READ AND SAVE THESE INSTRUCTIONS
INSTALLATION and OPERATION MANUAL
MULTI-FUNCTION RESET VOLUME
CONTROLLER (CSC-3011 NO/NC—DA/RA)
COPYRIGHT © 2008 CARNES COMPANY
ALL RIGHTS RESERVED
18697-A
SUPERCEDES 18697
CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax: (608)845-6470 www.carnes.com
FORM 18697-A, Page 2
NOTE: Screw must be tight and arrows in perfect alignment for device to function properly.
SPECIFICATIONS
Air Consumption: 1.0 scfh @ 20 psig (28.8 scim @ 20 psig)
Ambient Limits: +40°F to +120°F operating
Damper Action: Normally Open or Normally Closed (Field Adjustable)
Thermostat Action: Direct or Reverse Action for Heating or Cooling
Differential Pressure Range: 0.0 to 1.0” water gauge
Main Air Pressure: 15 to 30 psig
Maximum Setpoint Range: Minimum to 1.0” water gauge
Minimum Setpoint Range: 0.0 to 1.0” water gauge
Reset Pressure Span: 0.0 to 10.0 psig (Field Adjustable
Reset Start Point: 0.0 to 10.0 psig (Field Adjustable)
Weight: 11 Ounces (312 Grams)