You are now the proud owner of an air exchanger. Carnes would like
to thank you for purchasing this unit which, if you carefully follow the
instructions in this guide, will provide you with years of comfort.
First fill the product information section at the end of this guide. The
data is necessary for any claim regarding the warranty.
c Air exchanger with heat recovery
This unit is specially designed to change the air in your home. This air
exchanger will ensure continuous ventilation on request. In winter, it will
dehumidify the ambient air to the level set on the control. Odors will
also be exhausted and the life span of your house will be extended.
The Carnes unit should be installed in an area where the temperature
is always above the freezing point.
The best location for the unit would minimize the total duct length and
the number of elbows. The shorter the ducts and the fewer elbows
there are, the higher the airflow will be.
b Of inlet grilles
The ambient air inlet grilles should be mounted close to areas with
high humidity levels. Most of the time, they are located in the corridor
between the kitchen and the washroom on the ground floor and close
to the washroom in the basement. It should not be located in a room
containing a combustion appliance like a furnace or a fireplace. The
grilles can be installed on the ceiling or a wall. Place the grille within
12” (30cm) of the ceiling.
c Of diffusers
The diffusers are normally installed in corridors as far from the ambient
air intake as possible. This forces the air to circulate through most of
the house.
The diffuser can be installed on a wall or on the ceiling. If it is located
in an occupied area, we recommend mounting the diffuser on the ceil ing. This allows the fresh air to be mixed with the ambient air
reaching the occupants, thus improving the comfort level during a cold
winter day. A wall-mounted diffuser should be located within 12’’ (30
cm) of the ceiling.
before
d Of the humidity control
The control has to be installed where excess humidity is more likely
to be detected. On the ground floor, this place is generally located
between the kitchen and the bathroom.
If you wish to control the humidity level mainly in the basement you
should install the control in this area. Avoid placing the humidistat in an
area with stagnant air, for example behind a door.
The installation of the air exchanger must be in accordance with the
applicable codes in your area.
The unit is designed to be installed on a shelf or suspended to the structure. When the unit is on a shelf, it is
necessary to have some vibration isolators under its casing to prevent the
propagation of noise.
The air exchanger must be leveled horizontally. This is necessary to drain the
condensation out of the unit. A drainage pipe should join the connection in
the bottom of the casing to the building
drainage system.
b Of the exhaust louver
The exhaust louver is installed through an exterior wall at 4’’ (10 cm)
minimum above ground. Attach the intermediary sleeve to the plastic
louver collar with a crew. Seal the gap between the sleeve and the wall.
c Of the inlet louver
The inlet louver is installed through an exterior wall, at more than 6’
(185 cm) from the exhaust louver and more than 18’’ (46 cm) above
ground. Make sure the inlet louver is installed so the insulated vent
duct, joining it to the cabinet, is as straight as possible.
d Of the humidity control
The control should be mounted on the wall, 5’ (150 cm) above the floor.
Drill a hole through the wall so you can pass a wire from the control to the
unit. This wire contains 4 wires in different colors. Connect them to the
wires coming out of the unit. Follow the color code. The wires are at 24V.
Attach the back part of the control to the wall. Install the plastic cover
with the help of the fixing screw and the control button.
To maximize the air exchanger airflow, install the ducts as straight as
possible. We recommend galvanized steel ducts for long ductwork be cause of their ease of cleaning and low flow resistance.
You can run ducts through floors, ceilings, walls or closets and cover
them thereafter with gypsum board. Ducts in unheated areas must be
insulated. The last 3’ (m) of the exhaust duct adjacent to the exhaust
louver should be insulated and covered with a vapor barrier.
Refer to page 18 to 25 to find where the ducts can be connected to the
unit. Slide end of flexible duct over unit port. Wrap 2” (5cm) wide tape
around duct.
If necessary, the gaps between ducts and walls or ceilings can be hidden
with the rubber strips.
f Air balancing
The air supplied through the diffuser should be warmer than 54°F
(12°C). Colder air would make people uncomfortable and create condensation on ducts surfaces. Balancing dampers should be installed in
all the air exchanger ducts. They must be adjusted so the supplied air
temperature is higher than the temperature stated above all year round.
The difference between the exhaust and supply airflow rates should be
negligible (below 10%). Airflows balancing are especially important in
houses with combustion appliances or in area where soil gas is deemed
to be a problem. Use airflow measuring stations and a magnetic gage to
measure the airflow rates.
The speed of each blower can be independently adjusted by turning
the adjustment knob located on the top of the electrical box.
• Wall mounted accessories
The wall mounted accessories must be installed on the wall at approx.
5’ (150cm) from the floor and connected to the device according to the
following illustration.
CNALB
TIHW E
CNALB
CNALB
CNALB
CNALB
TIHW E
TIHW E
TIHW E
TIHW E
CNALB
CNALB
CNALB
CNALB
TIHW E
TIHW E
TIHW E
TIHW E
CNALB
KCALB
GUOR E
EERG N
EERG N
TREV
TREV
TIHW E
RION
ER D
For the connection of the humidistat 611224 or DRY CONTACT, see the
following illustrations according to the installation needs.
WITHOUT recirculation option
WITH recirculation option
Option 1: the unit is in EXCHANGE mode at DEFAULT SPEED