CaptiveAire S60 User Manual

i
µ
CRO-STT
SENSORS
S60, S70
S80, S90
S60 DUCT SENSOR ADAPTER FOR THERMOSTAT
This sensor can be mounted directly onto the back of any MICRO-STAT, with the supplied hardware. This transforms the MICRO-STAT into a duct-mounted stat.
S70: REMOTE DUCT SENSOR
This sensor can be mounted directly onto the supply or return of the ventilation duct. The MICRO-STAT may be located on the wall with temperature sensing from the remote S70
sensor location.
S80: ROOM SENSOR
This sensor can be wall in any remote location. The MICRO­STAT may be located on the duct or other location, with temperature sensing from the S80 sensor location.
TEMPERATURE SENSORS ARE COMPATIBLE WITH ALL VICONICS MICRO-STAT SERIES ELECTRONIC THERMOSTATS.
WALL
DUCT
IMMERSION
The model S60, S70, S80, S90 are part of Viconics' Micro­Stat Series low voltage RHVAC room temperature and humidity controls line.
SPECIFICATIONS
Operating Conditions: -18 °C to 82 °C ( 0 °F to 180 °F )
0% to 95% R.H. non-condensing
Sensor: 47 K NTC thermistor
Interchangeability: ± 1 °C @ 25 °C ( ± 1.8 °F @ 77 °F )
Accuracy: ± 2 °C ( for -18 °C to 82 °C )
± 3.6 °F ( for 0 °F to 180 °F )
WIRING
These sensors may be wired using standard copper wiring 12 to 24 Ga. without regard to sensor polarity. Remove the internal "J4" thermostat jumper. By removing this internal jumper, one of these sensors may be used instead of the temperature sensor in the MICRO-STAT.
S90: IMMERSION SENSOR
This sensor is intended for temperature control for hot or cold water, or other fluids. The sensor features 316 Stainless teel construction with 1/4"
diameter.
APPLICATIONS
Remote control of temperature from air return.
Remote control supply temperature.
Limitation of supply temperature.
Auto changeover of damper operation from supply
temperature monitoring.
Hot water control.
Wire lengths may exceed 100 feet without causing temperature errors, due to the high 47,000 ohm resistance.
Avoid running long sensor leads closed to, or in the same conduit as, high voltage and power wiring.
Four sensors may be wired in series / parallel combination in order to obtain average temperature readings.
ORDER CODE
S60 - 47K
S70 - 47K
S80 - 47K
S90 - 47K
Example: S80 - 47K
DUCT SENSOR ADAPTER FOR THERMOSTAT
REMOTE DUCT SENSOR
ROOM SENSOR
IMMERSION SENSOR
APPLICATIONS
DIMENSIONS
MICRO-STAT
20
25
15
30
10
C
MICRO-STAT
MICRO-STAT
15
10
MICRO-STAT
15
10
2
MOUNTING HARDWARE
20
25
C
20
25
C
2
30
2
30
S60
S70
LIQUID
PIPE
COMPRESSION FITTING
S90
1/4" BORE-THRU
OR WELL
VENTILATION DUCT
ROOM
S80
S60
( 12.7 mm )
1.6"
( 40.6 mm )
S70
2.8"
( 71 mm )
S80
WIRING FROM TOP
SECURITY SCREW
HORIZONTAL MODEL
0.5"
1.275"
1 2 3 4
5
6 7 8 9
10
3.275"
( 83 mm )
( 95.8 mm )
WIDTH: 4.5"
( 114 mm )
OR FROM BACK
BASE
3.77"
3.77"
( 95.8 mm )
0.9"
( 22.8 mm )
0.9"
( 22.8 mm )
VICONICS
COVER
1.275" 32 mm
4.5"
( 114 mm )
2.8"
( 71 mm )
S90
6"
Specifications and equipment are subject to change without prior notice.
Represented by:
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.c om
028-2301 - M:\1_BINDER\1_MICSTA\1_ENGLI\2_SENS\SENSOR SE08.DOC 3/21/03
3"