FORM 40001
INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS
Fire Dampers - Static and Dynamic
CAUTION! DO NOT INSTALL, USE OR OPERATE THIS EQUIPMENT UNTIL THIS
MANUAL HAS BEEN READ AND UNDERSTOOD. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE USE.
GENERAL NOTES:
When UL is referred to in this document, it represents UL/ULC. This installation instruction
applies to Fire Dampers (static, dynamic, curtain, single, and multi blade types) mounted in the plane
of an UL approved fire partition. The dampers are designed for operation in the vertical or horizontal position with blades running horizontal. The dampers shall not be compressed or stretched into
the opening. Transportation and installation of the dampers shall be handled with the sleeve or
frame. Do not lift the damper with the blades or actuator. Special care shall be given to the damper
before installation and after to insure it is protected against dirt, weather, mortar and drywall dust, wall textures, and paint. Any of these
conditions could cause the damper not to operate correctly and void the warranty. Suitable access to inside duct is to be provided for
inspection and replacement of parts such as heat response devices and actuators per NFPA 90A and local authority having jurisdiction.
As with all joints, contractor must seal duct collar connections in the field after installation.
1. Opening Preparation/Clearances:
The fire barrier opening shall be larger than the damper to allow for thermal expansion and ease of installation. When steel stud/
gypsum or wood stud/gypsum partitions are being used then refer to Fig. 1-3 for additional information and details.
A. Dampers Assemblies Using Two Angles Methods (see note 4a) shall be a minimum of 1/8” (3mm) per linear foot
(305mm) of height and width of sleeved assembly up to a maximum of 1-1/2” (38mm) and a minimum of 1/4” (6mm). For Static Systems
the maximum single section curtain damper is 60” x 60” (1524mm x 1524mm) vertical and 40” x 40” (1016mm x 1016mm) or 48” x 48”
(1219mm x 1219mm) in vertical or horizontal mountings. For Dynamic Systems the maximum single section curtain damper is
36” x 36” (914mm x 914mm) in horizontal mountings, based on type “A” dampers. The maximum single section curtain damper is
36” x 48” (914mm x 1219mm) in vertical mountings and 24” x 24” (610mm x 610mm) in horizontal mountings, based on type “A”
dampers. The maximum single section multi blade damper is 36” x 48” (914mm x 1219mm) in vertical or horizontal mountings. This
method is acceptable for 1-1/2 and 3 hour fire dampers. See Underwriters Laboratories Listings for maximum multiple assembly sizes.
B. Dampers Assemblies Using One Angle Methods (see note 4b) shall be minimum of 1/8” (3mm) per linear foot (305mm)
of height and width of sleeved assembly up to a maximum of 1-1/2” (38mm) and a minimum of 1/4” (6mm). The maximum single
section is the same as in A above. The maximum multi-section is 108” wide or 108” height up to 36 square feet. This method is
acceptable for 1-1/2 hour fire dampers mounted in a masonry/concrete or steel stud/gypsum wall only.
C. Dampers Assemblies Using No Angles Methods (see note 4c) shall be a minimum of 1/4” (6mm) and a maximum of
1/2” (13mm). The maximum single section is the same as in A above. The maximum multi-section is 42” wide x 48” high. This method
is acceptable for 1-1/2 hour fire dampers mounted in a masonry/concrete or steel stud/gypsum wall only.
2. Sleeves shall be of the SAME GAUGE or heavier as the duct to which it is attached, if one of the breakaway connection is used as
defined in the SMACNA Fire, Smoke, and Radiation Damper Guide for HVAC Systems (Fig. 4-6) and in NFPA 90A. Gauges shall
conform to SMACNA or ASHRAE duct standards. Sleeves shall not extend beyond the fire barrier more than 6” (152mm) unless an
actuator or factory installed access door is supplied, then the sleeve may extend up to 16” (406mm). Sleeve shall terminate at both sides
of wall within dimensions shown. If a rigid connection is used, then the sleeve shall be minimum of 16 gauge for dampers up to
36” (914mm) wide by 24” (610mm) high and 14 gauge for dampers exceeding 36” (914mm) wide by 24” (610mm) high.
Round and oval breakaway connections must use either a 4” (102mm) wide draw band or #10 (M5) sheet metal screws spaced equally around the circumference of the duct as follows: 3 screws for duct sizes 22” (559mm) and smaller; 5 screws for duct sizes greater
than 22” (559mm) and up to and including 36” (914mm); 8 screws for duct sizes greater than 36” (914mm). Refer to SMACNA Fire,
Smoke, and Radiation Damper Guide for HVAC Systems for information on Ductmate, Nexus, Ward, TDC and TDF systems and any
additional information (Fig. 5-6). A sleeve may not be required if the damper frame is of sufficient size and shape so the mounting angles
can be directly fastened to it.
FORM 40001, Page 1
CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax: (608)845-6470 www.carnes.com
Fig. 1: Metal Stud/Gypsum Wall Design
1” Min.
Thermal
Gap
Thermal
Gap
2-1/2” Min. Stud
or Runner
1/2” Min. Gypsum
Wallboard
2-1/2” Min. Stud
or Runner
1/2” Min. Gypsum
Wallboard
Retaining
Angle
Damper Sleeve
Fasten with a 1/4” bolt/nut
1/2” welds, #10 sheet metal
screws, or 3/16” pop rivets
on 10” centers.
Damper Sleeve
Fasten with a 1/4” bolt/nut
1/2” welds, #10 sheet metal
screws, or 3/16” pop rivets
on 10” centers.
Retaining
Angle
1-1/2” Mineral
Fiber Blanket
In Cavity, If
Required
Fig. 2: Wood Stud/Gypsum Wall Design
1” Min.
Thermal
Gap
2-1/2” Min. Stud
or Runner
1/2” Min. Gypsum
Wallboard
2-1/2” Min.
Stud or
Runner
1/2” Min. Gypsum
Wallboard
Retaining
Angle
Damper Sleeve
Fasten with a 1/4” bolt/nut
1/2” welds, #10 sheet metal
screws, or 3/16” pop rivets
on 10” centers.
Damper Sleeve
Fasten with a 1/4” bolt/nut
1/2” welds, #10 sheet metal
screws, or 3/16” pop rivets
on 10” centers.
Retaining
Angle
1-1/2” Mineral
Fiber Blanket
In Cavity, If
Required
WALL RATING - 2 HR.
WALL RATING - 1 HR.
WALL RATING - 2 HR.
WALL RATING - 1 HR.