Carlo gavazzi WM24-96 PROGRAMMING User Manual

Universal Utility Meter Contatore Universale
USER MANUAL MANUALE ISTRUZIONI
WM24-96
Modular system Tecnologia modulare
Automation Components
WM24-96: Modular Universal Utility
Meter and Power Analyzer
Plug and play module system; ener­gy meters, gas and water meter. These are only a few among many other functions performed by your WM24-96. What’s more, Carlo Gavazzi means ISO9001 certification, a working experience of many decades and a widespread presence all over the world. All this because we want our customers to have the
top service and the top products.
Welcome in the Carlo Gavazzi world
and compliments for your smart choice. Visit our website and evaluate our range of products:
www.carlogavazzi.com
T
H
A
N
K
Y
O
U
F
O
R
C
H
O
O
S
I
N
G
C
A
R
L
O
G
A
V
A
Z
Z
I
CARLO GAVAZZI
Automation Components
Plug and Play
Modules
2
Index
Front Panel Description
4
3
CARLO GAVAZZI WM24-96, modular universal utility meter and power analyzer FW rev. 01
TO BEGIN WITH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .04
Front panel description . . . . . . . . . . . . . . . . . . . .04
List and description of displayed measuring pages . . . .04
PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .09
Access to the main menu . . . . . . . . . . . . . . . . . . .09
Change password . . . . . . . . . . . . . . . . . . . . . . . .09
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
CT ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
VT ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Dmd calculation . . . . . . . . . . . . . . . . . . . . . . . . .11
Access to the energy meters menus . . . . . . . . . .13
The functions of the Energy Meters submenu. . .13
Digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Digital output 1 . . . . . . . . . . . . . . . . . . . . . . .16
Pulse digital output . . . . . . . . . . . . . . . . . . . .16
Alarm digital output . . . . . . . . . . . . . . . . . . . .18
Digital output 2 . . . . . . . . . . . . . . . . . . . . . . .19
Setting of serial communication port address . . . .20
Digital filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
End of programming . . . . . . . . . . . . . . . . . . . . . .21
Reset of total gas, water, energy meters . . . . . . .21
Reset of partial gas, water, energy meters . . . . . .22
How to prevent key-pad programming . . . . . . . . .22
USEFUL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . .23
Example of how to use the digital filter . . . . . . . . .23
What is ASY? . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Retransmitted variables . . . . . . . . . . . . . . . . . . . .24
Alarm digital output . . . . . . . . . . . . . . . . . . . . . . .25
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Operations preliminary to the installation . . . . . . .26
Front panel cut-out . . . . . . . . . . . . . . . . . . . . . . .27
Position of slots and relevant modules . . . . . . . . .28
Connection of optional modules . . . . . . . . . . . . . .31
1-phase electrical diagrams . . . . . . . . . . . . . . . . .34
3-phase electrical diagrams . . . . . . . . . . . . . . . . .34
TECHNICAL FEATURES . . . . . . . . . . . . . . . . . . . . .36
We suggest you to keep the original packing in case it is necessary to return the instrument to our Technical Service Department. In order to achieve the best results with your instrument, we recommend you to read this instruction manual carefully.
HOW TO USE THE SYMBOLS
Go to the page where the previous main subject is described.
Go to the page where the next main subject is described.
Go to the page where the subject written on the top of the current page starts. Go to the page where the subject written on the top of the current page ends.
This symbol indicates a particularly important subject or information.
This symbol indicates that more details are given on the current subject.
3
Index
Display “tot -1 .Cn”
2
7
When the instrument is switched on it shows the page below:
4
To begin with
Gas, water, en. meters
pages
6
8
Back-lighted LCD Display.
Display previous page.
Display next page.
Access to programming or setting confirmation.
Front Panel Description
List and Description of Displayed
Measuring Pages
kW
PF
kvar
Hz
kW
PF
kVA
Hz
kW dmd
kVA dmd
Serial communica­tion status: r=Rx; t=Tx (only with serial communicat. module inserted)
If displayed in the measuring mode it means: the alarm is ON.
5
To begin with
Programming
3
Index
4
9
8
VL1-N
VL2-N
VL3-N
V
A L1
A L2
A L3
W L1
W L2
W L3
PF L1
PF L2
PF L3
PF
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
A n
Multiplyer
6
To begin with
tot-Prd
488
The energy meter pages are different according to the set­ting of the instrument (see energy meter menu on pag.13).
If you choose “tot” the instrument displays:
Generated capacitive reactive energy: integration of the sum of single phase reactive powers of quadrant 4 only.
Consumed capacitive reactive energy: integration of the sum of single phase reactive powers of quadrant 2 only.
Generated inductive reactive energy: integration of the sum of single phase reactive powers of quadrant 3 only.
Consumed inductive reactive energy: integration of the sum of single phase reactive powers of quadrant 1 only.
Generated active energy: integra­tion of the sum of single phase negative active powers only.
7
To begin with
dmd calculation
5
Measuring Pages
4
11
8
If you choose tot-1.Cnthe instrument displays all
the pages displayed in the “tot” selection as well as:
If you choose tot-2.Cnthe instrument displays all
the pages displayed in the tot selection as well as:
Consumed active energy: inte­gration of the sum of positive sin­gle phase active powers only.
GAS meter as m3, night tariff.
GAS meter as m3, day tariff.
Total WATER meter as m3.
Total GAS meter as m3.
8
To begin with
System
3
Index
4
10
If you choose tot-Prdthe instrument displays:
Once the energy meter pages are finished, the instrument will display some pages related to the variables connected to the alarm.
Reactive energy consumed dur­ing tariff 1: integration of the sys­tem active power only if positive (same is also for tariff 2, 3 and 4).
Active energy consumed during tariff 1: integration of the system active power only if positive (same is for tariff 2, 3 and 4).
Consumed total reactive energy: integration of the system reactive power only if positive.
Consumed total active energy: integration of the system active power only if positive.
The scrolling of the measuring pages is cyclic, at the end of the cycle, you go back to the first page (see page 4).
Display of alarm settings (AL1 and AL2 if both alarms have been set). It displays the variable connected to the alarm.
9
Programming
En. meters Menu
7
En. meters Display
13
22
When the AL box (normally used for the alarm indication) is active during the programming phase, it means that the displayed value can be modified. This rule applies to all the programming menus.
S
S
Access to the
main menu
Access to the main menu
To access to the programming menus from the measuring and dis-
play phase, press the key : when the instrument asks for the pass­word, enter the correct PASS value
by means of the and keys; afterwards confirm by means of the
key. If the password is correct (when the instrument is new, the password is 0), the instrument goes to the main functions menu.
S
S
S
S
Change Password
This function allows the operator to choose the desired password value (from 0 to 1000). Choose the CnG.PASS function
by means of the and keys,
then press to modify PASS, enter the desired value by means of
the and keys and confirm
the new value with the key.
S
S
10
Programming
Synchronization
5
Measuring Pages
91222
S
S
System
This function allows the operator to select the electrical system choos­ing between three-phase with neu­tral (3P.n) and three-phase without neutral (3P).
Choose by means of and
the SySTEn function, press to enter the menu; then, select the desired system by means of the
and keys and confirm with
.
S
S
S
S
S
S
1.2.. ..2.1
CT ratio
This function allows the user to select the value of the CT ratio. Example: if the CT primary (current transformer) has a current of 300A and the secondary has a current of 5A, the CT ratio corresponds to 60 (obtained by carrying out the fol­lowing calculation: 300/5). Choose the Ct.rAtio function by
means of the and keys; to
enter the menu press ; then select the desired value by means
of the and keys and con-
firm the new value with .
S
S
11
Programming
Digital Input Table
9
Main Menu
9
15
22
S
S
S
S
1.2.. ..2.1
VT ratio
This function allows the user to select the value of the VT ratio. Example: if the primary of the con­nected VT (voltage transformer) is of 20kV and the secondary is 100V, the VT ratio will correspond to 200 (obtained by carrying out the fol­lowing calculation: 20000/100). Choose the Vt.rAtio function by
means of the and keys; to
enter the menu press , then select the desired value by means
of the and keys and con-
firm it with .
By changing the VT and CT ratio, the energy meters are reset.
S
S
S
S
1.2.. ..2.1
Dmd calculation
This function allows the user to select the integration time of the W and VA demand value. To enter these functions select P.int t from
the main menu by the and
keys; to enter the menu press . Set the minutes by means of the
and keys and confirm the
new value with .
S
S
If, for example, you select the value 15 min­utes, the instrument calculates the demand value and updates the value every 15 minutes. See the diagram below.
12
Programming
Meters Submenu
7
Energy Meters Pages
91422
Where: Pc is the contractual power
t1 is the selected integration period
SYNCHRONIZATION OF THE POWER DEMAND CALCU­LATION The synchronization enables the WM24-96, by means of the digital inputs, to start the integration of the power demand at the same time as the official watthour meter. The syn­chronization can be carried out in two ways:
- Without digital input module: the reset and the start of the energy integration are carried out when the instrument is switched on;
- With the digital input module: the synch. starts when one of the digital inputs changes status (that is to say when the tariff changes). Any following change of status resets and synchronizes again the calculation of the power demand.
13
Programming
Retransmitt. en. Meters
11
VT Ratio
9
17
22
S
S
Access to the energy
meters menu
This function allows the user to choose the parameters for the management of the energy meters. Choose the function
COUntEr by means of the and
keys: to confirm the value and enter
the submenu press . By means of
the and keys, it’s possible to scroll all the functions relating to the energy meters that will be described in detail below.
S
S
S
The functions of the Energy
Meters submenu.
Choose the desired function by
means of the and keys,
press to confirm. Its possible to choose the following combina­tions: tot: it enables the combination of total and partial meters (see page
6). tot Prd: it enables the combination of total and partial meters: tariff t1, t2, t3 and t4 are managed by the digital inputs (see page 8);
S
14
Programming
Digital Outputs
9
Main Menu
91622
S
S
1.2.. ..2.1
tot 1.Cn: it enables the combination of total en. meters and day-time and night­time GAS meters (see also Display
pages on page 7). Press to select PrESCAL Cn1, then enter by means
of the keys the weight of every pulse of the IN2 digital input of the GAS
meters and confirm with . The same input IN2 increases alterna­tively the day-time and night-time GAS meters depending on the status of IN3. tot 2.Cn: it enables the combination of total energy meters and Water and Gas meters (see also Display pages on
page 7). Press to select PrESCAL
Cn1 then enter by means of the
keys the weight of every pulse of
the IN3 digital input of the water meters,
confirm with and go to the PrESCAL Cn2 submenu.
Enter by means of the keys the weight of every pulse of the IN2 digital input of the Gas meter, then
confirm with .
S
S
S
S
S
S
1.2.. ..2.1
S
S
1.2.. ..2.1
The prescaler (PrESCAL) sets the weight of the input pulses of the digital input module; e.g.: by setting the prescaler at 10, for each received pulse the meter increases by 10 (10, 20, 30, etc.). The range of the prescaler varies from 0.1 to 100.0.
15
Programming
Digital Output 2
13
Energy Meters
9
19
22
The increase of the Water, Gas meters, the selec­tion of night/day tariff of the gas meters or the change of tariff (t1, t2 t3, t4) is carried out thanks to the combination of the input pulses to the AQ1038 or AQ1042 digital input module, according to the
following table:
SETTING OF
INSTRUMENT
Setting tot Prd Display of total and par­tial multi-tariff energy meters.
Setting tot 1.Cn Display of total en. meters and GAS day/night tariff.
Setting tot 2.Cn Display of total energy meters, GAS and WATER.
RESULT
Tariff 1
Tariff 2
Tariff 3
Tariff 4
GAS night tariff
GAS day tariff
DIGITAL INPUTS
IN 3
ON
ON
OFF
OFF
ON
OFF
OFF
ON
Increase
of
GAS
meters
(*)
Increase
of
WATER
meters
(*)
Increase
of
GAS
meters
(*)
ON
ON
IN 2
(*) The pulse corresponds to an increase of the various meters by the pre-set weight. If the IN 1 contact is closed (3 digital inputs module), the programming from key pad is inhibited. The synchronisation starts at the status modification of the digital inputs (IN2 and IN3) when the instrument is set to tot or tot-Prd.
16
Programming
Alarm Output
11
dmd Calculation
91822
S
S
S
S
Alarm digital out-
put on page 18
Digital output 2
on page 19
Digital OutputsDigital Output 1
This function enables to set the parameters of the digital outputs. Choose the diGout function by
means of the and keys, to
enter the menu press . Then, select one of the following options; PUL: access to the retransmission functions of the totalized energy by means of pulses (see pulse dig­ital output); ALr: access to alarm functions (see alarm digital output); To enter
to relevant menu press ; rEn: enables the activation of the output by means of the serial
communication. Confirm with to enable the function.
Pulse digital output
Select diGout1 PUL by means of
the and keys: press to enter the relevant programming submenu, then choose the meter to be retransmitted among the available ones.
S
S
S
S
S
S
17
Programming
End of Programming
15
Digital Input Table
9
21
22
Digital output 2
on page 19
The list displaying the en. meters to be retransmitted varies depending on the chosen setting of the instrument, that is, depending on the en. meter selection chosen among: tot, tot-Prd, tot-
1.Cn, tot-2.Cn, as reported in the table below:
IF THE SELECTION IS
tot, tot-1.Cn, tot-2.Cn:
kWh (consumed) kWh- (generated) kvarh ind (cons. inductive) kvarh -ind (gen. inductive) kvarh CAP (cons. capacitive) kvarh -CAP (gen. capacitive)
IF THE SELECTION IS
tot-Prd:
kWh tot (total energy meter) kvarh tot (total en. meter) kWh t1 (energy meter tariff 1) kvarh t1 (energy meter tariff 1) and so on for the other tariffs t2-t3-t4.
EXAMPLE OF DISPLAY
Scroll the energy meters displayed by means of and
choose the desired one by means of , then the instru­ment displays the page where the pulses to be associated to the energy are indicated.
S
Select the number of pulses by
means of (pulses/kWh from
1 to 100) and confirm with .
The programming continues for digital output 2.
S
S
1.2.. ..2.1
18
Programming
Digital Filter
13
Energy Meters Menu
92022
S
Alarm Digital Output
This function allows the user to set the parameters of the alarm digital output. Choose the diGout1- ALr function by means
of the keys: to enter the
menu press . Then, set the fol­lowing parameters: VAr: choose the variable to be associated to the alarm activation
by means of the and keys
and confirm with . rnG: choose the decimal point position. on: activation set-point, value of the variable over which the alarm is acti­vated. Select the value of the variable
by means of the and keys
and confirm it with ; oFF: deactivation set-point, value of the variable over which the alarm is deactivated. Select the value of the
variable by means of the and
keys and confirm it with ; nd: normally de-energized output when there is no alarm. nE: normally energized output when there is no alarm. Select the output status by means
of the and keys and con-
firm it with ;
S
S
S
S
S
1.2.. ..2.1
1.2.. ..2.1
S
S
S
S
19
Programming
Useful Information
17
R
etransmittable en. meters
9
23
22
SEC: delay time from the detection of the alarm and the activation of the output. Choose the value of the delay time in seconds by means of
the and keys (up to 255
seconds) and confirm with .
S
S
Digital output 2
1.2.. ..2.1
S
S
Digital Output 2
PUL: access to the retransmission functions of the totalized energy by means of pulses (see pulse digital output on page 16). ALr: access to alarm functions (see alarm output on page 18). To enter
the relevant menu press ; rEn: enables the activation of the output by means of the serial com-
munication. Confirm with to enable the function.
S
S
20
Programming
Meters Reset
15
Meters Increase
92222
RS422/485 Serial port
address
Select AddrESS from the main
menu by means of the and
keys; to enter the menu press , then set the desired serial address value (from 1 to 255) by means of
the and keys and confirm it
with .
S
S
S
S
1.2.. ..2.1
S
S
1.2.. ..2.1
S
1.2.. ..2.1
Digital Filter
Select “FiLtEr by means of the
and keys: to enter the menu press
. Select the parameters to be set
with the and keys, to enter
the menu press . There are two parameters:
- rnG, sets the operating range of the digital filter. The value is expressed as % of the full scale value: set the desired value (from 0 to 100%) by
means of the and keys and
confirm it with ;
S
S
S
-
Coe, sets the filtering coefficient of the instantaneous measure-
ments. Set the desired value (from 1 to 16) by means of the and
keys and confirm it with . By increasing the value both the
stability and the settling time of the measurements are increased.
See also Example 2 in Useful Information on page 23.
S
21
Programming
Up/Down Alarm
19
Digital Output 2
9
25
22
End of programming
To exit from programming and go back to the measuring mode, select End from the main menu by means
of the and keys, confirm it
with
.
S
Measuring mode
S
S
S
S
RESET
Reset of total meters
Select rESEt tot from main
menu by means of the keys,
then confirm with . When the instrument asks for the reset, choose,
by means of the keys:
no to avoid the reset or
yes to confirm it.
Then, press to carry out the com­mand.
S
S
Instrument revision
How to prevent the programming by key-pad
It is possible to prevent any access to programming by modifying the switch in the power supply slot (see the drawing on the left), or closing the contact N 1 of the digital input module if present.
22
Programming
What is ASY
17
Retransmittable meters
10
24
Reset of partial meters
Select rESEt Prt from the main
menu by means of the keys,
then confirm with . When the instrument asks for the reset, choose,
by means of the keys:
no to avoid the reset oryes to confirm it.
Then, press to carry out the com­mand.
S
S
S
S
RESET
Turn the switch using a little screwdriver.
-
Free programming.
- Lock programming.
23
Useful Information
Dimensions
21
End of Programming
27
25
The variables measured by the instrument are correct if the polarities of the inputs have been
observed (as shown in the figure below); if not, measuring and retransmission errors may occur due to the wrong direction of the current flowing in the primary / secondary of the connected current transformer.
Example 2 Use of digital filter”:
it’s necessary to stabilize the displayed value of the VL1-N variable that varies between 222V and 228V. The parameters of the digital filter are to be set as follows:
rnG: the variable varies within the average value, the amplitude of which is equal to ±1.3% of the variable’s rated value, calculated as follows:
(228-222)/2=±3V, then ±3*100/231V=±1.3%, where 231V is the phase-neutral rated value of a 400V input range. The range parameter, that corresponds to the action range of the digital filter, is set at a value which is slightly higher than the percentage amplitude of the fluctuation: e.g. 2%.
CoE: if the new value acquired by the instrument is with­in the filter’s action range, then the new displayed value is cal- culated by summing algebraically to the previous value the variation divided by the filtering coefficient. As a conse­quence, a value which is higher than this coefficient implies a longer settling time and therefore improves the stability. The latter can also be improved by increasing the filtering coeffi­cient: the admitted values are within 1 and 16. Enter the value in consecutive attempts until you reach the desired stability.
24
Useful Information
Installation
19
Digital Output 2
232625
What is ASY
The ASY variable allows the user to control the symmetry of the delta voltages (for systems without neutral) and star volt­ages (for systems with neutral). The variable is calculated according to the following formula:
Where: Vmax is the max. value among VL1-N, VL2-N, VL3-N
Vmin is the min. value among VL1-N, VL2-N, VL3-N Vavg is the average: (VL1-N, VL2-N, VL3-N)/3
The variable is not displayed by the instrument, but can be retransmitted by the analogue or RS422 / 485 output and can be controlled by means of the alarm.
Retransmitted variables
Vmax - Vmin
Vavg
*100ASY=
N° Variable 3-ph with 3-ph with- Notes
neutral out neutral
1 V L-NΣ x Σ = system 2V L-LΣ xxΣ = system 3WΣ xxΣ = system 4 varΣ xxΣ = system 5VAΣ xxΣ = system 6PFΣ xxΣ = system
7PF x x 8 VA dmd x x
9 W dmd x x 10 ASY x x asymmetry 11 The energy meters as per table on page 17
12 All instantaneous variables (powers, currents, voltages)
25
Useful Information
Available Modules
23
E.g.: Use of Digital Filter
23
29
Alarm digital output
The activation of the alarm can be up or down depending on how the ON and OFF parameters have been set, as per the following table:
Displaying of programming menu
It may be useful to know that the menus displayed by the instrument depend on its configuration; e.g.: the instrument will not display the menu rel­evant to the digital outputs if the optional module is not inserted.
It is important that the instrument is switched off when you plug-in or disconnect the modules.
ON-OFF ALARM TYPE
VALUES STATUS
ON OFF UP
ON < OFF DOWN
26
Installation
Position of Slot
21
End of Programming
28
35
Preliminary operations
Before switching the instrument on, make sure that the power supply voltage corresponds to what is shown on the side label of the relevant module.
Before mounting the modules
To know in which slot every module is to be mounted, refer to the figure on page 28. For a correct mounting of the instrument, insert the modules in the relevant slots, then, at the end, enter the central module, which can be a blind type module or an RS232 communication module. The central module will help fixing also the other modules in the relevant slots. To remove the modules use a screwdriver as shown in the picture below.
Gently depress the two fixing tabs. Directions 1-4.
1
Remove the central module from its slot: press your thumb towards points 2-5.
2
Extract the central module.
3
Any other slots that are not used must be filled with the rel­evant blind plug modules sup­plied with the instrument.
27
Installation
Optional Modules conn.
25
Up/Down Alarm
26
31
35
Overall dimensions and panel cut-out
Mounting
Insert the instrument (holding its front) and fasten it (from the back) by fixing the two lateral brackets (1) (supplied with the instrument) to the appropriate location (2), using the two screws (3) supplied with the instrument.
1
3
2
28
Installation
Optional Modules
23
E.g.: Use of Digital Filter
263035
Position of the slots and relevant modules
Available modulesRelay digital output modules
A
B
C
D
PU
PS
IM
AO1058
Single relay
output
AO1035
Dual relay
output
29
Installation
Serial connection
27
Mounting
26
33
35
DESCRIPTION A B C D PU PS IM
RS485/RS422 serial port RS232 serial port Single relay output ✓✓ Single open collector output ✓✓ Dual relay output ✓✓ Dual open coll. output ✓✓ 3 digital inputs 3 digital inputs +AUX Power supply Measuring inputs
Open collector digital output modules
AO1059
Single open
collector output
AO1036
Dual open
collector output
30
Installation
Relay Output conn.
25
Up/down Alarm
263235
AQ1038 3 digital
inputs
AQ1042
3 digital inputs +
aux
AR1034
RS485/422
serial port
AR1039
RS232 serial port
AP1020 90-260 VAC/DC Power supply AP1021 18-60VAC/DC Power supply
AP1025 24VAC Power supply AP1024 48VAC Power supply AP1023 115VAC Power supply AP1022 230VAC Power supply
Digital input modules
Serial port modules
Power supply modules
31
Installation
3-ph 3-wire connection
29
Modules Position
26
35
35
Connection by NPN transistor. AQ1042 Digital input module.
Connection by contacts. AQ1042 Digital input module.
Connection by contacts. AQ1038 Digital input module.
Connection by PNP transistor. AQ1042 Digital input module.
Optional module connectionsDigital inputs
32
Installation
Electrical diagrams
27
Dimensions
263435
This diagram is valid also for the single output open collector module. The value of the load resistances (Rc) must be chosen so that the short­circuit current is lower than 100mA; the VDC voltage must be lower than or equal to 30 VDC.
Relay output
Open collector output
AO1058 Single relay output
AO1035 Dual relay output
AO1059
Single open collector output
AO1036
Dual open collector output
33
Installation
Technical features
31
Digital Input Conn.
26
37
35
RS485/422 (AR1034) serial port
4-wire connection. Additional devices provided with RS485/RS422 (that is RS 1,2,3...N) are connected in paral­lel.
2-wire connection. Additional devices provided with RS485/RS422 (that is RS 1, 2, 3 ...N) are connected in par­allel.
The termination of the serial output is carried out only on the last instrument of the network, by means of a jumper between (Rx+) and (T). We recommend you to use the 4-wire connection: by means of the serial port the data are exchanged faster.
34
Installation
Accuracy
29
Available Modules
263635
Electrical diagramsSingle-phase connection
Three-phase, 4-wire, unbalanced load
L
1
N
L1
N
L3
L2
U
1
3 5
2
4 6
I
L1
L2
L3
8 7 10
9
CT and VT connectionsCT connection
L
1
N
L1
N
L3
L2
U
1
3 5
2
4 6
I
L1
L2
L3
8 7 10
9
CT connection (4-wire system)
CT and VT connections (4-wire system)
35
Installation
Technical Features
33
Serial Connection
26
39
CT connection (3-wire system) ARON
CT and VT connections (3-wire system) ARON
ARON connection, 3-phase, 3-wire, unbalanced load
CT and VT connections (3-wire system)
3 CT and 3 VT connections (3-wire system)
36
Technical Features
Digital Inputs
31
Digital Inputs Connection
38
40
Number of inputs
Current: 3; Voltage: 4
Accuracy
(display, RS232, RS485) In=5A; Pn= In* Un
Current: 0.003Ib to 0.2Ib: ±(0.5% rdg + 3DGT);
0.2Ib to Imax: ±(0.5 rdg + 1DGT);
Phase-neutral voltage: Un range: ±(0.5% rdg + 1DGT) Frequency: ±0.1% Hz Active power/energy: class 1 according to EN61036 Reactive power/energy: class 2 according to EN61268
Apparent power/energy: ±(1% Pn+2dgt), (@25°C ±5°C, R.H. 60%)
Temperature drift
200ppm/°C
Display refresh time
700ms
Display
Back-lighted LCD 70 x 38mm
4x3
1
/2 dgt: instantaneous variables;
1x7
1
/
2
dgt: energy meters.
Measurements
Current, voltage, power, power factor, frequency, energies. TRMS measurements of distorted waves. Coupling type: direct.
Input impedance
208VLL 5(6)AAC (AV4): >200 k(phase-neutral) 400VLL 5(6)AAC (AV5): >900 k(phase-neutral) 100VLL 5(6)AAC (AV6): >200 k(phase-neutral) 660VLL 5(6)AAC (AV7): >900 k(phase-neutral)
Input/Output modules technical features
RS422/RS485 (on request) Multidrop bidirectional (static and dynamic variables)
37
Technical Features
35
Electrical diagrams
36
40
Connections: 2 or 4 wires, max. distance 1200m, termina­tion directly on the instruments.
Addresses: from 1 to 255, selectable by key-pad Protocol: MODBUS/JBUS (RTU)
Data (bidirectional) Dynamic (reading only) System and phase variables: see display pages on page 41 All configuration parameters, activation of the static output. Data format: 1 start bit, 8-data bit, no parity,1 stop bit. Baud-rate: 9600. Insulation: By means of optocouplers, 4000 V
RMS
between
output and measuring input, 4000 V
RMS
between output and
power supply input.
RS232 (optional) Bidirectional (static and dynamic variables)
Connections: 3 wires, max. distance: 15m. Data format: 1 start bit, 8 data bit, no parity, 1 stop bit. Baud-rate: 9600 bauds. Protocol: MODBUS (JBUS) Other features: as per RS422/485
Pulse outputs (optional) Number of outputs: Up to 2 Type:
from 1 to 100 programmable pulses
VON1.2 VDC/ max.
100 mA. V
OFF
30 VDC max.
The outputs can be connected to total and/or partial en. meters. Pulse duration: ON=
220 ms, OFF220 ms
according to DIN43864 Insulation: By means of opto-couplers, 4000 V
RMS
between
output and measuring input, 4000 V
RMS
between output and
power supply input.
Notes: outputs can be open collector or relay type (for the relay output refer to the technical features described in the alarms).
38
Technical Features
General Specifications
33
Electrical diagrams
364040
Alarm outputs (optional) Number of outputs: up to 2, independent Alarm type: up or down alarm, phase asymmetry Control on the variables: All variables listed in the paragraph
retransmitted variables on page 24 can be controlled.
Alarm set-point: can be modified from 0 to 100% of the dis­played electrical scale.
Hysteresis: From 0 to 100% of the displayed scale On-time delay: from 0 to 255 sec Relay status: selectable, normally disabled or normally
enabled. Output type: Relay, SPDT AC 1-8A, 250VAC; DC 12-5A, 24VDC; AC 15-2.5A, 250VAC; DC 13-2.5A, 24VDC
Min. response time: ≤ 150 ms, filters excluded, FFT exclud-
ed, on-time delay: ”0” Insulation: 4000 V
RMS
between output and measuring input,
4000 V
RMS
between output and power supply input. Notes: Outputs can be open collector type or relay type (for the open collector type refer to the technical features described in the pulse outputs).
Digital inputs AQ 1038: N. of inputs: 3 (free-of-voltage) Reading voltage: 24VDC/1mA AQ1042: N. of inputs: 3 + power supply inputs Power supply inputs:
output voltage: 16V<+Aux<24VDC; output current: Max 15mA.
Input frequency: Max 20Hz, duty cycle 50%
Close contact resistance: Max 1k Open contact resistance: Min 100k
Insulation: 4000VRMS
Use of contact 1: lock of the programming from key-pad (when the contact is closed).
39
Technical Features
37
Pulse outputs
36
40
Contacts 2-3: to be used in one of the following ways:
tariff selection (t1-t2-t3-t4) and synchronization;
total meters for day-night GAS tariffs;
total GAS and WATER meters ;
Software functions
Password: Numerical code of 4 dgts; 2 protection levels of the programming data 1st level: Password “0”, no protection 2nd level: Password from 1 to 1000, all data are protected Transformer ratio: CT from 1 to 5000
VT from 1.0 to 1999, with CT x VT 10000 max
Power dmd: Integration time programmable from 1 to 30 min Filter: operating range: from 0 to 100% of the electrical input
scale
Filtering coefficient: 1 to 16 Filtering action: measurements, alarms, serial output Display: up to 4 variables per page, 3-phase system with
neutral:
Page 1:
V L1, V L2, V L3, V LN
Page
2: AL1, AL2, AL2
Page 3:
W L1, W L2, W L3 Page 4: VA L1, VA L2, VA L3 Page 5: var L1, var L2, var L3
Page 6: PF L1, PF L2, PF L3, PF Page 7: W ∑, var ∑, PF ∑, Hz Page 8: W ∑, VA ∑, PF ∑, Hz
Page 9: W dmd, VA dmd Counter pages depending on the instruments setting:
Wh+ tot, Wh- tot, Wh tot, varh tot, varh L+ tot, varh L-, varh C+, varh C-, m3 day GAS, m3 night GAS, m3 GAS, m3 WATER, Wh t1, Wh t2, Wht 3, Wht4, varht1, varht2, varht3, varht4.
40
Technical features
35
Electrical diagrams
36
Power supply specifications
90 to 260 VDC/VAC;18 to 60VDC/VAC; 24 VAC -15%+10% 50-60Hz; 48 VAC -15%+10% 50-60Hz; 115VAC -15%+10% 50-60Hz; 230 VAC -15%+10% 50-60Hz
General features
Operating temperature:
0 to +50°C (32 to 122°F) (H.R. < 90% non condensing)
Storage temperature:
-10 to +60°C (14 to 140°F) (HR. < 90% non-condensing)
Installation category: Cat. III (IEC 664) Key-pad lock: by means of switch placed behind the dis-
play or by means of contact (if module 3 - input contacts ­is present). Insulation: 4000 V
RMS
between inputs/outputs and ground
Dielectric strength: 4000 V
RMS
for 1 minute
EMC
Emissions: EN50082-1 (class A) residential, commercial and light industry environment. Immunity: EN 61000-6-2 (class A) industrial environment.
Other standards
Safety: IEC 61010-1, EN 61010-1 Product: IEC 60688-1, EN 60688-1 Approvals: CE 5(6)A connections: screw-type, max. section 2.5 mm
2
(2 x 1.5mm2)
Housing: Dimensions: 96x96x140 mm Material: ABS, NORYL, PC (front); self-extinguishing: UL 94 V-0 Protection degree: Front: IP65 Connections: IP20 Weight: approx. 400 g (packing included)
OUR PRODUCTION SITES
Carlo Gavazzi Industri A/S Hadsten - DENMARK
Inductive and Capacitive Proximity Sensors in full metal and plastic housings. Photoelectric Sensors. Level Sensors: Optical, Conductive and Capacitive. Ultrasonic Sensors and Magnetic Switches. Limit Switches.
Dupline Field and Installation Bus. Building Automation Systems.
Carlo Gavazzi Ltd Zejtun - MALTA
Solid States Relays. Versions for PCB and panel mounting. AC Semiconductor Motor Controllers Soft starters. Industrial and PCB Relays.
Carlo Gavazzi Controls SpA Belluno - ITALY
Energy Management. Timers and Monitoring Relays. Digital Panel Meters and Temperature Controllers.
SAIET Elettronica SpA Castel Maggiore (BO) - ITALY
Safety and Magnetic Switches, Safety Modules. Mat Systems, Light Curtains, Electrical Transient, Protections. Measuring Systems and Encoders.
OUR SALES NETWORK
Carlo Gavazzi GmbH Wien - AUSTRIA
Carlo Gavazzi NV/SA Vilvoorde - BELGIUM
Carlo Gavazzi Inc. Mississauga, ON - CANADA Montreal, PQ - CANADA
Carlo Gavazzi Handel A/S Hadsten - DENMARK Carlo Gavazzi OY AB Helsinki - FINLAND
Carlo Gavazzi Sarl Roissy - FRANCE
Carlo Gavazzi GmbH Weiterstadt - GERMANY
Carlo Gavazzi UK Ltd Aldershot - GREAT BRITAIN
Carlo Gavazzi SpA Lainate (MI) - ITALY
Carlo Gavazzi Automation Sdn Bhd Petaling Jaya, Selangor - MALAYSIA
Carlo Gavazzi BV Beverwijk - NETHERLANDS
Carlo Gavazzi AS Porsgrunn - NORWAY
Carlo Gavazzi Lda Lisboa - PORTUGAL
Carlo Gavazzi SA Leioa (Bizkaia) - SPAIN
Carlo Gavazzi AB Karlstad - SWEDEN
Carlo Gavazzi AG Steinhausen - SWITZERLAND
Carlo Gavazzi Inc. Buffalo Grove IL - USA
Further information on
www.carlogavazzi.com
CARLO GAVAZZI
Automation Components
WM24 ita-eng code 8020593 02/2003
Loading...