Precision DIN-rail
mounted timing relays
for any industrial
application
Sprecher + Schuh’s new RZ7-FS precision electronic timing relays offer 19
different output functions applicable
to all types of industrial control.
In addition to standard
and OFF-Delay relays, the series also
includes many specials such as an
Delay that operates without supply
voltage. Various timing ranges from
0.05 seconds to 60 hours are available,
with many relays offering multi-time
setting capability in the same device.
ON-Delay
OFF-
Solid state accuracy and
reliability
Except for their hard silver contacts, all
RZ7-FS timing relays are built with solid
state electronics and controlled by a mi
croprocessor. ey are accurate to within
0.2 percent. eir ruggedness and high
level of accuracy is due to the thorough
testing of function, timing characteristics
and surge voltage strength performed on
each device prior to shipment.
In addition, RZ7-FS relays function
reliably from 15% under rated oper
ating voltage to 10% over rated voltage
(AC). Voltage tolerance is even greater
in DC applications.
-
-
Multiple functions and
timing ranges in one relay
e RZ7-FSM combines eight separate
timing functions (plus ON and OFF
functions) into one device. In addition, ten timing ranges are individually
selectable from 0.05 seconds to 60
hours. ese special relays reduce in
ventories and are ideal for maintaining
remote installations where stocking
several different timing relays would
not be practical.
-
Many safety and
G
Timing Relays
Control &
RZ7-FS
The new multifunction RZ7-FSM Electronic
Timing Relay provides eight different timing
functions and ten different timing ranges.
Eliminates additional relays
e standard RZ7-FS is supplied with
one single pole double throw
contact within a compact case only
22.5mm wide. If more contacts are
required, several relays are available
that provide two separate, electrically
isolated SPDT contacts within the
same narrow footprint. Output two is
selectable as an instantaneous contact,
which can eliminate the need for aux
iliary relays in complex installations.
ese two pole relays can also be used
with an external potentiometer for
remote time setting.
(SPDT)
convenience features
• Every RZ7 accepts a broad range of
AC and DC supply voltages without
special ordering.
• Each relay is equipped with an LED
that indicates four output status
conditions.
• Finger and back of hand protection
to IP40.
• Terminals are captive and supplied
in the open position.
-
• All RZ7’s can be surface mounted, rail
mounted, or mounted directly on our
family of CA7/CS7 or CA4/CS4 devices.
• RZ7 relays can be mounted in any
plane.
• Terminals, setting knob and LED’s are
all accessible from the front of the unit.
• RZ7 Timing Relays are very compact,
measuring approximately 1" x 3" x 4".
G39
G
Control &
Timing Relays
RZ7-FS
Electronic Timing Relays
Quick Selection Guide
Single Function Timing Relays
RZ7-FSA3AU23
TypeFunction
A On-Delay
B Off-Delay
C On and Off-Delay
D One Shot / Watchdog
E Fleeting Off-Delay
F Symmetric flasher starting with a pulse
G Symmetric flasher starting with a pause
I On-Delay pulse generator
J On-Delay (pulse controlled)
K One Shot / Watch Dog (pulse controlled)
L Impulse Converter
RZ7-FSQ3QU18
Type
Q Off-Delay Without Supply Voltage
Function
Contacts
All functions:
3 One single pole
double throw contact
Functions A & B only:
4
Two single pole
double throw contacts ➋
(Available with Time
Range “U” only. Not
available with “U18”
supply voltage)
Contacts
3 One single pole
double throw contact
4
Two single pole double
throw contacts ➋
Time Ranges
A 0.05…1 second
B 0.15… 3 seconds
C 0.5…10 seconds
D 1.5…30 seconds
E 0.05…1 minute
F 0.15…3 minutes
G 0.5…10 minutes
H 1.5…30 minutes
I 0.05…1 hour
J 0.15…3 hours
K 0.5…10 hours
L 3.0…60 hours
U 0.05s…60 hours ➊
Time Ranges
Q 0.15s…10 minutes ➊
Supply Voltages
Standard:
U23 24…48VDC
24…240V 50/60Hz
Special Order:
U18* 24…240VAC or DC
A40 346…440V 50/60Hz ➌
Z12 12VDC
* Not available with Time Range “U”
Supply Voltages
U18 24…240VAC or DC
Series RZ7-FS
Multi-Function Timing Relay
RZ7-FSM3UU23
TypeFunction
M Multi-Function
Eight single functions plus ON & OFF function (for installation/maintenance)
- On-Delay
- Off-Delay
- On and Off-Delay
- One Shot / Watchdog
- Fleeting Off-Delay
- Symmetric flasher starting with a pulse
Contacts
3 One single pole
double throw contact
4
Two single pole
double throw contacts ➋
Time Ranges
U 0.15…60 hours
Supply Voltages
➊
Standard:
U23 24…48VDC
24…240V 50/60Hz
Special Order:
U18 24…240VAC or DC
A40 346…440V 50/60Hz ➌
Z12 12VDC
Special Function Timing Relays
RZ7-FSH3UU23
TypeFunction
H Repeat Cycle Timer (Flasher)
Includes four separate functions
- Supply voltage controlled, output
starts with a pause
- Supply voltage controlled, output
starts with a pulse
- Pulse controlled, output starts with a
pause
- Pulse controlled, output starts with a
pulse
Contacts
All functions:
3 One single pole
double throw contact
Time Ranges
For equal timing of pulse
and pause
U 0.05s…60 hours ➊
For separate timing of
pulse and pause
V 2 x 0.05s…60 hours
➊
Supply Voltages
Standard:
U23 24…48VDC
24…240V 50/60Hz
Special Order:
A40 346…440V 50/60Hz ➌
Z12 12VDC
RZ7-FSY2CU23
Type
Y Wye Delta Timing Relay
➊
Multi-time setting range. See Technical Section for specific time settings.
➋
Second output selectable as timed or instantaneous.
Function
Contacts
2 Two normally open
contacts
Time Ranges
C 0.5…10 seconds
D 1.5…30 seconds
E 0.05…1 minute
F 0.15…3 minutes
G 0.5…10 minutes
➌
Timers with supply voltage code A40 (346...440VAC) are not UL listed.
Supply Voltages
Standard:
U23 24…48VDC
24…240V 50/60Hz
Special Order:
A40 346…440V 50/60Hz ➌
G40
Discount Schedule B
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
S
L/+
A2
N/-
A1
18 16
15
B1
S
L/+
A2
N/-
A1
18 16
15
B1
Z1 Z2
28 26
25
24 22
21
L/+
A2
N/-
A1
18 16
15
28 26
25
Electronic Timing Relays
L/+
A2
N/-
A1
18 16
15
L/+
A2
N/-
A1
18 16
15
Series RZ7-FS
RZ7-FS Timing Relays – Single Function, One and Two Pole
Functional
Description
ON-Delay Timing Relay (A)
When supply voltage is applied, output
contact(s) change state after time
delay t.
OFF-Delay Timing Relay (B)
When control contact “S” closes, output
contact(s) change state immediately. When
control contact S opens, output contact(s)
change state after time delay
supply voltage required on terminals A1/A2.
Note: Control pulse duration minimum 50ms
(AC) - 30ms (DC).
t. Constant
Functional
Diagram
Terminal
ArrangementTypeCatalog NumberPrice
➋
➋
G
Timing Relays
Control &
• One SPDT contact
• Single timing range
• One SPDT contact
• Multi-timing range
(from 0.05s to 60h)
• Two SPDT contacts ➋
• Multi-timing range
(from 0.05s to 60h)
➌
➋
➊
➊
➌
• One SPDT contact
• Single timing range
• One SPDT contact
• Multi-timing range
(from 0.05s to 60h)
• Two SPDT contacts ➋
• Multi-timing range
(from 0.05s to 60h)
➋
RZ7-FSA3✱U23
RZ7-FSA3UU2364
➍
RZ7-FSA4UU2384
➍
RZ7-FSB3✱U23
RZ7-FSB3UU2364
➍
RZ7-FSB4UU2384
➍
61
RZ7-FS
61
• One SPDT contact
Off-Delay Without Supply Voltage (Q)
When supply voltage is applied, output
contact(s) change state immediately. When
supply voltage is removed, output contact(s)
change state after time delay
➏
t.
Ordering Instructions
• Specify catalog number
• Replace (✱) with Timing Range Code
Refer to table
at right
Supply Voltage
Single Function RZ7-FS...U23 timers (except RZ7-FSQ) accept supply voltages of 24…48VDC and 24…240VAC (RZ7-FSQ accepts
24…240VAC or DC). Other voltages are available by special order.
See Quick Selection Guide on page G40 for details or contact your
Sprecher + Schuh representative for information.
➊
For timing control, a voltage other than the supply voltage can also be used.
• Multi-timing range
(from 0.15s to 10min)
• Two SPDT contacts
• Multi-timing range
(from 0.15s to 10min) ➎
Timing Range Codes
Timing Range
0.05…1 sec
0.15…3 sec
0.5…10 sec
1.5…30 sec
0.05…1 min
0.15…3 min
0.5…10 min
1.5…30 min
0.05…1 hour
0.15…3 hour
0.5…10 hour
3.0…60 hour
Code
A
B
C
D
E
F
G
H
I
J
K
L
RZ7-FSQ3QU18121
➎
RZ7-FSQ4QU18141
RZ7-FS two pole timing relay
➋ Output two is selectable as an instantaneous contact by sliding a switch on the
faceplate.
➌ Bridge or potentiometer 10kΩ, min. 0.25W (low voltage) for external time setting.
➍ Timing range is screwdriver selectable from the faceplate. Timing range selections
include those found in the Timing Range Code chart.
Discount Schedule B
➎ Timing range is screwdriver selectable from the faceplate. Exact timing ranges can be
found in the Technical Section.
➏ Due to shock during shipment, the state of the contacts should be verified before
initial use.
G41
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.