CaptiveAire RZ7-FS User Manual

RZ7-FS
R
Electronic Timing Relays
Precision DIN-rail mounted timing relays for any industrial application
Sprecher + Schuh’s new RZ7-FS preci­sion electronic timing relays offer 19 different output functions applicable to all types of industrial control. In addition to standard and OFF-Delay relays, the series also includes many specials such as an Delay that operates without supply voltage. Various timing ranges from
0.05 seconds to 60 hours are available, with many relays offering multi-time setting capability in the same device.
ON-Delay
OFF-
Solid state accuracy and reliability
Except for their hard silver contacts, all RZ7-FS timing relays are built with solid state electronics and controlled by a mi croprocessor. ey are accurate to within
0.2 percent. eir ruggedness and high level of accuracy is due to the thorough testing of function, timing characteristics and surge voltage strength performed on each device prior to shipment.
In addition, RZ7-FS relays function reliably from 15% under rated oper ating voltage to 10% over rated voltage (AC). Voltage tolerance is even greater in DC applications.
-
-
Multiple functions and timing ranges in one relay
e RZ7-FSM combines eight separate timing functions (plus ON and OFF functions) into one device. In addi­tion, ten timing ranges are individually selectable from 0.05 seconds to 60 hours. ese special relays reduce in ventories and are ideal for maintaining remote installations where stocking several different timing relays would not be practical.
-
Many safety and
G
Timing Relays
Control &
RZ7-FS
The new multifunction RZ7-FSM Electronic
Timing Relay provides eight different timing
functions and ten different timing ranges.
Eliminates additional relays
e standard RZ7-FS is supplied with one single pole double throw contact within a compact case only
22.5mm wide. If more contacts are required, several relays are available that provide two separate, electrically isolated SPDT contacts within the same narrow footprint. Output two is selectable as an instantaneous contact, which can eliminate the need for aux iliary relays in complex installations. ese two pole relays can also be used with an external potentiometer for remote time setting.
(SPDT)
convenience features
• Every RZ7 accepts a broad range of AC and DC supply voltages without special ordering.
• Each relay is equipped with an LED that indicates four output status conditions.
• Finger and back of hand protection to IP40.
• Terminals are captive and supplied in the open position.
-
• All RZ7’s can be surface mounted, rail mounted, or mounted directly on our family of CA7/CS7 or CA4/CS4 devices.
• RZ7 relays can be mounted in any plane.
• Terminals, setting knob and LED’s are all accessible from the front of the unit.
• RZ7 Timing Relays are very compact, measuring approximately 1" x 3" x 4".
G39
G
Control &
Timing Relays
RZ7-FS
Electronic Timing Relays
Quick Selection Guide
Single Function Timing Relays
RZ7-FS A 3 A U23
Type Function
A On-Delay B Off-Delay C On and Off-Delay D One Shot / Watchdog E Fleeting Off-Delay F Symmetric flasher starting with a pulse G Symmetric flasher starting with a pause
I On-Delay pulse generator
J On-Delay (pulse controlled) K One Shot / Watch Dog (pulse controlled) L Impulse Converter
RZ7-FS Q 3 Q U18
Type
Q Off-Delay Without Supply Voltage
Function
Contacts
All functions:
3 One single pole double throw contact
Functions A & B only:
4
Two single pole
double throw contacts
(Available with Time Range “U” only. Not available with “U18” supply voltage)
Contacts
3 One single pole
double throw contact
4
Two single pole double
throw contacts
Time Ranges
A 0.05…1 second B 0.15… 3 seconds C 0.5…10 seconds D 1.5…30 seconds E 0.05…1 minute F 0.15…3 minutes G 0.5…10 minutes H 1.5…30 minutes
I 0.05…1 hour
J 0.15…3 hours K 0.5…10 hours L 3.0…60 hours U 0.05s…60 hours
Time Ranges
Q 0.15s…10 minutes
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
U18* 24…240VAC or DC A40 346…440V 50/60Hz Z12 12VDC
* Not available with Time Range “U”
Supply Voltages
U18 24…240VAC or DC
Series RZ7-FS
Multi-Function Timing Relay
RZ7-FS M 3 U U23
Type Function
M Multi-Function
Eight single functions plus ON & OFF function (for installation/maintenance)
- On-Delay
- Off-Delay
- On and Off-Delay
- One Shot / Watchdog
- Fleeting Off-Delay
- Symmetric flasher starting with a pulse
Contacts
3 One single pole
double throw contact
4
Two single pole
double throw contacts
Time Ranges
U 0.15…60 hours
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
U18 24…240VAC or DC A40 346…440V 50/60Hz Z12 12VDC
Special Function Timing Relays
RZ7-FS H 3 U U23
Type Function
H Repeat Cycle Timer (Flasher)
Includes four separate functions
- Supply voltage controlled, output starts with a pause
- Supply voltage controlled, output starts with a pulse
- Pulse controlled, output starts with a pause
- Pulse controlled, output starts with a pulse
Contacts
All functions:
3 One single pole double throw contact
Time Ranges
For equal timing of pulse and pause
U 0.05s…60 hours
For separate timing of pulse and pause
V 2 x 0.05s…60 hours
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
A40 346…440V 50/60Hz Z12 12VDC
RZ7-FS Y 2 C U23
Type
Y Wye Delta Timing Relay
Multi-time setting range. See Technical Section for specific time settings.
Second output selectable as timed or instantaneous.
Function
Contacts
2 Two normally open
contacts
Time Ranges
C 0.5…10 seconds D 1.5…30 seconds E 0.05…1 minute F 0.15…3 minutes G 0.5…10 minutes
Timers with supply voltage code A40 (346...440VAC) are not UL listed.
Supply Voltages
Standard:
U23 24…48VDC 24…240V 50/60Hz
Special Order:
A40 346…440V 50/60Hz
G40
Discount Schedule B
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
S
L/+
A2
N/-
A1
18 16
15
B1
S
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
L/+
A2
N/-
A1
18 16
15
28 26
25
Electronic Timing Relays
L/+
A2
N/-
A1
18 16
15
L/+
A2
N/-
A1
18 16
15
Series RZ7-FS
RZ7-FS Timing Relays – Single Function, One and Two Pole
Functional
Description
ON-Delay Timing Relay (A)
When supply voltage is applied, output contact(s) change state after time delay t.
OFF-Delay Timing Relay (B)
When control contact “S” closes, output contact(s) change state immediately. When control contact S opens, output contact(s) change state after time delay supply voltage required on terminals A1/A2.
Note: Control pulse duration minimum 50ms (AC) - 30ms (DC).
t. Constant
Functional
Diagram
Terminal
Arrangement Type Catalog Number Price
G
Timing Relays
Control &
• One SPDT contact
• Single timing range
• One SPDT contact
• Multi-timing range (from 0.05s to 60h)
• Two SPDT contacts
• Multi-timing range (from 0.05s to 60h)
• One SPDT contact
• Single timing range
• One SPDT contact
• Multi-timing range (from 0.05s to 60h)
• Two SPDT contacts
• Multi-timing range (from 0.05s to 60h)
RZ7-FSA3U23
RZ7-FSA3UU23 64
RZ7-FSA4UU23 84
RZ7-FSB3U23
RZ7-FSB3UU23 64
RZ7-FSB4UU23 84
61
RZ7-FS
61
• One SPDT contact
Off-Delay Without Supply Voltage (Q)
When supply voltage is applied, output contact(s) change state immediately. When supply voltage is removed, output contact(s) change state after time delay
t.
Ordering Instructions
Specify catalog number
Replace () with Timing Range Code
Refer to table
at right
Supply Voltage
Single Function RZ7-FS...U23 timers (except RZ7-FSQ) accept sup­ply voltages of 24…48VDC and 24…240VAC (RZ7-FSQ accepts 24…240VAC or DC). Other voltages are available by special order. See Quick Selection Guide on page G40 for details or contact your Sprecher + Schuh representative for information.
For timing control, a voltage other than the supply voltage can also be used.
• Multi-timing range (from 0.15s to 10min)
• Two SPDT contacts
• Multi-timing range (from 0.15s to 10min)
Timing Range Codes
Timing Range
0.05…1 sec
0.15…3 sec
0.5…10 sec
1.5…30 sec
0.05…1 min
0.15…3 min
0.5…10 min
1.5…30 min
0.05…1 hour
0.15…3 hour
0.5…10 hour
3.0…60 hour
Code
A B C D E F G H
I
J K L
RZ7-FSQ3QU18 121
RZ7-FSQ4QU18 141
RZ7-FS two pole timing relay
Output two is selectable as an instantaneous contact by sliding a switch on the
faceplate.
Bridge or potentiometer 10kΩ, min. 0.25W (low voltage) for external time setting. Timing range is screwdriver selectable from the faceplate. Timing range selections
include those found in the Timing Range Code chart.
Discount Schedule B
Timing range is screwdriver selectable from the faceplate. Exact timing ranges can be
found in the Technical Section.
Due to shock during shipment, the state of the contacts should be verified before
initial use.
G41
Loading...
+ 7 hidden pages