INSTALLATION
Remove any excess insulation from the duct that would
prevent the probe from extending a minimum of 4” (106mm)
into the air stream.
Make a 1-1/2” (38mm) hole in the duct for inserting the
probe.
Use a gasket, sealer, or other means to seal the area
between the unit and the duct to ensure proper operation.
Snap-on
plastic
cover
Aluminum housing
DUCT
Allen screws
Use Allen wrench
to unlock cover (1/16”)
16745-B, page 2
The first (farthest left) adjustable switch controls
whether the unit is in proportional control mode or on/off
control mode. When the switch is off, the unit is in
proportional mode. When it is on, the unit is in on/off mode.
In on/off mode, the output voltage signal is either 0 or 10
Volts. This limits the humidifier to either run at full capacity
when there is a humidity demand, or turn off when there is
no demand. In proportional mode, the output signal to the
humidifier varies between 0-10 Volts, this mode has the
benefit of being able to adjust the unit to operate at a
percentage of its full capacity. Proportional mode allows the
humidifier to regulate at a more precise humidity level
(between 1-2% from setpoint), whereas the on/off mode
has a wider regulatory band but can have some added
operational benefits, including decreased energy
consumption.
The second (middle) adjustable switch controls whether or
not to halt operation of the humidifier when sensing a temperature error. If the switch is off, the humidistat will shut
down the humidity demand signal if the sensor senses a
temperature inside the duct of less than 50 degrees
Fahrenheit. If the switch is on, the humidistat will continue
to operate normally regardless of the temperature inside the
duct. At temperatures less than 50 degrees, the possibility
of condensation accumulating on the inside of the duct work
increases significantly.
The third (farthest right) adjustable switch controls whether
the two seven segment LED displays humidity or temperature when not in setpoint adjustment mode. If the switch is
on, the unit displays temperature (in Fahrenheit). If the
switch is off, the unit displays humidity (in % RH). If the
switch is on, and the temperature being sensed is 100
degrees or greater, any digits beyond the 1’s and 10’s digit
will not be displayed.
On/Off or Proportional Control
Enable or Disable Temperature Error
Humidity or Temperature Display
Self tapping metal
screws or facsimile