information, a cus­tom program must be written in a Comfort Controller to read the reset value and change the set point of the static pressure control in the air source. Use this configuration to create a vari­able name (Static Pressure Reset Value). See the application manual for information about creating this custom program.
The Comfort System AirManager control has an internal SPRESET variable which functions to accept the stat ic pres­sure reset value from the linkage coordinator (refer to the Air Manager manual for configuration setup).
CCN Linkage Data Linkage master has the ability to poll its slaves and collect the high, low or average value of any variable within its slaves. Once the high, low or average is det ermined, the master can then transfer that value to a configured bus number, element number and point name. Typically this feature is used to deter­mine a system’s highest indoor air quality reading.
In order to utilize this feature the CCN V ariable Name being collected from the slaves must be supplied. The data transfer rate must be specified and whether the high, low, or average value is being determined. After the value has been deter­mined, a valid point name and CCN address to transfer the value to must be entered.
CCN Variable Name: Units ASCII (8 Characters)
CCN Function Config: Units none
Data Transfer Rate: Units minutes
CCN Output Point: Units ASCII (8 Characters)
Destination Bus Number: Units none
Destination Element Number: Units none
Range 0 to 99 Default V alue 50
Range 0 to 99 Default V alue 80
Range 0.0 to 5.0 Default V alue 0.0
Range A-Z,0-9 Default V alue *
A zone controller configured as a
Range A-Z, 0-9 Default Value (blank)
Range 0 = none, 1 = average,
2 = low, 3 = high
Default V alue 3
Range 1-15 Default V alue 10
Range A-Z, 0-9 Default Value (blank)
Range 0-239 Default V alue 0
Range 0-239 (0 = disabled) Default V alue 0
Temp Sensor Grouping the capability to broadcast the associated space temperature sensors data or listen to another controllers sensor data over the network. All controllers sharing the same sensor must be installed on the same CCN bus.
There are three configuration decisions that must be config­ured in order to share sensors. The Temp Sensor Mode is used to specify if a controller will use its own local sensor, broadcast its local sensor, or listed to another controller’s sensor broad- cast. The Temp Sensor Config is used to specify if the control­ler is sharging the space temperature information only or the space temperature and temperature offset slidebar information. The Broadcast Device ID decision is used to specify which controller number a zone will listen for when configured to receive another controllers broadcast.
Temp Sensor Mode: Units none
Temp Sensor Config: Units none
Broadcast Device ID: Units None
OCCUPANCY CONFIGURATION SCREEN The Oc­cupancy Configuration screen is used to set the occupied schedule. See Table 7.
Manual Override Hours sion is used to command a timed override by entering the num­ber of hours the override will be in effect.
If the occupancy schedule is occupied when this number is downloaded, the current occupancy period will be extended by the number of hours downloaded.
If the current occupancy period is unoccupied when the oc­cupancy override is initiated, the mode will change to occupied for the duration of the number of hours downloaded.
If the occupancy override will end after the start of the next occupancy period, the mode will transition from occupancy override to occupied without becoming unoccupied, and the occupancy override timer will be reset.
An active occupancy override or a pending occupancy over­ride may be canceled by downloading a zero to this configura­tion. Once a number other than zero has been downloaded to this configuration any subsequent downloads of any value oth­er than zero will be ignored by the zone controller.
Manual Override Hours: Units hours
Occupancy Scheduling occupancy programming is broken into eight separate pe riods. For each period the scheduling, the active days of the week, occupied start time, and occupied stop time needs to be configured.
Day of W eek corresponding to the seven days of the week and a holiday field in the following order: Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday, Holiday. A separate con­figuration screen is used.
This configuration consists of eight fields
Each ComfortID controller has
Range 1 = Local Sensor,
2 = Broadcast, 3 = Listen
Default V alue 1
Range 1 = SPT, 2 = SPT and
offset
Default V alue 1
Range 1-239 Default V alue 1
The Manual Override Hours deci-
Range 0 to 4 Default V alue 0
For flexibility of scheduling, the
35
801
Page 36
DESCRIPTION DEFAULT POINT NAME Manual Override Hours Period 1: Day of Week Period 1: Occupied From Period 1: Occupied To Period 2: Day of Week Period 2: Occupied From Period 2: Occupied To Period 3: Day of Week Period 3: Occupied From Period 3: Occupied To Period 4: Day of Week Period 4: Occupied From Period 4: Occupied To Period 5: Day of Week Period 5: Occupied From Period 5: Occupied To Period 6: Day of Week Period 6: Occupied From Period 6: Occupied To Period 7: Day of Week Period 7: Occupied From Period 7: Occupied To Period 8: Day of Week Period 8: Occupied From Period 8: Occupied To
Table 7 Occupancy Schedule Information Screen
0OVRD
11111111 DOW1
00:00 OCC1 24:00 UNOCC1
00000000 DOW2
00:00 OCC2 24:00 UNOCC2
00000000 DOW3
00:00 OCC3 24:00 UNOCC3
00000000 DOW4
00:00 OCC4 24:00 UNOCC4
00000000 DOW5
00:00 OCC5 24:00 UNOCC5
00000000 DOW6
00:00 OCC6 24:00 UNOCC6
00000000 DOW7
00:00 OCC7 24:00 UNOCC7
00000000 DOW8
00:00 OCC8 24:00 UNOCC8
If a 1 is configured in the corresponding place for a certain day of the week, the related Occupied from and “Occupied to times for that period will take effect on that day of the week. If a 1 is placed in the holiday field the related times will take effect on a day configured as a holiday. A zero means the schedule period will not apply to that day.
Period (1-8): Day of W eek: Range 0 or 1
Default Values 11111111 for period 1, 00000000 for periods 2-8.
Occupied From
This field is used to configure the hour and minute, in military time, when the mode for the zone controller becomes occupied.
Period (1-8): Occupied from: Units Hours: Minutes
Range 00:00 to 24:00 Default Value 00:00
Occupied To
This field is used to configure the hour and minute, in military time, when the occupied mode for th e zone controller becomes unoccupied.
Period (1-8): Occupied from: Units Hours: Minutes
Range 00:00 to 24:00 Default Value 24:00
SET POINT SCREEN The Set Point screen is used to modify the zone controller set points. See Table 8.
Occupied Heat
The Occupied Heat set point is used to con­figure the heating set point for the zone controller during Occu­pied mode.
Occupied Heat: Units F (C)
Range 40.0 to 90.0 Default Value 70.0
Occupied Cool
The Occupied Cool set point is used to con­figure the cooling set point for the zone controller during Occu­pied mode.
Occupied Cool: Units F (C)
Range 45.0 to 99.9 Default Value 74.0
Unoccupied Heat
The Unoccupied Heat set point is used to configure the heating set point for the zone controller during Unoccupied mode.
Unoccupied Heat: Units F (C)
Range 40.0 to 90.0 Default Value 55.0
Unoccupied Cool
The Unoccupied Cool set point is used to configure the cooling set point for the zone controller during Unoccupied mode.
Unoccupied Cool: Units F (C)
Range 45.0 to 99.9 Default Value 90.0
Occupied High Humidity
The Occupied High Humidity set point is used to configure the humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.
Occupied High Humidity: Units % Humidity
Range 0.0 to 100.0 Default Value 60.0
Unoccupied High Humidity
The unoccupied high humidi­ty set point is used to configure the unoccupied humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.
Unoccupied High Humidity: Units % humidity
Range 0 to 100 Default Value 100
1001
36
Page 37
Air Quality
The Air Quality set point is used to configure the IAQ set point for the zone controller if optional controlled ventilation support is used.
Air Quality Units none shown (ppm (ppm): implied)
Range 0 to 5000 Default Value 850
Delta Airflow
The Delta Airf low set point is used to con­figure the Delta Airflow set point for the zone controller if the zone pressure control option is used. If a negative pressure is desired, configure the value as a positive delta.
Delta Airflow: Units cfm
Range -9999 to 9999 Default V alue 0
Service Configuration Selection Screen
The Service Configuration Selection screen is a menu of Service screens which can be accessed by the user. The following screens are available: Airflow Service Configuration, T erminal Service Configuration, Option Service Configuration, and Sec­ondary Damper Service Configuration.
AIRFLOW SERVICE CONFIGURATION SCREEN The Airflow Service Configuration Table is used to configure the pressure independent and backup pressure dependent set points. See Tabl e 9.
Pressure Independent
Pressure Independent (PI) set points should be configured for pressure independent operation applications.
Cool Minimum (PI)
This configuration is the minimum airflow the ter minal will control t o when the equipme nt is in Cooling mode (or Fan Only mode) or free cooling. The space requirements for cooling must be at a minimum, or the terminal is a fan powered terminal and the s pace requirements are for heat.
Cool Minimum: Units CFM
Range 0 to 9999 (Limited by the High V elocity pressure limit alarm) Default V alue 0
Cool Maxi mum (PI)
This configuration is the maximum airflow the ter minal will control t o when the equipme nt is in Cooling mode (or Fan Only mode) or free cooling and the space requirements for cooling are at a maximum.
Cool Maximum: Units CFM
Range 0 to 9999 (Limited by the High V elocity pressure limit alarm) Default Value 4000
Terminal Reheat (PI)
This configuration is for single duct units with ducted reheat. The desired airflow is configured at which the reheat will provide optimum performance. This val­ue is compared to the Minimum Cool value and the greater of the two values is used to determine the airflow set point.
T erminal Reheat: Units CFM
Range 0 to 9999 (Limited by the High V elocity pressure limit alarm) Default V alue 0
DESCRIPTION DEFAULT POINT NAME Set Points Occupied Heat Occupied Cool Unoccupied Heat Unoccupied Cool Occupied HIgh Humidity Unoccupied High Humidity Air Quality (ppm) Delta Airflow
DESCRIPTION DEFAULT POINT NAME Pressure Independent Cool Minimum Cool Maximum Terminal Reheat Heat Minimum Heat Maximum Parallel Fan On Dual Duct CV Airflow Pressure Dependent Cool Minimum Position Cool Maximum Position Reheat Minimum Position Heat Minimum Positon Heat Maximum Position Deadband Percent
Table 8 Set Point Screen
70.0 F OHSP
74.0 F OCSP
55.0 F UHSP
90.0 F UCSP
60.0 % ORHH 100 % URHH
850 ppm AQSP
0 cfm DCFM
Table 9 Airflow Service Configuration Screen
0 cfm COOLMIN
4000 cfm COOLMAX
0 cfm REHEAT 0 cfm HEATMIN
4000 cfm HEATMAX
0 cfm FNONCFM
4000 cfm DDCVFLOW
0 % CMINPOS
100 % CMAXPOS
0 % REMINPOS 0 % HMINPOS
100 % HMAXPOS
12.5 % DB_PCT
37
1001
Page 38
Heat Minimum (PI) airflow the terminal will control to when the equipment mode is Warm-Up or Heat. If the terminal is not configured for VAV central heating this is the only airflow the terminal will control to for these equipment modes.
Heat Minimum: Units CFM
Heat Maximum (PI) ure the maximum airflow at which the zone controller will op­erate if VAV central heat i s conf igured t o yes. If the equipment mode is heat or warm-up, and the demand in the space is for heat, the zone controller will calculate the proper airflow need­ed to achieve space temperature set point (operating between the Heat Min and Heat Max).
Heat Maximum: Units CFM
Parallel Fan On (PI) the primary airflow setting below which a parallel fan terminal should energize its fan. The setting should be used to allow a low volume of primary airflow to be better diffused into the space.
Parallel Fan On: Units CFM
Dual Duct CV Airflow (PI) Dual Duct, constant volume, total airflow set point.
Dual Duct Airflow: Units CFM
Pressure Dependent should be configured for backup pressure dependent operation, if an operating problem with the pressure transducer occurs.
IMPORTANT: Pressure dependent settings are included for use only in the event of a pressure trans­ducer failure. The inclusion of these configuration set­tings does not indicate that Carrier is endorsing this product for pressure dependent operation. In the case of a pressure sensor failure, the zone controller will broadcast a pressure sensor failure message on the CCN bus. These configurations may be used by a ser­vice technician to put the terminal in pr essure depen­dent mode until the zone controller can be replaced.
Cool Minimum Position (PD) minimum damper position the terminal will control to when the equipment mode is Cooling (or Fan Only), or fr ee cooling and the space requirements for cooling are at a minimum.
Cool Minimum Position: Units %
Cool Maximum Position (PD) maximum damper position the terminal will control to when the equipment mode is cooling (or fan only), or free cooling and the space requirements for cooling are at a maximum.
Cool Maximum Position: Units %
This configuration is the minimum
Range 0 to 9999 (Limited by the High V elocity pressure limit alarm) Default V alue 0
This configuration is used to config-
Range 0 to 9999 (Limited by the High V elocity pressure limit alarm) Default Value 4000
This configuration is used to define
Range 0 to 9999 (Limited by the High V elocity pressure limit alarm) Default V alue 0
This configuration defines the
Range 0 to 9999 (Limited by the High V elocity pressure limit alarm) Default Value 4000
Pressure Dependent (PD) set points
This configuration is the
Range 0 to 100 Default V alue 0
This configuration is the
Range 0 to 100 Default Value 100
Reheat Minimum Position (PD) single duct units with ducted reheat. Configure the desired damper position at which the reheat will provide optimum per­formance. This value is com p ared to the Minimum Cool value and the greater of the two values is used to determine the damper position.
Reheat Minimum Position: Units %
Heat Minimum Position (PD) Minimum damper position the terminal will control to when the equipment mode is Warm-Up or Heat. If the terminal is not configured for VAV central heating this is the only position the terminal will control to for these equipment modes.
Heat Minimum Position: Units %
Heat Maximum Position (PD) to configure the maximum damper position at which the zone controller will operate if VAV central heat is configured to yes. If the equipment mode is Heat or Warm-Up and the demand in the space is for heat the zone controller will calculate the prop­er damper position needed to achieve space temperature set point, operating between the Heat Min and Heat Max.
Heat Maximum Position: Units %
Deadband Percent the Deadband Percent that the airflow will operate with.
Deadband Percent: Units %
TERMINAL SERVICE CONFIGURATION SCREEN The Terminal Service Configuration screen lists the main con­figuration settings for the air terminal controller. See Ta ble 10.
Ter minal Type terminal type that the zone controller is installed on. A 1 is for Single Duct te rminals, a 2 is for Parallel Fa n terminals, a 3 is for Series Fan terminals, and a 4 is for Dual Duct applications.
T erminal Type: Range 1 to 4
Primary Inlet Size used to input the inlet diameter of t he terminal if used with a round inlet. The Inlet Area configuration is used for oval or rectangular inlets. The zone controller will use the larger value for CFM calculations if both values are configured.
NOTE: Carrier sizes 12, 14, and 16 are oval. Primary Inlet Size
(Inlet Diameter): Units Inches
Inlet Area The Inlet Area configuration is used if the termi- nal has an oval or rectangular inlet. The Primary Inlet Size configuration is used for round inlets. The zone c ontroller will use the larger value for CFM calculations if both values are configured. Inlet Area: Units Square Inches
Range 0 to 100 Default V alue 0
Range 0 to 100 Default V alue 0
Range 0 to 100 Default Value 100
This configuration is used to configure
Range 0.0 to 100.0 Default Value 12.5
This configuration is used to indicate the
Default V alue 1
The Primary Inlet Size configuration is
Range 3.0 to 24.0 Default V alue 6.0
Range 0.0 to 500.0 Default V alue 0.0
This configuration is for
This configuration is the
This configuration is used
38
Page 39
COOLING Terminal Type Primary Inlet Size
Inlet Diameter Inlet Area
Probe Multiplier Calibration Gain Offset Damper
Proportional Gain Integral Gain Derivative Gain Starting Value
CW Rotation Pressure Independent HEATING Heat Type VAV Central Heating Heating
Proportional Gain Integral Gain Derivative Gain Starting Value
Ducted Heat Maximum Temperature Number of Electric Heat Stages Heat On Delay Fan Off Delay 2-Position Heat Logic SPT Trim SAT Trim Remote Contact Configuration
DESCRIPTION DEFAULT POINT NAME
Table 10 Terminal Service Configuration Screen
1 TERMTYPE
6.0 in.
0.0 in.
2.443 PMF
1.000 CAL_GAIN 0 cfm OFFSET
30.0
5.0
0.0
20 %
Close DMPDIR
Ye s P R E S I N D
0 HEATTYPE
Ye s C E N H E AT
8.0
3.0
0.0
80 F
Yes DUCTHEAT
110 F MAXTEMP
1STAGES 2HONDEL 2 FNOFFD
Normal HEATYPE
0.0 F SPTTRIM
0.0 F SATTRIM
Close RMTCFG
RNDSZ
SQA
KP
KI
KD
STARTVAL
KP
KI
KD
STARTVAL
Probe Mu ltipl i er This configuration is used to input a factor
for the velocit y pressure probe insta lled in the terminal inlet. Most inlet probes will have some aerodynamic characteristics that will affect the differential pressure output from the probe. The formula used by the ComfortID controller for calculat­ing the airflow (cfm) is based on measuring velocity with a Pitot tube probe. A PMF (Pitot measurement factor) is required in the calculation for different probes. Because various probe characteristics are different, the PMF is used to determine the correct airflow based on the type of probe installed. The PMF will compensate for the difference between Pitot-type probes and the actual probe installed.
The default PMF value of 2.273 is the correct va lue to use when the zone controller is used with a Carrier probe in a Carrier air terminal. For terminals and probes supplied by other manufacturers, the PMF must be calculated and entered into the zone controller configuration in order t o correct ly mea sure airflow.
T o determine the correct PMF value, there are several meth­ods depending on the data supplied by the terminal manufac­turer. The manufacturer may supply a K factor” or may sup- ply a chart of velocity pressure vs. airflow for the terminal. The K factor is the actual airflow velocity at a velocity pressure reading of 1 in. wg for the probe. This value is in ft/min and can be used to calculate the PMF. When the K factor is entered into the following equation, it is compared to the value of 4005, which is the K factor for a Pitot tube probe:
PMF = (4005/K F ACT OR)
2
If a chart is supplied by the manufacturer instead of the K factor, then the K factor can be calculat ed from the chart using the following formula:
K FA CTOR = (cfm at 1-in. wg)/(duct area ft
2
)
As an example, an air terminal with an 8-in. round inlet is used. The terminal manufacturer has provided an airflow chart
that gives an airflow value of 820 cfm at a velocity pressure reading of 1 in. wg. To determine the PMF for the terminal:
1. Determine duct area. radius of duct = diameter of duct/2 radius = 8-in./2-in. radius = 4-in. Area of circular duct = Πr Area = 3.14159 x 4 Area = 3.14159 x 16 Area = 50.26-in. Area must be in ft
2
2
50.26-in.2/(144-ft2) = 0.34906 ft
2
2
2
2. Determine K factor. K factor = (820 cfm/0.34906 ft2) K factor = 2349 fpm
3. Determine PMF. PMF = (4005 fpm/2349 fpm)
2
PMF = 2.907
Another way to determine the probe constant for a probe without documentation is to measure the velocity pressure with a Magnahelic gage. Open the damper and adjust the static pres­sure or open the damper until you have one inch of velocity pressure on the Magnahelic gage. Measure the total CFM of air being delivered. The CFM just measured divided by the inlet area in square feet should equal the K factor for the formula. Now use the K factor that was empirically derived to determine the probe multiplier.
Probe Multiplier: Range 0.250 to 9.999
Default Value 2.443
Calibration Gain
Air terminal testing by industry standards is done with straight duct, upstream of the terminal. Since some applications do not get installed in this manner, the actual air­flow from the terminal at balancing may not equal the reading from the zone controller.
39
303
Page 40
The calibration gain is used for the fine tuning adjustments which might need to be made to the air flow calculation. This number is calculated automatically by the zone controller after input to the air balance maintenance screen, or it can be input manually at this screen. For ease of use it is recommended to use the Air Balan ce Ma inten ance s cree n to de termin e thi s num­ber. The Air Balancing Maintenance screen will cause the val­ue to be updated during the balancing procedure.
If the Calibration Gain must be configured manually, it is determined as a percentage up or down that the CFM indicated will be offset. A number of .95 will cause the maximum air­flow calculated to be reduced to 95% of the value. A Calibra­tion Gain of 1.00 will cause no change. A number of 1.05 would cause readings to become 5% higher.
The Calibration Gain is adjusted on the Air Balance Mainte­nance screen when performing the Maximum Airflow calibra ­tion and will have the greatest effect on the airflow at maxi­mum CFM. Any error in reading at minimum airflow is adjust­ed by calculating the Offset configuration value. After performing the air balance using the Air Balance Maintenance screen it is a good idea to upload and save the Calibration Gain and Offset values.
Calibration Gain: Range 0.000 to 9.999
Offset
The Offset configuration is included for precision applications where the minimum airflow is critical and not ze­ro. This configuration indicates the amount of CFM the trans­ducer is off by, at minimum airflow, during the minimum air­flow test on the air balance screen. This configuration should not be used to zero the airflow transducer since an aut o zero test is included on the air balance screen and is also automati­cally performed each time the equipment fan is disabled (or every 72 hours for systems which run the fan continuously). After performing the air balance testing using the Air Balance Maintenance screen it is a good idea to upload a nd save the Calibration gain and Offset values. The cfm will be offset by the value entered in th e Minimum Cfm va riable and will zero at the value enter ed i n the Ma xim um C fm var iab le. Th ere wi ll be a linear relationship between the two set points.
Offset: Units cfm
Damper Loop Parameters define how the terminal will respond to deviations in measured CFM in order to control to the airflow set point.
The Proportional Gain is calculated each time the airflow is compared to the active airflow set point . As the error from set point goes to zero, the proportional term will also go to zero.
The Integral Gain is a running summation of all integral terms since the loop started. This has the effect of trimming off any offset from the set point which might occur, if only the pro­portional term existed. Normally a proportional loop with no integral term would require frequent adjustments of the starting value to eliminate the offset as static pressure and other condi­tions change.
The Derivative Gain is not needed. The Derivative Gain would tend to nullify large changes in the Proportional Gain for dampened response. These large changes in the Proportional Gain do not tend to happen for this type of control.
Damper Loop Parameters Proportional Gain:Range 00.0 to 99.9
Integral Gain: Range 00.0 to 99.0
Derivative Gain: Range 00.0
Default Value 1.000
Range -250 to 250 Default V alue 0
The loop gains and start value
Default Value 30.0
Default V alue 5.0
Default V alue 0.0
Start Value: Units %
Range 0 to 100 Default V alue 20
Clockwise Rotation what effect a clockwise rotation of the actuator will have on the damper. If the actuator rotates clockwise to closed position, the configuration should be set to Close. If the actuator rotates clockwise to open, the configuration should be set to open. This configuration is used to change the rotation of the actuator so that the damper transducer calibration will w ork properly. The actuator does not have to be re-installed nor any switches changed to reverse the action.
Clockwise Rotation: Range Close/Open
Pressure Independent minal will function in the pressure independent or pressure de­pendent mode.
NOTE: Pressure dependent mode should only be used in an emergency, if the pressure sensor is not functioning.
Pressure Independent: Range No/Yes
Heat Type heat installed on the terminal. A 0 is equal to None. A 1 is equal to Modulating/VAV. A 2 is equ al to Two Positio n. A 3 is equal to staged Electric. A 4 is equal to Modulating/CV.
Heat Type: Range 0 to 4
VAV Central Heatin g tion is used if the air source has the ability to provide heat and the terminal is required to modulate, using the heat minimum and heat maximum airflows, when the air source is in the heat mode. If this variable is set to No, the terminal will use its available local heat to heat the zone at all times.
VAV Cen tra l Heating: Range No/Y es
Heating Loop Parameters value define how the terminal will respond to deviations in measured space temperature in order to control to the heat set point.
temperature is compared to the heat set point. As the error from set point goes to zero, the Proportional Gain will also go to zero.
terms since the loop started. This has the affect of trimming off any offset from set point which might occur if only the Propor­tional Gain existed. Normally a proportional loop with no Inte­gral Gain would require frequent adjustments of the starting value to eliminate the offset as loading conditions on the room change.
fy large changes in the Proportional Gain for dampened response.
Heating Loop Parameters Proportional Gain: Range 00.0 to 99.9
Integral Gain: Range 00.0 to 99.0
Derivative Gain: Range 00.0
This configuration is used to define the type of
The Proportional Gain is calculated each time the space
The Integral Gain is a running summation of all integral
The Derivative Gain is not needed. This term tends to nulli-
This configuration is used to define
Default V alue Close
This configuration defines if the ter-
Default V alue Yes
Default V alue 0
The VAV Central Heating configura-
Default V alue Yes
The heating loop gains and start
Default V alue 8.0
Default V alue 3.0
Default V alue 0.0
801
40
Page 41
Start Value: Units F (C)
Range 40 to 125 Default V alue 80
Ducted Heat
The Ducted Heat configuration is used to con­figure the terminal for ducted heat. If a local heat sourc e is in the duct and requires airflow to provide heat, set the Ducted Heat configuration for yes.
Ducted Heat Range No/Yes
Default V alue Yes
Maximum Duct Temperature
This configuration is used to configure the maximum supply-air temperature desirable for heating the space. This will cause the heat to be modul ated or cycled using this value as the maximum t emperat ure of th e air to be supplied.
Maximum Duct T emperature: Units F (C)
Range 40 to 200 Default Value 110
Number of Electric Stages
This configuration is used to define the number of stages of electric hea t controlled by the zone controller.
Number of Electric Stages: Range 1 to 3
Default V alue 1
Heat On Delay
The Heat On Delay configuration is used to define a delay from the time a paral lel terminal fan is started until the heat is activated.
Heat On Delay: Units minutes
Range 1 to 60 Default V alue 2
Fan Off Delay
The Fan Off Delay configuration is used to define a delay time. The delay time is from when the heat is de­activated (in a parallel terminal) until the parall el fan is deac ti­vated. This allows the fan to circulate air and remove the resid­ual heat from the heat source.
Fan Off Delay: Units minutes
Range 1 to 15 Default V alue 2
Two-Position Heat Logic
This configuration is used for controlling a normally closed or normally open valve for hot water. Use normal logic if the valve is normally closed. Use in­verted logic if the valve is normally open.
T wo Position Heat Logic: Range Normal/Invert
Default Value Normal
Space Temperature Trim
This configuration is used to trim a space sensor which might need ca libration. For example, if the temperature displayed is two degrees above the value mea­sured with calibrated test equipment, input a value of –2.0.
Space Temperature Trim: Units delta F (delta C)
Range –9.9 to 9.9 Default V alue 0.0
Supply Air Temperature Trim
This configuration is used to trim a supply air sensor which might need calibration. For example, if the temperature displayed is two degrees above the value measured with calibrated test equipment, input a value of –2.0.
Supply Air T emperature Trim: Units delta F (delta C)
Range –9.9 to 9.9 Default V alue 0.0
Remote Contact Config
The remote timeclock contact in­put can be configured as a normally open or normally closed contact. When the timeclock input is ‘On’ the zone will follow it’s local occupancy schedule. When the timeclock input is Off the zone will be forced into unoccupied state.
Remote Contact Config: Range Close/Open
Default V alue Close
OPTIONS SERVICE CONFIGURATION SCREEN The Options Service Configuration screen is used to configure the service options of the air terminal controller. See T able 1 1.
Occupancy Schedule Number
The Occupancy Schedule Number defines what Occupancy schedule the zone controller will use. Occupancy Schedule 64 is a local schedule. Occupan­cy Schedules 65 to 99 are global schedules.
Occupancy Schedule Number: Range 64 to 99
Default V alue 64
Global Schedule Master
The Global Schedule Master con­figuration allows the Occupancy Schedule to be used as a Glo­bal Schedule Master (Occupancy Schedules 65-99).
Global Schedule Master: Range No/Yes
Default V alue No
Occupancy Schedule Number Global Schedule Master Override Broadcast Acknowledge Set Point Group Number Global Set Point Master Maximum Offset Adjust Control Options Humidity
Proportional Gain Integral Gain Maximum Output Value
Air Quality Proportional Gain Integral Gain Maximum Output Value
AQ Low Voltage AQ High Voltage AQ Low Reference AQ High Reference
DESCRIPTION DEFAULT POINT NAME
Table 11 Options Service Configuration Screen
64 SCH
No GSM
00:00 OVR
No BCACK
0SETT No GSTM 2 F LIMT
0CTLOPT
1.5
0.30
100.0 cfm
0.10
0.03
100.0 cfm
0.0 AQINLO
10.0 AQINHI
0 ppm AQLO
2000 ppm AQHI
41
KP
KI
MAXOUT
KP
KI
MAXOUT
801
Page 42
Override
The Override parameter is used to configure the number of hours and minutes the override will be in effect. The user initiates override by pressing the override button on the space temperature sensor. This will cause the schedule to enter into the Occupied mode. If global scheduling is used, all zones using the global schedule will enter Occupied mode. Pushing the override button during Occupied mode will have no effect.
If the occupancy override is due to end after the start of the next occupancy period, the mode will transition from occupan­cy override to occupied without becoming unoccupied, and the occupancy override timer will be reset.
NOTE: If using the tenant billing function, the override hours set point must be configured between 1 and 3 hours.
Override: Units Hours: Minutes
Range 00:00 to 24:00 Default Value 00:00
Broadcast Acknowledger
This configuration defines if the zone controller will be used to acknowledge broadcast messag­es on the CCN bus. One broadcast acknowledger is required per bus, including secondary busses created by the use of a bridge.
Broadcast Acknowledger: Range No/Yes
Default V alue No
Set Point Group Number
The Set Point Group Number is used to define the current zone controller as a part of a group of zone controllers which share the same set points. All zone con­trollers with the same Set Point Group Number will have the same set points. The set points are broadcast to the group by the zone controller defined by the Global Set Point Master config­uration. A value of 0 is a local schedule. V alues 1 to 16 are used for global scheduling.
Set Point Group Number: Range 0 to 16
Default V alue 0
Global Set Point Master
This configuration defines if the current zone controller will broadcast its set point values to the other zone controllers which are made part of the same group by configuring the Set Point Group Number.
Global Set Point Master: Range No/Yes
Default V alue No
Maximum Offset Adjustment
This configuration deter­mines the maximum amount that the set point will be biased (up or down), by adjusting the slide bar on the space tempera­ture sensor (if installed).
Maximum Offset Adjustment: Units delta F (delta C)
Range 0 to 15 Default V alue 2
Control Options
The Control Options configuration deter­mines whether the zone controller will use a humidity sensor or an indoor air quality sensor. A configuration of 0 means no sensors are used. A configuration of 1 means a Humidity Sen­sor is used. A configuration of 2 means an IAQ Sensor is used.
Control Options: Range 0 to 2
Default V alue 0
Humidity Control
These configuration values define the calculation parameters for determining the airflow needed to correct a high humidity problem in the space. The Maximum Output Value is measured in percentage of nominal terminal cfm.
Proportional Gain: Range 0.0 to 9.9
Default V alue 1.5
Integral Gain: Range 0.00 to 9.99
Default V alue 0.30
Maximum Output Value: Range 0.0 to 100.0% (max cool cfm)
Default Value 100.0
Indoor Air Quality Control
These configuration values de­fine the calculation parameters for determining the airflow needed to correct a high incidence of air pollution contami­nants in the space, such as CO
. The Maximum Output V alue is
2
measured in percentage of nominal terminal cfm. Proportional Gain:Range 0.00 to 9.99
Default V alue 0.10
Integral Gain: Range 0.00 to 9.99
Default V alue 0.03
Maximum Output Value: Range 0.0 to 100.0% (max cool
cfm)
Default Value 100.0
IAQ Sensor Low Voltage
This configuration defines the lowest voltage which should be read from the air quality sensor.
IAQ Sensor Low Voltage: Range 00.0 to 10.0
Default V alue 0.0
IAQ Sensor High Voltage
This configuration defines the highest voltage which should be read from the air quality sen­sor.
IAQ Sensor High Voltage: Range 00.0 to 10.0
Default Value 10.0
IAQ Low Reference
This configuration defines the value in parts per million which correlate to the low voltage reading from the air quality sensor.
IAQ Low Reference: Units ppm (parts per million)
Range 0 to 5000 Default V alue 0
IAQ High Reference
This confi guration defines the value in parts per million which correlate to the high voltage reading from the air quality sensor.
IAQ High Reference: Units ppm (parts per million)
Range 0 to 5000 Default Value 2000
SECONDARY DAMPER SERVICE CONFIGURATION SCREEN The Secondary Damper Service Configuration screen is used to configure the secondary damper settings. See Table 12.
Zone Pressure Control
The Zone Pressure Control config­uration determines whether the primary and secondary control­lers will be configured for zone pressure control.
Zone Pressure Control: Range Dsable/Enable
Default V alue Dsable
Dual Duct Type
The Dual Duct Type setting configures the secondary controller for the correct dual duct type. A value of 0 configures the type to None. A value of 1 configures the type to Second Inlet (Hot Deck). A value of 2 configures the duct to T otal Probe (terminal outlet).
Dual Duct Type: Range 0 to 2
Default V alue 0
800
42
Page 43
Zone Pressure Control Dual Duct Type Secondary Duct Size
Inlet Diameter Inlet Area
Probe Multiplier Calibration Gain Offset CW Rotation
DESCRIPTION DEFAULT POINT NAME
Tab l e 1 2 Secondary Damper Service Configuration Screen
Dsable ZPCNTL
0 DDTYPE
6.0 in.
0.0 sq. in.
2.443 SPMF
1.000 CAL_GAIN 0 cfm SOFFSET Close DMPDIR
SRNDSZ
SSQA
Secondary Duct Size
The Secondary Duct Size setting is used to input the inlet diameter of the terminal, if used with a round inlet. The Inlet Area configuration is used for oval or rectangular inlets. The zone controller will use the larger value for CFM calculations if both values are configured.
Secondary Duct Size (Inlet Diameter): Units Inches
Range 3.0 to 24.0 Default V alue 6.0
Inlet Area The Inlet Area configuration is used if the termi- nal has an oval or rectangular inlet. The Primary Inlet Size configuration is used for round inlets. The zone c ontroller will use the larger value for CFM calculations if both values are configured. Inlet Area: Units Square Inches
Range 0.0 to 500.0 Default V alue 0.0
Probe Multiplier
This configuration is used to input a fac­tor for the velocity pressure probe characteristics installed in the inlet. All averaging probes will have some aerodynamic characteristics which will ampli fy the pressure difference read at the inlet of the terminal. The de fault of 2.443 is the correct value to use if the probe is a Carrier probe in a 35 or 45 Series terminal.
The formula for calculating velocity using an Ideal probe is: Velocity = 4005* SQRT (Velocity Pressure)
Most manufactures will provide a probe constant for the probe supplied. For example, Velocity = 2213*SQRT(Velocity Pressure). To calculate the number to input in this decision (Probe Multiplier) use the formula. (4005/2213)
2
= 3.3. So you would use 3.3 in place of 2.443 for a probe with a probe con­stant of 2213.
An easy way to determine the probe constant for a probe without documentation is to measure the velocity pressure with a Magnahelic gage. Open the damper and adjust the static pres­sure until you have one inch of velocity pressure on the Magna­helic gage. Measure the total CFM of air being produced. The CFM just measured divided by the inlet area in feet should equal the probe constant for the formula. Velocity = (CFM just measured/inlet area) * SQRT (1.0). Now use the constant that was empirically derived to determine the probe multiplier (4005/(CFM at 1.0 Inch/Inlet area))
2
= Probe Multip lie r.
Probe Multiplier: Range 0.250 to 9.999
Default Value 2.443
Calibration Gain
Air terminal testing by industry standards is done with straight duct, upstream of the terminal. Since most applications do not get installed in this manner, the actual air­flow from the terminal at balancing may not equal the readin g from the zone controller.
The calibration gain is used for the fine tuning adjustments
which might need to be made to the airflow calculation.
If the Calibration Gain must be configured manually. It is
determined as a percentage up or down that the CFM indicated
will be offset. A number of .95 will cause the maximum air­flow calculated to be reduced to 95% of the value. A Calibra­tion Gain of 1.00 will cause no change. A number of 1.05 would cause readings to become 5% higher.
Any error in reading at minimum airflow is adjusted by cal-
culating the Offset configuration value. Calibration Gain: Range 0.000 to 9.999
Default Value 1.000
Offset
The Offset configuration is included for precision applications where the minimum airflow is critical and not zero. The cfm will be offset by the value entered in the Mini­mum Cfm variable and will zero at the value ent ered in the Maximum Cfm variable. There will be a linear relationship be­tween the two set points.
Offset: Units cfm
Range –250 to 250 Default V alue 0
Clockwise Rotation
This configuration is used to define what effect a clockwise rotation of the actuator will have on the damper. If the actuator rotates clockwise to closed position, the configuration should be set to Close. If the actuator rotates clockwise to open, the configuration should be set to open. This configuration is used to change the rotation of the actuator so that the damper transducer calibration will w ork properly. The actuator does not have to be reinstalled nor any switches changed to reverse the action.
Clockwise Rotation: Range Close/Open
Default V alue Close
Maintenance Table Menu Screen
The Mainte­nance Table Menu screen allows the user to select one of 4 available maintenance tables: the Linkage Maintenance Table, the Occupancy Maintenance Table, the Zone Air Balance T able, and the Zone Maintenance Table.
LINKAGE MAINTENANCE TABLE The Linkage Maintenance table is used to view the zone linkage variables. See Tabl e 13.
Air Source Bus Number
This variable will display the bus number of the air source that the zone controller will be com­municating Linkage to, if this zone is the Linkage Master .
Air Source Bus Number: Range 0 to 239
Default V alue 0 Network Access None
Air Source Element Number
This var i a b le w il l d i sp l ay the Element Address of the Air Source that the zone controller will be communicating Linkage to, if this zone is the Linkage Master.
Air Source Element Number: Display Range 1 to 239
Default V alue 0 Network Access None
43
501
Page 44
Master Zone Element Number the element address of the zone which is the Linkage Master.
Master Zone Element Number: Display Range 1 to 239
Default V alue 0 Network Access Read only
Operating Mode erating mode of the air source, if Linkage is available, or the mode determined by the Linkage Master using the primary ai r sensor, if available. If the primary air sensor has failed or was not installed, the Linkage master will assume the default mode of cooling.
Operating Mode: Display Range COOLING, HEATING,
Air Source Supply Temperature supply temperature reading of the air source.
Air Source Supply T emperature: Units F (C)
Start Bias Time in minutes, calculated by the air source. The Start Bias Time is calculated to bring the temperature up or down to the set point under the optimum start routine. This value will be sent to all associated zones for optimum start of zone controllers. This function is supported by all Carrier equipment which perform linkage.
Start Bias Time: Display Units minutes
Average Occupied Heat Set Point the weighted average of the occupied heat set point, calculated by the linkage coordinator, from the information received from polling its associated zones. The set points are weighted by the maximum airflow capacities of the zone controllers scanned by the linkage coordinator.
A verage Occupied Heat Set Point: Display Units F (C)
Average Occupied Cool Set Point the weighted average of the occupied cool set point, calculated by the linkage coordinator, from the information received from polling its associated zones. The set points are weighted by the maximum airflow capacities of the zone controllers scanned by the linkage coordinator.
A verage Occupied Cool Set Point: Display Units F (C)
Average Unoccupied Heat Set Point the weighted average of the unoccupied heat set point, calculat­ed by the linkage coordinator, from the information received from polling its associated zones. The set points are weighted by the maximum airflow capacities of the zone controllers scanned by the linkage coordinator .
A verage Unoccupied Heat Set Poin t: Display Units F (C)
This variable will display the c urrent op-
WARM-UP, FREECOOL, PRESSURE, EVAC, OFF Default V alue OFF Network Access Read only
Display Range -40 to 245 Default V alue 0 Network Access None
This variable displays the Start Bias Time,
Display range 0 to 185 Default V alue 0 Network Access None
Display Range 0.0 to 99.9 Default V alue 0.0 Network Access None
Display Range 0.0 to 99.9 Default V alue 0.0 Network Access None
Display Range 0.0 to 99.9 Default V alue 0.0 Network Access None
This vari able will display
This variable displays the
This variable displays
This variable displays
This variable displays
Average Unoccupied Cool Set Point plays the weighted average of the unoccupied cool set point, calculated by the linkage coordinator, from the information re­ceived from polling its associated zones. The set points are weighted by the maximum airflow capacities of the zone con­trollers scanned by the linkage coordinator.
A verage Occupied Cool Set Point: Display Units F (C)
Display Range 0.0 to 99.9 Default V alue 0.0 Network Access None
Average Zone Temperature weighted average of the space temperatures, collect ed by the linkage coordinator, from polling its associated zones. The temperatures are weighted by the maximum airflow capaciti es of the zone controllers scanned by the linkage coordinator.
A verage Zone T emperature: Display Units F (C)
Display Range 0.0 to 99.9 Default V alue 0.0 Network Access Read Only
Average Occupied Zone Temperature plays the weighted average of the space temp eratures of occu­pied zones, collected by the linkage coordinator, from polling its associated zones. The temperatures are weighted by the maximum airflow capacities of the zone controllers scanned by the linkage coordinator.
A verage Occupied Zone Temperature:D isplay Units F (C)
Composite CCN Value or average of the CCN variable collected from each zone as configured in the Linkage Coordinator Configuration Screen. The value is sent to th e CCN address and variable specified within that configuration table.
Composite CCN Value: Display Range 0-65535
Occupancy Status least one of the associated zone controllers (that are being scanned) is in the occupied mode.
Occupancy Status:Display Range 0 or 1 (1 = occupied)
Next Occupied Day the next associated zone is schedule d to change from unoc cu­pied to occupied mode. This point is read in conjunction with the next occupied time to allow the user to know the next time and day when a zone will become occupied.
Next Occupied Day: Display Range MON, TUE, WED,
Next Occupied Time when the next associated zone is scheduled to change from un­occupied to occupied mode. This point is read in conj unction with the next occupied day to allow t he user to know the next time and day when a zone will become occupied.
Next Occupied Time: Display Range 00:00 to 24:00
Display Range 0.0 to 99.9 Default V alue 0.0 Network Access Read Only
Default V alue 0 Network Access Read Only
This variable displays a 1 when at
Default V alue 0 Network Access Read only
This variable displays the day when
Default Value No display (Blank) Network Access None
Default V alue 0:00 Network Access None
This variable displays the
This vari able displays the hig h, low
This variable displays the time of day
This variable dis-
This variable dis-
THU, FRI, SAT , SUN
801
44
Page 45
DESCRIPTION DEFAULT POINT NAME Air Source Bus Number Air Source Element Number Master Zone Element Number Operating Mode Air Source Supply Temperature Start Bias Time Average Occupied Heat Set Point Average Occupied Cool Set Point Average Unoccupied Heat Set Point Average Unoccupied Cool Set Point Average Zone Temperature Average Occupied Zone Temperature Composite CCN Value Occupancy Status Next Occupied Day Next Occupied Time Next Unoccupied Day Next Unoccupied Time Previous Unoccupied Day Previous Unoccupied Time Maximum Damper Position Static Pressure Reset Pressure Decrease Value Pressure Increase Value
Table 13 Linkage Maintenance Screen
0 ASBUSNUM 0 ASDEVADR 0MZDEVADR
OFF ASOPMODE
0 F ASTEMP
0 minutes STRTBIAS
0.0 F AOHS
0.0 F AOCS
0.0 F AUHS
0.0 F AUCS
0.0 F AZT
0.0 F AOZT 0 CCCNVAL 0 OCCSTAT
(blank) NXTOCCD
00:00 NXTOCCT
(blank) NXTUNOD
00:00 NXTUNOT
(blank) PREVUNOD
00:00 PRVUNOT
0.0 % MAXDMPOS
0.0 in. wg PRESVAL
0.000 in. wg PRESDECR
0.000 in. wg PRESINCR
Next Unoccupied Day
This variable displays the day when the next associated zone is scheduled to change from occupied to unoccupied mode. This point is read in conjunction with the next unoccupied time to allow the user to know the next time and day when a zone will become unoccupied.
Next Unoccupied Day: Display Range MON, TUE, WED,
THU, FRI, SAT , SUN Default Value No display (Blank) Network Access None
Next Unoccupied Time
This variable displays the time of day when the next associated zone is scheduled to change from occupied to unoccupied mode. This point is read in conjunction with the next unoccupied day to allow the user to know the next time and day when a zone will become unoccupied.
Next Unoccupied Time: Display Range 00:00 to 24:00
Default Value 0:00 Network Access None
Previous Unoccupied Day
This variable displays the day when the last associated zone changed from occupied to unoc­cupied mode. This point is read in conjunction with the previ­ous unoccupied time to allow the user to know the last time and day when a zone became unoccupied.
Previous Unoccupied Day: Display Range MON, TUE, WED,
THU, FRI, SAT , SUN Default Value No display (Blank) Network Access None
Previous Unoccupied Time
This variable displays the time of day when the last associated zone changed from occupied to unoccupied mode. This point is read in conjunction with the previous unoccupied day to allow the user to know the last time and day when a zone became unoccupied.
Previous Unoccupied Time: Display Range 00:00 to 24:00
Default Value 0:00 Network Access None
Maximum Damper Position
This variable displays the damper position of the zone controller in the system with the damper in the most open position. This is used by the linkage coordinator to calculate the static pressure reset.
Maximum Damper Position: Display Units % (open)
Display Range 0.0 to 100.0 Default V alue 0.0 Network Access Read/Write
Static Pressure Reset
This variable displays the current static pressure reset calculated, using the maximum damper po­sition and the configuration information from the linkage con­figuration table.
Static Pressur e Reset: Display Units in. wg
Display Range 0.0 to 5.0 Default V alue 0.0 Network Access Read/Write
Pressure Decrease Value
If the maximum damper position in the system goes below the minimum configuration setting, the linkage coordinator will calculate an amount that the static pressure should be decreased. This is used to open the system dampers more so that they will modulate between their mini­mum and maximum settings.
This number is rounded to the nearest tenth of an inch and will be added to the static pressure reset value unless the static pressure reset value has reached maximum reset.
Pressure Decrease Value: Display Units in. wg
Display Range 0.000 to 5.000 Default Value 0.000 Network Access Read/Write
Pressure Increase Value
If the ma ximum damper position in the system goes above the maximum configuration setting, the linkage coordinator will calculate an amount that the static pressure should be increased. This is used to close the system dampers more so that they will modulate between their mini­mum and maximum settings.
45
801
Page 46
This number is rounded to the nearest tenth of an inch and will be subtracted to the static pressure reset value unless the static pressure reset value has reached zero.
Pressure Increase Value: Display Un its in. wg
Display Range 0.000 to 5.000 Default Value 0.000 Network Access Read/Write
OCCUPANCY MAINTENANC E TABLE The Occu­pancy Maintenance table is used to view the occupancy set points. See Tabl e 14.
Mode
This variable displays the current occupied mode for the zone controller. If the zone controller is following its own local schedu le, thi s is the r esult o f the lo cal sche dule st atus. If the zone controller is configured to follow a global schedule, this point displays the mode last received from a global sched­ule broadcast.
Mode: Display Range 0 or 1 (1 = occupied)
Default V alue 0 Network Access None
Current Occupied Period
If the zone controller is config­ured to determine occupancy locally, this variable will display the current period determining occupancy.
Current Occupied Period: Display Range 1 to 8
Default V alue 0 Network Access None
Override in Progress
If an occupancy override is in
progress, this variable will display a yes. Override In
Progress: Display Range Yes /No
Default V alue No Network Access None
Override Duration
This variable displays the number of minutes remaining for an occupancy override which is in effect. If the number of override hours was downloaded, the value will be converted to minutes.
Override Duration: Display Units minutes
Display Range 0 to 1440 Default V alue 0 Network Access None
Occupied Start Time
This variable displays the time that the current occupied mode began. If the current mode is unoc­cupied or the zone controller is following a global schedule, the value displayed by this point will be 0:00.
Occupied Start Time: Display Range 00:00 to 23:59
Default Value 0:00 Network Access None
Unoccupied Start Time
This variable displays the time that the current occupied mode will end (the beginning of the next unoccupied mode). If the current mode is unoccupied or the zone controller is following a global schedule, the va lue dis­played by this point will be 0:00.
Unoccupied Start Time: Display Range 00:00 to 24:00
Default V alue 0:00 Network Access None
Next Occupied Day
This variable displays the day when the next occupied period is scheduled to begin. This point is read in conjunction with the next occupied time to allow the user to know the next time and day when the next occupied pe­riod will occur. If the zone controller is following a global schedule this point will remain at default.
NOTE: If the current mode is occupied, this point makes refer­ence to the next occupied period and, in most cases, may not be the same as the current occupied start time.
Next Occupied Day: Display Range MON, TUE, WED,
THU, FRI, SAT , SUN Default Value No display (Blank) Network Access None
Next Occupied Time
This variable displays the time of day when the next occupied period will occur. This point is read in conjunction with the next occupied day to allow the user to know the next time and day when the zone will become occu­pied. If the zone controller is following a global schedule this point will remain at default.
NOTE: If the current mode is occupied, this point makes reference to the next occupied period and, in most cases, may not be the same as the current occupied start time. Next Occupied Time: Display Range 00:00 to 24:00
Default V alue 0:00 Network Access None
Next Unoccupied Day
This variable displays the day when the next unoccupied period is scheduled to begin. This point is read in conjunction with the next unoccupied time to allow the user to know the next time and day when the zone will become unoccupied. If the zone controller is following a global sched­ule this point will remain at default.
NOTE: If the current mode is unoccupied, this point makes reference to the next unoccupied period and, in most cases, may not be the same as the current unoccupied start time.
Next Unoccupied Day: Display Range MON, TUE, WED,
THU, FRI, SAT , SUN Default Value No display (Blank) Network Access None
DESCRIPTION DEFAULT POINT NAME Mode Current Occupied Period Override in Progress Override Duration Occupied Start Time Unoccupied Start Time Next Occupied Day Next Occupied Time Next Unoccupied Day Next Unoccupied Time Last Unoccupied Day Last Unoccupied Time
501
Table 1 4 Occupancy Maintenance Screen
0MODE 0PERIOD
No OVERLAST
0 OVERDURA 00:00 OCCSTART 00:00 UNSTART
(blank) NXTOCCD
00:00 NXTOCCT
(blank) NXTUNOD
00:00 NXTUNOT
(blank) PRVUNOD
00:00 PRVUNOT
46
Page 47
Next Unoccupied Time day when the next unoccupied period is scheduled to begin. This point is read in conjunction with the next unoccupied day to allow the user to know the next time and day when the zone will become unoccupied. If the zone controller is following a global schedule this point will remain at default.
NOTE: If the current mode is unoccupied, this point makes reference to the next unoccupied period and, in most cases, may not be the same as the current unoccupied start time.
Next Unoccupied Time: Display Range 00:00 to 24:00
Last Unoccupied Day when the zone changed from occupied t o unoccupied mode. This point is read in conjunction with the last unoccupied time to allow the user to know the last time and day when the zone became unoccupied. If the zone controller is following a global schedule this point will remain at default.
Last Unoccupied Day: Display Range MON, TUE, WED,
Last Unoccupied Time of day when the zone changed from occupied to unoccupied mode. This point is read in conjunction with the last unoccu­pied day to allow the user to know the last time and day when a zone became unoccupied. If the zone controller is following a global schedule this point will remain at default.
Last Unoccupied Time: Display Range 00:00 to 24:00
ZONE AIR BALANCE/COMMISSIONING TABLE The Zone Air Balance/Commissioning T abl e is used t o display the air balance variables. See Table 15.
Commissioning Mode controller into the commissioning mode. Force this point to en­able. The zone controller will be ready to accept a command to perform the tests and functions on this screen.
NOTE: Commissioning mode will automatically be dis­abled after one hour.
Commissioning Mode: Display Range Dsable/Enable
Damper Actuator/Transducer Calibration Actuator Transducer calibration is t he first calibration which should be performed on a newly installed actuator. The zone controller will command the actuator to close and read the feedback potentiometer to determine the zero position of t he damper. It will then command the damper to fully open. The zone controller will read the potentiometer to determine the maximum open position. Damper positions from closed to maximum open will be scaled to read 0 to 100% for the damp­er position.
The zone controller will then close the damper and open it once more to zero calibrate the airflow sensor. The entire calibration procedure can take up to 3 minutes. If the damper fails the test or the airflow calibration is unable to be com plet­ed, the Auto-Calibration point will indicate an Alarm.
Damper Actuator Transducer Calibration: Display Range Dsable/Enable
This variable displays the time of
Default Value 0:00 Network Access None
This variable displays the last day
THU, FRI, SAT , SUN Default Value No display (Blank) Network Access None
This variable displays the last time
Default Value 0:00 Network Access None
This variable is used to put the zone
Default Value Dsable Network Access Read /Write
The Damper
Default Value Dsable Network Access Read /Write
Maximum Cooling Airflow Calibration Maximum Cooling Airflow Calibration, the Maximum Cool­ing Airflow from the set point schedule will be made the Air­flow CFM Set Point. The zone controller will modulate the damper to control to this set point. The actual ai rflow, damper position, and velocity pressure readings will be displayed.
If the set point is not correct, it may be changed from this screen by forcing the airflow set point to the desired value. The value will be writ te n to th e se t p oin t sche d u le in th e Ma xim um Cool CFM set point, and the zone controller will begin to con­trol to the new value.
The airflow can be measured using test and balance equip­ment and compared to the actual reading on the screen. If the value measured requires adjustment to the value on t h e screen, force the value on the sc reen to the value measured. T he zone controller will take the value and calculate a new calibration gain which will be shown at the bottom of the screen. The new value will be a u toma ti cal ly load ed i nto t he Se rv ice Con fi gur a­tion table.
Maximum Cooling Airflow Calibration: Display Range Dsable/Enable
Minimum Cooling Airflow Calibration imum Cooling Airflow Calibration will cause the airflow CFM set point to change to the Minimum Cooling set point. The ac­tual airflow, damper position, and velocity pressure readings will be displayed.
If the set point is not correct, it may be changed from this screen by forcing the Airflow set point to the desired value. The value will be written to the set point schedule in the Mini­mum Cool CFM set point, and the zone controller will begin to control to the new value.
The airflow can be measured using test and balance equip­ment and compared to the actual reading on the screen. If the value measured requires adjustment to the value on t h e screen, force the value on the sc reen to the value measured. T he zone controller will take the value and calculate a new offset.
The Offset configuration is included for precision applica­tions where the minimum airflow is critical and not zero. The Offset configuration should not be used to zero the airflow transducer since an auto zero test is included in the normal function of the zone controller and is automatically performed each time the equipment fan is disabled (or every 72 hours for systems which run the fan continuously). After performing air balance testing using the Air Balance Maintenance screen, it is a good idea to upload and save the Airflow set points, Calibra­tion Gain, and Offset values.
Minimum Cooling Airflow Calibration: Display Range Dsable/Enable
Fan Override ries and parallel fan powered terminals. Enabling this point will cause the terminal fan to run until this point is disabled or the commissioning mode is ended.
Fan Override: Display Range Dsable/Enable
Default Value Dsable Network Access Read /Write
Default Value Dsable Network Access Read /Write
This variable can be used to test the fan on se-
Default Value Dsable Network Access Read /Write
By enabling the
Enabling the Min-
47
501
Page 48
Commissioning Mode
DESCRIPTION DEFAULT POINT NAME
Damper/Transducer Calibration Maximum Cooling Minimum Cooling Heating Override Fan Override CFM Set Point Actual Airflow Primary Damper Position Measured Velocity Pressure Supply Air Temperature Auto-Calibration Calibration Gain
Table 15 Zone Air Balance/Commissioning Table
Dsable CMODE Dsable CALIBRAT Dsable MAXCOOL Dsable MINCOOL Dsable HEATOVER Dsable FANOVER
0 cfm COMCFM 0 cfm AIRFLOW
100 % DMPPOS
0.000 in. wg MVP
0.0 F SAT
Normal CAL
1.000 CAL_GAIN
Heating Override
This variable can be used to test the heat outputs. Enabling this variable will cause the heat to be modu­lated or staged to full heat until this point is disabled or the force released. Ducted reheat operation will be controlled so as not to exceed the configured maximum duct temperature. The supply-air temperature is included on this screen to verify that the heat is operating.
Heating Override: Display Range Dsable/Enable
Default Value Dsable Network Access Read /Write
Airflow CFM Set Point
This vari able displays the current airflow set point that the zone controller is controlling to. Dur­ing the calibration tests this value can be forced, whic h will change the set point configuration for the value being tested.
Airflow CFM Set Point: Display Units CFM
Display Range 0 to 9999 (Limited by velocity pressure transducer high alarm limit) Default V alue 0 Network Access Read /Write
Actual Airflow Display
This variable shows the actual air­flow being measured, based on the inlet size configured. D ur­ing the Maximum and Minimum Cooling Airflow calibration tests this valu e c an b e for c ed, w hic h will cor rec t t he mu l tipl ie r or offset used to calculate the airflow.
Actual Airflow: Display Units CFM
Display Range 0 to 9999 (Limited by velocity pressure transducer high alarm limit) Default V alue 0 Network Access Read /Write
Primary Damper Position
This variable displays the cur­rent damper position. During CFM Balancing, this variable is used to display the position of the damper. This value can be used to see if the damper is fully open and the system air is sufficient.
Primary Damper Position: Display Units % (open)
Display Range 0 to 100 Default Value 100 Network Access Read Only
Measured Velocity Pressure
This variable displays the measured velocity pressure, which is used to check accuracy during test and balancing of the terminal. If the pressure appears to be much different than that measured with a Magna­helic gage, the transducer can be forced to recalibrate its zero by enabling the Damper/Transducer Calibration.
Measured V elocity Pressure: Display Units in. wg
Display Range 0.000 to 2.000 (Limited by velocity pressure transducer high alarm limit) Default Value 0.000 Network Access Read Only
Supply-Air Temperature
This variable displays the supply­air temperature for ease of verifying the heat operation during the heat test.
Supply-Air T emperature: Display Units F (C)
Display Range -40.0 to 245.0 Default V alue 0.0 Network Access Read /Write
Auto-Calibration
This variable will displa y Nor m a l” if the actuator and airflow transducer calibrat ions are successful. If damper or transducer calibration was not successful, this point will display “Alarm” and the zone controller will broadcast the appropriate alarm (if configured to transmit alarms).
Auto-Calibration: Display Range Normal/Alarm
Default V alue Normal Network Access Read Only
Calibration Gain
Air terminal testing by industry standards is done with straight duct, upstream of the terminal. Since most applications are not installed in this manner, the actual airflow from the terminal, at balancing, may not equal the reading from the zone controller.
The Calibration Gain is used for making fine tuning adjust­ments to the airflow calculation. This number is calcul ated au­tomatically by the zone controller after input to the air balance maintenance screen. The Calibra tion Gain can also be entered manually in the service configuration CONFIG screen.
A number of .95 entered into the Calibration Gain variable will cause the maximum airflow to be reduced to 95% of the calculated value. A number of 1.05 would c ause readings to become 5% higher. The Calibration Gain is adjusted on the Air Balance maintenance screen when performing the Maximum Airflow Calibration and will have the greatest affect on the air­flow at maximum CFM.
After performing the air balance procedure using the air bal­ance maintenance screen, it is recommended to upload and save the Airflow Configuration, Calibration Gain, and Offset settings.
Calibration Gain: Display Range 0.000 to 9.999
Default Value 1.000 Network Access Read Only
501
48
Page 49
ZONE MAINTENANCE TABLE The Zone Maintenance table is used to display zone set points and variables. See T able 16.
Occupied
This variable indicates if the zone controller is
operating in the occupied mode. Occupied: Display Range No/Yes
Default V alue No Network Access Read Only
Linkage Slave
This variable displays if air source linkage is
in effect. Linkage Slave: Display Range No/Yes
Default V alue No Network Access Read Only
Linkage Master
This variable displays if this zone control-
ler is functioning as a linkage master. Linkage Master: Display Range No/Yes
Default V alue No Network Access Read Only
Timed Override in Effect
This variable indicates if a timed
override is in effect. Timed Override
in Effect: Display Range No/Yes
Default V alue No Network Access Read Only
Set Point Offset (T-56)
This variable displays the degrees of offset when using a 33ZCT56SPT space temperature sensor with set point adjustment. The slidebar on the sensor will adjust the desired temperature in that zone, up or down, w hen it is moved. The Set Point Offset (T-56) variable can disable set point offset (set to 0).
Set Point Offset (T-56): Display Units delta F (delta C)
Display Range 0.0 to 15.0 Default V alue 0.0 Network Access Read Only
Cool Master Reference
This variable displays the cooling master reference from the set point schedule. This should be the occupied cool set point when the zone is in occupied mode or the unoccupied cool set point when the zone is in
unoccupied mode. This variable will display any space temper­ature sensor slidebar offset that is being applied.
Cool Master Reference: Display Units F (C)
Display Range 45.0 to 99.9 Default Value 90.0 Network Access Read/Write
Primary Damper Airflow Reference
This variable dis-
plays the current controlling airflow set point. Primary Damper
Airflow Display Units CFM Reference: Display Range 0 to 9999 (Limited by
velocity pressure transducer high alarm limit) Default V alue 0 Network Access Read /Write
Primary Damper Position
This variable displays the cur-
rent damper position. Primary Damper
Position: Display Units % (open)
Display Range 0 to 100 Default Value 100 Network Access Read/Write
Secondary Damper Airflow Reference
This variable dis­plays the current controlling airflow set point for the secondary damper.
Secondary Damper Airflow Display Units CFM Reference: Display Range 0 to 9999 (Limited by
velocity pressure transducer high alarm limit) Default V alue 0 Network Access Read /Write
Heat Enable
This variable displays the demand for heat in the space. The space tem perature must be below the appropri­ate heat set point.
Heat Enable: Display Range Dsable/Enable
Default Value Dsable Network Access Read Only
DESCRIPTION DEFAULT POINT NAME Occupied Linkage Slave Linkage Master Timed Override in Effect Set Point Offset (T-56) Cool Master Reference PI Primary Damper Reference PD Primary Damper Reference Secondary Damper Reference Heat Enable Heat Master Reference Heat Submaster Reference Temperature Control Airflow Relative Humidity Airflow Air Quality Airflow Cooling in Effect Heating in Effect RH in Effect AQ in Effect Unoccupied Dehumidification Cooling Energy Heating Energy
Table 1 6 Zone Maintenance Table
No ZONEOCC No DAVCTL No LINKMAST No TIMOV
0.0 F T56OFF
90.0 F CCMR 0 cfm PISMR
100 % PDSMR
0 cfm SDSMR
Dsable HEATENA
55.0 F HCMR
0 F HSMR
100 % TCA
0 % RHA 0 % AQA
Yes COOLFLAG
No HEATFLAG No RHFLAG No AQFLAG
No UNOCCDH 0 Btu COOLBTUS 0 Btu HEATBTUS
49
801
Page 50
Heat Master Reference heat set point if occupied, or the unoccupied heat set point if unoccupied. This variable will display any space temperature sensor slidebar offset that is being applied.
Heat Master Reference: Display Units F (C)
Heat Submaster Reference displays the desired supply air temperature calculated to heat the space. This is a result of the heating PID loop calculation.
Heat Submaster Reference: Display Units F (C)
Temperature Control Airflow airflow set point determined from the temperature loop calcula­tion. The zone controller compares the Temperature, Relative Humidity, and Air Quality loop. The greatest of the three will become the primary damper airflow reference.
T emperature Control Airflow: Display Units %
Relative Humidity Control Airflow plays the airflow set point determined from the relative humidity loop calculation. The zone controller compa res the Temperature, Relative Humidity, and Air Quality loop. The greatest of the three will become the primary dampe r airflow reference.
Relative Humidity Control Airflow: Display Units %
Air Quality Control Airflow flow set point determined from the air quality loop calculation. The zone controller compares the Temperature, Relative Humidity, and Air Quality loop. The greatest of the three will become the primary damper airflow reference.
Air Quality Control Airflow: Display Units %
This point displays the occupied
Display Range 40.0 to 90.0 Default Value 55.0 Network Access Read/Write
If heat is enabled, this variable
Display Range 0 to 240 Default V alue 0 Network Access Read/Write
This variable displays the
Display Range 0 to 100 Default Value 100 Network Access Read Only
This variable dis-
Display Range 0 to 100 Default V alue 0 Network Access Read Only
This variable displays the air-
Display Range 0 to 100 Default V alue 0 Network Access Read Only
Cooling in Effect in the Cooling mode and if the terminal is using the cooling air­flow set points.
Cooling In Effect: Display Range No/Yes
Heating in Effect in the Heat mode and if the terminal is using the he ating air­flow set points.
Heating In Effect: Display Range No/Yes
Relative Humidity Control in Effect cates if the relative humidity control is active.
Relative Humidity Control In Effect: Display Range No/Yes
Air Quality Control in Effect air quality control is active.
Air Quality Control In Effect: Display Range No/Yes
Unoccupied Dehumidification unoccupied dehumidification control is in effect.
Unoccupied Dehumidification: Display Range Ye s/No
Cooling Energy mary air source cooling BTUs being provided to the space by the terminal. A CCN compatible air source or PAT sensor on a linkage master is required.
Cooling Energy: Display Units Btu
Heating Energy air source heating BTUs being provided to the space by the ter­minal. This value will not include zone level heating. A CCN compatible air source or PAT sensor on a linkage master is required.
Heating Energy: Display Units Btu
This variable displays if the air source is
Default V alue Yes Network Access Read Only
This variable dis plays if the air sourc e is
Default V alue No Network Access Read Only
This variable indi-
Default V alue No Network Access Read Only
This variable indicates if the
Default V alue No Network Access Read Only
This variable indicates if
Default V alue No Network Access Read Only
This variable displays the amount of pri-
Display Range 0 to 999999 Default V alue 0 Network Access Read Only
This point displays the amount of primary
Display Range 0 to 999999 Default V alue 0 Network Access Read Only
801
50
Page 51
Page 52
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 1 1 a 1 3 a
PC 111 Catalog No. 533-355 Printed in U.S.A. Form 33ZC-1SI Pg 52 303 11-99 Replaces: New
Loading...