Fire, Smoke & Ceiling Radiation Dampers
Fire Dampers
E-6 www.carnes.com
Model EABA - Type A Curtain Fire Damper
UL 555 Classified 1-1/2 and 3 Hours, For Use in Static Systems
t Application and Design
The Model EABA is UL Classified for installation in walls,
floors and partitions with a fire rating of less than 3 hours.
This damper may be installed vertically or horizontally in
static HVAC systems that automatically shut down in the
event of fire. (See optional 3 hour rating.)
Standard Construction:
Frame: roll formed frame, galvanized steel
Blades: low profile roll formed, galvanized steel
Closure Springs
(horizontal models only): stainless steel
constant force coil
Fusible Link - UL-33: UL listed 165°F (standard),
212°F (optional)
Model EABA meets or complies with the following as a fire damper:
All major building codes, including IBC/ICC International Code
UL 555 Listing 1-1/2 hour - File #R25410
ULC S112
NFPA 90A, 80
Note: Dampers are furnished approx. 1/4” undersized as given duct
dimensions, unless otherwise noted.
*May consist of multi-sections
Standard Sizes (duct) 3 Hour
Min. V or H Max. Vertical or Horizontal Size
4”W x 4”H
102mm x 102mm
*80”W x 40”H
2032mm x 1016mm
*May consist of multi-sections
Options:
Factory Sleeve
Retaining Angles
One Side
Both Sides
3 Hour Rating
Mounting
Horizontal
Vertical
3-11/16”
(94mm)
H*
W*
Standard Sizes (duct) 1-1/2 Hour
Min. V or H Max. Vertical Size Max. Horizontal Size
4”W x 4”H
102mm x 102mm
*120”W x 120”H
3048mm x 3048mm
*120”W x 40”Hor96”W x 48”H
3048mm x 1016mm 2438mm x 1219mm