2
The steam manifold may be located below the humidifier if
the installation is made in accordance with Figure C. In this
installation the condensate return line is routed to a drain
below the humidifier and a steam trap is necessary to
prevent live steam from flowing through the condensate line.
The steam manifold cannot be installed in a vertical duct as
shown in Figure D because condensate will not drain
properly and will discharge into the duct.
INSTALLATION OF MANIFOLD
1.
2.
3.
The manifold has an integral mounting flange for ease
of installation. Separate mounting flanges, supplied by
others, are needed for the duct to mate with the
manifold. Refer to Figure E.
Make sure the manifold is oriented properly with the
steam discharge holes facing upward.
Use #12x3/4” self-tapping screws spaced no farther
than 12” to secure the unit to the duct.
Figure D
Figure E
Figure C
INSTALLATION OF STEAM HOSE ANDCONDENSATE
RETURN LINE
It is very important that both the steam hose and condensate return line be installed so that sags are prevented.
The steam is at very low pressure and cannot overcome
resistance caused by water standing in the steam hose.
Water accumulating in sags in the return line will restrict
the flow of condensate and may cause water to be discharged into the duct.
INSTALL THE STEAM HOSE:
If the steam manifold is used with a humidifier having two
cylinders it will require two separate lengths of steam hose
to connect to the two inlets on the steam manifold. Do not
combine the outputs of two cylinders into one steam
hose. See Figure F.
Figure F
If it is difficult to prevent sags, it is recommended that
copper tube be used as a substitute. If copper tube is
used, a minimum of one inch of insulation must be applied
to prevent excessive condensation and contact with the
hot pipe. A short length of steam hose must be used to
connect the plastic cylinder in the humidifier to the copper
tube and another short length to connect the copper tube
to the steam manifold. Size 3/4” copper tube can be used
with steam cylinders having output rates up to 30 pounds
per hour. Size 1-1/2” copper tube should be used with
steam cylinders over 30 pounds per hour. Length
restrictions shown in Table 1 also apply where copper
tube is used and any 90° elbows add approximately three
feet of equivalent length.
Connect the steam hose to the plastic steam cylinder and
steam manifold using the clamps provided.
INSTALL THE CONDENSATE RETURN LINE:
If it is impossible to maintain a 6” drop from the bottom of
the manifold to the top of the humidifier cabinet the return
line can be run to a separate drain. A trap (usually 8” is
sufficient) may be necessary to prevent loss of steam
through the return line. Do not install a trap if the
condensate is returned to the top of the humidifier
cabinet.
If the humidifier has two cylinders, two return lines will be
required. Connect the return line to the inlet at the top of
the humidifier and to the steam manifold using the clamps
provided.
Two Cylinder
Operation
Steam
Inlets
Return Line
Connections