i
µ
CRO-ST∆T
SENSORS
S60, S70
S80, S90
S60 DUCT SENSOR
ADAPTER FOR
THERMOSTAT
This sensor can be mounted
directly onto the back of any
MICRO-STAT, with the
supplied hardware. This
transforms the MICRO-STAT
into a duct-mounted stat.
S70: REMOTE DUCT
SENSOR
This sensor can be mounted
directly onto the supply or return
of the ventilation duct. The
MICRO-STAT may be located
on the wall with temperature
sensing from the remote S70
sensor location.
S80: ROOM SENSOR
This sensor can be wall in any
remote location. The MICROSTAT may be located on the
duct or other location, with
temperature sensing from the
S80 sensor location.
TEMPERATURE SENSORS ARE COMPATIBLE
WITH ALL VICONICS MICRO-STAT SERIES
ELECTRONIC THERMOSTATS.
• WALL
• DUCT
• IMMERSION
The model S60, S70, S80, S90 are part of Viconics' MicroStat Series low voltage RHVAC room temperature and
humidity controls line.
SPECIFICATIONS
Operating Conditions: -18 °C to 82 °C ( 0 °F to 180 °F )
0% to 95% R.H. non-condensing
Sensor: 47 K NTC thermistor
Interchangeability: ± 1 °C @ 25 °C ( ± 1.8 °F @ 77 °F )
Accuracy: ± 2 °C ( for -18 °C to 82 °C )
± 3.6 °F ( for 0 °F to 180 °F )
WIRING
These sensors may be wired using standard copper wiring 12 to
24 Ga. without regard to sensor polarity. Remove the internal
"J4" thermostat jumper. By removing this internal jumper, one of
these sensors may be used instead of the temperature sensor in
the MICRO-STAT.
S90: IMMERSION
SENSOR
This sensor is intended for
temperature control for hot or
cold water, or other fluids. The
sensor features 316 Stainless
teel construction with 1/4"
diameter.
APPLICATIONS
• Remote control of temperature from air return.
• Remote control supply temperature.
• Limitation of supply temperature.
• Auto changeover of damper operation from supply
temperature monitoring.
• Hot water control.
Wire lengths may exceed 100 feet without causing temperature
errors, due to the high 47,000 ohm resistance.
Avoid running long sensor leads closed to, or in the same conduit
as, high voltage and power wiring.
Four sensors may be wired in series / parallel combination in
order to obtain average temperature readings.
ORDER CODE
S60 - 47K
S70 - 47K
S80 - 47K
S90 - 47K
Example: S80 - 47K
DUCT SENSOR ADAPTER FOR
THERMOSTAT
REMOTE DUCT SENSOR
ROOM SENSOR
IMMERSION SENSOR
APPLICATIONS
DIMENSIONS
MICRO-STAT
20
25
15
30
10
C
MICRO-STAT
MICRO-STAT
15
10
MICRO-STAT
15
10
2
MOUNTING HARDWARE
20
25
C
20
25
C
2
30
2
30
S60
S70
LIQUID
PIPE
COMPRESSION FITTING
S90
1/4" BORE-THRU
OR WELL
VENTILATION DUCT
ROOM
S80
S60
( 12.7 mm )
1.6"
( 40.6 mm )
S70
2.8"
( 71 mm )
S80
WIRING
FROM TOP
SECURITY SCREW
HORIZONTAL MODEL
0.5"
1.275"
1
2
3
4
5
6
7
8
9
10
3.275"
( 83 mm )
( 95.8 mm )
WIDTH: 4.5"
( 114 mm )
OR FROM BACK
BASE
3.77"
3.77"
( 95.8 mm )
0.9"
( 22.8 mm )
0.9"
( 22.8 mm )
VICONICS
COVER
1.275"
32 mm
4.5"
( 114 mm )
2.8"
( 71 mm )
S90
6"
Specifications and equipment are subject to change without prior notice.
Represented by:
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.c om
028-2301 - M:\1_BINDER\1_MICSTA\1_ENGLI\2_SENS\SENSOR SE08.DOC 3/21/03
3"
1/4"