Performance Data - Armstrong TechZone™ Compatible Linear Supply Diffuser (Models DT, DG, DH)
Correction Factors for Lengths Other than Shown.
Performance data is given for a 4-foot long diffuser. When other lengths are used, apply these corrections to the table data below.
Correction Factors for Vertical Discharge Adjustment of Model CD.
Performance data is given for horizontal discharge. When the deflector is set for vertical discharge, apply these corrections to the
table data below.
Correction Factors for Cold Air Performance.
Performance data is based on tests conducted in isothermal conditions. When 20°DT cooling conditions exist, horizontal throw
(assuming the presence of a ceiling) is reduced by approximately 35%. To get horizontal throws corrected for 20°DT cooling conditions, multiply the table throw data by .65.
This correction does not apply in vertical discharge situations.
Notes on Performance Data
• Performance data is based on tests conducted in accordance
with ANSI/ASHRAE Standard 70-1991.
• Actual performance in the field may vary.
• Tests were conducted in isothermal conditions.
• Sound levels are based on a room absorption of 10 db re 10
-12
watts.
Notes on Units of Measure Used
• Air flow is given in cubic feet per minute (CFM).
• Static Pressure is given in inches of water (w.g.).
• Sound data is given in NC.
• Throws are given in feet to terminal velocities of 150, 100 and
50 fpm, respectively.
NC/RC Correction (Add) -3
Throw Correction (Multiply)
No Correction Necessary
Pressure Correction (Multiply) 0.8
Length 24” 36” 48” 60” 72”
Pressure Correction No pressure correction is necessary
NC Correction (Add)
-3 -1 0 1 3
Throw Correction (Multiply)
0.75 0.88 1 1.12 1.25
One
Slot
Airflow per foot 10 15 20 25 30 40 50 60
Static Pressure 0.008 0.018 0.032 0.050 0.072 0.128 0.202 0.288
Sound (NC) ~ ~ ~ 13 17 25 31 37
Throw 1 2 5 3 5 10 5 8 12 19 11 15 23 15 20 28 18 23 32 20 25 35
Two
Slot
Airflow per foot 15 30 45 60 75 90 105 120
Static Pressure 0.005 0.017 0.040 0.072 0.115 0.162 0.222 0.291
Sound (NC) ~ ~ 12 20 28 31 36 40
Throw 1 1 3 5 8 16 10 14 23 13 18 28 16 22 32 19 25 36 22 27 38 24 31 42
Three
Slot
Airflow per foot 20 40 60 80 100 120 140 160 180
Static Pressure 0.003 0.012 0.030 0.054 0.087 0.127 0.173 0.231 0.294
Sound (NC) ~ ~ 10 17 24 29 34 38 42
Throw 1 2 5 5 9 18 9 15 25 14 19 30 17 23 34 20 26 38 22 28 40 24 30 43 26 32 46
Four
Slot
Airflow per foot 40 60 80 100 120 140 160 180 200 240
Static Pressure 0.008 0.017 0.031 0.049 0.070 0.098 0.127 0.162 0.198 0.288
Sound (NC) ~ ~ 13 19 23 27 31 34 38 43
Throw 4 6 15 7 11 22 10 16 28 13 20 32 16 23 35 19 26 38 21 28 40 23 30 42 24 31 44 27 35 48
Return Air Factors
When Channelaire is used as an air return, either ducted or plenum, the pattern control is used for dampering only. With pattern control set at wide open these correction factors apply to the performance data.
NC/RC Correction (Add) -3
Throw Correction (Multiply)
Not Applicable
Pressure Correction (Multiply) 0.8