2 Cool Stages
Adjustable 2nd & 3rd Stage
Timers & Deadbands
Backlit Display & Button
Legends
Aux Heat Indicator
Dry Contact Equipped
Outdoor Sensor Ready with
High/Low Readouts for the Day
Set Point Limiting
Economizer Control
Preoccupancy Fan Purge
Use with most Air Conditioning & Heating Systems including: 1 or 2 Stage
Electric Cooling & 3 Stage Gas Heating, Heat Pump, Electric or Hydronic Heat.
HEAT
PUMP
&
Accepts the
Accepts the
OPTIONAL
OPTIONAL
HUMIDITY MODULE
HUMIDITY MODULE
Carrier Corporation 04/06
Accepts EZ Programmer
Remote Averaging
Programmable Output
Light Activation Equipped
Accepts Optional Humidity Module:
Controls Humidification,
Dehumidification and Reheat
Accepts Optional IR Remote Control
I2:00
Su
AUTO
Pm
74
COOL
HEAT
72
Page 2
Carrier
CAUTION
Follow the Installation Instructions before proceeding.
Set the thermostat mode to “OFF” prior to changing
settings in setup or restoring Factory Defaults.
CAUTION
NEVER PUT MORE THAN ONE
JUMPER ON THE SAME MISC
JUMPER BLOCK!
THIS MAY DAMAGE YOUR
THERMOSTAT.
NOTE: Due to variations in environmental conditions, it is not
always possible to achieve the desired humidification or
dehumidification setpoint.
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Thermostat 33CS450-01
F
4Z95
FOR HOME OR OFFICE USE
Tested to Comply
c
with FCC Standards
C
MISC3
OK
MISC3
Page i
Page 3
How to Use This ManualHow to Use This Manual
Carrier
The Table of Contents divides the thermostat features into sections
The first page of each section contains a more detailed list of the contents
SECTION 14
Timers and DeadbandsTimers and Deadbands
making it easier to quickly find information.
within that section, such as the example page shown below.
Carrier
Header shows section #
Section 14 Contents:
Adjusting the Heat/Cool
Differential..............................14.2
Adjusting the Cycles
Per Hour..................................14.3
Adjusting the Deadband..........14.4
Adjusting the Minutes of
Run-Time Before the
Next Stage...............................14.6
Selecting 2nd Stage Turn
Off Temperature.....................14.7
and title of section
Section contents
14
Visible section tab
on the side of the
page
Section and page #
Page 14.1
In addition, this manual also has an Index to help you find any information
regarding this thermostat quickly.
Page ii
Page 4
Glossary of TermsGlossary of Terms
Auto-Changeover: A mode in which the thermostat will turn on
the heating or cooling based on room temperature demand.
Configurable Output Jumper: Using jumpers on the thermostat
you can configure the MISC1, MISC2, and MISC3 terminals to
control humidification, dehumidification, 2nd stage cooling, 3rd
stage heating, and a programmable output.
Cool Setpoint: The warmest temperature that the space should
rise to before cooling is turned on (without regards to
deadband).
Deadband: The number of degrees the thermostat will wait, once
setpoint has been reached, before energizing heating or cooling.
Dehumidify: To reduce the amount of moisture in the air.
Differential: The forced temperature difference between the heat setpoint and the cool setpoint.
Heat Setpoint: The coolest temperature that the space should
drop to before heating is turned on (without regards to
deadband).
Humidify: To increase the amount of moisture in the air.
Icon: The word or symbol that appears on the thermostat
display.
Mode: The current operating condition of the thermostat (i.e. Off,
Heat, Cool, Auto, Program On).
Non-Programmable Thermostat: A thermostat that does not
have the capability of running the Time Period Programming.Programmable Thermostat: A thermostat that has the capability
of running the Time Period Programming.Reheat: Running the cooling and 2nd stage strip heaters at the
same time in order to dehumidify the air without cooling down
the room temperature.
Temperature Swing: Same as Deadband.
Time Period Programming: A program that allows the
thermostat to automatically adjust the heat setpoint and/or the
cool setpoint based on the time of day.
Carrier
Page iii
Page 5
Page 6
Table of ContentsTable of Contents
Page iv
Carrier
Quick Start
Getting to Know Your
Thermostat
Setting Clock and Day
Basic Operation
Viewing Temperature
and Humidity
Programming the
Daily Schedule
Programming the
Fan Operation
Thermostat Display
Options
Humidification
Dehumidification
Viewing Equipment
Run-Times
Electric Heat and
Heat Pump Operation
Timers and Deadbands
Using the
Programmable Output
Programming Remote
Sensor Operation
Dry Contact Operation
Light Activated
Operation
Energy Save
Operation
Programming the Run Time Alerts
Programming the
Holiday Mode
Configuring the MISC
Outputs
Note: Following the instructions in this section will allow you to
operate your thermostat using the factory default settings. These
settings are depicted in the illustrations throughout this manual.
Page 1.1
Page 8
Carrier
HUMIDITYMODE
SET CLOCK
Press the MODE and
HUMIDITY buttons
at the same time
Setting the Clock Setting the Clock
Am
I2:00
Setting the DaySetting the Day
Mo
Press the MODE
and HUMIDITY
buttons at the
same time to
return to normal
operation.
Setup
Setup
SET CLOCK
I
2
HUMIDITYMODE
During Setup & Programming:
Pressing the UP or DOWN
buttons will modify the flashing
selection.
To adjust the
Clock or Day use
Press
MODE
Buttons.
1
Page 1.2
Page 9
Selecting the Heat or Cool ModeSelecting the Heat or Cool Mode
1
Select Mode by Pressing the MODE Button
Pm
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
Cooling Only
The COOL setting indicates the
temperature the room has to
reach before the air conditioner
will turn on to cool the room.
Heating or Cooling
AUTO will automatically select
heat or cool based on room
temperature demand.
I2:00
Su
I2:00
Su
I2:00
Su
AUTO
70
Pm
70
Pm
70
Time Schedule for
Heating or Cooling
Program On will activate the
stored timer operation for the
heating and cooling
setpoints (occupied or
unoccupied periods).
OFF indicates both heating
Off
and air conditioning
systems are turned off.
I2:00
Su
I2:00
Su
OFF
occupied
1
Program On
Pm
70
Pm
70
HEAT
68
76
COOL
76
COOL
HEAT
68
76
COOL
HEAT
68
Carrier
Press
MODE
Press
MODE
Press
MODE
Press
MODE
Page 1.3
Page 10
Carrier
Selecting Your Desired Temperature
Selecting Your Desired Temperature
(adjusting the setpoints)
(adjusting the setpoints)
AUTO OR PROGRAM MODE
Pressing the UP or DOWN buttons in Auto or Program mode
will adjust both the heat and cool set temperatures
simultaneously.
Pm
I2:00
Su
AUTO
70
HEAT OR COOL MODE
Pressing the UP or DOWN buttons in Heat or Cool mode will
adjust only the heat or cool set temperature.
Pm
I2:00
Su
76
COOL
HEAT
68
76
COOL
Adjust the desired
set temperature with the
buttons.
Adjust the desired
set temperature with the
70
buttons.
Using the Fan ButtonUsing the Fan Button
Pm
I2:00
Su
AUTO
FanOn
70
76
68
COOL
HEAT
Press
FAN
Fan On indicates constant fan operation.
If Fan On is selected the fan will run
continuously at all times, except in Off,
and will only run if there is a heating or
cooling demand in Unoccupied periods.
Pressing the FAN button toggles this
feature on or off.
Page 1.4
1
Page 11
SECTION 2
Getting to Know Your ThermostatGetting to Know Your Thermostat
2
Section 2 Contents:
Front Panel Buttons.....................2.2
Display Features...........................2.3
Carrier
Page 2.1
Page 12
Front Panel Front Panel
Backlit LCD Display
Carrier
I2:00
Su
AUTO
Heat or Cool Demand Indicator
Red = Heat, Green = Cool
QUICK RELEASE FOR
ACCESSORY PORT
(pg. 23.1)
Pm
74
COOL
HEAT
72
Premier
Commercial
Programmable Thermostat
Pm
I2:00
Su
AUTO
HUMIDITY
SET CLOCK
Warmer Button
(glows red)
Override
Button
74
COOL
HEAT
72
HOLIDAY
FANMODEPROGRAM
OUTSIDE
Carrier
2
sometimes referred
to as the UP button
[]
Cooler Button sometimes refer-
(glows blue) red to as the
DOWN button
OVER
RIDE
[]
HUMIDITY
SET CLOCK
FANMODE
Page 2.2
PROGRAM
OUTSIDE
HOLIDAY
Page 13
Display FeaturesDisplay Features
2
2
Carrier
Program On
Am
I8:88
SuMoTuWeThFrSa
Service Filter
Pan UV Light
AUTO
OFFON
Unoccupied
123
Override
FanOn
Mode Indicators - Section 4
Selects the operational mode of the equipment.
HEAT - Indicates the heating mode.
COOL - Indicates the air conditioning mode.
AUTO - Indicates the system will automatically changeover
between heat and cool modes as the temperature varies.
OFF - Indicates heating and cooling is turned off.
PROGRAM ON - Indicates the time period program is enabled to
run.
Clock with Day of the Week - Section 3
Indicates the current time and day. This clock is also used to program
the time period schedules.
Room Temperature Display - Section 5
Indicates the current room temperature and displays the outside
temperature when selected.
Desired Set Temperature - Section 4/5
Indicates desired room temperature(s). Also displays the highest
and lowest outside temperatures for the day.
Outside icon - Section 5
Indicates the temperature displayed is from the optional outside
sensor.
Pm
StartStop
DeHumidify
I88
Page 2.3
Setup
H I
88
COOL
Outside
Remote
AUXHEAT
L O
88
Page 14
Carrier
Display FeaturesDisplay Features
2
Program On
Am
I8:88
SuMoTuWeThFrSa
Service Filter
Pan UV Light
AUTO
OFFON
Unoccupied
123
Override
FanOn
Occupied & Unoccupied icons - Section 6
Indicates the program number: Occupied 1,2,3,or Unoccupied.
Override icon - Section 6
Indicates the program is currently being overridden for up to 4 hours.
Setup icon - Sections 7-20
Indicates the thermostat is in the setup mode.
Fan On icon - Section 7
Indicates constant, continuous fan operation. When Fan On is not
lit - indicates the fan will only operate when necessary to heat or to
cool.
Service Filter icon - Section 19
Appears when the filter should be serviced under normal conditions.
Adjustable from 0 - 1950 hours of blower operation.
icon - Section 8
Indicates keypad has been locked.
StartStop icon Appears when programming occupied time periods.
Pm
StartStop
DeHumidify
I88
Section 6
Page 2.4
Setup
H I
88
COOL
Outside
Remote
AUXHEAT
L O
88
2
Page 15
Display FeaturesDisplay Features
2
Carrier
Program On
Am
I8:88
SuMoTuWeThFrSa
Service Filter
Pan UV Light
AUTO
OFFON
Unoccupied
123
Override
FanOn
UV Light icon - Section 11/19
Appears when the UV bulb should be serviced under normal
conditions. Adjustable from 0 - 1950 days of operation.
Remote icon - Page 22.4
Indicates the remote sensor reading of the thermostat is being
viewed.
AuxHeat icon - Pages
Indicates 2nd stage electric strip heat is being used when the therm ostat is programmed for Heat Pump operation. Only the Aux icon
will appear during Cool to Dehumidify to indicate Reheat operation.
Humidify/DeHumidify icon Indicates the system is currently humidifying/dehumidifying the air.
Lo icon Indicates the lowest recorded outside temperature for the day.
Hi icon - Section 5
Indicates the highest recorded outside temperature for the day.
Service Pan icon - Section 16
Indicates that a sensor (accessory) has detected the condensate
drain pan is full and the compressor (Y1) has been locked out.
Section 5
Pm
StartStop
DeHumidify
I88
10.5 & 13.4
Sections 9-10
Page 2.5
Setup
H I
88
COOL
Outside
Remote
AUXHEAT
L O
88
Page 16
SECTION 3
Setting the Clock and DaySetting the Clock and Day
Section 3 Contents:
Setting the Clock..........................3.2
Setting the Day.............................3.2
Carrier
3
Note: During setup & programming pressing the UP or DOWN
buttons will modify the flashing selection.
Page 3.1
Page 17
HUMIDITYMODE
SET CLOCK
3
Setting the Clock Setting the Clock
I2:00
Press the MODE and
HUMIDITY buttons
at the same time
Am
Setup
I
Carrier
During Setup & Programming:
Pressing the UP or DOWN
buttons will modify the flashing
selection.
To adjust the
Clock or Day use
Setting the DaySetting the Day
Mo
Press the MODE
and HUMIDITY
buttons at the
same time to
return to normal
operation.
Setup
2
HUMIDITYMODE
SET CLOCK
Page 3.2
Press
MODE
Buttons.
Page 18
SECTION 4
Basic OperationBasic Operation
Section 4 Contents:
Programming for Auto or
Program Operation....................4.2
Selecting the Proper
Operating Mode.........................4.3
Selecting Your Desired
Temperature...............................4.7
Carrier
4
Note: During setup & programming pressing the UP or DOWN
buttons will modify the flashing selection.
Page 4.1
Page 19
Carrier
Programmable or Non-Programmable
Programmable or Non-Programmable
Thermostat
Thermostat
When the very simplest operation is desired, this thermostat
4
may be configured to be non-programmable, with or without
Auto-Changeover. Follow the step below.
If ‘NO’ is selected, the thermostat will lockout the Program On screen;
only the Off, Heat, Cool, and Auto screens may be accessed by
pressing the MODE button.
Select ‘YES’ if you would like your thermostat to be programmable,
then the Program mode will be accessible through the use of the
MODE button.
Note: Press the MODE
button momentarily
MODE
PROGRAM
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
YES
Select Yes if you would like
the thermostat to be programmable or No for non-programmable.
NO
pressed, the display will leave the setup screens after 30 seconds.
Program On
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Setup
i
Press
PROGRAM
Page 4.2
Page 20
Carrier
Manual or Auto-Changeover
Manual or Auto-Changeover
Thermostat
Thermostat
When the very simplest operation is desired, this thermostat may
be configured to be a manual heat and cool thermostat, with or
without time period programmability. Follow the step below.
The thermostat may be programmed to function as a Heat Only or
Cool Only thermostat by selecting ‘NO’ in the setup screen below.
This will lockout the Auto-Changeover screen and only allow the Off,
Heat, Cool, and Program On screens to be accessed.
4
MODE
PROGRAM
MODE
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
YES
Select Yes if you would
like the thermostat to
be Auto-Changeover or
No for a Heat Only and
Cool Only Thermostat.
NO
pressed, the display will leave the setup screens after 30 seconds.
AUTO
Setup
Page 4.3
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
2
Press
PROGRAM
Page 21
Operating Mode when the Thermostat
Operating Mode when the Thermostat
is Configured to be:
is Configured to be:
NON-PROGRAMMABLE WITH MANUAL-CHANGEOVER - If the
thermostat is configured to be a non-programmable thermostat with
4
Manual-Changeover, the following screens will be available by
pressing the MODE button.
Select the Mode by Pressing the MODE Button
Pm
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
The COOL setting indicates the
reach before the air conditioner
Cooling Only
temperature the room has to
will turn on to cool the room.
OFF indicates both heating
systems are turned off.
Off
and air conditioning
I2:00
Su
I2:00
Su
I2:00
Su
OFF
70
Pm
70
Pm
68
76
70
Carrier
HEAT
Press
MODE
COOL
Press
MODE
Page 4.4
Page 22
Operating Mode when the Thermostat
Operating Mode when the Thermostat
is Configured to be:
is Configured to be:
NON-PROGRAMMABLE WITH AUTO-CHANGEOVER - If the
thermostat is configured to be a non-programmable thermostat
with Auto-Changeover, the following screens will be available by
pressing the MODE button
Select the Mode by Pressing the MODE Button
Pm
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
Cooling Only
The COOL setting indicates the
temperature the room has to
reach before the air conditioner
will turn on to cool the room.
Heating or Cooling
AUTO will automatically select
heat or cool based on room
temperature demand.
OFF indicates both heating
systems are turned off.
Off
and air conditioning
I2:00
Su
I2:00
Su
I2:00
Su
AUTO
I2:00
Su
OFF
70
Pm
70
Pm
70
Pm
HEAT
68
76
COOL
76
COOL
HEAT
68
70
Carrier
4
Press
MODE
Press
MODE
Press
MODE
Page 4.5
Page 23
Carrier
Operating Mode when the Thermostat
Operating Mode when the Thermostat
is Configured to be:
is Configured to be:
PROGRAMMABLE WITH MANUAL-CHANGEOVER - If the thermostat is
configured to be a programmable thermostat with Manual-Changeover, the
following screens will be available by pressing the MODE button.
4
Select the Mode by Pressing the MODE Button
Pm
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
Cooling Only
The COOL setting indicates the
temperature the room has to
reach before the air conditioner
will turn on to cool the room.
Time Schedule for
Heating Only
The HEAT Program On setting
will activate the time period
program for the heating
setpoint ONLY (occupied or
unoccupied periods).
Time Schedule for
Cooling Only
The COOL Program On setting
will activate the time period
program for the cooling
setpoint ONLY (occupied or
unoccupied periods).
OFF indicates both heating
systems are turned off.
Off
and air conditioning
I2:00
Su
I2:00
Su
I2:00
Su
occupied
1
I2:00
Su
occupied
1
I2:00
Su
OFF
70
Pm
70
Program On
Pm
70
Program On
Pm
70
Pm
HEAT
68
76
COOL
HEAT
68
76
COOL
70
Page 4.6
Press
MODE
Press
MODE
Press
MODE
Press
MODE
Page 24
Operating Mode when the Thermostat
Operating Mode when the Thermostat
is Configured to be:
is Configured to be:
PROGRAMMABLE WITH AUTO-CHANGEOVER - If the thermostat is
configured to be a programmable thermostat with Auto-Changeover,
the following screens will be available by pressing the MODE button.
Select the Mode by Pressing the MODE Button
Pm
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
Cooling Only
The COOL setting indicates the
temperature the room has to
reach before the air conditioner
will turn on to cool the room.
Heating or Cooling
AUTO will automatically select
heat or cool based on room
temperature demand.
Time Schedule for
Heating or Cooling
Program On will activate the
time period program for the
heating and cooling
setpoints. (occupied or
unoccupied periods)
OFF indicates both heating
Off
and air conditioning
systems are turned off.
I2:00
Su
I2:00
Su
I2:00
Su
AUTO
I2:00
Su
occupied
1
I2:00
Su
OFF
70
Pm
70
Pm
70
Program On
Pm
70
Pm
HEAT
68
76
COOL
76
COOL
HEAT
68
76
COOL
HEAT
68
70
Page 4.7
Carrier
4
Press
MODE
Press
MODE
Press
MODE
Press
MODE
Page 25
Carrier
Selecting Your Desired Temperature (adjusting setpoints)Selecting Your Desired Temperature (adjusting setpoints)
AUTO OR PROGRAM MODE
Pressing the UP or DOWN buttons in Auto or Program
modes will adjust both the heat and cool set temperatures
4
simultaneously. For more information on this see page 13.2.
Adjust the desired
Pm
I2:00
Su
AUTO
70
HEAT OR COOL MODE
Pressing the UP or DOWN buttons in Heat or Cool modes will
adjust only the heat or cool set temperature.
Pm
I2:00
Su
76
COOL
HEAT
68
76
COOL
set temperature with the
buttons.
Adjust the desired
set temperature with the
70
buttons.
Page 4.8
Page 26
SECTION 5
Viewing the Temperature and Humidity SensorsViewing the Temperature and Humidity Sensors
Carrier
Section 5 Contents:
Viewing the Outside
Temperature..............................5.2
Viewing the Indoor
Humidity....................................5.3
5
Page 5.1
Page 27
Carrier
Viewing the Outside TemperatureViewing the Outside Temperature
Requires an outside sensor (optional accessory) to be installed (see
page 15.2 for wiring instructions). To read the temperature from the
outside sensor, press the PROGRAM and HOLIDAY buttons. The
display will then show the current outside temperature along with the
highest and lowest temperatures for the day.
5
PROGRAM
OUTSIDE
HOLIDAY
Press the PROGRAM
button. While holding
PROGRAM, press the
HOLIDAY button to view
the Outside temperature.
The highest and lowest
temperatures for the day
will be displayed along
with the current outside
temperature.
This reading is from the
sensor connected to RS2.
Press the PROGRAM
button. While holding
PROGRAM, press the
HOLIDAY button to leave
the Outside temperature
screen.
Note: If no sensors are connected 2 dashes [- -] will appear.
83
PROGRAM
OUTSIDE
H I
L O
HOLIDAY
92
Outside
68
Page 5.2
High temperature
for the day.
Current outside
temperature.
Low temperature
for the day.
Page 28
Carrier
Viewing the Indoor HumidityViewing the Indoor Humidity
Requires the Humidity Module (optional accessory) to be installed.
To display the current humidity at the thermostat, press the
HUMIDITY button. The display will then show the current indoor
humidity along with the humidification setpoint (Section 9).
Note: The humidity reading will not appear unless the Humidity
Module has been installed. If the Humidity Module has not been
installed dashes will appear in place of the humidity reading.
5
HUMIDITY
Current Room Humidity
NOTE: Due to variations in environmental conditions, it is not always possible
to achieve the desired humidification or dehumidification setpoint.
To view the indoor humidity
reading, press the
HUMIDITY button
40
Press the HUMIDITY button
again to return the display
to normal operation.
Humidify
0
Setup
I
Press
HUMIDITY
Page 5.3
Page 29
SECTION 6
Programming the Daily ScheduleProgramming the Daily Schedule
Section 6 Contents:
6
Programming a Daily
Schedule...................................6.2
Overriding the Daily
Schedule...................................6.6
Carrier
Page 6.1
Page 30
Programming a Daily ScheduleProgramming a Daily Schedule
Carrier
Press
PROGRAM
Press the PROGRAM button to enter time period programming.
Use the Programming Worksheet on the back cover
to help with this section.
Select the maximum # of
occupied periods to be
used on any one day.
Typically most installations
use only Occupied 1.
(1,2 or 3)
Adjust the cooling
setpoint for Occupied 1.
(35 - 99, OF )
Adjust the heating
setpoint for Occupied 1.
(OF, 35 - 99 )
Adjust the cooling
setpoint for unoccupied
periods.
(35 - 99, OF )
occupied
1
occupied
1
occupied
1
Unoccupied
Page 6.2
74
COOL
74
COOL
HEA T
72
85
COOL
Continued
MODE
MODE
MODE
MODE
6
Press
Press
Press
Press
Page 31
Carrier
Adjust the heating setpoint for Unoccupied
periods.
(OF, 35 - 99 )
Unoccupied
85
COOL
HEAT
55
Press
MODE
6
Mo
Select the day for
Occupied 1.
(Mo - Su)
Adjust the start time
for Occupied 1.
Adjust the stop time
for Occupied 1.
On
Select Occupied 1 to run
on this day (On), or not to
run on this day (Off).
Off
occu pied
1
7:00
Mo
occu pied
1
6:00
Mo
occupied
1
Mo
ON
occupied
1
Press
MODE
Am
Start
Press
MODE
Pm
Stop
Press
MODE
Press
MODE
Continued
Page 6.3
Page 32
Press
MODE
The copy command becomes available after the maximum # of
occupied periods are programmed in a day. This example uses
only one occupied period.
Yes
Select Yes to copy the
previous day’s program
to this day.
No
If Yes is selected:
Selecting Yes, then pressing mode will copy the
previous day’s program. If yes is selected again,
or each time, this routine will repeat.
Select the day
for Occupied 1.
(Tu - M)
Adjust the start time
for Occupied 1.
Adjust the stop time
for Occupied 1.
Tu
Tu
occupied
1
7:00
Tu
occupied
1
6:00
Tu
occupied
1
Am
Start
Pm
Stop
Carrier
If No is selected:
6
Press
MODE
Press
MODE
Press
MODE
Press
MODE
Page 6.4
Continued
Page 33
On
Select Occupied 1 to run
on this day (On), or not to
run on this day (Off).
Off
Tu
ON
occupied
1
Carrier
Yes
Select Yes to copy
6
Press
MODE
If No is selected, as in previous steps, flashing prompts will appear to input start
and stop times for Occupied 1. If more than one occupied period was selected in
the first programming step (page 6.2), then the cool and heat setpoints, and start
and stop times for each additional occupied period will be prompted.
Press
PROGRAM
PROGRAMMING TIPS
the previous day’s
program to this day.
No
If Yes is selected:
Selecting Yes, then pressing mode will copy the
previous day’s program. If yes is selected each
time, this routine will repeat.
After programming for all seven days is complete, press the PROGRAM button to
leave the Setup screens. If no buttons are pressed, the display will leave the setup
screens after 30 seconds.
If only the Occupied 1 period is selected in the first programming step (page 6.2), Occupied
2 & 3 programming steps are skipped. Furthermore, if Occupied 2 is selected, Occupied 3
programming steps are skipped.
Heat & Cool setpoints for Occupied 1 are the same for every day of the week. If desired,
Heat & Cool setpoints for Occupied 2 & 3 can be adjusted differently for each day of the week.
If the start time is set later in the day than the stop time, the program will run from the start
time to midnight and from midnight to the stop time on the same day. For example: 9pm start,
8am stop, on Monday. In this example the program will run from 12am Monday to 8am Monday
and again from 9pm Monday to 12am Tuesday.
Unoccupied Operation: The unoccupied settings take effect at all times when: (1) the program is
on and (2) the current time is outside a preset occupied period. For this reason start and stop
times are not necessary for unoccupied time periods.
If the same start and stop times are programmed for an occupied period, then it will run
24 hours.
If one occupied period starts and stops within another occupied period the lower occupied # has
priority. For example: If Occupied 3 is programmed to be on 24 hours, and Occupied 2 is
programmed to run that day, then the Occupied 2 setting will take over for Occupied 3 between
Occupied 2 start and stop times.
We
Page 6.5
If No is selected:
Press
MODE
Page 34
Carrier
Overriding the Daily ScheduleOverriding the Daily Schedule
The OVERRIDE button may be used to interrupt the normal time
schedule programming of the thermostat. Override may only be used
when the thermostat is running the time schedule, in Program On
mode.
Unoccupied Operation - During programmed, unoccupied
periods, pressing the OVERRIDE button will temporarily
force the thermostat into Occupied 1 comfort settings for 30
minutes. The remaining Override time will alternate with the
clock (refer to the second display below). The Override timer
can be set up to a maximum of four (4:00) hours, in increments
of 30 minutes. If the timer has been set for the maximum time,
the next press of the OVERRIDE button will reset the timer,
returning the thermostat to the correct time period program for
the day.
Occupied Operation - During programmed, occupied periods, a
press of the OVERRIDE button will force the thermostat into an
unoccupied period for the remainder of the day. During this
forced unoccupied period the OVERRIDE button will operate as
described above.
Unoccupied
Override
7:56
:
30
occupied
1
Program On
Pm
We
65
7:56
Program On
We
65
Pm
Page 6.6
85
COOL
HEAT
55
74
COOL
HEAT
72
Press
OVERRIDE
6
Page 35
SECTION 7
Programming the Fan OperationProgramming the Fan Operation
When the fan is set for automatic operation it will energize any time
there is a call for heating or cooling, otherwise the fan will remain off.
Pressing the FAN button will energize the fan and display the FanOn
icon on the thermostat display. To operate the fan in the automatic
mode, press the FAN button again and the FanOn icon will disappear.
Press
FAN
7
I2:00
Su
AUTO
FanOn
Pm
70
76
68
Fan On indicates constant fan operation.
If Fan On is selected the fan will run
continuously at all times, except in Off,
COOL
and will only run if there is a heating or
HEAT
cooling demand in Unoccupied periods.
Pressing the FAN button toggles this
feature on or off.
Smart Fan OperationSmart Fan Operation
This feature allows the fan to run continuously during Occupied 1, 2
or 3 and automatically de-energize during Unoccupied, except when
necessary to heat or cool. To use this feature, place the thermostat in
the Program On mode. Next, press the FAN button to display the
FanOn icon (see below).
Press
FAN
Program On
Pm
I2:00
Su
occupied
1
FanOn
70
Page 7.2
76
COOL
HEAT
68
Page 37
Carrier
Setting the Fan-Off Time DelaySetting the Fan-Off Time Delay
To increase cooling efficiency of your unit, the thermostat may be
programmed to continue running the fan after a call for cooling has
been satisfied. This delay may be set for 30, 60, or 90 seconds. If
the Fan Off Delay is set for zero seconds, the fan will not energize
after a call for cooling has been satisfied.
7
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
:00
Set the Fan Off Delay
to 0, 30, 60, or 90
seconds.
FanOn
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Setup
3
Page 7.3
Press
PROGRAM
Page 38
Carrier
Fan Purge OperationFan Purge Operation
When this feature is activated, the fan will turn on during an
unoccupied period at a preset amount of time prior to Occupied 1.
This preoccupancy fan purge timer may be set from zero to three
hours, in 15 minute increments. Zero means this feature is turned off.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
7
Adjust the preoccupancy
fan purge timer.
0 - 3 hours.
0:00 = off
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Turning On/Off the BacklightTurning On/Off the Backlight
Carrier
MODE
PROGRAM
MODE
Programming the Thermostat to Display
Programming the Thermostat to Display
Temperature in Fahrenheit or Celsius
Temperature in Fahrenheit or Celsius
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Select backlight operation:
AUTO - Light from 6pm to
6am nightly.
ON - Light continuously.
OFF - Light for 8 seconds
after a button press.
C
Select thermostat
operation in degrees
Fahrenheit or Celsius.
F
pressed, the display will leave the setup screens after 30 seconds.
AUTO
Setup
Setup
f
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
5
Press
MODE
6
Press
PROGRAM
8
Page 8.2
Page 41
Carrier
Locking/Unlocking the KeypadLocking/Unlocking the Keypad
To prevent unauthorized use of the thermostat, the front panel
buttons may be disabled. To disable, or ‘lock’ the keypad, press
and hold the MODE button. While holding the MODE button,
press the UP and DOWN buttons together. The icon will
appear on the display, then release the buttons.
Press all three
buttons in the order
8
outlined above for
keypad lockout
To unlock the keypad, press and hold the MODE button. While
holding the MODE button, press the UP and DOWN buttons
together. The icon will disappear from the display, then
release the buttons.
MODE
I2:00
AUTO
Pm
65
85
COOL
HEAT
55
Page 8.3
Page 42
Carrier
Programming a Security LevelProgramming a Security Level
When a security level has been programmed, the thermostat will allow
limited adjustment to the setpoints (steps # 8 and 9). In security
levels 2 and 3, the thermostat is forced into the Program On mode.
To disable the security feature, set the value in step #7 to 0; this will
cause steps # 8 and 9 not to appear.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
8
Select the security level:
0=No security in effect
1=Setpoint range limited
2=1+ program on all times
3=2 + prohibits setpoint
changes
Step #8 appears only
if step #7 is not 0.
Adjust the maximum
allowable heat setpoint
when security is in effect.
Step #9 appears only
if step #7 is not 0.
Adjust the minimum
allowable cool setpoint
when security is in effect.
(35 - 99 )
(35 - 99 )
80
Setup
0
Setup
Setup
65
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 8.4
7
Press
MODE
HI
8
HEAT
9
COOL
LO
Press
MODE
Press
PROGRAM
Page 43
SECTION 9
HumidificationHumidification
Carrier
Section 9 Contents:
Installing the Humidity
Module.......................................9.2
Setting a Thermostat Jumper
9
for Humidity Operation............9.3
Adjusting the Humidification
Setpoint.....................................9.4
NOTE: The humidification functions described in this section will
only be available if a Humidity Module has been properly installed.
Disclaimer:
The manufacturer of this thermostat cannot be liable for
misinstallation, improper connection or improper programming of
the humidity functions of this thermostat that may result in water
damage or mold growth.
Additionally, the manufacturer of this thermostat is not responsible
for the fitness of the humidifier and/or installation of said humidifier
connected to this thermostat. Furthermore, the maintenance of the
humidifier components, including but not limited to, the filters and
pads are not the responsibility of the thermostat manufacturer.
The Humidifier Service icon is only a suggestive reminder and
should not take the place of the humidifier manufacturer’s
required maintenance requirements and schedule.
Page 9.1
Page 44
Carrier
Installing the Humidity ModuleInstalling the Humidity Module
To install the Humidity Module the thermostat must be detached
from the back plate. Plug the Humidity Module into the Humidity
Module connector as shown in Figure 2 below. Follow the detailed
instructions included with the Humidity Module accessory. Once the
Humidity Module has been installed, you must adjust the Humidity
jumper setting to HUM as shown in Figure 1 below. This will allow
you to access the humidification and dehumidification setup steps.
Back of 33CS450-01
W3
PROG
HUM
DEHUM
ECON
Y2
(MISC1
MISC3 MISC2 MISC1
ONLY)
W1
Y1
G
MISC2
CK1
CKGND
R
C
MODULEWITHSENSING
2
4
INSTALLHUMIDITY
ELEMENTOUTWARD
1
3
For proper humidity operation, this
jumper must be set for HUM.
Figure 1
(FAN)
ELEC
GAS
HP
GAS
B
O
W2
MISC1
HUM
NO HUM
Rs2
MISC3
RS+5
Z
8
6
X
Rs1
1
RSGND
Y
579
Install the Humidity Module
(see Humidity Module Instruction
Sheet for more detailed information).
HUM
OR
NO HUM
9
Figure 2
Humidity Module
Thermostat Circuit
Board.
Page 9.2
Humidity Module
Plug located on
the Thermostat
Circuit Board.
Page 45
Carrier
Setting a Thermostat Jumper for
Setting a Thermostat Jumper for
Humidity Operation
Humidity Operation
To operate one of the MISC outputs using humidity-based operation,
place the MISC1, MISC2, or MISC3 jumper on the terminal labeled
HUM (see diagram below). This will supply 24VAC to the selected
MISC terminal based on the humidification programming in the
following pages. Only one of the three outputs (MISC1, MISC2, or
MISC3) is required to have this jumper. For more information
regarding the MISC1, MISC2, and MISC3 outputs, please see
section 21.
9
In the diagram below, the MISC3 jumper
has been set for HUM (humidify) operation.
(FAN)
DEHUM
CKGND
W3
PROG
HUM
ECON
MISC2
MISC3 MISC2MISC1
W1
Y1
G
CK1
R
C
ELEC
GAS
HP
Y2
(MISC1ONLY)
INSTALLHUMIDITY
MODULEWITHSENSING
ELEMENTOUTWARD
GAS
B
O
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
Z
2
8
4
6
X
Rs1
1
RSGND
1
Y
3
579
W3
PROG
HUM
DEHUM
ECON
MISC3 MISC2MISC1
(MISC1
ONLY)
IMPORTANT CAUTION
NEVER PUT MORE THAN ONE JUMPER
ON THE SAME MISC JUMPER BLOCK!
THIS MAY DAMAGE THE THERMOSTAT
MISC3
OK
MISC3
Y2
Page 9.3
Page 46
Carrier
Adjusting the Humidification SetpointAdjusting the Humidification Setpoint
If your HVAC unit is equipped with a humidification system and the
Humidity Module has been installed, the thermostat will provide power
to the appropriate terminal on the backplate of the thermostat when
the humidity in the building falls below the setpoint you have chosen.
The value for this setpoint ranges from 0% to 60%.
NOTE: Due to variations in environmental conditions, it is not always possible
to achieve the desired humidification or dehumidification setpoint.
HUMIDITY
Press the HUMIDITY
button to enter the
Humidity Setup screen.
NOTE: Each step # is located at
the top right corner of the
display for easy reference.
9
Current Room Humidity
Adjust the desired
humidification setpoint
(0%-60%)
40
Press the HUMIDITY button to leave the
Humidity Control screens (if no buttons are
pressed, the display will leave the Humidity
Control screens after 30 seconds).
Humidify
0
Setup
I
Press
HUMIDITY
Humidification Notes: Press the button to set the humidity
setpoint to 0% for no humidification operation.
You cannot set the dehumidify setpoint any lower than the humidify setpoint; a
5% differential is forced between the humidify and dehumidify setpoints.
Page 9.4
Page 47
SECTION 10
DehumidificationDehumidification
Section 10 Contents:
Configuring a Thermostat Output
Jumper for Dehumidification
Operation................................10.2
10
Adjusting the Dehumidification
Setpoint...................................10.3
Using Your Air Conditioner
to Dehumidify.........................10.4
Using the Reheat
Function..................................10.5
Using the DEHUM
Terminal..................................10.6
Carrier
NOTE: The dehumidification functions described in this section will
only be available if a Humidity Module has been properly installed.
For instructions on installing the Humidity Module please see page 9.2.
Page 10.1
Page 48
Carrier
Setting a Thermostat Jumper for
Setting a Thermostat Jumper for
Dehumidification Operation
Dehumidification Operation
To control a MISC output for dehumidification, install the Humidity
Module and place the Humidity Jumper on HUM (see page 9.2).
Then place the MISC1, MISC2, or MISC3 jumper on the terminal
labeled DEHUM (see diagram below). This will supply 24VAC to the
selected MISC terminal based on the programming in the following
pages. Only one of the three outputs (MISC1, MISC2, or MISC3) is
required to have a jumper. For more information regarding the
MISC1, MISC2, and MISC3 outputs, please see section 21.
In the diagram below, the MISC2 jumper has
been set for DEHUM (dehumidification) operation.
(FAN)
DEHUM
CKGND
PROG
ECON
MISC2
W3
HUM
W1
Y1
G
CK1
R
C
MISC3 MISC2 MISC1
ELEC
GAS
HP
Y2
(MISC1
ONLY)
INSTALLHUMIDITY
MODULEWITHSENSING
ELEMENTOUTWARD
GAS
B
O
W2
MISC1
HUM
NO HUM
Rs2
MISC3
RS+5
Z
2
8
4
6
X
Rs1
1
RSGND
1
Y
3
579
W3
PROG
HUM
DEHUM
ECON
IMPORTANT CAUTION
NEVER PUT MORE THAN ONE JUMPER
ON THE SAME MISC JUMPER BLOCK!
THIS MAY DAMAGE THE THERMOSTAT
MISC3
OK
MISC3
Page 10.2
MISC3 MISC2 MISC1
10
Y2
(MISC1
ONLY)
Page 49
Carrier
Adjusting the Dehumidification SetpointAdjusting the Dehumidification Setpoint
Dehum Terminal: If a MISC terminal is selected for DEHUM operation
(see page 10.2), then the thermostat will provide power to this terminal
when the humidity in the building is above the setpoint you have chosen.
See page 10.6 for detailed programming instructions. To utilize this
feature your HVAC unit must be equipped with a DEHUM terminal.
Cool to Dehumidify: If the thermostat is programmed for Cool to
Dehumidify operation, then the thermostat will energize the cooling
system any time the humidity in the building is above the setpoint you
have chosen. The thermostat may also be programmed for Reheat
operation if available. See pages 10.4 and 10.5 for detailed
programming instructions.
In each case, when the indoor humidity falls below the setpoint you
have selected, Cool to Dehumidify and the MISC terminal will be
de-energized. The value for this setpoint ranges from 25% to 99%.
10
NOTE: Due to variations in environmental conditions, it is not always
possible to achieve the desired humidification or dehumidification setpoint.
HUMIDITY
MODE
Press the HUMIDITY button
to enter the Humidification
Setup screens.
Press the MODE button once
NOTE: Each step # is located at
the top right corner of the
display for easy reference.
Current Room Humidity
ON / +
Adjust the desired
dehumidification setpoint
(25%-99%)
OFF / -
40
99
Press the HUMIDITY button to leave the Humidity
Control screens (if no buttons are pressed, the display
will leave the Humidity Control screens after 30 seconds).
DeHumidify
Setup
2
Press
HUMIDITY
Dehumidification Notes: Press the button to set the
dehumidification setpoint to 99% for no dehumidification operation.
This will lockout Advanced Setup steps 10, 11, and 12 (see pages
10.4 - 10.5).
You cannot set the dehumidify setpoint any lower than the humidify setpoint; a
5% differential is forced between the humidify and dehumidify setpoints.
Page 10.3
Page 50
Carrier
Using Your Air Conditioner to Dehumidify Using Your Air Conditioner to Dehumidify
If Cool to Dehumidify is on and the Humidity Module is installed,
the thermostat has the ability to initiate a cooling cycle for advanced
dehumidification operation. When the thermostat detects the humidity
percentage is above the setpoint for dehumidification, and heating or
cooling is not on, the thermostat will force the compressor to run with
the fan, thus reducing moisture in the air. The green LED will blink
once every eight seconds to indicate this is taking place. This feature
will also allow you to adjust the cooling overshoot of the
°°
0 to 5 (adjustable in step #11). For
°°
set for 3 F and the cooling setpoint is set for 74 F, then as long as the room
temperature reads between 71 F and 74 F this feature will energize the
compressor and fan to dehumidify the air.
MODE
PROGRAM
MODE
Steps 10 and 11 only appear if the Dehumidification
setpoint is not 99% (see page 10.3).
Step 11 appears only if step 10 is set to “ON”
Press the PROGRAM button to leave the Setup screens. If no buttons are
Dehumidification Notes: The thermostat must be in the Cool, Auto, or
Program On mode for the Cool to Dehumidify feature to be available.
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
On
Select Cool to
Dehumidify feature.
Off
Adjust the maximum
overshoot of the set
temperature in Cool to
Dehumidify mode.
(0 - 5 )
pressed, the display will leave the setup screens after 30 seconds.
°°
Example: If the cooling overshoot is
Setup
DeHumidify
OFF
Setup
DeHumidify
3
Page 10.4
setpoint, from
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
I0
Press
MODE
I i
COOL
Press
PROGRAM
10
Page 51
Carrier
Using the Reheat FunctionUsing the Reheat Function
This feature allows the thermostat to turn on Electric Heating (W2)
during Cool to Dehumidify to maintain room temperature until the
dehumidification setpoint is reached. The cooling cycle will allow for
the dehumidification of the air to occur while the Electric Heating will
allow for a constant room temperature. If Reheat is enabled the Aux
icon will appear on the display during Cool to Dehumidify operation.
Setup
I2
HEAT
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
MODE
PROGRAM
MODE
10
Step 12 appears only if step 10 is set to “ON” and if the
Dehumidification setpoint is not 99% (see page 10.3).
On
Off
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
If Reheat operation is
desired during the
dehumidification process
select On; otherwise select
Off.
pressed, the display will leave the setup screens after 30 seconds.
OFF
DeHumidify
Dehumidification Notes: Reheat is only available if Cool to
Dehumidify has been set to ON in step #10 (see page 10.4).
Page 10.5
Press
PROGRAM
Page 52
Carrier
Using the Dehum TerminalUsing the Dehum Terminal
If you configure a MISC output jumper for DEHUM, it may be
programmed to operate in one of two ways:
1) Normally Closed (NC): The thermostat will de-energize the
DEHUM terminal to allow the fan to run in low speed when there
is a call for 1st stage cooling and the room humidity is greater than
the dehumidification setpoint.
2) Normally Open (NO): The thermostat will energize the DEHUM
terminal to allow the fan to run in low speed when there is a call
for 1st stage cooling only and the room humidity is greater than
the dehumidification setpoint.
10
MODE
PROGRAM
MODE
Press the PROGRAM button to leave the Setup screens. If no buttons are
Dehumidification Notes: The DEHUM terminal will “release” and allow
the fan to operate normally if there is call for 2nd stage cooling or if the call
for Cooling and/or Cool to Dehumidify has been satisfied.
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
NC
Normally Closed (NC) =
DEHUM deenergized for
low speed fan.
Normally Open (NO) =
DEHUM energized for
NO
low speed fan.
pressed, the display will leave the setup screens after 30 seconds.
DeHumidify
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Viewing the Heat Run-Time - Energy WatchViewing the Heat Run-Time - Energy Watch
This display will track the number of hours that your heating system
has been operating. Press the FAN button to reset the counter.
MODE
PROGRAM
MODE
Press
Energy Watch: This feature enables you to closely monitor your
*
energy usage by keeping track of the number of hours your
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Counts the number of
hours Heat has been
running. Press FAN to
reset the Energy Watch*
FAN
Heat counter.
(0 - 1999 hrs.)
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
0
Setup
I4
HEAT
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
PROGRAM
heating system has been operating.
Page 11.2
11
Press
Page 55
Carrier
Viewing the Cool Run-Time - Energy WatchViewing the Cool Run-Time - Energy Watch
This display will track the number of hours that your cooling system
has been operating. Press the FAN button to reset the counter.
MODE
PROGRAM
MODE
Press
11
FAN
Press the PROGRAM button to leave the Setup screens. If no buttons are
Energy Watch: This feature enables you to closely monitor your
*
energy usage by keeping track of the number of hours your
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Counts the number of
hours Cool has been
running. Press FAN to
reset the Energy Watch*
Cool counter.
(0 - 1999 hrs.)
pressed, the display will leave the setup screens after 30 seconds.
0
Setup
I5
COOL
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
PROGRAM
cooling system has been operating.
Page 11.3
Press
Page 56
Carrier
Viewing the Override Operation Run-TimeViewing the Override Operation Run-Time
This display will track the number of hours that your thermostat has
been operating in the Override mode (see page 6.6). Press the FAN
button to reset the counter.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Press
Counts the number of
hours Override has
been active. Press FAN
to reset the Override Run-
FAN
Time counter.
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
0
Override
Setup
I6
Page 11.4
11
Press
PROGRAM
Page 57
Carrier
Viewing the Humidification Run-TimeViewing the Humidification Run-Time
After your humidification system has been operating for the number of
days set in step #17 below, the Service Humidify icon will appear. This
counter keeps track of the number of days since the Service Humidify
icon was reset.
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Counts the number of
days the humidifier has
been running. Press
FAN to reset the
Service Humidify
counter and remove the
FAN
icon from the display.
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Service
0
Humidify
PROGRAM
11
MODE
MODE
Press
Page 11.5
Setup
I7
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Press
PROGRAM
Page 58
Carrier
Viewing the UV Light Run-TimeViewing the UV Light Run-Time
After the UV light has been operating for the number of days set in
step #18 below, the Service UV Light icon will appear. This counter
keeps track of the number of days since the UV light icon was last
reset.
MODE
PROGRAM
MODE
Press
FAN
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Setup
Counts the number of days
since the UV Light was last
reset. Press FAN to reset
the Service UV Light counter
and remove the icon from the
display.
pressed, the display will leave the setup screens after 30 seconds.
Service
UV Light
0
Page 11.6
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
I8
Press
PROGRAM
11
Page 59
SECTION 12
Electric Heat and Heat Pump OperationElectric Heat and Heat Pump Operation
Section 12 Contents:
Viewing the Heat Pump and
Reversing Valve Jumper
Setting.....................................12.2
Viewing the Electric Heat
Jumper Setting.......................12.3
12
Using Emergency Heat............12.4
Carrier
Page 12.1
Page 60
Carrier
Viewing the Heat Pump and
Viewing the Heat Pump and
Reversing Valve Jumper Settings
Reversing Valve Jumper Settings
Steps 19 and 20 are ‘Read Only’ and may only be set with the
jumpers on the circuit board of the thermostat.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Setup
ON = Heat Pump
operation
OFF = Gas Electric
operation
Indicates that the
thermostat jumper
is set for an O
reversing valve
(energize in cooling)
or a b reversing valve
(energize in heating).
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
OFF
Setup
O
Page 12.2
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
I9
20
PROGRAM
12
Press
MODE
Press
Page 61
Carrier
Viewing the Electric Heat Jumper SettingViewing the Electric Heat Jumper Setting
Placing the jumper on ELEC will cause the thermostat to turn on the
fan immediately any time there is a heat demand. Since most gas
furnaces control the fan, this feature should be off unless it is
necessary for the thermostat to energize the fan with first stage heat.
Step 21 is ‘Read Only’ and may only be set with the jumpers on the
circuit board of the thermostat.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
12
ON indicates that the
thermostat jumper is
set for Electric Heat
operation, or OFF for
Gas/Electric or Heat
Pump operation.
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
OFF
EH
Setup
Page 12.3
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
2 i
PROGRAM
Press
Page 62
Carrier
Using Emergency HeatUsing Emergency Heat
ENTER EMERGENCY HEAT: Only available if you have a Heat Pump
installed. To initiate the Emergency Heat feature, press the FAN
button. While holding the FAN button press UP button. The
Cool setpoint display will read ‘EH’ (emergency heat).
Pm
I2:00
Press for
Emergency Heat
FAN
Su
73
the
HEAT
74
OPERATION: During Emergency Heat operation the
thermostat will turn on the fan and the 2nd stage of heat
when there is a demand for heat. Also during Emergency
Heat the 1st stage of heating or cooling will be unavailable.
EXIT EMERGENCY HEAT: Follow the same steps as entering
Emergency Heat by pressing the FAN and UP buttons. During
Emergency Heat, only OFF and HEAT modes are available by
pressing the MODE button.
Page 12.4
12
Page 63
SECTION 13
Timers and DeadbandsTimers and Deadbands
Section 13 Contents:
Adjusting the Heat/Cool
Differential..............................13.2
Adjusting the Cycles
Per Hour..................................13.3
Adjusting the Deadband..........13.4
Adjusting the Minutes of
13
Run-Time Before the
Next Stage...............................13.6
Selecting 2nd Stage Turn
Off Temperature.....................13.7
Carrier
Page 13.1
Page 64
Carrier
Adjusting the Heat/Cool DifferentialAdjusting the Heat/Cool Differential
The Heat and Cool setpoints will not be allowed to come any closer to
each other than the value in this step. This minimum difference is
enforced during Auto-Changeover operation.
MODE
PROGRAM
MODE
Press the PROGRAM button to leave the Setup screens. If no buttons
are pressed, the display will leave the setup screens after 30 seconds.
Note: To increase the spread between the heating and cooling
setpoints, press the MODE button until only the heat setpoint is
displayed. Adjust the desired setpoint. Wait two seconds after
adjusting the set point so the thermostat can accept the change.
Press the MODE button until only the cool setpoint is displayed.
Adjust the desired setpoint.
set point so the thermostat can accept the change.
MODE button again to enter the Auto-Changeover mode where
both the heat and cool setpoints are displayed.
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Adjust the minimum
difference between
cooling & heating
setpoints.
(0 - 6 )
Wait two seconds after adjusting the
Page 13.2
Setup
2
22
COOL
HEAT
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Press
PROGRAM
13
Press the
Page 65
Carrier
Adjusting the Cycles Per HourAdjusting the Cycles Per Hour
The Cycles Per Hour setting limits the number of times per hour
your HVAC unit may energize. For example, at a setting of 6 cycles
per hour the HVAC unit will only be allowed to energize once every 10
minutes. The Cycles Per Hour limit may be overridden and reset by
pressing the UP or DOWN buttons on the thermostat.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Select the cycles per
hour limit.
d=cycles per hour
limit defeated.
13
Press the PROGRAM button to leave the Setup screens. If no buttons are
d1=d + defeat 5 min.
compressor lockout.
(d1, d, 2 - 6)
pressed, the display will leave the setup screens after 30 seconds.
6
Page 13.3
Setup
23
Cy
Press
PROGRAM
Page 66
Carrier
Adjusting the DeadbandAdjusting the Deadband
MULTI-STAGE OPERATION - Controls up to three Heat and two Cool
stages.
The 2nd Stage of heat or cool is
(A) The 1st Stage has been on for the time required (step #27, page 13.6). It is adjustable from 0-60 minutes and the default
is two minutes.
And
(B) The temperature spread
than: the setpoint
plus the 1st stage deadband (step #24, next
page), plus the 2nd stage deadband (step #25, next page).
This 2nd stage deadband is adjustable from 0-10 degrees and
the default is two degrees.
The 3rd Stage of Heat is turned on when:
(A) The 2nd stage has been on for the time required (step #28,
page 13.6). It is adjustable from 0-60 minutes and the default
is two minutes.
And
(B) The temperature from the setpoint is equal to or greater
than: the setpoint plus the 1st stage deadband (step #24, next
page), plus the 2nd stage deadband (step #25, next page)
plus the 3rd stage deadband (step #26, next page). This 3rd
stage deadband is adjustable from 0-10 degrees and the
default is two degrees.
Heating
DeadbandDeadbandDeadbandDeadbandDeadband
3rd Stage
turn on
2nd Stage
turn on
1st Stage
turn on
DECREASEINCREASE
The above figure assumes the minimum on time for the prior stage has
been met to allow the next stage to turn on, once the deadbands have
been exceeded.
For more detailed information, please see the explanation on the
previous page.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Adjust the deadband
for the 1st stage.
(1 - 6 )
2
13
Adjust the deadband
for the 2nd stage.
(0 - 10 )
Adjust the deadband
for the 3rd stage.
(0 - 10 )
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 13.5
2
2
Setup
Setup
Setup
24
Press
MODE
25
Press
MODE
26
Press
PROGRAM
Page 68
Carrier
Adjusting the Minutes of Run-Time
Adjusting the Minutes of Run-Time
Before the Next Stage
Before the Next Stage
For more detailed information, please see the explanation on page 13.4.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Adjust the amount of
time stage 1 must be
on before stage 2 turns
on.
(0 - 60 min.)
0:02
Adjust the amount of
time stage 2 must be
on before stage 3 turns
on.
(0 - 60 min.)
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
0:02
Setup
27
2
Setup
28
3
Page 13.6
Press
MODE
13
Press
PROGRAM
Page 69
Carrier
Selecting 2nd Stage Turn
Selecting 2nd Stage Turn
Off Temperature
Off Temperature
If ON is selected, the second stage of cooling or heating will remain
energized until the thermostat reaches the setpoint on the thermostat
display.
If OFF is selected, the second stage of cooling or heating will turn off
after reaching the 1st stage (see page 13.4 for more
deadband
information).
MODE
PROGRAM
MODE
13
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
On
Select On or Off:
On - 2nd stage will
remain on until
setpoint is reached.
Off - 2nd stage will
turn off after reaching
Off
1st stage deadband.
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
OFF
2
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Setup
29
PROGRAM
Page 13.7
Press
Page 70
SECTION 14
Using the Programmable OutputUsing the Programmable Output
Section 14 Contents:
Configuring a Thermostat Output
Jumper for Programmable
Output Operation...................14.2
Time-Based Control of the
Programmable Output...........14.3
Temperature-Based Control of
the Programmable Output.....14.6
Carrier
14
Page 14.1
Page 71
Carrier
Setting a Thermostat Jumper for
Setting a Thermostat Jumper for
Programmable Output Operation
Programmable Output Operation
To control one of the MISC outputs using time, temperature, or
Internet/phone based operation, place the MISC1, or MISC2, or
MISC3 jumper on the terminal labeled PROG (see diagram below).
This extra output will supply 24VAC to the selected MISC terminal
based on the programming described in the following pages. Only
one of the three outputs (MISC1, MISC2, or MISC3) is required to
have this jumper. For more information regarding the MISC1, MISC2,
and MISC3 outputs, please see section 21.
In the diagram below, the MISC1 jumper has
been set for PROG operation.
(FAN)
14
DEHUM
CKGND
W3
PROG
HUM
ECON
MISC2
CK1
MISC3MISC2 MISC1
W1
Y1
G
R
C
ELEC
GAS
HP
2
4
INSTALLHUMIDITY
ELEMENTOUTWARD
1
3
GAS
B
O
W2
MISC1
HUM
NO HUM
Rs2
MISC3
RS+5
Z
8
6
X
Rs1
1
RSGND
Y
579
Y2
(MISC1
ONLY)
MODULEWITHSENSING
W3
PROG
HUM
DEHUM
ECON
MISC3MISC2 MISC1
IMPORTANT CAUTION
NEVER PUT MORE THAN ONE JUMPER
ON THE SAME MISC JUMPER BLOCK!
THIS MAY DAMAGE THE THERMOSTAT
MISC3
OK
MISC3
AND VOID YOUR WARRANTY
Y2
(MISC1
ONLY)
Page 14.2
Page 72
Carrier
Time-Based Control of the
Time-Based Control of the
Programmable Output
Programmable Output
To operate one of the MISC outputs using time-based operation, set
Advanced Setup step #30 (below) for Time i8:88. This extra output
will supply 24VAC to the selected MISC terminal, which is especially
useful for devices that require a start and stop time. Refer to page
14.4 - 14.5 for more details on programming this output.
Possible TIME scenarios:
1) An exterior lighting system that needs to be energized every
day between the hours of 8pm and 1am.
2) A sprinkler system that needs to be energized every day
between the hours of 2am and 4am.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
14
OFF Time = Temp = Aux
I8:88
Press the UP button to
set the programmable
output for time based
operation. The digits in the
clock area will appear.
88
I8:88
Page 14.3
Setup
30
Continued on
the next page
Press
MODE
Page 73
Time-Based Control of the
Time-Based Control of the
Programmable Output
Programmable Output
Programmable Output Polarity:
NC
NC = Normally Closed to turn off
between the start and stop times
in steps 34 and 35.
NO = Normally Open to operate
between the start and stop times
in steps 34 and 35.
NO
Carrier
Setup
3 i
Press
MODE
7-Day
Select 7-Day or 1-Day
Programming:
7-Day = Different program
for each day.
1-Day = Same program
1-Day
every day.
If Step 32 is set for 1-Day, then Day of the
Week and Copy functions do not appear or apply.
14
Select the day of
the week
Adjust the programmable output start time
for Monday.
(24 Hours)
Day
Mo
7:00
Mo
Am
Page 14.4
Start
7
Setup
Setup
Setup
32
33
34
Continued on
the next page
Press
MODE
Press
MODE
Press
MODE
Page 74
Time-Based Control of the
Time-Based Control of the
Programmable Output
Programmable Output
Carrier
Stop
Setup
35
Pm
9:00
Adjust the programmable
output stop time for Monday
If Step 32 is set for 1-Day, then Day of the
Week and Copy functions do not appear or apply.
Yes
Select Yes to copy the
previous day’s program
to this day.
No
If Yes is selected:
Press
FAN
If No is selected, as in previous steps, flashing prompts for input will appear for
the start and stop times for the next day.
Once configuration of the programmable output has been
Press
MODE
completed, press the MODE button to move on to the next
setup step, or press the PROGRAM button to exit Advanced
Setup.
Mo
Tu
Selecting Yes, then pressing FAN will copy the
previous day’s program. If yes is selected each
time, this routine will repeat.
Page 14.5
Press
MODE
If No is selected:
14
Page 75
Carrier
Temperature-Based Control of the
Temperature-Based Control of the
Programmable Output
Programmable Output
To operate a MISC output using temperature-based operation,
program advanced setup step #30 (below) for temperature 88 .
his extra output will supply 24VAC to the selected MISC terminal
T
based on the temperature of RS1 and the setpoint in step #36 (below).
Possible TEMPERATURE scenario:
1) An exhaust fan in the attic of a store that needs to be energ ized when the attic temperature is above 85 degrees.
MODE
PROGRAM
MODE
OFF Time = Temp = Aux
14
NC
NO
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
I8:88
Press the UP button twice
to set the programmable
output for temperaturebased operation. The
large temperature digits
will appear.
Programmable Output Polarity:
NC = Normally Closed to operate
when the setpoint is less than
the setpoint in step #36.
NO = Normally Open to operate
when the setpoint is equal to or
greater than the setpoint in step
#36.
Adjust the programmable
output setpoint.
o
(35-125 )
pressed, the display will leave the setup screens after 30 seconds.
88
88
o
80
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Setup
30
Setup
3 i
Setup
36
Press
MODE
Press
MODE
Press
PROGRAM
Page 14.6
Page 76
Carrier
Internet/Phone Control of the
Internet/Phone Control of the
Programmable Output
Programmable Output
To operate a MISC output using Internet/phone-based operation,
program advanced setup step #30 for Aux . (below) This terminal is
especially useful for devices that can be energized via the Internet.
Telephone control may also be available when the thermostat is
connected to the Internet.
Possible REMOTE scenarios:
1) Arm the alarm system in your building after you have left for
the day.
2) Turn off your sign lights after arriving home.
3) Turn on your interior lights while you’re closed.
MODE
PROGRAM
MODE
OFF Time = Temp = Aux
NC
NO
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
I8:88
Press the UP button three
times to set the
programmable output
for Aux (web-based
operation).
Programmable Output Polarity:
NC = Normally Closed to operate
when programmed to be OFF
through the phone or internet.
NO = Normally Open to operate
when programmed to be ON
through the phone or internet.
pressed, the display will leave the setup screens after 30 seconds.
88
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Controlling or Reading the
Remote Temperature (RS1)...15.3
Averaging the Remote Sensor
(RS1) with the Thermostat
Sensor.....................................15.4
15
Carrier
Page 15.1
Page 78
Carrier
Installing the Remote SensorsInstalling the Remote Sensors
Up to eight wired or wireless remote sensors may be installed on the
thermostat (RS1) to control the temperature in other rooms. If more
than one sensor is connected to (RS1) the thermostat will average the
sensors to determine the displayed temperature reading. One wired or
wireless remote sensor may be installed to read the outside temperature (RS2). If a sensor(s) is connected to RS1 and is programmed
to control the thermostat, the degree icon on the thermostat will blink
once per second to indicate that a remote sensor reading is being displayed. The wired sensor can be connected to the thermostat with up
to 150’ of 18 ga., 300’ of 20 ga., or 450’ of 22 ga. unshielded, thermostat wire. If multiple sensors are wired to the thermostat, then the
total wiring distance of the furthest sensor should be used in determining the appropriate wire gauge. The wired sensor can be connected to
the thermostat using a two or three wire installation. If a two wire installation is required, then RS+5 must be connected to RSGND (see below).
This wire MUST be completely separated from the thermostat
or any other control wiring and must NOT be in the same
conduit as high voltage wiring.
RS-GND
RS
RS2
RS+5
W2
MISC1
RS2
MISC3
RS+5
RS1
RSGND
W1/O/B
MISC2
CKGND
Y1
G
CK1
R
C
15
RS-GND
RS+5
RS1-1
See the Remote Sensor accessory for further details.
RS-GND
RS
RS-GND
RS
RS+5
RS-GND
RS
RS+5
RS
RS+5
RS1-4RS1-3RS1-2
Page 15.2
Page 79
Carrier
Controlling or Reading the
Controlling or Reading the
Remote Temperature (RS1)
Remote Temperature (RS )1
The thermostat may be programmed to only READ the remote sensor,
or to CONTROL to the remote sensor. Refer to advanced setup step
#37, below.
Read Only Sensor (RS1): If step #37 is set to only READ to the
remote sensor, the thermostat will not use this sensor for temp erature control. This sensor may be viewed by entering advanced
setup (see below) and pressing and holding the MODE button to
scroll backwards one step to setup step #48 (see page 22.4).
Control Sensor (RS1): If step #37 is set to CONTROL to the remote
sensor, the thermostat will ignore the reading of its internal
temperature sensor and only display the temperature reading from
the remote sensor. The degree icon on the thermostat will blink
once per second to indicate that a remote sensor reading is being
displayed.
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Optional Remote Sensor:
YES = Control to Remote
Sensor RS1.
NO = Read Only Remote
Sensor RS1.
Setup
37
Remote
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Press
PROGRAM
PROGRAM
15
MODE
MODE
YES
NO
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 15.3
Page 80
Carrier
Averaging the Remote Sensor (RS1) with
Averaging the Remote Sensor (RS1) with
the Thermostat Sensor
the Thermostat Sensor
If step #37 is set to control to the remote sensor, the thermostat will
ignore the reading of its internal temperature sensor and only display
the temperature reading from the remote sensor. The degree icon on
the thermostat will blink once per second to indicate that a remote
sensor reading is being displayed.
If step #38 is set to ON (see below), the thermostat will average its
internal sensor with the wired temperature sensor connected to RS1.
f multiple remote temperature sensors are installed on RS1, they will
I
automatically average together.
The temperature displayed will be the
average of the thermostat’s internal sensor and the remote (RS1)
sensor(s).
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
15
Optional Remote Sensor
On
Operation:
ON = Averages thermostat
sensor with Remote
Sensor 1.
OFF = Does not average
thermostat sensor
Off
with Remote Sensor 1.
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
OFF
Setup
38
Remote
Press
PROGRAM
Page 15.4
Page 81
SECTION 16
Programming the Dry ContactProgramming the Dry Contact
Section 16 Contents:
Dry Contact Operation............ 16.2
Dry Contact Polarity.................16.2
Dry Contact Programming.......16.3
Random Start Operation..........16.4
16
Carrier
Page 16.1
Page 82
Carrier
Dry Contact Operation Dry Contact Operation
If the dry contact is going to be used, select YES in step #39. If the
dry contact is not going to be used, select NO in step #39 below.
DRY CONTACT POLARITY - The terminals may be set to be
Normally Open (NO) or Normally Closed (NC) in step #40.
If NO is selected the dry contact will operate when it is forced
closed. If NC is selected, the dry contact will operate until it is
forced open.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
YES
Set to YES if the dry
contact will be used.
Set to NO if the dry
contact will not be used.
NO
Step 40 appears only if step 39 is “YES”.
NC
Dry Contact Polarity:
Normally Closed (NC)
Normally Open (NO)
NO
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Setup
Setup
Page 16.2
39
Press
MODE
16
40
Press
PROGRAM
Page 83
Carrier
Dry Contact ProgrammingDry Contact Programming
OCCUPIED 1 OR SERVICE THE CONDENSATE DRAIN PAN - If
Occupied 1 is selected in step #41 (below), when the dry contact is
energized the thermostat will be forced into Occupied 1 setpoints
and the Occupied 1 icon will blink (Section 6). The thermostat must
be in Program On mode for this feature to have any effect.
If Service Pan is selected, when the dry contact is energized the
thermostat will lockout Y1 (compressor) and write Service Pan on
the display.
MODE
PROGRAM
MODE
Step 41 appears only if step 39 is “YES”.
Service Pan
Occupied 1
Press the PROGRAM button to leave the Setup screens. If no buttons are
NOTE: If Service Pan is selected and the dry contact was closed at least once, the
16
Service Pan icon will remain on the display to alert the user that a problem has
occurred. This icon will be cleared once a button is pressed.
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Select Service Pan to lockout
Y1 when the dry contact is
energized. Select Occupied 1
to enable Occupied 1 setpoints
when the dry contact is
energized.
occupied
1
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Setup
4 i
pressed, the display will leave the setup screens after 30 seconds.
Occupied 1Service Pan
Press
PROGRAM
W2
W1/O/B
MISC1
RS2
MISC3
RS+5
RS1
RSGND
Connect wires to a time
clock or other device to
force the thermostat into
Occupied 1.
MISC2
CKGND
Y1
G
CK1
R
C
OR
Page 16.3
W2
MISC1
RS2
MISC3
RS+5
RS1
RSGND
Connect wires to a device that
will complete the circuit between CK1 and CKGND when the
Condensate Drain Pan is full.
W1/O/B
MISC2
CKGND
Y1
G
CK1
R
C
Page 84
Carrier
Random Start OperationRandom Start Operation
This feature allows a 2 to 30 second delay before energizing
the thermostat outputs after any of these events:
Loss of Power to the thermostat: When power to the thermostat
is interrupted and then restored, Random Start will lockout the
outputs of the thermostat for a random amount of time. This
delay helps to keep multiple thermostats from energizing their
outputs at the same time after a power outage.
Changing from an Unoccupied time period to an Occupied
time period: If the thermostat is running in the Program On mode
and the start time for an Occupied period forces the thermostat
from Unoccupied to Occupied 1, Random Start will lockout all
outputs of the thermostat for a random amount of time. This
delay helps to keep multiple thermostats from energizing their
outputs at the same time each day.
Closure of the Dry Contact to force Occupied 1 time period:
If step #41 (previous page) is programmed for Occupied 1, then
Random Start will lockout all outputs of the thermostat for a
random amount of time when a Dry Contact closure occurs
(depending on step #40). This delay helps to keep multiple
thermostats from energizing their outputs each time the Dry
Contact is used.
Sensing of a light source by the Light Sensor to force
Occupied 1 time period:
If step #42 (page 17.2) is programmed YES for Light Activated
operation, Random Start will lockout the outputs of the thermostat
for a random amount of time when a light source forces the
thermostat into Occupied 1. This delay helps to keep multiple
thermostats from energizing their outputs each time the lights are
turned on.
A light sensor is provided on the thermostat for light activation. If the
thermostat is set up to be light activated, the thermostat will enter
Occupied 1 and blink the Occupied 1 icon when a light source is
detected. When the thermostat is set up to be light activated, the time
period programming for each day should be set to OFF (Section 6).
The thermostat must be in Program On mode for light activation to
have any effect. Page 17.3 explains how to adjust the light sensitivity
for this type of operation.
NOTE: Light activation does not work in Holiday mode (Section 21).
MODE
PROGRAM
MODE
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
YES
Select YES if the
thermostat should be
Light Activated.
Select NO to allow only
Time Period Programming
(Section 6).
NO
pressed, the display will leave the setup screens after 30 seconds.
The Light Sensor is located on
the top of the thermostat.
Setup
33CS450-01
Light Sensor
Page 17.2
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
42
Press
PROGRAM
17
Page 87
Carrier
Adjusting the Light Sensor Adjusting the Light Sensor
The light sensor can be adjusted for variable degrees of sensitivity.
The sensitivity adjustment screw is located on the side of the
thermostat, as illustrated below. Turning the screw clockwise
increases the sensitivity of the sensor to light.
To check for correct sensitivity, place the thermostat in the Program On
mode. When the lights are on the thermostat should enter Occupied 1
and blink the Occupied 1 icon. If the thermostat does not enter
Occupied 1 while the lights are on, use the supplied screw driver to
turn the light sensor screw clockwise until the Occupied 1 icon appears
on the display. The thermostat should enter an unoccupied period
when the lights are off. If the sensor does not enter an unoccupied
period when the lights are turned off, use the supplied screw driver to
turn the light sensor screw counterclockwise until the Unoccupied icon
appears on the display, with the lights off.
The Light Sensor Adjustment Screw
is located on the side of the thermostat.
Light Sensor
Adjustment Screw
17
Turn the screw clockwise
to INCREASE light sensor
sensitivity
Turn the screw counterclockwise to DECREASE
light sensor sensitivity
Due to varying lighting conditions, light activation may
not be suitable for all installations.
Page 17.3
Page 88
SECTION 18
Energy Save OperationEnergy Save Operation
Carrier
How to Use the Energy Save FeatureHow to Use the Energy Save Feature
If the thermostat is configured to be programmable (Section 4), and
Energy Save has been selected in step #43 (below), the room will
attempt to reach the selected comfort temperature at the exact time
programmed into the thermostat. Energy Save, or more commonly
known as Smart Recovery, only works when the thermostat enters
Occupied 1 from Unoccupied. For example, if the Unoccupied
program is set for 6pm at 55°F heating and 85°F cooling, and the
Occupied 1 program is set for 8am at 72°F heating and 75°F cooling,
the thermostat will turn the system on before 8am in an effort to bring
the temperature to its correct setting at exactly 8am.
The P374-2900 learns from experience, so please allow 4-8 days
after a program change or after initial installation to give Energy Save
time to adjust to local weather, the construction of your business, and
your heating and cooling system.
MODE
PROGRAM
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
On
Select Energy Save
on or off.
Off
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
This counter keeps track of the number of hours of fan run-time
whether the fan is energized in the Heating or Cooling modes, or in
stand alone fan operation. The Service Filter icon will appear after the
preset number of hours of fan run-time in step #45 (below) has been
achieved. Setting this counter to zero in step #45 will prevent the
Service Filter icon from ever appearing.
MODE
PROGRAM
MODE
Press
FAN
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Hours the fan has
run since last reset
Reset the counter to 0 to
remove the Service Filter
icon from the display.
Adjust the number of
hours, in increments of
50, the fan will run
before the Service
Filter icon appears on
the display. 0 = off.
(0 - 1950 hours)
pressed, the display will leave the setup screens after 30 seconds.
0
Service Filter
0
Service Filter
Setup
Setup
Page 19.2
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
44
45
PROGRAM
Press
MODE
Press
19
Page 91
Carrier
How to Set and Reset the UV Light
How to Set and Reset the UV Light
Run-Time Alert
Run-Time Alert
This counter keeps track of the number of days since the UV Light
counter has been reset. The UV Light icon will appear after the
number of days has been achieved, as shown in step #46 (below).
Setting the counter to zero in Step #46 will prevent the Service UV
Light icon from ever appearing.
MODE
PROGRAM
MODE
Press
FAN
MODE
19
Press the PROGRAM button to leave the Setup screens. If no buttons are
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Days since the UV Light
icon has been reset
Reset the counter to 0 to
remove the Service UV
Light icon from the display.
Press the MODE button repeatedly
until this setup screen appears.
Adjust the number of days
in increments of 10 before
the UV Light icon appears
on the display. 0 = off.
(0 - 1990 days)
pressed, the display will leave the setup screens after 30 seconds.
Service
Service
0
UV Light
0
UV Light
Page 19.3
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Setup
I8
Setup
46
Press
PROGRAM
Page 92
Carrier
How to Set and Reset the Humidifier
How to Set and Reset the Humidifier
Run-Time Alert
Run-Time Alert
This counter keeps track of the number of days since the Service
Humidify icon was last reset; this icon will appear after the number of
days set in step #47 (below) has elapsed. Setting this counter to zero
in step #47 will prevent the Service Humidify icon from ever appearing.
MODE
PROGRAM
MODE
Press
FAN
MODE
Press the MODE button. While holding
the MODE, press the PROGRAM
button to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
Days since the last reset
of the Service Humidify
counter.
Reset the counter to 0 to
remove the Service Humidify
icon from the display.
Press the MODE button repeatedly
until this setup screen appears.
Service
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move backwards through the
setup screens.
Humidify
Setup
I7
0
Adjust the number of days
in increments of 10 before
the Service Humidify icon
appears.
0 = Off
(0 - 1990 days)
Press the PROGRAM button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Service
0
Humidify
Setup
47
The humidifier run-time alert does not take the place of
any humidifier manufacturer’s recommended maintenance
plan; it only serves as a helpful reminder.
Page 19.4
PROGRAM
Press
19
Page 93
SECTION 20
Programming Holiday ModeProgramming Holiday Mode
When the thermostat is programmed for a Holiday mode, it will take
effect at 12:00 am of the next day. In order for the Holiday mode to
take effect the thermostat must be in the Program On mode.
The thermostat will control to the Unoccupied cooling and heating
setpoints set in Section 6, pages 6.2 and 6.3.
Holiday setpoints will be enforced for the number of days specified in
step #1 (0 - 99 days).
Press
HOLIDAY
Press the HOLIDAY button to enter
the Holiday programming setup
steps.
Carrier
Select the number of days
that the Holiday schedule
will be in effect. A value
of 0 disables Holiday
mode.
(0 - 99 days)
Press the HOLIDAY button to exit the setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
0
Setup
I
y
HOLIDAY
20
You cannot set the Heat setpoint any higher than the Cool setpoint minus
the deadband setting in Advanced Setup step #22 on page 13.2.
HOLIDAY DISPLAY - When the thermostat is placed into the
Holiday mode, the thermostat will display the screen shown below.
2
To return the thermostat to normal operation from Holiday mode, press
the HOLIDAY button and adjust the number of days in step #1 to zero
(see previous page).
Press the HOLIDAY button to return to normal operation.
y
Overriding the Holiday ModeOverriding the Holiday Mode
Pressing the OVERRIDE
button during Holiday Mode
will temporarily force the
thermostat into Occupied 1
comfort settings for 30 min.
The remaining Override time
will alternate with the clock
display.
The Override timer can be
set up to a maximum of four
(4:00) hours, in increments
of 30 minutes. If the timer
has been set for the maximum time, the next press of
the OVERRIDE button will
reset the timer, returning the
thermostat to the correct time
period program for the day.
Page 20.2
:
30
We
occupied
1
Override
2
Pm
7:56
Program On
65
y
74
COOL
HEAT
72
Press
OVERRIDE
20
Page 95
SECTION 21
Configuring the MISC OutputsConfiguring the MISC Outputs
Section 21 Contents:
Configuring the Jumpers........21.2
Explanation of Jumper
Settings..................................21.3
Carrier
21
Page 21.1
Page 96
Carrier
Configuring the JumpersConfiguring the Jumpers
For additional flexibility, your thermostat has three configurable
outputs. These outputs are designed to have different functions
depending on how the jumpers are set (below).
Each output, labeled MISC1, MISC2, and MISC3 may be set for one
of the five choices available.
In the diagram below, the MISC3 jumper has been set for HUM*
(humidification) operation, the MISC2 jumper has been set for
DEHUM* (dehumidification) operation, and the MISC1 jumper has
been set for PROG (programmable) operation.
(FAN)
ELEC
GAS
HP
GAS
B
O
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
Z
2
8
4
6
X
Rs1
1
RSGND
1
Y
3
579
DEHUM
CKGND
PROG
ECON
MISC2
W3
HUM
W1
Y1
G
CK1
R
C
MISC3 MISC2 MISC1
Y2
(MISC1
ONLY)
INSTALLHUMIDITY
MODULEWITHSENSING
ELEMENTOUTWARD
CAUTION
NEVER PUT MORE THAN
ONE JUMPER ON THE SAME
MISC JUMPER BLOCK!
DOING SO MAY DAMAGE
YOUR THERMOSTAT.
Page 21.2
W3
PROG
HUM
DEHUM
ECON
MISC3 MISC2 MISC1
*The Humidity Module (sold separately) must
be installed to operate a humidification
and/or dehumidification system.
MISC3
MISC3
(MISC1
OK
Y2
ONLY)
21
Page 97
Carrier
Explanation of Jumper SettingsExplanation of Jumper Settings
W3 JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to W3, the corresponding MISC screw terminal
on the backplate will control a third stage of heat.
W3 MULTI-STAGE OPERATION EXPLAINED - PAGE 13.4
The 3rd Stage of Heat is turned on when:
(A) The 1st and 2nd stages have been on for the time required (steps 27
and 28, page 13.6). It is adjustable from 0-60 minutes and the default
And
is two minutes.
(B) The temperature from the setpoint is equal to or greater than: the set-
point plus the 1st stage deadband (step #24, 13.5), plus the 2nd stage
deadband (step #25, 13.5) plus the 3rd stage deadband (step #26,
13.5). This 3rd stage deadband is adjustable from 0-10 degrees and
the default is two degrees.
3rd Stage
turn on
PROG JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to PROG, the corresponding MISC screw
terminal on the backplate will control a pilot relay or other accessory.
This jumper setting allows the MISC outputs to control a pilot relay by time,
temperature, or a signal from the Internet/Phone. The following are three
possible scenarios:
By Time: A device that requires a start and stop time. For example,
an exterior lighting system that needed to be energized every day
21
between the hours of 8pm and 1am.
By Temperature: An exhaust fan that needs to energize whenever
the temperature from RS1 rises above 90 degrees F.
By Remote: Remotely arming a security system through the web or phone.
Page 21.3
Cooling
1st Stage
turn on
2nd Stage
turn on
Page 98
Carrier
Explanation of Jumper Settings (continued)Explanation of Jumper Settings (continued)
HUM JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to HUM, the corresponding MISC screw
terminal on the backplate will control a humidification system.
HUMIDIFICATION OPERATION - SECTION 9
If your HVAC unit is equipped with a humidification system and the Humidity
Module (sold separately) has been installed, the thermostat will provide power
to the MISC1, MISC2, or MISC3 terminal of the thermostat when the humidity in
the home falls below the humidity setpoint you have chosen. The value for this
setpoint ranges from 0% to 60%. If no humidity is desired or if a humidification
system has not been installed, set the value to 0%.
DEHUM JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to DEHUM, the corresponding MISC screw
terminal on the backplate will be connected to the dehumidification terminal of a furnace board.
NOTE: Not all furnaces have a dehumidification terminal.
DEHUMIDIFICATION OPERATION - SECTION 10
If your HVAC unit is equipped with a dehumidification system the thermostat will
operate in one of two ways.
1) Normally Closed (NC): The thermostat will de-energize the MISC1, MISC2,
or MISC3 terminal of the thermostat (this MISC terminal is connected to the
DEHUM terminal on your furnace) to allow the fan to run in low speed when
the humidity in the building is above the dehumidify setpoint you have
chosen and there is a call for 1st stage cooling.
2) Normally Open (NO):
MISC3 terminal of the thermostat (this MISC terminal is connected to the
DEHUM terminal on your furnace) to allow the fan to run in low speed when
the humidity in the building is above the dehumidify setpoint you have
chosen and there is a call for 1st stage cooling.
The thermostat will energize the MISC1, MISC2, or
21
Page 21.4
Page 99
Carrier
Explanation of Jumper Settings (continued)Explanation of Jumper Settings (continued)
ECON JUMPER SETTING
If the jumper for MISC2 or MISC3 is set to ECON, the corresponding MISC screw
terminal on the backplate will be connected to an economizer.
ECONOMIZER OPERATION - If your HVAC unit is equipped with an
economizer system, the thermostat will provide power to the MISC2 or
MISC3 terminal of the thermostat when the thermostat is in an occupied
time period. The MISC2 or MISC3 terminal will be de-energized when the
thermostat is in an unoccupied time period.
Y2 JUMPER SETTING
If the jumper for MISC1 is set to Y2 the MISC1 screw terminal on the backplate will control a
second stage of cooling.
Y2 OPERATION - SECTION 13
Control up to two Cool stages.
The 2nd Stage of cool is turned on when:
(A) The 1st Stage has been on for the time required (step #27, page 13.6). It is adjustable from 0-60 minutes and the default
is two minutes.
And
(B) The temperature spread from the setpoint is equal to or greater
than: the setpoint plus the deadband (step #24, page 13.5), plus the 2nd deadband (step #25, page 13.5). This 2nd deadband is
adjustable from 0-10 degrees and the default is two degrees.
21
Cool
Setpoint
TEMPERATURE
Cooling
DeadbandDeadband
db 1db 2
(adj. 0-10 )(adj. 1-6 )
1st Stage
INCREASE
turn on
2nd Stage
turn on
Page 21.5
Page 100
SECTION 22
Factory Defaults, Calibration, and SensorsFactory Defaults, Calibration, and Sensors
Section 22 Contents:
Resetting the Thermostat to the
Factory Default Settings........22.2
Calibrating the Temperature
and Humidity Sensors...........22.3
Viewing the Remote
Temperature Sensors............22.4
Carrier
Page 22.1
22
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.