Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifications. When
operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury
to personnel.
Be sure you understand and follow the procedures and safety
precautions contained in the chiller instructions as well as
those listed in this guide.
DANGER
Failure to follow these procedures will result in severe personal injury or death.
DO NOT VENT refrigerant relief valves within a building.
Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/
ASHRAE 15 (American National Standards Institute/
American Society of Heating, Refrigerating, and AirConditioning Engineers). The accumulation of refrigerant
in an enclosed space can displace oxygen and cause
asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/
ASHRAE 15, especially for enclosed and low overhead
spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or
death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products
are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a
chiller for any purpose. Oxygen gas reacts violently with
oil, grease, and other common substances.
NEVER EXCEED specified test pressures; VERIFY the allowable test pressure by checking the instruction literature
and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or
dry nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly in-
stalled and functioning before operating any chiller.
RISK OF INJURY OR DEATH by electrocution. High
voltage can be present on motor leads even though the motor is not running. Open the power supply disconnect before touching motor leads or terminals.
WARNING
Failure to follow these procedures may result in personal
injury or death.
DO NOT USE TORCH to remove any component. System
contains refrigerant which may be under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover or isolate refrigerant from system using high-
pressure and low pressure ports as appropriate. Note that
R-1233zd(E) will be less than atmospheric pressure
until a temperature of about 65°F (18.5°C).
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit.
e. Carefully unsweat remaining tubing stubs when necessary.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the entire assembly.
DO NOT work on high-voltage equipment unless you are a
qualified electrician.
DO NOT WORK ON electrical components, including
control panels, switches, or starters, until you are sure ALL
POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.
(Warnings continued on next page.)
2
Page 3
WARNING
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are de-energized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it
into the eyes. USE SAFETY GOGGLES. Wash any spills
from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water
and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous overpressure can result. When it is
necessary to heat refrigerant, use only warm (110°F [43°C])
water.
VERIFY that refrigerant storage cylinders are clean with no
residual moisture, oil, or refrigerant that can contaminate
the refrigerant charge.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas
pressure, loosen the collar, and unscrew and discard the
valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introduction of the wrong refrigerant can cause damage or malfunction to this chiller.
Operation of this equipment with refrigerants other than
those cited herein should comply with ANSI/ASHRAE 15
(latest edition). Contact Carrier for further information on
use of this chiller with other refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc.,
while chiller is refrigerant charged or at any time while
chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection. Note that chiller
will be in a vacuum condition when temperature is below
normal room temperature.
CAREFULLY INSPECT all rupture discs and other relief
devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION
any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body
or mechanism. Replace the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a com-
pressed spring. Sudden release of the spring can cause it
and objects in its path to act as projectiles.
CAUTION
Failure to follow these procedures may result in personal
injury or damage to equipment.
DO NOT STEP on refrigerant lines. Broken lines can whip
about and release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or
staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to
lift or move inspection covers or other heavy components.
Even if components are light, use mechanical equipment
when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN
ENGAGE THE STARTER, TOWER FAN, OR PUMPS.
Open the disconnect ahead of the starter, tower fans, or
pumps.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids without the permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.
DO NOT LOOSEN a packing gland nut before checking
that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping
for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each
pressure relief device to prevent a build-up of condensate or
rain water.
DO NOT leave refrigerant system open to air any longer than
the actual time required to service the equipment. Seal circuits
being serviced and charge with dry nitrogen to prevent contamination when timely repairs cannot be completed.
INTRODUCTION
Prior to initial start-up of the 19DV unit, those involved in the
start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary job data.
Procedures in this manual are arranged in the sequence required for proper chiller start-up and operation. This book also
outlines the control system for those involved in the start-up,
operation and maintenance of the unit before performing startup procedures. It is intended to be used in combination with the
19DV Semi-Hermetic Centrifugal Liquid Chillers Controls
Operation and Troubleshooting manual that describes the controls in detail.
CAUTION
Do NOT punch holes or drill into the top surface of the control or VFD enclosure for field wiring. Knockouts are provided for field wiring connections. Drilling holes through
the top of the cabinet can result in a loss of warranty on the
starter assembly because of metal particulate falling on and
into electronic components.
CAUTION
PROVIDE MACHINE PROTECTION. Store machine and
starter indoors, protected from construction dirt and moisture. Inspect under shipping tarps, bags, or crates to be sure
water has not collected during transit. Keep protective shipping covers in place until machine is ready for installation.
Follow latest Water-Cooled Chillers Long Term Storage
document located in Chiller Builder Library.
3
Page 4
CAUTION
WHEN FLUSHING THE WATER SYSTEMS isolate the
chiller from the water circuits to prevent damage to the heat
exchanger tubes.
CAUTION
This unit uses a microprocessor control system. Do not
short or jumper between terminations on circuit boards or
modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when
handling or making contact with circuit boards or module
connections. Always touch a chassis (grounded) part to
dissipate body electrostatic charge before working inside
control center or use a grounding strap before handling
printed circuit boards.
Use extreme care when handling tools near boards and when
connecting or disconnecting terminal plugs. Circuit boards can
easily be damaged. Always hold boards by the edges and
avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may cause interference to radio communications. The PIC6 control boards have been tested and found to
comply with the limits for a Class A computing device pursuant to International Standard in North America EN 610002/3 which are designed to provide reasonable protection
against such interference when operated in a commercial environment. Operation of this equipment in a residential area
is likely to cause interference, in which case the user, at his
own expense, will be required to take whatever measures
may be required to correct the interference.
Always store and transport replacement or defective boards
in anti-static shipping bag.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include:
AWG— American Wire Gage
BMS— Building Management System
CCN— Carrier Comfort Network
DCIB— Digital Control Interface Board
DVM— Digital Volt-Ohmmeter
EC— Envelope Control
ECDW — Entering Condenser Water
ECW— Entering Chilled Water
EMS— Energy Management System
HMI— Human Machine Interface
HVIB— High Voltage Interface Board
I/O— Input/Output
IGBT— Insulated-Gate Bipolar Transistor
IGV— Inlet Guide Vane
IOB— Input Output Board
LCDW — Leaving Condenser Water
LCW— Leaving Chilled Water
LED— Light-Emitting Diode
MAWP — Maximum Allowable Working Pressure
NSTV— Network Service Tool V
OLTA— Overload Trip Amps
PIC— Product Integrated Controls
PPE— Protective Personal Equipment
PWM— Pulse Width Modulating
RLA— Rated Load Amps
RMS— Root Mean Square
SCCR— Short Circuit Current Rating
SCR— Silicon Controlled Rectifier
SIOB— Starfire 2 Input Output Board
TXV— Thermostatic Expansion Valve
VFD— Variable Frequency Drive
VPF— Variable Primary Flow
Factory-installed additional components are referred to as options
in this manual; factory-supplied but field-installed additional components are referred to as accessories.
®
CHILLER FAMILIARIZATION (Fig. 1 and 2)
Chiller Information Nameplate
The information nameplate is located on the left side of the
chiller control panel.
System Components
The main components include the evaporator and condenser
heat exchangers in separate vessels, motor-compressor, refrigerant, lubrication package, control panels, PIC6 Touch Screen
HMI, economizer, VFD, and purge system.
Evaporator
This vessel is located underneath the compressor. The evaporator is maintained at a lower temperature/pressure so evaporating refrigerant can remove heat from water flowing through its
internal tubes. Water flows through the internal tubes to provide comfort or process cooling.
Condenser
The condenser operates at a higher temperature/pressure than the
evaporator and has water flowing through its internal tubes in order to remove heat from the refrigerant. It contains a metering device that regulates the flow of refrigerant into the economizer.
Economizer
This chamber reduces the refrigerant pressure to an intermediate
level between the evaporator and condenser vessels. In the economizer, vapor is separated from the liquid, the separated vapor
flows to the second stage of the compressor, and the liquid flows
into the evaporator. The energy removed from the vaporized refrigerant in the economizer allows the liquid refrigerant in the
evaporator to absorb more heat when it evaporates and benefits
the overall cooling efficiency cycle. It contains a float assembly
that regulates the flow of refrigerant into the evaporator.
Motor-Compressor
This component maintains system temperature and pressure
differences and moves the heat-carrying refrigerant from the
evaporator to the condenser. The 19DV utilizes a two-stage
back to back direct drive configuration.
Purge Unit
This is a small independent condensing unit with compressor, separator, regenerative carbon filters, heater and vacuum pump. The
purge extracts gas from condenser (or from compressor if unit is
not in operation) and purifies it by removing non-condensable
gases and any water vapor that may be present.
Variable Frequency Drive (VFD)
The VFD variable frequency is a voltage source design that
converts line voltage into PWM (pulse width modulating) motor input for motor speed and torque control.
Refrigerant Lubrication System
This system provides lubrication to the compressor bearing by
means of a refrigerant pump.
Chiller Control Panel
This control panel includes the input and output boards (IOBs),
control transformer, relays, contactors, and circuit breakers. It provides the power distribution and protection to the electrical components installed on chiller and has the following functions:
• Communication with PIC6 touch screen
• Communication with purge panel
• Communication with VFD
• Sensor input and outputs
• Actuators control
• Refrigerant pump control
4
Page 5
Purge Control Panel
Description
19 —
High Efficiency Semi-Hermetic
Centrifugal Chiller
19G4
DV
–
V — Variable Speed Drive
Evaporator Frame Size, Length,
Pass Arrangement, and Tube Count
4
4
G
4
4
Condenser Frame Size, Length,
Pass Arrangement, and Tube Count
The compressor continuously draws refrigerant vapor from the
evaporator at a rate set by the amount of first stage guide vane
opening and motor speed. As the compressor suction reduces
the pressure in the evaporator, the remaining refrigerant boils
at a fairly low temperature (typically 38 to 42°F [3 to 6°C]).
The energy required for boiling is obtained from the water
flowing through the evaporator tubes. With heat energy removed, the water becomes cold enough to use in an air-conditioning circuit or process liquid cooling.
After taking heat from the water, the refrigerant vapor is compressed by a back-to-back compression connected by means of interstage piping. Compression adds heat energy and the refrigerant
is quite warm (typically 98 to 102°F [37 to 40°C]) when it is discharged from the compressor into the condenser.
Relatively cool (typically 65 to 90°F [18 to 32°C]) water flowing into the condenser tubes removes heat from the refrigerant,
and the vapor condenses to liquid. The liquid drains into a high
side float valve chamber between the condenser and the economizer. The refrigerant is then metered into the economizer. In
the economizer, due to lower pressure, as liquid enters the
chamber, some liquid will flash into a vapor and cool the remaining liquid. The separated vapor flows to the second stage
of the compressor for greater cycle efficiency. The second
stage guide vane on the compressor acts as a pressure regulating device to stabilize operating conditions. At part load the
second stage guide vane will back up gas flow and thereby
raises the economizer pressure to allow appropriate refrigerant
flow from economizer to the compressor.
The cooled liquid left in the economizer flows through a low
side float valve and then into the evaporator. The float valve
forms a liquid seal to keep vapor from entering the evaporator.
The refrigerant is now at a temperature and pressure at which the
cycle began. Figure 3 summarizes the refrigeration cycle.
The 19DV unit utilizes R-1233zd(E) refrigerant. At atmospheric pressure its boiling point is 65.5°F (18.6°C). The result is
that at normal operating conditions the evaporator typically
will be in a vacuum condition and the condenser will operate at
a pressure above atmospheric pressure. Unit near room temperature will be close to atmospheric pressure.
To avoid adverse effects on chiller operation, considerations
must be made to condenser water temperature control. For
steady state operation, the minimum operating refrigerant
pressure differential between evaporator and condenser is approximately 7 psid (48 kPa) with a maximum evaporator refrigerant temperature of 65°F (18°C). Consult Chiller Builder for required steady state operational limits and low lift options. Inverted start conditions are acceptable for short
durations of time, but for periods exceeding 5 minutes, a special control solution strategy should be used to allow the
chiller to establish a minimum refrigerant pressure differential (and thereby adequate equipment cooling).
REFRIGERANT LUBRICATION CYCLE
Summary
The 19DV Series chiller uses refrigerant to lubricate the bearings.
The lubrication control is automatically controlled by the chiller
controls. In normal RUN mode refrigerant is pumped by means of
a refrigerant pump from the high side condenser float chamber to
the bearings. Prior to start-up, liquid level in the high side condenser float chamber is maintained by pumping refrigerant liquid
from the evaporator to the high side float chamber until level sensor is satisfied. If liquid high side float level is not satisfied, the
pump will move refrigerant from the evaporator to the condenser.
During pre-lube and post-lube cycles, refrigerant is drawn from
the evaporator for bearing lubrication.
Figures 4 and 5 identify the refrigerant lubrication assembly. Supply refrigerant is pulled through a filter drier by the refrigerant
pump and is pumped to the bearings through two protective filters
and then returned to the evaporator.
There are two pressure sensors located across the refrigerant
pump. During RUN mode a minimum of 12 psid is required for
the refrigerant pump delta difference. An alert will trigger if
this value is less than 13 psid while the machine is in normal
operating mode. Consult the 19DV with PIC6 Controls Operation and Troubleshooting manual for details.
Bearings
The 19DV motor-compressor assembly includes two matched
sets of refrigerant-lubricated bearings. The motor shaft is supported by a combination set of journal bearing and roller element bearings on each end of compressor. The refrigerant lubrication pressure difference is defined as the bearing input
pressure minus the bearing output pressure plus the Refrigerant
Delta P Offset.
Fig. 4 — Refrigerant Lubrication Cycle
8
Page 9
STRAINER
PUMP
PUMP
SUCTION
DISCHARGE
ACTUATOR
Fig. 5 — Refrigerant Lubrication Assembly
Inhibitor Reclaim System
The inhibitor reclaim system moves inhibitor from the evaporator
and returns it to the first stage suction inlet which allows it to be
mixed in the system since it has a tendency to have higher concentration in the evaporator compared with the rest of the system. The
reclaim is powered by an eductor driven by the gas pressure difference between first stage suction and discharge of second stage.
Motor Cooling System
The motor is cooled by liquid refrigerant taken from the bottom of the high side condenser float chamber. Refrigerant flow
is maintained by the pressure differential that exists due to
compressor operation. After the refrigerant flows past an isolation valve, an in-line filter drier, and a sight glass/moisture indicator, it is directed over the motor by spray nozzles. The refrigerant collects in the bottom of the motor casing and is then
drained back into the evaporator through the motor refrigerant
drain line. The motor is protected by temperature thermistors
embedded in the stator windings. An increase in motor winding temperature past the motor override set point overrides the
temperature capacity control to hold, and if the motor temperature exceeds 10°F (5.5°C) above this set point, the controls
close the inlet guide vanes. If the temperature rises above
122°F (50°C), the compressor shuts down. See Fig. 6.
VFD Cooling System
The VFD enclosure is sealed from the atmosphere to protect electronics from outside contaminants. Refrigerant is routed through a
coil in the VFD enclosure to regulate enclosure temperature while
still maintaining a temperature high enough to prevent condensation. The VFD cooling line is branched off the motor cooling supply. The refrigerant is then drained back into the evaporator
through the motor/VFD drain line. Rectifier and inverter sections
are air-cooled and protected by temperature sensors embedded in
the inverter. An increase in inverter temperature past the override
set point overrides the temperature capacity control to hold, and if
the temperature exceeds 10°F (5.5°C) above this set point, the
controls close the inlet guide vanes. If the IGBT temperature rises
above 144°F (80°C), the compressor shuts down. See Fig. 6.
NOTE: VALVES SHUT AT FACTORY TO CONTAIN
INHIBITOR IN LUBRICATION ASSEMBLY.
IMPORTANT: OPEN THESE VALVES
PRIOR TO STARTUP.
FROM EVAPORATOR
TO COMPRESSOR/
MOTOR BEARINGS
REFRIGERANT
F
PUMP
ILTER
FROM
HIGH SIDE
FLOAT
CHAMBER
VFD
All 19DV units are equipped with a VFD to operate the centrifugal semi-hermetic compressor motor. The VFD and control panel are the main field wiring interfaces for the installing contractor. The VFD and control panel are mounted on the chiller. See
Manufacturer VFD specific information and VFD schematics.
VFD model 32VS is designed to operate in an ambient range of
up to 104°F (40°C). The drive has two control circuit boards.
The Digital Control Interface Board (DCIB) controls the fans for
cooling operation, controls insulated-gage bipolar transistors
(IGBTs), measures three phase line current, controls temperature
input and cooling solenoid, controls outputs for pilot relays, and
controls communication with HMI controller.
The High Voltage Interface Board (HVIB) steps down incoming voltage to 24 VAC and sends this to the DCIB for monitoring. The HVIB measures DC Bus voltage, controls the precharge circuit, and controls SCR gating. It contains watchdog
LED to confirm DC Bus potential is depleted.
If the drive needs to be removed, use the 4 lifting lugs. See Fig. 7.
A 32VS 850A weighs approximately 1500 lbs. The drive is compatible with the Network Service Tool V (NSTV) for diagnostics.
Purge System
The purge system is located under the condenser. See Fig. 8. It has
two gas inlets coming from condenser and compressor. When
chiller is running, the condenser line is active/open and non-condensable gas is pulled out from condenser; when chiller is idle the
compressor line is active and non-condensables are pulled out
from compressor volute. This is implemented due to non-condensable gas density being less than refrigerant and therefore it will accumulate at the highest point when chiller is not running.
In the purge tank the purge gas is cooled by a separate integral
R-134a cooling system. The cooling system consists of an
compressor, an air cooled condenser coil, an expansion valve,
and a cooling coil in purge tank. Cooling the purge gas results
in condensation of R-1233zd(E) vapor as it touches the coil, resulting in a vacuum with the result that more refrigerant is
pushed to the coil. As the purge tank fills up with refrigerant it
will be drained through the purge drain to the refrigerant pump
assembly. See Fig. 9.
9
Page 10
SOLENOID VALVE
VFD
COOLER
COMPRESSOR
LIFTING LUGS
MOISTURE
INDICATOR
MOISTURE
INDICATOR
P
P
Fig. 6 — Motor/VFD Cooling System
CONDENSER
MOTOR COOLING
SYSTEM
Fig. 7 — 32VS 850A
10
LIFTING LUGS
Page 11
COMPRESSOR
VOLUTE (SV02)
CONDENSER
(SV01)
MOTOR
DRAIN
(SV05)
VENTING
(SV06)
PURGE TANK
PURGE PUMPOUT (SV03)
VACUUM PUMP
COMPRESSOR
SUCTION
CONTROL
PANEL
PURGE DRAIN (SV04)
(REFRIGERANT PUMP INLET)
COMPRESSOR
CONDENSER
ASSEMBLY
STRAINER
EXTRA FILTERS
WITH STRAP HEATERS
(NOT SHOWN)
CONDENSER
COMPRESSOR
SV01
SV02
COMPRESSOR VALVE
COMPRESSORSUCTION TEMP
STRAINER
134A CIRCUIT
LEVEL
SV04
PURGE DRAIN
CARBON FILTERS VACCUM PUMPSV06
SV05
STRAINER
SIGHT GLASS
CONDENSER ASSY
REGULATOR
SV03
PUMP OUT
VALV E
CHECK VALVE
(TO MOTOR DRAIN)
(TO LUBE ASSY)
FIELD CONNECTION / PURGE VENT
3/8 SAE FLARE
SWITCHES
VENT LINE
REGENERATED
REFRIGERANT
THROTTLE
DEVICE
CONDENSER VALVE
Fig. 8 — Purge System
Fig. 9 — Purge Tank
11
Page 12
Non-condensables that come into contact with the cold coil in
the purge tank will not condense and will accumulate at the top
of the purge tank, raising the pressure and reducing the flow of
refrigerant vapor. When the controls sense that there is sufficient non-condensable gas in the purge tank, the control will
open the pumpout valve, activate the purge evacuation pump,
and force the gas through the active carbon filters. To capture
any remaining refrigerant the gas is routed through two active
carbon filters that will absorb the refrigerant. As the carbon filters become saturated the system will regenerate the filters by
applying heat to the filters while under vacuum and then
disperse the regenerated refrigerant back to the evaporator
while releasing the non-condensables to atmosphere.
The 19DV purge control is automatic. Purge control should be
active when purge inlet temperature (evaporator refrigerant liquid temp when chiller compressor OFF or condenser saturated
temperature when chiller compressor ON) is greater than purge
active temperature set point (65°F default [18.3°C)].
If chiller compressor is running, condenser solenoid valve
should be opened to purge refrigerant from condenser.
If chiller compressor is not running, open the compressor solenoid valve to purge refrigerant from compressor. If Purge
Comp Suction Temp is less than purge compressor off temp
(default to 4°F [–15.5°C]) and the refrigerant level flag is ON,
close compressor solenoid valve and condenser solenoid valve,
and open pump out solenoid valve. Purge vent valve and purge
vacuum pump shall be kept ON for about 10s. After 10s discharge, pump out solenoid valve, purge vent valve, and purge
vacuum pump shall be kept OFF. Condenser solenoid valve
shall be opened if chiller compressor is running or compressor
solenoid valve shall be opened if chiller compressor is not running. After 10s discharge, it will start 20s delay. Then, check
purge compressor suction temperature again; if it is less than
6°F (–14°C), it will continue cycle as before.
If refrigerant level in the purge tank is high (both PGLE_HI
and PGLE_LO are ON), or purge compressor suction temperature is less than 12°F (–11°C) and PGLE_LO is ON, then
drainage solenoid valve should be opened to drain refrigerant
from purge tank to evaporator (open CV1, SV04, SV01, SV02
when chiller is off, open SV04, SV01 when chiller is on). After
PGLE_LO is OFF, keep drain process for another 1s, then set
the refrigerant level flag to ON. If purge level in the purge tank
is low (both PGLE_HI and PGLE_LO are OFF), drainage solenoid valve should be closed.
If pump out solenoid valve is accumulated ON for 100 minutes,
purge system should do regeneration process for reg_tim minutes
(default = 120 minutes – 19DV Configuration Menu), regardless
whether purge is active. When regeneration process is active, the
Purge Regeneration Valve and Purge Heater should be on for
reg_tim minutes, purge vacuum pump should be on for 3 minutes
and then 10 minutes off, alternating during reg_tim minutes.
Upon regeneration completion, purge system will wait for another 4 hours to let carbon filter cool down before it will operate normally.
WARNING
The main circuit breaker (if equipped) on the front of the
starter disconnects the main motor power only. Power may
be still energized for other circuits. Always check wiring
diagrams before initiating any work on the chiller and follow applicable lock-out/tag-out procedures. Failure to disconnect power will result in personal injury.
CONTROLS
Definitions
ANALOG SIGNAL
An analog signal varies in proportion to the monitored source. It
quantifies values between operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proportion to the temperature, generating many values.)
DISCRETE SIGNAL
A discrete signal is a 2-position representation of the value of a
monitored source. (Example: A switch produces a discrete signal indicating whether a value is above or below a set point or
boundary by generating an on/off, high/low, or open/closed
signal.)
General
The 19DV centrifugal liquid chiller contains a microprocessorbased control center that monitors and controls all operations
of the chiller. The microprocessor control system matches the
cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls
cooling load within the set point plus the deadband by sensing
the leaving chilled water or brine temperature and regulating
the inlet guide vanes and compressor speed. The guide vane is
a variable flow pre-whirl assembly that controls the refrigeration effect in the evaporator by regulating the amount of refrigerant vapor flow into the compressor. An increase in guide
vane opening increases capacity. A decrease in guide vane
opening decreases capacity. The microprocessor-based control
center protects the chiller by monitoring the digital and analog
inputs and executing capacity overrides or safety shutdowns, if
required. The variable frequency drive (VFD) allows compressor start-up and capacity control by modulating the motor frequency based on the operating condition.
PIC6 System Components
The chiller control system is called the PIC6 (Product Integrated
Control 6). See Table 1. As with previous PIC versions, the PIC6
system controls the operation of the chiller by monitoring all operating conditions. The PIC6 control system can diagnose a
problem and let the operator know what the problem is and what
to check. It positions the guide vanes and VFD speed to maintain
leaving chilled water temperature. It controls the refrigerant
pump providing compressor bearing lubrication and can interface with auxiliary equipment such as pumps and cooling tower
fans to turn them on when required. It continually checks all
safeties to prevent any unsafe operating condition. It regulates
the envelope control valve for stabilized aerodynamic operation,
if installed. The PIC6 controls offer an operator trending function to help the operator monitor the chiller status more easily
and for critical compressor motor protection. The PIC6 system
provides open protocols to support the competitive BMS system
and can be integrated into Carrier’s Lifecycle System Management for remote monitoring and data management.
Table 1 — Major Controls Components and
Panel Locations
PIC6 COMPONENTPANEL LOCATION
Variable Frequency DriveTop of condenser
Purge PanelUnder condenser
Remote MonitoringControl Panel
NOTE: For detailed information about the PIC6 HMI (human machine interface), see the 19DV with PIC6 Controls Operation and
Troubleshooting manual.
12
Page 13
START-UP/SHUTDOWN/
RECYCLE SEQUENCE
Local Start/Stop Control
Local start-up (or manual start-up) is initiated by pressing the
gray Start/Stop icon on the HMI interface. See Fig. 10.
Fig. 10 — Chiller Start/Stop Icon
This initiates the PIC6 starting sequence by displaying the list of
operating modes. Press Local On to initiate start-up. See Fig. 11.
Fig. 11 — Local On
Prior to start-up the start-to-start timer and the stop-to-start
timer must have elapsed and all alarms must be cleared (see
Troubleshooting Guide section).
When start-up is initiated the status screen displays the start-up
progress and the Start/Stop icon blinks green.
Once local start-up begins, the PIC6 control system performs a
series of prestart tests to verify that all prestart alerts and safeties are within acceptable limits. Table 2 shows appropriate
Prestart Alerts/Alarms conditions. If a test is not successful, the
start-up is delayed or aborted. If the tests are successful, the
start-up will be in progress and the COMPRESSOR RUN
STATUS will be “Startup.” The control will then energize the
chilled water/brine pump relay.
Five seconds later, the condenser pump relay energizes. Thirty
seconds later the PIC6 control system monitors the chilled water
and condenser water flow devices and waits until the WATERFLOW VERIFY TIME (operator-configured, default 5 minutes)
expires to confirm flow. After flow is verified, the chilled water
temperature is compared to CONTROL POINT plus 1/2CHILLED WATER DEADBAND. If the temperature is less than
or equal to this value, the PIC6 control system turns off the condenser pump relay and goes into a Recycle mode.
If the water/brine temperature is high enough, the start-up sequence continues and checks the guide vane position. If the
guide vanes are more than 4% open, the start-up waits until the
PIC6 control system closes the vanes. If the vanes are closed
and the refrigerant pump pressure difference is less than
2.5 psid (17.2 kPa), the refrigerant pump relay energizes. The
PIC6 control system then waits until the refrigerant pressure
(REF PRESS VERIFY TIME, operator-configured, default of
40 seconds) reaches 12 psid (82.7 kPa). After refrigerant pressure is verified, if high side float chamber has adequate liquid
level, refrigerant pump will be kept ON for 20 seconds for prelube; if not, refrigerant pump will be kept ON pumping refrigerant from evaporator to the high side float chamber until liquid level is satisfied. Upon pre-lube satisfied the compressor
start relay is energized.
Compressor ontime and service ontime timers start, and the
compressor STARTS IN 12 HOURS counter and the number of
starts over a 12-hour period counter advance by one.
Failure to verify any of the requirements up to this point will
result in the PIC6 control system aborting the start and displaying the applicable prestart alert alarm state number near the
bottom of the home screen on the HMI panel. A prestart failure
does not advance the STARTS IN 12 HOURS counter. Any failure after the 1CR relay has energized results in a safety shutdown, advances the starts in 12 hours counter by one, and displays the applicable shutdown status on the display.
The minimum time to complete the entire prestart sequence is
approximately 185 seconds. See Fig. 12 for normal start-up
timing sequence. See Table 2 for a list of prestart checks.
Lubrication Control
For the 19DV system, refrigerant is used to lubricate and cool
the compressor bearings. The refrigerant lubrication system includes refrigerant pump pressure transducers, control valves,
filters, liquid level switch and inhibitor reclaim system. See
Fig. 13 for the lube assembly schematic.
When the chiller is powered on, the controller will maintain the
liquid level in the condenser float chamber. If liquid level is
low, refrigerant will be pumped from evaporator to the condenser high side float chamber until the liquid level switch is
ON. Once the operator pushes the start button, the system will
go into prestart check process.
When Refrigerant Pump request is on for pre-lube and the bearing
pressure difference is OK for start, if evaporator temperature plus
leaving condenser water temperature is less than 10°F (–12.2°C),
pump refrigerant from evaporator to condenser until compressor is
ON. Else, if evaporator temperature plus leaving condenser water
is equal or larger than 10°F (–12.2°C), pump refrigerant from condenser to bearing and drain to condenser until compressor is ON.
During pre-lubrication, if the bearing pressure difference is less
than 8 psid (55.2 kPa) for 8 seconds continuously, the chiller will
shut down. To proceed to start-up, the bearing pressure difference
needs to exceed 12 psid (82.7 kPa) during the pressure verification
time. The compressor will run after the pre-lubrication process.
Refrigerant from the high side condenser float chamber will be
pumped to bearings and will drain to evaporator. When chiller
shuts down, the condenser control valve will be opened and the refrigerant evaporator control valve will open (3-way valve will
connect evaporator to pump suction). This position allows refrigerant to be pumped from evaporator to condenser high side float
chamber. When the chiller is OFF, always open evaporator control
valve. While running, if compressor is ON and the bearing pressure difference is less than 10 psid (68.9 kPa) for 10 seconds continuously, the chiller will shut down.
13
Page 14
Table 2 — Prestart Checks
A
START INITIATED: prestart checks are made; evaporator
pump started.*
BCondenser water pump started (5 seconds after A).
C
Water flows verified (30 seconds to 5 minutes maximum
after B). Chilled water temperatures checked against control
point. Guide vanes checked for closure. Refrigerant pump
started; tower fan control enabled.
D
Ref pressure verified (15 seconds minimum, 300 seconds
maximum after C).
E
Compressor motor starts; compressor on-time and service
on-time start, 15-minute inhibit timer starts (10 seconds after
D), total compressor starts advances by one, and the number of starts over a 12-hour period advances by one.
F
SHUTDOWN INITIATED; Compressor motor stops; compressor on-time and service on-time stop, and 2-minute
inhibit timer starts.
G
Refrigerant pump and evaporator pumps de-energized
(120 seconds after F).Condenser pump and tower fan control may continue to operate if condenser pressure is high.
Evaporator pump may continue if in RECYCLE mode.
O/A
Restart permitted (both inhibit timers expired: minimum of
15 minutes after E; minimum of 2 minutes after F).
* Auto Restart After Power Failure Timing sequence will be faster.
MACHINE SAFETIES
EVAPORATOR PUMP
CONDENSER
WATER PUMP
WATER FLOW, CHILLED WATER
TEMP, GUIDE VANES, REF PUMP,
TOWER FAN CONTROL
REF PUMP
COMPRESSOR,
COMPRESSOR ONTIME,
SERVICE ONTIME
15-MINUTE
START-TO-STA RT
2-MINUTE
STOP-TO-START
PUMP
REFRIGERANT FILTER
PURGE DRAIN
COOLER
SIGHT GLASSSTRAINER
STRAINER
PUMPOUT
DRAIN
BEARING FILTER
BEARING
SUPPLY
HS FLOAT CHAMBER
2-WAY
ACTUATED VALVE
3-WAY
ACTUATED
VALV E
PRESTART CHECK CONDITION*STATE NUMBER
STARTS IN 12 HOURS 8 (not counting recycle restarts or auto restarts after power failure)Alert – 100
COND PRESSURE COND PRESS OVERRIDE – 20 psiAlert – 102
#RECYCLE RESTARTS LAST 4 HOURS > 5Alert – 103
COMP BEARING TEMP >= COMP BEARING ALERT– 10°F (5.6°C)Alarm – 230
COMP MOTOR WINDING TEMP COMP MOTOR WINDING– 10°F (5.6°C)Alarm – 231
COMP DISCHARGE TEMPERATURE COMP DISCHARGE ALERT– 10°F (5.6°C)Alarm – 232
EVAP_SAT <Evap trip point** + EVAP OVERRIDE DELTA TAlarm – 233
EVAP REFRIG LIQUID TEMP <Evap trip point** + EVAP OVERRIDE DELTA TAlarm – 233
AVERAGE LINE VOLTAGE UNDERVOLTAGE THRESHOLD
AVERAGE LINE VOLTAGE OVERVOLTAGE THRESHOLD
CHECK FOR GUIDE VANE 1 CALIBRATIONAlarm – 236
CHECK FOR GUIDE VANE 2 CALIBRATIONAlarm – 238
* If Prestart Check Condition is True, then resulting State is as indi-
cated in the State Number column.
† See the Controls Operation and Troubleshooting guide for alarm
and alert codes.
††
††
Alarm – 234
Alarm – 235
** Evap trip point = 33°F (0.6°C) (water) or EVAP REFRIG TRIP-
POINT (brine).
†† Condition ignored for Eaton/Rockwell VFDs.
†
Fig. 12 — Control Timing Sequence for Normal Start-Up
Fig. 13 — Lube Assembly Schematic
14
Page 15
Shutdown
Unit Start/Stop
The unit can be stopped locally using the HMI by pressing the
green Start/Stop icon . The Unit Start/Stop screen is displayed. Press Confirm Stop (see Fig. 14).
Fig. 14 — Confirm Stop
Chiller shutdown begins if any of the following occurs:
•Local OFF button is pressed
•A recycle condition is present
•The time schedule has gone into unoccupied mode when in
Network or Local Schedule control mode
•The chiller protective limit has been reached and chiller is
in alarm
•The start/stop status (CHIL_S_S) is overridden to stop
from the network when in Network mode
If the chiller is normally shut down from running, soft stop shutdown will be performed. The soft stop feature closes the guide
vanes of the compressor automatically if a non-alarm stop signal
occurs before the compressor motor is de-energized.
Any time the compressor is directed to stop (except in the cases
of a fault shutdown), the guide vanes are directed to close and
VFD is directed to minimum speed for variable speed compressor, and the compressor shuts off when any of the following is true:
•PERCENT LOAD CURRENT (%) drops below the SOFT
STOP AMPS THRESHOLD
•ACTUAL GUIDE VANE OPENING drops below 4%
•4 minutes have elapsed after initializing stop.
When any one of the above conditions is true, the shutdown sequence stops the compressor by deactivating the compressor
start relay. Then the guide vane shall be closed and stay at the
fully closed position, the refrigerant pump relay will be turned
off after 120 seconds post lube, and the chilled water/brine
pump and condenser water pump will be shut down.
BEFORE INITIAL START-UP
Job Data Required
•list of applicable design temperatures and pressures (product data submittal)
•chiller certified prints
•VFD details and wiring diagrams
•diagrams and instructions for special controls or options
•19DV Installation Instructions
Equipment Required
•mechanic’s tools (refrigeration)
•digital volt-ohmmeter (DVM)
•true RMS (root mean square) digital multimeter with
clamp-on current probe or true RMS digital clamp-on ammeter rated for at least 480 vac
•electronic refrigerant leak detector
•absolute pressure manometer or electronic micron gage
(see Fig. 15)
•drum charging valve (unless refrigerant bottles already
have charging valves)
•charging hose
Fig. 15 — Digital Vacuum Gage
Remove Shipping Packaging
Remove any packaging material from the unit, VFD, and control
panels. Inspect the unit for damage that occurred during shipping
or installation. Document any damage that was identified.
Tighten All Gasketed Joints
Gaskets normally relax by the time the chiller arrives at the
jobsite. Tighten all gasketed joints to ensure a leak-tight chiller
(does not apply to refrigerant joints covered by factory insulation). Gasketed joints (excluding O-rings) may include joints at
some or all of the following:
•Waterbox covers
•Compressor first suction elbow flanges (at compressor and
at the evaporator)
•Compressor secondary suction flanges (at compressor and
low side float chamber)
•Compressor discharge flange
•Evaporator inlet line spacer (both sides)
•Envelope control flange (both sides of valve)
•ICP piping flange
•High and low side float chamber covers
See Tables 3 and 4 for bolt torque requirements.
Check Chiller Tightness
Figure 16 outlines the proper sequence and procedures for leak
testing.
The 19DV chillers are shipped without the refrigerant charge.
The chiller is shipped with a 15 psig (103 kPa) dry nitrogenholding charge.
If the 15 psig factory nitrogen charge is present, then release pressure and proceed to pull a deep vacuum on the unit. Vacuum
should be pulled through 1
tom of first stage side of the evaporator. Upon completion of pulling the required vacuum the chiller can be charged with refrigerant. The
1
/
-in. charging valve on top of the evaporator shell should
2
1
/
-in. female NPT located under bot-
2
15
Page 16
be used for charging by lifting charge cylinder and gravity feed
into the evaporator. The chiller should be charged with refrigerant.
If the holding charge is not present, the chiller must be examined
for leaks. To test for leaks add a small refrigerant holding charge to
unit and pressurize with nitrogen up to 20 psig to determine and
correct the origin of the leak. Use an electronic leak detector to
check all flanges and solder joints after the chiller is pressurized. If
the 15 psig factory nitrogen charge is present, then release pressure and proceed to pull a vacuum on the unit. The chiller should
Table 3 — Bolt Torque Requirements, Foot Pounds
be charged with refrigerant. Follow the leak test chiller procedure
(page 18).
If the chiller is spring isolated, keep all springs blocked in both
directions to prevent possible piping stress and damage during
the transfer of refrigerant from vessel to vessel during the leak
test process, or any time refrigerant is being transferred. Adjust
the springs when the refrigerant is in operating condition and
the water circuits are full. Any piping weights are to be separately supported.
19DV Field Procedure for new units with
less than 15 psig holding charge or units
suspected of leaking.
1. Attach compound gage to vessel
2. Note ambient temperature
Raise pressure to 20 psig (138 kPa)
using Nitrogen with added tracer gas for
electronic leak detection
Leak check
Pass
Evacuate vessel and
perform standing
vacuum test
Locate and mark all
leak sources
Dehydrate
Pass
Charge unit
NOTE: Be sure to add refrigerant as gasuntil chiller pressure exceeds
15 in Hg (vac) / 380 mmHg (vac)
to avoid possible tube freezing.
Repair all leaks
No
Yes
Yes
No
Fig. 16 — 19DV Leak Test Procedures
17
Page 18
Refrigerant Tracer
Carrier recommends the use of an environmentally acceptable
refrigerant tracer for leak testing with an electronic refrigerant
detector.
Ultrasonic leak detectors can also be used if the chiller is under
pressure.
WARNING
Do not use air or oxygen as a means of pressurizing the
chiller. Mixtures of HFO R-1233zd(E) and air at elevated
pressure can undergo combustion, resulting in equipment
damage and possible personal injury.
Leak Test Chiller
Due to regulations regarding refrigerant emissions and the difficulties associated with separating contaminants from the refrigerant, Carrier recommends the following leak test procedure.
Refer to Table 5 for refrigerant pressure/temperature values.
1.If the pressure readings are normal for the chiller condition:
a. Evacuate the charge from the vessels, if present.
b. Raise the chiller pressure, if necessary, by adding
refrigerant until pressure is at the equivalent saturated
pressure for the surrounding temperature.
CAUTION
Never charge liquid refrigerant into the chiller if the pressure in the chiller is less than 15 in. Hg (vac) / 380 mm Hg
(vac) for HFO R-1233zd(E). Charge as a gas only, with the
evaporator and condenser pumps running, until this pressure is reached, using PUMPDOWN/LOCKOUT (located
in the Maintenance menu) and END LOCKOUT mode on
the PIC6 control interface. Flashing of liquid refrigerant at
low pressures can cause tube freeze-up and considerable
damage.
c. Leak test chiller as outlined in Steps 3 to 7.
2.If the pressure readings are abnormal for the chiller condition:
a. Prepare to leak test chiller.
b. For cooling machines, check for leaks by connecting a
nitrogen bottle with added tracer to allow for electronic leak detection if possible; otherwise, soap bubble solution is to be used. Raise the pressure to
20 psig (138 kPa). If electronic leak detector is avail-
able, ensure small amount of tracer material is added.
c. Plainly mark any leaks that are found.
d. Release the pressure in the system.
e. Repair all leaks.
f. Retest the joints that were repaired.
NOTE: Suggested test pressure is 20 psig (138 kPa); maximum allowable test pressure 45 psig (310 kPa).
3.Check the chiller carefully with an electronic leak detector
or soap bubble solution.
4.Leak Determination — If an electronic leak detector indicates a leak, use a soap bubble solution, if possible, to confirm. Total all leak rates for the entire chiller. Leakage at
rates greater than 0.1% of the total charge per year should
be repaired. Local regulation governs the requirements for
when repair of leaks become mandatory. Note the total
chiller leak rate as well as the full charge amount on the
start-up report.
5.If no leak is found during the initial start-up procedures,
complete the transfer of refrigerant gas from the storage
tank to the chiller. Recover any gas used for leak detection
purposes as required per local jurisdiction.
6.If no leak is found after a retest:
a. Perform a standing vacuum test as outlined in the
Standing Vacuum Test section, below.
b. If the chiller fails the standing vacuum test, repeat
leak test and repair.
c. If the chiller passes the standing vacuum test, dehy-
drate the chiller. Follow the procedure in the Chiller
Dehydration section, page 20. Charge the chiller with
refrigerant.
7.If the chiller is opened to the atmosphere for an extended
period, evacuate it before repeating the leak test. A nitrogen purge should be maintained to reduce the potential for
corrosion when open to the atmosphere.
NOTE: Alternate optional leak testing method is to isolate the water circuits and use a portable water heater to raise the temperature
of the evaporator and condenser water circuits to approximately
100°F (38°C) which corresponds to a pressure of approximately
14.40 psig (99.3 kPag).
Standing Vacuum Test
When performing the standing vacuum test or chiller dehydration, use a manometer or a wet bulb indicator. Dial gages cannot indicate the small amount of acceptable leakage during a
short period of time.
1.Attach an absolute pressure manometer or wet bulb indicator to the chiller.
2.Evacuate the vessel to at least 18 in. Hg vac (41 kPa [abs]),
using a vacuum pump or a pumpout unit.
3.Valve off the pump to hold the vacuum and record the
manometer or indicator reading.
a. If the leakage rate is less than 0.05 in. Hg (0.17 kPa
in 24 hours, the chiller is sufficiently tight.
b. If the leakage rate exceeds 0.05 in. Hg (0.17 kPa)
24 hours, re-pressurize the vessel and test for leaks.
4. Repair the leak, retest, and proceed with dehydration.
)
in
18
Page 19
Table 5 — HFO R-1233zd(E) Pressure and Temperature
TEMP.PRESSURE
FCPSIAPSIGIN HGKPAGKPA ABSMMHG (VAC)% VACUUM
20.0–6.7
22.0–5.6
24.0–4.4
26.0–3.3
28.0–2.2
30.0–1.1
32.00.0
34.01.1
36.02.2
38.03.3
40.04.4
42.05.6
44.06.7
46.07.8
48.08.9
50.010.0
52.011.1
54.012.2
56.013.3
58.014.4
60.015.6
62.016.7
64.017.8
66.018.9
68.020.0
70.021.1
72.022.2
74.023.3
76.024.4
78.025.6
80.026.7
82.027.8
84.028.9
86.030.0
88.031.1
90.032.2
92.033.3
94.034.4
96.035.6
98.0
100.037.8
102.038.9
104.040.0
106.041.1
108.042.2
110.043.3
112.044.4
114.045.6
116.046.7
118.047.8
120.048.9
122.050.0
124.051.1
126.052.2
128.053.3
130.054.4
36.7
5.16
5.43
5.72
6.01
6.32
6.64
6.98
7.33
7.69
8.06
8.45
8.86
9.28
9.72
10.17
10.64
11.13
11.63
12.15
12.69
13.25
13.83
14.43
15.05
15.69
16.34
17.03
17.73
18.46
19.20
19.98
20.77
21.59
22.44
23.31
24.21
25.13
26.08
27.06
28.07
29.10
30.17
31.26
32.39
33.54
34.73
35.95
37.20
38.48
39.80
41.16
42.54
43.97
45.42
46.92
48.45
–9.54
–9.27
–8.98
–8.69
–8.38
–8.06
–7.72
–7.37
–7.01
–6.64
–6.25
–5.8
–5.42
–4.98
–4.53
–4.06
–3.57
–3.07
–2.55
–2.01
–1.45
–0.87
–0.27
0.35
0.99
1.64
2.33
3.03
3.76
4.50
5.28
6.07
6.89
7.74
8.61
9.51
10.43
11.38
12.36
13.37
14.40
15.47
16.56
17.69
18.84
20.03
21.25
22.50
23.78
25.10
26.46
27.84
29.27
30.72
32.22
33.75
–19.4–65.835.6493.565
–18.9–63.937.4479.463
–18.3–61.939.4464.661
–17.7–59.941.5449.359
–17.1–57.843.6433.357
–16.4–55.645.8416.755
–15.7–53.248.1399.353
–15.0–50.850.5381.350
–14.3–48.353.0362.648
–13.5–45.855.6343.245
–12.7–43.158.3323.042
4
–11.9–40.361.1302.040
–11.0–37.464.0280.237
–10.1–34.367.0257.634
–9.2–31.270.1234.231
–8.3–28.073.4209.928
–7.3–24.676.7184.824
–6.2–21.280.2158.721
–5.2–17.683.8131.717
–4.1–13.887.5103.814
–2.9–10.091.474.910
–1.8–6.095.445.06
–0.6–1.999.514.02
0.72.4103.7——
2.06.8108.1——
3.311.3112.7——
4.716.0117.4——
6.220.9122.2——
7.625.9127.2——
9.231.1132.4——
10.736.4137.7——
12.441.9143.2——
14.047.5148.9——
15.853.4154.7——
17.559.4160.7——
19.465.6166.9——
21.271.9173.3——
23.278.5179.8——
25.285.2186.6——
27.292.2193.5——
29.399.3200.7——
31.5106.7208.0——
33.7114.2215.5——
36.0122.0223.3——
38.4129.9231.3——
40.8138.1239.5——
43.3146.5247.9——
45.8155.1256.5——
48.4164.0265.3——
51.1173.1274.4——
53.9182.4283.8——
56.7192.0293.3——
59.6201.8303.1——
62.6211.8313.2——
65.6222.1323.5——
68.7232.7334.1——
19
Page 20
Check the Installation
Use the following instructions to verify the condition of the
installation. Note that the contractor should not apply power
to the chiller before the Carrier Start-up Technician arrives at
the job site.
1.Inspect the water piping to the chiller to confirm it is correct. Confirm it is adequately supported from the chiller
and there are isolation valves installed.
2.Turn off, lock out, and tag the input power to the drive.
3.Wait a minimum of 5 minutes for the DC bus to discharge.
4.All wiring should be installed in conformance with the
applicable local, national, and international codes (e.g.,
NEC/CSA).
5.Remove any debris, such as metal shavings, from the
enclosure.
6.Check that there is adequate clearance around the
machine.
7.Verify that the wiring to the terminal strip and the power
terminals is correct and that no external voltage potential
is connected to any of the inputs.
8.Verify that all of the VFD power module circuit board connectors are fully engaged and taped in place.
9.Check that the field-installed wire size is within terminal
specifications and that the wires are tightened properly and
adequately supported.
10. Check that specified branch circuit protection is installed
and correctly rated.
11. Check that the incoming power is within ±10% of chiller
nameplate voltage.
12. Verify that a properly sized ground wire is installed and a
suitable earth ground is used. Check for and eliminate any
grounds between the power leads. Verify that all ground
leads are unbroken to the power supply. Only a wye secondary power supply transformer with solidly grounded
neutral is acceptable as a power supply to this chiller. If a
ground wire is not present or the transformer secondary is
any other type than a wye with solidly grounded delta,
please contact the Technical Service Manager or Service
Engineering.
Inspect Wiring
WARNING
Do not check the voltage supply without proper equipment
and precautions. Serious personal injury may result. Follow
power company recommendations.
CAUTION
Do not apply any kind of test voltage, even for a rotation
check, if the chiller is under a dehydration vacuum. Insulation breakdown and serious damage may result.
WARNING
Do not apply power unless a qualified Carrier technician is
present. Serious personal injury may result.
1.Examine the wiring for conformance to the job wiring diagrams and all applicable electrical codes.
2.Ensure that the VFD is protected by fused disconnects or
circuit breakers as per electrical code.
3.Compare the ampere rating on the VFD nameplate to rating on the compressor nameplate.
4.Check that there is adequate service clearance around the
machine.
5.Check that specified branch circuit protection is installed
and correctly rated.
6.Ensure there is capability to turn off, lock out, and tag the
input power to the drive.
7.If power is applied to the drive then wait a minimum of
5 minutes for the DC bus to discharge and check DC bus
voltage prior to starting any work.
8.Inspect the control panels and VFD enclosure to ensure
that the contractor has used the knockouts or provided top
hat to feed the wires into the enclosures. Generally, wiring
into the top of the enclosures can allow debris to fall into
the enclosures. Clean and inspect the interior of the power
panel and VFD enclosure if this has occurred. If metal particulate has fallen into the rectifier or inverter assemblies
contact Service Engineering or your Technical Service
Manager for further instructions.
9.Check that the incoming power is within ±10% of chiller
nameplate voltage.
10. Check that the room environmental conditions match the
chiller enclosure type.
11. Ensure the customer’s contractor has verified proper operation of the pumps, cooling tower fans, and associated
auxiliary equipment. This includes ensuring motors are
properly lubricated and have proper electrical supply and
proper rotation. Carrier must maintain pump control for
freeze protection algorithm.
12. Verify that the incoming source does not exceed the SCCR
(short circuit current rating) of the equipment marking.
13. Ensure all electrical equipment and controls are properly
grounded in accordance with the job drawings, certified
drawings, and all applicable electrical codes.
CAUTION
Disconnect leads to VFD prior to megohm test. The voltage
generated from the tester can damage VFD components.
Test #1: For 3-lead motor, tie terminals 1, 2, and 3 together and
test between the group and ground.
1.With the tester connected to the motor leads, take 10-second
and 60-second megohm readings.
2.Divide the 60-second resistance reading by the 10-second
reading. The ratio, or polarization index, must be one or
higher. Both the 10 and 60-second readings must be at
least 50 megohms. If the readings on a field-installed
starter are unsatisfactory, repeat the test at the motor with
the power leads disconnected. Satisfactory readings in this
second test indicate the fault is in the power leads.
Test #2: Only perform this test if the unit has been disassembled at the job site, if the starter has been removed, or during
annual maintenance.
Perform a megohm test from each terminal to ground. The
megohm value should be greater than 20 megohm. Note that if
a megohm test is performed between the terminals it will show
a direct short and is not a valid test because of the 3 terminal
motor internal delta configuration.
Chiller Dehydration
Dehydration is recommended if the chiller has been open for a
considerable period of time, if the chiller is known to contain
moisture, or if there has been a complete loss of chiller holding
charge or refrigerant pressure.
20
Page 21
CAUTION
Do not start or megohm-test the compressor motor or any
other pump motor, even for a rotation check, if the chiller is
under dehydration vacuum. Insulation breakdown and severe damage may result.
WARNING
Power to the motor and VFD must be disconnected by an isolation switch before placing the machine under a vacuum. To
be safe, isolate input power before evacuating the chiller if you
are not sure if there are live leads to the hermetic motor.
Dehydration can be done at room temperatures. Using a cold
trap (Fig. 17) may substantially reduce the time required to complete the dehydration and is recommended should the unit be exposed to liquid moisture. The higher the room temperature, the
faster dehydration takes place. At low room temperatures, a very
deep vacuum is required to boil off any moisture and heating of
the water in the water circuits of the chiller to approximately
100°F (38°C) may be required.
pockets of moisture can turn into ice. The slow rate of evaporation (sublimation) of ice at these low temperatures and
pressures greatly increases dehydration time.
6.Valve off the vacuum pump, stop the pump, and record the
instrument reading.
7.After a 2-hour wait, take another instrument reading. If the
reading has not changed, dehydration is complete. If the
reading indicates vacuum loss, repeat Steps 4 and 5.
8.If the reading continues to change after several attempts,
perform a leak test (maximum 45 psig [310 kPa] pressure).
Locate and repair the leak, and repeat dehydration.
9.Once dehydration is complete, the evacuation process can
continue. The final vacuum prior to charging the unit with
refrigerant should in all cases be 29.9 in. Hg (500 microns,
0.07 kPa [abs]) or less.
Inspect Water Piping
Refer to piping diagrams provided in the certified drawings
and the piping instructions in the 19DV Installation Instructions manual. Inspect the piping to the evaporator and condenser. Be sure that the flow directions are correct and that all piping specifications have been met.
Piping systems must be properly vented with no stress on waterbox nozzles and covers. Water flows through the evaporator
and condenser must meet job requirements. Measure the pressure drop across the evaporator and the condenser.
Fig. 17 — Dehydration Cold Trap
Perform dehydration as follows:
1.Connect a high capacity vacuum pump (5 cfm [.002 m
or larger is recommended) to the refrigerant vacuum/
charging valve (Fig. 2). Tubing from the pump to the
chiller should be as short in length with a minimum diameter of 0.5 in. (13 mm) and as large in diameter as possible
to provide least resistance to gas flow.
2.Use an absolute pressure manometer or a electronic
micron gage to measure the vacuum. Open the shutoff
valve to the vacuum indicator only when taking a reading.
Leave the valve open for 3 minutes to allow the indicator
vacuum to equalize with the chiller vacuum.
3.If the entire chiller is to be dehydrated, open all isolation
valves (if present).
4.With the chiller ambient temperature at 60°F (15.6°C) or
higher, operate the vacuum pump until the manometer
reads 29.8 in. Hg (vac), –14.63 psig (–100.9 kPag), or a
vacuum indicator reads 35°F (1.7°C). Operate the pump
an additional 2 hours.
5.Do not apply a greater vacuum than 29.82 in. Hg vac
(757.4 mm Hg) or go below 33°F (0.56°C) on the wet bulb
vacuum indicator. At this temperature and pressure, isolated
3
/s]
CAUTION
Water must be within design limits, clean, and treated to ensure proper chiller performance and to reduce the potential of
tube damage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller damage resulting from untreated or improperly treated water.
Check Safety Valves
Be sure safety valves have been piped to the outdoors in compliance with the latest edition of ANSI/ASHRAE Standard 15
and applicable local safety codes. Piping connections must allow for access to the valve mechanism for periodic inspection
and leak testing.
The standard 19DV relief devices are set to relieve at 57 psig
(393 kPa) chiller design pressure. To avoid potential rupture
the chiller should never be pressurized above 45 psig (310 kPa)
for any testing purpose.
Check Purge Compressor Operation
Enter Quick Test menu (under Main Menu) and select “Quick
Test Purge Comp.” Connect a pressure gage to purge compressor inlet Schrader valve (suction is top fitting).
The purge system is shown in Fig. 18. The reading should be
about 0 ± 0.25 psig (–15.6 to –14.3°F) [0 ± 1.724 kPa (–26.5 to
–25.7°C)]. If not, adjust the purge expansion valve in the
R-134a purge compressor circuit until the reading is correct.
NOTE: This step should only be performed if the purge is not
working correctly. The installation of the gage will result in a loss
of refrigerant and the charge of R-134a is a very small quantity affecting the operation of the purge. The charge should be weighed
into this circuit using a charging cylinder or similar device.
21
Page 22
NOTE: CLOCKWISE ROTATION OF
EXPANSION VALVE ADJUSTMENT
SCREW INCREASES THE PRESSURE
SETTING AND COUNTERCLOCKWISE ROTATION DECREASES PRESSURE
SETTING.
EXPANSION VALVE
Fig. 18 — Purge System
Ground Fault Troubleshooting
Follow this procedure only if ground faults are declared by the
chiller controls. Test the chiller compressor motor and its power lead insulation resistance with a 500-v insulation tester such
as a megohmmeter.
1.Open the VFD main disconnect switch and follow lockout/
tagout rules.
CAUTION
The motor leads must be disconnected from the VFD before an insulation test is performed. The voltage generated
from the tester can damage the VFD.
2.Perform test #1: For 3-lead motor, tie terminals 1, 2, and 3
together and test between the group and ground.
a. With the tester connected to the motor leads, take 10-
second and 60-second megohm readings.
b. Divide the 60-second resistance reading by the 10-
second reading. The ratio, or polarization index, must
be one or higher. Both the 10 and 60-second readings
must be at least 50 megohms. If the readings are
SUCTION
SCHRADER
VALVE
unsatisfactory, repeat the test at the motor with the
power leads disconnected. Satisfactory readings in
this second test indicate the fault is in the power leads.
3.Perform test #2: Only perform this test if the unit has been
disassembled at the job site, if the starter has been
removed, or during annual maintenance.
Perform a megohm test from each terminal to ground. The
megohm value should be greater than 20 megohm. Note
that if a megohm test is performed between the terminals it
will show a direct short and is not a valid test because of
the 3 terminal motor internal delta configuration.
Carrier Comfort Network® Interface
The Carrier Comfort Network (CCN) communication bus wiring is supplied and installed by the electrical contractor. It consists of shielded, 3-conductor cable with drain wire.
The system elements are connected to the communication bus
in a daisy chain arrangement. The positive pin of each system
element communication connector must be wired to the positive pins of the system element on either side of it. The negative pins must be wired to the negative pins. The signal ground
pins must be wired to the signal ground pins. See installation
manual.
22
Page 23
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
1
, or polyethylene. An aluminum/polyester 100% foil
Tefl on
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of –4°F
to 140°F (–20°C to 60°C) is required. See Table 6 for cables
that meet the requirements.
Table 6 — Manufacturers and Cable Numbers
MANUFACTURERCABLE NO.
ALPHA2413 or 5643
AMERICANA22503
BELDEN8772
COLUMBIA02525
When connecting the CCN communication bus to a system element, a color code system for the entire network is recommended to simplify installation and checkout. The color code
shown in Table 7 is recommended.
Table 7 — Recommended Color Code
SIGNAL
TYPE
+RedRed (+)
GROUNDWhiteWhite (G)
–BlackBlack (–)
CCN BUS CONDUCTOR
INSULATION COLOR
CCN TERMINAL
CONNECTION
WARNING
BE AWARE that certain automatic start arrangements can
engage the starter. Open the disconnect ahead of the starter
in addition to shutting off the chiller or pump. Failure to
follow this procedure may result in personal injury by electric shock.
WARNING
The main disconnect on the starter front panel may not deenergize all internal circuits. Open all internal and remote
disconnects before servicing the starter. Failure to follow this
procedure may result in personal injury by electric shock.
Inhibitor Charge
The inhibitor charge is included with the 19DV unit supplied
from the factory. No action associated with inhibitor is required
unless a new refrigerant charge is added or the inhibitor has
been distilled out of the existing refrigerant charge.
If the unit needs to be disassembled, add 1% (mass of total refrigerant charge) of inhibitor PP23BZ110001 (part number is for
1 Gal. Inhibitor Density is 8.2202 lb/Gal [0.985 Kg/L]). For example, see Tables 8 and 9; sum up the evaporator, condenser,
and economizer charge; take 1% of total charge; then calculate
required inhibitor volume. For a G20 evaporator with G22 condenser this yields: (700+413+342)lb*0.01/(8.2202 lb/Gal)=1.77
Gal (1 Gal + 99 oz) [6.70 L]. See Fig. 19 for field inhibitor addition assuming compressor running and negative evaporator pressure. A dose of Carrier inhibitor is supplied with the unit by the
factory.
Suggested Procedure:
1.Ensure availability of appropriate PPE such as protective
gloves/protective clothing/eye protection/face protection
and wash throughly after handling.
2.If new inhibitor charge is required, a refrigerant charge hose
can be used for this purpose or a hard pipe creating a funnel
using a 90 degree 2-in. x
1
/
-in. NPT female elbow reducer
2
along with a 2-in. NPT pipe to create a reservoir (add inhibitor as it is being sucked into the evaporator and close
1
/
-in.
2
charging ball valve prior to air being sucked into chiller).
Ensure that parts used to add inhibitor are clean to avoid any
chiller contamination.
Software Configuration
WARNING
Do not operate the chiller before the control configurations
have been checked and a Calibration and Control Test has
been satisfactorily completed. Protection by safety controls
cannot be assumed until all control configurations have
been confirmed.
See the 19DV with PIC6 Controls Operation and Troubleshooting manual for instructions on using the PIC6 interface to configure the 19DV unit. As the unit is configured, all configuration
settings should be written down. A log, such as the one shown
starting on page CL-1, provides a list for configuration values.
Charge Unit with Refrigerant
IMPORTANT: Turn on the chilled water and condenser water
pumps to prevent freezing.
.
CAUTION
Always operate the condenser and chilled water pumps
whenever charging, transferring, or removing refrigerant
from the chiller. Always confirm that water flow is established. Failure to follow this procedure may result in equipment damage.
CAUTION
The transfer, addition, or removal of refrigerant in spring
isolated chillers may place severe stress on external piping
if springs have not been blocked in both up and down directions. Failure to block springs in both up and down directions could result in severe personal injury and equipment
damage.
CAUTION
Always operate the condenser and chilled water pumps
during charging operations to prevent freeze-ups. Damage
could result to equipment if condenser and chilled water
pumps are not operated during pumpdown or charging.
WARNING
Always charge refrigerant gas into unit until pressure exceeds
water freeze temperature using PUMPDOWN/LOCKOUT
(located in the Maintenance menu) and TERMINATE LOCKOUT mode on the PIC6. Evaporator and condenser water
pumps must be running to prevent tube freezing.
For R-1233zd(E) water freeze point is exceeded at -15 in. Hg
(-51 kPa).
1. Teflon is a registered trademark of DuPont.
23
Page 24
All 19DV units are field charged. Charge the unit from refrigerant cylinders. Use Tables 8 and 9 to find expected approximate
charge by adding evaporator and condenser charge together. Refer to unit nameplate and E-Cat output for certified values.
Prior to charging ensure the following:
1.Standing vacuum test completed.
2.Only initiate refrigerant charging into a deep vacuum.
3.Adequate refrigerant supply is available as per unit nameplate.
CAUTION
Do not apply power to the VFD or motor when in a dehydration vacuum because it will result in equipment damage.
charging gas until the pressure is greater than the above saturation pressure temperature to avoid refrigerant flashing and potential tube freezing. Once required pressure is reached, switch
over to charge liquid either by lifting refrigerant cylinder above
charging valve to allow for gravity feed or, if charge is isolated
in storage tank, by using pumpout equipment suited for low
pressure refrigerant.
After the machine has been started, adjust charge for optimum
machine performance. Operate the chiller at design load and
then add or remove refrigerant slowly until the difference between the leaving chilled water temperature and the evaporator
refrigerant temperature reaches design conditions or becomes a
minimum. Do not overcharge.
Use the evaporator sight glass (see Fig. 20) to determine the
correct refrigerant at all times. During steady state operation at
full load, the boiling pool tubes under compressor suction
With water pumps running, connect charging hose from refrigerant cylinder to chiller evaporator charging valve. Start with
Table 8 — Refrigerant Charge — English (lbs)
GH
EVAPORATOR HXREFRIGERANT
G20 through
G2K
G40 through
G4K
——G24, G29402H22, H27763H24, H29507
WT [lbs]
700
840
CONDENSER
G22, G27, G2C,
G2H
G23, G28, G2D,
G2J
REFRIGERANT
WT [lbs]
413H20, H25741H22, H27484
405H21, H26752H23, H28495
should be covered with liquid refrigerant. There is no benefit to
a refrigerant liquid level higher than the tubes.
*
DV4
EVAPORATOR HXREFRIGERANT
WT [lbs]
CONDENSER
REFRIGERANT
WT [lbs]
——G2E, G2K397H23, H28778H2C, H2H431
——
——
——G44, G49455H2B, H2G707H42, H47563
——G4E, G4K448H2C, H2H716H43, H48576
————H2D, H2J726H44, H49590
————H2E, H2K736H4C, H4H499
————H40, H45841H4D, H4J508
————H41, H46853H4E, H4K518
————H42, H47866——
————H43, H48883— —
————H44, H49900——
————H4A, H4F795——
————H4B, H4G803——
————H4C, H4H813——
————H4D, H4J824——
————H4E, H4K836——
G42, G47, G4C,
G4H
G43, G48, G4D,
G4J
468H24, H29792H2D, H2J439
458H2A, H2F700H2E, H2K448
* The economizer factor for Frame G, H is 342 lbs, so for example the charge for
a G20 evaporator coupled with G22 condenser is:
700 lbs + 413 lbs + 342 lbs = 1455 lbs
24
Page 25
Table 9 — Refrigerant Charge — SI (kg)
Cooler
½" NPT charging valve
½" x 2" NPT reducer elbow or alternate adapter
2" NPT pipe
or alternate container
DV4
GH
EVAPORATOR HXREFRIGERANT
G20 through
G2K
G40 through
G4K
——G24, G29182H22, H27346H24, H29230
——G2E, G2K180H23, H28353H2C, H2H195
——
——
——G44, G49206H2B, H2G321H42, H47255
——G4E, G4K203H2C, H2H325H43, H48261
————H2D, H2J329H44, H49268
————H2E, H2K334H4C, H4H226
————H40, H45381H4D, H4J230
WT [kg]
318
381
CONDENSER
G22, G27, G2C,
G2H
G23, G28, G2D,
G2J
G42, G47, G4C,
G4H
G43, G48, G4D,
G4J
REFRIGERANT
WT [kg]
187H20, H25336H22, H27220
184H21, H26341H23, H28225
212H24, H29359H2D, H2J199
208H2A, H2F318H2E, H2K203
EVAPORATOR HXREFRIGERANT
*
WT [kg]
CONDENSER
REFRIGERANT
WT [kg]
————H41, H46387H4E, H4K235
————H42, H47393——
————H43, H48401——
————H44, H49408——
————H4A, H4F361——
————H4B, H4G364——
————H4C, H4H369——
————H4D, H4J374——
————H4E, H4K379——
* The economizer factor for Frame G, H is 155 kg, so for example the charge for
a G20 evaporator coupled with G22 condenser is:
318 kg + 187 kg + 155 kg = 660 kg
Fig. 19 — Inhibitor Addition
25
Page 26
1
/2" NPT COOLER
CHARGING VALVE
Fig. 20 — Evaporator Charging Valve and Sight Glasses
HOME SCREEN
The home screen is the first screen shown after switching the
unit on. See Fig. 21. Note the Globe and Lock icons.
COOLER SIGHT GLASSES
(APPLY LIGHT TO ONE AND
VIEW THROUGH OTHER)
The Lock icon on the Home screen allows access to the password menu and displays current software version. See Fig. 23.
Fig. 21 — Home Screen
The Globe icon on the Home screen allows access to language and measurement settings. See Fig. 22.
Fig. 22 — Language and Units Selection Screen
Fig. 23 — Login Screen
CHANGE THE SET POINTS
To access the set point screen, press the lock icon on the Main
Menu. In the User Login menu, enter the password (default
USER password = 1111), and click accept. The screen will then
default back to the home screen. See Fig. 24. The Service Login
access is reserved for access to equipment service tables.
Fig. 24 — Home Screen
26
Page 27
The Main Menu screen is displayed. See Fig. 25. Press the Setpoint Table icon.
Fig. 25 — Main Menu
The Setpoint screen is displayed. See Fig. 26. Set the base demand limit, and either the LCW set point or the ECW set point.
To set a value, press the appropriate set point, enter the value,
and press OK. For more information, see the PIC6 Control
User Manual.
5.Equipment configuration
6.Automated control quick test
PA SS WO R D
The PIC6 provides a smart factory password for better security
and the password changes periodically. With a smart password,
only authorized users can log into the controller factory tables to
access key product configuration and maintenance data.
A password must be entered to access the Set Point or other
common user tables. See Fig. 28. User password can be
changed from the General Configuration Menu. USER CONFIGURATION allows change of the User access password.
IMPORTANT: Be sure to remember the password. Retain a
copy for future reference. Without the password, access will
not be possible unless accessed by a Carrier representative.
Factory password is required to enter configuration menus required for chiller setup.
Fig. 26 — Setpoint Menu
INPUT THE LOCAL OCCUPIED SCHEDULE
Access the schedule menu (Main Menu→ConfigurationMenu→Schedule Menu) and set up the occupied time schedule
according to the customer’s requirements. If no schedule is
available, the default is factory set for 24 hours occupied, 7 days
per week including holidays. When the control mode is LOCAL
SCHEDULE, the chiller will be automatically started if the configured local schedule is occupied and will be automatically shut
down by the unoccupied schedule.
The Network Schedule should be configured if a CCN system
is being installed. When control mode is NETWORK, the
chiller can be started and stopped by the CHIL_S_S software
point as written by other equipment through the network command and network schedule. The Schedule Menu contains a table to set the Network Schedule if required.
For more information about setting time schedules, please refer
to the PIC6 Control User Manual.
INPUT SERVICE CONFIGURATIONS
See Fig. 27 for 19DV Configuration Tables. For specific values
for the following configurations, refer to the chiller performance data or job-specific data sheet:
1.Password
2.Log in/log out
3.Input time and date
4.Service parameters
Fig. 27 — 19DV Configuration Tables
Fig. 28 — User Login Screen
INPUT TIME AND DATE
Set day and time and, if applicable, holidays through MAIN
MENU SYSTEM CONFIGURATION and then select Date/
Time Configuration. See the Controls Operation and Troubleshooting guide for details. Because a schedule is integral to the
chiller control sequence, the chiller will not start until the time
and date have been set.
MODIFY CONTROLLER IDENTIFICATION IF NECESSARY
The CCN address can be changed from the Configuration
Menu. Change this address under CONTROL IDENTIFICATION for each chiller if there is more than one chiller at the
jobsite. Write the new address on the PIC6 Touch Screen module for future reference.
27
Page 28
CONFIGURE TABLES
Access the related tables through MAIN MENU CONFIGURATION MENU (Fig. 27) to modify or view job site parameters
shown in 19DV Configuration tables. Tables 10-16 should be
verified or configured during startup/commissioning. Consult
chiller nameplates as indicated.
DESCRIPTIONRANGEUNITSDEFAULTVALUE
VFD Gain0.10 to 1.50—0.750.75
VFD Max Speed Per90.0 to 110.0%100100
VFD Min Speed Per45.0 to 89.0%7060
VFD Start Speed Per65.0 to 100.0%100100
VFD Current Limit0.0 to 99999.0AMPS250Nameplate
VFD Load Current 20mA10.0 to 5000.0AMPS200n/a
Comp Frequency 100%45.0 to 62.0Hz50Nameplate
VFD Load Current InputEnable/Dsable—EnableDsable
Table 12 — 19DV Configuration
Main Menu
DESCRIPTIONRANGEUNITSDEFAULTVALUE
Motor Pole Pair1, 2—11
IGV2 Travel Limit 30 to 100%%9693.6
IGV2 minimum Degree0 to 20Degree22
IGV2 Fully Open Degree 10 to 100Degree9088
IGV2 Actuator Max Deg.90 to 120Degree9494
IGV2 Deg@IGV1 20 Deg10 to 30Degree28.128.1
IGV2 Deg@IGV1 30 Deg10 to 50Degree37.237.2
IGV2 Deg@IGV1 50 Deg10 to 80Degree71.671.6
VFD Rate Speed Hz10 to 200Hz8
Purge Regen Lasting Time0 to 65535minutes120120
Daily PG Pumpout Limit20 to 200minutes5050
Compressor Speed 100%47 to 110Hz50Nameplate
Rated Line Voltage200 to 13800Volts460Nameplate
Motor Nameplate Current10 to 1500AMPS200Nameplate
Motor Rated Load Current10 to 2000AMPS200Nameplate
Motor Nameplate Voltage200 to 13800Volts460Nameplate
Motor Nameplate RPM1500 to 3600rpm3000Nameplate
Motor Nameplate KW0 to 5600KW1500Nameplate
Skip Frequency 10.0 to 102.0Hz3030
Skip Frequency 20.0 to 102.0Hz3030
Skip Frequency 30.0 to 102.0Hz3030
Skip Frequency Band0.0 to 102.0Hz00
Increase Ramp Time5 to 60sec3030
Decrease Ramp Time5 to 60sec3030
Line Voltage Imbalance%1 to 10%1010
Line Volt Imbalance Time1 to 10sec1010
Line Current Imbalance%5 to 40%4040
Line Current Imbal Time1 to 10sec1010
Motor Current Imbalance%5 to 40%4040
Motor Current Imbal Time1 to 10sec1010
Single Cycle DropoutDsable/Enable—DsableDsable
PWM Switch Frequency
0=2 KHZ, 1=4 KHZ
Restore DefaultsNo/Yes—NoNo
LEN Comm Timeout0 to 255sec1010
Modbus Comm Timeout0 to 255sec22
Gateway Modbus Baud Rate
Surge Delta Tsmaxdts_max0.0 to 150.0^F70Nameplate
Surge Delta Tsmindts_min0.0 to 150.0^F45Nameplate
PR at Full Load Openingpr_ful1.0000 to 5.0000—33
PR at Minimum Openingpr_min1.0000 to 5.0000—1.51.5
IGV1 Full Load Open Deggv1_dful80 to 120.0—8888
Sound Ctrl IGV1 Open Deggv1_dmed10.0 to 40.0—2727
IGV1 Minimum Open Deggv1_dmin0.0 to 10.0—22
IGV1 Maximum Open Deggv1_dmax90 to 120.0—10994
IGV1 Minimum Positiongv1_pmin0.0 to 100.0%55
IGV1 Full Load Positiongv1_pful0.0 to 100.0%10093.6
Envelop Line Offsetsgl_off1.0 to 3.0^F21
Envelop Lower Deadbandsgl_loff0.5 to 3.0^F1.51.5
Envelop Upper Deadbandsgl_hoff0.1 to 3.0^F1.51.5
Surge Line Shape Factorsgl_shfh–1.000 to 0.000—–0.01Nameplate
Sound Line Shape Factorsgl_shfl0.000 to 1.000—0.01Nameplate
Envelop Speed Factorsgl_spdf0.00 to 3.00—2Nameplate
Surge Delay Timesurg_del0 to 120sec1515
Surge Time Periodsurge_t7 to 10min88
Surge Delta Amps %surge_a5.0 to 40.0%2020
GV1 Close Step Surgegvstp_sg1.0 to 3.0%22
VFD Speed Step Surge
EC Valve Step Surgehgbpstsg1.0 to 10.0%44
Surge Profile Offsetsgl_pro0.00 to 5.0^F00
High Efficiency Modehigh_effDsable/Enable—EnableEnable
High Noise Alertnoi_altDsable/Enable—EnableEnable
Water Flow Measurement
No=0, Flow Meter=1,Water Pres. D=2
Water Flow Determination
Sat Temp=0,Flow Switch=1
Water Flow at 4mA
Water Flow at 20mA
Evap Flow Rate Baseline
Evap Pres Drop Baseline
Cond Flow Rate Baseline
Cond Pres Drop Baseline
Water Pres Drop @20mA
Max Oil Pressure Diff
Oil Pump VFD Max Step
Vapor Source SV Delay
Vapor Source SV Option
Liquid Bypass Selection
Purge On Idle Option
Evap Liquid Temp Opt
Evap App Calc Selection
Sat Temp=0, Ref Temp=1
Configuration Menu Option Configuration [CONF_OPT
Dsable/Enable—DsableJobsite specific
Dsable/Enable—DsableJobsite specific
0 to 3—02 (if selected)
0 to 3—0Jobsite specific
0.5 to 10.0%55 (adjust as required)
1.5 to 20.0%1010 (adjust as required)
0.5 to 10^F44 (adjust as required)
0.5 to 10^F22 (adjust as required)
0.5 to 2.0^F11 (adjust as required)
Dsable/Enable—DsableJobsite specific
20 to 85PSI2525 (adjust as required)
20 to 85PSI5050 (adjust as required)
0 to 100%00 (adjust as required)
55 to 105°F7575 (adjust as required)
Dsable/Enable—DsableJobsite specific
4 to 20mA2020 (adjust as required)
Dsable/Enable—DsableDsable
100 to 140°F122n/a
90 to 130°F113n/a
0.25 to 3.00—11
0.70 to 1.20—0.950.95
0 to 60min1515
Dsable/Enable—DsableDsable
Dsable/Enable—DsableJobsite specific
Dsable/Enable—DsableJobsite specific
Dsable/Enable—DsableJobsite specific
0 to 2—0Jobsite specific
0 to 2—0Jobsite specific
0 to 2—0Jobsite specific
0 to 1—0Jobsite specific
0 to 200GPS0(adjust as required)
0 to 200GPS0(adjust as required)
0 to 150GPS0(adjust as required)
0 to 20PSI0(adjust as required)
0 to 150GPS0(adjust as required)
0 to 20PSI0(adjust as required)
10 to 40PSI10(adjust as required)
35 to 60PSI50n/a
0 to 10%7n/a
0 to 10min5n.a
Dsable/Engale—Dsablen.a
Dsable/Enable—DsablePer selection
Dsable/Enable—Dsable(adjust as required for force)
Dsable/Enable—Enablen/a
0 to 1—11
30
Page 31
Table 16 — Service Parameters Table
Configuration MenuService Parameters [SERVICE]
Menu
DESCRIPTIONMenu nameRANGEDEFAULTUNITSVALUE*
Service Passwordser_pass0 to 655352222—
Atmospheric Pressureatom_pre8 to 1514.5PSI
GV1 Travel Limitgv1_lim30 to 10080.7%
GV1 Closure at Startupgv1stpos0 to 404%
Controlled Fluid DBctrl_db0.5 to 21^F
Derivative EWT Gainewtdgain1 to 32—
Proportional Dec Bandgv1decdb2 to 106—
Proportional Inc Bandgv1incdb2 to 106.5—
Maximum GV Movementmax_gv1.0 to 4.02%
Demand Limit At 20 mAdem_20ma10 to 10040%
Demand Limit Prop Banddem_pdb3 to 1510%
Amps or KW Ramp per Minldramprt5 to 205%
Temp Ramp per Mintmramprt1 to 103^F
Recycle Shutdown Delta Trcysh_dt0.5 to 41^F
Recycle Restart Delta Trcyst_dt2 to 105^F
Damper Valve Act Delaydmp_dly1 to 52min
Damper Valve Close DBdmp_cldb2 to 105PSI
Damper Valve Open DBdmp_opdb10 to 2013PSI
Damper Action Delta Tdmp_dt4 to 107^F
Lub Press Verify Timeoilpvr_t15 to 30040sec
Soft Stop Amps Thresholdsf_st_th40 to 10070%
Water Flow Verify Timewflow_t0.5 to 55min
Power Calibration Factormbb_pfcl0.5 to 21—
Enable Excessive Startsex_startNo/YesNo—
Purge Active Temp SPpgt_set30 to 9065—
Oil Stir Cycle(19XR6/7)
No Stir=0, 30s/30m=1,
1m/4h=2, Comb. 0&1=3
* Most Service Parameters do not require any change from default.
Adjust as required.
oilstiro0 to 31—
Field Set Up and Verification
IMPORTANT: Some parameters are specific to the chiller
configuration and will need to be verified prior to operation.
All command functions must be initiated from the HMI.
Use the HMI touch screen to confirm that the VFD values
match the chiller parameter labels and Chiller Builder design
data sheet. The VFD values can be located from Main Menu
Configuration Menu.
LABEL LOCATIONS
Verify the following labels have been installed properly and
match the chiller requisition:
•Surge Parameters — Located inside the HMI chiller control panel.
•Chiller identification nameplate — Located on the left side
of the control panel. See Fig. 29.
•VFD Nameplate data - located on the right side of the VFD.
See Fig. 29.
MODIFY EQUIPMENT CONFIGURATION IF NECESSARY
The EQUIPMENT SERVICE table has screens to select, view,
or modify parameters. Carrier’s certified drawings have the
configuration values required for the jobsite. Modify these values only if requested. Modifications can include:
•Chilled water reset
•Entering chilled water control (Enable/Disable)
•4 to 20 mA demand limit
•Auto restart option (Enable/Disable)
•Remote contact option (Enable/Disable)
See the 19DV with PIC6 Controls Operation and Troubleshooting guide for more details about these functions; see the
Control Panel Schematic for field wiring.
Fig. 29 — Machine Identification Nameplate and VFD
Electrical Nameplate
31
Page 32
Perform a Controls Test
(Quick Calibration/Quick Test)
NOTE: The QUICK TEST screens can only be accessed when the
chiller is in STOP mode.
Check the safety controls status by performing an automated
controls test. First, perform a Quick Calibration Test (Path
Main Menu → Quick Calibration). This is required for all
modulating analog actuators. Upon successful calibration, use
Quick Test (Main Menu → Quick Test) to verify operation on
desired components. Note that this is a very useful feature for
troubleshooting. On the QUICK TEST table screen, select a
test to be performed.
The Quick Test checks all outputs and inputs for proper functionality. In order to successfully proceed with the controls test,
the compressor must be off with no alarms showing, and voltage should be within ±10% of rating plate value. Each test asks
the operator to confirm the operation is occurring and whether
or not to continue. If an error occurs, the operator can try to address the problem as the test is being done or note the problem
and proceed to the next test.
NOTE: The refrigerant pump test will not energize the pump if
evaporator pressure is below –13 psig (–90 kPa).
When the controls test is finished the test stops and the QUICK
TEST menu displays. If a specific automated test procedure is
not completed, access the particular control test to test the
function when ready. Disable the Quick Test feature when testing is complete. For information about calibration, see the sections Checking Pressure Transducers, page 50, and High Altitude Locations, page 51.
EVAPORATOR AND CONDENSER PRESSURE TRANSDUCER AND WATERSIDE FLOW DEVICE CALIBRATION
(Waterside Device Optional with IOB Inputs Available)
Calibration can be checked by comparing the pressure readings
from the transducer to an accurate refrigeration gage reading.
The transducer can be checked and calibrated at 2 pressure
points. These calibration points are 0 psig (0 kPa) and between
10 psig (68.9 kPa) and 30 psig (206.8 kPa). To calibrate these
transducers:
1.Shut down the compressor and the evaporator and condenser pumps.
NOTE: There should be no flow through the heat exchangers.
2.Disconnect the transducer in question from its Schrader
fitting for evaporator or condenser transducer calibration.
For pump pressure or bearing pressure or flow device calibration keep transducer in place.
NOTE: If the evaporator or condenser vessels are at 0 psig (0 kPa)
atmospheric pressure, the transducers can be calibrated for zero
without removing the transducer from the vessel.
3.Access the PRESSURE screen from the Main Menu and
view the particular transducer reading (the evaporator
pressure, condenser pressure, economizer pressure, pump
inlet pressure, pump outlet pressure, bearing inlet pressure, bearing outlet pressure).
4.To calibrate a device, view the particular reading on the
screen. It should read 0 kPa. If the reading is not 0 kPa, but
within 35 kPa, the value may be set to zero while the
appropriate transducer parameter is highlighted. The value
will now go to zero. No high end calibration is necessary
for REF PUMP DELTA P or flow devices. If the transducer value is not within the calibration range, the transducer will return to the original reading. If the pressure is
within the allowed range (noted above), check the voltage
ratio of the transducer. To obtain the voltage ratio, divide
the voltage (dc) input from the transducer by the supply
voltage signal (see Maintenance Others in Maintenance
Menu) or measure across the positive (+ red) and negative
(– black) leads of the transducer. The voltage ratio must be
between 0.80 and 0.11 for the software to allow calibration. Rotate the waterside flow pressure device from the
inlet nozzle to the outlet nozzle and repeat this step. If
rotating the waterside flow device does not allow calibration then pressurize the transducer until the ratio is within
range. Then attempt calibration again.
5.A high pressure point can be calibrated between 10 and
30 psig (68.9 and 206.8 kPa) by attaching a regulated pressure source (usually from a nitrogen cylinder with high
resolution pressure gage). The high pressure point can be
calibrated by accessing the appropriate transducer parameter on the PRESSURES screen, highlighting the parameter, then increasing or decreasing the value to the exact
pressure on the refrigerant gage.
Pressures at high altitude locations must be compensated for,
so the chiller temperature/pressure relationship is correct. This
is set in the Service Parameters (Configuration Menu).
The PIC6 does not allow calibration if the transducer is too far
out of calibration. In this case, a new transducer must be installed and re-calibrated.
IMPORTANT: When screen display calibration is complete,
do not press Calibration Enable/Dsable since the new values
will be deleted. Values are kept by exiting the pressure sensor
table.
Set the flow through the water circuit to the minimum safe
flow that will be encountered.
Reduce the sensitivity of the switch by turning the adjustment
counter-clockwise until the yellow LED turns off. This indicates that the switch is now open.
Increase the sensitivity of the flow switch by turning the adjustment potentiometer clockwise until the yellow LED is lit.
In case of nuisance trips at low flow, increase the sensitivity of
the switch by turning the potentiometer clockwise.
HYDRAULIC STATUS
The HYDRAULIC STATUS screen (access from the Main
Menu) provides a convenient way to detect if any of the evaporator/condenser pressure switches (if installed) are in need of
calibration. See Fig. 30 for the hydraulic status menu. With no
flow the water delta should read 0 kPa. If it does not, the value
may be set to zero using PRESSURE SENSOR CALIB located
in the Maintenance Menu. See Fig. 31 for the pressure sensor
calibration menu. High end calibration is not necessary.
Fig. 30 — Hydraulic Status Menu
32
Page 33
IMPORTANT: When screen display calibration is complete, do
not press Calibration Enable/Dsable since the new values will
be deleted. Values are kept by exiting the pressure sensor table.
Fig. 31 — Pressure Sensor Calibration Menu
INITIAL START-UP
Preparation
Before starting the chiller, verify:
1.Power is on to the VFD, chiller control panel, water
pumps, and other equipment as required.
2.Cooling tower water is at proper level and at-or-below
design entering temperature.
3.Chiller is charged with refrigerant and all refrigerant
valves are in their proper operating positions.
4.Valves in the evaporator and condenser water circuits are
open and flow is as per design.
NOTE: If the pumps are not automatic, ensure water is circulating
properly.
b. Open evaporator control valve, open condenser drain
valve, close condenser control valve, and close evapora-
tor control valve. Run refrigerant pump for 30 seconds.
c. Start the motor and ramp to 5 Hz in 10 seconds.
d. Once the motor speed reaches 5 Hz, stop motor.
e. Stop refrigerant pump 1 minute after motor speed
reaches 5 Hz, then reset all 4 refrigerant lubrication
valves to close.
f. Three minutes after motor speed reaches 5 Hz, close
first IGV. Status can be followed in Quick Test as
Check State IDLE=0, PreLub=1, Rotat=2, PosLub=3,
End=4.
6.When the VFD is energized and the motor begins to turn,
check for clockwise motor rotation through first stage
sight glasses. See Fig. 32.
IMPORTANT: Do not check motor rotation during coastdown. Rotation may have reversed during equalization of
vessel pressures.
CORRECT MOTOR ROTATION
IS CLOCKWISE WHEN VIEWED
THROUGH SUCTION PIPE
LEADING TO COMPRESSOR
1ST STAGE SIGHT GLASS
CAUTION
Do not permit water or brine that is warmer than 150°F
(65°C) to flow through the evaporator or condenser. Refrigerant overpressure may discharge through the relief device
and result in the loss of refrigerant charge (applicable only
with standard Charlotte rupture disk).
5.Access the PUMPDOWN/LOCKOUT feature from the
Maintenance Menu. Press the End Lockout button on the
touch screen and accept the “press OK to Terminate Lockout?” prompt. The unit is reset to operating mode. The chiller
is locked out at the factory to prevent accidental start-up.
Check Motor Rotation
1.Close the starter enclosure door.
2.Apply 3-phase power to drive.
3.The VFD checks for proper phase rotation as soon as power
is applied to the starter and the PIC6 controls power up.
4.An alarm message will appear on the HMI screen if the
phase rotation is incorrect. If this occurs reverse any 2 of
the 3 incoming power leads to the starter and reapply
power. The motor is now ready for a rotation check.
5.Go to Main Menu, Quick Test and Enable Quick Test following by enabling Motor Rotation Check. This starts the
following sequence:
a. Fully open the first IGV (inlet guide vane).
Fig. 32 — Correct Motor Rotation
Check Refrigerant Lube
1.In Quick Test the refrigerant lube pressure can be checked.
Open evaporator control valve, then run the refrigerant pump.
Pressure drop across the refrigerant pump must exceed 8 psig
(55 kPa). If pressure drop is negative, check the pump rotation. If pressure drop is below 8 psig (55 kPa), check for
clogged filter drier or bearing supply filter.
2.Press the Stop button and listen for any unusual sounds
from the compressor as it coasts to a stop.
To Prevent Accidental Start-Up
Achiller STOP override setting may be entered to prevent accidental start-up during service or whenever necessary. From
the Main Menu, access the General Parameters Menu and use
the down arrow to reach Stop Override on the GENUNIT table.
Change Stop Override to Yes; then execute the command by
touching the lightning button. The message “ALM-276 Protective Limit - Stop Override” will appear in the Home Screen
message area. To restart the chiller, access the same screen and
change the Stop Override option to No.
Check Chiller Operating Condition
Check to be sure that chiller temperatures, pressures, water
flows, and refrigerant levels indicate the system is functioning
properly.
33
Page 34
Instruct the Customer Operator(s)
Ensure the operator understands all operating and maintenance
procedures. Point out the various chiller parts and explain their
function as part of the complete system.
EVAPORATOR-CONDENSER
High side float chamber, relief devices, refrigerant charging valve,
temperature sensor locations, pressure transducer locations,
Schrader fittings, waterboxes and tubes, and vents and drains.
MOTOR COMPRESSOR ASSEMBLY
Guide vane actuator, transmission, motor cooling system, temperature and pressure sensors, sight glasses, motor temperature
sensors, and compressor serviceability.
COMPRESSOR LUBRICATION SYSTEM
Valves, dryers and filters, liquid level switch and inhibitor reclaim system.
CCN and LOCAL start, reset, menu, softkey functions, HMI
operation, occupancy schedule, set points, safety controls, and
auxiliary and optional controls.
PURGE
Check for potential leaks by monitoring purge hours in RUNTIME. Note changes over time.
AUXILIARY EQUIPMENT
Starters and disconnects, separate electrical sources, pumps,
and cooling tower.
DESCRIBE CHILLER CYCLES
Refrigerant, motor cooling, lubrication, and liquid reclaim.
REVIEW MAINTENANCE
Scheduled, routine, and extended shutdowns, importance of a
log sheet, importance of water treatment and tube cleaning, and
importance of maintaining a leak-free chiller.
SAFETY DEVICES AND PROCEDURES
Electrical disconnects, relief device inspection, and handling
refrigerant.
CHECK OPERATOR KNOWLEDGE
Start, stop, and shutdown procedures, safety and operating controls, refrigerant charging, and job safety.
REVIEW THE START-UP, OPERATION, AND MAINTENANCE MANUAL.
FINE TUNING VPF (VARIABLE PRIMARY FLOW)
SURGE PREVENTION
Figures 33-36 show how the parameters defined below will affect the configured surge line. The menu can be found under
Main Menu
Config.
NOTE: Before tuning surge prevention, check for VFD (variable
frequency drive) speed limitation or capacity overrides. If the
Configuration Menu Surge Correction
source of low capacity is found in one of these places, do not proceed with an attempt to tune the Surge Prevention configurations.
If capacity is not reached
and
1.ACTUAL GUIDE VANE POSITION < GUIDE VANE
TRAVEL RANGE
and
2.SURGE PREVENTION ACTIVE = YES (can be identified
in Main Menu
and
3.PERCENT LINE CURRENT < 100%
then the surge line is probably too conservative.
Note the following parameters from HMI when maximum
ACTUAL LINE CURRENT is achieved:
•EVAPORATOR REFRIGERANT TEMP
•EVAPORATOR PRESSURE
•CONDENSER REFRIG TEMP
•CONDENSER PRESSURE
•ACTUAL GUIDE VANE POSITION
•ACTUAL LINE CURRENT
The ACTIVE DELTA TSAT and the CALC REF DELTA
TSAT can be monitored on the Maintenance Menu Correction screen. When ACTUAL DELTA TSAT exceeds
CALC REF DELTA TSAT + ENVELOPE LINE OFFSET
surge prevention will occur.
If ACTUAL GUIDE VANE POSITION is less than 30%, then
increase SURGE DELTA TSMIN in steps of 2ºF (1.2ºC) until
one of the three conditions listed above no longer applies. Do
not change SURGE DELTA TSMAX.
If ACTUAL GUIDE VANE POSITION is greater than 60%,
then increase SURGE DELTA TSMAX in steps of 2ºF (1.2ºC)
until cooling capacity is reached or one of conditions listed
above no longer applies. Do not change SURGE/HGBP DELTA
TSMIN.
If ACTUAL GUIDE VANE POSITION is more than 30%
AND less than 60%, then:
1.Increase SURGE DELTA TSMIN in steps of 2ºF (1.2ºC).
2.Increase SURGE DELTA TSMAX in steps of 2ºF (1.2ºC).
3.Repeat Steps 1 and 2 until one of the conditions listed
above no longer applies.
NOTE: DELTA TSMIN should seldom need to be increased more
than 10 degrees above the selection program value. Likewise,
DELTA TSMAX rarely requires more than a 2ºF (1.2ºC) increase.
If surge is encountered then the controls surge prevention algorithm surge line is probably too optimistic or high. Note following parameters from HMI at surge:
•EVAPORATOR REFRIGERANT TEMP
•EVAPORATOR PRESSURE
•CONDENSER REFRIG TEMP
•CONDENSER PRESSURE
•ACTUAL GUIDE VANE POSITION
•AVERAGE LINE CURRENT
Maintenance Menu Surge Correction)
Surge
34
Page 35
Fig. 33 — Effect of SURGE DELTA TSMIN on Surge
0
5
10
15
20
25
30
35
40
010 20 30 40 50 60 70 80 90 100 110
Tsmin= 30
Tsmin= 40
Tsmin= 50
GV_POS
Delta Tsat
0
5
10
15
20
25
30
35
40
45
0 102030405060708090100110
Tsmax= 60
Tsmax= 70
Tsmax= 80
GV_POS
Delta Tsat
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
50.00
55.00
60.00
0 102030405060708090100110
Shape factor
= -0.020
Shape factor
= -0.040
Shape factor
= -0.050
GV_POS
Delta Tsat
0
5
10
15
20
25
30
35
40
0 102030405060708090100110
Speed Factor
=1.60
Speed Factor
=1.85
Speed Factor
=2.00
GV_POS
Delta Tsat
Prevention
Fig. 34 — Effect of SURGE DELTA TSMAX on Surge
Prevention
Fig. 35 — Effect of SURGE LINE SHAPE FACTOR on
Surge Prevention
Fig. 36 — Effect of SURGE LINE SPEED FACTOR on
Surge Prevention
If ACTUAL GUIDE VANE POSITION is less than 30%, go to
Step 1. If ACTUAL GUIDE VANE POSITION is greater than
60%, then go to Step 3.
1.Do not change SURGE LINE SHAPE FACTOR from the
value selected by Chiller Builder (ECAT). Decrease SURGE
DELTA TSMIN in 1°F steps up to 5 times. Monitor chiller
for surge.
2.If ACTUAL GUIDE VANE POSITION is still less than
30% and Step 1 failed, increase the value of SURGE LINE
SHAPE FACTOR in steps of 0.01 up to 2 times. For example, if surge is encountered when shape factor is –0.06,
increase the SURGE LINE SHAPE FACTOR to –0.05. If
this does not solve the problem, go to Step 5, even if
ACTUAL GUIDE VANE POSITION is less than 30%.
3.Do not change SURGE LINE SHAPE FACTOR from the
value selected by Chiller Builder (ECAT). Decrease SURGE
DELTA TSMAX by 1°F steps up to 5 times. Monitor chiller
for surge.
4.If ACTUAL GUIDE VANE POSITION is greater than
60% and Step 3 failed to eliminate surge, then set SURGE
DELTA TSMAX to 5°F below the value specified by
Chiller Builder (ECAT). Increase the value of the SURGE
LINE SHAPE FACTOR in steps of 0.01 up to 2 times. For
example, if surge is encountered when the SURGE LINE
SHAPE FACTOR is –0.06, increase the SURGE LINE
SHAPE FACTOR to –0.05. If this does not solve the problem, go to Step 5, even if ACTUAL GUIDE VANE POSITION is greater than 60%.
5.If ACTUAL GUIDE VANE POSITION is greater than 30%
but less than 60% or if Step 2 failed (with ACTUAL GUIDE
VANE POSITION less than 30) or if Step 4 failed (with
ACTUAL GUIDE VANE POSITION greater than 60), then
perform this step. Do not change SURGE LINE SHAPE
FACTOR from the value specified by Chiller Builder
(ECAT). Reset SURGE DELTA TSMIN and SURGE
DELTA TSMAX to the value specified by Chiller Builder
(ECAT). Decrease SURGE DELTA TSMIN and SURGE
DELTA TSMAX in steps of 1°F up to 5 times. Monitor
chiller for surge.
If the drive does not slow down adequately at part load, then
the machine may be operating at a point above the configured
“software” surge line and the machine is in surge prevention
mode. Check for a surge protection message on the HMI. If the
unit is not in a surge protection state, then the ENVELOPE
SPEED FACTOR may need to be increased (more aggressive
surge line protection) in combination with a decrease in the
SURGE LINE SHAPE FACTOR.
35
Page 36
OPERATING INSTRUCTIONS
Operator Duties
1.Become familiar with the chiller and related equipment
before operating the chiller.
2.Prepare the system for start-up, start and stop the chiller,
and place the system in a shutdown condition.
3.Maintain a log of operating conditions and document any
abnormal readings.
4.Inspect the equipment, make routine adjustments, and perform a Control Test. Maintain the proper refrigerant levels.
5.Protect the system from damage during shutdown periods.
6. Maintain the set point, time schedules, and other PIC
functions.
Prepare the Chiller for Start-Up
Follow the steps described in the Initial Start-Up section, page 33.
To Start the Chiller
1.Start the water pumps, if they are not automatic.
2.Press the Start/Stop icon on the HMI home screen to start
the system. If the chiller is in the OCCUPIED mode and
the start timers have expired, the start sequence will start.
Follow the procedure described in the Start-Up/Shutdown/
Recycle Sequence section, page 13.
can be overridden to limit the compressor kW, or the pulldown rate can be decreased to avoid a high demand charge
for the short period of high demand operation. Pulldown
rate can be based on load rate or temperature rate and is
viewed at Maintenance Menu RAMP_DEM (Ramping Demand Limit Value). Configuration is done in General Config and rate is done in Service
Parameters.
9.High and low float chambers each provide two sight glasses
for looking into the float chamber to confirm proper float
operation. Note that the sight glasses on the float covers are
used to diagnose a float operation failure of fully closed,
stuck in one position, or fully open. The sight glasses are not
used to identify correct refrigerant charge.
Capacity Controls
To Stop the Chiller
The occupancy schedule starts and stops the chiller automatically once the time schedule is configured.
The unit can be stopped manually using the HMI by pressing
the green Start/Stop icon . The Unit Start/Stop screen is displayed. Press Confirm Stop. The compressor will then follow
the normal shutdown sequence as described in the Start-Up/
Shutdown/Recycle Sequence section on page 13. The chiller is
now in the OFF control mode.
Check the Running System
After the compressor starts, the operator should monitor the display and observe the parameters for normal operating conditions:
1.The normal bearing temperature should be about 95°F
(35°C). Alert will initiate at 104°F (40°C) and Alarm will
be initiated at 122°F (50°C).
2.The First Stage and Second Stage Bearing Temperatures
can be accessed from the Temperatures menu. If the bearing temperature is high or in Alarm/Alert state with the
refrigerant pump running, stop the chiller and determine
the cause of the high temperature. Do not restart the
chiller until corrected.
3.The liquid level sensor on the condenser float chamber
should indicate Closed in the INPUT menu.
4.The bearing pressure drop should exceed 13 psid (90 kPa)
when the compressor is ON, as seen on the HMI Transmission Status screen. If not, an alert will be generated. Typically the reading will be slightly lower at initial start-up.
There will be an alarm if compressor is ON and the bearing pressure drop is less than 10 psid for 10 seconds.
5.The moisture indicator sight glass on the refrigerant motor
cooling line should indicate single phase refrigerant flow
and a dry condition; i.e., solid liquid with no turbulent
bubbles.
6.The condenser pressure and temperature varies with the
chiller design conditions. Typically the pressure will range
from –1.5 to 17.5 psig (–10.3 to 120.6 kPa). with a corresponding temperature range of 60 to 105°F (15 to 41°C).
The condenser entering water temperature should be controlled below the specified design entering water temperature to save on compressor kilowatt requirements.
7.Evaporator pressure and temperature also will vary with
the design conditions. Typical pressure range will be
between –7.7 to –5.0 psig (–50.8 kPa to –35 kPa), with
temperature ranging between 34 and 45°F (1.1 and 7.2°C).
8.The compressor may operate at full capacity for a short time
after the pulldown ramping has ended, even though the
building load is small. The active electrical demand setting
IMPORTANT: Do not attempt to stop the chiller by opening
an isolating knife switch. High intensity arcing may occur.
If the chiller is stopped by an alarm condition, do not restartthe chiller until the problem is diagnosed and corrected.
After Limited Shutdown
No special preparations should be necessary. Follow the regular preliminary checks and starting procedures.
PREPARATION FOR EXTENDED SHUTDOWN
If freezing temperatures are likely to occur in the chiller area,
drain the chilled water, condenser water, and pumpout condenser water circuits to avoid freeze-up. Keep the waterbox
drains open. Ensure that chiller is powered up so purge can automatically remove non-condensables from the low pressure
chiller system during the shutdown. It is recommended not to
store the refrigerant in the unit if below-freezing temperatures
are anticipated or if the extended shutdown extends past a normal seasonal shutdown. In that case both refrigerant and water
side should be purged with positive pressure of dry nitrogen.
After Extended Shutdown
Ensure the water system drains are closed. It may be advisable
to flush the water circuits to remove any soft rust that may have
formed. This is a good time to brush the tubes and inspect the
Schrader fittings on the waterside flow devices for fouling, if
necessary.
Match the actual to the recorded nitrogen pressure prior to the
extended shutdown to determine if a leak is present. Check the
evaporator pressure on the HMI panel and compare it to the
original holding charge that was left in the chiller. If, after adjusting for ambient pressure changes, any change in pressure is
indicated, check for refrigerant leaks. See Check Chiller Tightness section, page 15.
If charge was removed, recharge the chiller by transferring refrigerant from the pumpout storage tank (if supplied). Follow
the Pumpout and Refrigerant Transfer Procedures section on
page 39. Observe freeze-up precautions.
Carefully make all regular preliminary and running system
checks.
36
Page 37
Cold Weather Operation
When the entering condenser water temperature drops very
low, the operator should automatically cycle the cooling tower
fans off to keep the temperature up and tower bypass piping or
condenser water flow modulation may be required. Economizer bypass option may be required for units operating at low lift
outside of the selected lift as identified in the Carrier Equipment Selection Program.
IMPORTANT: A field-supplied water temperature control
system for condenser water should be installed. The system
should be able to maintain the leaving condenser water temperature at design conditions.
Manual Guide Vane Operation
It is possible to manually operate the guide vanes in order to
check control operation or to control the guide vanes in an
emergency. Manual operation is possible by overriding the target guide vane position.
NOTE: Manual control overrides the configured pulldown rate
during start-up and permits the guide vanes to open at a faster
rate. Motor current above the electrical demand setting, capacity
overrides, and chilled water temperature below the control point
override the manual target and close the guide vanes. For descriptions of capacity overrides and set points, see the 19DV
with PIC6 Controls Operation and Troubleshooting guide.
Refrigeration and Service Log
A refrigeration log (as shown in Fig. 37), is a convenient checklist
for routine inspection and maintenance and provides a continuous
record of chiller performance. It is also an aid when scheduling
routine maintenance and diagnosing chiller problems.
Keep a record of the chiller pressures, temperatures, and liquid
levels on a sheet similar to the one in Fig. 37. Automatic recording of data is possible by using CCN devices such as the
Data Collection module and a Building Supervisor. Contact a
Carrier representative for more information.
PLANT______________________ MACHINE MODEL NO.______________________ MACHINE SERIAL NO. _______________________
EVAPORATOR
CONDENSER
COMPRESSOR
DESCRIPTION
REFRIGERANT
WATER
REFRIGERANT
WATER
CAPACITY
BEARINGS
DATE
PRESSURE SAT
LIQUID TEMP
LEVEL
FLOW
TEMP IN
TEMP OUT
PRESSURE
TEMP SAT
FLOW
TEMP IN
TEMP OUT
GV1 ACTUAL POS
GV2 ACTUAL POS
1ST STAGE TEMP
2ND STAGE TEMP
REFRIGERANT LUBE
MOTOR
DRIVE TRAIN
VFDACTUAL SPEED
PURGERUNTIMEAV DAILY PURGE IN 7 DAYS
REMARKS: Indicate shutdowns on safety controls, repairs made, and
inhibitor or refrigerant added or removed. Include amounts.
BEARING DELTA P
REF PUMP DELTA P
RUNNING AMPS
TEMPERATURE
Fig. 37 — Refrigeration and Service Log
38
Page 39
PUMPOUT AND REFRIGERANT
STORAGE
TANK LIQUID
VALV E
OIL
SEPARATOR
PUMPOUT
CONDENSER
WATER SUPPLY
AND RETURN
PUMPOUT
CONDENSER
STORAGE TANK
VAPOR VALVE
2
3
4
5
PRESSURE
RELIEF SAFETY
VALV E
PUMPOUT
COMPRESSOR
REFRIGERANT
CHARGING VALVE
LIQUID LINE
SERVICE
VALV E
CHILLER
CONDENSER
VESSEL
CHILLER
COOLER
VESSEL
10
6
7
11
1a
1b
SERVICE VALVE ON
PUMPOUT UNIT
=
SERVICE VALVE ON
CHILLER (FIELD
SUPPLIED)
=
=
MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUND
STORAGE TANK FOR SERVICE AND OPERATION WORK.
REFRIGERANT
CHARGING VALVE
TRANSFER PROCEDURES
Preparation
For refrigerant side service work the refrigerant can be isolated
in a storage tank. The following procedures and Fig. 38 and 39
describe how to transfer refrigerant from vessel to vessel and
perform chiller evacuation.
CAUTION
If equipped, the power to the pumpout compressor oil heater must be on whenever any valve connecting the pumpout
compressor to the chiller or storage tank is open. Leaving
the heater off will result in oil dilution by refrigerant and
can lead to compressor failure. Similarly a recovery unit
suited for low pressure refrigerant should be used.
WARNING
During transfer of refrigerant into and out of the optional
storage tank, carefully monitor the storage tank level gage.
Do not fill the tank more than 90% of capacity to allow for
refrigerant expansion. Overfilling may result in damage to
the tank or the release of refrigerant which will result in
personal injury or death.
CAUTION
Do not mix refrigerants from chillers that use different
compressor oils and ensure that tanks previously used with
a different refrigerant have been cleaned in order to avoid
refrigerant contamination. Compressor and heat exchanger
damage can result.
CAUTION
Always run the chiller evaporator and condenser water
pumps and always charge or transfer refrigerant as a gas
when the chiller pressure is less than –15 in. Hg (–51 kPa).
Below this pressure, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the evaporator/
condenser tubes and possibly causing tube freeze-up.
CAUTION
Transfer, addition, or removal of refrigerant in spring-isolated
chillers may place severe stress on external piping if springs
have not been blocked in both up and down directions.
Fig. 38 — Typical Optional Pumpout System Piping Schematic with Storage Tank
39
Page 40
PUMP-OUT WITH STORAGE TANK
ECONOMIZER
AND LS FLOAT
9
CONDENSER
COOLER
HS FLOAT
8
1A
PUMP-OUT
COMPRESSOR
RELIEF
VALVE
OIL
SEPARATOR
PUMP-OUT
CONDENSER
CHECK
VALVE
6
STORAGE VESSEL
7
Fig. 39 — Refrigerant Transfer Schematic
The following procedures assume that system is piped in
agreement with Fig. 39. Use the PIC6 Pumpdown/Lockout feature under the Maintenance menu.
NOTE: Instructions assume pumpout unit with four control valves
oriented as shown. Actual equipment may have a different design,
in which case the procedure changes.
Transfer Refrigerant from Storage Tank Vessel to Chiller
1.Equalize refrigerant pressure.
a. Turn on chiller water pumps, establishing water flow
(assumes vacuum condition in chiller system).
b. Open (O) and close (C) pumpout and storage tank
valves according to below table.
VALVE1A1B2345678910
CONDITIONOOCOCCOCCCC
c. Gradually open valve 5 to allow vapor pressure to
equalize between storage tank and chiller system.
d. Open valve 5 fully after the chiller pressure exceeds
–12.7 in. Hg (58.3 kPa abs) corresponding to a saturation temperature of 40°F (4.4°C). The chiller water
10
pumps can be turned off (if desired). When vacuum
pressure is fully equalized, close valve 5.
VALVE1A1B2345678910
CONDITIONO O COCCOCCC C
e. Open valve 7 and 10 to prepare to let higher pressure
in the recovery tank push liquid refrigerant into the
chiller through the evaporator charging/vacuum
valve.
VALVE1A1B2345678910
CONDITIONO O COCCOOCC O
2.Push liquid to chiller; then remove remaining vapor from
storage tank.
a. Open valve 4.
b. Ensure pumpout condenser water is off; then turn on
the pumpout compressor in manual mode to push liquid to chiller. Monitor the storage tank level until tank
is empty of liquid refrigerant.
c. Close charging valves 7 and 10.
40
Page 41
d. Turn off the pumpout compressor.
VALVE1A1B2345678910
CONDITIONOOCOOCOCCCC
e. To prepare for removal of remaining refrigerant vapor
in storage tank, close pumpout valves 3 and 4 and
open valves 2 and 5.
VALVE1A1B2345678910
CONDITIONO O OCCOOCCCC
f. Turn on the pumpout condenser water.
g. Run pumpout unit in auto until the vacuum switch is sat-
isfied. This occurs approximately at 15 in. Hg vacuum
(48 kPa absolute or 7 psia), removing the residual refrigerant vapor from the recovery tank and condensing the a
liquid in the chiller. Close valves 1a, 1b, 2, 5, 6.
VALVE1A1B2345678910
CONDITIONC C CCCCCCCCC
h. Turn off pumpout condenser water.
Transfer Refrigerant from Chiller to Storage Tank Vessel
1.Equalize refrigerant pressure. Be sure to run pumps if saturated refrigerant temperature is near the freezing point to
avoid potential tube freeze up.
a. Dehydrate the refrigerant storage vessel and con-
nected hoses/piping so there are no non-condensables
mixed with the refrigerant.
b. Open (O) and close (C) pumpout and storage tank
valves according to below table.
VALVE1A1B2345678910
CONDITIONOOCOCCOCCCC
c. Gradually open valve 5 to allow vapor pressure to equal-
ize between chiller system and storage tank, and open
valve 7 and 10 to allow liquid refrigerant to drain by
gravity.
VALVE1A1B2345678910
CONDITIONOOCOCCOOCCO
2.Push remaining liquid, followed by refrigerant vapor removal
from chiller. Open valve 7 and 10 to prepare to let higher
pressure in the recovery tank push liquid refrigerant into the
chiller through the evaporator charging/vacuum valve.
a. To prepare for liquid push, turn off the pumpout con-
denser water. Place valves in the following positions.
VALVE1A1B2345678910
CONDITIONOOOCCOOOCCO
b. Run the pumpout compressor in manual until all liquid is
pushed out of the chiller (approximately 45 minutes). To
drain remaining liquid in HS and LS float chambers
refrigerant hoses can be connected to valve 8 and 9 and
this liquid can be drained (or pushed) to the storage tank
prior to next step. Close valves 2, 5, 7 and 10, then stop
compressor.
VALVE1A1B2345678910
CONDITIONOOCCCCOCCCC
c. Turn on pumpout condenser water.
d. Open valves 3 and 4, and place valves in the follow-
ing positions.
e. Run the pumpout compressor until the chiller pressure
reaches –7.5 psig (49.5 kPa abs), followed by turning
off the pumpout compressor. Note it is possible that the
pressure switch is satisfied before this condition. Warm
chiller condenser water will boil off any entrapped liquid refrigerant, and chiller pressure will rise.
f. When chiller pressure increases to –5.5 psig (63 kPa
abs) turn on the pumpout compressor until the pressure reaches 7.5 psig (49.5 kPa abs) again; then turn
off the pumpout compressor. Repeat this process until
the chiller pressure no longer rises.
g. Start the chiller water pumps (condenser and evapora-
tor), establish water flow. At this point turn on the
pumpout compressor in auto until the vacuum switch
is satisfied. This occurs at approximately 15 in. Hg
vacuum (48 kPa abs, 7 psia).
h. Close all valves.
VALVE1A1B2345678910
CONDITIONC C CC CC CCCC C
i. Turn off the pumpout condenser water.
DISTILLING THE REFRIGERANT
1.Transfer the refrigerant from the chiller to the pumpout
storage tank as described in the Transfer Refrigerant from
Chiller to Storage Tank Vessel section.
2.Equalize the refrigerant pressure
a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2, 4, 5, 7 and
10. Open any isolation valves, if present. Open pumpout and storage tank valves 3 and 6; open chiller
valves 1a and 1b.
VALVE1A1B2345678910
CONDITIONO O COCCOCCC C
c. Gradually crack open valve 5 to increase chiller pres-
sure to –7.5 psig (49.5 kPa abs). Slowly feed refrigerant to prevent freeze-up.
d. Open valve 5 fully after the chiller pressure rises
above the freezing point. Let the storage tank and
chiller pressure equalize.
3.Transfer remaining refrigerant.
e. Set valves as per below table and turn on the pumpout
condenser water.
VALVE1A1B2345678910
CONDITIONO O OCCOOCCCC
f. Run the pumpout compressor until all refrigerant is
removed from the storage tank (remaining content in
tank is non-condensables).
g. Turn off the pumpout compressor, close all valves,
and turn off the pumpout condenser water.
VALVE1A1B2345678910
CONDITIONC C CC CC CCCC C
4.Drain the contaminants from the bottom of the storage
tank into a container and dispose of it safely.
VALVE1A1B2345678910
CONDITIONOOCOOCOCCCC
41
Page 42
GENERAL MAINTENANCE
Refrigerant Properties
The standard refrigerant for the 19DV chiller is HFO
R-1233zd(E). At normal atmospheric pressure, HFO R-1233zd(E)
will boil at 65°F (18°C) and must, therefore, be kept in pressurized
containers or storage tanks. The refrigerant is practically odorless
when mixed with air and is noncombustible at atmospheric pressure. Read the Material Safety Data Sheet and the latest ASHRAE
Safety Guide for Mechanical Refrigeration to learn more about
safe handling of this refrigerant.
DANGER
HFO R-1233zd(E) in heavy concentrations may displace
enough oxygen to cause asphyxiation. When handling this
refrigerant, protect the hands and eyes and avoid breathing
fumes.
Adding Refrigerant
Follow the procedures described in the Trim Refrigerant
Charge section, page 44.
CAUTION
Always use the compressor pumpdown function in the
PUMPDOWN/LOCKOUT feature to turn on the evaporator
pump and lock out the compressor when transferring refrigerant. Liquid refrigerant may flash into a gas and cause possible freeze-up and damage to the unit when the chiller pressure is below –15 in. Hg (–53 kPa) for HFO R-1233zd(E).
Adjusting the Refrigerant Charge
If the addition or removal of refrigerant is required to improve
chiller performance, follow the procedures given under the
Trim Refrigerant Charge section, page 44.
Refrigerant Leak Testing
Since parts of the refrigerant system operate in vacuum, noncondensables will enter the cooling systems. The PIC6 HMI
will issue an alert indicating excessive purge operation. Leaks,
which cause frequent purge cycles, should be repaired without
delay. Non-condensable gas in the machine causes higher than
normal condenser pressure, compressor surge at start-up, and
frequent purge cycles, so locate and repair any leaks as soon as
possible. Before making any necessary repairs to a leak, transfer all refrigerant from the vessel.
Leak Rate
It is recommended by ASHRAE that chillers be taken off line
immediately and repaired if the refrigerant leak rate for the entire chiller is more than 10% of the operating refrigerant charge
per year.
Carrier recommends that leaks totaling less than the above rate
but more than a rate of 0.1% of the total charge per year should
be repaired during annual maintenance or whenever the refrigerant is transferred for other service work.
Test After Service, Repair, or Major Leak
If all the refrigerant has been lost or if the chiller has been
opened for service, the chiller or the affected vessels must be
pressure tested and leak tested. Refer to the Leak Test Chiller
section on page 18 to perform a leak test.
WARNING
HFO R-1233zd(E) should not be mixed with air or oxygen
and pressurized for leak testing. In general, this refrigerant
should not be present with high concentrations of air or oxygen above atmospheric pressures, because the mixture can
undergo combustion.
TESTING WITH REFRIGERANT TRACER
Use an environmentally acceptable refrigerant as a tracer for
leak test procedures. Use dry nitrogen to raise the machine
pressure to leak testing levels.
TESTING WITHOUT REFRIGERANT TRACER
Another method of leak testing is to pressurize with nitrogen
only and to use a soap bubble solution or an ultrasonic leak detector to determine if leaks are present.
TO PRESSURIZE WITH DRY NITROGEN
NOTE: Pressurizing with dry nitrogen for leak testing should not
be done if the full refrigerant charge is in the vessel because purging the nitrogen is very difficult.
1.Connect a copper tube from the pressure regulator on the
cylinder to the refrigerant charging valve. Never apply full
cylinder pressure to the pressurizing line. Follow the listed
sequence.
2.Open the charging valve fully.
3.Slowly open the cylinder regulating valve.
4.Observe the pressure gage on the chiller and close the regulating valve when the pressure reaches test level. Do notexceed maximum allowable test pressure 45 psig (310 kPa)
for units marked 57 MAWP (maximum allowable working
pressure) to allow for plenty of margin to avoid from bursting the rupture discs.
5.Close the charging valve on the chiller. Remove the copper tube if it is no longer required.
Repair Leaks, Retest, Standing Vacuum Test
After pressurizing the chiller, test for leaks with an electronic
halide leak detector, soap bubble solution, or ultrasonic leak
detector. Bring the chiller back to atmospheric pressure, repair
any leaks found, and retest.
After retesting and finding no leaks, apply a standing vacuum
test. Then dehydrate the chiller. Refer to the Standing Vacuum
Test and Chiller Dehydration sections (pages 18 and 20) in the
Before Initial Start-Up section.
Checking Guide Vanes
During normal shutdown, when the chiller is off, the guide
vanes are closed. Complete the following steps to adjust position if required (see Fig. 40 and 41):
1.Remove the set screw in the guide vane coupling.
2.Loosen the holddown bolts on the guide vane actuator.
3.Pull the guide vane actuator away from the suction housing.
42
Page 43
Fig. 40 — Guide Vane Actuator
43
Page 44
Fig. 41 — Guide Vane Actuator Detail
NOTE: For first stage, rotate coupling clockwise to close
guide vanes; rotate coupling counterclockwise to open
guide vanes. For second stage, rotate coupling counterclockwise to close guide vanes; rotate coupling clockwise
to open guide vanes.
4.If required, rotate the guide vane shaft fully clockwise for
first stage and counterclockwise for second stage and spotdrill the guide vane actuator shaft. Spot-drilling is necessary when the guide vane actuator sprocket set screws on
the guide vane actuator shaft need to be re-seated.
(Remember: Spot-drill and tighten the first set screw
before spot-drilling for the second set screw.)
Trim Refrigerant Charge
If to obtain optimal chiller performance it becomes necessary to
adjust the refrigerant charge, operate the chiller at design load and
then add or remove refrigerant slowly until the difference between
the leaving chilled water temperature and the evaporator refrigerant temperature reaches design conditions or becomes a minimum. Do not overcharge. Use evaporator sight glasses to visually
determine optimum charge. At steady state full load operation the
evaporator tubes, as viewed in the boiling pool section of the
evaporator, should be covered with liquid refrigerant — if tubes
are covered, maximum efficiency is achieved and there is no benefit of additional refrigerant.
Refrigerant may be added either through the storage tank or directly into the chiller as described in the Charge Unit with Refrigerant section on page 23.
To remove any excess refrigerant, follow the procedure in
Transfer Refrigerant from Chiller to Storage Tank Vessel section on page 41.
WEEKLY MAINTENANCE
Check the Refrigerant Lubrication System
1.Enter INPUT menu and verify that Liquid Level Switch is
closed (if compressor is on).
2.Check moisture indicating sight glass on bearing supply
line (Fig. 42) as well as on the motor/VFD liquid cooling
line (located between vessels feeding of the high side float
chamber; sight glass is located downstream of filter drier).
3.Check that pressure Ref Pump Delta P (PRESSURE Menu
is above 13 psig [89.6 kPa]).
Check for Leaks
Frequent purge pumpout operation is an indication of a leak.
When the daily pumpout limit is exceeded, the controls will
show process Alert 148 — Purge Daily Pumpout Limit Exceeded. If no alert, the purge run-time for the past 24 hours as
well as the past 7 days can be obtained from RUNTIME menu.
SCHEDULED MAINTENANCE
Establish a regular maintenance schedule based on your actual
chiller requirements such as chiller load, run hours, and water
quality. The time intervals listed in this section are offered as
guides to service only.
Service Ontime
The HMI will display resettable “After Service Hrs”, “Total
Pumpout Numbers”, and “Total Pumpout Time” values on the
Main Menu
Run Times screen. These values should be reset
to zero by the service person or the operator each time major service work is completed so that the time between service events
can be viewed and tracked. Previous values and associated dates
should be logged for future reference prior to resetting.
Inspect the Control Panel
Maintenance consists of general cleaning and tightening of
connections. Vacuum the control cabinets to eliminate dust
build-up. If the chiller control malfunctions, refer to the Troubleshooting Guide section on page 47 for control checks and
adjustments.
WARNING
Ensure power to the starter is isolated when cleaning and
tightening connections inside the starter enclosure. Failure
to disconnect power could result in electrocution.
44
Page 45
Inspect the Purge
MOISTURE
INDICATOR
SIGHT GLASS
FOR INSPECTION
NOTE: SECOND INDICATOR IS
LOCATED IN THE MOTOR/VFD
COOLING LINE (ON THE
CONDENSER SIDE) COMING
OFF THE BOTTOM OF THE
HIGH SIDE FLOAT CHAMBER.
With unit off drain, purge tank by entering the Quick Test
menu, opening Drainage Solenoid Valve and Purge Condenser
Solenoid Valve, and turning the Refrigerant pump on to drain
the refrigerant liquid. Let it run for about 15 minutes. Turn on
Purge Compressor and verify that it runs. Close all valves using the Quick Test menu. Clean the condenser coil as required
and replace the strainer as needed.
Changing Refrigerant Lubrication Filters
Change the refrigerant lubrication filter, motor cooling filter,
and bearing filter on an annual basis or when the chiller is
opened for repairs. The filters can be isolated so they can be
changed with refrigerant remaining in the chiller. Strainers
such as 2x refrigerant pump suction strainers, inhibitor reclaim,
and inductor are to be replaced every 5 years or as required
when the machine is open for service. These filters do not contain desiccant for moisture removal so changing the filter will
not change the moisture indicator status.
Change strainers/filters by closing isolation valves and slowly
opening the flare fitting with a wrench and back-up wrench to
relieve pressure.
Inspect Refrigerant Float System
Perform this inspection only if the following symptoms are
seen:
•There is a simultaneous drop in evaporator pressure and
increase in condenser pressure. This will be accompanied
by an increase in kW/Ton.
•The liquid line downstream of the float valve feels warm
and float valve seems stuck based on a visual inspection
through the end cover sight glass. This indicates condenser
gas flowing past the float.
1.Transfer the refrigerant into a pumpout storage tank.
2.Remove the float access cover.
3.Clean the chamber and valve assembly thoroughly. Be
sure the valve moves freely. Ensure that all openings are
free of obstructions.
4.Examine the cover gasket and replace if necessary.
Fig. 42 — Moisture Indicator Sight Glass for inspection
This applies for both the high side float (first float downstream
of condenser) and the low side float (second float downstream
of condenser). The float refrigerant level can be observed
through the two sight glasses located on the float cover under
the condenser. See Fig. 43 for float detail. Inspect the float every five years. Clean the chamber and the float valve assembly.
Be sure that the float moves freely and the ball bearings that
the float moves on are clean.
Fig. 43 — Float System
Inspect Safety Relief Devices and Piping
The relief device on this chiller protects the system against the
potentially dangerous effects of overpressure. To ensure
against damage to the equipment and possible injury to personnel, these devices must be kept in peak operating condition.
As a minimum, the following maintenance is required.
1.At least once a year, disconnect the vent piping at the
valve outlet and carefully inspect the rupture disk for any
evidence of internal corrosion or rust, dirt, scale, leakage,
etc. Verify that vent piping has a section leaning away
from valve to avoid the valve outlet becoming a trap for
dirt, condensation etc.
45
Page 46
2.If corrosion or foreign material is found, do not attempt to
repair or recondition. Replace the safety relief device.
3.If the chiller is installed in a corrosive atmosphere or the
relief devices are vented into a corrosive atmosphere,
inspect the safety relief devices at more frequent intervals.
Compressor Bearing Maintenance
The key to good bearing maintenance is proper lubrication. Inspect the lubrication system regularly and thoroughly. Annual
vibration measurements are recommended to monitor overall
compressor status. Annual refrigerant analysis is recommended
to monitor refrigerant acid and moisture levels over time.
Excessive bearing wear can often be detected through increased vibration or increased bearing temperature. To inspect
the bearings, a complete compressor teardown is required.
Only a trained service technician should perform a compressor
disassembly. Bearings cannot be field inspected; excessive vibration is the primary sign of wear or damage. If either symptom appears, contact an experienced and responsible service
organization for assistance. Annual compressor vibration analysis and trending is recommended for compressor preventative
monitoring and maintenance.
CAUTION
If compressor requires disassembly, cleanliness is of critical
importance to avoid contamination. Small amounts of contamination can result in damage to ceramic bearings.
Inspect the Heat Exchanger Tubes
and Flow Devices
EVAPORATOR AND OPTIONAL FLOW DEVICES
Inspect and clean the evaporator tubes at the end of the first operating season. Because these tubes have internal ridges, a rotary-type tube cleaning system is needed to fully clean the tubes.
Inspect the tubes’ condition to determine the scheduled frequency for future cleaning and to determine whether water
treatment in the chilled water/brine circuit is adequate. Inspect
the entering and leaving chilled water temperature sensors and
flow devices for signs of corrosion or scale. Replace a sensor
or Schrader fitting if corroded or remove any scale if found.
CONDENSER AND OPTIONAL FLOW DEVICES
Since this water circuit is usually an open-type system, the
tubes may be subject to contamination and scale. Clean the
condenser tubes with a rotary tube cleaning system at least
once per year and more often if the water is contaminated. Inspect the entering and leaving condenser water sensors and
flow devices for signs of corrosion or scale. Replace the sensor
or Schrader fitting if corroded or remove any scale if found.
Higher than normal condenser pressures, together with the inability to reach full refrigeration load, usually indicate dirty
tubes or air in the chiller. If the refrigeration log indicates a rise
above normal condenser pressures, check the condenser refrigerant temperature against the leaving condenser water temperature. If this reading is more than what the design difference is
supposed to be, the condenser tubes may be dirty, water flow
may be incorrect, or non-condensables have contaminated the
refrigerant circuit. To resolve, check the purge status. If purge
is operating normally and does not have excessive run time,
that may be an indication to double check pressure transducer
and temperature readings along with flow.
During the tube cleaning process, use brushes specially designed to avoid scraping and scratching the tube wall. Contact
your Carrier representative to obtain these brushes. Do not use
wire brushes. Hard scale may require chemical treatment for its
prevention or removal. Consult a water treatment specialist for
proper treatment.
Water Leaks
The refrigerant moisture indicator on the refrigerant motor
cooling line along with the moisture indicator located in the
liquid refrigerant feeding the compressor bearings (Fig. 2) indicates whether there is water or air leakage during chiller operation. Water leaks should be repaired immediately.
CAUTION
The chiller must be dehydrated after repair of water leaks or
damage may result. See Chiller Dehydration section, page 20.
Water Treatment
Untreated or improperly treated water may result in corrosion,
scaling, erosion, or algae. The services of a qualified water
treatment specialist should be obtained to develop and monitor
a treatment program.
CAUTION
Water must be within design flow limits, clean, and treated
to ensure proper chiller performance and reduce the potential of tube damage due to corrosion, scaling, erosion, and
algae. Carrier assumes no responsibility for chiller damage
resulting from untreated or improperly treated water. If the
unit is going to be stored for an extended period of time,
Carrier has specific long-term storage requirements that are
documented and available from the chiller sales group.
Inspect the VFD
Before working on any starter, shut off the chiller, then open
and tag all disconnects supplying power to the starter.
CAUTION
The motor leads must be disconnected from the VFD before an insulation test is performed. The voltage generated
from the tester can damage the drive components.
CAUTION
Failure to follow these procedures may result in personal
injury or damage to equipment.
TO AVOID an electric shock hazard, verify that the voltage
on the bus capacitors has discharged completely before servicing. Check the DC bus voltage at the power terminal
block by measuring between the +DC and –DC terminals,
between the +DC terminal and the chassis, and between the
–DC terminal and the chassis. The voltage must be zero for
all three measurements.
WARNING
DC bus capacitors retain hazardous voltages after input
power has been disconnected. An isolated multimeter will
be needed to measure DC bus voltage and to make resistance checks.
After disconnecting input power, wait 5 minutes for the DC
bus capacitors to discharge and then check the voltage with
a voltmeter rated for the DC bus voltage to ensure the DC
bus capacitors are discharged before touching any internal
components. Failure to observe this precaution could result
in severe bodily injury or loss of life.
WARNING
The disconnect on the starter front panel does not always deenergize all internal circuits. Open all internal and remote
disconnects before servicing the starter. Failure to follow this
procedure may result in personal injury by electric shock.
46
Page 47
Periodically vacuum accumulated debris on the internal parts.
Use electrical cleaner for electrical parts as required. Perform
visual inspection of the capacitors located on the DC bus and
inductors. Check cooling fan operation. Check condensate
drain for the VFD enclosure.
Power connections on newly installed starters may relax and
loosen after a short period of operation. Turn power off and retighten. Recheck annually thereafter.
CAUTION
Loose power connections can cause voltage spikes, overheating, malfunctioning, or failures.
Recalibrate Pressure Transducers
Once a year, the pressure transducers should be checked
against a pressure gage reading. Check all pressure transducers: evaporator pressure, condenser pressure, refrigerant pump
inlet pressure, refrigerant pump outlet pressure, bearing inlet
pressure, bearing outlet pressure, and optional evaporator entering and leaving water pressure, as well as condenser entering and leaving water pressure. See Fig. 31.
Recalibrate Temperature Thermistors
Entering chilled water (ECW), leaving chilled water (LCW),
entering condenser water (ECDW), leaving condenser water
(LCDW).
Ordering Replacement Chiller Parts
When ordering Carrier specified parts, the following information must accompany an order:
•chiller model number and serial number
•name, quantity, and part number of the part required
•delivery address and method of shipment.
TROUBLESHOOTING GUIDE
Overview
The PIC6 control system has many features to help the operator and technician troubleshoot a 19DV chiller.
•The HMI shows the chiller’s actual operating conditions
and can be viewed while the unit is running.
•The HMI default screen indicates when an alarm occurs.
Once all alarms have been cleared (by correcting the problems), the HMI default screen indicates normal operation.
For information about displaying and resetting alarms and
a list of alert codes, see the 19DV with PIC6 Controls Operation and Troubleshooting manual.
•The Configuration menu screens display information that
helps to diagnose problems with chilled water temperature
control, chilled water temperature control overrides, hot gas
bypass, surge algorithm status, and time schedule operation.
•The quick test and quick calibration feature facilitates the
proper operation and test of temperature sensors, pressure
transducers, the guide vane actuator, refrigerant pump, water
pumps, tower control, and other on/off outputs while the compressor is stopped. It also has the ability to lock off the compressor and turn on water pumps for pumpout operation
(Maintenance Menu). The HMI shows the temperatures and
pressures required during these operations.
•If an operating fault is detected, an alarm indicator is displayed on the HMI default screen. A more detailed message — along with a diagnostic message — is also stored
in the Current Alarms table.
•Review the Alarms History table to view other less critical
events which may have occurred. Compare timing of relevant events and alarms.
For detailed information about alarms, see the 19DV with PIC6
Controls Operation and Troubleshooting manual. Press the bell
icon in the top right corner of the home screen to access current
alarms and alarm history, and to reset alarms.
Checking Display Messages
The first area to check when troubleshooting the 19DV is the
HMI display. Status messages are displayed at the bottom of
the screen, and the alarm icon indicates a fault. For a complete
list of alarms, see the 19DV with PIC6 Controls Operation and
Troubleshooting manual.
Checking Temperature Sensors
All temperature sensors are thermistor-type sensors. This
means that the resistance of the sensor varies with temperature.
All sensors have the same resistance characteristics. If the controls are on, determine sensor temperature by measuring voltage drop; if the controls are powered off, determine sensor
temperature by measuring resistance. Compare the readings to
the values listed in Tables 17 and 18.
RESISTANCE CHECK
Turn off the control power and, from the module, disconnect the
terminal plug of the sensor in question. With a digital ohmmeter,
measure sensor resistance between receptacles as designated by
the wiring diagram. The resistance and corresponding temperature
are listed in Tables 17 and 18. Check the resistance of both wires
to ground. This resistance should be infinite.
VOLTAGE DROP
The voltage drop across any energized sensor can be measured
with a digital voltmeter while the control is energized. Tables 17
and 18 list the relationship between temperature and sensor voltage drop (volts dc measured across the energized sensor). Exercise care when measuring voltage to prevent damage to the sensor leads, connector plugs, and modules. Sensors should also be
checked at the sensor plugs.
CAUTION
Relieve all refrigerant pressure or drain the water before removing any thermowell threaded into the refrigerant pressure boundary. Failure to do so could result in personal injury and equipment damage.
47
Page 48
Table 17 — Thermistor Temperature (F) vs. Resistance/Voltage Drop
Place the sensor in a medium of known temperature and compare that temperature to the measured reading. The thermometer used to determine the temperature of the medium should be
of laboratory quality with 0.5F (0.25C) graduations. The sensor in question should be accurate to within 2F (1.2C).
Note that the PIC6 control module, MAINTENANCE menu,
offers a temperature sensor calibration feature where the sensor
temperature can be offset. Note that only the four water temperatures can be calibrated. To use this feature, place the sensor
at 32°F (0C) or other known temperature. Read the raw temperature and calculate offset based on the reading seen in the
TEMP_CAL menu. Enter and execute the offset, which cannot
exceed ± 2F (1.2C).
See Fig. 2 for sensor locations. The sensors are immersed directly in the refrigerant or water circuits. When installing a
new sensor, apply a pipe sealant or thread sealant to the sensor
threads.
An additional thermistor, factory installed in the bottom of the
evaporator barrel, is displayed as Evap Refrig Liquid Temp on
the TEMPERATURES display screen. This thermistor provides additional protection against a loss of water flow.
DUAL TEMPERATURE SENSORS
For servicing convenience, there are 2 redundant sensors each
on the bearing and motor temperature sensors. If one of the
sensors is damaged, the other can be used by simply moving a
wire. The number 2 terminal in the sensor terminal box is the
common line. To use the second sensor, move the wire from
the number 1 position to the number 3 position. See Fig. 44 or
Fig. 45.
Checking Pressure Transducers
There are 6 factory-installed pressure transducers measuring
refrigerant pressure: condenser pressure, evaporator pressure,
refrigerant pump suction, discharge pressure, bearing inlet
pressure, and bearing outlet pressure.
These transducers can be calibrated if necessary. It is necessary
to calibrate at initial start-up, particularly at high altitude locations, to ensure the proper refrigerant temperature/pressure relationship. Each transducer is supplied with 5 vdc power. If the
power supply fails, a transducer voltage reference alarm occurs. If the transducer reading is suspected of being faulty,
check the TRANSDUCER VOLTAGE REF supply voltage. It
should be 5 vdc ± 0.5 v as displayed in Maintenance Menu
Maintenance Others, where all the transducer voltages are
shown. If the TRANSDUCER VOLTAGE REF supply voltage
is correct, the transducer should be recalibrated or replaced.
Also check that any external inputs have not been grounded
and are not receiving anything other than a 4 to 20 mA signal.
TRANSDUCER REPLACEMENT
Since the transducers are mounted on Schrader-type fittings,
there is no need to remove refrigerant from the vessel when replacing the transducers. Disconnect the transducer wiring. Donot pull on the transducer wires. Unscrew the transducer from
the Schrader fitting. When installing a new transducer, do not
use pipe sealer (which can plug the sensor). Put the plug connector back on the sensor and snap into place. Check for refrigerant leaks.
WARNING
Be sure to use a back-up wrench on the Schrader fitting
whenever removing a transducer, since the Schrader fitting
may back out with the transducer, causing a large leak and
possible injury to personnel.
Fig. 44 — Motor Housing Temperature Sensors
Fig. 45 — First and Second Stage Bearing
Temperature Wiring and Motor Thermistor Wiring
EVAPORATOR, CONDENSER, REFRIGERANT PUMP
SUCTION AND DISCHARGE, BEARING INLET AND
OUTLET PRESSURE TRANSDUCER CALIBRATION
Calibration can be checked by comparing the pressure readings
from the transducer to an accurate refrigeration gage reading.
These readings can be viewed or calibrated from the HMI
screen. The transducer can be checked and calibrated at 2 pressure points. These calibration points are 0 psig (0 kPa) and between 10 and 30 psig (69 and 207 kPa). Connect pressure transducer to Schrader connection. To calibrate these transducers:
1.Shut down the compressor, evaporator, and condenser
pumps.
NOTE: There should be no flow through the heat exchangers.
2.Disconnect the transducer in question from its Schrader
fitting for evaporator or condenser transducer calibration.
For other pressure or flow device calibration, leave the
transducer in place.
NOTE: If the evaporator or condenser vessels are at 0 psig (0 kPa)
or are open to atmospheric pressure, the transducers can be calibrated for zero without removing the transducer from the vessel.
3.Access the PRESSURE or (if water side pressure)
HYDRAULIC STATUS screen and view the particular transducer reading. To calibrate pressure or waterside flow device,
view the particular reading. It should read 0 psig (0 kPa). If
the reading is not 0 psig (0 kPa), but within ± 5 psig (35 kPa),
the value may be set to zero from the Maintenance Menu
while the appropriate transducer parameter is highlighted.
The value will now go to zero.
50
Page 51
4.If the transducer value is not within the calibration range,
the transducer returns to the original reading. If the pressure is within the allowed range (noted above), check the
voltage ratio of the transducer. To obtain the voltage ratio,
divide the voltage (dc) input from the transducer by the
supply voltage signal or measure across the positive
(+ red) and negative (– black) leads of the transducer. The
input to reference voltage ratio must be between 0.80 and
0.11 for the software to allow calibration. Rotate the
waterside flow pressure device from the inlet nozzle to the
outlet nozzle and repeat this step. If rotating the waterside
flow device does not allow calibration, pressurize the
transducer until the ratio is within range. Then attempt calibration again.
5.Installation of pressure transducers into water nozzles using
flushable dirt leg trap is suggested; see Fig. 46. Pressures
can be calibrated between 100 and 250 psig (689.5 and
1723.7 kPa) by attaching a regulated 250 psig (1724 kPa)
pressure (usually from a nitrogen cylinder). For calibration,
access the Pressure Sensor Calibration Menu from the
Maintenance Menu and calibrate the appropriate sensor.
The PIC6 control system does not allow calibration if the transducer is too far out of calibration. In this case, a new transducer
must be installed and re-calibrated.
High Altitude Locations
Because the chiller is initially calibrated at sea level, it is necessary to recalibrate the pressure transducers if the chiller has
been moved to a high altitude location. Note that Atmospheric
Pressure can be adjusted in the Service Parameters Menu (located in the Configuration Menu).
Quick Test
The Quick Test feature is located in the Main Menu. Use this
feature to test chiller status, test the status of various actuators,
view water temperature deltas, and test pump and relays, as
well as control inlet guide vane, EC (Envelope Control) valve,
alarms, condenser, and chilled water pumps. The tests can help
to determine whether a switch is defective or a pump relay is
not operating, as well as other useful troubleshooting issues.
During pumpdown operations, the pumps are energized to prevent freeze-up and the vessel pressures and temperatures are
displayed.
Quick Calibration
Use this menu to calibrate IGVs and the EC valve if it has feedback.
Pumpdown/Lockout
The Pumpdown/Lockout feature, available from the Maintenance Menu, prevents compressor start-up when there is no refrigerant in the chiller or if the vessels are isolated. The Terminate Lockout feature ends the Pumpdown/Lockout after the
pumpdown procedure is reversed and refrigerant is added.
Physical Data
Tables 19-27 and Fig. 47-59 provide additional information on
component weights, compressor fits and clearances, physical
and electrical data, and wiring schematics for the operator’s
convenience during troubleshooting.
WATERBOX
NOZZLE
TWO (2) 2” PIPE NIPPLES
1
SCHRADER VALVE
1
/4 NPTF TEE, BRASS
BALL VALVE
/4 - 18 NPT
Fig. 46 — Suggested Installation of Pressure Transducers into Water Nozzles Using Flushable Dirt Leg Trap
51
Page 52
Table 19 — Component Weights
COMPONENT
SUCTION PIPE ASSEMBLY (INCLUDES FLANGES)569258
INTERSTAGE PIPING346156
DISCHARGE PIPING53
HMI PANEL2411
CONTROL PANEL19086
HIGH SIDE FLOAT CHAMBER COVER5023
LOW SIDE FLOAT CHAMBER COVER5023
PURGE ASSEMBLY263119
ENVELOP CONTROL VALVE / HGBP (OPTION)9744
ECONOMIZER BYPASS VALVE (OPTION)12155
FREE COOLING VALVE (OPTION)20091
LIQUID BYPASS AND ISOLATION VALVE (OPTION)300136
VFD 32VSS08501450658
VFD HARMONIC FILTER800363
VFD CABLE20091
VFD TRAY12457
DV4 COMPRESSOR
lbkg
Table 20 — 19DV Compressor and Motor Weights* — DV4 High-Efficiency Motors
MOTOR
CODE
Voltage: 380/460
* Total compressor weight is the sum of the compressor aerodynamic
† Compressor aerodynamic component weight only, motor weight not
COMPRESSOR
WEIGHT† (lb)
B619510903302810494150
D619511503402810522154
F619512303502810558359
H619513163642810597165
components (compressor weight column), stator, rotor, and end
bell cover weights.
included. Applicable to standard compressors only.
1.0 Variable Frequency Drive (VFD) shall be designed and manufactured in accordance with Carrier engineering requirement.
1.1 All field-supplied conductors and devices must be compliant,
and be installed in compliance with all applicable codes and job
specifications.
1.2 The routing of field-installed conduit and conductors and the location of field-installed devices must not interfere with equipment
access or the reading, adjusting or servicing of any component.
1.3 Equipment installation and all starting and control devices must
comply with details in equipment submittal drawings and literature.
1.4 Contacts and switches are shown in the position they would
assume with the circuit deenergized and the chiller shutdown.
1.5 Warning — Do not use aluminum conductors.
1.6 Warning — Remove panel above VFD bus bar before drilling. Do
not drill into any other VFD cabinet panels.
II. Power Wiring To VFD
2.0 Provide a means of disconnecting branch feeder power to VFD.
Provide short circuit protection and interrupt capacity for branch
feeder in compliance with all applicable codes.
2.1 Metal conduit must be used for the power wires, from VFD to
branch feeder.
2.2 Line side power conductor rating must meet VFD nameplate voltage and chiller full load amps (minimum circuit ampacity).
2.3 Lug adapters may be required if installation conditions dictate that
conductors be sized beyond the minimum ampacity required. Lugs
will accommodate the quantity (#) and size cables (per phase) as
follows. If larger lugs are required, they may be purchased from the
manufacturer of the circuit breaker.
VFD MAX
INPUT AMPS
32VSS085044/0 - 500 kcmil2/0
100KAIC LUG CAPACITY (PER PHASE)
NO. OF
CONDUCTORS
CONDUCTOR
RANGE
GROUND
CONNECTOR
2.4 Compressor motor and controls must be grounded by using
equipment grounding lug provided inside unit-mounted VFD
enclosure.
III. Control Wiring
3.0 Field-supplied control conductors to be at least 18 AWG (American Wire Gage) or larger.
3.1 Ice build start/terminate device contacts, remote start/stop device
contacts and spare safety device contacts (devices not supplied
by Carrier) must have 24 vac rating. Max current is 60 mA, nominal current is 10 mA. Switches with gold-plated bifurcated contacts
are recommended.
3.2 Each integrated contact output can control loads (VA) for evaporator
pump, condenser pump, tower fan low, tower fan high and alarm
annunciator devices rated 5 amps at 115 vac and up to 3 amps at
250 vac.
WARNING
Control wiring required for Carrier to start pumps and tower fan
motors, and established flows must be provided to assure machine
protection. If primary pump, tower fan and flow control is by other
means, also provide a parallel means for control by Carrier. Failure
to do so could result in machine freeze-up or overpressure.
3.3 Do not use control transformers in the VFD enclosure or control
panel as the power source for external or field-supplied contactor
coils, actuator motors or any other loads.
3.4 Do not route control wiring carrying 30 v or less within a conduit
which has wires carrying 50 v or higher or along side wires carrying 50 v or higher.
3.5 Spare 4 to 20 mA output signal is designed for controllers with a
non-grounded 4 to 20 mA input signal and a maximum input
impedance of 500 ohms.
66
Page 67
LEGEND
3TR—
Transformer
4TR—
Transformer
7TB 1,2—
24VAC Low Voltage Wiring Terminal Block
7TB PP1, PP2 —
Main One Phase Power
7TB PE—
Ground
CC—
Purge Compressor/Fan Contactor
HC—
Purge Heater Contactor
HSR—
High Level Switch Relay
LSR—
Low Level Switch Relay
PR—
Purge Vacuum Pump Relay
SIOB—
Purge Input/Output Board
Fig. 55 — 19DV Purge Panel Layout
67
Page 68
LEGEND
SV01—
Condenser Solenoid Valve
SV02—
Compressor Solenoid Valve
SV03—
Pumpout Solenoid Valve
SV04—
Drain Solenoid Valve
SV05—
Regeneration Solenoid Valve
SV06—
Vent Solenoid Valve
TS01—
Purge Compressor Inlet Temperature
Fig. 56 — Purge Schematic
68
Page 69
13
14
16
12
15
1
2
3456
8
9
10
11
17
18
19
7
1
—
FLEX BAR
2
—
DCIB
3
—
COIL ASSEMBLY
4
—
TRANSFORMER 4 kVA
5
—
DC REACTOR
6
—
CURRENT TRANSFORMERS
7
—
RECTIFIER
8
—
AC REACTOR
9
—
RECTIFIER FAN ASSEMBLY
10
—
INVERTER FAN ASSEMBLY
11
—
INVERTER
12
—
COIL ASSEMBLY
13
—
DCIB/HVIB (BACK) CONTROL ASSEMBLY
14
—
TRANSFORMER 4 kVA
15
—
DC REACTOR
16
—
CONTROL ASSEMBLY
17
—
CURRENT TRANSFORMERS
18
—
SERVICE COMMUNICATION PANEL
19
—
DC REACTOR
Fig. 57 — Exploded View of 32VS VFD
69
Page 70
DRIVE CONTROL
INTERFACE BOARD
TRANSFER SWITCH
FOR SINGLE PHASE
SERVICE POWER
(IF PROVIDED)
Fig. 58 — VFD Power Panel Assembly
70
Page 71
71
Fig. 59 — 32VS 850A VFD Control Schematic
Page 72
APPENDIX A — PIC6 SCREEN AND MENU STRUCTURE
HOME
MAIN MENULOG IN/LOG OUTCONFIRM STOPCHOOSE OPERATING MODEALARM MENU
Fig. A — Screen Structure, Basic Level (All) Access (No Password Required)
HOME
MAIN MENULOG IN/LOG OUTCONFIRM
STOPCHOOSE OPERATING MODEALARM MENU
Fig. B — Screen Structure, User Level Access (User Password Required)
72
Page 73
APPENDIX A — PIC6 SCREEN AND MENU STRUCTURE (CONT)
HOME
MAIN MENULOG IN/LOG OUTCONFIRM STOPCHOOSE OPERATING MODEALARM MENU
Fig. C — Screen Structure, Service (Advanced User) / Factory Level Access Password Required
73
Page 74
APPENDIX A — PIC6 SCREEN AND MENU STRUCTURE (CONT)
MAIN MENU DESCRIPTION
ICONDISPLAYED TEXT*ACCESSASSOCIATED TABLE†
General ParametersBasic, User, FactoryGENUINT
TemperaturesBasic, User, FactoryTEMP
PressuresBasic, User, FactoryPRESSURE
Inputs StatusBasic, User, FactoryINPUTS
Outputs StatusBasic, User, FactoryOUTPUTS
Hydraulic StatusBasic, User, FactoryHYDRLIC
Run TimesBasic, User, FactoryRUNTIME
ModesBasic, User, FactoryMODES
Set pointUser, FactorySETPOINT
Configuration MenuUser, FactoryCONFIG
Quick TestFactoryQCK_TEST
Maintenance MenuFactoryMAINTAIN
TrendingBasic, User, FactoryTRENDING
Quick CalibrationFactoryQCK_CALI
* Displayed text depends on the selected language (default is English).
† See the 19DV with PIC6 Controls Operation and Troubleshooting
manual for table details.
74
Page 75
APPENDIX B — CCN COMMUNICATION WIRING FOR MULTIPLE CHILLERS (TYPICAL)
BLACK (G)
WHITE (-)
RED (+)
DRAIN WIRE
NOTE : Field-supplied terminal strip must be located in control panel.
75
Page 76
APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS
19DV MAINTENANCE INTERVAL REQUIREMENTS
WEEKLY
COMPRESSOR NoneCONTROLS Review PIC6 Alarm/Alert History.
EVAPORATOR None.VFDNone.
CONDENSERNone.OIL RECLAIM None.
MONTHLY
COMPRESSOR None.CONTROLS Review and record purge operating time.
ANNUALLY
COMPRESSOR
EVAPORATOR
CONDENSER
LUBRICATION
ASSEMBLY
COMPRESSOR None.CONTROLS None.
EVAPORATOR Perform eddy current test.VFDNone.
CONDENSER
COMPRESSOR
EVAPORATOR None.VFDNone.
CONDENSERNone.PURGE
LUBRICATION
ASSEMBLY
COMPRESSOR None.CONTROLS Do not disconnect control power.
EVAPORATOR
CONDENSER
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
Inspect and clean evaporator tubes. Confirm there is
no foreign debris in the tubes or waterboxes from the
water system. Inspect all pressure relief devices. Leak
test. Verify water pressure differential. Inspect water
pumps. Send refrigerant sample out for analysis.
Replace liquid strainer in inhibitor reclaim line (closes
to evaporator inlet).
Inspect and clean condenser tubes. Leak test. Verify
water pressure differential. Inspect water pumps and
cooling tower.
Replace both refrigerant filter and bearing filter.
EVERY 3 TO 5 YEARS
Inspect float valves and strainers. Perform eddy current test.
EVERY 5 YEARS
Replace gas strainer prior to eductor (or when refrigerant is removed).
Replace lubrication assembly suction strainers (or when refrigerant is removed).
SEASONAL SHUTDOWN
Isolate and drain waterbox. Remove waterbox cover
from one end. Use compressed air to clear tubes.
Isolate and drain waterbox. Remove waterbox cover
from one end. Use compressed air to clear tubes.
CONTROLS
VFD
PURGE
PURGENone.
CONTROLS None.
VFDNone.
PURGEPurge operation is required to remove non-condensables.
Perform general cleaning. Tighten connections. Check
pressure transducers. Confirm accuracy of thermistors.
Perform general cleaning. Tighten connections. Change
refrigerant/motor filter feeding VFD devices. Perform
visual inspection of the capacitors located on the DC bus
and inductors. Check cooling fan operation. Check condensate drain for the VFD enclosure. Change VFD
strainer.
Record total purge Pumpout Numbers and Pumpout
Time. If excessive then leak test and correct. Inspect
moisture sight glasses in line to bearings and VFD.
Replace purge strainer in drain line.
76
Page 77
APPENDIX D — REMOTE CONNECTIVITY COMMISSIONING
ROUTER
MODEM (BACKSIDE OF
RIGHT-HAND DOOR)
Introduction
Cellular Remote Connectivity is a system developed by Carrier
to remotely monitor a chiller. It consists of a PIC6 controller,
IP Switch, cellular modem, and an antenna.
This appendix describes typical commissioning steps required
for a chiller supplied with the Remote Connectivity option.
First locate the cellular antenna which is located in the chiller control panel. See Fig. D. This component is not installed at the factory since optimum mounting location is needed to be identified at
the site as part of Remote Connectivity commissioning.
Installation During Commissioning
1.Disconnect unit power. Use proper lockout-tagout procedures to ensure safety while installing this equipment since
the control panel door will need to be open during installation. See Fig. E for 19DV modem and router installation
locations.
2.In Table A, record serial number of Cellular Modem
which is printed on two labels on either side of the
modem. It begins with the manufacture year, such as
“2017”. This will be required later during commissioning.
Control Box
Cellular
Antenna
PIC5 OR PIC6
Cellular
Modem
Fig. D — Remote Connectivity Option
24Vac
Controls
IP Switch
Fig. E — Modem and Router Installation Locations (19DV)
77
Page 78
APPENDIX D — REMOTE CONNECTIVITY COMMISSIONING (CONT)
Table A — Customer Gateway Data Submittal Information
Submittal Data: Fill out all white fields. Scan or photograph
and submit per Customer Gateway instructions.
CHILLER INFORMATION
ParameterWrite Values BelowDescription
#
PIC6 Software
1.1
Part Number
Chiller Model
1.2
Number
Chiller Serial
1.3
Number
GATEWAY INFORMATION
Parameter Write Values Below
#
Modem
information
2.1
____________________
____________________
____________________
Modem serial number e.g. “2017N089911”:
Modem S/N: ____________________
Shown at bottom of start-up screen, or in the menu under Configuration > Control Identification. E.g. SCG-SR-20M200400
E.g. 19DV-G4CG4C4425H4-
E.g. 5217Q28248
STATUS LED
2.2
CHILLER CONTROLLER INFORMATION
ParameterValueDescription
BACnet
3.1
Identifier
IP Address
3.2
SITE INFORMATION
ParameterValueDescription
#
Jobsite Name
4.1
Jobsite Address
4.2
Service Office
4.3
Service Office
Contact_____________________
4.4
SIGNAL LED Color (per Table B) – (circle one): RED / YELLOW / GREEN
STATE (circle one): SOLID / FLASHING
_________________________
____.____.____.____
_____________________
_____________________
_____________________
_____________________
_____________________
_____________________
Seven digits e.g. 1600001 (from Customer Gateway).
This is the IP address with which the PIC6 is configured (from Customer Gateway).
This is the name by which the jobsite is usually recognized. It will be used to distinguish the
site in the monitoring system.
Full address of jobsite. Used to uniquely identify jobsites in case Jobsite Name is duplicated.
Name of service office that services this site.
Name and Telephone Number (or e-mail address).
78
Page 79
APPENDIX D — REMOTE CONNECTIVITY COMMISSIONING (CONT)
3.Verify that both power wiring and connection to router is
intact. Verify that a SIM card is installed in the modem.
See Fig. F for connections.
Fig. F — Modem Connections
4.Install the provided antenna and route through knockout in
back of control panel. Be sure to observe the warning in
Fig. G.
Fig. G — Arc Flash Warning
5.Apply appropriate protective personal equipment (PPE)
and apply power to unit and verify that modem and router
are powered by confirming power LEDs are on.
6.Wait approximately 5 minutes before proceeding to next
step to allow communication to be fully initiated.
Signal Evaluation
Test the antenna at various positions where it can possibly be
wall mounted. See Fig. H.
Fig. H — Antenna Mounting
At each position, wait at least 5 seconds, and then read the state
of the SIGNAL LED on the modem. The states and conclusions are given in Table B. Signal strength is measured in DBm
(decibel-milliwatts), and is always a negative number.
Table B — Signal Evaluation
COLORSTATEGSM SIGNALACTION
REDFlashing <–85This location will not work
REDSolid–80 through –85
YELLOW Flashing –75 through –80
YELLOW Solid–70 through –75 This location should work
GREEN Flashing –65 through –70 This location should work well
GREEN Solid>–65This location is highly likely to work well
This location may work with a high-gain
antenna, but other options should be
explored first
This location may work, but there may
be occasional delays in sending data,
and it may not be robust over time
Even if a position is found with signal better than –75, several
positions should be tested to find the best signal case. Also
consideration should be given to the accessibility of each position for mounting. Consideration should also be given to the
routed length of the antenna cable — total length 196 in. (5 m).
For final mounting of the antenna secure the bracket to fixed
object and ensure that the antenna body itself does not make
contact with any objects.
Signal strength can also be evaluated with a smart phone if operating on AT&T network. Path to see the phone’s current dBm
signal varies by phone make and model.
Note that the network signal strength is outside of Carrier’s control. If no suitable positions are identified with the standard antenna cable, there are some alternate approaches that can be considered such as trying a high gain antenna (expect +3-5dBm but this
option also has a longer cable), using an AT&T signal boost device, or installing a Remote Connectivity Accessory box (a separately powered box that can be installed up to 100m [330 ft] from
chiller).
The standard offering during the start-up of the chiller is with
the 5 meter cable equipment supplied with the chiller. Any additional requirements to get the remote connectivity fully functional will be part of the chiller installation cost, is not part of
the standard chiller start-up, and is not covered under warranty.
Commissioning the Modem
As the Remote Connectivity feature involves communication
over the cellular network into a server, commissioning requires
support from support personnel at the Customer Gateway.
Fill out Table A, sections 1, 2, and 4, and then call the Customer Gateway at 877-963-1995 and advise that you are commissioning Cellular Remote Connectivity. They will assign a case
number and inform the support personnel. The assigned support engineer will call back within a short time.
Receive Data for Configuring the PIC6 and Enter
in PIC6 HMI
REQUIRED DATA
There are two pieces of data that have to be provided by the
Customer Gateway support engineer and configured into the
PIC6 by the commissioning engineer.
•BACnet Identifier
•IP Address
These parameters should be recorded and kept for future use.
PIC6 CONFIGURATION
For PIC6 the network configuration is entered from Main Menu→ System Configuration [Service level password required].
PIC5 CONFIGURATION
For PIC5, hold fingers on the left side of the Home Screen. The
Setup menu will appear after about 10 seconds; see Fig. I.
79
Page 80
APPENDIX D — REMOTE CONNECTIVITY COMMISSIONING (CONT)
Fig. I — PIC5 Home Screen and Setup Menu
From the Setup Menu, select “Network”. The PIC5 Network
Setup menu will display; see Fig. J.
In Network Configuration do the following:
•“Enable” BACnet/IP
•Verify that BACnet Metric Units is set to the default “No”
•Type in the provided BACnet Identifier from the Customer
Gateway
After making these changes, save the changes and the PIC5
panel will cycle power automatically. For PIC6 BACnet IP is
configured from Main Menu → Protocol ConfigurationT.
INADEQUATE SIGNAL STRENGTH
Sites with inadequate signal strength should work with Carrier
Service for the best on-site solution to activate the remote connectivity. Current alternatives to the standard antenna are a
higher gain antenna, AT&T signal boost device or installing a
Remote Connectivity Accessory box which is a separately
powered box that can be installed up to 100 m (330 ft) from
chiller.
Fig. J — PIC5 Network Setup
Verify that “Enable DHCP” is unchecked and Subnet mask is
set to 255.255.255.0.
Enter the supplied IP Address.
Save the changes.
Enter current Factory Password into PIC5, then go to Configu-
ration → Network Configuration and navigate to page 3 (see
Fig. K) using the bottom right arrow.
Control Panel
Inspecting, 44
Controller identification, modifying, 27
Controls
Description, 12
PIC6 system components, 12
Display messages, checking, 47
Economizer
Description, 4
Equipment required, 15
Evaporator
Description, 4
Extended shutdown
Preparing for, 36
Operation after, 36
Field set up and verification, 31
Filter, changing, 45
Gasketed joints, tightening, 15
Guide vanes
Checking, 42
Operation, manual, 37
Heat exchanger tubes and
flow devices, maintenance, 46
High altitude locations, 51
Initial start-up, 33
Initial start-up checklist, CL-1
Inspecting equipment, 46
Instructing customer operator, 34
Job data required, 15
Leak test procedures (chart), 17
Limited shutdown, operation after, 36
Local start/stop control, 13
Lubrication control, 13
Lubrication cycle, 8
Lubrication system, checking, 44
Machine identification, 31
Maintenance
General, 42
Scheduled, 44
Summary and log sheets, 76
Weekly, 44
Motor rotation, checking, 33
Operating instructions, 36
Operator duties, 36
Physical data, 51
PIC6
Screen and menu reference, 72
System components, 12
Piping
Inspecting before start-up, 21
Maintenance, 45
Pressure transducers
Calibration, 50
Checking, 50
INDEX
Recalibrating, 47
Pumpdown/lockout, 51
Pumpout and refrigerant transfer, 39
Quick test
Perform, 32
Use in troubleshooting, 51
Refrigerant
Adding, 42
Adjusting charge, 42
Charge, 24,25
Float system, inspecting, 45
Leak rate, 42
Leak testing, 42
Properties, 42
Testing after service, repair,
or major leak, 42
Tracer, 18
Trimming charge, 44
Refrigeration cycle, 7
Refrigeration log, 37,38
Replacement parts, ordering, 47
Running system, checking, 36
Safety considerations, 2
Safety valves
Checking before start-up, 21
Maintenance, 45
Schedule, inputting local occupied, 27
Sensor accuracy, checking, 50
Service configurations, inputting, 27
Service ontime, 44
Service tables, configuring, 28
Shipping packaging, removing, 15
Shutdown
After extended, 36
After limited, 36
Local (with HMI), 15
Preparation for extended, 36
Software configuration, 23
Standing vacuum test, 18
Start-Up
Accidental, preventing, 33
Before initial, 15
Chiller dehydration, 20
Control test (quick test), 32
Equipment required, 15
Field set up and verification, 31
Gasketed joints, tightening, 15
Initial, 33
Inspecting water piping, 21
Job data required, 15
Leak test, 18
Safety valves, checking, 21
Schedule, inputting local occupied, 27
Service configurations, inputting, 27
Shipping packaging, removing, 15
Software configuration, 23
Standing vacuum test, 18
Timing sequence, 14
Tracer, 18
Start-up/shutdown/recycle sequence, 13
Surge prevention, 34
System components, 4
Temperature sensors, checking, 47
Thermistor temperature vs.
resistance/voltage drop (C) 49
Thermistor temperature vs.
resistance/voltage drop (F) 48
Time and date, inputting, 27
Troubleshooting guide, 47
Wa te r
Leaks, 46
Treatment, 46
Wiring
Bearing temperature sensors, 50
CCN for multiple chillers, 75
Control panel IOB layer, 59
HMI panel, 58
81
Page 82
Copyright 2019 Carrier Corporation
Catalog No. 04-53190056-01Printed in U.S.A.Form 19DV-CLT-2SSPg 82 6-19Replaces: 19DV-CLT-1SS
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 83
INITIAL START-UP CHECKLIST
FOR 19DV SEMI-HERMETIC TWO-STAGE CENTRIFUGAL LIQUID CHILLER
(Remove and use for job file.)
NOTE: To avoid injury to personnel and damage to equipment or
property when completing the procedures listed in this start-up
checklist, use good judgment, follow safe practices, and adhere
to the safety considerations/information as outlined in preceding
sections of this Start-Up, Operation, and Maintenance Instructions document.
MACHINE INFORMATION:
NAME SALES ORDER NO.
ADDRESS MODEL
CITY STATE ZIP S/N
DESIGN CONDITIONS:
TONS
(kW)
EVAPORATOR******
CONDENSER******
BRINE
FLOW
RATE
TEMPERATUREINTEMPERATURE
OUT
PRESSURE
DROP
PASS
SUCTION
TEMPERATURE
CONDENSER
TEMPERATURE
CHILLER LINE SIDE:Volts FLA OLTA
REFRIGERANT: Type:
CARRIER OBLIGATIONS:Disassembled at Job Site . . . . . . . .Yes No
START-UP TO BE PERFORMED IN ACCORDANCE WITH APPROPRIATE MACHINE START-UP INSTRUCTIONS
JOB DATA REQUIRED:
1. Machine Installation Instructions Yes No
2. Machine Assembly, Wiring and Piping DiagramsYes No
3. Starting Equipment Details and Wiring DiagramsYes No
4. Applicable Design Data (see above)Yes No
5. Diagrams and Instructions for Special ControlsYes No
INITIAL MACHINE PRESSURE:
YESNO
Was Machine Tight?
If Not, Were Leaks Corrected?
Was Machine Dehydrated After Repairs?
RECORD ACTUAL PRESSURE DROPS Evaporator Condenser
CHARGE REFRIGERANT: Initial ChargeFinal Charge After Trim
Catalog No. 04-53190056-01Printed in U.S.A.Form 19DV-CLT-2SSPg CL-1 6-19Replaces: 19DV-CLT-1SS
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 84
INSPECT WIRING AND RECORD ELECTRICAL DATA:
RATINGS:
Motor Voltage
Motor RLA Chiller LRA Rating
Actual Line Voltages: VFDRefrigerant (1TB L1/L2/L3) Pump Controls (1TB LL1/LL2)
Verify 6-in. clearance surrounding all VFD enclosure louvers. Yes No
Record:
L1 to ground
L2 to ground
L3 to ground
L1 to L2
L1 to L3
L2 to L3
NOTE: The % of voltage imbalance should be the same for the two different measurements
Visually inspect the top of the starter cabinet for penetrations and internally for metal particulate:Yes No
VFD Manufacturer ___________________________
VFD Serial Number __________________________
Mfd in _____________________________________
CONTROLS: SAFETY, OPERATING, ETC.
Perform Quick Calibration (Yes/No)
COMPRESSOR MOTOR AND CONTROL PANEL MUST BE PROPERLY AND INDIVIDUALLY
CONNECTED BACK TO THE EARTH GROUND IN THE VFD (IN ACCORDANCE WITH CERTIFIED
DRAWINGS). THE TRANSFORMER SUPPLYING POWER TO THE UNIT SHOULD BE A WYE
SECONDARY WITH SOLIDLY GROUNDED NEUTRAL.
VFD Nameplate I.D. Number ___________________
VFD Nameplate Input Rating ___________________
on ________________________________________
Yes
WATER/BRINE PUMP CONTROL: Can the Carrier controls independently start the pumps?
Condenser Water PumpYes No
Chilled Water PumpYes No
RUN MACHINE:Do these safeties shut down machine?
Condenser Water FlowYes No
Chilled Water FlowYes No
Pump Interlocks (optional)Yes No
INITIAL START:
Line up all valves in accordance with instruction manual:
Start water pumps and establish water flow:
Check refrigerant pump rotation-pressure:
Check compressor motor rotation (first stage suction housing sight glass) and record: Clockwise
Restart compressor, bring up to speed (operating for at least 2 minutes), and shut down.
Any abnormal coastdown noise? If yes, determine cause:Yes No
START MACHINE AND OPERATE. COMPLETE THE FOLLOWING:
A: Trim charge and record under Charge Refrigerant section on page CL-1.
B: Take at least two sets of operational log readings and record.
C: Give operating instructions to owner’s operating personnel. Given at:
Hours
D: Call your Carrier factory representative to report chiller start-up.
E: Return a copy of this checklist to the local Carrier Service office.
IGV2 Travel Limit30 to 100%96.0
IGV2 Minimum Degree0 to 20Deg.2.0
IGV2 Fully Open Degree10 to 100Deg.90.0
IGV2 Actuator Max90 to 120Deg.94.0
IGV2 Position @IGV1 20°10 to 30Deg.28.1
IGV2 Position @IGV1 30°10 to 50Deg.37.2
IGV2 Position @IGV1 50°10 to 80Deg.71.6
VFD Rate Speed Hz10 to 200Hz80.5
Purge Regen Lasting Time0 to 65535min120
Daily PG Pumpout Limit20 to 200min50
Surge Delta Tsmax0 to 150°F70
Surge Delta Tsmin0 to 150°F45
IGV1 Full Load Open Deg.80.0 to 120.0Deg.88.0
IGV1 Minimum Open Deg.0.0 to 10.0Deg.2.0
IGV1 Actuator Max Deg.90.0 to 120.0Deg.109.0
IGV1 Minimum Position0.0 to 100.0%5.0
IGV1 Full Load Position0.0 to 100.0%100.0
Envelope Line Offset0.1 to 3.0°F2.0
Envelope Speed Factor0.00 to 3.002.0
Surge Line Shape Factor–1.000 to 0.000–0.01
DESCRIPTIONRANGEUNITSDEFAULTVALUE
VFD Max Speed Per90 to110%100
VFD Min Speed Per65 to
VFD Start Speed Per 45 to 100%100
VFD Current Limit0 to 99999AMPS250
DESCRIPTIONRANGEUNITSDEFAULTVALUE
Compressor Speed 100%47 to 200Hz50
Motor Rated Line Voltage200 to 13800Volts460
Motor Nameplate Current10 to 2000AMPS200
Motor Rated Load Current10 to 2000AMPS200
Motor Nameplate Voltage200 to 13800Volts460
Motor Nameplate RPM1500 to 5000rpm3000
Motor Nameplate KW0 to 5600KW1500
Skip Frequency 1 0.0 to 102 Hz 30
Skip Frequency 2 0.0 to 102 Hz 30
Skip Frequency 3 0.0 to 102 Hz 30
19DV PIC6 SERVICE PARAMETERS TABLE CONFIGURATION SHEET
DESCRIPTIONRANGEUNITSDEFAULTVALUE
Atmospheric Pressure8.000 to 15.000PSI14.5
GV1 Travel Limit30 to 100%80.7
GV1 Closure at Startup0 to 40%4
Controlled Fluid DB0.5 to 2^F1
Demand Limit At 20 mA10 to 100%40
Demand Limit Prop Band3 to 15%10
Amps or KW Ramp per Min5 to 20%5
Temp Ramp per Min1 to 10^F3
Recycle Shutdown Delta T0.5 to 4^F1
Recycle Restart Delta T2 to 10^F5
Soft Stop Amps Threshold40 to 100%70
Water Flow Verify Time0.5 to 5min5
Power Calibration Factor0.5 to 2—1
Enable Excessive Starts0 to 1—0
Purge Active Temp SP30 to 90—65
Ice Build Option0 to 10
Water Flow Determination0 to 10
Liquid Bypass Selection0 to 10
Purge On Idle Option0 to 10
0 to 30
0 to 30
19DV PIC6 GENERAL PARAMETERS TABLE (GENUNIT) CONFIGURATION SHEET
DESCRIPTIONRANGEUNITSDEFAULTVALUE
Cooling/Heating Select0 to 1
19DV PIC6 SETPOINT TABLE CONFIGURATION SHEET
DESCRIPTIONRANGEUNITSDEFAULTVALUE
Cooling ECW Setpoint15 to 120°F60
Cooling LCW Setpoint–12.2 to 48.9°F45
ICE Build Setpoint–9.4 to 15.6°F104
Heating ECDW Setpoint17.2 to 65.6°F113
Heating LCDW Setpoint20 to 65.6°F40
Base Demand Limit10.0 to 100.0%100.0