CaptiveAire RZ7-FS User Manual

RZ7-FS
R
Electronic Timing Relays
Precision DIN-rail mounted timing relays for any industrial application
Sprecher + Schuh’s new RZ7-FS preci­sion electronic timing relays offer 19 different output functions applicable to all types of industrial control. In addition to standard and OFF-Delay relays, the series also includes many specials such as an Delay that operates without supply voltage. Various timing ranges from
0.05 seconds to 60 hours are available, with many relays offering multi-time setting capability in the same device.
ON-Delay
OFF-
Solid state accuracy and reliability
Except for their hard silver contacts, all RZ7-FS timing relays are built with solid state electronics and controlled by a mi croprocessor. ey are accurate to within
0.2 percent. eir ruggedness and high level of accuracy is due to the thorough testing of function, timing characteristics and surge voltage strength performed on each device prior to shipment.
In addition, RZ7-FS relays function reliably from 15% under rated oper ating voltage to 10% over rated voltage (AC). Voltage tolerance is even greater in DC applications.
-
-
Multiple functions and timing ranges in one relay
e RZ7-FSM combines eight separate timing functions (plus ON and OFF functions) into one device. In addi­tion, ten timing ranges are individually selectable from 0.05 seconds to 60 hours. ese special relays reduce in ventories and are ideal for maintaining remote installations where stocking several different timing relays would not be practical.
-
Many safety and
G
Timing Relays
Control &
RZ7-FS
The new multifunction RZ7-FSM Electronic
Timing Relay provides eight different timing
functions and ten different timing ranges.
Eliminates additional relays
e standard RZ7-FS is supplied with one single pole double throw contact within a compact case only
22.5mm wide. If more contacts are required, several relays are available that provide two separate, electrically isolated SPDT contacts within the same narrow footprint. Output two is selectable as an instantaneous contact, which can eliminate the need for aux iliary relays in complex installations. ese two pole relays can also be used with an external potentiometer for remote time setting.
(SPDT)
convenience features
• Every RZ7 accepts a broad range of AC and DC supply voltages without special ordering.
• Each relay is equipped with an LED that indicates four output status conditions.
• Finger and back of hand protection to IP40.
• Terminals are captive and supplied in the open position.
-
• All RZ7’s can be surface mounted, rail mounted, or mounted directly on our family of CA7/CS7 or CA4/CS4 devices.
• RZ7 relays can be mounted in any plane.
• Terminals, setting knob and LED’s are all accessible from the front of the unit.
• RZ7 Timing Relays are very compact, measuring approximately 1" x 3" x 4".
G39
G
Control &
Timing Relays
RZ7-FS
Electronic Timing Relays
Quick Selection Guide
Single Function Timing Relays
RZ7-FS A 3 A U23
Type Function
A On-Delay B Off-Delay C On and Off-Delay D One Shot / Watchdog E Fleeting Off-Delay F Symmetric flasher starting with a pulse G Symmetric flasher starting with a pause
I On-Delay pulse generator
J On-Delay (pulse controlled) K One Shot / Watch Dog (pulse controlled) L Impulse Converter
RZ7-FS Q 3 Q U18
Type
Q Off-Delay Without Supply Voltage
Function
Contacts
All functions:
3 One single pole double throw contact
Functions A & B only:
4
Two single pole
double throw contacts
(Available with Time Range “U” only. Not available with “U18” supply voltage)
Contacts
3 One single pole
double throw contact
4
Two single pole double
throw contacts
Time Ranges
A 0.05…1 second B 0.15… 3 seconds C 0.5…10 seconds D 1.5…30 seconds E 0.05…1 minute F 0.15…3 minutes G 0.5…10 minutes H 1.5…30 minutes
I 0.05…1 hour
J 0.15…3 hours K 0.5…10 hours L 3.0…60 hours U 0.05s…60 hours
Time Ranges
Q 0.15s…10 minutes
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
U18* 24…240VAC or DC A40 346…440V 50/60Hz Z12 12VDC
* Not available with Time Range “U”
Supply Voltages
U18 24…240VAC or DC
Series RZ7-FS
Multi-Function Timing Relay
RZ7-FS M 3 U U23
Type Function
M Multi-Function
Eight single functions plus ON & OFF function (for installation/maintenance)
- On-Delay
- Off-Delay
- On and Off-Delay
- One Shot / Watchdog
- Fleeting Off-Delay
- Symmetric flasher starting with a pulse
Contacts
3 One single pole
double throw contact
4
Two single pole
double throw contacts
Time Ranges
U 0.15…60 hours
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
U18 24…240VAC or DC A40 346…440V 50/60Hz Z12 12VDC
Special Function Timing Relays
RZ7-FS H 3 U U23
Type Function
H Repeat Cycle Timer (Flasher)
Includes four separate functions
- Supply voltage controlled, output starts with a pause
- Supply voltage controlled, output starts with a pulse
- Pulse controlled, output starts with a pause
- Pulse controlled, output starts with a pulse
Contacts
All functions:
3 One single pole double throw contact
Time Ranges
For equal timing of pulse and pause
U 0.05s…60 hours
For separate timing of pulse and pause
V 2 x 0.05s…60 hours
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
A40 346…440V 50/60Hz Z12 12VDC
RZ7-FS Y 2 C U23
Type
Y Wye Delta Timing Relay
Multi-time setting range. See Technical Section for specific time settings.
Second output selectable as timed or instantaneous.
Function
Contacts
2 Two normally open
contacts
Time Ranges
C 0.5…10 seconds D 1.5…30 seconds E 0.05…1 minute F 0.15…3 minutes G 0.5…10 minutes
Timers with supply voltage code A40 (346...440VAC) are not UL listed.
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
A40 346…440V 50/60Hz
G40
Discount Schedule B
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
S
L/+
A2
N/-
A1
18 16
15
B1
S
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
L/+
A2
N/-
A1
18 16
15
28 26
25
Electronic Timing Relays
L/+
A2
N/-
A1
18 16
15
L/+
A2
N/-
A1
18 16
15
Series RZ7-FS
RZ7-FS Timing Relays – Single Function, One and Two Pole
Functional
Description
ON-Delay Timing Relay (A)
When supply voltage is applied, output contact(s) change state after time delay t.
OFF-Delay Timing Relay (B)
When control contact “S” closes, output contact(s) change state immediately. When control contact S opens, output contact(s) change state after time delay supply voltage required on terminals A1/A2.
Note: Control pulse duration minimum 50ms (AC) - 30ms (DC).
t. Constant
Functional
Diagram
Terminal
Arrangement Type Catalog Number Price
G
Timing Relays
Control &
• One SPDT contact
• Single timing range
• One SPDT contact
• Multi-timing range (from 0.05s to 60h)
• Two SPDT contacts
• Multi-timing range (from 0.05s to 60h)
• One SPDT contact
• Single timing range
• One SPDT contact
• Multi-timing range (from 0.05s to 60h)
• Two SPDT contacts
• Multi-timing range (from 0.05s to 60h)
RZ7-FSA3U23
RZ7-FSA3UU23 64
RZ7-FSA4UU23 84
RZ7-FSB3U23
RZ7-FSB3UU23 64
RZ7-FSB4UU23 84
61
RZ7-FS
61
• One SPDT contact
Off-Delay Without Supply Voltage (Q)
When supply voltage is applied, output contact(s) change state immediately. When supply voltage is removed, output contact(s) change state after time delay
t.
Ordering Instructions
Specify catalog number
Replace () with Timing Range Code
Refer to table
at right
Supply Voltage
Single Function RZ7-FS...U23 timers (except RZ7-FSQ) accept sup­ply voltages of 24…48VDC and 24…240VAC (RZ7-FSQ accepts 24…240VAC or DC). Other voltages are available by special order. See Quick Selection Guide on page G40 for details or contact your Sprecher + Schuh representative for information.
For timing control, a voltage other than the supply voltage can also be used.
• Multi-timing range (from 0.15s to 10min)
• Two SPDT contacts
• Multi-timing range (from 0.15s to 10min)
Timing Range Codes
Timing Range
0.05…1 sec
0.15…3 sec
0.5…10 sec
1.5…30 sec
0.05…1 min
0.15…3 min
0.5…10 min
1.5…30 min
0.05…1 hour
0.15…3 hour
0.5…10 hour
3.0…60 hour
Code
A B C D E F G H
I
J K L
RZ7-FSQ3QU18 121
RZ7-FSQ4QU18 141
RZ7-FS two pole timing relay
Output two is selectable as an instantaneous contact by sliding a switch on the
faceplate.
Bridge or potentiometer 10kΩ, min. 0.25W (low voltage) for external time setting. Timing range is screwdriver selectable from the faceplate. Timing range selections
include those found in the Timing Range Code chart.
Discount Schedule B
Timing range is screwdriver selectable from the faceplate. Exact timing ranges can be
found in the Technical Section.
Due to shock during shipment, the state of the contacts should be verified before
initial use.
G41
A2
N/-
18 16
15
L/+
A1
B1
S
RZ7-FS Timing Relays – Single Function, One Pole
L/+
A2
N/-
A1
18 16
15
L/+
A2
N/-
A1
18 16
15
L/+
A2
N/-
A1
18 16
15
B1
S
G
Functional
Description
Functional
Diagram
Electronic Timing Relays
Series RZ7-FS
Terminal
Arrangement Type Catalog Number Price
Control &
Timing Relays
RZ7-FS
ON and OFF-Delay Timing Relay (C)
When control contact “S” closes, output contact changes state after time delay When control contact S opens, output contact changes state again after time delay Constant supply voltage required on terminals A1/A2.
Note: Closure duration of S must be greater than t.
One Shot / Watchdog Relay (D)
When supply voltage is applied, the output contact changes state for time period
Fleeting OFF-Delay Timing Relay (E)
When control contact “S” is pulsed, output contact changes state for time period
Note: Control pulse duration minimum 50ms (AC) - 30ms (DC).
Symmetric Flasher Starting With A Pulse (F)
When supply voltage is applied, output contact changes state immediately and then repeatedly changes after every time period continuing until supply voltage is removed.
t.
t.
t.
t.
• One SPDT contact
• Single timing range
• One SPDT contact
• Single timing range
• One SPDT contact
• Single timing range
• One SPDT contact
t,
• Single timing range
RZ7-FSC3U23
RZ7-FSD3U23
RZ7-FSE3U23
RZ7-FSF3U23
68
68
68
68
Ordering Instructions
Specify catalog number
Replace () with Timing Range Code
Refer to table
at right
Supply Voltage
Single Function RZ7-FS...U23 timers (except RZ7-FSQ) accept sup­ply voltages of 24…48VDC and 24…240VAC (RZ7-FSQ accepts 24…240VAC or DC). Other voltages are available by special order. See Quick Selection Guide on page G40 for details or contact your Sprecher + Schuh representative for information.
For timing control, a voltage other than the supply voltage can also be used.
G42
Discount Schedule B
Timing Range Codes
Timing Range
0.05…1 sec
0.15…3 sec
0.5…10 sec
1.5…30 sec
0.05…1 min
0.15…3 min
0.5…10 min
1.5…30 min
0.05…1 hour
0.15…3 hour
0.5…10 hour
3.0…60 hour
Code
A B C D
E
F G H
I
J K
L
RZ7-FS one pole timing relay
A2
N/-
18 16
15
L/+
A1
B1
S
L/+
A2
N/-
A1
18 16
15
B1
S
L/+
A2
N/-
A1
18 16
15
L/+
A2
N/-
A1
18 16
15
Electronic Timing Relays
A2
N/-
18 16
15
L/+
A1
B1
S
Series RZ7-FS
RZ7-FS Timing Relays – Single Function, One Pole
Functional
Description
Symmetric Flasher Starting With A Pause (G)
When supply voltage is applied, output contact changes state after time period then repeatedly changes again after every period t, continuing until supply voltage is removed.
On-Delay Pulse Generator (I)
When supply voltage is applied, output contact changes state after time period Output contact changes state again after
0.5 seconds.
On-Delay (pulse controlled) (J)
When control contact “S” is pulsed, the out put contact changes state after time period
One Shot / Watchdog (pulse controlled) (K)
When control contact “S” closes, the output contact changes state immediately. After the last pulse of contact S, the output contact changes state after time delay
t and
t.
t.
­t.
Functional
Diagram
Terminal
Arrangement Type Catalog Number Price
• One SPDT contact
• Single timing range
• One SPDT contact
• Single timing range
• One SPDT contact
• Single timing range
• One SPDT contact
• Single timing range
RZ7-FSG3U23
RZ7-FSI3U23
RZ7-FSJ3U23
RZ7-FSK3U23
68
68
68
68
G
Timing Relays
Control &
RZ7-FS
Impulse Converter (L)
When a pulse is applied to control contact “S”, the output contact changes state im mediately for time period during timing period t have no further effect.
Note: The period t is not dependent on the length of the control pulse. Control pulse duration minimum 50ms (AC) - 30ms (DC).
t. Pulses received
-
Ordering Instructions
Specify catalog number
Replace () with Timing Range Code
Refer to table
at right
Supply Voltage
Single Function RZ7-FS..U23 timers (except RZ7-FSQ) accept supply voltages of 24…48VDC and 24…240VAC (RZ7-FSQ accepts 24…240VAC or DC). Other voltages are available by special order. See Quick Selection Guide on page G40 for details or contact your Sprecher + Schuh representative for information.
• One SPDT contact
• Single timing range
Timing Range Codes
Timing Range
0.05…1 sec
0.15…3 sec
0.5…10 sec
1.5…30 sec
0.05…1 min
0.15…3 min
0.5…10 min
1.5…30 min
0.05…1 hour
0.15…3 hour
0.5…10 hour
3.0…60 hour
Code
A B C D E F G H
I
J K L
RZ7-FSL3U23
RZ7-FS one pole timing relay
68
For timing control, a voltage other than the supply voltage can also be used.
Discount Schedule B
G43
G
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
S
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
S
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
S
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
S
Control &
Timing Relays
RZ7-FS
Electronic Timing Relays
Series RZ7-FS
RZ7-FS Timing Relays – Multi-Function, One and Two Pole
RZ7-FSM
Multi-Function Relay Functional Description Type Catalog Number Price
Multi-Function Relay (M)
The RZ7-FSM multifunction relay combines eight timing functions plus ON and OFF functions (for installation and maintenance). Each timing function and timing range is selectable from the face of the relay with a screwdriver actuated knob. The RZ7-FSM offers the following timing functions:
On-Delay Off-Delay On and Off-Delay Fleeting Off-Delay On-Delay Pulse Generator ON Function (see below) With a Pulse OFF Function (see below)
The two pole RZ7-FSM4 offers two separate, electrically isolated single pole double throw (SPDT) contacts which allow applications in complex installations without additional auxiliary relays. This series may also be operated remotely via an external potentiometer.
One Shot / Watchdog
Impulse Converter Symmetric Flasher Starting
• One SPDT contact
• Multifunction, multi-timing range relay (from 0.05s to 60h)
• Two SPDT contacts
• Multifunction, multi-timing range relay (from 0.05s to 60h)
RZ7-FSM3UU23 101
RZ7-FSM4UU23 121
On-Delay (A) Off-Delay (B)
On and Off-Delay (C) One Shot / Watchdog (D)
Fleeting Off-Delay (E) Symmetric Flasher Starting With a Pulse (F)
On-Delay Pulse Generator (I) Impulse Converter (L)
ON-Function OFF-Function LED display indicates function
Output in rest position, no timing Output in rest position, time running Output in operation position, no timing Output in operation position, time running
Supply Voltage
The RZ7-FSM timer accepts supply voltages of 24…48VDC and 24…240VAC. Other supply voltages are available by special order. See Quick Selection Guide on page G40 for details or contact your Sprecher + Schuh representative for information.
G44
Discount Schedule B
For timing control, a voltage other than the supply voltage can also be used.
Output two is selectable as an instantaneous contact by sliding a switch on the
faceplate
Bridge or potentiometer 10kΩ, min. 0.25W (low voltage) for external time setting. Function selection and timing range is screwdriver selectable from the faceplate. Exact
timing range selections can be found in Technical Information.
Electronic Timing Relays
L/+
A2
N/-
A1
18
16
15
B1
S
L/+
A2
N/-
A1
18
16
15
B1
S
L
A2
N
A1
18
28
17
Y
L/+
A2
N/-
A1
18
16
15
B1
S
L/+
A2
N/-
A1
18
16
15
B1
S
Series RZ7-FS
RZ7-FS Timing Relays – Special Function, One Pole
Functional
Description
Wye-Delta Timing Relay (Y)
When supply voltage is applied, output contact Y closes for time period period t, plus a fixed time period tu, (50­65ms) output contact Δ closes.
Repeat Cycle Timer (H) - (Flasher)
The Repeat Cycle Timer offers four different operating characteristics within the same relay. Depending on how the unit is wired, cycles are initiated either by supply voltage being applied or by a pulse from control contact “S”. Regardless of the activation method, each cycle may begin with a pause or a pulse.
The RZ7-FSH3U relay sets the pulse and pause durations equally. The RZ7-FSH3 allows individual time settings of pulse and pause. Both relays offer multiple time settings between 0.05s and 60h, selectable in ten increments.
t. After time
V
Functional
Diagram
Supply voltage controlled,
output starts with a pause
Supply voltage controlled,
output starts with a pulse
Pulse controlled,
output starts with a pause
Terminal
Arrangement Type Catalog Number Price
• Two single pole N.O. contacts
• Single timing range
• One SPDT contact
• Multi-timing range (from 0.05s to 60h)
Equal setting of pause and
pulse
Individual setting of pause
and pulse
RZ7-FSY2U23
RZ7-FSH3UU23
RZ7-FSH3VU23
81
81
81
G
Timing Relays
Control &
RZ7-FS
Pulse controlled,
output starts with a pulse
Ordering Instructions
Specify catalog number
Replace () with Timing Range Code
Refer to table
at right
Timing Range Codes
Timing Range
0.5…10 sec
1.5…30 sec
0.05…1 min
0.15…3 min
0.5…10 min
Code
C D E F G
Supply Voltage
These timers accept supply voltages of 24…48VDC and 24…240VAC. A supply voltage of 346…440VAC is also available by special order. See Quick Selection Guide on page G40 for details or contact your Sprecher + Schuh representative for information.
For timing control, a voltage other than the supply voltage can also be used.
Timing range is screwdriver selectable from the faceplate. Exact timing range
selections can be found in Technical Information.
Discount Schedule B
RZ7-FSY one pole timing relay
G45
G
Accessories - Field Installable
Series RZ7-FS Electronic Timing Relays
Accessories
Accessory Description Catalog Number Price
Control &
Timing Relays
RZ7-FS
Setting Knob With Scale -
For time setting without tools.
Panel Mounting Adaptor -
For surface mounting RZ7-FS/FE timing relays.
Dovetail joint -
for fitting all timers to CA7/CS7 and CA4/CS4 devices
DIN-rail - 2 meter lengths (6' 6")
Top Hat, low profile (price per rail Top Hat, high profile (price per rail)
RZ7-FSK 5
26.506.221-01 4
25.944.201-03 1.30
3F 3AF
17 26
Marking Systems
Component Description
Label Sheet –
1 sheet with 105 self-adhesive paper labels each, 6 x 17mm
Marking Tag Sheet -
1 sheet with 160 perforated paper labels each, 6 x 17mm. To be used with transparent cover.
Transparent Cover -
To be used with Marking Tag Sheets.
Tag Carrier -
For marking with Series V7 Clip-on Tags.
Minimum order quantity is one package of 100. Price each x 100 = total price.
Pkg.
Qty. Catalog Number
CA7-FMS
1
CA7-FMP
1
100
CA7-FMC
100
CA7-FMA2
Price Each
1
1
.10
.10
G46
Discount Schedule B
Technical Data
Timing Characteristics (according to VDE 0435, Part 2021)
Timing ranges for
RZ7-FSM-A, B, C, D, E, F, I, & L (1s) 0.05…1 sec RZ7-FSH (3s) 0.15…3 sec
RZ7-FSQ (2.5s) 0.15…2.5 sec
Setting accuracy Repeatability Tolerance Voltage:
Power Supply
Supply voltages 24…48VDC and 24…240VAC, 50/60Hz
Voltage tolerance AC: -15%... +10%
Power consumption AC: 5VA at 240V
Time energized Reset time 50ms Voltage interruption Input Impedance Relay On: 3k-13k ohms
Cable length (supply voltage control)
Pulse Control (B1)
Impulse duration Input voltage Supply voltage range Input current 1 mA Max. Leakage Current 400 micro Amps Cable length
Outputs
Type of outputs Relay contacts: hard silver Maximum admissible
operating voltage Dielectric Coil to contact Withstand
Voltage Switching capacity
Current Ith: (AC1) 8A (5A for RZ7-FSQ) Power: 2000VA
Short circuit resistance 10 A gL (fast blow fuse)
(10s) 0.5…10 sec (1mn) 0.05…1 min (3mn) 0.15…3 min (10mn) 0.5…10 min (1h) 0.05…1 hour (3h) 0.15…3 hours (10h) 0.5…10 hours (60h) 3…60 hours
(10s) 0.5…10 sec (80s) 4…80 sec (10mn) 0.5…10 min
±5% of full scale value ±0.2% of the setting values
±0.001%/%ΔU
Temperature:
(dual voltage) 12VDC 24…240V AC or DC (universal voltage) 346…440VAC, 50/60Hz
DC: -20%... +20%
DC: 0.5W at 24V 100%
20ms without reset (supply voltage)
Relay Off: 0.7k-4k ohms 250 meters (800 ft.) max.
50ms (AC), 30ms (DC)
max. 250 m (800 ft.) without parallel load between B1 & A2
max. 50 m (160 ft.) with load ( B1 & B2
Alternating current: 440VAC 5,000 V
according to IEC947-5-1: 3A/440VAC (inductive load, AC14) 3A/250VAC (inductive load, AC15) 1A/24VDC (inductive load, DC13) according to UL 508:
1.5A/250VAC (B300) 3A/120VAC (B300)
±0.025%/°C
<3kΩ
) between
Technical Information
Series RZ7-FS Electronic Timing Relays
Life expectancy (electrical) 4 million ops. at 1A/250VAC, cos
Life expectancy (mechanical) 30 million operations
General Data
Insulation Characteristics
EMC/Interference Immunity Performance of following requirements:
EMC/Emission Electromagnetic fields according to EN 55 022:
Safe isolation According to VDE 106, part 101 Climatic withstand 56 cycles (24h) at 25…40°C and 95% relative
Vibration resistance 4 g in 3 axis at 10…500 Hz, test FC according Shock resistance 50 g according to IEC 68-2-27 Protection class Enclosure:
Weight Approvals/Standards UL, C-UL up to 240VAC, Germanischer Lloyd, CE Ambient temperature Open:
Connections Screw terminal - M3.5 for Pozidrive No.2, Phillips and slotted screws
Rated tightening torque -
Mounting – Snap-on mounting (35mm DIN-rail)
Relays
Disposal Synthetic material without dioxin according to EC/
Standards EN 60947-1, EN 60947-5-1, EN 50081-1, IEC 947,
Wire Size -
Finger Protection - According to VDE 0106
0.2 million ops. at 6A/250VAC, cos
1.5 million ops. at 1A/250VAC, cos
0.3 million ops. at 3A/250VAC, cos
0.5 million ops. at 6A/24VDC, resistive 2 million ops. at 4A/24VDC, resistive 2 million ops. at 0.2A/230VDC, resistive 1 million ops. at 0.4A/24VDC, L/R = 20ms 1 million ops. at 0.2A/110VDC, L/R = 20ms 1 million ops. at 0.1A/230VDC, L/R = 20ms
2 kVAC/50 Hz test voltage according to VDE and 6 kV 1.2/50 μs surge voltage according to IEC 947-1 between all inputs and outputs
- Surge capacity of the supply voltage according to IEC1000-4-5: 4 kV 1.2/50
- Burst according to IEC 1000-4-4: 6 kV/ 6/50ns
- ESD discharge according to IEC 1000-4-2:
- Contact 8 kV, air 8 kV
- Electromagnetic HF field according to IEC and conducted electromagnetic HF according to IEC 801-6: Level 3
Class B
humidity according to IEC 68-2-30 and IEC 68-2-3.
IP40
Terminal: IP20 according to IEC 947-1 100g
Enclosed: Storage
No.2 suitable for power screwdriver.
0.8 Nm (max. 1.2 Nm) - [8.8 lb-in]
Dual-chamber system for terminal cross-sections of 1 x 0.5mm2 (solid) or 2 x 2.5mm2 (flexible with sleeve), AWG 20…14.
– Side mounting on CA7/CA4 contactors and
– Screw fixing by Panel Mount Adapter and two
EFTA notification No. 93/0141/D. Electrical contain cadmium.
UL 508. CSA 22.2
IP30 (single function)
–25°C…+60°C
–25°C…+45°C –25°C…+85°C
CS7/CS4 with dovetail joint any position]
screws (M4) [surface mounting in any position]
RZ7 Relative Scale Setting Knob
Series RZ7 Timing Relays have a “relative scale” setting knob numbered 0 to 1.0. ink about this as 0 to 100% of the relay’s built-in time range. Example: To set an RZ7-FS timing relay (with a 0.05 to 1 minute range) to activate after 25 seconds:
1) Divide the desired activation time (25 seconds) by the maximum time limit of the relay (60 seconds).
25
÷ 60 = .416
2) Rotate the setting knob to just past the .4 mark.
ϕ = 1
ϕ = 1 ϕ = 0.3 ϕ = 0.3
0435
μs
801-3
signal
[surface mounting in
contacts
G
Timing Relays
Control &
RZ7-FS
Discount Schedule B
G47
G
9
4,3
22,5
4,3
75
35
5,5
58
17
12
13
2
Control &
Timing Relays
RZ7-FS
Dimensions
Series RZ7-FS Electronic Timing Relays
Dimensions
Series RZ7-FS Timing Relays (one and two pole)
• Dimensions are in millimeters
• Dimensions not intended for manufacturing purposes
RZ7-FS (1 SPDT contact) RZ7-FS (2 SPDT contacts)
Panel Mount Adaptor (26.506.221-01)
• Dimensions are in millimeters
• Dimensions not intended for manufacturing purposes
G48