SPECIFICATIONS AND INSTALLATION
DRAIN WATER PUMP
Model HXWA
COMBINATION DIMENSIONS
IP and (SI Metric)
SPECIFICATIONS
INSTALLATION
MICRO SWITCH
CONTROLLED BY FLOAT
3-PRONG
MOLDED CAP
3-WIRE CORD
6 FT. LONG
OUTLET 3/8”
F.P.T.
3000 R.P.M. 3.1 AMP, 115 VAC
OPEN MOTOR
INLET
OVERFLOW
9” (229)
2 GALLON RESERVOIR OF
CAST ALUMINUM
EPOXY CLAD
7/8” (22)
10”
(254)
12” (305)
6”
(152)
2” (51)
ACCESS COVER
PLATE
WEIGHT: 15 LBS. (6.8 Kg.)
A drain water pump is available for mounting directly
below the humidifier cabinet. This pump is ideal for an
application where the building drain is remotely
located or is at a higher elevation than the humidifier
drain connection. This unit operates on a float principle
which automatically starts the pump when the reservoir
is 3/4 full of water.
HEAD AND FLOW DATA
Connect discharge tube or pipe to the 3/8” NPT
discharge hole. Raise the discharge line to the highest
point possible above the pump [20 feet (6m) max.];
form an inverted “U” trap and then slope downward
into drain. This helps to prevent backward siphoning
which causes excessive pump cycling. If drainback
is a problem, the installation of a checkvalve is
recommended.
Maintenance - In normal applications, this pump
requires no scheduled maintenance for efficient
operation. However, to extend motor bearing life it is
recommended that they be oiled every 6 months with
S.A.E. 20.
INVERTED “U”
TRAP
Gallons per hour at:
2’ 6’ 10’ 14’ 16’ 20’
720 660 552 432 372 252