Carnes DTBA, DTCA, DTDA User Manual

Imperial [IP] Dimensions Metric (SI) in Parentheses
SPECIFICATION SHEET
Models DTAA, DTBA, DTCA, DTDA
Extruded Aluminum Slot Diffuser
T-Bar Mount
CARNES COMPANY © 2010 COPYRIGHT
ALL RIGHTS RESERVED
SUPERSEDES 13100 13100-A
Slot Pattern Adjustments
Parallel Left
Parallel Right
Blankoff
Two Way
DIM
No. of Slots
1 2 3 4 A 1-3/8 (35) 2-11/16 (66) 4 (102) 5-5/16 (135) B 2-1/2 (64) 1-13/16 (46) 1-3/16 (30) 17/32 (13)
Dimensions List in Inches (Millimeters)
Duct= A + 1/4”
A
1-7/16”
(37)
9/16” (14)
3/4” (19)
B
Length
Size
-1/4”
Armstrong®TechZone™Compatible
CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax: (608)845-6470 www.carnes.com
5-3/4” (146)
Performance Data - Armstrong TechZone™ Compatible Linear Supply Diffuser (Models DT, DG, DH)
Correction Factors for Lengths Other than Shown.
Performance data is given for a 4-foot long diffuser. When other lengths are used, apply these corrections to the table data below.
Correction Factors for Vertical Discharge Adjustment of Model CD.
Performance data is given for horizontal discharge. When the deflector is set for vertical discharge, apply these corrections to the table data below.
Correction Factors for Cold Air Performance.
Performance data is based on tests conducted in isothermal conditions. When 20°DT cooling conditions exist, horizontal throw (assuming the presence of a ceiling) is reduced by approximately 35%. To get horizontal throws corrected for 20°DT cooling condi­tions, multiply the table throw data by .65.
This correction does not apply in vertical discharge situations.
Notes on Performance Data
• Performance data is based on tests conducted in accordance with ANSI/ASHRAE Standard 70-1991.
• Actual performance in the field may vary.
• Tests were conducted in isothermal conditions.
• Sound levels are based on a room absorption of 10 db re 10
-12
watts.
Notes on Units of Measure Used
• Air flow is given in cubic feet per minute (CFM).
• Static Pressure is given in inches of water (w.g.).
• Sound data is given in NC.
• Throws are given in feet to terminal velocities of 150, 100 and 50 fpm, respectively.
NC/RC Correction (Add) -3 Throw Correction (Multiply)
No Correction Necessary
Pressure Correction (Multiply) 0.8
Length 24” 36” 48” 60” 72”
Pressure Correction No pressure correction is necessary NC Correction (Add)
-3 -1 0 1 3
Throw Correction (Multiply)
0.75 0.88 1 1.12 1.25
One Slot
Airflow per foot 10 15 20 25 30 40 50 60
Static Pressure 0.008 0.018 0.032 0.050 0.072 0.128 0.202 0.288
Sound (NC) ~ ~ ~ 13 17 25 31 37
Throw 1 2 5 3 5 10 5 8 12 19 11 15 23 15 20 28 18 23 32 20 25 35
Two Slot
Airflow per foot 15 30 45 60 75 90 105 120
Static Pressure 0.005 0.017 0.040 0.072 0.115 0.162 0.222 0.291
Sound (NC) ~ ~ 12 20 28 31 36 40
Throw 1 1 3 5 8 16 10 14 23 13 18 28 16 22 32 19 25 36 22 27 38 24 31 42
Three
Slot
Airflow per foot 20 40 60 80 100 120 140 160 180
Static Pressure 0.003 0.012 0.030 0.054 0.087 0.127 0.173 0.231 0.294
Sound (NC) ~ ~ 10 17 24 29 34 38 42
Throw 1 2 5 5 9 18 9 15 25 14 19 30 17 23 34 20 26 38 22 28 40 24 30 43 26 32 46
Four
Slot
Airflow per foot 40 60 80 100 120 140 160 180 200 240
Static Pressure 0.008 0.017 0.031 0.049 0.070 0.098 0.127 0.162 0.198 0.288
Sound (NC) ~ ~ 13 19 23 27 31 34 38 43
Throw 4 6 15 7 11 22 10 16 28 13 20 32 16 23 35 19 26 38 21 28 40 23 30 42 24 31 44 27 35 48
Return Air Factors
When Channelaire is used as an air return, either ducted or plenum, the pattern control is used for dampering only. With pattern con­trol set at wide open these correction factors apply to the performance data.
NC/RC Correction (Add) -3 Throw Correction (Multiply)
Not Applicable
Pressure Correction (Multiply) 0.8
Loading...